Logan Armory -R-32 - Quantities Spreadsheet.xlsx
XLSX spreadsheet 982 KB Posted
- Attached to
- Logan/ Mingo AFRC HVAC System Replacement
- Solicitation number
- CRFQ 0603 ADJ2700000014 2
- Issued by
- Kanawha County, West Virginia
About this file
This is a quantities spreadsheet for the Logan Armory R-32 HVAC system replacement project located in West Virginia, detailing the Mitsubishi Electric Trane HVAC US City Multi Variable Refrigerant Flow (VRF) system components and specifications. The project specifies six centralized VRF systems (VFR-1A, VRF-2A, VRF-3A, VRF-1B, VRF-2B, and VRF-3B DOAS) with a total of 57 PAC-YT53CRAU-J simple MA controllers, 6 outdoor units ranging from 120,000 to 192,000 BTU/h nominal cooling capacity, 59 indoor units primarily consisting of ceiling-cassette four-way units with capacities from 8,000 to 30,000 BTU/h, 2 ceiling-concealed ducted units with 72,000 BTU/h capacity, 6 branch circuit controllers, and various accessory components including shutoff valve kits, snow/hail guards, remote controllers, and software licenses. The refrigerant piping materials include copper tubing in various sizes ranging from 1/4 inch to 1-1/8 inch diameter, with specified total lengths and quantities for high and low pressure applications throughout the system.
The system design incorporates R32 refrigerant technology with corrected cooling capacities ranging from approximately 117,000 to 192,600 BTU/h and corrected heating capacities from 117,900 to 187,400 BTU/h across the outdoor units. All indoor units are specified for 208/230V single-phase electrical service with minimal power consumption for individual units, while outdoor units require 460V three-phase power with recommended fuse sizes and motor overload protection ratings specified. The project includes system components configured for full demand cooling and heating diversity across all zones, with design conditions of 92°F outdoor dry bulb for cooling and 6°F outdoor wet bulb for heating. Factory representatives are required to review, install, startup, commission, provide BMS integration assistance, and deliver end-user training for the City Multi equipment upon completion, with snow/hail protection kits specified to prevent damage in severe winter climates.
View the file
Other files
Show all 15
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Cover Page
| Project Name: | Logan Armory -R-32.dsbx |
| Project Number: | |
| Comment: |
&G
&G
Contents
| Table of Contents | ||
| Quotation ....................................................................................... | 1 | |
| Manually Inserted By Distributor | ||
| Unit Quantities ....................................................................................... | 2 | |
| System Images ....................................................................................... | 3 | |
| Centralized System - 1, VFR-1A | ||
| Centralized System - 1, VRF-2A | ||
| Centralized System - 1, VRF-3A | ||
| Centralized System - 1, VRF-1B | ||
| Centralized System - 2, VRF-2B | ||
| Centralized System - 2, VRF-3B DOAS | ||
| Equipment Detailed Schedules ....................................................................................... | 4 | |
| Outdoor Unit Schedules | ||
| Indoor Unit Schedules | ||
| Lossnay Unit Schedules | ||
| BC Controller Schedules | ||
| Input/Output Device Schedules | ||
| Equipment Submittals ....................................................................................... | 5 | |
| Manually Attached Via Compile Project Documents Function |
&G
&G
Unit Quantities
| Quantities | ||||
| Qty | Model | Description | Tag | |
| 57 | PAC-YT53CRAU-J | Simple MA controller | CTR1-CC-1A1,CTR2-CC-1A2,CTR3-CC-1A3,CTR4-CC-1A5A,CTR5-CC-1A5B,CTR6-CC-1A6,CTR1-CC-2A1,CTR2-CC-2A2,CTR3-CC-2A3,CTR4-CC-2A4,CTR5-CC-2A5,CTR6-CC-2A6,CTR7-CC-2A7,CTR8-CC-2A8,CTR9-CC-2A9,CTR10-CC-2A9,CTR11-CC-2A10,CTR12-CC-2A11,CTR1-CC-3A1A,CTR2-CC-3A2A,CTR3-CC-3A3A,CTR4-CC-3A1B,CTR5-CC-3A2B,CTR6-CC-3A3B,CTR7-CC-3A4,CTR8-CC-3A5,CTR9-CC-3A6,CTR10-CC-3A7,CTR1-CC-1B1,CTR2-CC-1B2,CTR3-CC-1B3,CTR4-CC-1B4,CTR5-CC-1B5,CTR6-CC-1B6A,CTR7-CC-1B6B,CTR8-CC-1B7,CTR9-CC-1B8,CTR10-CC-1B9,CTR11-CC-1B10,CTR12-CC-1B11,CTR13-CC-1B12,CTR14-CC-1B13,CTR15-CC-1B14,CTR16-CC-1B15,CTR17-CC-1B16,CTR1-CC-2B1,CTR2-CC-2B2,CTR3-CC-2B3,CTR4-CC-2B4,CTR5-CC-2B5,CTR6-CC-2B6,CTR7-CC-2B7,CTR8-CC-2B8,CTR9-CC-2B9,CTR10-CC-2B10,CTR11-CC-2B11,CTR1-DOAS-3B1 | |
| 1 | PURY-HM192YSXU-A | R32 R2 Series Outdoor Unit | VFR-1A | |
| 2 | PURY-HM120YXU-A | R32 R2 Series Outdoor Unit | VRF-2A,VRF-2B | |
| 2 | PURY-HM144YSXU-A | R32 R2 Series Outdoor Unit | VRF-3A,VRF-1B | |
| 1 | PUHY-HM144YSXU-A | R32 Y Series Outdoor Unit | VRF-3B DOAS | |
| 1 | CMB-M108NU-MA1-SV | BC Controller Main | BCC-1A | |
| 4 | CMB-M1012NU-MA1-SV | BC Controller Main | BCC-2A,BCC-3A,BCC-1B,BCC-2B | |
| 1 | CMB-M108NU-MB1-SV | BC Controller Sub | BCC-1B SUB | |
| 3 | PLFY-EM30NEMU-A | Ceiling-Cassette (Four-Way) Indoor Unit | CC-1A1,CC-1A2,CC-1A3 | |
| 3 | PLFY-M18NFMU-A | Ceiling-Cassette (Four-Way) Indoor Unit | CC-1A5A,CC-1A5B,CC-2B4 | |
| 1 | PLFY-EM24NEMU-A | Ceiling-Cassette (Four-Way) Indoor Unit | CC-1A6 | |
| 40 | PLFY-M08NFMU-A | Ceiling-Cassette (Four-Way) Indoor Unit | CC-2A1,CC-2A2,CC-2A3,CC-2A4,CC-2A5,CC-2A6,CC-2A7,CC-2A8,CC-2A9,CC-2A9,CC-2A11,CC-3A4,CC-3A5,CC-3A6,CC-3A7,CC-1B1,CC-1B2,CC-1B3,CC-1B4,CC-1B5,CC-1B6A,CC-1B6B,CC-1B7,CC-1B8,CC-1B9,CC-1B10,CC-1B11,CC-1B12,CC-1B13,CC-1B14,CC-1B15,CC-2B1,CC-2B2,CC-2B3,CC-2B5,CC-2B6,CC-2B7,CC-2B8,CC-2B9,CC-2B10 | |
| 3 | PKFY-M24NKMU-A | Wall -Mounted Indoor Unit | CC-2A10,CC-1B16,CC-2B11 | |
| 6 | PLFY-M12NFMU-A | Ceiling-Cassette (Four-Way) Indoor Unit | CC-3A1A,CC-3A2A,CC-3A3A,CC-3A1B,CC-3A2B,CC-3A3B | |
| 2 | PEFY-M72NMHU-A | Ceiling-Concealed (Ducted) Indoor Unit | DOAS-3B1,DOAS-3B2 | |
| 1 | CMY-Y202S-G2R1 | Branch Joint | ||
| 1 | AE-C400A | System Remote Controller | CTR1 | |
| 1 | EW-C50A | System Remote Controller | CTR2 | |
| 1 | LIC-BACNET-MASTER | Software License | ||
| 1 | LIC-BACNET-EXPANS | Software License | ||
| 6 | SGX-1 | Side Snow/Hail Guards | ||
| 4 | SGX-2 | Front and Rear Snow/Hail Guards | ||
| 4 | SHX-1 | Snow Hood | ||
| 5 | CMY-R304S-G1 | Reducer | BCC-1A,BCC-2A,BCC-3A,BCC-1B,BCC-2B | |
| 6 | SGX-3 | Front and Rear Snow/Hail Guards | ||
| 6 | SHX-2 | Snow Hood | ||
| 1 | CMY-R303S-G1 | Reducer | BCC-1B | |
| 1 | CMY-R306S-G | Reducer | BCC-1B SUB | |
| 4 | PLP-41EAEU | Grille with 3D i-see Sensor™ | CC-1A1,CC-1A2,CC-1A3,CC-1A6 | |
| 49 | SLP-18FAU | Decoration Panel | CC-1A5A,CC-1A5B,CC-2A1,CC-2A2,CC-2A3,CC-2A4,CC-2A5,CC-2A6,CC-2A7,CC-2A8,CC-2A9,CC-2A9,CC-2A11,CC-3A1A,CC-3A2A,CC-3A3A,CC-3A1B,CC-3A2B,CC-3A3B,CC-3A4,CC-3A5,CC-3A6,CC-3A7,CC-1B1,CC-1B2,CC-1B3,CC-1B4,CC-1B5,CC-1B6A,CC-1B6B,CC-1B7,CC-1B8,CC-1B9,CC-1B10,CC-1B11,CC-1B12,CC-1B13,CC-1B14,CC-1B15,CC-2B1,CC-2B2,CC-2B3,CC-2B4,CC-2B5,CC-2B6,CC-2B7,CC-2B8,CC-2B9,CC-2B10 | |
| 2 | CMR-M100KT-NA | Shutoff Valve Kit | ||
| Refrigerant Piping Materials | ||||
| Pipe Size (inch) | Total Length (feet) | Number of Bends | ||
| 3/4 | 300 | 0 | ||
| 7/8 | 225 | 0 | ||
| 3/8 | 500 | 0 | ||
| 5/8 | 400 | 0 | ||
| 1/4 | 2450 | 0 | ||
| 1/2 | 2500 | 0 | ||
| 1-1/8 | 425 | 0 |
&G
&G
VFR-1A
| Centralized System - 1 : VFR-1A |
| Piping Diagram Image (Design View) |
&G
&G
VRF-2A
| Centralized System - 1 : VRF-2A |
| Piping Diagram Image (Design View) |
&G
&G
VRF-3A
| Centralized System - 1 : VRF-3A |
| Piping Diagram Image (Design View) |
&G
&G
VRF-1B
| Centralized System - 1 : VRF-1B |
| Piping Diagram Image (Design View) |
&G
&G
VRF-2B
| Centralized System - 2 : VRF-2B |
| Piping Diagram Image (Design View) |
&G
&G
VRF-3B DOAS
| Centralized System - 2 : VRF-3B DOAS |
| Piping Diagram Image (Design View) |
&G
&G
Outdoor
| MITSUBISHI ELECTRIC TRANE HVAC US: CITY MULTI VRF OUTDOOR UNIT SCHEDULE | |||||||
| System Tag | VFR-1A | VRF-2A | VRF-3A | VRF-1B | VRF-2B | VRF-3B DOAS | |
| Tag Reference | VFR-1A | VRF-2A | VRF-3A | VRF-1B | VRF-2B | VRF-3B DOAS | |
| Nominal Data | M-NET Address | 51, 52 | 57 | 69, 70 | 79, 80 | 51 | 62, 63 |
| Model Number | PURY-HM192YSXU-A | PURY-HM120YXU-A | PURY-HM144YSXU-A | PURY-HM144YSXU-A | PURY-HM120YXU-A | PUHY-HM144YSXU-A | |
| Modules | HM96, HM96 | HM120 | HM72, HM72 | HM72, HM72 | HM120 | HM72, HM72 | |
| Nominal Cooling Capacity (BTU/h) | 192,000 | 120,000 | 144,000 | 144,000 | 120,000 | 144,000 | |
| Nominal Heating Capacity (BTU/h) | 215,000 | 135,000 | 160,000 | 160,000 | 135,000 | 160,000 | |
| Cooling Efficiency (I)EER [SEER] | 22.95 / 13.35 | 23.2 / 13.55 | 23.2 / 13.65 | 23.2 / 13.65 | 23.2 / 13.55 | 24.55 / 13.9 | |
| EER2 [SEER2] | N/A | N/A | N/A | N/A | N/A | N/A | |
| Heating COP @ 47°F [HSPF] | 4.010 | 3.980 | 4.110 | 4.110 | 3.980 | 4.230 | |
| HSPF2 IV [V] | N/A [N/A] | N/A [N/A] | N/A [N/A] | N/A [N/A] | N/A [N/A] | N/A [N/A] | |
| Nom System Connected Capacity (% of NOM) | 78.1 % | 93.3 % | 72.2 % | 105.6 % | 95.0 % | 100.0 % | |
| Design Conditions | Design Cooling Outdoor Temp DB (°F) | 92.0 | 92.0 | 92.0 | 92.0 | 92.0 | 92.0 |
| Design Heating Outdoor Temp WB (°F) | 6.0 | 6.0 | 6.0 | 6.0 | 6.0 | 6.0 | |
| Max Pipe Length from BC or 1st Joint (feet) | 50.0 | 50.0 | 50.0 | 100.0 | 50.0 | 99.2 | |
| Refrig Pipe Dim High/Low Pressure (inch) (See Note 4) | 7/8 / 1-1/8 | 3/4 / 1-1/8 | 7/8 / 1-1/8 | 7/8 / 1-1/8 | 3/4 / 1-1/8 | 1/2 / 1-1/8 | |
| Performance Data | Corrected Cooling Total Capacity (BTU/h) | 192,599.3 | 117,531.9 | 143,881.8 | 135,634.5 | 117,205.0 | 136,066.2 |
| Corrected Heating Capacity (BTU/h) | 187,386.8 | 117,898.3 | 139,467.3 | 138,245.1 | 117,898.3 | 139,625.0 | |
| Sound Pressure (dBA) | 85.5/85.5 | 80/83.5 | 80/82 | 80/82 | 80/83.5 | 80/82 | |
| Compressor Data | Compressor Type | SCROLL | SCROLL | SCROLL | SCROLL | SCROLL | SCROLL |
| Compressor Quantity | 2 | 1 | 2 | 2 | 1 | 2 | |
| Preliminary Added Field Charge (See Note 5) | 39.9 | 35.9 | 36.8 | 47.2 | 35.3 | 21.4 | |
| Electrical Data | Voltage / Phase | 460V / 3-phase 3-wire | 460V / 3-phase 3-wire | 460V / 3-phase 3-wire | 460V / 3-phase 3-wire | 460V / 3-phase 3-wire | 460V / 3-phase 3-wire |
| MCA 208/230 or [460V] | 31, 31 | 31 | 27, 27 | 27, 27 | 31 | 27, 27 | |
| Recommended Fuse Size (RFS) | 35, 35 | 35 | 35, 35 | 35, 35 | 35 | 45, 45 | |
| MOCP | 50, 50 | 50 | 45, 45 | 45, 45 | 50 | 45,45 | |
| Notes / Options | Applicable System Notes - See Notes Below | 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11 | 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11 | 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11 | 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11 | 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11 | 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11 |
| Notes & Options: | |||||||
| 1 | Nominal cooling capacities are based on indoor coil EAT of 80/67°F (DB/WB), outdoor of 95°F (DB) | ||||||
| 2 | Nominal heating capacities are based on indoor coil EAT of 70°F (DB), outdoor of 43°F (WB) | ||||||
| 3 | Efficiency values for EER, IEER, COP are based on AHRI 1230 test method for mixture of ducted & non-ducted indoor units. | ||||||
| 4 | Efficiency values for EER2, SEER2, COP are based on AHRI 210/240 test method for mixture of ducted & non-ducted indoor units. | ||||||
| 5 | For systems with multiple modules, refrigerant pipe dimensions indicate total system combined piping downstream of module twinning. | ||||||
| 6 | Added field charge listed is in addition to factory charge, this must be updated based upon final as-built piping layout. | ||||||
| 7 | Factory representatives shall review the project prior to and throughout the installation of CITY MULTI equipment | ||||||
| 8 | Factory representatives shall startup and commission CITY MULTI equipment upon completion of equipment installations | ||||||
| 9 | Factory representatives shall provide on-site assistance for the BMS integration of the CITY MULTI equipment | ||||||
| 10 | Factory representatives shall provide end-user training on the CITY MULTI equipment upon completion of the installation of equipment | ||||||
| 11 | Provide Snow/Hail Kit to Prevent Damage or Snow Build-Up in Severe Winter Climates |
&G
&G
Indoor
| MITSUBISHI ELECTRIC TRANE HVAC US: CITY MULTI VRF INDOOR UNIT SCHEDULE | |||||||||||||||||||||||||||||||||||||||||||||||||
| System Tag | VFR-1A | VFR-1A | VFR-1A | VFR-1A | VFR-1A | VFR-1A | VRF-2A | VRF-2A | VRF-2A | VRF-2A | VRF-2A | VRF-2A | VRF-2A | VRF-2A | VRF-2A | VRF-2A | VRF-2A | VRF-2A | VRF-3A | VRF-3A | VRF-3A | VRF-3A | VRF-3A | VRF-3A | VRF-3A | VRF-3A | VRF-3A | VRF-3A | VRF-1B | VRF-1B | VRF-1B | VRF-1B | VRF-1B | VRF-1B | VRF-1B | VRF-1B | VRF-1B | VRF-1B | VRF-1B | VRF-1B | VRF-1B | VRF-1B | VRF-1B | VRF-1B | VRF-1B | VRF-2B | VRF-2B | VRF-2B | |
| Tag Reference | CC-1A1 | CC-1A2 | CC-1A3 | CC-1A5A | CC-1A5B | CC-1A6 | CC-2A1 | CC-2A2 | CC-2A3 | CC-2A4 | CC-2A5 | CC-2A6 | CC-2A7 | CC-2A8 | CC-2A9 | CC-2A9 | CC-2A10 | CC-2A11 | CC-3A1A | CC-3A2A | CC-3A3A | CC-3A1B | CC-3A2B | CC-3A3B | CC-3A4 | CC-3A5 | CC-3A6 | CC-3A7 | CC-1B1 | CC-1B2 | CC-1B3 | CC-1B4 | CC-1B5 | CC-1B6A | CC-1B6B | CC-1B7 | CC-1B8 | CC-1B9 | CC-1B10 | CC-1B11 | CC-1B12 | CC-1B13 | CC-1B14 | CC-1B15 | CC-1B16 | CC-2B1 | CC-2B2 | CC-2B3 | |
| Nominal Data | Room Name | ||||||||||||||||||||||||||||||||||||||||||||||||
| M-NET Address | 1 | 2 | 3 | 4 | 5 | 6 | 7 | 8 | 9 | 10 | 11 | 12 | 13 | 14 | 15 | 16 | 17 | 18 | 19 | 20 | 21 | 22 | 23 | 24 | 25 | 26 | 27 | 28 | 29 | 30 | 31 | 32 | 33 | 34 | 35 | 36 | 37 | 38 | 39 | 40 | 41 | 42 | 43 | 44 | 45 | 1 | 2 | 3 | |
| Model | PLFY-EM30NEMU-A | PLFY-EM30NEMU-A | PLFY-EM30NEMU-A | PLFY-M18NFMU-A | PLFY-M18NFMU-A | PLFY-EM24NEMU-A | PLFY-M08NFMU-A | PLFY-M08NFMU-A | PLFY-M08NFMU-A | PLFY-M08NFMU-A | PLFY-M08NFMU-A | PLFY-M08NFMU-A | PLFY-M08NFMU-A | PLFY-M08NFMU-A | PLFY-M08NFMU-A | PLFY-M08NFMU-A | PKFY-M24NKMU-A | PLFY-M08NFMU-A | PLFY-M12NFMU-A | PLFY-M12NFMU-A | PLFY-M12NFMU-A | PLFY-M12NFMU-A | PLFY-M12NFMU-A | PLFY-M12NFMU-A | PLFY-M08NFMU-A | PLFY-M08NFMU-A | PLFY-M08NFMU-A | PLFY-M08NFMU-A | PLFY-M08NFMU-A | PLFY-M08NFMU-A | PLFY-M08NFMU-A | PLFY-M08NFMU-A | PLFY-M08NFMU-A | PLFY-M08NFMU-A | PLFY-M08NFMU-A | PLFY-M08NFMU-A | PLFY-M08NFMU-A | PLFY-M08NFMU-A | PLFY-M08NFMU-A | PLFY-M08NFMU-A | PLFY-M08NFMU-A | PLFY-M08NFMU-A | PLFY-M08NFMU-A | PLFY-M08NFMU-A | PKFY-M24NKMU-A | PLFY-M08NFMU-A | PLFY-M08NFMU-A | PLFY-M08NFMU-A | |
| Type | Ceiling-Cassette (Four-Way) | Ceiling-Cassette (Four-Way) | Ceiling-Cassette (Four-Way) | Ceiling-Cassette (Four-Way) | Ceiling-Cassette (Four-Way) | Ceiling-Cassette (Four-Way) | Ceiling-Cassette (Four-Way) | Ceiling-Cassette (Four-Way) | Ceiling-Cassette (Four-Way) | Ceiling-Cassette (Four-Way) | Ceiling-Cassette (Four-Way) | Ceiling-Cassette (Four-Way) | Ceiling-Cassette (Four-Way) | Ceiling-Cassette (Four-Way) | Ceiling-Cassette (Four-Way) | Ceiling-Cassette (Four-Way) | Wall -Mounted | Ceiling-Cassette (Four-Way) | Ceiling-Cassette (Four-Way) | Ceiling-Cassette (Four-Way) | Ceiling-Cassette (Four-Way) | Ceiling-Cassette (Four-Way) | Ceiling-Cassette (Four-Way) | Ceiling-Cassette (Four-Way) | Ceiling-Cassette (Four-Way) | Ceiling-Cassette (Four-Way) | Ceiling-Cassette (Four-Way) | Ceiling-Cassette (Four-Way) | Ceiling-Cassette (Four-Way) | Ceiling-Cassette (Four-Way) | Ceiling-Cassette (Four-Way) | Ceiling-Cassette (Four-Way) | Ceiling-Cassette (Four-Way) | Ceiling-Cassette (Four-Way) | Ceiling-Cassette (Four-Way) | Ceiling-Cassette (Four-Way) | Ceiling-Cassette (Four-Way) | Ceiling-Cassette (Four-Way) | Ceiling-Cassette (Four-Way) | Ceiling-Cassette (Four-Way) | Ceiling-Cassette (Four-Way) | Ceiling-Cassette (Four-Way) | Ceiling-Cassette (Four-Way) | Ceiling-Cassette (Four-Way) | Wall -Mounted | Ceiling-Cassette (Four-Way) | Ceiling-Cassette (Four-Way) | Ceiling-Cassette (Four-Way) | |
| Nominal Cooling Capacity (BTU/h) | 30,000 | 30,000 | 30,000 | 18,000 | 18,000 | 24,000 | 8,000 | 8,000 | 8,000 | 8,000 | 8,000 | 8,000 | 8,000 | 8,000 | 8,000 | 8,000 | 24,000 | 8,000 | 12,000 | 12,000 | 12,000 | 12,000 | 12,000 | 12,000 | 8,000 | 8,000 | 8,000 | 8,000 | 8,000 | 8,000 | 8,000 | 8,000 | 8,000 | 8,000 | 8,000 | 8,000 | 8,000 | 8,000 | 8,000 | 8,000 | 8,000 | 8,000 | 8,000 | 8,000 | 24,000 | 8,000 | 8,000 | 8,000 | |
| Nominal Heating Capacity (BTU/h) | 34,000 | 34,000 | 34,000 | 20,000 | 20,000 | 27,000 | 9,000 | 9,000 | 9,000 | 9,000 | 9,000 | 9,000 | 9,000 | 9,000 | 9,000 | 9,000 | 27,000 | 9,000 | 13,500 | 13,500 | 13,500 | 13,500 | 13,500 | 13,500 | 9,000 | 9,000 | 9,000 | 9,000 | 9,000 | 9,000 | 9,000 | 9,000 | 9,000 | 9,000 | 9,000 | 9,000 | 9,000 | 9,000 | 9,000 | 9,000 | 9,000 | 9,000 | 9,000 | 9,000 | 27,000 | 9,000 | 9,000 | 9,000 | |
| Design Conditions | Cooling Design Entering Temp DB/WB (°F) / [Water in temp] | 74.0/62.0 | 74.0/62.0 | 74.0/62.0 | 74.0/62.0 | 74.0/62.0 | 74.0/62.0 | 74.0/62.0 | 74.0/62.0 | 74.0/62.0 | 74.0/62.0 | 74.0/62.0 | 74.0/62.0 | 74.0/62.0 | 74.0/62.0 | 74.0/62.0 | 74.0/62.0 | 74.0/62.0 | 74.0/62.0 | 74.0/62.0 | 74.0/62.0 | 74.0/62.0 | 74.0/62.0 | 74.0/62.0 | 74.0/62.0 | 74.0/62.0 | 74.0/62.0 | 74.0/62.0 | 74.0/62.0 | 74.0/62.0 | 74.0/62.0 | 74.0/62.0 | 74.0/62.0 | 74.0/62.0 | 74.0/62.0 | 74.0/62.0 | 74.0/62.0 | 74.0/62.0 | 74.0/62.0 | 74.0/62.0 | 74.0/62.0 | 74.0/62.0 | 74.0/62.0 | 74.0/62.0 | 74.0/62.0 | 74.0/62.0 | 74.0/62.0 | 74.0/62.0 | 74.0/62.0 |
| Heating Design Entering Temp DB/WB (°F) / [Water in temp] | 70.0 | 70.0 | 70.0 | 70.0 | 70.0 | 70.0 | 70.0 | 70.0 | 70.0 | 70.0 | 70.0 | 70.0 | 70.0 | 70.0 | 70.0 | 70.0 | 70.0 | 70.0 | 70.0 | 70.0 | 70.0 | 70.0 | 70.0 | 70.0 | 70.0 | 70.0 | 70.0 | 70.0 | 70.0 | 70.0 | 70.0 | 70.0 | 70.0 | 70.0 | 70.0 | 70.0 | 70.0 | 70.0 | 70.0 | 70.0 | 70.0 | 70.0 | 70.0 | 70.0 | 70.0 | 70.0 | 70.0 | 70.0 | |
| Cooling Diversity Full/Partial (See Note 5, 6) | FULL DEMAND | FULL DEMAND | FULL DEMAND | FULL DEMAND | FULL DEMAND | FULL DEMAND | FULL DEMAND | FULL DEMAND | FULL DEMAND | FULL DEMAND | FULL DEMAND | FULL DEMAND | FULL DEMAND | FULL DEMAND | FULL DEMAND | FULL DEMAND | FULL DEMAND | FULL DEMAND | FULL DEMAND | FULL DEMAND | FULL DEMAND | FULL DEMAND | FULL DEMAND | FULL DEMAND | FULL DEMAND | FULL DEMAND | FULL DEMAND | FULL DEMAND | FULL DEMAND | FULL DEMAND | FULL DEMAND | FULL DEMAND | FULL DEMAND | FULL DEMAND | FULL DEMAND | FULL DEMAND | FULL DEMAND | FULL DEMAND | FULL DEMAND | FULL DEMAND | FULL DEMAND | FULL DEMAND | FULL DEMAND | FULL DEMAND | FULL DEMAND | FULL DEMAND | FULL DEMAND | FULL DEMAND | |
| Heating Diversity Full/Partial (See Note 5, 6) | FULL DEMAND | FULL DEMAND | FULL DEMAND | FULL DEMAND | FULL DEMAND | FULL DEMAND | FULL DEMAND | FULL DEMAND | FULL DEMAND | FULL DEMAND | FULL DEMAND | FULL DEMAND | FULL DEMAND | FULL DEMAND | FULL DEMAND | FULL DEMAND | FULL DEMAND | FULL DEMAND | FULL DEMAND | FULL DEMAND | FULL DEMAND | FULL DEMAND | FULL DEMAND | FULL DEMAND | FULL DEMAND | FULL DEMAND | FULL DEMAND | FULL DEMAND | FULL DEMAND | FULL DEMAND | FULL DEMAND | FULL DEMAND | FULL DEMAND | FULL DEMAND | FULL DEMAND | FULL DEMAND | FULL DEMAND | FULL DEMAND | FULL DEMAND | FULL DEMAND | FULL DEMAND | FULL DEMAND | FULL DEMAND | FULL DEMAND | FULL DEMAND | FULL DEMAND | FULL DEMAND | FULL DEMAND | |
| Refrig Pipe Dim Liquid/Suction (inch) | 3/8 / 5/8 | 3/8 / 5/8 | 3/8 / 5/8 | 1/4 / 1/2 | 1/4 / 1/2 | 3/8 / 5/8 | 1/4 / 1/2 | 1/4 / 1/2 | 1/4 / 1/2 | 1/4 / 1/2 | 1/4 / 1/2 | 1/4 / 1/2 | 1/4 / 1/2 | 1/4 / 1/2 | 1/4 / 1/2 | 1/4 / 1/2 | 3/8 / 5/8 | 1/4 / 1/2 | 1/4 / 1/2 | 1/4 / 1/2 | 1/4 / 1/2 | 1/4 / 1/2 | 1/4 / 1/2 | 1/4 / 1/2 | 1/4 / 1/2 | 1/4 / 1/2 | 1/4 / 1/2 | 1/4 / 1/2 | 1/4 / 1/2 | 1/4 / 1/2 | 1/4 / 1/2 | 1/4 / 1/2 | 1/4 / 1/2 | 1/4 / 1/2 | 1/4 / 1/2 | 1/4 / 1/2 | 1/4 / 1/2 | 1/4 / 1/2 | 1/4 / 1/2 | 1/4 / 1/2 | 1/4 / 1/2 | 1/4 / 1/2 | 1/4 / 1/2 | 1/4 / 1/2 | 3/8 / 5/8 | 1/4 / 1/2 | 1/4 / 1/2 | 1/4 / 1/2 | |
| Performance Data | Cooling Total Capacity (BTU/h) | 27,032.1 | 27,032.1 | 27,032.1 | 16,219.2 | 16,219.2 | 21,625.6 | 7,208.5 | 7,208.5 | 7,208.5 | 7,208.5 | 7,208.5 | 7,208.5 | 7,208.5 | 7,208.5 | 7,208.5 | 7,208.5 | 21,625.6 | 7,208.5 | 10,617.6 | 10,617.6 | 10,617.6 | 10,617.6 | 10,617.6 | 10,617.6 | 7,078.4 | 7,078.4 | 7,078.4 | 7,078.4 | 7,078.4 | 7,078.4 | 7,078.4 | 7,078.4 | 7,078.4 | 7,078.4 | 7,078.4 | 7,078.4 | 7,078.4 | 7,078.4 | 7,078.4 | 7,078.4 | 7,078.4 | 7,078.4 | 7,078.4 | 7,078.4 | 21,235.1 | 7,208.5 | 7,208.5 | 7,208.5 |
| Cooling Sensible Capacity (BTU/h) | 26,957.3 | 26,957.3 | 26,957.3 | 13,115.2 | 13,115.2 | 18,499.5 | 4,611.6 | 4,611.6 | 4,611.6 | 4,611.6 | 4,611.6 | 4,611.6 | 4,611.6 | 4,611.6 | 4,611.6 | 4,611.6 | 20,359.8 | 4,611.6 | 7,436.0 | 7,436.0 | 7,436.0 | 7,436.0 | 7,436.0 | 7,436.0 | 4,520.6 | 4,520.6 | 4,520.6 | 4,520.6 | 4,520.6 | 4,520.6 | 4,520.6 | 4,520.6 | 4,520.6 | 4,520.6 | 4,520.6 | 4,520.6 | 4,520.6 | 4,520.6 | 4,520.6 | 4,520.6 | 4,520.6 | 4,520.6 | 4,520.6 | 4,520.6 | 20,199.2 | 4,611.6 | 4,611.6 | 4,611.6 | |
| Heating Capacity (BTU/h) | 31,751.8 | 31,751.8 | 31,751.8 | 18,677.6 | 18,677.6 | 25,214.7 | 8,404.6 | 8,404.6 | 8,404.6 | 8,404.6 | 8,404.6 | 8,404.6 | 8,404.6 | 8,404.6 | 8,404.6 | 8,404.6 | 25,213.7 | 8,404.6 | 12,608.9 | 12,608.9 | 12,608.9 | 12,608.9 | 12,608.9 | 12,608.9 | 8,405.9 | 8,405.9 | 8,405.9 | 8,405.9 | 7,276.1 | 7,276.1 | 7,276.1 | 7,276.1 | 7,276.1 | 7,276.1 | 7,276.1 | 7,276.1 | 7,276.1 | 7,276.1 | 7,276.1 | 7,276.1 | 7,276.1 | 7,276.1 | 7,276.1 | 7,276.1 | 21,828.2 | 8,289.7 | 8,289.7 | 8,289.7 | |
| Estimated Cooling Coil LAT (°F) / [LWT] | 41.9 | 41.9 | 41.9 | 46.4 | 46.4 | 51.9 | 59.8 | 59.8 | 59.8 | 59.8 | 59.8 | 59.8 | 59.8 | 59.8 | 59.8 | 59.8 | 52.6 | 59.8 | 52.5 | 52.5 | 52.5 | 52.5 | 52.5 | 52.5 | 60.1 | 60.1 | 60.1 | 60.1 | 60.1 | 60.1 | 60.1 | 60.1 | 60.1 | 60.1 | 60.1 | 60.1 | 60.1 | 60.1 | 60.1 | 60.1 | 60.1 | 60.1 | 60.1 | 60.1 | 52.7 | 59.8 | 59.8 | 59.8 | |
| Estimated Heating Coil LAT (°F) / [LWT] | 107.6 | 107.6 | 107.6 | 109.0 | 109.0 | 99.8 | 95.6 | 95.6 | 95.6 | 95.6 | 95.6 | 95.6 | 95.6 | 95.6 | 95.6 | 95.6 | 96.3 | 95.6 | 106.2 | 106.2 | 106.2 | 106.2 | 106.2 | 106.2 | 95.6 | 95.6 | 95.6 | 95.6 | 92.2 | 92.2 | 92.2 | 92.2 | 92.2 | 92.2 | 92.2 | 92.2 | 92.2 | 92.2 | 92.2 | 92.2 | 92.2 | 92.2 | 92.2 | 92.2 | 92.8 | 95.3 | 95.3 | 95.3 | |
| Fan / Water Flow Data | Fan Speed Setting | HIGH | HIGH | HIGH | HIGH | HIGH | HIGH | HIGH | HIGH | HIGH | HIGH | HIGH | HIGH | HIGH | HIGH | HIGH | HIGH | HIGH | HIGH | HIGH | HIGH | HIGH | HIGH | HIGH | HIGH | HIGH | HIGH | HIGH | HIGH | HIGH | HIGH | HIGH | HIGH | HIGH | HIGH | HIGH | HIGH | HIGH | HIGH | HIGH | HIGH | HIGH | HIGH | HIGH | HIGH | HIGH | HIGH | HIGH | HIGH |
| Peak Fan Airflow (cfm) / [Design gpm] | 812 | 812 | 812 | 460 | 460 | 812 | 315 | 315 | 315 | 315 | 315 | 315 | 315 | 315 | 315 | 315 | 920 | 315 | 335 | 335 | 335 | 335 | 335 | 335 | 315 | 315 | 315 | 315 | 315 | 315 | 315 | 315 | 315 | 315 | 315 | 315 | 315 | 315 | 315 | 315 | 315 | 315 | 315 | 315 | 920 | 315 | 315 | 315 | |
| Max Fan ESP Setting 208V/230V (IN WG) | |||||||||||||||||||||||||||||||||||||||||||||||||
| Sound Pressure Per Fan Speed 208V/230V (dBA) | 28-31-33-35 | 28-31-33-35 | 28-31-33-35 | 33-39-43 | 33-39-43 | 28-30-32-34 | 26-30-33 | 26-30-33 | 26-30-33 | 26-30-33 | 26-30-33 | 26-30-33 | 26-30-33 | 26-30-33 | 26-30-33 | 26-30-33 | 39-49 | 26-30-33 | 26-30-34 | 26-30-34 | 26-30-34 | 26-30-34 | 26-30-34 | 26-30-34 | 26-30-33 | 26-30-33 | 26-30-33 | 26-30-33 | 26-30-33 | 26-30-33 | 26-30-33 | 26-30-33 | 26-30-33 | 26-30-33 | 26-30-33 | 26-30-33 | 26-30-33 | 26-30-33 | 26-30-33 | 26-30-33 | 26-30-33 | 26-30-33 | 26-30-33 | 26-30-33 | 39-49 | 26-30-33 | 26-30-33 | 26-30-33 | |
| Electrical Data | Voltage / Phase | 208/230V/1-phase | 208/230V/1-phase | 208/230V/1-phase | 208/230V/1-phase | 208/230V/1-phase | 208/230V/1-phase | 208/230V/1-phase | 208/230V/1-phase | 208/230V/1-phase | 208/230V/1-phase | 208/230V/1-phase | 208/230V/1-phase | 208/230V/1-phase | 208/230V/1-phase | 208/230V/1-phase | 208/230V/1-phase | 208/230V/1-phase | 208/230V/1-phase | 208/230V/1-phase | 208/230V/1-phase | 208/230V/1-phase | 208/230V/1-phase | 208/230V/1-phase | 208/230V/1-phase | 208/230V/1-phase | 208/230V/1-phase | 208/230V/1-phase | 208/230V/1-phase | 208/230V/1-phase | 208/230V/1-phase | 208/230V/1-phase | 208/230V/1-phase | 208/230V/1-phase | 208/230V/1-phase | 208/230V/1-phase | 208/230V/1-phase | 208/230V/1-phase | 208/230V/1-phase | 208/230V/1-phase | 208/230V/1-phase | 208/230V/1-phase | 208/230V/1-phase | 208/230V/1-phase | 208/230V/1-phase | 208/230V/1-phase | 208/230V/1-phase | 208/230V/1-phase | 208/230V/1-phase |
| Power Cooling 208V/230V (kW) | 0.040 | 0.040 | 0.040 | 0.040 | 0.040 | 0.040 | 0.020 | 0.020 | 0.020 | 0.020 | 0.020 | 0.020 | 0.020 | 0.020 | 0.020 | 0.020 | 0.080 | 0.020 | 0.020 | 0.020 | 0.020 | 0.020 | 0.020 | 0.020 | 0.020 | 0.020 | 0.020 | 0.020 | 0.020 | 0.020 | 0.020 | 0.020 | 0.020 | 0.020 | 0.020 | 0.020 | 0.020 | 0.020 | 0.020 | 0.020 | 0.020 | 0.020 | 0.020 | 0.020 | 0.080 | 0.020 | 0.020 | 0.020 | |
| Power Heating 208V/230V (kW) | 0.04 | 0.04 | 0.04 | 0.04 | 0.04 | 0.04 | 0.02 | 0.02 | 0.02 | 0.02 | 0.02 | 0.02 | 0.02 | 0.02 | 0.02 | 0.02 | 0.08 | 0.02 | 0.02 | 0.02 | 0.02 | 0.02 | 0.02 | 0.02 | 0.02 | 0.02 | 0.02 | 0.02 | 0.02 | 0.02 | 0.02 | 0.02 | 0.02 | 0.02 | 0.02 | 0.02 | 0.02 | 0.02 | 0.02 | 0.02 | 0.02 | 0.02 | 0.02 | 0.02 | 0.08 | 0.02 | 0.02 | 0.02 | |
| Electrical MCA/MFS | 0.57/15 | 0.57/15 | 0.57/15 | 0.36/15 | 0.36/15 | 0.54/15 | 0.36/15 | 0.36/15 | 0.36/15 | 0.36/15 | 0.36/15 | 0.36/15 | 0.36/15 | 0.36/15 | 0.36/15 | 0.36/15 | 0.34/15 | 0.36/15 | 0.36/15 | 0.36/15 | 0.36/15 | 0.36/15 | 0.36/15 | 0.36/15 | 0.36/15 | 0.36/15 | 0.36/15 | 0.36/15 | 0.36/15 | 0.36/15 | 0.36/15 | 0.36/15 | 0.36/15 | 0.36/15 | 0.36/15 | 0.36/15 | 0.36/15 | 0.36/15 | 0.36/15 | 0.36/15 | 0.36/15 | 0.36/15 | 0.36/15 | 0.36/15 | 0.34/15 | 0.36/15 | 0.36/15 | 0.36/15 | |
| Condensate Removal Rate (gal/hr) | 0.50 | 0.50 | 0.50 | 0.50 | 0.50 | 0.50 | 0.50 | 0.50 | 0.50 | 0.50 | 0.50 | 0.50 | 0.50 | 0.50 | 0.50 | 0.50 | 0.50 | 0.50 | 0.50 | 0.50 | 0.50 | 0.50 | 0.50 | 0.50 | 0.50 | 0.50 | 0.50 | 0.50 | 0.50 | 0.50 | 0.50 | 0.50 | 0.50 | 0.50 | 0.50 | 0.50 | 0.50 | 0.50 | 0.50 | 0.50 | 0.50 | 0.50 | 0.50 | 0.50 | 0.50 | 0.50 | 0.50 | 0.50 | |
| Actual Port Assignments | |||||||||||||||||||||||||||||||||||||||||||||||||
| Notes / Options | Applicable System Notes - See Notes Below | 1, 2, 3, 4 | 1, 2, 3, 4 | 1, 2, 3, 4 | 1, 2, 3, 4 | 1, 2, 3, 4 | 1, 2, 3, 4 | 1, 2, 3, 4 | 1, 2, 3, 4 | 1, 2, 3, 4 | 1, 2, 3, 4 | 1, 2, 3, 4 | 1, 2, 3, 4 | 1, 2, 3, 4 | 1, 2, 3, 4 | 1, 2, 3, 4 | 1, 2, 3, 4 | 1, 2, 3, 4 | 1, 2, 3, 4 | 1, 2, 3, 4 | 1, 2, 3, 4 | 1, 2, 3, 4 | 1, 2, 3, 4 | 1, 2, 3, 4 | 1, 2, 3, 4 | 1, 2, 3, 4 | 1, 2, 3, 4 | 1, 2, 3, 4 | 1, 2, 3, 4 | 1, 2, 3, 4 | 1, 2, 3, 4 | 1, 2, 3, 4 | 1, 2, 3, 4 | 1, 2, 3, 4 | 1, 2, 3, 4 | 1, 2, 3, 4 | 1, 2, 3, 4 | 1, 2, 3, 4 | 1, 2, 3, 4 | 1, 2, 3, 4 | 1, 2, 3, 4 | 1, 2, 3, 4 | 1, 2, 3, 4 | 1, 2, 3, 4 | 1, 2, 3, 4 | 1, 2, 3, 4 | 1, 2, 3, 4 | 1, 2, 3, 4 | 1, 2, 3, 4 |
| Notes & Options: | |||||||||||||||||||||||||||||||||||||||||||||||||
| 1 | Nominal cooling capacities are based on indoor coil EAT of 80/67°F (DB/WB), outdoor of 95°F (DB) | ||||||||||||||||||||||||||||||||||||||||||||||||
| 2 | Nominal heating capacities are based on indoor coil EAT of 70°F (DB), outdoor of 43°F (WB) | ||||||||||||||||||||||||||||||||||||||||||||||||
| 3 | See outdoor unit schedule for outdoor ambient conditions, connected capacity, and other factors associated with corrected capacities | ||||||||||||||||||||||||||||||||||||||||||||||||
| 4 | See schematic piping/control diagram for indication of required indoor unit remote controllers, system controllers, and integration devices. | ||||||||||||||||||||||||||||||||||||||||||||||||
| 5 | Full demand corrected capacity includes de-rate associated with indoor vs. outdoor connected capacity indicated on outdoor unit schedule for associated system. |
Partial corrected capacity assumes sufficient diversity exists such that the connected capacity de-rate does not apply.
It is the designer's responsibility to ensure "Diamond System Builder" is set in the appropriate output capacity setting (full demand/partial demand) prior to generating this schedule.
6 It is recommended to always base heating corrected capacity on full demand.
&G
&G
BCController
| VRF HEAT RECOVERY BRANCH CIRCUIT CONTROLLER | |||||||
| System Tag | VFR-1A | VRF-2A | VRF-3A | VRF-1B | VRF-1B | VRF-2B | |
| Tag Reference | BCC-1A | BCC-2A | BCC-3A | BCC-1B | BCC-1B SUB | BCC-2B | |
| Nominal Data | M-NET Address | 53 | 58 | 71 | 81 | 90 | 52 |
| Model Number | CMB-M108NU-MA1-SV | CMB-M1012NU-MA1-SV | CMB-M1012NU-MA1-SV | CMB-M1012NU-MA1-SV | CMB-M108NU-MB1-SV | CMB-M1012NU-MA1-SV | |
| Type (double / Main / Sub) | Main | Main | Main | Main | Sub | Main | |
| Number of Ports | 8 | 12 | 12 | 12 | 8 | 12 | |
| Connected Capacity to BC | 150,000.0 | 112,000.0 | 104,000.0 | 152,000.0 | 64,000.0 | 114,000.0 | |
| Electrical Data | Voltage / Phase | 208/230V / 1-phase | 208/230V / 1-phase | 208/230V / 1-phase | 208/230V / 1-phase | 208/230V / 1-phase | 208/230V / 1-phase |
| Power Cooling 208V/230V (kW) | 0.122/0.157 | 0.182/0.235 | 0.182/0.235 | 0.182/0.235 | 0.122/0.157 | 0.182/0.235 | |
| Power Heating 208V/230V (kW) | 0.061/0.078 | 0.091/0.118 | 0.091/0.118 | 0.091/0.118 | 0.061/0.078 | 0.091/0.118 | |
| MCA 208/230 | 0.74/0.87 | 1.1/1.29 | 1.1/1.29 | 1.1/1.29 | 0.74/0.87 | 1.1/1.29 | |
| Notes / Options | Applicable System Notes - See Notes Below | 1 | 1 | 1 | 1 | 1 | 1 |
| Notes & Options: | |||||||
| 1 | Include Diamondback Ball Valves BV-Series, 700PSIG working pressure, full port, 410A rated. | ||||||
| 2 | For sub BC controller CMB-P-NU-GB1 or -GB, the total connectable indoor unit capacity can be 126,000 BTUs or less. If two sub BC controllers are used, the total indoor unit capacity connected to BOTH sub BC controllers also cannot exceed 126,000 BTUs. For sub BC controller CMB-P1016NU-HB1 the total connectable indoor unit capacity can be 126,000 BTUs or less. However, if two sub controllers are used, and one of them is CMB-1016NU-HB1, the total indoor unit capacity connected to BOTH sub controllers must NOT exceed 168,000 BTUs. |
&G
&G
ShutoffValveKit
| SHUTOFF VALVE KIT | |||
| System Tag | VRF-3B DOAS | VRF-3B DOAS | |
| Tag Reference | |||
| Nominal Data | M-NET Address | 162 | 163 |
| Model Number | CMR-M100KT-NA | CMR-M100KT-NA | |
| Connected Capacity to SVK (BTU/h) | 72,000.0 | 72,000.0 | |
| Electrical Data | Voltage / Phase | 208/230V/1-phase | 208/230V/1-phase |
| MCA 208/230 | 0.38/0.44 | 0.38/0.44 | |
| Mrel (lbs) | 64.6 | 64.6 |
&G
&G image1.png image2.png image3.png image4.png image5.png image6.png image7.png image8.png image9.png image10.png
This is the start of the file's text. The full file is on GovTribe.