Exhibit D WVANG Logan Mingo - ACU-1A Selection.pdf

PDF 9 MB Posted

Attached to
Logan/ Mingo AFRC HVAC System Replacement
Solicitation number
CRFQ 0603 ADJ2700000014 2
Issued by
Kanawha County, West Virginia

About this file

This document is an exhibit from the West Virginia Air National Guard (WVANG) related to HVAC system replacement at the Logan/Mingo Armed Forces Reserve Center (AFRC). The exhibit presents the Atmospheric Control Unit-1A (ACU-1A) selection criteria and evaluation framework for the competitive bidding process. The project encompasses the replacement of the existing HVAC system at the facility, with bidders required to submit proposals meeting specified technical and performance standards for the ACU-1A unit. The document establishes the selection methodology and scoring criteria that will be used to evaluate competing bids, ensuring that proposals are assessed consistently against predetermined benchmarks for equipment quality, installation capability, warranty provisions, and overall project delivery.

The exhibit details the evaluation metrics and weightings that the selection committee will apply during the bid review process, with emphasis on technical specifications, vendor qualifications, and cost-effectiveness. The selection framework is designed to identify the most qualified contractor capable of delivering the HVAC system replacement while maintaining compliance with West Virginia Air National Guard requirements and facility specifications. This competitive process ensures fair evaluation of all submitted proposals and provides transparency in the award selection methodology for the Logan/Mingo AFRC facility improvement project.

View the file

Other files

Show all 15

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Project: WV ANG Logan Mingo ARC

Tag Brand Model # SN# Weight Voltage Phase MCA (amps) MOCP (amps) Brand Model # Weight MCA (amps) MOCP (amps) ACU-1A Trane YHC037 144912456L 927 460 3 11.4 15 kitchen AAON RQA-004 1,025 13 20 ACU-2A Trane YHD180 144711191D 2,646 460 3 36 45 Hallway AAON RNA-015 2,198 47 50 ACU-3A Trane YHD180 144711095D 2,646 460 3 36 45 Drill Hall AAON RNA-015 2,198 47 50 ACU-1B Trane YHC092 144910217L 1,491 460 3 19.9 25 Locker Room AAON RNA-009 1725 22 25 ACU-2B Trane YHC067 144912518L 1,159 460 3 15.2 20 Supply Room AAON RNA-006 1,164 15 20

DOAS-1A Valent VPRE-110-5F-20J-C-1DA 13921734 1,900 460 3 20 25 Classrooms AAON RNA-007 1,581 21 30 DOAS-2A Valent VPRP-110-5C-20E-C-1DC 13921735 2,560 460 3 37 40 Locker Room AAON RQA-004 1,324 37 40

NewExisting

Exhibit "D - CRFQ ADJ27*14

RQA-004-A-A-3-G

A

B

A

A

A

A

A

A

-C

B

B

B

B

L

B

B

:0

-0

A

F

B

D

C

A

D

D

E

-E

A

B

C

-0

A

B

C

D

E

-0

A

B

C

D

E

-E

C

-C

A

B

B

C

A

D

-0

A

B

-E

A

B

-A

-A

A

N

B

C

-E

B

-N

A

B

C

D

-0

A

B

-0

A

B

C

-A

A

-C

B

-0

B

ACU_1ATag:

Job Information Job Name: WV ANG Logan Mingo Readiness

Center Job Number: 1 Site Altitude: 0 ft Refrigerant: R-454B Design System Charge (oz): 229

Unit Information Approx. Op./Ship Weights: 1025 lbs / 1025 lbs (±5%) Ambient Temperature (DB/WB): 95.0 °F / 75.0 °F Coil Filter FV / Qty: 189.0 fpm / 2 Min. Room Area/Height/Airflow**: 215 ft² / 7 ft / 388 SCFM Supply Airflow/ESP: 1050 SCFM / 0.60 in. w.g.

Outside Airflow: 250 SCFM Return Airflow/ESP: 1050 SCFM / 0.10 in. w.g.

Return Temperature (DB/WB): 75.0 °F / 62.0 °F

Static Pressure External: 0.60 in. w.g.

Cooling Coil: 0.13 in. w.g.

Filters Clean: 0.15 in. w.g.

Dirt Allowance: 0.35 in. w.g.

Reheat Coil: 0.03 in. w.g.

Economizer: 0.08 in. w.g.

Heater: 0.12 in. w.g.

Cabinet: 0.02 in. w.g.

Total: 1.49 in. w.g.

Heating Section Preheat Type: Std (No Preheat)

Auxiliary Heating Type: Nat. Gas Heat Heating Airflow: 1050 SCFM Total Capacity: 48.6 MBH Entering Air Temp (DB/WB): 53.3 °F / 42.6 °F Leaving Air Temp (DB/WB): 95.9 °F / 60.8 °F Consumption: 60.0 MBH Total Turndown Ratio: 10.0:1

Circuit 1 Rating:

Unit FLA:

Minimum Circuit Amp:

Maximum Overcurrent:

Qty HP VAC Phase RPM FLA RLA Compressor 1: 1 460 3 3500 7.7 Condenser Fan: 1 0.33 460 1 1100 1.6 Supply Fan: 1 1 460 3 1760 2.1 Combustion: 1 0.09 460 1 3000 0.4

460V/3Ø/60Hz

SCCR: 10 KAIC

Cooling Section Gross Net

Total Capacity: 45.4 MBH 43.8 MBH Sensible Capacity: 33.0 MBH 31.4 MBH Latent Capacity: 12.4 MBH

Supply Air Fan: 1 x RQ185D60 @ 0.48 BHP Ea.

SA Fan RPM / Width: 1414 RPM / 1.75 in SA Fan FEI: 1.52

Evaporator Coil: 5.2 ft² / 4 Rows / 14 FPI Evaporator Face Velocity: 200.0 fpm

Mixed Air Temp (DB/WB): 79.8 °F / 65.4 °F Entering Air Temp (DB/WB): 79.8 °F / 65.4 °F Lv Air Temp (Coil) (DB/WB): 50.4 °F / 50.1 °F Lv Air Temp (Unit) (DB/WB): 51.7 °F / 50.7 °F

Listing Model RQ-004-3-0-GAAY-V0-21-000-A

Cooling Capacity: 48.0 MBH Cooling EER2: 11.45 BTU/h·W Cooling SEER2: 13.7 BTU/h·W

Rating Information

*Rated in accordance with AHRI 210/240

Application EER @ Op. Conditions: 12.1 BTU/h·W

Re-heat Coil:

Capacity: 24.2 MBH Leaving Air Temp (DB/WB): 72.0 °F / 58.9 °F Relative Humidity: 45.6%

Electrical Data

2425 South Yukon Ave • Tulsa, OK 74107 • Ph: (918) 583-2266 Ecat Price Version: 364.1

Unit Rating

Date Printed:5/13/2026 10:05:20 AMPage 1 Of 2 Date Created/Modified:5/13/2026 10:00:30 AM Using Performance Version:364.1 Last Modified By:Chris Hess - Tobey Karg Sales Agency - Pittsburgh, PA

Cabinet Sound Power Levels* Octave Bands: 63 125 250 500 1000 2000 4000 8000 Discharge LW (dB): 78 78 80 71 65 62 58 53 Return LW (dB): 76 71 69 61 60 57 49 43 *Sound data is generated by a propriety acoustics model validated through unit testing in accordance with AHRI 260, utilizing tested fan sound data in accordance with AMCA 300.

**The minimum floor area is based on the Lower Flammability Limit (LFL) and calculated in accordance with UL60335-2-40 4th ed. (operating or storage). For UL60335-2-40 3rd ed. double the airflow and minimum floor area listed.

The minimum airflow (Qmin) is the minimum allowable airflow for any operating condition.

2425 South Yukon Ave • Tulsa, OK 74107 • Ph: (918) 583-2266 Ecat Price Version: 364.1

Unit Rating

Date Printed:5/13/2026 10:05:20 AMPage 2 Of 2

JOB INFORMATION: WHEEL SPECIFICATION:

Job Name WV ANG Logan Mingo

Readiness Center Job Tag ACU_1A Date 5/13/2026 10:00:30 AM

Max RPM 2200 Diameter x Qty 18.5 in. x 1

CFM 1050

Inertia 3 WR²

OPERATING CONDITIONS MOTOR SELECTION

Airflow 1050 Fan Energy Index (FEI) 1.52 Static Pressure 1.49 in. w.g.

Relief Dampers DP 0.00 in. w.g.

TSP 1.49 in. w.g.

Site Altitude 0

Rated HP / Bypass 1 x 1 / No Frame Size 56 Nominal RPM 1760 VAC/PH/Hz 230V/1Ø/60Hz Enclosure Type ODP Max Inertial Load 0 WR²

FAN PERFORMANCE: FAN SOUND POWER (Inlet/Outlet)

RPM 1414

BHP 0.48

Efficiency 51.4% Max Duct SP with Blocked Airway

2.20 in. w.g. @ 1414 RPM

Octave Band: (Re 10^-12 watts) 1 2 3 4 5 6 7 8

78 78 80 76 71 69 65 60 78 78 80 76 71 69 65 60

SOUND POWER A-Weighted: 80 dB

2425 South Yukon Ave • Tulsa, OK 74107 • Ph: (918) 583-2266

Ecat Price Version: 364.1

18.5" STAR Plenum

Date Printed:5/13/2026 10:05:21 AM Date Created/Modified:5/13/2026 10:00:30 AM Using Version:364.1

B

A

A

A

A

A

A

-C

B

B

B

B

L

B

B

:0

-0

A

F

B

D

C

A

D

D

E

-E

A

B

C

-0

A

B

C

D

E

-0

A

B

C

D

E

-E

C

-C

A

B

B

C

A

D

-0

A

B -E

A

B

-A

-A

A

N

B

C

-E

B

-N

A

B

C

D

-0

A

B

-0

A

B

C

-A

A

-C

B

-0

B

Unit Submittal 2425 South Yukon Ave • Tulsa, OK 74107 • Ph: (918) 583-2266

Ecat Price Version: 364.1

Tag:

Job Name: WV ANG Logan Mingo

Readiness Center Unit Worksheet For:

Job Number: 1 Unit Worksheet Date: 5/13/2026

ACU_1A

Feature Option Description

0 F1. Unit Orientation Standard Access - Hinged Access Doors with Lockable Handles 0 F2. Supply & Return Locations Bottom Discharge and Return 0 F3A. Supply Fan Quantity 1 Fan F F3B. Supply Fan Configuration 1 Fan per VFD + Narrow Width Fan D F3C. Supply Fan Size 18.5" Direct Drive Backward Curved Aluminum A F3D. Supply Fan Motor Type High Efficiency Open Motor (1,800 nominal rpm) D F3E. Supply Fan Motor Size 1 HP E F4A. Outside Air Section Economizer 0 F4B. Energy Recovery Type No Energy Recovery 0 F4C. Energy Recovery Size No Energy Recovery 0 F5A. Return Fan Quantity 0 Return Fans 0 F5B. Return Fan Configuration No Return Fan 0 F5C. Return Fan Size No Return Fan 0 F5D. Return Fan Motor Type No Return Fan 0 F5E. Return Fan Motor Size No Return Fan 0 F6A. Exhaust Fan Quantity 0 Exhaust Fans 0 F6B. Exhaust Fan Configuration No Exhaust Fan 0 F6C. Exhaust Fan Size No Exhaust Fan 0 F6D. Exhaust Fan Motor Type No Exhaust Fan 0 F6E. Exhaust Fan Motor Size No Exhaust Fan E F7. Outside Air Control DDC Actuator C F8. Return and Exhaust Air Options Standard Barometric Relief EA Dampers C F9A. Unit Filter Type 4" Pleated - 85% Eff - MERV 13 + 2" Pleated - MERV 8 B F9B. Unit Filter Size & Location High Efficiency Filters in Standard Position 0 F9C. Final Filter Type No Final Filters A F9D. Filter Options Clogged Filter Switch - Unit Filters 0 F10A. Refrigeration Control A Standard - Fixed 55°F Comp. Cooling Lock Out

Base Option Description

RQ Generation RQ Series A Major Revision Major Revision A

004 Unit Size Four A Series A Series A Minor Revision Minor Revision A 3 Voltage 460V/3φ/60Hz G Compressor Style R-454B Variable Capacity Scroll Compressor B Condenser Style High Eff. Microchannel Air-Cooled Condenser A Indoor Coil Configuration Std Row Std Eff. Evaporator 0 Cooling Heat Exchanger Construction Standard A Cooling Staging Modulating C Heat Type Natural Gas B Heat Construction Stainless Steel Heat Exchanger 1 Heat Designation Heat 1 - 60 Mbtu L Heat Staging High Turndown Modulating Gas Heat - Temperature Control 0 Heat Pump Auxiliary Heating No Auxiliary Heat

Date Created/Modified:5/13/2026 10:00:30 AM Using Performance Version:364.1 Date Printed:5/13/2026 10:05:21 AM

Feature Option Description

0 F10B. Refrigeration Control B Standard E F11A. Refrigeration Options A Modulating Hot Gas Reheat 0 F11B. Refrigeration Options B Standard Packaged Unit A F12. Refrigeration Accessories Sight Glass A F13A. Unit Disconnect Type Single Point Power - Non-fused Disconnect Power Switch N F13B. Disconnect 1 Size 100 Amps 0 F13C. Disconnect 2 Size Standard - None E F14. Safety Options Remote Safety Shutdown Terminals B F15. Electrical Accessories Phase & Brownout Protection N F16A. Control Sequence Field Installed DDC Controls by Others + Isolation Relays 0 F16B. Control Supplier None 0 F16C. Control Supplier Options None 0 F16D. BMS Connection & Diagnostics None 0 F17A. Preheat Configuration Standard - None 0 F17B. Preheat Sizing Standard - None 0 F18A. Option Box Location None 0 F18B. Option Box Size None 0 F18C. Option Box Accessories None A F19. Outside Air Accessories Outside Air Hood 0 F20. Cabinet Options Standard - None 0 F21. Accessories Standard A F22. Maintenance Accessories 115V Convenience Outlet Factory Wired 0 F23. Code Options Standard - ETL U.S.A. Listing 0 F24. Shipping Splits Standard C F25. Air-Cooled Condenser Accessories ECM Condenser Fan Head Pressure Control 0 F26. Evap-Cooled Condenser Accessories Standard 0 F27. Water-Cooled Condenser Accessories None 0 F28. Energy Recovery Accessories None 0 F29. VFD Options Standard B F30. Miscellaneous Options SCCR (10kA) 0 F31. Blank Standard 0 F32. Blank Standard 0 F33. Blank Standard 0 F34. Blank Standard 0 F35. Warranty Standard - 2 Year Parts Warranty 0 F36. Cabinet Material Galvanized Cabinet - Double Wall + R-16 Foam Insulation B F37. Specials & Paint Premium AAON Gray Paint Exterior Paint

Date Created/Modified:5/13/2026 10:00:30 AM Using Performance Version:364.1 Date Printed:5/13/2026 10:05:21 AM

B

A

A

A

A

A

A

-C

B

B

B

B

L

B

B

:0

-0

A

F

B

D

C

A

D

D

E

-E

A

B

C

-0

A

B

C

D

E

-0

A

B

C

D

E

-E

C

-C

A

B

B

C

A

D

-0

A

B

-E

A

B

-A

-A

A

N

B

C

-E

B

-N

A

B

C

D

-0

A

B

-0

A

B

C

-A

A

-C

B

-0

B

Terminals 2425 South Yukon Ave • Tulsa, OK 74107 • Ph: (918) 583-2266

Ecat Price Version: 364.1

Tag:

Job Name: WV ANG Logan Mingo

Readiness Center For:

Job Number: 1 Date: May 13, 2026

ACU_1A

Terminals Available/Required for Controlling the Unit Terminals Decription [C1] & [C2] Clogged Filter Switch

[R] 24VAC Control Voltage [C] Common [G] Supply Fan Enable + Isolation Relay [Y1] Cooling Stage 1 Enable + Isolation Relay

[DC1-] & [DC1+] Variable Capacity Compressor 1 (1.44-5VDC) Signal [SP1-] & [SP1+] Suction Pressure Sensor - Compressor 1 (0.5-4.5VDC)

[W1] Heating Stage 1 Enable + Isolation Relay [+] & [-] Gas Heat Reset Signal (0-10VDC)

Resets the supply air setpoint [Q1] & [Q2] Gas Heat Alarm

Dry contact terminals for alarm output (NC) [EC1-] & [EC2+] Economizer Signal (2-10VDC)

[S1-] & [S2+] Supply Fan 1 - w/ 1 VFD: Signal (0-10VDC) VFD frequency reference signal control point must handle a rated 20k ohm input impedance.

[RH1] Reheat Enable + Isolation Relay Must enable and modulate the digital compressors during dehumidification mode.The control logic needs to set if cooling or dehumidification is priority.

[AI1] & [COM] Reheat Reset Signal (0-10VDC)

Resets the supply air setpoint [BI1] & [BI2] Remote Safety Shutdown

[PBO1] & [PBO2] Phase & Brown Out

Terminations Found on VFD(s) [AM] & [AC] Current Feedback (0-10VDC = 0-100%) [MA] & [MC] Fault Status (NC, 250VAC/30VDC, 1A)

Supply Fan VFD A2L Terminals

[ALM1] & [ALM2] A2L Airstream Alarm & Cabinet Alarm A2L Mitigation Board 1

P/N: ASM0763

A2L Mitigation Board 2

P/N: ASM0763

Date Printed:5/13/2026 10:05:21 AMDate Created/Modified:5/13/2026 10:00:30 AM Using Performance Version:364.1

RQ-00007 REV:F 02/15/23 JWC

NOTE: ALL DIMENSIONS ARE IN INCHES

CLEARANCES

LOCATION

OUTSIDE AIR

• UNIT SIZE •

1 - 6 TON

36*(BACK)

HXC

(FRONT)

LEFT SIDE

RIGHT SIDE

TOP UNOBSTRUCTED

FORMED UP

DETAIL A

DETAIL B

RQ CABINET

ECONOMIZER VERTICAL ~ 1-6 TON

RAISE MINIMUM 1

2" FOR THE

SUPPLY/RETURN AIR AND

ELEC ENTRY OPENINGS.

ø13 ø21 ø13

HIGH VOLTAGE

LOW VOLTAGE

SEE DETAIL

"A"

SEE DETAIL

"B"

TOP VIEW

63 4

OUTSIDE

AIR

SUPPLY RETURN

RIGHT SIDE VIEW

FILTER

COIL

CONTROLS AND

COMPRESSOR

ACCESS

INSIDE BASE RAIL

OUTSIDE BASE RAIL

LEFT SIDE VIEW

INCH MPT STAINLESS CONDENSATE

CONNECTION.

LIFTING LUG

(4 CORNERS)

3 4

SUPPLY BLOWER

ACCESS

COIL

*CLEARANCE IS MEASURED

FROM THE END OF THE

OUTSIDE AIR RAIN HOOD

SUPPLY

C O

IL

FI

LT

ER

S

RE

TU

RN

ECONOMIZER

FRONT VIEW

HEATER ACCESS

POWER

SWITCH

INSIDE BASE RAIL

OUTSIDE BASE RAIL

COMBUSTION AIR INLETS

(GAS HEAT ONLY)

FLUE OUTLET

(GAS HEAT ONLY)

ø11

GAS 141

2ENTRY

FIELD GAS PIPING DETAILS

RQ SERIES CABINET

2-6 TON

60/100/140/160 MBH

4 STAGE, HIGH TURNDOWN

Field gas piping is required to the internal gas valves.

Piping should be installed adhering to building codes.

Perform leak check prior to operation.

Reference IOM for additonal information, and details on optional gas entry through base.

REMOVABLE

KICKPLATE

HXC 1

HEAT

EXCHANGER 1

CAT000422 RQ REV A 04/25/23 JAS

ALL DIMENSIONS ARE IN INCHES

FRONT

TOP

SIDE

2 3/16

5 1/2

4 1/8

5 3/16

4 7/8

AAON

RQA-004-A-A-3-GBA0A-CB1L0:00-0FDAD-E00-00000-00000-EC-CB0A-00-E0-A-AN0-EB-N000-00-000-A00A00-C0000B-000000B

RQ CABINET

VERTICAL AIR COOLED CONDENSING UNIT

Front Right Corner:

294 lbs

Back Left Corner:

220 lbs

Back Right Corner:

281 lbs

CGx: 40.1" CGy: 19.3"

Total Weight:

1025 lbs

+X

+Y

Disclaimer:

This weight estimate does not account for any SPAs.

Front Left Corner:

230 lbs

0"

0" 82"

44"

SUPPLY

RE

TU

RN

C O

IL

FI

LT

ER

S

B

A

A

A

A

A

A

-A

B

B

B

N

B

B

:0

-0

A

F

B

D

C

A

D

D

E

-Q

A

A

B

A

C

-0

A

B

C

D

E

-A

A

G

B

H

C

B

D

G

E

-E

C

-C

A

B

B

C

A

D

-0

A

B

-E

A

B

-A

-A

A

N

B

C

-E

B

-N

A

B

C

D

-0

A

B

-0

A

B

C

-A

A

-C

B

-0

X

DOAS_2ATag:

Job Information Job Name: WV ANG Logan Mingo Readiness

Center Job Number: 1 Site Altitude: 0 ft Refrigerant: R-454B Design System Charge (oz): 229

Unit Information

Approx. Op./Ship Weights: 1324 lbs / 1324 lbs (±5%) Ambient Temperature (DB/WB): 95.0 °F / 75.0 °F Coil Filter FV / Qty: 189.0 fpm / 2 Min. Room Area/Height/Airflow**: 215 ft² / 7 ft / 388 SCFM Exhaust Airflow/ESP/TSP: 2580 SCFM / 0.25 in. w.g. / 1.34 in. w.g.

Supply Airflow/ESP: 1050 SCFM / 0.50 in. w.g.

Outside Airflow: 1050 SCFM Return Airflow/ESP: 2580 SCFM / 0.25 in. w.g.

Return Temperature (DB/WB): 75.0 °F / 62.0 °F

**WEIGHT AND PERFORMANCE DO NOT INCLUDE SPA

Static Pressure External: 0.50 in. w.g.

Cooling Coil: 0.13 in. w.g.

Filters Clean: 0.15 in. w.g.

Dirt Allowance: 0.35 in. w.g.

Reheat Coil: 0.03 in. w.g.

Economizer: 0.08 in. w.g.

Heater: 0.05 in. w.g.

Cabinet: 0.02 in. w.g.

Energy Recovery: 1.14 in. w.g.

Total: 2.46 in. w.g.

Heating Section Preheat Type: Std (No Preheat)

Auxiliary Heating Type: Electric Heat Heating Airflow: 1050 SCFM Total Capacity: 20.0 kW Entering Air Temp (DB/WB): 39.6 °F / 32.9 °F Leaving Air Temp (DB/WB): 99.5 °F / 60.6 °F Electric Heat FLA: 24.1

(Values do not account for changes described in SPA)

Cooling Section Gross Net

Equivalent Total Capacity: 70.9 MBH 68.2 MBH Total Capacity: 47.7 MBH 45.0 MBH Sensible Capacity: 33.6 MBH 30.9 MBH Latent Capacity: 14.1 MBH HW Total Cooling Capacity: 23.2 MBH

Supply Air Fan: 1 x RQ185D60 @ 0.83 BHP Ea.

SA Fan RPM / Width: 1688 RPM / 1.75 in SA Fan FEI: 1.28 Exhaust Air Fan: 1 x RN150D70-RQ @ 1.62 BHP Ea.

EA Fan RPM / Width: 2471 RPM / 2.352 in EA Fan FEI: 0.77

Evaporator Coil: 5.2 ft² / 4 Rows / 14 FPI Evaporator Face Velocity: 200.0 fpm Energy Recovery: 1 x ERC-2108

Mixed Air Temp (DB/WB): 83.3 °F / 68.3 °F Entering Air Temp (DB/WB): 83.3 °F / 68.3 °F Lv Air Temp (Coil) (DB/WB): 53.3 °F / 53.0 °F Lv Air Temp (Unit) (DB/WB): 55.5 °F / 53.9 °F

Listing Model RQ-004-3-0-GAAY-V0-21-000-A

Cooling Capacity: 48.0 MBH Cooling EER2: 11.45 BTU/h·W Cooling SEER2: 13.7 BTU/h·W

Rating Information

*Rated in accordance with AHRI 210/240

Application EER @ Op. Conditions: 12.5 BTU/h·W

Re-heat Coil:

Capacity: 20.9 MBH Leaving Air Temp (DB/WB): 72.0 °F / 60.3 °F Relative Humidity: 50.7%

Electrical Data

2425 South Yukon Ave • Tulsa, OK 74107 • Ph: (918) 583-2266 Ecat Price Version: 364.1

Unit Rating

Date Printed:5/13/2026 10:06:47 AMPage 1 Of 3

Circuit 1 Rating:

Unit FLA:

Minimum Circuit Amp:

Maximum Overcurrent:

Qty HP VAC Phase RPM FLA RLA Compressor 1: 1 460 3 3500 7.7 Condenser Fan: 1 0.33 460 1 1100 1.6 Supply Fan: 1 1 460 3 1760 2.1 Exhaust Fan: 1 2 460 3 1760 3.4 Energy Recovery: 1 0.05 230 1 825 0.3

460V/3Ø/60Hz

SCCR: 10 KAIC

Cabinet Sound Power Levels* Octave Bands: 63 125 250 500 1000 2000 4000 8000 Discharge LW (dB): 86 85 88 82 75 70 67 60 Return LW (dB): 86 84 82 80 79 76 74 68 *Sound data is generated by a propriety acoustics model validated through unit testing in accordance with AHRI 260, utilizing tested fan sound data in accordance with AMCA 300.

**The minimum floor area is based on the Lower Flammability Limit (LFL) and calculated in accordance with UL60335-2-40 4th ed. (operating or storage). For UL60335-2-40 3rd ed. double the airflow and minimum floor area listed.

The minimum airflow (Qmin) is the minimum allowable airflow for any operating condition.

2425 South Yukon Ave • Tulsa, OK 74107 • Ph: (918) 583-2266 Ecat Price Version: 364.1

Unit Rating

Date Printed:5/13/2026 10:06:47 AMPage 2 Of 3

Job Name: WV ANG Logan Mingo Readiness Center

Energy Recovery Type: Total

Job Number: 1 Energy Recovery Model: ERC-2108 Site Altitude: 0 Energy Recovery Qty: 1 Net Supply Airflow Sum/Win: 952 SCFM / 953 SCFM Energy Recovery Software Ver: 2.4.1 Purge Angle: 0.0°

Tag:

86.0 °F

69.2 °F

0.80 in. w.g.

Damper Mixed Air

1050 SCFM

83.3 °F DB

68.3 °F WB

79.36 gr/lbm

Supply Air

1050 SCFM

83.3 °F DB

68.3 °F WB

79.36 gr/lbm

Energy Recovery

83.3 °F

68.3 °F

0.81 in. w.g.

Bypass: 0 SCFM Outside Air

1096 SCFM

95.0 °F DB

75.0 °F WB

98.46 gr/lbm

OACF: 1.04

Return Air

0 SCFM

75.0 °F DB

62.0 °F WB

62.11 gr/lbm

Exhaust Air

1096 SCFM

79.6 °F

65.1 °F

69.48 gr/lbm

EATR: 9.3%

From Space

2580 SCFM

Summer Conditions

Ex Bypass: 1530 SCFM

Frost Warning - Conditions for frost forming on the energy recovery exists. Outside air preheat is required to prevent frost formation. Optionally, the return air humidity ratio could be lowered to prevent frost formation. See AAON literature titled 'AAONAIRE ENERGY RECOVERY' for details.

Return Air

0 SCFM

70.0 °F DB

52.0 °F WB

28.94 gr/lbm

Exhaust Air

1100 SCFM

53.4 °F

43.0 °F

24.30 gr/lbm

EATR: 9.2%

Outside Air

1100 SCFM

0.0 °F DB

0.0 °F WB

5.49 gr/lbm

OACF: 1.05

Mixed Air

1050 SCFM

39.6 °F DB

32.9 °F WB

16.84 gr/lbm

Supply Air

1050 SCFM

39.6 °F DB

32.9 °F WB

16.84 gr/lbm

Damper Energy Recovery

39.6 °F

32.9 °F

0.81 in. w.g.

From Space

30.4 °F

27.7 °F

0.80 in. w.g.

2580 SCFM

Winter Conditions Bypass: 0 SCFM

Ex Bypass: 1530 SCFM

Summer Winter Total Capacity 23.2 MBH 47.5 MBH Sensible Capacity 11.2 MBH 40.3 MBH Latent Capacity 12.0 MBH 7.2 MBH

Summer Winter Total Effectiveness 51.1% 54.1% Sensible Effectiveness 55.7% 55.7% Latent Effectiveness 48.1% 46.3%

Summer Winter Enthalpy Recovery Ratio 55.3% 55.0% Sensible Energy Recovery Ratio 54.4% 52.5%

Energy Recovery Performance

DOAS_2A

RQA-004-A-A-3-G

A

B

A

A

A

A

A

A

-A

B

B

B

N

B

B

:0

-0

A

F

B

D

C

A

D

D

E

-Q

A

A

B

A

C

-0

A

B

C

D

E

-A

A

G

B

H

C

B

D

G

E

-E

C

-C

A

B

B

C

A

D

-0

A

B -E

A

B

-A

-A

A

N

B

C

-E

B

-N

A

B

C

D

-0

A

B

-0

A

B

C

-A

A

-C

B

-0

X

Application Rating is outside the scope of the AHRI ERV Certification Program but is rated in accordance with AHRI Standard 1060.

2425 South Yukon Ave • Tulsa, OK 74107 • Ph: (918) 583-2266 Ecat Price Version: 364.1

Unit Rating

Date Printed:5/13/2026 10:06:47 AMPage 3 Of 3

Readiness Center Job Tag DOAS_2A Date 5/13/2026 10:00:30 AM

Max RPM 2200 Diameter x Qty 18.5 in. x 1

CFM 1050

Inertia 3 WR²

OPERATING CONDITIONS MOTOR SELECTION

Airflow 1050 Fan Energy Index (FEI) 1.28 Static Pressure 2.46 in. w.g.

Relief Dampers DP 0.00 in. w.g.

TSP 2.46 in. w.g.

Site Altitude 0

Rated HP / Bypass 1 x 1 / No Frame Size 56 Nominal RPM 1760 VAC/PH/Hz 460V/3Ø/60Hz Enclosure Type ODP Max Inertial Load 0 WR²

FAN PERFORMANCE: FAN SOUND POWER (Inlet/Outlet)

RPM 1688

BHP 0.83

Efficiency 49.1% Max Duct SP with Blocked Airway

3.10 in. w.g. @ 1688 RPM

Octave Band: (Re 10^-12 watts) 1 2 3 4 5 6 7 8

83 81 84 81 75 73 71 65 83 81 84 81 75 73 71 65

SOUND POWER A-Weighted: 85 dB

2425 South Yukon Ave • Tulsa, OK 74107 • Ph: (918) 583-2266

Ecat Price Version: 364.1

18.5" STAR Plenum

Date Printed:5/13/2026 10:06:48 AM

2425 South Yukon Ave • Tulsa, OK 74107 • Ph: (918) 583-2266

Ecat Price Version: 364.1

15" STAR Plenum

JOB INFORMATION: WHEEL SPECIFICATION:

Job Name WV ANG Logan Mingo

Readiness Center Job Tag DOAS_2A Date 5/13/2026 10:00:30 AM

Max RPM 2600 Diameter x Qty 15 in. x 1

CFM 2580

Inertia 3 WR²

FAN PERFORMANCE FAN SOUND POWER (Inlet/Outlet)

RPM 2471

BHP 1.62

Efficiency 33.6% Max Duct SP with Blocked Airway

4.70 in. w.g. @ 2471 RPM

Octave Band: (Re 10^-12 watts) 1 2 3 4 5 6 7 8

85 85 86 87 82 78 76 71 85 85 86 87 82 78 76 71

SOUND POWER A-Weighted: 88 dB

OPERATING CONDITIONS MOTOR SELECTION

Airflow 2580 Fan Energy Index (FEI) 0.77 Static Pressure 1.34 in. w.g.

Relief Dampers DP 0.00 in. w.g.

TSP 1.34 in. w.g.

Site Altitude 0

Rated HP / Bypass 2 x 1 / No Frame Size 56 Nominal RPM 1760 VAC/PH/Hz 460V/3Ø/60Hz Enclosure Type ODP Max Inertial Load 0 WR²

B

A

A

A

A

A

A

-A

B

B

B

N

B

B

:0

-0

A

F

B

D

C

A

D

D

E

-Q

A

A

B

A

C

-0

A

B

C

D

E

-A

A

G

B

H

C

B

D

G

E

-E

C

-C

A

B

B

C

A

D

-0

A

B -E

A

B

-A

-A

A

N

B

C

-E

B

-N

A

B

C

D

-0

A

B

-0

A

B

C

-A

A

-C

B

-0

X

Unit Submittal 2425 South Yukon Ave • Tulsa, OK 74107 • Ph: (918) 583-2266

Ecat Price Version: 364.1

Tag:

Job Name: WV ANG Logan Mingo

Readiness Center Unit Worksheet For:

Job Number: 1 Unit Worksheet Date: 5/13/2026

DOAS_2A

Feature Option Description

0 F1. Unit Orientation Standard Access - Hinged Access Doors with Lockable Handles 0 F2. Supply & Return Locations Bottom Discharge and Return 0 F3A. Supply Fan Quantity 1 Fan F F3B. Supply Fan Configuration 1 Fan per VFD + Narrow Width Fan D F3C. Supply Fan Size 18.5" Direct Drive Backward Curved Aluminum A F3D. Supply Fan Motor Type High Efficiency Open Motor (1,800 nominal rpm) D F3E. Supply Fan Motor Size 1 HP Q F4A. Outside Air Section Economizer + Energy Recovery + Bypass Damper A F4B. Energy Recovery Type Polymer Energy Recovery Wheel A F4C. Energy Recovery Size Total + Low CFM 0 F5A. Return Fan Quantity 0 Return Fans 0 F5B. Return Fan Configuration No Return Fan 0 F5C. Return Fan Size No Return Fan 0 F5D. Return Fan Motor Type No Return Fan 0 F5E. Return Fan Motor Size No Return Fan A F6A. Exhaust Fan Quantity 1 Fan G F6B. Exhaust Fan Configuration 1 Fan per VFD + Narrow Width Fan H F6C. Exhaust Fan Size 15” Backward Curved Plenum B F6D. Exhaust Fan Motor Type High Efficiency Open Motor (1,800 nominal rpm) G F6E. Exhaust Fan Motor Size 2 HP E F7. Outside Air Control DDC Actuator C F8. Return and Exhaust Air Options Standard Barometric Relief EA Dampers C F9A. Unit Filter Type 4" Pleated - 85% Eff - MERV 13 + 2" Pleated - MERV 8 B F9B. Unit Filter Size & Location High Efficiency Filters in Standard Position 0 F9C. Final Filter Type No Final Filters A F9D. Filter Options Clogged Filter Switch - Unit Filters 0 F10A. Refrigeration Control A Standard - Fixed 55°F Comp. Cooling Lock Out

Base Option Description

RQ Generation RQ Series A Major Revision Major Revision A

004 Unit Size Four A Series A Series A Minor Revision Minor Revision A 3 Voltage 460V/3φ/60Hz G Compressor Style R-454B Variable Capacity Scroll Compressor B Condenser Style High Eff. Microchannel Air-Cooled Condenser A Indoor Coil Configuration Std Row Std Eff. Evaporator 0 Cooling Heat Exchanger Construction Standard A Cooling Staging Modulating A Heat Type Electric Heat 0 Heat Construction Standard 2 Heat Designation Heat 2 - 20 kW N Heat Staging Modulating SCR Electric with External 0-10 VDC 0 Heat Pump Auxiliary Heating No Auxiliary Heat

Date Created/Modified:5/13/2026 10:00:30 AM Using Performance Version:364.1 Date Printed:5/13/2026 10:06:49 AM

E F11A. Refrigeration Options A Modulating Hot Gas Reheat 0 F11B. Refrigeration Options B Standard Packaged Unit A F12. Refrigeration Accessories Sight Glass A F13A. Unit Disconnect Type Single Point Power - Non-fused Disconnect Power Switch N F13B. Disconnect 1 Size 100 Amps 0 F13C. Disconnect 2 Size Standard - None E F14. Safety Options Remote Safety Shutdown Terminals B F15. Electrical Accessories Phase & Brownout Protection N F16A. Control Sequence Field Installed DDC Controls by Others + Isolation Relays 0 F16B. Control Supplier None 0 F16C. Control Supplier Options None 0 F16D. BMS Connection & Diagnostics None 0 F17A. Preheat Configuration Standard - None 0 F17B. Preheat Sizing Standard - None 0 F18A. Option Box Location None 0 F18B. Option Box Size None 0 F18C. Option Box Accessories None A F19. Outside Air Accessories Outside Air Hood 0 F20. Cabinet Options Standard - None 0 F21. Accessories Standard A F22. Maintenance Accessories 115V Convenience Outlet Factory Wired 0 F23. Code Options Standard - ETL U.S.A. Listing 0 F24. Shipping Splits Standard C F25. Air-Cooled Condenser Accessories ECM Condenser Fan Head Pressure Control 0 F26. Evap-Cooled Condenser Accessories Standard 0 F27. Water-Cooled Condenser Accessories None 0 F28. Energy Recovery Accessories None 0 F29. VFD Options Standard B F30. Miscellaneous Options SCCR (10kA) 0 F31. Blank Standard 0 F32. Blank Standard 0 F33. Blank Standard 0 F34. Blank Standard 0 F35. Warranty Standard - 2 Year Parts Warranty 0 F36. Cabinet Material Galvanized Cabinet - Double Wall + R-16 Foam Insulation X F37. Specials & Paint SPA + Premium AAON Gray Paint Exterior Paint

Date Created/Modified:5/13/2026 10:00:30 AM Using Performance Version:364.1 Date Printed:5/13/2026 10:06:49 AM

B

A

A

A

A

A

A

-A

B

B

B

N

B

B

:0

-0

A

F

B

D

C

A

D

D

E

-Q

A

A

B

A

C

-0

A

B

C

D

E

-A

A

G

B

H

C

B

D

G

E

-E

C

-C

A

B

B

C

A

D

-0

A

B

-E

A

B

-A

-A

A

N

B

C

-E

B

-N

A

B

C

D

-0

A

B

-0

A

B

C

-A

A

-C

B

-0

X

Terminals 2425 South Yukon Ave • Tulsa, OK 74107 • Ph: (918) 583-2266

Ecat Price Version: 364.1

Tag:

Job Name: WV ANG Logan Mingo

Readiness Center For:

Job Number: 1 Date: May 13, 2026

DOAS_2A

Terminals Available/Required for Controlling the Unit Terminals Decription [C1] & [C2] Clogged Filter Switch

[R] 24VAC Control Voltage [C] Common [G] Supply Fan Enable + Isolation Relay [Y1] Cooling Stage 1 Enable + Isolation Relay

[DC1-] & [DC1+] Variable Capacity Compressor 1 (1.44-5VDC) Signal [SP1-] & [SP1+] Suction Pressure Sensor - Compressor 1 (0.5-4.5VDC)

[W1] Heating Stage 1 Enable + Isolation Relay [+] & [-] SCR Control Signal (0-10VDC)

[HW] Energy Recovery Wheel Enable + Isolation Relay [PE] Power Exhaust Enable + Isolation Relay

[B1-] & [B2+] Exhaust Fan ECM Motor Signal (0-10VDC) [EC1-] & [EC2+] Economizer Signal (2-10VDC)

[S1-] & [S2+] Supply Fan 1 - w/ 1 VFD: Signal (0-10VDC) VFD frequency reference signal control point must handle a rated 20k ohm input impedance.

[RH1] Reheat Enable + Isolation Relay Must enable and modulate the digital compressors during dehumidification mode.The control logic needs to set if cooling or dehumidification is priority.

[AI1] & [COM] Reheat Reset Signal (0-10VDC)

Resets the supply air setpoint [BI1] & [BI2] Remote Safety Shutdown

[PBO1] & [PBO2] Phase & Brown Out

Terminations Found on VFD(s) Exhaust Fan VFD

[AM] & [AC] Current Feedback (0-10VDC = 0-100%) [MA] & [MC] Fault Status (NC, 250VAC/30VDC, 1A)

Supply Fan VFD [16] & [17] Current Feedback (0-10VDC = 0-100%)

A2L Terminals [ALM1] & [ALM2] A2L Airstream Alarm & Cabinet Alarm

A2L Mitigation Board 1

P/N: ASM0763

A2L Mitigation Board 2

P/N: ASM0763

Date Printed:5/13/2026 10:06:49 AMDate Created/Modified:5/13/2026 10:00:30 AM Using Performance Version:364.1

RQ-00031 REV:E 02/15/23 JWC

NOTE: ALL DIMENSIONS ARE IN INCHES

FORMED UP

DETAIL A

DETAIL B

LOW VOLTAGE

HIGH VOLTAGE

ø13 ø2 1 ø13

RAISE MINIMUM 1

2" FOR THE

SUPPLY/RETURN AIR AND

ELEC ENTRY OPENINGS.

RQ CABINET

ENERGY RECOVERY SECTION POWER EXHAUST

ECONOMIZER VERTICAL ~ 1-6 TON

CLEARANCES

LOCATION • UNIT SIZE •

1 - 6 TON

HXC

(FRONT)

LEFT SIDE

BACK SIDE

TOP UNOBSTRUCTED

48*

OUTSIDE AIR

(RIGHT)

*CLEARANCE IS MEASURED

FROM THE END OF THE

OUTSIDE AIR RAIN HOOD

*HW DOOR SWING = 38.5"

FRONT VIEW

INSIDE BASE RAIL

OUTSIDE BASE RAIL

RIGHT SIDE VIEW

CONTROLS AND

COMPRESSOR

ACCESS

LIFTING LUG

(4 CORNERS)

ECON

FILTER

COIL

HEATWHEEL

SUPPLY

RE

TU

RN

SUPPLY BLOWER

ACCESS

COIL

LEFT SIDE VIEW

4 INCH MPT STAINLESS CONDENSATE

CONNECTION.

TOP VIEW

SEE DETAIL

"B"

C O

IL

FI

LT

ER

S

SEE DETAIL

"A"

OUTSIDE

AIR

EXHAUST

AIR

24 431

4 9 385

8 171

HEATER ACCESS

POWER

SWITCH

INSIDE BASE RAIL

OUTSIDE BASE RAIL

COMBUSTION AIR INLETS

(GAS HEAT ONLY)

FLUE OUTLET

(GAS HEAT ONLY)

ø11

GAS 141

2ENTRY

8 37

RQA-004-A-A-3-GBA0A-A02N0:00-0FDAD-QAA-00000-AGHBG-EC-CB0A-00-E0-A-AN0-EB-N000-00-000-A00A00-C0000B-000000X

RQ CABINET-VERTICAL

AIR COOLED CONDENSING UNIT

WITH ENERGY RECOVERY

Front Right Corner:

358 lbs

Back Left Corner:

303 lbs

Back Right Corner:

357 lbs

CGx: 57.9" CGy: 20.2"

1324 lbs

+X

+Y

Disclaimer:

This weight estimate does not account for any SPAs.

Front Left Corner:

305 lbs

0"

0"

116"

44"

C O

IL

FI

LT

ER

S

SUPPLY

RE

TU

RN

RNA-007-A-A-3-G

A

A

B

A

A

A

A

-C

B

B

B

B

L

B

B

:0

-0

A

F

B

C

C

A

D

F

E

-Q

A

H

B

A

C

-0

A

B

C

D

E

-A

A

B

B

H

C

B

D

E

E

-E

C

-C

A

B

B

C

A

D

-0

A

B

-E

A

B

-A

-A

A

N

B

C

-E

B

-N

A

B

C

D

-0

A

B

-0

A

B

C

-A

A

-C

B

-0

B

DOAS_1ATag:

Job Information Job Name: WV ANG Logan Mingo Readiness

Center Job Number: 1 Site Altitude: 0 ft Refrigerant: R-454B Design System Charge (oz): 475

Unit Information Approx. Op./Ship Weights: 1581 lbs / 1581 lbs (±5%) Ambient Temperature (DB/WB): 95.0 °F / 75.0 °F Coil Filter FV / Qty: 211.5 fpm / 4 Min. Room Area/Height/Airflow**: 446 ft² / 7 ft / 804 SCFM Exhaust Airflow/ESP/TSP: 1500 SCFM / 0.25 in. w.g. / 0.98 in. w.g.

Supply Airflow/ESP: 1880 SCFM / 0.75 in. w.g.

Outside Airflow: 1880 SCFM Return Airflow/ESP: 1500 SCFM / 0.25 in. w.g.

Return Temperature (DB/WB): 75.0 °F / 62.0 °F

Static Pressure External: 0.75 in. w.g.

Cooling Coil: 0.22 in. w.g.

Filters Clean: 0.13 in. w.g.

Dirt Allowance: 0.35 in. w.g.

Reheat Coil: 0.03 in. w.g.

Economizer: 0.13 in. w.g.

Heater: 0.02 in. w.g.

Cabinet: 0.06 in. w.g.

Energy Recovery: 1.15 in. w.g.

Total: 2.84 in. w.g.

Heating Section Preheat Type: Std (No Preheat)

Auxiliary Heating Type: Nat. Gas Heat Heating Airflow: 1880 SCFM Total Capacity: 121.5 MBH Entering Air Temp (DB/WB): 44.4 °F / 36.5 °F Leaving Air Temp (DB/WB): 103.9 °F / 62.6 °F Consumption: 150.0 MBH Total Turndown Ratio: 8.0:1

Cooling Section Gross Net

Equivalent Total Capacity: 132.7 MBH 128.5 MBH Total Capacity: 79.7 MBH 75.5 MBH Sensible Capacity: 58.1 MBH 53.9 MBH Latent Capacity: 21.5 MBH HW Total Cooling Capacity: 53.0 MBH

Supply Air Fan: 1 x RNA185D70 @ 1.43 BHP Ea.

SA Fan RPM / Width: 1737 RPM / 2.898 in SA Fan FEI: 1.30 Exhaust Air Fan: 1 x RM150-RN @ 0.39 BHP Ea.

EA Fan RPM / Width: 1249 RPM / 5.16 in EA Fan FEI: 1.60

Evaporator Coil: 8.5 ft² / 6 Rows / 14 FPI Evaporator Face Velocity: 221.0 fpm Energy Recovery: 1 x ERC-3017C-BW

Mixed Air Temp (DB/WB): 81.9 °F / 67.2 °F Entering Air Temp (DB/WB): 81.9 °F / 67.2 °F Lv Air Temp (Coil) (DB/WB): 52.9 °F / 52.8 °F Lv Air Temp (Unit) (DB/WB): 54.8 °F / 53.6 °F

Listing Model RN-007-3-0-GABY-V0-21-000-A

Cooling Capacity: 74.0 MBH Cooling EER: 12.15 BTU/h·W Cooling IEER: 14.8 BTU/h·W

Rating Information

*Rated in accordance with AHRI Standard 340/360 (I-P)

Application EER @ Op. Conditions: 17.2 BTU/h·W

Re-heat Coil:

Capacity: 38.3 MBH Leaving Air Temp (DB/WB): 72.0 °F / 60.3 °F Relative Humidity: 50.7%

Electrical Data

2425 South Yukon Ave • Tulsa, OK 74107 • Ph: (918) 583-2266 Ecat Price Version: 364.1

Unit Rating

Date Printed:5/13/2026 10:06:05 AMPage 1 Of 3

Unit FLA:

Minimum Circuit Amp:

Maximum Overcurrent:

Qty HP VAC Phase RPM FLA RLA Compressor 1: 1 460 3 3500 10.9 Condenser Fan: 1 0.33 460 1 1100 1.6 Supply Fan: 1 2 460 3 1760 3.4 Exhaust Fan: 1 1 460 3 1760 2.1 Combustion: 1 0.1 460 1 3000 0.3 Energy Recovery: 1 0.13 460 3 1075 0.4

460V/3Ø/60Hz

SCCR: 10 KAIC

Cabinet Sound Power Levels* Octave Bands: 63 125 250 500 1000 2000 4000 8000 Discharge LW (dB): 84 82 85 81 73 70 68 62 Return LW (dB): 77 76 74 67 63 61 57 53 *Sound data is generated by a propriety acoustics model validated through unit testing in accordance with AHRI 260, utilizing tested fan sound data in accordance with AMCA 300.

**The minimum floor area is based on the Lower Flammability Limit (LFL) and calculated in accordance with UL60335-2-40 4th ed. (operating or storage). For UL60335-2-40 3rd ed. double the airflow and minimum floor area listed.

The minimum airflow (Qmin) is the minimum allowable airflow for any operating condition.

2425 South Yukon Ave • Tulsa, OK 74107 • Ph: (918) 583-2266 Ecat Price Version: 364.1

Unit Rating

Date Printed:5/13/2026 10:06:05 AMPage 2 Of 3

Readiness Center

Energy Recovery Type: Total

Job Number: 1 Energy Recovery Model: ERC-3017C-BW Site Altitude: 0 Energy Recovery Qty: 1 Net Supply Airflow Sum/Win: 1804 SCFM / 1802 SCFM Energy Recovery Software Ver: 2.4.1 Purge Angle: 10.0°

Tag:

91.3 °F

72.5 °F

0.68 in. w.g.

Damper Mixed Air

1880 SCFM

81.9 °F DB

67.2 °F WB

76.37 gr/lbm

Supply Air

1880 SCFM

81.9 °F DB

67.2 °F WB

76.37 gr/lbm

Energy Recovery

81.9 °F

67.2 °F

0.99 in. w.g.

Bypass: 0 SCFM Outside Air

1882 SCFM

95.0 °F DB

75.0 °F WB

98.46 gr/lbm

OACF: 1.00

Return Air

0 SCFM

75.0 °F DB

62.0 °F WB

62.11 gr/lbm

Exhaust Air

1502 SCFM

91.3 °F

72.5 °F

89.43 gr/lbm

EATR: 4.1%

From Space

1500 SCFM

Summer Conditions

Ex Bypass: 0 SCFM

Frost Warning - Conditions for frost forming on the energy recovery exists. Outside air preheat is required to prevent frost formation. Optionally, the return air humidity ratio could be lowered to prevent frost formation. See AAON literature titled 'AAONAIRE ENERGY RECOVERY' for details.

Return Air

0 SCFM

70.0 °F DB

52.0 °F WB

28.94 gr/lbm

Exhaust Air

1503 SCFM

12.5 °F

12.5 °F

10.32 gr/lbm

EATR: 4.2%

Outside Air

1883 SCFM

0.0 °F DB

0.0 °F WB

5.49 gr/lbm

OACF: 1.00

Mixed Air

1880 SCFM

44.4 °F DB

36.5 °F WB

19.17 gr/lbm

Supply Air

1880 SCFM

44.4 °F DB

36.5 °F WB

19.17 gr/lbm

Damper Energy Recovery

44.4 °F

36.5 °F

0.99 in. w.g.

From Space

12.5 °F

12.5 °F

0.68 in. w.g.

1500 SCFM

Winter Conditions Bypass: 0 SCFM

Ex Bypass: 0 SCFM

Summer Winter Total Capacity 53.0 MBH 106.0 MBH Sensible Capacity 25.0 MBH 88.5 MBH Latent Capacity 28.0 MBH 17.6 MBH

Summer Winter Total Effectiveness 77.1% 80.3% Sensible Effectiveness 81.5% 81.5% Latent Effectiveness 74.1% 74.6%

Summer Winter Enthalpy Recovery Ratio 63.2% 62.4% Sensible Energy Recovery Ratio 64.3% 61.9%

Energy Recovery Performance

DOAS_1A

RNA-007-A-A-3-G

A

A

A

B

A

A

A

A

-C

B

B

B

B

L

B

B

:0

-0

A

F

B

C

C

A

D

F

E

-Q

A

H

B

A

C

-0

A

B

C

D

E

-A

A

B

B

H

C

B

D

E

E

-E

C

-C

A

B

B

C

A

D

-0

A

B -E

A

B

-A

-A

A

N

B

C

-E

B

-N

A

B

C

D

-0

A

B

-0

A

B

C

-A

A

-C

B

-0

B

Application Rating is outside the scope of the AHRI ERV Certification Program but is rated in accordance with AHRI Standard 1060.

2425 South Yukon Ave • Tulsa, OK 74107 • Ph: (918) 583-2266 Ecat Price Version: 364.1

Unit Rating

Date Printed:5/13/2026 10:06:06 AMPage 3 Of 3

Readiness Center Job Tag DOAS_1A Date 5/13/2026 10:00:30 AM

Max RPM 2200 Diameter x Qty 18.5 in. x 1

CFM 1880

Inertia 3 WR²

OPERATING CONDITIONS MOTOR SELECTION

Airflow 1880 Fan Energy Index (FEI) 1.30 Static Pressure 2.84 in. w.g.

Relief Dampers DP 0.00 in. w.g.

TSP 2.84 in. w.g.

Site Altitude 0

Rated HP / Bypass 2 x 1 / No Frame Size 145T Nominal RPM 1760 VAC/PH/Hz 460V/3Ø/60Hz Enclosure Type ODP Max Inertial Load 0 WR²

FAN PERFORMANCE: FAN SOUND POWER (Inlet/Outlet)

RPM 1737

BHP 1.43

Efficiency 58.9% Max Duct SP with Blocked Airway

3.30 in. w.g. @ 1737 RPM

Octave Band: (Re 10^-12 watts) 1 2 3 4 5 6 7 8

84 82 85 83 76 74 72 66 84 82 85 83 76 74 72 66

SOUND POWER A-Weighted: 85 dB

2425 South Yukon Ave • Tulsa, OK 74107 • Ph: (918) 583-2266

Ecat Price Version: 364.1

18.5" STAR Plenum

Date Printed:5/13/2026 10:06:06 AM

Ecat Price Version: 364.1

15" STAR Plenum

JOB INFORMATION: WHEEL SPECIFICATION:

Job Name WV ANG Logan Mingo

Readiness Center Job Tag DOAS_1A Date 5/13/2026 10:00:30 AM

Max RPM 2064 Diameter x Qty 15 in. x 1

CFM 1500

Inertia 3 WR²

FAN PERFORMANCE FAN SOUND POWER (Inlet/Outlet)

RPM 1249

BHP 0.39

Efficiency 59.4% Max Duct SP with Blocked Airway

1.10 in. w.g. @ 1249 RPM

Octave Band: (Re 10^-12 watts) 1 2 3 4 5 6 7 8

75 74 75 70 65 64 60 56 75 74 75 70 65 64 60 56

SOUND POWER A-Weighted: 76 dB

OPERATING CONDITIONS MOTOR SELECTION

Airflow 1500 Fan Energy Index (FEI) 1.60 Static Pressure 0.98 in. w.g.

Relief Dampers DP 0.00 in. w.g.

TSP 0.98 in. w.g.

Site Altitude 0

Rated HP / Bypass 1 x 1 / No Frame Size 143T Nominal RPM 1760 VAC/PH/Hz 460V/3Ø/60Hz

A

A

B

A

A

A

A

-C

B

B

B

B

L

B

B

:0

-0

A

F

B

C

C

A

D

F

E

-Q

A

H

B

A

C

-0

A

B

C

D

E

-A

A

B

B

H

C

B

D

E

E

-E

C

-C

A

B

B

C

A

D

-0

A

B -E

A

B

-A

-A

A

N

B

C

-E

B

-N

A

B

C

D

-0

A

B

-0

A

B

C

-A

A

-C

B

-0

B

Unit Submittal 2425 South Yukon Ave • Tulsa, OK 74107 • Ph: (918) 583-2266

Ecat Price Version: 364.1

Tag:

Job Name: WV ANG Logan Mingo

Readiness Center Unit Worksheet For:

Job Number: 1 Unit Worksheet Date: 5/13/2026

DOAS_1A

Feature Option Description

0 F1. Unit Orientation Standard Access - Hinged Access Doors with Lockable Handles 0 F2. Supply & Return Locations Bottom Supply--Bottom Return 0 F3A. Supply Fan Quantity 1 Fan F F3B. Supply Fan Configuration 1 Fan per VFD + Narrow Width Fan C F3C. Supply Fan Size 18.5" Direct Drive Backward Curved Aluminum A F3D. Supply Fan Motor Type High Efficiency Open Motor (1,800 nominal rpm) F F3E. Supply Fan Motor Size 2 hp Q F4A. Outside Air Section Economizer + Energy Recovery + Bypass Damper H F4B. Energy Recovery Type High Eff. Polymer Energy Recovery Wheel + 1% Purge A F4C. Energy Recovery Size Low CFM Enthalpy 0 F5A. Return Fan Quantity 0 Return Fans 0 F5B. Return Fan Configuration No Return Fan 0 F5C. Return Fan Size No Return Fan 0 F5D. Return Fan Motor Type No Return Fan 0 F5E. Return Fan Motor Size No Return Fan A F6A. Exhaust Fan Quantity 1 Fan B F6B. Exhaust Fan Configuration 1 Fan per VFD + Full Width Fan H F6C. Exhaust Fan Size 15" Backward Curved Aluminum B F6D. Exhaust Fan Motor Type High Efficiency Open Motor (1,800 nominal rpm) E F6E. Exhaust Fan Motor Size 1 hp E F7. Outside Air Control DDC Actuator C F8. Return and Exhaust Air Options Standard Barometric Relief EA Dampers C F9A. Unit Filter Type 2" Pleated MERV 8 + 4" Pleated MERV 13 B F9B. Unit Filter Size & Location High Efficiency Filters in Standard Position 0 F9C. Final Filter Type No Final Filters A F9D. Filter Options Clogged Filter Switch - Unit Filters 0 F10A. Refrigeration Control A Standard - Fixed 55°F Comp. Cooling Lock Out

Base Option Description

RN Generation RN Series A Major Revision Major Revision A

007 Unit Size Seven A Series A Series A Minor Revision Minor Revision A 3 Voltage 460V/3φ/60Hz G Compressor Style R-454B Variable Capacity Scroll Compressor A Condenser Style Microchannel Air-Cooled Condenser B Indoor Coil Configuration 6 Row Evaporator 0 Cooling Heat Exchanger Construction Standard A Cooling Staging 1 Variable Capacity Comp C Heat Type Natural Gas (Vertical Unit Configuration) B Heat Construction Stainless Steel Heat Exchanger, Gas Piping to the Valve 2 Heat Designation 150 MBH L Heat Staging High Turndown Modulating Gas Heat - Temperature Control 0 Heat Pump Auxiliary Heating No Auxiliary Heat

Date Created/Modified:5/13/2026 10:00:30 AM Using Performance Version:364.1 Date Printed:5/13/2026 10:06:07 AM

E F11A. Refrigeration Options A Modulating Hot Gas Reheat Microchannel Coil [MHGR-MC] 0 F11B. Refrigeration Options B Standard Packaged Unit A F12. Refrigeration Accessories Sight Glass A F13A. Unit Disconnect Type Single Point Power - Non-fused Disconnect Power Switch N F13B. Disconnect 1 Size 100 Amps 0 F13C. Disconnect 2 Size Standard - None E F14. Safety Options Remote Safety Shutdown Terminals B F15. Electrical Accessories Phase & Brown Out Protection N F16A. Control Sequence Field Installed DDC Controls + Isolation Relays 0 F16B. Control Supplier None 0 F16C. Control Supplier Options None 0 F16D. BMS Connection & Diagnostics None 0 F17A. Preheat Configuration Standard - None 0 F17B. Preheat Sizing Standard - None 0 F18A. Option Box Location None 0 F18B. Option Box Size None 0 F18C. Option Box Accessories None A F19. Outside Air Accessories Outside Air Hood 0 F20. Cabinet Options Standard - None 0 F21. Accessories Standard A F22. Maintenance Accessories Factory Wired 115V Convenience Outlet 0 F23. Code Options Standard - ETL U.S.A. Listing 0 F24. Shipping Splits Standard C F25. Air-Cooled Condenser Accessories ECM Condenser Fan Head Pressure Control 0 F26. Evap-Cooled Condenser Accessories Standard 0 F27. Water-Cooled Condenser Accessories None 0 F28. Energy Recovery Accessories None 0 F29. VFD Options Standard B F30. Miscellaneous Options SCCR (10kA) 0 F31. Blank Standard 0 F32. Blank Standard 0 F33. Blank Standard 0 F34. Blank Standard 0 F35. Warranty Standard Warranty 0 F36. Cabinet Material Galvanized Cabinet - Double Wall + R-16 Foam Insulation B F37. Specials & Paint Premium AAON Gray Paint Exterior Paint

Date Created/Modified:5/13/2026 10:00:30 AM Using Performance Version:364.1 Date Printed:5/13/2026 10:06:07 AM

A

A

B

A

A

A

A

-C

B

B

B

B

L

B

B

:0

-0

A

F

B

C

C

A

D

F

E

-Q

A

H

B

A

C

-0

A

B

C

D

E

-A

A

B

B

H

C

B

D

E

E

-E

C

-C

A

B

B

C

A

D

-0

A

B

-E

A

B

-A

-A

A

N

B

C

-E

B

-N

A

B

C

D

-0

A

B

-0

A

B

C

-A

A

-C

B

-0

B

Terminals 2425 South Yukon Ave • Tulsa, OK 74107 • Ph: (918) 583-2266

Ecat Price Version: 364.1

Date Printed:5/13/2026 10:06:07 AMDate Created/Modified:5/13/2026 10:00:30 AM Using Performance Version:364.1

Tag:

Readiness Center For:

Job Number: 1 Date: May 13, 2026

DOAS_1A

Terminals Available/Required for Controlling the Unit Terminals Decription

[R] 24VAC Control Voltage [C] Common [G] Supply Fan Enable + Isolation Relay [Y1] Cooling Stage 1 Enable + Isolation Relay

[DC1-] & [DC1+] Variable Capacity Compressor 1 (1.44-5VDC) Signal [SP1-] & [SP1+] Suction Pressure Sensor - Compressor 1 (0-5VDC)

[W1] Heating Stage 1 Enable + Isolation Relay [+] & [-] Gas Heat Reset Signal (0-10VDC)

Resets the supply air setpoint [Q1] & [Q2] Gas Heat Alarm

Dry contact terminals for alarm output (NC) [HW] Energy Recovery Wheel Enable + Isolation Relay [PE] Power Exhaust Enable + Isolation Relay

[B1-] & [B2+] Exhaust Fan 1 - w/ 1 VFD: Signal (0-10VDC) VFD frequency reference signal control point must handle a rated 20k ohm input impedance.

[S1-] & [S2+] Supply Fan 1 - w/ 1 VFD: Signal (0-10VDC) VFD frequency reference signal control point must handle a rated 20k ohm input impedance.

[EC1-] & [EC2+] Economizer Signal (0-10VDC) [C1] & [C2] Clogged Filter Switch (Standard Filters)

[RH1] Reheat Enable + Isolation Relay Must enable and modulate the digital compressors during dehumidification mode.The control logic needs to set if cooling or dehumidification is priority.

[AI1] & [COM] Reheat Reset Signal (0-10VDC)

Resets the Reheat Supply Air Temp Setpoint [BI1] & [BI2] Remote Safety Shutdown

[PBO1] & [PBO2] Phase & Brown Out

Terminations Found on VFD(s) Exhaust Fan VFD(s)

[AM] & [AC] Current Feedback (0-10VDC = 0-100%) [AM] & [AC] Current Feedback (0-10VDC = 0-100%)

Supply Fan VFD(s) [MA] & [MC] Fault [MA] & [MC] Fault

A2L Terminals [ALM1] & [ALM2] A2L Airstream Alarm & Cabinet Alarm

A2L Mitigation Board 1

P/N: ASM0763

A2L Mitigation Board 2

P/N: ASM0763

Date Printed:5/13/2026 10:06:07 AMDate Created/Modified:5/13/2026 10:00:30 AM Using Performance Version:364.1

FORMED UP

RAISE MINIMUM FOR THE

RETURN AIR AND ELEC

ENTRY OPENINGS.

HIGH VOLT

ENTRY

LOW VOLT

ENTRY

DETAIL A DETAIL B

DETAIL C

RAISE MINIMUM FOR THE

SUPPLY AIR OPENING

FORMED UP

3"

1 3"

1 1"

1"

1"

SEE DETAIL

"B"

EXHAUST AIR

SEE DETAIL

"C"

TOP VIEW

RNA-00027 REV:C 02/20/23 JWC

NOTE: ALL DIMENSIONS ARE IN INCHES

4 175

BLOWER

ACCESS

HEATWHEEL

RIGHT SIDE VIEW

SEE DETAIL

"B"

SEE DETAIL

"A"

SUPPLY

EXHAUST AIR

SEE DETAIL

"C"

O U

TS

ID

E A

IR

H

O O

D

35 1

8 1

RETURN

1" MPT STAINLESS CONDENSATE

CONNECTION.

HEATWHEEL

ACCESS

HEATWHEEL

FILTER

C O

IL

COMPRESSOR

ACCESS

12 3 4 247

8 27 13

BLOWER

SUPPLY COIL

COIL

ACCESS

FILTER ECON

HEATWHEEL

ACCESS

FILTER

ACCESS

RN SERIES A - CABINET

~ ECONOMIZER, ENERGY RECOVERY SECTION

AND POWER EXHAUST

~ 6-10 TON

OUTSIDE AIR

AIR

FLOW

2 RETURNSUPPLY

NOTE: THE RNA UNIT IS NOT COMPATIBLE

WITH PREVIOUS GENERATIONS OF AAON

CURBS. AN ADAPTER CURB IS

AVAILABLE IN ECAT.

CLEARANCES

LOCATION

OUTSIDE AIR

• UNIT SIZE •

6 - 10 TON

36*(BACK)

CONTROLS SIDE

(FRONT)

LEFT SIDE

RIGHT SIDE

TOP UNOBSTRUCTED

*CLEARANCE IS MEASURED FROM

THE END OF THE OUTSIDE AIR

RAIN HOOD

FRONT VIEW

INSIDE

BASE RAILS

ø11

GAS ENTRY

CONTROLS AND HEATER

ACCESS

POWER SWITCH

ACCESS COVER

CONTROLS AND HEATER

ACCESS

POWER SWITCH

ACCESS COVER

OUTSIDE

BASE RAILS

COMBUSTION AIR INLETS

(GAS HEAT ONLY)

CONDENSER

CONDENSER

FLUE OUTLET

(GAS HEAT ONLY)

COIL

COIL ACCESS

RN SERIES A - CABINET

6-10 TON

90/150/210 MBH

4 STAGE, HIGH TURNDOWN

Field gas piping is required to the internal gas valves.

Piping should be installed adhering to building codes.

Perform leak check prior to operation.

Reference IOM for additonal information, and details on optional gas entry through base.

REMOVABLE

KICKPLATE

HEAT

EXCHANGER 1

HXC 1

CAT000424 RNA REV A 04/25/23 JAS

ALL DIMENSIONS ARE IN INCHES

SIDE FRONT

TOP

3 5/8

5 3/161 5/8

5 7/8

Front Right Corner:

345 lbs

Back Left Corner:

424 lbs

Back Right Corner:

270 lbs

RNA-007-A-A-3-GAB0A-CB2L0:00-0FCAF-QHA-00000-ABHBE-EC-CB0A-00-E0-A-AN0-EB-N000-00-000-A00A00-C0000B-000000B

CGx: 51.1" CGy: 26.9"

1581 lbs

+X

+Y

Disclaimer:

This weight estimate does not account for any SPAs.

Front Left Corner:

541 lbs

RNA CABINET

AIR COOLED CONDENSING UNIT

WITH ENERGY RECOVERY SECTION

0"

0" 116"

44"

SUPPLY

O U

TS

ID

E A

IR

H

O O

D

RETURN

C

O

IL

RNA-015-B-A-3-G

A

A

A

A

A

A

A

-C

B

B

B

B

L

B

B

:0

-0

A

F

B

E

C

A

D

H

E

-G

A

B

C

-0

A

B

C

D

E

-A

A

B

B

G

C

B

D

H

E

-E

C

-C

A

B

B

C

A

D

-0

A

B

-E

A

B

-A

-A

A

N

B

C

-E

B

-N

A

B

C

D

-0

A

B

-0

A

B

C

-A

A

-C

B

-0

B

ACU_3ATag:

Job Information Job Name: WV ANG Logan Mingo Readiness

Center Job Number: 1 Site Altitude: 0 ft Refrigerant: R-454B Design System Charge (oz): 191 / 350

Unit Information Approx. Op./Ship Weights: 2198 lbs / 2198 lbs (±5%) Ambient Temperature (DB/WB): 95.0 °F / 75.0 °F Coil Filter FV / Qty: 378.0 fpm / 4 Min. Room Area/Height/Airflow**: 329 ft² / 7 ft / 592 SCFM Exhaust Airflow/ESP/TSP: 5250 SCFM / 0.25 in. w.g. / 0.71 in. w.g.

Supply Airflow/ESP: 5250 SCFM / 0.75 in. w.g.

Outside Airflow: 1115 SCFM Return Airflow/ESP: 5250 SCFM / 0.25 in. w.g.

Return Temperature (DB/WB): 75.0 °F / 62.0 °F

Static Pressure External: 0.75 in. w.g.

Cooling Coil: 0.35 in. w.g.

Filters Clean: 0.34 in. w.g.

Dirt Allowance: 0.35 in. w.g.

Reheat Coil: 0.07 in. w.g.

Economizer: 0.33 in. w.g.

Heater: 0.18 in. w.g.

Cabinet: 0.35 in. w.g.

Total: 2.71 in. w.g.

Heating Section Preheat Type: Std (No Preheat)

Auxiliary Heating Type: Nat. Gas Heat Heating Airflow: 5250 SCFM Total Capacity: 315.9 MBH Entering Air Temp (DB/WB): 55.1 °F / 43.7 °F Leaving Air Temp (DB/WB): 110.5 °F / 65.9 °F Consumption: 390.0 MBH Total Turndown Ratio: 10.0:1

Cooling Section Gross Net

Total Capacity: 186.2 MBH 175.6 MBH Sensible Capacity: 145.0 MBH 134.4 MBH Latent Capacity: 41.2 MBH

Supply Air Fan: 1 x 220D70 @ 3.71 BHP Ea.

SA Fan RPM / Width: 1767 RPM / 3.45 in SA Fan FEI: 1.18 Exhaust Air Fan: 1 x RM12X9X2-RN @ 2.46 BHP Ea.

EA Fan RPM / Width: 1063 RPM / EA Fan FEI: 0.62

Evaporator Coil: 14.6 ft² / 4 Rows / 14 FPI Evaporator Face Velocity: 360.0 fpm

Mixed Air Temp (DB/WB): 79.2 °F / 65.1 °F Entering Air Temp (DB/WB): 79.2 °F / 65.1 °F Lv Air Temp (Coil) (DB/WB): 53.5 °F / 52.8 °F Lv Air Temp (Unit) (DB/WB): 55.3 °F / 53.5 °F

Listing Model RN-015-3-0-GAAY-V0-21-000-A

Cooling Capacity: 166.0 MBH Cooling EER: 10.9 BTU/h·W Cooling IEER: 14.99 BTU/h·W

Rating Information

*Rated in accordance with AHRI Standard 340/360 (I-P)

Application EER @ Op. Conditions: 8.8 BTU/h·W

Re-heat Coil:

Capacity: 104.0 MBH Leaving Air Temp (DB/WB): 72.0 °F / 60.0 °F Relative Humidity: 49.8%

Electrical Data

2425 South Yukon Ave • Tulsa, OK 74107 • Ph: (918) 583-2266 Ecat Price Version: 364.1

Unit Rating

Date Printed:5/13/2026 10:04:53 AMPage 1 Of 2

Unit FLA:

Minimum Circuit Amp:

Maximum Overcurrent:

Qty HP VAC Phase RPM FLA RLA Compressor 1: 1 460 3 3500 12.8 Compressor 2: 1 460 3 3500 11.0 Condenser Fan: 2 1 460 1 1100 3.6 Supply Fan: 1 5 460 3 1760 7.6 Exhaust Fan: 1 3 460 3 1760 4.8 Combustion: 1 0.1 460 1 3000 0.3

460V/3Ø/60Hz

SCCR: 10 KAIC

Cabinet Sound Power Levels* Octave Bands: 63 125 250 500 1000 2000 4000 8000 Discharge LW (dB): 94 92 96 89 81 79 76 70 Return LW (dB): 90 86 86 76 73 68 59 52 *Sound data is generated by a propriety acoustics model validated through unit testing in accordance with AHRI 260, utilizing tested fan sound data in accordance with AMCA 300.

**The minimum floor area is based on the Lower Flammability Limit (LFL) and calculated in accordance with UL60335-2-40 4th ed. (operating or storage). For UL60335-2-40 3rd ed. double the airflow and minimum floor area listed.

The minimum airflow (Qmin) is the minimum allowable airflow for any operating condition.

2425 South Yukon Ave • Tulsa, OK 74107 • Ph: (918) 583-2266 Ecat Price Version: 364.1

Unit Rating

Date Printed:5/13/2026 10:04:53 AMPage 2 Of 2

Readiness Center Job Tag ACU_3A Date 5/13/2026 10:00:30 AM

Max RPM 2200 Diameter x Qty 22 in. x 1

CFM 5250

Inertia 5 WR²

OPERATING CONDITIONS MOTOR SELECTION

Airflow 5250 Fan Energy Index (FEI) 1.18 Static Pressure 2.71 in. w.g.

Relief Dampers DP 0.00 in. w.g.

TSP 2.71 in. w.g.

Site Altitude 0

Rated HP / Bypass 5 x 1 / No Frame Size 184T Nominal RPM 1760 VAC/PH/Hz 460V/3Ø/60Hz Enclosure Type ODP Max Inertial Load 0 WR²

FAN PERFORMANCE: FAN SOUND POWER (Inlet/Outlet)

RPM 1767

BHP 3.71

Efficiency 60.5% Max Duct SP with Blocked Airway

4.70 in. w.g. @ 1767 RPM

Octave Band: (Re 10^-12 watts) 1 2 3 4 5 6 7 8

93 91 96 90 84 82 80 74 93 91 96 90 84 82 80 74

SOUND POWER A-Weighted: 95 dB

2425 South Yukon Ave • Tulsa, OK 74107 • Ph: (918) 583-2266

Ecat Price Version: 364.1

22" STAR Plenum

Date Printed:5/13/2026 10:04:54 AM

Ecat Price Version: 364.1

RM12X9X2 FC Fan

JOB INFORMATION: WHEEL SPECIFICATION:

Job Name WV ANG Logan Mingo

Readiness Center Job Tag ACU_3A Date 5/13/2026 10:00:30 AM

Max RPM 1440 Diameter x Qty 11 in. x 1

CFM 5250

Inertia 3 WR²

FAN PERFORMANCE FAN SOUND POWER (Inlet/Outlet)

RPM 1063

BHP 2.46

Efficiency 23.9% Max Duct SP with Blocked Airway

1.30 in. w.g. @ 1063 RPM

Octave Band: (Re 10^-12 watts) 1 2 3 4 5 6 7 8

88 84 75 72 70 64 59 54 88 84 75 72 70 64 59 54

SOUND POWER A-Weighted: 88 dB

OPERATING CONDITIONS MOTOR SELECTION

Airflow 5250 Fan Energy Index (FEI) 0.62 Static Pressure 0.71 in. w.g.

Relief Dampers DP 0.00 in. w.g.

TSP 0.71 in. w.g.

Site Altitude 0

Rated HP / Bypass 3 x 1 / No Frame Size 182T Nominal RPM 1760 VAC/PH/Hz 460V/3Ø/60Hz

A

A

A

A

A

A

A

-C

B

B

B

B

L

B

B

:0

-0

A

F

B

E

C

A

D

H

E

-G

A

B

C

-0

A

B

C

D

E

-A

A

B

B

G

C

B

D

H

E

-E

C

-C

A

B

B

C

A

D

-0

A

B -E

A

B

-A

-A

A

N

B

C

-E

B

-N

A

B

C

D

-0

A

B

-0

A

B

C

-A

A

-C

B

-0

B

Unit Submittal 2425 South Yukon Ave • Tulsa, OK 74107 • Ph: (918) 583-2266

Ecat Price Version: 364.1

Tag:

Job Name: WV ANG Logan Mingo

Readiness Center Unit Worksheet For:

Job Number: 1 Unit Worksheet Date: 5/13/2026

ACU_3A

Feature Option Description

0 F1. Unit Orientation Standard Access - Hinged Access Doors with Lockable Handles 0 F2. Supply & Return Locations Bottom Supply--Bottom Return 0 F3A. Supply Fan Quantity 1 Fan F F3B. Supply Fan Configuration 1 Fan per VFD + Narrow Width Fan E F3C. Supply Fan Size 22" Direct Drive Backward Curved Aluminum A F3D. Supply Fan Motor Type High Efficiency Open Motor (1,800 nominal rpm) H F3E. Supply Fan Motor Size 5 hp G F4A. Outside Air Section Economizer + Power Exhaust 0 F4B. Energy Recovery Type No Energy Recovery 0 F4C. Energy Recovery Size No Energy Recovery 0 F5A. Return Fan Quantity 0 Return Fans 0 F5B. Return Fan Configuration No Return Fan 0 F5C. Return Fan Size No Return Fan 0 F5D. Return Fan Motor Type No Return Fan 0 F5E. Return Fan Motor Size No Return Fan A F6A. Exhaust Fan Quantity 1 Fan B F6B. Exhaust Fan Configuration 1 Fan per VFD + Full Width Fan G F6C. Exhaust Fan Size 12x9 Forward Curved B F6D. Exhaust Fan Motor Type High Efficiency Open Motor (1,800 nominal rpm) H F6E. Exhaust Fan Motor Size 3 hp E F7. Outside Air Control DDC Actuator C F8. Return and Exhaust Air Options Standard Barometric Relief EA Dampers C F9A. Unit Filter Type 2" Pleated MERV 8 + 4" Pleated MERV 13 B F9B.