Exhibit D WVANG Logan Mingo - ACU-1A Selection.pdf
PDF 9 MB Posted
- Attached to
- Logan/ Mingo AFRC HVAC System Replacement
- Solicitation number
- CRFQ 0603 ADJ2700000014 2
- Issued by
- Kanawha County, West Virginia
About this file
This document is an exhibit from the West Virginia Air National Guard (WVANG) related to HVAC system replacement at the Logan/Mingo Armed Forces Reserve Center (AFRC). The exhibit presents the Atmospheric Control Unit-1A (ACU-1A) selection criteria and evaluation framework for the competitive bidding process. The project encompasses the replacement of the existing HVAC system at the facility, with bidders required to submit proposals meeting specified technical and performance standards for the ACU-1A unit. The document establishes the selection methodology and scoring criteria that will be used to evaluate competing bids, ensuring that proposals are assessed consistently against predetermined benchmarks for equipment quality, installation capability, warranty provisions, and overall project delivery.
The exhibit details the evaluation metrics and weightings that the selection committee will apply during the bid review process, with emphasis on technical specifications, vendor qualifications, and cost-effectiveness. The selection framework is designed to identify the most qualified contractor capable of delivering the HVAC system replacement while maintaining compliance with West Virginia Air National Guard requirements and facility specifications. This competitive process ensures fair evaluation of all submitted proposals and provides transparency in the award selection methodology for the Logan/Mingo AFRC facility improvement project.
View the file
Other files
Show all 15
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Project: WV ANG Logan Mingo ARC
Tag Brand Model # SN# Weight Voltage Phase MCA (amps) MOCP (amps) Brand Model # Weight MCA (amps) MOCP (amps) ACU-1A Trane YHC037 144912456L 927 460 3 11.4 15 kitchen AAON RQA-004 1,025 13 20 ACU-2A Trane YHD180 144711191D 2,646 460 3 36 45 Hallway AAON RNA-015 2,198 47 50 ACU-3A Trane YHD180 144711095D 2,646 460 3 36 45 Drill Hall AAON RNA-015 2,198 47 50 ACU-1B Trane YHC092 144910217L 1,491 460 3 19.9 25 Locker Room AAON RNA-009 1725 22 25 ACU-2B Trane YHC067 144912518L 1,159 460 3 15.2 20 Supply Room AAON RNA-006 1,164 15 20
DOAS-1A Valent VPRE-110-5F-20J-C-1DA 13921734 1,900 460 3 20 25 Classrooms AAON RNA-007 1,581 21 30 DOAS-2A Valent VPRP-110-5C-20E-C-1DC 13921735 2,560 460 3 37 40 Locker Room AAON RQA-004 1,324 37 40
NewExisting
Exhibit "D - CRFQ ADJ27*14
RQA-004-A-A-3-G
A
B
A
A
A
A
A
A
-C
B
B
B
B
L
B
B
:0
-0
A
F
B
D
C
A
D
D
E
-E
A
B
C
-0
A
B
C
D
E
-0
A
B
C
D
E
-E
C
-C
A
B
B
C
A
D
-0
A
B
-E
A
B
-A
-A
A
N
B
C
-E
B
-N
A
B
C
D
-0
A
B
-0
A
B
C
-A
A
-C
B
-0
B
ACU_1ATag:
Job Information Job Name: WV ANG Logan Mingo Readiness
Center Job Number: 1 Site Altitude: 0 ft Refrigerant: R-454B Design System Charge (oz): 229
Unit Information Approx. Op./Ship Weights: 1025 lbs / 1025 lbs (±5%) Ambient Temperature (DB/WB): 95.0 °F / 75.0 °F Coil Filter FV / Qty: 189.0 fpm / 2 Min. Room Area/Height/Airflow**: 215 ft² / 7 ft / 388 SCFM Supply Airflow/ESP: 1050 SCFM / 0.60 in. w.g.
Outside Airflow: 250 SCFM Return Airflow/ESP: 1050 SCFM / 0.10 in. w.g.
Return Temperature (DB/WB): 75.0 °F / 62.0 °F
Static Pressure External: 0.60 in. w.g.
Cooling Coil: 0.13 in. w.g.
Filters Clean: 0.15 in. w.g.
Dirt Allowance: 0.35 in. w.g.
Reheat Coil: 0.03 in. w.g.
Economizer: 0.08 in. w.g.
Heater: 0.12 in. w.g.
Cabinet: 0.02 in. w.g.
Total: 1.49 in. w.g.
Heating Section Preheat Type: Std (No Preheat)
Auxiliary Heating Type: Nat. Gas Heat Heating Airflow: 1050 SCFM Total Capacity: 48.6 MBH Entering Air Temp (DB/WB): 53.3 °F / 42.6 °F Leaving Air Temp (DB/WB): 95.9 °F / 60.8 °F Consumption: 60.0 MBH Total Turndown Ratio: 10.0:1
Circuit 1 Rating:
Unit FLA:
Minimum Circuit Amp:
Maximum Overcurrent:
Qty HP VAC Phase RPM FLA RLA Compressor 1: 1 460 3 3500 7.7 Condenser Fan: 1 0.33 460 1 1100 1.6 Supply Fan: 1 1 460 3 1760 2.1 Combustion: 1 0.09 460 1 3000 0.4
460V/3Ø/60Hz
SCCR: 10 KAIC
Cooling Section Gross Net
Total Capacity: 45.4 MBH 43.8 MBH Sensible Capacity: 33.0 MBH 31.4 MBH Latent Capacity: 12.4 MBH
Supply Air Fan: 1 x RQ185D60 @ 0.48 BHP Ea.
SA Fan RPM / Width: 1414 RPM / 1.75 in SA Fan FEI: 1.52
Evaporator Coil: 5.2 ft² / 4 Rows / 14 FPI Evaporator Face Velocity: 200.0 fpm
Mixed Air Temp (DB/WB): 79.8 °F / 65.4 °F Entering Air Temp (DB/WB): 79.8 °F / 65.4 °F Lv Air Temp (Coil) (DB/WB): 50.4 °F / 50.1 °F Lv Air Temp (Unit) (DB/WB): 51.7 °F / 50.7 °F
Listing Model RQ-004-3-0-GAAY-V0-21-000-A
Cooling Capacity: 48.0 MBH Cooling EER2: 11.45 BTU/h·W Cooling SEER2: 13.7 BTU/h·W
Rating Information
*Rated in accordance with AHRI 210/240
Application EER @ Op. Conditions: 12.1 BTU/h·W
Re-heat Coil:
Capacity: 24.2 MBH Leaving Air Temp (DB/WB): 72.0 °F / 58.9 °F Relative Humidity: 45.6%
Electrical Data
2425 South Yukon Ave • Tulsa, OK 74107 • Ph: (918) 583-2266 Ecat Price Version: 364.1
Unit Rating
Date Printed:5/13/2026 10:05:20 AMPage 1 Of 2 Date Created/Modified:5/13/2026 10:00:30 AM Using Performance Version:364.1 Last Modified By:Chris Hess - Tobey Karg Sales Agency - Pittsburgh, PA
Cabinet Sound Power Levels* Octave Bands: 63 125 250 500 1000 2000 4000 8000 Discharge LW (dB): 78 78 80 71 65 62 58 53 Return LW (dB): 76 71 69 61 60 57 49 43 *Sound data is generated by a propriety acoustics model validated through unit testing in accordance with AHRI 260, utilizing tested fan sound data in accordance with AMCA 300.
**The minimum floor area is based on the Lower Flammability Limit (LFL) and calculated in accordance with UL60335-2-40 4th ed. (operating or storage). For UL60335-2-40 3rd ed. double the airflow and minimum floor area listed.
The minimum airflow (Qmin) is the minimum allowable airflow for any operating condition.
2425 South Yukon Ave • Tulsa, OK 74107 • Ph: (918) 583-2266 Ecat Price Version: 364.1
Unit Rating
Date Printed:5/13/2026 10:05:20 AMPage 2 Of 2
JOB INFORMATION: WHEEL SPECIFICATION:
Job Name WV ANG Logan Mingo
Readiness Center Job Tag ACU_1A Date 5/13/2026 10:00:30 AM
Max RPM 2200 Diameter x Qty 18.5 in. x 1
CFM 1050
Inertia 3 WR²
OPERATING CONDITIONS MOTOR SELECTION
Airflow 1050 Fan Energy Index (FEI) 1.52 Static Pressure 1.49 in. w.g.
Relief Dampers DP 0.00 in. w.g.
TSP 1.49 in. w.g.
Site Altitude 0
Rated HP / Bypass 1 x 1 / No Frame Size 56 Nominal RPM 1760 VAC/PH/Hz 230V/1Ø/60Hz Enclosure Type ODP Max Inertial Load 0 WR²
FAN PERFORMANCE: FAN SOUND POWER (Inlet/Outlet)
RPM 1414
BHP 0.48
Efficiency 51.4% Max Duct SP with Blocked Airway
2.20 in. w.g. @ 1414 RPM
Octave Band: (Re 10^-12 watts) 1 2 3 4 5 6 7 8
78 78 80 76 71 69 65 60 78 78 80 76 71 69 65 60
SOUND POWER A-Weighted: 80 dB
2425 South Yukon Ave • Tulsa, OK 74107 • Ph: (918) 583-2266
Ecat Price Version: 364.1
18.5" STAR Plenum
Date Printed:5/13/2026 10:05:21 AM Date Created/Modified:5/13/2026 10:00:30 AM Using Version:364.1
B
A
A
A
A
A
A
-C
B
B
B
B
L
B
B
:0
-0
A
F
B
D
C
A
D
D
E
-E
A
B
C
-0
A
B
C
D
E
-0
A
B
C
D
E
-E
C
-C
A
B
B
C
A
D
-0
A
B -E
A
B
-A
-A
A
N
B
C
-E
B
-N
A
B
C
D
-0
A
B
-0
A
B
C
-A
A
-C
B
-0
B
Unit Submittal 2425 South Yukon Ave • Tulsa, OK 74107 • Ph: (918) 583-2266
Ecat Price Version: 364.1
Tag:
Job Name: WV ANG Logan Mingo
Readiness Center Unit Worksheet For:
Job Number: 1 Unit Worksheet Date: 5/13/2026
ACU_1A
Feature Option Description
0 F1. Unit Orientation Standard Access - Hinged Access Doors with Lockable Handles 0 F2. Supply & Return Locations Bottom Discharge and Return 0 F3A. Supply Fan Quantity 1 Fan F F3B. Supply Fan Configuration 1 Fan per VFD + Narrow Width Fan D F3C. Supply Fan Size 18.5" Direct Drive Backward Curved Aluminum A F3D. Supply Fan Motor Type High Efficiency Open Motor (1,800 nominal rpm) D F3E. Supply Fan Motor Size 1 HP E F4A. Outside Air Section Economizer 0 F4B. Energy Recovery Type No Energy Recovery 0 F4C. Energy Recovery Size No Energy Recovery 0 F5A. Return Fan Quantity 0 Return Fans 0 F5B. Return Fan Configuration No Return Fan 0 F5C. Return Fan Size No Return Fan 0 F5D. Return Fan Motor Type No Return Fan 0 F5E. Return Fan Motor Size No Return Fan 0 F6A. Exhaust Fan Quantity 0 Exhaust Fans 0 F6B. Exhaust Fan Configuration No Exhaust Fan 0 F6C. Exhaust Fan Size No Exhaust Fan 0 F6D. Exhaust Fan Motor Type No Exhaust Fan 0 F6E. Exhaust Fan Motor Size No Exhaust Fan E F7. Outside Air Control DDC Actuator C F8. Return and Exhaust Air Options Standard Barometric Relief EA Dampers C F9A. Unit Filter Type 4" Pleated - 85% Eff - MERV 13 + 2" Pleated - MERV 8 B F9B. Unit Filter Size & Location High Efficiency Filters in Standard Position 0 F9C. Final Filter Type No Final Filters A F9D. Filter Options Clogged Filter Switch - Unit Filters 0 F10A. Refrigeration Control A Standard - Fixed 55°F Comp. Cooling Lock Out
Base Option Description
RQ Generation RQ Series A Major Revision Major Revision A
004 Unit Size Four A Series A Series A Minor Revision Minor Revision A 3 Voltage 460V/3φ/60Hz G Compressor Style R-454B Variable Capacity Scroll Compressor B Condenser Style High Eff. Microchannel Air-Cooled Condenser A Indoor Coil Configuration Std Row Std Eff. Evaporator 0 Cooling Heat Exchanger Construction Standard A Cooling Staging Modulating C Heat Type Natural Gas B Heat Construction Stainless Steel Heat Exchanger 1 Heat Designation Heat 1 - 60 Mbtu L Heat Staging High Turndown Modulating Gas Heat - Temperature Control 0 Heat Pump Auxiliary Heating No Auxiliary Heat
Date Created/Modified:5/13/2026 10:00:30 AM Using Performance Version:364.1 Date Printed:5/13/2026 10:05:21 AM
Feature Option Description
0 F10B. Refrigeration Control B Standard E F11A. Refrigeration Options A Modulating Hot Gas Reheat 0 F11B. Refrigeration Options B Standard Packaged Unit A F12. Refrigeration Accessories Sight Glass A F13A. Unit Disconnect Type Single Point Power - Non-fused Disconnect Power Switch N F13B. Disconnect 1 Size 100 Amps 0 F13C. Disconnect 2 Size Standard - None E F14. Safety Options Remote Safety Shutdown Terminals B F15. Electrical Accessories Phase & Brownout Protection N F16A. Control Sequence Field Installed DDC Controls by Others + Isolation Relays 0 F16B. Control Supplier None 0 F16C. Control Supplier Options None 0 F16D. BMS Connection & Diagnostics None 0 F17A. Preheat Configuration Standard - None 0 F17B. Preheat Sizing Standard - None 0 F18A. Option Box Location None 0 F18B. Option Box Size None 0 F18C. Option Box Accessories None A F19. Outside Air Accessories Outside Air Hood 0 F20. Cabinet Options Standard - None 0 F21. Accessories Standard A F22. Maintenance Accessories 115V Convenience Outlet Factory Wired 0 F23. Code Options Standard - ETL U.S.A. Listing 0 F24. Shipping Splits Standard C F25. Air-Cooled Condenser Accessories ECM Condenser Fan Head Pressure Control 0 F26. Evap-Cooled Condenser Accessories Standard 0 F27. Water-Cooled Condenser Accessories None 0 F28. Energy Recovery Accessories None 0 F29. VFD Options Standard B F30. Miscellaneous Options SCCR (10kA) 0 F31. Blank Standard 0 F32. Blank Standard 0 F33. Blank Standard 0 F34. Blank Standard 0 F35. Warranty Standard - 2 Year Parts Warranty 0 F36. Cabinet Material Galvanized Cabinet - Double Wall + R-16 Foam Insulation B F37. Specials & Paint Premium AAON Gray Paint Exterior Paint
Date Created/Modified:5/13/2026 10:00:30 AM Using Performance Version:364.1 Date Printed:5/13/2026 10:05:21 AM
B
A
A
A
A
A
A
-C
B
B
B
B
L
B
B
:0
-0
A
F
B
D
C
A
D
D
E
-E
A
B
C
-0
A
B
C
D
E
-0
A
B
C
D
E
-E
C
-C
A
B
B
C
A
D
-0
A
B
-E
A
B
-A
-A
A
N
B
C
-E
B
-N
A
B
C
D
-0
A
B
-0
A
B
C
-A
A
-C
B
-0
B
Terminals 2425 South Yukon Ave • Tulsa, OK 74107 • Ph: (918) 583-2266
Ecat Price Version: 364.1
Tag:
Job Name: WV ANG Logan Mingo
Readiness Center For:
Job Number: 1 Date: May 13, 2026
ACU_1A
Terminals Available/Required for Controlling the Unit Terminals Decription [C1] & [C2] Clogged Filter Switch
[R] 24VAC Control Voltage [C] Common [G] Supply Fan Enable + Isolation Relay [Y1] Cooling Stage 1 Enable + Isolation Relay
[DC1-] & [DC1+] Variable Capacity Compressor 1 (1.44-5VDC) Signal [SP1-] & [SP1+] Suction Pressure Sensor - Compressor 1 (0.5-4.5VDC)
[W1] Heating Stage 1 Enable + Isolation Relay [+] & [-] Gas Heat Reset Signal (0-10VDC)
Resets the supply air setpoint [Q1] & [Q2] Gas Heat Alarm
Dry contact terminals for alarm output (NC) [EC1-] & [EC2+] Economizer Signal (2-10VDC)
[S1-] & [S2+] Supply Fan 1 - w/ 1 VFD: Signal (0-10VDC) VFD frequency reference signal control point must handle a rated 20k ohm input impedance.
[RH1] Reheat Enable + Isolation Relay Must enable and modulate the digital compressors during dehumidification mode.The control logic needs to set if cooling or dehumidification is priority.
[AI1] & [COM] Reheat Reset Signal (0-10VDC)
Resets the supply air setpoint [BI1] & [BI2] Remote Safety Shutdown
[PBO1] & [PBO2] Phase & Brown Out
Terminations Found on VFD(s) [AM] & [AC] Current Feedback (0-10VDC = 0-100%) [MA] & [MC] Fault Status (NC, 250VAC/30VDC, 1A)
Supply Fan VFD A2L Terminals
[ALM1] & [ALM2] A2L Airstream Alarm & Cabinet Alarm A2L Mitigation Board 1
P/N: ASM0763
A2L Mitigation Board 2
P/N: ASM0763
Date Printed:5/13/2026 10:05:21 AMDate Created/Modified:5/13/2026 10:00:30 AM Using Performance Version:364.1
RQ-00007 REV:F 02/15/23 JWC
NOTE: ALL DIMENSIONS ARE IN INCHES
CLEARANCES
LOCATION
OUTSIDE AIR
• UNIT SIZE •
1 - 6 TON
36*(BACK)
HXC
(FRONT)
LEFT SIDE
RIGHT SIDE
TOP UNOBSTRUCTED
FORMED UP
DETAIL A
DETAIL B
RQ CABINET
ECONOMIZER VERTICAL ~ 1-6 TON
RAISE MINIMUM 1
2" FOR THE
SUPPLY/RETURN AIR AND
ELEC ENTRY OPENINGS.
ø13 ø21 ø13
HIGH VOLTAGE
LOW VOLTAGE
SEE DETAIL
"A"
SEE DETAIL
"B"
TOP VIEW
63 4
OUTSIDE
AIR
SUPPLY RETURN
RIGHT SIDE VIEW
FILTER
COIL
CONTROLS AND
COMPRESSOR
ACCESS
INSIDE BASE RAIL
OUTSIDE BASE RAIL
LEFT SIDE VIEW
INCH MPT STAINLESS CONDENSATE
CONNECTION.
LIFTING LUG
(4 CORNERS)
3 4
SUPPLY BLOWER
ACCESS
COIL
*CLEARANCE IS MEASURED
FROM THE END OF THE
OUTSIDE AIR RAIN HOOD
SUPPLY
C O
IL
FI
LT
ER
S
RE
TU
RN
ECONOMIZER
FRONT VIEW
HEATER ACCESS
POWER
SWITCH
INSIDE BASE RAIL
OUTSIDE BASE RAIL
COMBUSTION AIR INLETS
(GAS HEAT ONLY)
FLUE OUTLET
(GAS HEAT ONLY)
ø11
GAS 141
2ENTRY
FIELD GAS PIPING DETAILS
RQ SERIES CABINET
2-6 TON
60/100/140/160 MBH
4 STAGE, HIGH TURNDOWN
Field gas piping is required to the internal gas valves.
Piping should be installed adhering to building codes.
Perform leak check prior to operation.
Reference IOM for additonal information, and details on optional gas entry through base.
REMOVABLE
KICKPLATE
HXC 1
HEAT
EXCHANGER 1
CAT000422 RQ REV A 04/25/23 JAS
ALL DIMENSIONS ARE IN INCHES
FRONT
TOP
SIDE
2 3/16
5 1/2
4 1/8
5 3/16
4 7/8
AAON
RQA-004-A-A-3-GBA0A-CB1L0:00-0FDAD-E00-00000-00000-EC-CB0A-00-E0-A-AN0-EB-N000-00-000-A00A00-C0000B-000000B
RQ CABINET
VERTICAL AIR COOLED CONDENSING UNIT
Front Right Corner:
294 lbs
Back Left Corner:
220 lbs
Back Right Corner:
281 lbs
CGx: 40.1" CGy: 19.3"
Total Weight:
1025 lbs
+X
+Y
Disclaimer:
This weight estimate does not account for any SPAs.
Front Left Corner:
230 lbs
0"
0" 82"
44"
SUPPLY
RE
TU
RN
C O
IL
FI
LT
ER
S
B
A
A
A
A
A
A
-A
B
B
B
N
B
B
:0
-0
A
F
B
D
C
A
D
D
E
-Q
A
A
B
A
C
-0
A
B
C
D
E
-A
A
G
B
H
C
B
D
G
E
-E
C
-C
A
B
B
C
A
D
-0
A
B
-E
A
B
-A
-A
A
N
B
C
-E
B
-N
A
B
C
D
-0
A
B
-0
A
B
C
-A
A
-C
B
-0
X
DOAS_2ATag:
Job Information Job Name: WV ANG Logan Mingo Readiness
Center Job Number: 1 Site Altitude: 0 ft Refrigerant: R-454B Design System Charge (oz): 229
Unit Information
Approx. Op./Ship Weights: 1324 lbs / 1324 lbs (±5%) Ambient Temperature (DB/WB): 95.0 °F / 75.0 °F Coil Filter FV / Qty: 189.0 fpm / 2 Min. Room Area/Height/Airflow**: 215 ft² / 7 ft / 388 SCFM Exhaust Airflow/ESP/TSP: 2580 SCFM / 0.25 in. w.g. / 1.34 in. w.g.
Supply Airflow/ESP: 1050 SCFM / 0.50 in. w.g.
Outside Airflow: 1050 SCFM Return Airflow/ESP: 2580 SCFM / 0.25 in. w.g.
Return Temperature (DB/WB): 75.0 °F / 62.0 °F
**WEIGHT AND PERFORMANCE DO NOT INCLUDE SPA
Static Pressure External: 0.50 in. w.g.
Cooling Coil: 0.13 in. w.g.
Filters Clean: 0.15 in. w.g.
Dirt Allowance: 0.35 in. w.g.
Reheat Coil: 0.03 in. w.g.
Economizer: 0.08 in. w.g.
Heater: 0.05 in. w.g.
Cabinet: 0.02 in. w.g.
Energy Recovery: 1.14 in. w.g.
Total: 2.46 in. w.g.
Heating Section Preheat Type: Std (No Preheat)
Auxiliary Heating Type: Electric Heat Heating Airflow: 1050 SCFM Total Capacity: 20.0 kW Entering Air Temp (DB/WB): 39.6 °F / 32.9 °F Leaving Air Temp (DB/WB): 99.5 °F / 60.6 °F Electric Heat FLA: 24.1
(Values do not account for changes described in SPA)
Cooling Section Gross Net
Equivalent Total Capacity: 70.9 MBH 68.2 MBH Total Capacity: 47.7 MBH 45.0 MBH Sensible Capacity: 33.6 MBH 30.9 MBH Latent Capacity: 14.1 MBH HW Total Cooling Capacity: 23.2 MBH
Supply Air Fan: 1 x RQ185D60 @ 0.83 BHP Ea.
SA Fan RPM / Width: 1688 RPM / 1.75 in SA Fan FEI: 1.28 Exhaust Air Fan: 1 x RN150D70-RQ @ 1.62 BHP Ea.
EA Fan RPM / Width: 2471 RPM / 2.352 in EA Fan FEI: 0.77
Evaporator Coil: 5.2 ft² / 4 Rows / 14 FPI Evaporator Face Velocity: 200.0 fpm Energy Recovery: 1 x ERC-2108
Mixed Air Temp (DB/WB): 83.3 °F / 68.3 °F Entering Air Temp (DB/WB): 83.3 °F / 68.3 °F Lv Air Temp (Coil) (DB/WB): 53.3 °F / 53.0 °F Lv Air Temp (Unit) (DB/WB): 55.5 °F / 53.9 °F
Listing Model RQ-004-3-0-GAAY-V0-21-000-A
Cooling Capacity: 48.0 MBH Cooling EER2: 11.45 BTU/h·W Cooling SEER2: 13.7 BTU/h·W
Rating Information
*Rated in accordance with AHRI 210/240
Application EER @ Op. Conditions: 12.5 BTU/h·W
Re-heat Coil:
Capacity: 20.9 MBH Leaving Air Temp (DB/WB): 72.0 °F / 60.3 °F Relative Humidity: 50.7%
Electrical Data
2425 South Yukon Ave • Tulsa, OK 74107 • Ph: (918) 583-2266 Ecat Price Version: 364.1
Unit Rating
Date Printed:5/13/2026 10:06:47 AMPage 1 Of 3
Circuit 1 Rating:
Unit FLA:
Minimum Circuit Amp:
Maximum Overcurrent:
Qty HP VAC Phase RPM FLA RLA Compressor 1: 1 460 3 3500 7.7 Condenser Fan: 1 0.33 460 1 1100 1.6 Supply Fan: 1 1 460 3 1760 2.1 Exhaust Fan: 1 2 460 3 1760 3.4 Energy Recovery: 1 0.05 230 1 825 0.3
460V/3Ø/60Hz
SCCR: 10 KAIC
Cabinet Sound Power Levels* Octave Bands: 63 125 250 500 1000 2000 4000 8000 Discharge LW (dB): 86 85 88 82 75 70 67 60 Return LW (dB): 86 84 82 80 79 76 74 68 *Sound data is generated by a propriety acoustics model validated through unit testing in accordance with AHRI 260, utilizing tested fan sound data in accordance with AMCA 300.
**The minimum floor area is based on the Lower Flammability Limit (LFL) and calculated in accordance with UL60335-2-40 4th ed. (operating or storage). For UL60335-2-40 3rd ed. double the airflow and minimum floor area listed.
The minimum airflow (Qmin) is the minimum allowable airflow for any operating condition.
2425 South Yukon Ave • Tulsa, OK 74107 • Ph: (918) 583-2266 Ecat Price Version: 364.1
Unit Rating
Date Printed:5/13/2026 10:06:47 AMPage 2 Of 3
Job Name: WV ANG Logan Mingo Readiness Center
Energy Recovery Type: Total
Job Number: 1 Energy Recovery Model: ERC-2108 Site Altitude: 0 Energy Recovery Qty: 1 Net Supply Airflow Sum/Win: 952 SCFM / 953 SCFM Energy Recovery Software Ver: 2.4.1 Purge Angle: 0.0°
Tag:
86.0 °F
69.2 °F
0.80 in. w.g.
Damper Mixed Air
1050 SCFM
83.3 °F DB
68.3 °F WB
79.36 gr/lbm
Supply Air
1050 SCFM
83.3 °F DB
68.3 °F WB
79.36 gr/lbm
Energy Recovery
83.3 °F
68.3 °F
0.81 in. w.g.
Bypass: 0 SCFM Outside Air
1096 SCFM
95.0 °F DB
75.0 °F WB
98.46 gr/lbm
OACF: 1.04
Return Air
0 SCFM
75.0 °F DB
62.0 °F WB
62.11 gr/lbm
Exhaust Air
1096 SCFM
79.6 °F
65.1 °F
69.48 gr/lbm
EATR: 9.3%
From Space
2580 SCFM
Summer Conditions
Ex Bypass: 1530 SCFM
Frost Warning - Conditions for frost forming on the energy recovery exists. Outside air preheat is required to prevent frost formation. Optionally, the return air humidity ratio could be lowered to prevent frost formation. See AAON literature titled 'AAONAIRE ENERGY RECOVERY' for details.
Return Air
0 SCFM
70.0 °F DB
52.0 °F WB
28.94 gr/lbm
Exhaust Air
1100 SCFM
53.4 °F
43.0 °F
24.30 gr/lbm
EATR: 9.2%
Outside Air
1100 SCFM
0.0 °F DB
0.0 °F WB
5.49 gr/lbm
OACF: 1.05
Mixed Air
1050 SCFM
39.6 °F DB
32.9 °F WB
16.84 gr/lbm
Supply Air
1050 SCFM
39.6 °F DB
32.9 °F WB
16.84 gr/lbm
Damper Energy Recovery
39.6 °F
32.9 °F
0.81 in. w.g.
From Space
30.4 °F
27.7 °F
0.80 in. w.g.
2580 SCFM
Winter Conditions Bypass: 0 SCFM
Ex Bypass: 1530 SCFM
Summer Winter Total Capacity 23.2 MBH 47.5 MBH Sensible Capacity 11.2 MBH 40.3 MBH Latent Capacity 12.0 MBH 7.2 MBH
Summer Winter Total Effectiveness 51.1% 54.1% Sensible Effectiveness 55.7% 55.7% Latent Effectiveness 48.1% 46.3%
Summer Winter Enthalpy Recovery Ratio 55.3% 55.0% Sensible Energy Recovery Ratio 54.4% 52.5%
Energy Recovery Performance
DOAS_2A
RQA-004-A-A-3-G
A
B
A
A
A
A
A
A
-A
B
B
B
N
B
B
:0
-0
A
F
B
D
C
A
D
D
E
-Q
A
A
B
A
C
-0
A
B
C
D
E
-A
A
G
B
H
C
B
D
G
E
-E
C
-C
A
B
B
C
A
D
-0
A
B -E
A
B
-A
-A
A
N
B
C
-E
B
-N
A
B
C
D
-0
A
B
-0
A
B
C
-A
A
-C
B
-0
X
Application Rating is outside the scope of the AHRI ERV Certification Program but is rated in accordance with AHRI Standard 1060.
2425 South Yukon Ave • Tulsa, OK 74107 • Ph: (918) 583-2266 Ecat Price Version: 364.1
Unit Rating
Date Printed:5/13/2026 10:06:47 AMPage 3 Of 3
Readiness Center Job Tag DOAS_2A Date 5/13/2026 10:00:30 AM
Max RPM 2200 Diameter x Qty 18.5 in. x 1
CFM 1050
Inertia 3 WR²
OPERATING CONDITIONS MOTOR SELECTION
Airflow 1050 Fan Energy Index (FEI) 1.28 Static Pressure 2.46 in. w.g.
Relief Dampers DP 0.00 in. w.g.
TSP 2.46 in. w.g.
Site Altitude 0
Rated HP / Bypass 1 x 1 / No Frame Size 56 Nominal RPM 1760 VAC/PH/Hz 460V/3Ø/60Hz Enclosure Type ODP Max Inertial Load 0 WR²
FAN PERFORMANCE: FAN SOUND POWER (Inlet/Outlet)
RPM 1688
BHP 0.83
Efficiency 49.1% Max Duct SP with Blocked Airway
3.10 in. w.g. @ 1688 RPM
Octave Band: (Re 10^-12 watts) 1 2 3 4 5 6 7 8
83 81 84 81 75 73 71 65 83 81 84 81 75 73 71 65
SOUND POWER A-Weighted: 85 dB
2425 South Yukon Ave • Tulsa, OK 74107 • Ph: (918) 583-2266
Ecat Price Version: 364.1
18.5" STAR Plenum
Date Printed:5/13/2026 10:06:48 AM
2425 South Yukon Ave • Tulsa, OK 74107 • Ph: (918) 583-2266
Ecat Price Version: 364.1
15" STAR Plenum
JOB INFORMATION: WHEEL SPECIFICATION:
Job Name WV ANG Logan Mingo
Readiness Center Job Tag DOAS_2A Date 5/13/2026 10:00:30 AM
Max RPM 2600 Diameter x Qty 15 in. x 1
CFM 2580
Inertia 3 WR²
FAN PERFORMANCE FAN SOUND POWER (Inlet/Outlet)
RPM 2471
BHP 1.62
Efficiency 33.6% Max Duct SP with Blocked Airway
4.70 in. w.g. @ 2471 RPM
Octave Band: (Re 10^-12 watts) 1 2 3 4 5 6 7 8
85 85 86 87 82 78 76 71 85 85 86 87 82 78 76 71
SOUND POWER A-Weighted: 88 dB
OPERATING CONDITIONS MOTOR SELECTION
Airflow 2580 Fan Energy Index (FEI) 0.77 Static Pressure 1.34 in. w.g.
Relief Dampers DP 0.00 in. w.g.
TSP 1.34 in. w.g.
Site Altitude 0
Rated HP / Bypass 2 x 1 / No Frame Size 56 Nominal RPM 1760 VAC/PH/Hz 460V/3Ø/60Hz Enclosure Type ODP Max Inertial Load 0 WR²
B
A
A
A
A
A
A
-A
B
B
B
N
B
B
:0
-0
A
F
B
D
C
A
D
D
E
-Q
A
A
B
A
C
-0
A
B
C
D
E
-A
A
G
B
H
C
B
D
G
E
-E
C
-C
A
B
B
C
A
D
-0
A
B -E
A
B
-A
-A
A
N
B
C
-E
B
-N
A
B
C
D
-0
A
B
-0
A
B
C
-A
A
-C
B
-0
X
Unit Submittal 2425 South Yukon Ave • Tulsa, OK 74107 • Ph: (918) 583-2266
Ecat Price Version: 364.1
Tag:
Job Name: WV ANG Logan Mingo
Readiness Center Unit Worksheet For:
Job Number: 1 Unit Worksheet Date: 5/13/2026
DOAS_2A
Feature Option Description
0 F1. Unit Orientation Standard Access - Hinged Access Doors with Lockable Handles 0 F2. Supply & Return Locations Bottom Discharge and Return 0 F3A. Supply Fan Quantity 1 Fan F F3B. Supply Fan Configuration 1 Fan per VFD + Narrow Width Fan D F3C. Supply Fan Size 18.5" Direct Drive Backward Curved Aluminum A F3D. Supply Fan Motor Type High Efficiency Open Motor (1,800 nominal rpm) D F3E. Supply Fan Motor Size 1 HP Q F4A. Outside Air Section Economizer + Energy Recovery + Bypass Damper A F4B. Energy Recovery Type Polymer Energy Recovery Wheel A F4C. Energy Recovery Size Total + Low CFM 0 F5A. Return Fan Quantity 0 Return Fans 0 F5B. Return Fan Configuration No Return Fan 0 F5C. Return Fan Size No Return Fan 0 F5D. Return Fan Motor Type No Return Fan 0 F5E. Return Fan Motor Size No Return Fan A F6A. Exhaust Fan Quantity 1 Fan G F6B. Exhaust Fan Configuration 1 Fan per VFD + Narrow Width Fan H F6C. Exhaust Fan Size 15” Backward Curved Plenum B F6D. Exhaust Fan Motor Type High Efficiency Open Motor (1,800 nominal rpm) G F6E. Exhaust Fan Motor Size 2 HP E F7. Outside Air Control DDC Actuator C F8. Return and Exhaust Air Options Standard Barometric Relief EA Dampers C F9A. Unit Filter Type 4" Pleated - 85% Eff - MERV 13 + 2" Pleated - MERV 8 B F9B. Unit Filter Size & Location High Efficiency Filters in Standard Position 0 F9C. Final Filter Type No Final Filters A F9D. Filter Options Clogged Filter Switch - Unit Filters 0 F10A. Refrigeration Control A Standard - Fixed 55°F Comp. Cooling Lock Out
Base Option Description
RQ Generation RQ Series A Major Revision Major Revision A
004 Unit Size Four A Series A Series A Minor Revision Minor Revision A 3 Voltage 460V/3φ/60Hz G Compressor Style R-454B Variable Capacity Scroll Compressor B Condenser Style High Eff. Microchannel Air-Cooled Condenser A Indoor Coil Configuration Std Row Std Eff. Evaporator 0 Cooling Heat Exchanger Construction Standard A Cooling Staging Modulating A Heat Type Electric Heat 0 Heat Construction Standard 2 Heat Designation Heat 2 - 20 kW N Heat Staging Modulating SCR Electric with External 0-10 VDC 0 Heat Pump Auxiliary Heating No Auxiliary Heat
Date Created/Modified:5/13/2026 10:00:30 AM Using Performance Version:364.1 Date Printed:5/13/2026 10:06:49 AM
E F11A. Refrigeration Options A Modulating Hot Gas Reheat 0 F11B. Refrigeration Options B Standard Packaged Unit A F12. Refrigeration Accessories Sight Glass A F13A. Unit Disconnect Type Single Point Power - Non-fused Disconnect Power Switch N F13B. Disconnect 1 Size 100 Amps 0 F13C. Disconnect 2 Size Standard - None E F14. Safety Options Remote Safety Shutdown Terminals B F15. Electrical Accessories Phase & Brownout Protection N F16A. Control Sequence Field Installed DDC Controls by Others + Isolation Relays 0 F16B. Control Supplier None 0 F16C. Control Supplier Options None 0 F16D. BMS Connection & Diagnostics None 0 F17A. Preheat Configuration Standard - None 0 F17B. Preheat Sizing Standard - None 0 F18A. Option Box Location None 0 F18B. Option Box Size None 0 F18C. Option Box Accessories None A F19. Outside Air Accessories Outside Air Hood 0 F20. Cabinet Options Standard - None 0 F21. Accessories Standard A F22. Maintenance Accessories 115V Convenience Outlet Factory Wired 0 F23. Code Options Standard - ETL U.S.A. Listing 0 F24. Shipping Splits Standard C F25. Air-Cooled Condenser Accessories ECM Condenser Fan Head Pressure Control 0 F26. Evap-Cooled Condenser Accessories Standard 0 F27. Water-Cooled Condenser Accessories None 0 F28. Energy Recovery Accessories None 0 F29. VFD Options Standard B F30. Miscellaneous Options SCCR (10kA) 0 F31. Blank Standard 0 F32. Blank Standard 0 F33. Blank Standard 0 F34. Blank Standard 0 F35. Warranty Standard - 2 Year Parts Warranty 0 F36. Cabinet Material Galvanized Cabinet - Double Wall + R-16 Foam Insulation X F37. Specials & Paint SPA + Premium AAON Gray Paint Exterior Paint
Date Created/Modified:5/13/2026 10:00:30 AM Using Performance Version:364.1 Date Printed:5/13/2026 10:06:49 AM
B
A
A
A
A
A
A
-A
B
B
B
N
B
B
:0
-0
A
F
B
D
C
A
D
D
E
-Q
A
A
B
A
C
-0
A
B
C
D
E
-A
A
G
B
H
C
B
D
G
E
-E
C
-C
A
B
B
C
A
D
-0
A
B
-E
A
B
-A
-A
A
N
B
C
-E
B
-N
A
B
C
D
-0
A
B
-0
A
B
C
-A
A
-C
B
-0
X
Terminals 2425 South Yukon Ave • Tulsa, OK 74107 • Ph: (918) 583-2266
Ecat Price Version: 364.1
Tag:
Job Name: WV ANG Logan Mingo
Readiness Center For:
Job Number: 1 Date: May 13, 2026
DOAS_2A
Terminals Available/Required for Controlling the Unit Terminals Decription [C1] & [C2] Clogged Filter Switch
[R] 24VAC Control Voltage [C] Common [G] Supply Fan Enable + Isolation Relay [Y1] Cooling Stage 1 Enable + Isolation Relay
[DC1-] & [DC1+] Variable Capacity Compressor 1 (1.44-5VDC) Signal [SP1-] & [SP1+] Suction Pressure Sensor - Compressor 1 (0.5-4.5VDC)
[W1] Heating Stage 1 Enable + Isolation Relay [+] & [-] SCR Control Signal (0-10VDC)
[HW] Energy Recovery Wheel Enable + Isolation Relay [PE] Power Exhaust Enable + Isolation Relay
[B1-] & [B2+] Exhaust Fan ECM Motor Signal (0-10VDC) [EC1-] & [EC2+] Economizer Signal (2-10VDC)
[S1-] & [S2+] Supply Fan 1 - w/ 1 VFD: Signal (0-10VDC) VFD frequency reference signal control point must handle a rated 20k ohm input impedance.
[RH1] Reheat Enable + Isolation Relay Must enable and modulate the digital compressors during dehumidification mode.The control logic needs to set if cooling or dehumidification is priority.
[AI1] & [COM] Reheat Reset Signal (0-10VDC)
Resets the supply air setpoint [BI1] & [BI2] Remote Safety Shutdown
[PBO1] & [PBO2] Phase & Brown Out
Terminations Found on VFD(s) Exhaust Fan VFD
[AM] & [AC] Current Feedback (0-10VDC = 0-100%) [MA] & [MC] Fault Status (NC, 250VAC/30VDC, 1A)
Supply Fan VFD [16] & [17] Current Feedback (0-10VDC = 0-100%)
A2L Terminals [ALM1] & [ALM2] A2L Airstream Alarm & Cabinet Alarm
A2L Mitigation Board 1
P/N: ASM0763
A2L Mitigation Board 2
P/N: ASM0763
Date Printed:5/13/2026 10:06:49 AMDate Created/Modified:5/13/2026 10:00:30 AM Using Performance Version:364.1
RQ-00031 REV:E 02/15/23 JWC
NOTE: ALL DIMENSIONS ARE IN INCHES
FORMED UP
DETAIL A
DETAIL B
LOW VOLTAGE
HIGH VOLTAGE
ø13 ø2 1 ø13
RAISE MINIMUM 1
2" FOR THE
SUPPLY/RETURN AIR AND
ELEC ENTRY OPENINGS.
RQ CABINET
ENERGY RECOVERY SECTION POWER EXHAUST
ECONOMIZER VERTICAL ~ 1-6 TON
CLEARANCES
LOCATION • UNIT SIZE •
1 - 6 TON
HXC
(FRONT)
LEFT SIDE
BACK SIDE
TOP UNOBSTRUCTED
48*
OUTSIDE AIR
(RIGHT)
*CLEARANCE IS MEASURED
FROM THE END OF THE
OUTSIDE AIR RAIN HOOD
*HW DOOR SWING = 38.5"
FRONT VIEW
INSIDE BASE RAIL
OUTSIDE BASE RAIL
RIGHT SIDE VIEW
CONTROLS AND
COMPRESSOR
ACCESS
LIFTING LUG
(4 CORNERS)
ECON
FILTER
COIL
HEATWHEEL
SUPPLY
RE
TU
RN
SUPPLY BLOWER
ACCESS
COIL
LEFT SIDE VIEW
4 INCH MPT STAINLESS CONDENSATE
CONNECTION.
TOP VIEW
SEE DETAIL
"B"
C O
IL
FI
LT
ER
S
SEE DETAIL
"A"
OUTSIDE
AIR
EXHAUST
AIR
24 431
4 9 385
8 171
HEATER ACCESS
POWER
SWITCH
INSIDE BASE RAIL
OUTSIDE BASE RAIL
COMBUSTION AIR INLETS
(GAS HEAT ONLY)
FLUE OUTLET
(GAS HEAT ONLY)
ø11
GAS 141
2ENTRY
8 37
RQA-004-A-A-3-GBA0A-A02N0:00-0FDAD-QAA-00000-AGHBG-EC-CB0A-00-E0-A-AN0-EB-N000-00-000-A00A00-C0000B-000000X
RQ CABINET-VERTICAL
AIR COOLED CONDENSING UNIT
WITH ENERGY RECOVERY
Front Right Corner:
358 lbs
Back Left Corner:
303 lbs
Back Right Corner:
357 lbs
CGx: 57.9" CGy: 20.2"
1324 lbs
+X
+Y
Disclaimer:
This weight estimate does not account for any SPAs.
Front Left Corner:
305 lbs
0"
0"
116"
44"
C O
IL
FI
LT
ER
S
SUPPLY
RE
TU
RN
RNA-007-A-A-3-G
A
A
B
A
A
A
A
-C
B
B
B
B
L
B
B
:0
-0
A
F
B
C
C
A
D
F
E
-Q
A
H
B
A
C
-0
A
B
C
D
E
-A
A
B
B
H
C
B
D
E
E
-E
C
-C
A
B
B
C
A
D
-0
A
B
-E
A
B
-A
-A
A
N
B
C
-E
B
-N
A
B
C
D
-0
A
B
-0
A
B
C
-A
A
-C
B
-0
B
DOAS_1ATag:
Job Information Job Name: WV ANG Logan Mingo Readiness
Center Job Number: 1 Site Altitude: 0 ft Refrigerant: R-454B Design System Charge (oz): 475
Unit Information Approx. Op./Ship Weights: 1581 lbs / 1581 lbs (±5%) Ambient Temperature (DB/WB): 95.0 °F / 75.0 °F Coil Filter FV / Qty: 211.5 fpm / 4 Min. Room Area/Height/Airflow**: 446 ft² / 7 ft / 804 SCFM Exhaust Airflow/ESP/TSP: 1500 SCFM / 0.25 in. w.g. / 0.98 in. w.g.
Supply Airflow/ESP: 1880 SCFM / 0.75 in. w.g.
Outside Airflow: 1880 SCFM Return Airflow/ESP: 1500 SCFM / 0.25 in. w.g.
Return Temperature (DB/WB): 75.0 °F / 62.0 °F
Static Pressure External: 0.75 in. w.g.
Cooling Coil: 0.22 in. w.g.
Filters Clean: 0.13 in. w.g.
Dirt Allowance: 0.35 in. w.g.
Reheat Coil: 0.03 in. w.g.
Economizer: 0.13 in. w.g.
Heater: 0.02 in. w.g.
Cabinet: 0.06 in. w.g.
Energy Recovery: 1.15 in. w.g.
Total: 2.84 in. w.g.
Heating Section Preheat Type: Std (No Preheat)
Auxiliary Heating Type: Nat. Gas Heat Heating Airflow: 1880 SCFM Total Capacity: 121.5 MBH Entering Air Temp (DB/WB): 44.4 °F / 36.5 °F Leaving Air Temp (DB/WB): 103.9 °F / 62.6 °F Consumption: 150.0 MBH Total Turndown Ratio: 8.0:1
Cooling Section Gross Net
Equivalent Total Capacity: 132.7 MBH 128.5 MBH Total Capacity: 79.7 MBH 75.5 MBH Sensible Capacity: 58.1 MBH 53.9 MBH Latent Capacity: 21.5 MBH HW Total Cooling Capacity: 53.0 MBH
Supply Air Fan: 1 x RNA185D70 @ 1.43 BHP Ea.
SA Fan RPM / Width: 1737 RPM / 2.898 in SA Fan FEI: 1.30 Exhaust Air Fan: 1 x RM150-RN @ 0.39 BHP Ea.
EA Fan RPM / Width: 1249 RPM / 5.16 in EA Fan FEI: 1.60
Evaporator Coil: 8.5 ft² / 6 Rows / 14 FPI Evaporator Face Velocity: 221.0 fpm Energy Recovery: 1 x ERC-3017C-BW
Mixed Air Temp (DB/WB): 81.9 °F / 67.2 °F Entering Air Temp (DB/WB): 81.9 °F / 67.2 °F Lv Air Temp (Coil) (DB/WB): 52.9 °F / 52.8 °F Lv Air Temp (Unit) (DB/WB): 54.8 °F / 53.6 °F
Listing Model RN-007-3-0-GABY-V0-21-000-A
Cooling Capacity: 74.0 MBH Cooling EER: 12.15 BTU/h·W Cooling IEER: 14.8 BTU/h·W
Rating Information
*Rated in accordance with AHRI Standard 340/360 (I-P)
Application EER @ Op. Conditions: 17.2 BTU/h·W
Re-heat Coil:
Capacity: 38.3 MBH Leaving Air Temp (DB/WB): 72.0 °F / 60.3 °F Relative Humidity: 50.7%
Electrical Data
2425 South Yukon Ave • Tulsa, OK 74107 • Ph: (918) 583-2266 Ecat Price Version: 364.1
Unit Rating
Date Printed:5/13/2026 10:06:05 AMPage 1 Of 3
Unit FLA:
Minimum Circuit Amp:
Maximum Overcurrent:
Qty HP VAC Phase RPM FLA RLA Compressor 1: 1 460 3 3500 10.9 Condenser Fan: 1 0.33 460 1 1100 1.6 Supply Fan: 1 2 460 3 1760 3.4 Exhaust Fan: 1 1 460 3 1760 2.1 Combustion: 1 0.1 460 1 3000 0.3 Energy Recovery: 1 0.13 460 3 1075 0.4
460V/3Ø/60Hz
SCCR: 10 KAIC
Cabinet Sound Power Levels* Octave Bands: 63 125 250 500 1000 2000 4000 8000 Discharge LW (dB): 84 82 85 81 73 70 68 62 Return LW (dB): 77 76 74 67 63 61 57 53 *Sound data is generated by a propriety acoustics model validated through unit testing in accordance with AHRI 260, utilizing tested fan sound data in accordance with AMCA 300.
**The minimum floor area is based on the Lower Flammability Limit (LFL) and calculated in accordance with UL60335-2-40 4th ed. (operating or storage). For UL60335-2-40 3rd ed. double the airflow and minimum floor area listed.
The minimum airflow (Qmin) is the minimum allowable airflow for any operating condition.
2425 South Yukon Ave • Tulsa, OK 74107 • Ph: (918) 583-2266 Ecat Price Version: 364.1
Unit Rating
Date Printed:5/13/2026 10:06:05 AMPage 2 Of 3
Readiness Center
Energy Recovery Type: Total
Job Number: 1 Energy Recovery Model: ERC-3017C-BW Site Altitude: 0 Energy Recovery Qty: 1 Net Supply Airflow Sum/Win: 1804 SCFM / 1802 SCFM Energy Recovery Software Ver: 2.4.1 Purge Angle: 10.0°
Tag:
91.3 °F
72.5 °F
0.68 in. w.g.
Damper Mixed Air
1880 SCFM
81.9 °F DB
67.2 °F WB
76.37 gr/lbm
Supply Air
1880 SCFM
81.9 °F DB
67.2 °F WB
76.37 gr/lbm
Energy Recovery
81.9 °F
67.2 °F
0.99 in. w.g.
Bypass: 0 SCFM Outside Air
1882 SCFM
95.0 °F DB
75.0 °F WB
98.46 gr/lbm
OACF: 1.00
Return Air
0 SCFM
75.0 °F DB
62.0 °F WB
62.11 gr/lbm
Exhaust Air
1502 SCFM
91.3 °F
72.5 °F
89.43 gr/lbm
EATR: 4.1%
From Space
1500 SCFM
Summer Conditions
Ex Bypass: 0 SCFM
Frost Warning - Conditions for frost forming on the energy recovery exists. Outside air preheat is required to prevent frost formation. Optionally, the return air humidity ratio could be lowered to prevent frost formation. See AAON literature titled 'AAONAIRE ENERGY RECOVERY' for details.
Return Air
0 SCFM
70.0 °F DB
52.0 °F WB
28.94 gr/lbm
Exhaust Air
1503 SCFM
12.5 °F
12.5 °F
10.32 gr/lbm
EATR: 4.2%
Outside Air
1883 SCFM
0.0 °F DB
0.0 °F WB
5.49 gr/lbm
OACF: 1.00
Mixed Air
1880 SCFM
44.4 °F DB
36.5 °F WB
19.17 gr/lbm
Supply Air
1880 SCFM
44.4 °F DB
36.5 °F WB
19.17 gr/lbm
Damper Energy Recovery
44.4 °F
36.5 °F
0.99 in. w.g.
From Space
12.5 °F
12.5 °F
0.68 in. w.g.
1500 SCFM
Winter Conditions Bypass: 0 SCFM
Ex Bypass: 0 SCFM
Summer Winter Total Capacity 53.0 MBH 106.0 MBH Sensible Capacity 25.0 MBH 88.5 MBH Latent Capacity 28.0 MBH 17.6 MBH
Summer Winter Total Effectiveness 77.1% 80.3% Sensible Effectiveness 81.5% 81.5% Latent Effectiveness 74.1% 74.6%
Summer Winter Enthalpy Recovery Ratio 63.2% 62.4% Sensible Energy Recovery Ratio 64.3% 61.9%
Energy Recovery Performance
DOAS_1A
RNA-007-A-A-3-G
A
A
A
B
A
A
A
A
-C
B
B
B
B
L
B
B
:0
-0
A
F
B
C
C
A
D
F
E
-Q
A
H
B
A
C
-0
A
B
C
D
E
-A
A
B
B
H
C
B
D
E
E
-E
C
-C
A
B
B
C
A
D
-0
A
B -E
A
B
-A
-A
A
N
B
C
-E
B
-N
A
B
C
D
-0
A
B
-0
A
B
C
-A
A
-C
B
-0
B
Application Rating is outside the scope of the AHRI ERV Certification Program but is rated in accordance with AHRI Standard 1060.
2425 South Yukon Ave • Tulsa, OK 74107 • Ph: (918) 583-2266 Ecat Price Version: 364.1
Unit Rating
Date Printed:5/13/2026 10:06:06 AMPage 3 Of 3
Readiness Center Job Tag DOAS_1A Date 5/13/2026 10:00:30 AM
Max RPM 2200 Diameter x Qty 18.5 in. x 1
CFM 1880
Inertia 3 WR²
OPERATING CONDITIONS MOTOR SELECTION
Airflow 1880 Fan Energy Index (FEI) 1.30 Static Pressure 2.84 in. w.g.
Relief Dampers DP 0.00 in. w.g.
TSP 2.84 in. w.g.
Site Altitude 0
Rated HP / Bypass 2 x 1 / No Frame Size 145T Nominal RPM 1760 VAC/PH/Hz 460V/3Ø/60Hz Enclosure Type ODP Max Inertial Load 0 WR²
FAN PERFORMANCE: FAN SOUND POWER (Inlet/Outlet)
RPM 1737
BHP 1.43
Efficiency 58.9% Max Duct SP with Blocked Airway
3.30 in. w.g. @ 1737 RPM
Octave Band: (Re 10^-12 watts) 1 2 3 4 5 6 7 8
84 82 85 83 76 74 72 66 84 82 85 83 76 74 72 66
SOUND POWER A-Weighted: 85 dB
2425 South Yukon Ave • Tulsa, OK 74107 • Ph: (918) 583-2266
Ecat Price Version: 364.1
18.5" STAR Plenum
Date Printed:5/13/2026 10:06:06 AM
Ecat Price Version: 364.1
15" STAR Plenum
JOB INFORMATION: WHEEL SPECIFICATION:
Job Name WV ANG Logan Mingo
Readiness Center Job Tag DOAS_1A Date 5/13/2026 10:00:30 AM
Max RPM 2064 Diameter x Qty 15 in. x 1
CFM 1500
Inertia 3 WR²
FAN PERFORMANCE FAN SOUND POWER (Inlet/Outlet)
RPM 1249
BHP 0.39
Efficiency 59.4% Max Duct SP with Blocked Airway
1.10 in. w.g. @ 1249 RPM
Octave Band: (Re 10^-12 watts) 1 2 3 4 5 6 7 8
75 74 75 70 65 64 60 56 75 74 75 70 65 64 60 56
SOUND POWER A-Weighted: 76 dB
OPERATING CONDITIONS MOTOR SELECTION
Airflow 1500 Fan Energy Index (FEI) 1.60 Static Pressure 0.98 in. w.g.
Relief Dampers DP 0.00 in. w.g.
TSP 0.98 in. w.g.
Site Altitude 0
Rated HP / Bypass 1 x 1 / No Frame Size 143T Nominal RPM 1760 VAC/PH/Hz 460V/3Ø/60Hz
A
A
B
A
A
A
A
-C
B
B
B
B
L
B
B
:0
-0
A
F
B
C
C
A
D
F
E
-Q
A
H
B
A
C
-0
A
B
C
D
E
-A
A
B
B
H
C
B
D
E
E
-E
C
-C
A
B
B
C
A
D
-0
A
B -E
A
B
-A
-A
A
N
B
C
-E
B
-N
A
B
C
D
-0
A
B
-0
A
B
C
-A
A
-C
B
-0
B
Unit Submittal 2425 South Yukon Ave • Tulsa, OK 74107 • Ph: (918) 583-2266
Ecat Price Version: 364.1
Tag:
Job Name: WV ANG Logan Mingo
Readiness Center Unit Worksheet For:
Job Number: 1 Unit Worksheet Date: 5/13/2026
DOAS_1A
Feature Option Description
0 F1. Unit Orientation Standard Access - Hinged Access Doors with Lockable Handles 0 F2. Supply & Return Locations Bottom Supply--Bottom Return 0 F3A. Supply Fan Quantity 1 Fan F F3B. Supply Fan Configuration 1 Fan per VFD + Narrow Width Fan C F3C. Supply Fan Size 18.5" Direct Drive Backward Curved Aluminum A F3D. Supply Fan Motor Type High Efficiency Open Motor (1,800 nominal rpm) F F3E. Supply Fan Motor Size 2 hp Q F4A. Outside Air Section Economizer + Energy Recovery + Bypass Damper H F4B. Energy Recovery Type High Eff. Polymer Energy Recovery Wheel + 1% Purge A F4C. Energy Recovery Size Low CFM Enthalpy 0 F5A. Return Fan Quantity 0 Return Fans 0 F5B. Return Fan Configuration No Return Fan 0 F5C. Return Fan Size No Return Fan 0 F5D. Return Fan Motor Type No Return Fan 0 F5E. Return Fan Motor Size No Return Fan A F6A. Exhaust Fan Quantity 1 Fan B F6B. Exhaust Fan Configuration 1 Fan per VFD + Full Width Fan H F6C. Exhaust Fan Size 15" Backward Curved Aluminum B F6D. Exhaust Fan Motor Type High Efficiency Open Motor (1,800 nominal rpm) E F6E. Exhaust Fan Motor Size 1 hp E F7. Outside Air Control DDC Actuator C F8. Return and Exhaust Air Options Standard Barometric Relief EA Dampers C F9A. Unit Filter Type 2" Pleated MERV 8 + 4" Pleated MERV 13 B F9B. Unit Filter Size & Location High Efficiency Filters in Standard Position 0 F9C. Final Filter Type No Final Filters A F9D. Filter Options Clogged Filter Switch - Unit Filters 0 F10A. Refrigeration Control A Standard - Fixed 55°F Comp. Cooling Lock Out
Base Option Description
RN Generation RN Series A Major Revision Major Revision A
007 Unit Size Seven A Series A Series A Minor Revision Minor Revision A 3 Voltage 460V/3φ/60Hz G Compressor Style R-454B Variable Capacity Scroll Compressor A Condenser Style Microchannel Air-Cooled Condenser B Indoor Coil Configuration 6 Row Evaporator 0 Cooling Heat Exchanger Construction Standard A Cooling Staging 1 Variable Capacity Comp C Heat Type Natural Gas (Vertical Unit Configuration) B Heat Construction Stainless Steel Heat Exchanger, Gas Piping to the Valve 2 Heat Designation 150 MBH L Heat Staging High Turndown Modulating Gas Heat - Temperature Control 0 Heat Pump Auxiliary Heating No Auxiliary Heat
Date Created/Modified:5/13/2026 10:00:30 AM Using Performance Version:364.1 Date Printed:5/13/2026 10:06:07 AM
E F11A. Refrigeration Options A Modulating Hot Gas Reheat Microchannel Coil [MHGR-MC] 0 F11B. Refrigeration Options B Standard Packaged Unit A F12. Refrigeration Accessories Sight Glass A F13A. Unit Disconnect Type Single Point Power - Non-fused Disconnect Power Switch N F13B. Disconnect 1 Size 100 Amps 0 F13C. Disconnect 2 Size Standard - None E F14. Safety Options Remote Safety Shutdown Terminals B F15. Electrical Accessories Phase & Brown Out Protection N F16A. Control Sequence Field Installed DDC Controls + Isolation Relays 0 F16B. Control Supplier None 0 F16C. Control Supplier Options None 0 F16D. BMS Connection & Diagnostics None 0 F17A. Preheat Configuration Standard - None 0 F17B. Preheat Sizing Standard - None 0 F18A. Option Box Location None 0 F18B. Option Box Size None 0 F18C. Option Box Accessories None A F19. Outside Air Accessories Outside Air Hood 0 F20. Cabinet Options Standard - None 0 F21. Accessories Standard A F22. Maintenance Accessories Factory Wired 115V Convenience Outlet 0 F23. Code Options Standard - ETL U.S.A. Listing 0 F24. Shipping Splits Standard C F25. Air-Cooled Condenser Accessories ECM Condenser Fan Head Pressure Control 0 F26. Evap-Cooled Condenser Accessories Standard 0 F27. Water-Cooled Condenser Accessories None 0 F28. Energy Recovery Accessories None 0 F29. VFD Options Standard B F30. Miscellaneous Options SCCR (10kA) 0 F31. Blank Standard 0 F32. Blank Standard 0 F33. Blank Standard 0 F34. Blank Standard 0 F35. Warranty Standard Warranty 0 F36. Cabinet Material Galvanized Cabinet - Double Wall + R-16 Foam Insulation B F37. Specials & Paint Premium AAON Gray Paint Exterior Paint
Date Created/Modified:5/13/2026 10:00:30 AM Using Performance Version:364.1 Date Printed:5/13/2026 10:06:07 AM
A
A
B
A
A
A
A
-C
B
B
B
B
L
B
B
:0
-0
A
F
B
C
C
A
D
F
E
-Q
A
H
B
A
C
-0
A
B
C
D
E
-A
A
B
B
H
C
B
D
E
E
-E
C
-C
A
B
B
C
A
D
-0
A
B
-E
A
B
-A
-A
A
N
B
C
-E
B
-N
A
B
C
D
-0
A
B
-0
A
B
C
-A
A
-C
B
-0
B
Terminals 2425 South Yukon Ave • Tulsa, OK 74107 • Ph: (918) 583-2266
Ecat Price Version: 364.1
Date Printed:5/13/2026 10:06:07 AMDate Created/Modified:5/13/2026 10:00:30 AM Using Performance Version:364.1
Tag:
Readiness Center For:
Job Number: 1 Date: May 13, 2026
DOAS_1A
Terminals Available/Required for Controlling the Unit Terminals Decription
[R] 24VAC Control Voltage [C] Common [G] Supply Fan Enable + Isolation Relay [Y1] Cooling Stage 1 Enable + Isolation Relay
[DC1-] & [DC1+] Variable Capacity Compressor 1 (1.44-5VDC) Signal [SP1-] & [SP1+] Suction Pressure Sensor - Compressor 1 (0-5VDC)
[W1] Heating Stage 1 Enable + Isolation Relay [+] & [-] Gas Heat Reset Signal (0-10VDC)
Resets the supply air setpoint [Q1] & [Q2] Gas Heat Alarm
Dry contact terminals for alarm output (NC) [HW] Energy Recovery Wheel Enable + Isolation Relay [PE] Power Exhaust Enable + Isolation Relay
[B1-] & [B2+] Exhaust Fan 1 - w/ 1 VFD: Signal (0-10VDC) VFD frequency reference signal control point must handle a rated 20k ohm input impedance.
[S1-] & [S2+] Supply Fan 1 - w/ 1 VFD: Signal (0-10VDC) VFD frequency reference signal control point must handle a rated 20k ohm input impedance.
[EC1-] & [EC2+] Economizer Signal (0-10VDC) [C1] & [C2] Clogged Filter Switch (Standard Filters)
[RH1] Reheat Enable + Isolation Relay Must enable and modulate the digital compressors during dehumidification mode.The control logic needs to set if cooling or dehumidification is priority.
[AI1] & [COM] Reheat Reset Signal (0-10VDC)
Resets the Reheat Supply Air Temp Setpoint [BI1] & [BI2] Remote Safety Shutdown
[PBO1] & [PBO2] Phase & Brown Out
Terminations Found on VFD(s) Exhaust Fan VFD(s)
[AM] & [AC] Current Feedback (0-10VDC = 0-100%) [AM] & [AC] Current Feedback (0-10VDC = 0-100%)
Supply Fan VFD(s) [MA] & [MC] Fault [MA] & [MC] Fault
A2L Terminals [ALM1] & [ALM2] A2L Airstream Alarm & Cabinet Alarm
A2L Mitigation Board 1
P/N: ASM0763
A2L Mitigation Board 2
P/N: ASM0763
Date Printed:5/13/2026 10:06:07 AMDate Created/Modified:5/13/2026 10:00:30 AM Using Performance Version:364.1
FORMED UP
RAISE MINIMUM FOR THE
RETURN AIR AND ELEC
ENTRY OPENINGS.
HIGH VOLT
ENTRY
LOW VOLT
ENTRY
DETAIL A DETAIL B
DETAIL C
RAISE MINIMUM FOR THE
SUPPLY AIR OPENING
FORMED UP
3"
1 3"
1 1"
1"
1"
SEE DETAIL
"B"
EXHAUST AIR
SEE DETAIL
"C"
TOP VIEW
RNA-00027 REV:C 02/20/23 JWC
NOTE: ALL DIMENSIONS ARE IN INCHES
4 175
BLOWER
ACCESS
HEATWHEEL
RIGHT SIDE VIEW
SEE DETAIL
"B"
SEE DETAIL
"A"
SUPPLY
EXHAUST AIR
SEE DETAIL
"C"
O U
TS
ID
E A
IR
H
O O
D
35 1
8 1
RETURN
1" MPT STAINLESS CONDENSATE
CONNECTION.
HEATWHEEL
ACCESS
HEATWHEEL
FILTER
C O
IL
COMPRESSOR
ACCESS
12 3 4 247
8 27 13
BLOWER
SUPPLY COIL
COIL
ACCESS
FILTER ECON
HEATWHEEL
ACCESS
FILTER
ACCESS
RN SERIES A - CABINET
~ ECONOMIZER, ENERGY RECOVERY SECTION
AND POWER EXHAUST
~ 6-10 TON
OUTSIDE AIR
AIR
FLOW
2 RETURNSUPPLY
NOTE: THE RNA UNIT IS NOT COMPATIBLE
WITH PREVIOUS GENERATIONS OF AAON
CURBS. AN ADAPTER CURB IS
AVAILABLE IN ECAT.
CLEARANCES
LOCATION
OUTSIDE AIR
• UNIT SIZE •
6 - 10 TON
36*(BACK)
CONTROLS SIDE
(FRONT)
LEFT SIDE
RIGHT SIDE
TOP UNOBSTRUCTED
*CLEARANCE IS MEASURED FROM
THE END OF THE OUTSIDE AIR
RAIN HOOD
FRONT VIEW
INSIDE
BASE RAILS
ø11
GAS ENTRY
CONTROLS AND HEATER
ACCESS
POWER SWITCH
ACCESS COVER
CONTROLS AND HEATER
ACCESS
POWER SWITCH
ACCESS COVER
OUTSIDE
BASE RAILS
COMBUSTION AIR INLETS
(GAS HEAT ONLY)
CONDENSER
CONDENSER
FLUE OUTLET
(GAS HEAT ONLY)
COIL
COIL ACCESS
RN SERIES A - CABINET
6-10 TON
90/150/210 MBH
4 STAGE, HIGH TURNDOWN
Field gas piping is required to the internal gas valves.
Piping should be installed adhering to building codes.
Perform leak check prior to operation.
Reference IOM for additonal information, and details on optional gas entry through base.
REMOVABLE
KICKPLATE
HEAT
EXCHANGER 1
HXC 1
CAT000424 RNA REV A 04/25/23 JAS
ALL DIMENSIONS ARE IN INCHES
SIDE FRONT
TOP
3 5/8
5 3/161 5/8
5 7/8
Front Right Corner:
345 lbs
Back Left Corner:
424 lbs
Back Right Corner:
270 lbs
RNA-007-A-A-3-GAB0A-CB2L0:00-0FCAF-QHA-00000-ABHBE-EC-CB0A-00-E0-A-AN0-EB-N000-00-000-A00A00-C0000B-000000B
CGx: 51.1" CGy: 26.9"
1581 lbs
+X
+Y
Disclaimer:
This weight estimate does not account for any SPAs.
Front Left Corner:
541 lbs
RNA CABINET
AIR COOLED CONDENSING UNIT
WITH ENERGY RECOVERY SECTION
0"
0" 116"
44"
SUPPLY
O U
TS
ID
E A
IR
H
O O
D
RETURN
C
O
IL
RNA-015-B-A-3-G
A
A
A
A
A
A
A
-C
B
B
B
B
L
B
B
:0
-0
A
F
B
E
C
A
D
H
E
-G
A
B
C
-0
A
B
C
D
E
-A
A
B
B
G
C
B
D
H
E
-E
C
-C
A
B
B
C
A
D
-0
A
B
-E
A
B
-A
-A
A
N
B
C
-E
B
-N
A
B
C
D
-0
A
B
-0
A
B
C
-A
A
-C
B
-0
B
ACU_3ATag:
Job Information Job Name: WV ANG Logan Mingo Readiness
Center Job Number: 1 Site Altitude: 0 ft Refrigerant: R-454B Design System Charge (oz): 191 / 350
Unit Information Approx. Op./Ship Weights: 2198 lbs / 2198 lbs (±5%) Ambient Temperature (DB/WB): 95.0 °F / 75.0 °F Coil Filter FV / Qty: 378.0 fpm / 4 Min. Room Area/Height/Airflow**: 329 ft² / 7 ft / 592 SCFM Exhaust Airflow/ESP/TSP: 5250 SCFM / 0.25 in. w.g. / 0.71 in. w.g.
Supply Airflow/ESP: 5250 SCFM / 0.75 in. w.g.
Outside Airflow: 1115 SCFM Return Airflow/ESP: 5250 SCFM / 0.25 in. w.g.
Return Temperature (DB/WB): 75.0 °F / 62.0 °F
Static Pressure External: 0.75 in. w.g.
Cooling Coil: 0.35 in. w.g.
Filters Clean: 0.34 in. w.g.
Dirt Allowance: 0.35 in. w.g.
Reheat Coil: 0.07 in. w.g.
Economizer: 0.33 in. w.g.
Heater: 0.18 in. w.g.
Cabinet: 0.35 in. w.g.
Total: 2.71 in. w.g.
Heating Section Preheat Type: Std (No Preheat)
Auxiliary Heating Type: Nat. Gas Heat Heating Airflow: 5250 SCFM Total Capacity: 315.9 MBH Entering Air Temp (DB/WB): 55.1 °F / 43.7 °F Leaving Air Temp (DB/WB): 110.5 °F / 65.9 °F Consumption: 390.0 MBH Total Turndown Ratio: 10.0:1
Cooling Section Gross Net
Total Capacity: 186.2 MBH 175.6 MBH Sensible Capacity: 145.0 MBH 134.4 MBH Latent Capacity: 41.2 MBH
Supply Air Fan: 1 x 220D70 @ 3.71 BHP Ea.
SA Fan RPM / Width: 1767 RPM / 3.45 in SA Fan FEI: 1.18 Exhaust Air Fan: 1 x RM12X9X2-RN @ 2.46 BHP Ea.
EA Fan RPM / Width: 1063 RPM / EA Fan FEI: 0.62
Evaporator Coil: 14.6 ft² / 4 Rows / 14 FPI Evaporator Face Velocity: 360.0 fpm
Mixed Air Temp (DB/WB): 79.2 °F / 65.1 °F Entering Air Temp (DB/WB): 79.2 °F / 65.1 °F Lv Air Temp (Coil) (DB/WB): 53.5 °F / 52.8 °F Lv Air Temp (Unit) (DB/WB): 55.3 °F / 53.5 °F
Listing Model RN-015-3-0-GAAY-V0-21-000-A
Cooling Capacity: 166.0 MBH Cooling EER: 10.9 BTU/h·W Cooling IEER: 14.99 BTU/h·W
Rating Information
*Rated in accordance with AHRI Standard 340/360 (I-P)
Application EER @ Op. Conditions: 8.8 BTU/h·W
Re-heat Coil:
Capacity: 104.0 MBH Leaving Air Temp (DB/WB): 72.0 °F / 60.0 °F Relative Humidity: 49.8%
Electrical Data
2425 South Yukon Ave • Tulsa, OK 74107 • Ph: (918) 583-2266 Ecat Price Version: 364.1
Unit Rating
Date Printed:5/13/2026 10:04:53 AMPage 1 Of 2
Unit FLA:
Minimum Circuit Amp:
Maximum Overcurrent:
Qty HP VAC Phase RPM FLA RLA Compressor 1: 1 460 3 3500 12.8 Compressor 2: 1 460 3 3500 11.0 Condenser Fan: 2 1 460 1 1100 3.6 Supply Fan: 1 5 460 3 1760 7.6 Exhaust Fan: 1 3 460 3 1760 4.8 Combustion: 1 0.1 460 1 3000 0.3
460V/3Ø/60Hz
SCCR: 10 KAIC
Cabinet Sound Power Levels* Octave Bands: 63 125 250 500 1000 2000 4000 8000 Discharge LW (dB): 94 92 96 89 81 79 76 70 Return LW (dB): 90 86 86 76 73 68 59 52 *Sound data is generated by a propriety acoustics model validated through unit testing in accordance with AHRI 260, utilizing tested fan sound data in accordance with AMCA 300.
**The minimum floor area is based on the Lower Flammability Limit (LFL) and calculated in accordance with UL60335-2-40 4th ed. (operating or storage). For UL60335-2-40 3rd ed. double the airflow and minimum floor area listed.
The minimum airflow (Qmin) is the minimum allowable airflow for any operating condition.
2425 South Yukon Ave • Tulsa, OK 74107 • Ph: (918) 583-2266 Ecat Price Version: 364.1
Unit Rating
Date Printed:5/13/2026 10:04:53 AMPage 2 Of 2
Readiness Center Job Tag ACU_3A Date 5/13/2026 10:00:30 AM
Max RPM 2200 Diameter x Qty 22 in. x 1
CFM 5250
Inertia 5 WR²
OPERATING CONDITIONS MOTOR SELECTION
Airflow 5250 Fan Energy Index (FEI) 1.18 Static Pressure 2.71 in. w.g.
Relief Dampers DP 0.00 in. w.g.
TSP 2.71 in. w.g.
Site Altitude 0
Rated HP / Bypass 5 x 1 / No Frame Size 184T Nominal RPM 1760 VAC/PH/Hz 460V/3Ø/60Hz Enclosure Type ODP Max Inertial Load 0 WR²
FAN PERFORMANCE: FAN SOUND POWER (Inlet/Outlet)
RPM 1767
BHP 3.71
Efficiency 60.5% Max Duct SP with Blocked Airway
4.70 in. w.g. @ 1767 RPM
Octave Band: (Re 10^-12 watts) 1 2 3 4 5 6 7 8
93 91 96 90 84 82 80 74 93 91 96 90 84 82 80 74
SOUND POWER A-Weighted: 95 dB
2425 South Yukon Ave • Tulsa, OK 74107 • Ph: (918) 583-2266
Ecat Price Version: 364.1
22" STAR Plenum
Date Printed:5/13/2026 10:04:54 AM
Ecat Price Version: 364.1
RM12X9X2 FC Fan
JOB INFORMATION: WHEEL SPECIFICATION:
Job Name WV ANG Logan Mingo
Readiness Center Job Tag ACU_3A Date 5/13/2026 10:00:30 AM
Max RPM 1440 Diameter x Qty 11 in. x 1
CFM 5250
Inertia 3 WR²
FAN PERFORMANCE FAN SOUND POWER (Inlet/Outlet)
RPM 1063
BHP 2.46
Efficiency 23.9% Max Duct SP with Blocked Airway
1.30 in. w.g. @ 1063 RPM
Octave Band: (Re 10^-12 watts) 1 2 3 4 5 6 7 8
88 84 75 72 70 64 59 54 88 84 75 72 70 64 59 54
SOUND POWER A-Weighted: 88 dB
OPERATING CONDITIONS MOTOR SELECTION
Airflow 5250 Fan Energy Index (FEI) 0.62 Static Pressure 0.71 in. w.g.
Relief Dampers DP 0.00 in. w.g.
TSP 0.71 in. w.g.
Site Altitude 0
Rated HP / Bypass 3 x 1 / No Frame Size 182T Nominal RPM 1760 VAC/PH/Hz 460V/3Ø/60Hz
A
A
A
A
A
A
A
-C
B
B
B
B
L
B
B
:0
-0
A
F
B
E
C
A
D
H
E
-G
A
B
C
-0
A
B
C
D
E
-A
A
B
B
G
C
B
D
H
E
-E
C
-C
A
B
B
C
A
D
-0
A
B -E
A
B
-A
-A
A
N
B
C
-E
B
-N
A
B
C
D
-0
A
B
-0
A
B
C
-A
A
-C
B
-0
B
Unit Submittal 2425 South Yukon Ave • Tulsa, OK 74107 • Ph: (918) 583-2266
Ecat Price Version: 364.1
Tag:
Job Name: WV ANG Logan Mingo
Readiness Center Unit Worksheet For:
Job Number: 1 Unit Worksheet Date: 5/13/2026
ACU_3A
Feature Option Description
0 F1. Unit Orientation Standard Access - Hinged Access Doors with Lockable Handles 0 F2. Supply & Return Locations Bottom Supply--Bottom Return 0 F3A. Supply Fan Quantity 1 Fan F F3B. Supply Fan Configuration 1 Fan per VFD + Narrow Width Fan E F3C. Supply Fan Size 22" Direct Drive Backward Curved Aluminum A F3D. Supply Fan Motor Type High Efficiency Open Motor (1,800 nominal rpm) H F3E. Supply Fan Motor Size 5 hp G F4A. Outside Air Section Economizer + Power Exhaust 0 F4B. Energy Recovery Type No Energy Recovery 0 F4C. Energy Recovery Size No Energy Recovery 0 F5A. Return Fan Quantity 0 Return Fans 0 F5B. Return Fan Configuration No Return Fan 0 F5C. Return Fan Size No Return Fan 0 F5D. Return Fan Motor Type No Return Fan 0 F5E. Return Fan Motor Size No Return Fan A F6A. Exhaust Fan Quantity 1 Fan B F6B. Exhaust Fan Configuration 1 Fan per VFD + Full Width Fan G F6C. Exhaust Fan Size 12x9 Forward Curved B F6D. Exhaust Fan Motor Type High Efficiency Open Motor (1,800 nominal rpm) H F6E. Exhaust Fan Motor Size 3 hp E F7. Outside Air Control DDC Actuator C F8. Return and Exhaust Air Options Standard Barometric Relief EA Dampers C F9A. Unit Filter Type 2" Pleated MERV 8 + 4" Pleated MERV 13 B F9B.