GA Drawing S5103-202P-(M-GA01)-V112030276-01_4.pdf

PDF 882 KB Posted

Attached to
Y1DA--Project 671-18-106, Replace Water Softeners - San Antonio
Solicitation number
36C25722B0024
Issued by

About this file

This document contains general arrangement drawings for a 60-inch by 72-inch duplex multimedia, carbon, and softener pre-treatment system. The drawings provide details on the equipment specifications, dimensions, component layout, connection points, fabrication and machining tolerances. Key specifications include a skid length of 145 inches, width of 99 inches, and height of 146 inches. The dry weight is listed as 5,691 pounds. Connection sizes and material types are indicated for the service inlet, outlet and drain, as well as the brine inlet, high point vent, and pressure relief valve discharge. Options for separate source backwash and a dissolved phosphate system are noted.

The related federal contract opportunity is solicitation number 36C25722B0024 for Project 671-18-106 to replace water softeners at the San Antonio location of the Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 17. The opportunity type is listed as a solicitation.

View the file

Other files

File Type Posted
Amendment 36C25722B0024 0004.docx DOCX document
Answers for 671-18-106 Replace Water Softeners with VA and A.E Responses.pdf PDF
Panel Board PIC IMG_0325.pdf PDF
Panel Board PIC IMG_0320.pdf PDF
Panel Board PIC IMG_0318.pdf PDF
Panel Board PIC IMG_0317.pdf PDF
Panel Board PIC IMG_0319.pdf PDF
Amendment 36C25722B0024 0003.docx DOCX document
Panel Board PIC IMG_0322.pdf PDF
CBB PANEL CIRCUIT.pdf PDF
CBA PANEL CIRCUIT.pdf PDF
COA PANEL CIRCUIT.pdf PDF
Panel Board PIC IMG_0323.pdf PDF
Panel Board PIC IMG_0321.pdf PDF
Panel Board PIC IMG_0324.pdf PDF
Amendment 36C25722B0024 0002.docx DOCX document
All 671-18-106 Water Softener Sign-In Walkthrough sheet.pdf PDF
Appendix D - Brine Tank Assessment Report_Redacted.pdf PDF
As Built 1-W2 Main.PDF PDF
Appendix E - Structural Observation Report_Redacted.pdf PDF
As Built Fuel Tank File 2 of 3.pdf PDF
As Built 12-725 Hazardous Storage Pad Sht C01.PDF PDF
Amendment 36C25722B0024 0001.pdf PDF
As Built I-S127.pdf PDF
As Built Fuel Tank File 1 of 3.pdf PDF
671-18-106 Design Analysis Report FINAL_Redacted.pdf PDF
As Built 1-W Warehouse.PDF PDF
Appendix G - GPR Scan Report and Findings_Redacted.pdf PDF
As Built 1-W3 Main.PDF PDF
As Built I-P70.pdf PDF
As Built Fuel Tank File 3 of 3.pdf PDF
As Built I-W12.pdf PDF
As Built 1-W1 Main.PDF PDF
Attachment 671-18-106 Construction Specifications.pdf PDF
OSHA - EMR requirement.pdf PDF
Attachment 671-18-106 Construction Drawings.pdf PDF
Attachment Replace Water Softeners - Requested Structural Drawings.pdf PDF
Addendum to SOW.pdf PDF
VA NOTICE OF LIMITATIONS ON SUBCONTRACTING REQUIREMENT.pdf PDF
SELF-PERFORMED CALCULATIONS.pdf PDF
Solicitation 36C25722B0024_1.docx DOCX document
Show all 41

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

TITLE

CLIENT

PROJ/PROD NUMBERPART NUMBER FILE/DRAWING NUMBER SHEET

OF

REV

S5103-202P V112030276 41 2

EQUIPMENT GENERAL ARRANGEMENT

60'' X 72" DUPLEX MULTIMEDIA / CARBON / SOFTENER, DELUXE

PRE-TREATMENT INDUSTRIAL

STANDARD PRODUCTS

CO

DWN BY: DATE

DATE

DATE

CKD BY:

APPD BY:

MGD BY:

CODE

SCALE

JRI

MRI

MEC

WGW

2018-10-08

2018-10-08

2018-10-08

M-GA01

NTS

COMPANY CONFIDENTIAL INFORMATION

THIS DOCUMENT AND ALL INFORMATION CONTAINED

HEREIN, INCLUDING THE DESIGN CONCEPTS AND THOSE

ARISING THEREFROM ARE THE PROPERTY OF EVOQUA

AND/OR ITS AFFILIATES AND ARE SUBMITTED IN

CONFIDENCE. THEY MAY BE USED ONLY FOR THE

EXPRESS PURPOSE FOR WHICH THEY ARE PROVIDED AND

MUST NOT BE DISCLOSED, REPRODUCED OR COPIED IN

ANY FORM, INCLUDING IN ELECTRONIC FORMAT, LOANED

OR USED IN ANY OTHER MANNER WITHOUT THE EXPRESS

WRITTEN CONSENT OF EVOQUA. ALL PATENT RIGHTS ARE

RESERVED. THIS DOCUMENT AND DERIVATIVE WORKS

THEREOF ARE PROTECTED UNDER APPLICABLE

COPYRIGHT LAWS. UPON DEMAND OF EVOQUA, THIS

DOCUMENT, ALONG WITH ALL COPIES AND EXTRACTS,

AND ALL RELATED NOTES AND ANALYSES MUST BE

RETURNED TO EVOQUA OR DESTROYED, AS INSTRUCTED

BY EVOQUA. ACCEPTANCE OF THE DELIVERY OF THIS

DOCUMENT CONSTITUTES AGREEMENT TO THESE TERMS.

EVOQUA WATER TECHNOLOGIES

COLORADO SPRINGS, CO, USA

+1 719-570-9600

WATER TECHNOLOGIES

S T

D x D v

B A

R

A

T

P

L O

T

S

C A

L E o c

G r o u p

D r a w i n g s c

T y p e

M e c h a n i c a l

A

7 6 5 4 3 2 1

B C

D

NOTES:

1. ALL DIMENSIONS ARE IN INCHES. ALL TOLERANCES ARE +/- 1/2".

2. ALL BOLT HOLE PATTERN OF FLANGES TO STRADDLE PRINCIPLE CENTER LINE OF PIPE.

3. ALL GASKETS TO BE EPDM.

4. ALL CONDUIT TO BE EMT (STD).

5. ALL WEIGHTS ASSOCIATED WITH GENERAL ARRANGEMENT DRAWINGS ARE NOMINAL.

6. ALL MOUNTING HARDWARE TO BE ZINC PLATED CARBON STEEL.

7. ALL INSTRUMENTATION TUBING IS P.E. STATICALLY PRESSURE TESTED TO 80 PSIG.

8. ALL INSTRUMENTATION, TIMERS, ETC. SHOULD BE CHECKED FOR PROPER SETUP AND/OR

CALIBRATION AT TIME OF START-UP.

9. ALL MANUAL VALVES AND HANDLES ARE TO BE ACCESSIBLE AND CLOSED PRIOR TO

SHIPMENT.

10. TAGS ARE EVOQUA STANDARD LAMICOID WITH WHITE BACKGROUND AND BLACK TEXT,

HUNG WITH PLASTIC TIE WRAPS.

11. REMOVE VALVES (HV-07 X) AND PRESSURE RELIEF VALVES (PSV-01X) FOR SHIPPING.

OPTIONS

SEPERATE SOURCE

BACK WASH

TURBIDITY (MMF)

CHLORINE (CARBON)

HARDNESS (SOFTNER)

DPS

NO OPTIONS

GENERAL ARRANGEMENT

SPECIFICATIONS

SKID LENGTH 145"

SKID WIDTH 99"

SKID HEIGHT 146"

WEIGHT DRY 5691 LBS

WEIGHT WET

(OPERATING)

SEE SPECS

4 INVENTOR TRANSITION 2020-07-10 CDK PVM JMP

3 SEE ECN DATABASE 2018-07-13 JF JF JF

REV DESCRIPTION DATE DWN CKD APPD ECN

DPS, STANDARD ON MMF,

OPTIONAL CARBON/SOFTENER

FV-01B

SP-01B

24'' X 24'' X 12''

PANEL

FV-03A

FV-07A

FV-06A

FV-02A

HV-02A

FV-01A

THIRD ANGLE PROJECTION

TK-01A

TK-01B

FV-04B

FV-04A

FV-05A

FV-05B

FV-07B

PI-01B

PI-02

TAKE-OFF FOR DPS

(WHEN DPS IS PRESENT)

BLIND FLANGE WHEN

SSBW IS NOT USED, 2 PL

SEPARATE SOURCE

BACKWASH KIT

(OPTIONAL)

TAKE-OFF FOR DPS

(WHEN DPS IS PRESENT)

BRINE VALVE STANDARD

ON SOFTENER ONLY

(BLIND FLANGE OTHERWISE)

CONNECTION POINTS

CONNECTION SIZE TYPE DESCRIPTION

A 1-1/2" 316L SS CLASS 150 FLANGE

BRINE INLET (SOFTENER ONLY)

B 4" 316L SS CLASS 150 FLANGE SERVICE INLET

C 4" 316L SS CLASS 150 FLANGE SERVICE OUTLET

D 4" 316L SS CLASS 150 FLANGE

TO DRAIN (CONNECT TO FLOOR DRAIN)

E 1" 316L SS CLASS 150 FLANGE

HIGH POINT VALVED VENT (TO BE FIELD PIPED TO WITHIN

8"-12" FROM FLOOR)

F 1" CS FNPT

PRESSURE RELIEF VALVE (TO BE FIELD PIPED TO DRAIN)

G 4" 316L SS CLASS 150 FLANGE

SEPARATE SOURCE BACKWASH (OPTIONAL)

FV-03B

HV-01B

HV-02B

FV-06B

FV-02B

SP-01A

E

E

A

B

G

HV-01A

PI-01A

F

F

FABRICATION MACHINING

.XX ± .06

[X] ± 2

ANG ± 2°

.XX ± .03

.XXX ± .005

[X] ± 1

[.X] ± .1

ANG ± 1°

TOLERANCES

UNLESS OTHERWISE SPECIFIED

PSV-01A

PSV-01B

ANCHOR HOLE DETAIL

SECTION A-A

A A

S T

D x v

B A

R

A

T

P

L O

T

S

C A

L E c

G r o u p

D r a w i n g s c

T y p e

M e c h a n i c a l

A

7 6 5 4 3 2 1

B C

D

TITLE

CLIENT

PROJ/PROD NUMBERPART NUMBER FILE/DRAWING NUMBER SHEET

OF

REV

S5103-202P V112030276 42 2

EQUIPMENT GENERAL ARRANGEMENT

60'' X 72" DUPLEX MULTIMEDIA / CARBON / SOFTENER, DELUXE

PRE-TREATMENT INDUSTRIAL

STANDARD PRODUCTS

CO

DWN BY: DATE

DATE

DATE

CKD BY:

APPD BY:

MGD BY:

CODE

SCALE

JRI

MRI

MEC

WGW

2018-10-08

2018-10-08

2018-10-08

M-GA01

NTS

COMPANY CONFIDENTIAL INFORMATION

THIS DOCUMENT AND ALL INFORMATION CONTAINED

HEREIN, INCLUDING THE DESIGN CONCEPTS AND THOSE

ARISING THEREFROM ARE THE PROPERTY OF EVOQUA

AND/OR ITS AFFILIATES AND ARE SUBMITTED IN

CONFIDENCE. THEY MAY BE USED ONLY FOR THE

EXPRESS PURPOSE FOR WHICH THEY ARE PROVIDED AND

MUST NOT BE DISCLOSED, REPRODUCED OR COPIED IN

ANY FORM, INCLUDING IN ELECTRONIC FORMAT, LOANED

OR USED IN ANY OTHER MANNER WITHOUT THE EXPRESS

WRITTEN CONSENT OF EVOQUA. ALL PATENT RIGHTS ARE

RESERVED. THIS DOCUMENT AND DERIVATIVE WORKS

THEREOF ARE PROTECTED UNDER APPLICABLE

COPYRIGHT LAWS. UPON DEMAND OF EVOQUA, THIS

DOCUMENT, ALONG WITH ALL COPIES AND EXTRACTS,

AND ALL RELATED NOTES AND ANALYSES MUST BE

RETURNED TO EVOQUA OR DESTROYED, AS INSTRUCTED

BY EVOQUA. ACCEPTANCE OF THE DELIVERY OF THIS

DOCUMENT CONSTITUTES AGREEMENT TO THESE TERMS.

EVOQUA WATER TECHNOLOGIES

COLORADO SPRINGS, CO, USA

+1 719-570-9600

WATER TECHNOLOGIES

42" CLEARANCE

REQUIRED FOR

PANEL

8 9/16"

72"

144 1/2"

OVERALL

145 11/16"

OVERALL

98 3/4"

OVERALL

24 1/4"

HV-03B

FE-02

C D

132 3/16"

64"

10 3/8"

15 1/2"

40 3/4"

60 1/4"

85 3/4"

40 3/4"

55 7/8"

119 7/8"

SP-02B

40 3/4"

49"

16 5/8"

HV-03A

SP-02A

SG-01

FE-01

MANUFACTURING TO LOCATE CENTER OF HMI SCREEN BETWEEN

4'6" AND 5'2" FROM BOTTOM OF FRAME

9 1/8"

35°

26 1/4"

26 1/4"

57 15/16"

31 5/8"

2" 52 7/8"

13 7/16"

52 7/8"

58 5/8"

15/16"

1" TYP

46 11/16"

2" 119 3/16"

1" THRU HOLE

7 PL

2"

C

A

D

BG

9 1/4"

10 1/4"

A

G B

139 3/16"

F

E

21 3/4"

C

A

B

G

D

E

Christina Moody Callout

MOVE PANEL TO FRONT (REDUCE 12" ON LENGTH)

Christina Moody Callout

DUPLEX MODIFIED LENGTH: 132.5"

Christina Moody Callout

QUADPLEX LENGTH: 272" (ADDED 6" FOR INSTALLATION/PIPING CONFIGURATION)

OVERALL LENGTH: 22'-8"

File details come from the government source that posted it. Updated .