This structural observation report documents site conditions at the Audie L. Murphy VA Hospital in San Antonio, Texas. The report describes heavy efflorescence, delamination, and signs of corrosion in the masonry walls surrounding the hospital's water softener room. Specific issues noted include salt deposits along joint lines, separation of walls, cracking around the perimeter, and a heavily cracked and warped brine tank lid. The related federal contract opportunity is solicitation number 36C25722B0024 from the Department of Veterans Affairs for project 671-18-106 to replace the hospital's water softeners in San Antonio.
View the file
Other files
Show all 41
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
APPENDIX E – STRUCTURAL
OBSERVATION REPORT
U.S. DEPARTMENT OF VETERANS AFFAIRS
AUDIE L. MURPHY MEMORIAL VA HOSPITAL
SAN ANTONIO, TEXAS
FIELD OBSERVATION REPORT
To:
For
From: .
For
Report Date: 10-09-19 Field Date: 10-08-19
Site: Audie L Murphy VA Hospital – San Antonio, TX
RE: Structural Site Visit – Water Softener Room and Brine Tank Report No.: PE-01577 – FR001
Person(s) Contacted:
Engineering), This report summarizes general conditions at the jobsite at the time of the actual field observation only. Conditions before or after the date(s) and time(s) indicated are not addressed in this report.
Weather Conditions: Time of Visit: 11 a.m.
Cool, Dry
Items Observed:
Water Softener Room, Brine Tank Location (Exterior Only)
Pierce Engineering 2
PE-01577-FR001
Additional Comments:
Water Softener Room
1. Heavy efflorescence, delamination, and signs of corrosion were observed in the masonry walls surrounding the room. The most extensive damage was observed near the bases of the walls. Damage was observed on both sides of the walls all around the room. The heaviest deposits of salts are found along the joint lines. Refer to Figure 1 and 2.
Figure 1. Salt Deposits.
Figure 2. Delamination of CMU Face Shell.
Pierce Engineering 3
2. The tops of the southern, eastern, and western walls surrounding the room were observed from an opening in the ceiling. The walls do not extend to the floor framing above and do not appear to be load-bearing. The northern wall appears to bypass a concrete beam, but how or if there is a connection could not be verified.
3. The eastern wall has separated from the northern wall or the joint filler has deteriorated.
4. Miscellaneous cracking of the walls was observed around the perimeter of the room. Refer to Figure 3.
Figure 3. Random Cracking.
5. The metal door frames are heavily corroded near the bottoms.
6. The upper surface of the floor slab has delaminated throughout the water softener room.
Pierce Engineering 4
Brine Tank
1. The surface of the brine tank was observed. The tank top is heavily cracked and warped. Refer to Figure 4.
Figure 4. Brine Tank Lid.
Please call if you have questions or need additional information.