Question__5.docx
DOCX document 14 KB Posted
- Attached to
- Renovate Command Post B-418 Federal contract opportunity
- Solicitation number
- FA6712-15-R-0004
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| Second_Site_Visit_Notice.docx | DOCX document | |
| Addendum_2_amendment.doc | DOC document | |
| 27_15_00__Data_Cabling.docx | DOCX document | |
| Addendum_2_JLSS_12-0010.docx | DOCX document | |
| Questions__4.docx | DOCX document | |
| Questions__3.docx | DOCX document | |
| Addendum_1_JLSS_12-0010.docx | DOCX document | |
| Amendment_One.pdf | ||
| A002CPPL_REVISION_1.pdf | ||
| Questions__2.docx | DOCX document | |
| Sign-In_Sheet_Site_Visit.pdf | ||
| Question__1.docx | DOCX document | |
| Drawings.zip | ZIP file | |
| Drawings.zip | ZIP file | |
| Past Performance Questionnaire Command Post.docx | DOCX document | |
| 911 B418 Construction Bid Specifications.pdf | ||
| PA1 13 Feb 15 Mod 5.txt | TXT text file | |
| FA6712-15-R-0004 Rpr Command Post.doc | DOC document |
Show all 18
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
1. The location of door DA-104A falls in the middle of the existing wall mural. What is the expectation for painting the wall around the new door?
Drawing A-4 notes "Paint to match adjacent walls" at location of existing door filled in with CMU block. Any disturbance caused by demo for new doorways DA-104A and DE-100A should be touched up with matching solid gray paint.
2. There is an IBR repeater or LAN hub mounted on the hanger wall in the new aisle way created by moving the fence. Will this stay or will it need to be moved?
Did not see anything like that in the new aisle, although there is a PA amplifier mounted to the wall near the mural. If there is anything in the way of the two doorways being opened up, such as the amp, conduits, water lines, etc. they will need to be relocated. The new aisle created by the fence will be wide enough that anything mounted anywhere else on the wall can stay (except maybe the TV).
3. What volts for the generator and what phase? 120/208 V 3 phase
There was a mention of a filter on a panel , what is this? note 13 on Drawing E4 What is the catalog number and manufacture? Refer to note 13.
All the information is in this note. It is an RFI filter. Filtron is the manufacturer. FSR-W Powerline Series is the model.