FA4897-16-R-0005
ATTACHMENT 2
STATEMENT OF WORK
Project: QYZH 15-1234 Title: Construct Warehouse Project Manager:
Facility: XYZ Period of Performance: 120 Days Liquidated Damages: Does not apply to this task order Submittals: See attached document Government Furnished Material: None The following is a list of requirements pertaining to this delivery order:
Concrete
1. Foundation will be in accordance with building manufacturer’s requirements
2. FFE shall be 2996.0
3. Flatwork shall be designed per “Warehouse Assumptions”
4. Warehouse shall be sealed concrete. Smooth trowel finish.
5. Include landings outside exterior doors
Masonry
6. Masonry walls shall extend 8’ above floor elevation and consist of 8” CMU, split face, and fluted, running bond, water sealed at exterior, solid grouted with #5 vertical and horizontal bars
7. Screen wall near double entrance shall be same height as other masonry
Metals
8. Upper exterior walls shall be metal vertical siding, to 20’ above FFE at eaves.
Thermal and Moisture Protection
9. Roof shall be metal framed, 12/2 pitch SSM, insulated to R30
10. Insulation for the building shall be in compliance with ANSI/ASHRAE/IES Standard
90.1-2010 for Climate Zone 5
Openings
11. Install 12’x12’ electrically operated, insulated rollup door centered on gable end
12. All doors HM with HM frame, enamel paint, Best compatible cylindrical locksets
13. Exterior doors shall be insulated
14. Main exterior doors shall be 6’0” x 7’0” x 1-3/4” with vision light
15. Single exterior door shall be 3’0”x7’0” x1-3/4” with vision light
16. Double utility room doors shall be 6’0” x 7’0” x 1-3/4”
17. Double interior doors shall be 6’0” x 7’0” x 1-3/4” with vision light
18. Single interior door shall be 3’0”x7’0” x1-3/4”
19. 1.5 pr. Hinges on each door
20. Use heavy duty closers on all doors
21. Install four windows, 4’ x4’ fixed, bronze anodized, blast resistant glass
Finishes
22. Administrative section shall consist of:
Two offices ADA accessible men’s and women’s latrine Break area Mechanical room Mop closet
23. Partition walls shall be metal studs
24. Wall between administrative area and warehouse shall be full height
25. Interior walls shall be 5/8” GWB type X, taped, textured, primed and painted. Latrine and mop room will have FRP up to 4’.
26. Office areas shall be carpeted, other areas shall be VCT
27. Latrines and mechanical room have hard ceilings
28. Suspended ceilings in office and entry area shall be 2’x4’ tegular,with an 8’ interior height
Specialties
29. Install Knox box adjacent to main entrance
30. Install 10 lb. ABC extinguisher at each exterior entrance in surface mount cabinet
31. Install bathroom accessories and partitions
32. Break room shall have 6’ base and wall cabinets with sink and space for 25 c.f.
refrigerator
Fire Suppression
33. Install wet pipe fire sprinkler system throughout
Plumbing
34. Tap existing 8” concrete sewer and install new lateral
35. Tap existing 10” water main, install curb stop and new lateral
36. Male latrine has one elongated bowl flushometer toilet, one urinal, two wall hung lavatories
37. Female latrine has two elongated bowl flushometer toilets, two wall hung lavatories
38. Install tankless water heater
39. Install refrigerated drinking fountain
40. Install single basin sink in break area
41. Install floor sink in mop closet
HVAC
42. HVAC in office areas shall be natural gas fired, forced air ducted with refrigerated cooling
43. HVAC in warehouse shall be natural gas fired unit heaters and evaporative cooling
44. Evaporative coolers shall be ground level and incorporate force protection requirements
Electrical
45. Lights in office areas shall be 4’ LED troffers with occupancy sensors
46. Lights in latrines shall be 4’ surface mount LED fixtures with occupancy sensors
47. Locate LED exit/emergency lights at exterior doors
48. Install office receptacles at residential spacing
49. Electrical service shall be two 400 amp, three phase electrical panels with exterior disconnect
50. Install duplex receptacles in warehouse at 20’ intervals
51. Warehouse high bay lighting shall be LED with occupancy sensors
52. Install photo cell control light above each exterior door
Communications
53. Install one telephone board in utility room with ground and receptacle
54. Install one 48 port Ortronic cat.6 patch panels for phone and data
55. Install duct for fiber optic cable to enter building
56. Install conduit and 10 boxes with cat 6 cable
57. Provide 10 quad jacks and faceplates
Earthwork
58. Apply termiticide in accordance with U.F.C.
59. Grade native soil at 2% slope away from building for 100’ around facility, 6” below
F.F.E.
Electronic Safety & Security
60. Install conventional FACP interfaced with Monaco D-21M wireless fire alarm reporting system
61. Install horn/strobe devices as required by code
62. Install manual pull stations at each exit