Site Visit Minutes 20241018.pdf

PDF 186 KB Posted

Attached to
Substation Maintenance Services Vandenberg Space Force Base Federal contract opportunity
Solicitation number
FA461024Q0028
Issued by
Department of the Air Force Space Command

About this file

This document contains the minutes from a site visit for a federal contract opportunity related to substation maintenance services at Vandenberg Space Force Base (VSFB). The key details are:

The solicitation is for a Request for Quote (RFQ) for Substation Maintenance commercial services at VSFB, with a NAICS code of 237130 (Power and Communication Line and Related Structures Construction) under a 100% Small Business Set-Aside. The contract will be Firm Fixed Price (FFP) with work items and quantities listed in the Performance Work Statement. A pre-proposal conference and site visit will be held on 15 October 2024, with proposals due by 31 October 2024. The government reserves the right to cancel the solicitation. Interested offerors must be registered in SAM. Questions must be submitted by 23 October 2024 via email.

View the file

Other files for this federal contract opportunity

Show all 13

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

DEPARTMENT OF THE AIR FORCE

UNITED STATES SPACE FORCE

SPACE LAUNCH DELTA 30

Substation Maintenance Site Visit Minutes 1515 Iceland Ave Bldg. 8500, Rm 150 Vandenberg AFB, CA 93437 15 October 2024

10:20AM-2:00PM PST

Attendees:

Jessica Rowe Kristofer Clark Susan Amerison-Hicks Samantha Dominguez Dennis “Lefty” Pakulski Sean Poindexter Christopher Torres Kenneth Allis Nhan Le Brett Hartshorne Larry Limoges Gerardo Lozano

Substation E

1. Dennis Pakulski stated that it was okay for contractors to take pictures of the switchyards.

2. Dennis Pakulski stated that there are nine (9) switchyards, each have a switch house which is not apart of this requirement.

3. Dennis Pakulski stated that CES prescribes the maintenance/repairs/tasks that need to be done and how often to do the diagnostic and cleaning.

4. There is one (1) transformer and three (3) circuit breaker on this switchyard.

Substation A

1. There are two (2) transformers and no circuit breakers on this switchyard.

Main Switching Station

1. Air disconnects belong to VSFB, which is in the small rectangle fence. This is apart of this requirement along with everything within the big rectangle fence. The big power poles located outside these two fences belong to PG&E.

2. It is the contractor’s responsibility to keep a well lite switchyard, i.e., changing light bulbs.

Substation D

1. There are two (2) transformers and five (5) dry air circuit breakers on this switchyard.

2. Insulator decontamination will change based on the type of bushings/insulator.

Substation F

1. There are two (2) transformers and five (5) circuit breakers on this switchyard.

2. This is a tight yard to work within.

Substation B

1. There are three (3) transformers and seven (7) circuit breakers on this switchyard

Substation C

1. There is one (1) transformer and three (3) dry air circuit breakers on this switchyard.

2. The Contractor will need to have a vendor for gas, SF6 and nitrogen.

Substation K

1. There are two (2) transformers and five (5) SF6 circuit breakers on this switchyard.

2. This switchyard has a resister bank.

3. Contractor will have to use materials that don’t corrode, being so close to the ocean.

Substation N

1. Has ground neutral resister bank.

2. There are two (2) transformers and five (5) SF6 circuit breakers.