Add_1_SECTION_15_20_00_DOMESTIC_WATER_PIPING.pdf

PDF 13 KB Posted

Attached to
Renovate Student Dorms Winters Manor
Solicitation number
FA3010-14-R-0006
Issued by

About this file

Addendum 1 Section 15 20 00

View the file

Other files

File Type Posted
RFI's_Winters_Manor.pdf PDF
SECTION_10_10_00_DISPLAY_CASES.pdf PDF
Section_12_48_23_Entrance_Floor_Grids.pdf PDF
FA3010-14-R-0006-0007.pdf PDF
MAHG10-1032_PAE_addendum_3.pdf PDF
Amendment_0006.pdf PDF
Amendment_0005.pdf PDF
Add_2_SECTION_12_36_00_COUNTERTOPS.pdf PDF
MAHG101032_Addendum_2.pdf PDF
Amendment_0004.pdf PDF
Winters_Manor_Additional_QA.pdf PDF
MAHG101032_Addendum_1_RFIs.pdf PDF
Add_1_Section_07_56_00_Fluid_Applied_Roofing.pdf PDF
Add_1_SECTION_16_11_00_RACEWAYS.pdf PDF
Amendment_0003.pdf PDF
Add_1_SECTION_15_40_00_PLUMBING.pdf PDF
Add_1_SECTION_16_72_60_PUBLIC_ADDRESS_AND_MASS_NOTIFICATION_SYSTEMS.pdf PDF
Add_1_SECTION_08_11_13_STEEL_DOORS_AND_FRAMES.pdf PDF
Add_1_SECTION_09_68_13_TILE_CARPETING.pdf PDF
Add_1_SECTION_16_50_00_LIGHTING.pdf PDF
Add_1_SECTION_16_00_00_GENERAL_PROVISIONS-ELECTRICAL.pdf PDF
Add_1_MAHG10-1032_Drawing_Sheets_Revision_01_5_21_14.pdf PDF
Amendment_0002.pdf PDF
Amendment_0001.pdf PDF
Site_Visit_Sign_In.pdf PDF
Attachment_5_Past_Performance_Reference_List.pdf PDF
Solicitation.pdf PDF
MAHG101032_Repair_student_Dorm_7404_SPECIFICATIONS.pdf PDF
MAHG101032_DRAWINGS_2013-2-20.pdf PDF
Attachment_4_Performance_Questionnaire.pdf PDF
Attachment_6_SF_1444.pdf PDF
Attachment_6_Instructions.pdf PDF
WD_MS140119.pdf PDF
Show all 33

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

MAHG10-1032

SECTION 15 20 00 - DOMESTIC WATER SYSTEM

PART 1 - GENERAL

1.01 SOURCE

A. The water source shall be from the 6" PVC water line installed as part of this project, as indicated on the Drawings.

1.02 INTERIOR WATER PIPING

A. Materials: Piping shall be Type M, hard-drawn copper conforming to ASTM-B-88. Water piping under concrete slabs shall be Type K soft drawn without joints. Two inch water lines under slab can be Type K with silver soldered joints.

B. Fittings: Fittings for copper tubing shall be cast brass or wrought copper, sweat pattern.

C. Installation: Pipe and tubing shall be cut accurately to measurements established at the building by the Contractor and shall be worked into place without springing or forcing. Piping shall run parallel with the lines of the building unless otherwise shown or noted on the Drawings.

D. Joints: Tubing shall be cut square and burrs shall be removed. Both sides of fittings and outside of tubing shall be well cleaned with steel wool before sweating. Joints for soldered fittings shall be made with a non-corrosive paste flux and solid string or wire solder composed of 95 percent tin and 5 percent lead. Joints for flared type fittings shall be of compression pattern. Brazed joints shall be made with silver solder, Classes 4 and 6. Swing joints shall be provided on all branch connections to mains and risers to provide for expansion and contraction of tubing. Threaded joints shall have American National screw threads, with graphite and oil compound applied to the male threads.

E. Valves: Valves shall be all brass with rough bodies and finished trimmings, except that those on chromium-plated brass pipe shall be finished and chromium plated. No valve shall be installed with its stem below the horizontal. Gate valves shall be Crane No. 1234 sweat type, Nibco No. S-126 sweat type or approved equal for tubing. Gate valves shall be Crane 400 or approved equal for threaded pipe.

F. Dielectric Unions: Where copper pipe is connected to steel pipe or steel equipment, connections shall be made with dielectric unions.

G. Unions: Unions installed in connection with ferrous piping shall be malleable-iron, zinc-coated.

Unions installed in connection with non-ferrous pipe or tubing shall be brass.

END OF SECTION