Add_1_SECTION_15_40_00_PLUMBING.pdf

PDF 14 KB Posted

Attached to
Renovate Student Dorms Winters Manor Federal contract opportunity
Solicitation number
FA3010-14-R-0006
Issued by
Department of the Air Force Air Education and Training Command

About this file

Addendum 1 Section 15 40 00

View the file

Other files for this federal contract opportunity

Other files attached to Renovate Student Dorms Winters Manor, newest first.
File Type Posted
SECTION_10_10_00_DISPLAY_CASES.pdf PDF
Section_12_48_23_Entrance_Floor_Grids.pdf PDF
RFI's_Winters_Manor.pdf PDF
MAHG10-1032_PAE_addendum_3.pdf PDF
FA3010-14-R-0006-0007.pdf PDF
Amendment_0006.pdf PDF
MAHG101032_Addendum_2.pdf PDF
Amendment_0005.pdf PDF
Add_2_SECTION_12_36_00_COUNTERTOPS.pdf PDF
Amendment_0004.pdf PDF
Winters_Manor_Additional_QA.pdf PDF
MAHG101032_Addendum_1_RFIs.pdf PDF
Add_1_SECTION_16_11_00_RACEWAYS.pdf PDF
Add_1_SECTION_08_11_13_STEEL_DOORS_AND_FRAMES.pdf PDF
Add_1_SECTION_16_72_60_PUBLIC_ADDRESS_AND_MASS_NOTIFICATION_SYSTEMS.pdf PDF
Add_1_SECTION_15_20_00_DOMESTIC_WATER_PIPING.pdf PDF
Add_1_Section_07_56_00_Fluid_Applied_Roofing.pdf PDF
Add_1_SECTION_16_50_00_LIGHTING.pdf PDF
Add_1_SECTION_16_00_00_GENERAL_PROVISIONS-ELECTRICAL.pdf PDF
Add_1_MAHG10-1032_Drawing_Sheets_Revision_01_5_21_14.pdf PDF
Amendment_0003.pdf PDF
Add_1_SECTION_09_68_13_TILE_CARPETING.pdf PDF
Amendment_0002.pdf PDF
Amendment_0001.pdf PDF
Site_Visit_Sign_In.pdf PDF
Attachment_5_Past_Performance_Reference_List.pdf PDF
Solicitation.pdf PDF
Attachment_6_SF_1444.pdf PDF
Attachment_6_Instructions.pdf PDF
WD_MS140119.pdf PDF
MAHG101032_Repair_student_Dorm_7404_SPECIFICATIONS.pdf PDF
MAHG101032_DRAWINGS_2013-2-20.pdf PDF
Attachment_4_Performance_Questionnaire.pdf PDF
Show all 33

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

MAHG10-1032

SECTION 15 40 00 - PLUMBING

PART 1 - GENERAL

1.01 DESCRIPTION

A. Furnish and install plumbing fixtures equal to those specified hereinafter.

1.02 GENERAL REQUIREMENTS

A. Generally all fixtures except water closets shall have the water supply above the rim. Fixtures with the supply discharge below the rim shall be equipped with backflow preventers. Exposed traps and supply lines for all fixtures and equipment shall be connected to the rough piping systems at the wall, unless otherwise specified under the item. Floor and wall plates and escutcheons shall be specified hereinbefore.

1.03 CROSS CONNECTIONS

A. Fixtures and trimmings shall be designed to prevent the backflow of polluted water or waste into the water supply system.

1.04 FIXTURE CONNECTIONS

A. Connections between earthenware fixtures and flanges on soil pipe shall be made absolutely gastight and watertight with plumbing-fixture setting compound or plumbing-fixture setting gaskets. Rubber gaskets or putty will not be permitted for the connection. Closet bolts shall be not less than 1/4 inch in diameter and shall be equipped with chromium-plated nuts and washers. Fixtures with outlet flanges will be set at the proper distance from floor or wall to make a first class joint with the closet setting compound or gasket and the fixture used. No fixture shall be set in place until the Contracting Officer has examined and approved such flange.

1.05 FINISH OF FITTINGS AND TRIMMINGS

A. The exposed piping, fittings and trimmings shall be chromium-plated on nickel plated brass with polished bright surfaces.

1.06 SUPPLY STOPS

A. Provide a supply stop valve for the domestic water service to each fixture.

1.07 PLUMBING FIXTURE SCHEDULE

A. Fixtures shall be Delta or equal to the manufacturer's numbers specified herein for identification of type and selection by Owner.

B. Lavatory Faucet shall be equal to Delta “Porter 25984LF”. With the following:

1. Solid brass cast body.

2. 4" (102 mm) centerset.

3. 5 11/16"(144 mm) long. 8 3/8"(213 mm) high, spout swings 360°.

4. 1/4 turn handle stops.

5. All operating parts shall be replaceable from the top.

6. Hot and cold stems are interchangeable.

7. 1/2" -14 NPSM threaded male inlet shanks.

8. Control mechanism is a rotating cylinder type with stainless steel plate and 90°rotating, with replaceable non-metallic seats.

9. Maximum flow rate 1.5 gpm @ 60 PSI.

10. To have drain with pop-up type fitting with plated flange and stopper.

END OF SECTION