E801_-_ELECTRICAL_SCHEDULES_AND_DIAGRAMS.pdf
PDF 415 KB Posted
- Attached to
- Haven on Vine Renovation Project State and local contract opportunity
- Solicitation number
- RFP2025-010
- Issued by
- Polk County, Lake Harbor CDP, Florida
About this file
The document E801 is an electrical riser diagram and schedule for the Haven on Vine Renovation Project in Kissimmee, Florida, prepared by Forefront Architecture & Engineering LLC. The electrical drawing provides comprehensive details for a 1200A service with a meter center (MC1) designed to support 43 residential units, featuring a single-line diagram that illustrates the electrical distribution system, voltage drop schedules, feeder schedules, and fault current analysis. The diagram covers multiple electrical panels, including unit panels, house panels, and specialized circuits for various building areas such as living units, mechanical rooms, and exterior lighting.
The electrical design reflects a complex renovation project with multiple power distribution considerations, including specific requirements for lighting control programming, circuit length calculations, and compliance with National Electrical Code (NEC) standards. The system is designed to support a diverse load of 652,138 VA across 43 residential units, with a demand factor of 0.27 and a total service size of 1200 amps at 208V three-phase. The design incorporates detailed specifications for feeder sizing, ground conductor requirements, and voltage drop limitations, demonstrating a comprehensive approach to electrical infrastructure that supports the affordable housing renovation project's technical and regulatory requirements.
View the file
Other files for this state and local contract opportunity
Show all 50
Haven on Vine Renovation Project has more files on GovTribe.
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
TC/PC
100A
100A
100A
100A
100A
100A
100A
100A
100A
100A
100A
100A
100A
100A
100A
100A
100A
100A
100A
100A
100A
100A
100A
100A
100A
100A
100A
100A
100A
100A
100A
100A
100A
100A
100A
100A
100A
100A
100A
100A
100A
100A
100A
400A
200A
3.3%
VOLTAGE DROP SCHEDULE
DEVICE FEEDER
VOLTAGE DROP WIRE SIZE LENGTH
MC1 0.36% (4)#500kcmil AL 30'
H 1.77% (2)#300kcmil AL 120'
ATS-LV 2.35% / 0.48% #1/0 AL / #2/0 AL 120' / 120'
LV1 #4/0 AL 250'
LV2 2.92% #4/0 AL 360'
INV1 1.8% #10 5'
POOL 2.97% #300kcmil AL 350'
H1 2.95% (2)#250kcmil AL 390'
INV2 3% #10 5'
FAULT CURRENT SCHEDULE
DEVICE FAULT AIC
RATING
L-L
VOLTS
TRANSFORMER
KVA Z% FAULT AT
PRIMARY
Utility T1 41,659 65,000 208V 300 2 UTILITY
MC1 37,026 65,000 208V
H 15,811 65,000 208V
ATS-LV 3,858 35,000 208V
LV1 2,065 10,000 208V
LV2 1,714 10,000 208V
INV1 9,540 22,000 120V
POOL 3,332 10,000 208V
H1 5,798 22,000 208V
INV2 4,603 22,000 120V
30/1
125.C
175/2.D
225.A
400.D
450.A
1200.B
FEEDER SCHEDULE
ID FEEDER
AMPS
CONDUIT AND FEEDER
30 1#10,#10N,#10G,1/2"C
110 3#1/0 AL,#1/0 AL N,#6G,2"C
125 3#2/0 AL,#2/0 AL N,#4G,2"C
175 2#4/0 AL,#4/0 AL N,#2G,2"C
225 3#300kcmil AL,#300kcmil AL N,#1G,3"C
400 (2)3#250kcmil AL,#250kcmil AL N,#3G,3"C
450 (2)3#300kcmil AL,#300kcmil AL N,#1G,3"C
1200 (4)3#500kcmil AL,#500kcmil AL N,#3/0G,4"C
USE CU GROUNDS
1ST FLR
2ND FLR
ROOF
#3/0 CU
METALLIC
WATER PIPE
BLDG LPS
CONCRETE
ENCASED
BLDG STEEL
ST
MC1
208Y/120V 3P 4W
1200A BUS
1200A MCB
450.A
208Y/120V 1P 3W
UNIT
PANEL P1
100A
MLO
Typical of 23
XFMR Utility T1
ASSUMED 300 KVA
208Y/120V
PANEL
POOL
200A MLO
208Y/120V 3P 4W
225.A
INV1
120V
30/1
INV2
120V
30/1
PANEL
LV1
60A
MCB
208/120V 2P 3W
1200.B
ATS-LV
208Y/120V
3P 4W
NEMA 3R
100A
PANEL
LV2
60A
MCB
208/120V 2P 3W
G1 208Y/120V
3P 4W
35KW
125.C
100/3
175/2.D
175/2.D
TC/PC
400.D
UNIT
PANEL P1
100A
MLO
208Y/120V 1P 3W
Typical of 17
UNIT
PANEL P2
100A
MLO
208Y/120V 1P 3W
Typical of 3
PANEL H
MCB
400A
208Y/120V 3P 4W
PANEL H1
MCB
200A
208Y/120V 3P
4W N E LOADS
MAX LENGTH (FT) / COPPER GND SIZE
#12 AWG
1/2" PVC
1/2" EMT
#10 AWG
1/2" PVC
1/2" EMT
#8 AWG
3/4" PVC
3/4" EMT
#6 AWG
3/4" PVC
3/4" EMT
#4 AWG
1" PVC
1" EMT
220' / #12 340' / #10 540' / #8 870' / #6
110' / #12 170' / #10 270' / #8 430' / #6 690' / #4
70' / #12 110' / #10 180' / #8 290' / #6 450' / #4
50' / #12 80' / #10 130' / #8 210' / #6 340' / #4
50' / #10 90' / #8 140' / #6 230' / #4
70' / #10 110' / #8 170' / #6
50' / #10 80' / #8 140' / #6
70' / #10 110' / #8
100' / #8
120V SINGLE PHASE CIRCUIT LENGTH
BREAKER
AMPACITY
(AMPS)
MAX
CIRCUIT
LOAD
(AMPS)
20 4
20 8
20 12
20 16
30 24
40 32
50 40
60 48
70 56
208V SINGLE PHASE CIRCUIT LENGTH
MAX LENGTH (FT) / COPPER GND SIZE
2/0
2" PVC
2" EMT
3/0
2" PVC
2" EMT
4/0
2-1/2" PVC
2-1/2" EMT
20 4 360' / #12 580' / #10 920' / #8 1400' / #6
20 180' / #12 290' / #10 460' / #8 730' / #6
20 120' / #12 180' / #10 300' / #8 490' / #6 770' / #4
20 80' / #12 130' / #10 220' / #8 350' / #6 580' / #4
30 80' / #10 150' / #8 230' / #6 390' / #4 490' / #3
40 110' / #10 180' / #8 290' / #6 360' / #4 450' / #4 560' / #3
50 80' / #10 130' / #8 240' / #6 290' / #4 350' / #4 460' / #3 590' / #1
60 110' / #10 180' / #8 240' / #6 300' / #6 360' / #4 490' / #3 500' / #2 700' / #1
70 170' / #8 200' / #6 250' / #6 310' / #4 410' / #3 470' / #2 600' / #1 700' / #1
80 140' / #8 180' / #6 220' / #6 270' / #4 360' / #3 410' / #2 510' / #1 600' / #1
90 170' / #8 200' / #6 240' / #4 320' / #3 360' / #2 450' / #1 590' / #1
100 140' / #8 180' / #6 210' / #4 290' / #3 320' / #2 410' / #1 540' / #1
110 160' / #6 190' / #4 260' / #3 290' / #2 360' / #1 430' / #1
125 160' / #6 220' / #4 250' / #4 310' / #3 370' / #2
NOTE:
1. FOR 240V SINGLE PHASE, MULTIPLY LENGTH BY 1.15.
2. FOR 277V SINGLE PAHSE, MULTIPLY LENGTH BY 1.32.
3. FOR 480V SINGLE PHASE, MULTIPLY LENGTH BY 2.3.
BREAKER
AMPACITY
(AMPS)
MAX
CIRCUIT
LOAD
(AMPS)
#12 AWG
1/2" PVC
1/2" EMT
#10 AWG
1/2" PVC
1/2" EMT
#8 AWG
3/4" PVC
3/4" EMT
#6 AWG
1" PVC
1" EMT
#4 AWG
1" PVC
1" EMT
#3 AWG
1-1/4" PVC
1-1/4" EMT
#2 AWG
1-1/4" PVC
1-1/4" EMT
#1 AWG
1-1/2" PVC
1-1/2" EMT
1/0
2" PVC
2" EMT
20 8
20 12
20 16
30 24
40 32
50 40
60 48
70 56
80 64
90 72
100 80
110 88
125 100
NOTE:
1. FOR 240V 3-PHASE, MULTIPLY LENGTH BY 1.12.
2. FOR 480V 3-PHASE, MULTIPLY LENGTH BY 2.2.
208V THREE PHASE CIRCUIT LENGTH
MAX LENGTH (FT) / COPPER GND SIZE
2/0
2" PVC
2" EMT
3/0
2" PVC
2" EMT
4/0
2-1/2" PVC
2-1/2" EMT
20 4 390' / #12 610' / #10 970' / #8
20 190' / #12 300' / #10 480' / #8 770' / #6
20 120' / #12 190' / #10 320' / #8 520' / #6 810' / #4
20 90' / #12 130' / #10 230' / #8 370' / #6 610' / #4
30 90' / #10 160' / #8 250' / #6 410' / #4 520' / #3
40 120' / #10 190' / #8 300' / #6 380' / #4 480' / #4 600' / #3
50 90' / #10 140' / #8 250' / #6 310' / #4 370' / #4 480' / #3 650' / #1
60 120' / #10 190' / #8 260' / #6 320' / #6 400' / #4 540' / #3 640' / #2 790' / #1
70 180' / #8 220' / #6 270' / #6 350' / #4 460' / #3 520' / #2 660' / #1 840' / #1
80 160' / #8 210' / #6 260' / #6 320' / #4 400' / #3 460' / #2 560' / #1 660' / #1
90 170' / #8 210' / #6 270' / #4 350' / #3 400' / #2 510' / #1 600' / #1
100 150' / #8 190' / #6 240' / #4 320' / #3 370' / #2 450' / #1 540' / #1
110 170' / #6 220' / #4 290' / #3 330' / #2 420' / #1 530' / #1
125 180' / #6 250' / #4 290' / #4 350' / #3 370' / #2
BREAKER
AMPACITY
(AMPS)
MAX
CIRCUIT
LOAD
(AMPS)
#12 AWG
1/2" PVC
1/2" EMT
#10 AWG
1/2" PVC
1/2" EMT
#8 AWG
3/4" PVC
3/4" EMT
#6 AWG
1" PVC
1" EMT
#4 AWG
1" PVC
1" EMT
#3 AWG
1-1/4" PVC
1-1/4" EMT
#2 AWG
1-1/4" PVC
1-1/4" EMT
#1 AWG
1-1/2" PVC
1-1/2" EMT
1/0
2" PVC
2" EMT
20 8
20 12
20 16
30 24
40 32
50 40
60 48
70 56
80 64
90 72
100 80
110 88
125 100
OFFICES, JANITOR CLOSETS, MULTIPURPOSE
ROOMS, STORAGE ROOMS, GREEN ROOM,
LIBRARY MEDIA CENTER, INDOOR PLAY, CONTROL,
KITCHEN, GYMNASIUM
1. ON: MANUAL ON THROUGH LOCAL SWITCH(ES). OFF: AUTOMATIC OFF THROUGH ROOM
OCCUPANCY SENSOR(S) WITHIN 20 MINUTES OF NO OCCUPANCY.
2. LOCAL SWITCH(ES): FOR MANUAL ON/OFF & DIMMING CONTROL.
3. DAYLIGHT SENSOR: FOR AUTOMATIC CONTROL OF LIGHTING FOR DIMMING FIXTURES BASED
ON DAYLIGHT LEVELS FOR ROOMS ON THE BUILDING PERIMETER. ONCE DAYLIGHT SENSOR
AUTO CALIBRATES IN THE ROOM, SET DAYLIGHT SENSOR TO DIM TO NO LESS THAN 30%, AND
"FAST" DIMMING RATE.
MECHANICAL, ELEC, AND IDF
ROOM
RESTROOMS, TOILETS
AREAS (WHERE APPLICABLE) CONTROL SCHEME
CORRIDORS
EXTERIOR BLDG WALL LIGHTS, EXTERIOR
CANOPY LIGHTS, EXTERIOR PATHWAY AND
PARKING LOT LIGHTING
1. LIGHTING ON/OFF BY LOCAL SWITCH
1. ON: AUTOMATIC ON THROUGH OCCUPANCY SENSORS DURING & AFTER PROGRAMMED
NORMAL OPERATING HOURS. OFF: AUTOMATIC OFF THROUGH OCCUPANCY SENSOR(S)
WITHIN 20 MINUTES OF NO OCCUPANCY.
1. ON: AUTOMATIC ON THROUGH TIME OF DAY SCHEDULE DURING PROGRAMMED NORMAL
OPERATING HOURS. OFF: AUTOMATIC OFF AFTER PROGRAMMED OPERATING HOURS.
2. LOCAL SWITCH(ES): (SLVO) ARE OVERRIDE SWITCHES FOR HOUSEKEEPING/MAINTENANCE
PURPOSES AFTER PROGRAMMED NORMAL OPERATING HOURS. LIGHTS SHALL STAY ON FOR A
MAXIMUM OF TWO HOURS.
3. DAYLIGHT SENSOR: FOR AUTOMATIC CONTROL OF LIGHTING FOR DIMMING FIXTURES BASED
ON DAYLIGHT LEVELS FOR LIGHTS WITHIN DAYLIGHT ZONES SHOWN AT BUILDING PERIMETER.
ONCE DAYLIGHT SENSOR AUTOCOLLIMATORS IN THE ARE, SET DAYLIGHT SENSOR TO DIM TO
NO LESS THAN 30% "FAST" DIMMING RATE.
1. ON: AUTOMATIC ON THROUGH LIGHTING CONTROL RELAY PANEL SYSTEM PHOTOCELL AT
DUSK OFF AT DAWN BY LIGHTING CONTROL RELAY PANEL SYSTEM PHOTOCELL.
2. PARKING LOT AND NON-FACADE SITE LIGHTING: AUTO-ON/OFF VIA PHOTOCELL. FIXTURES
SHALL BE PROVIDED WITH INTEGRAL MOTION SENSOR TO DIM TO 50% FROM ONE HR AFTER
AND PRIOR TO NORMAL BUSINESS HOURS WHEN ACTIVITY HAS NOT BEEN DETECTED FOR
MORE THAN 15 MINUTES.
PROGRAMMING NOTES
1. TIME CLOCK/LIGHTING CONTRACTOR IS TO BE PROGRAMMED FOR THE TIME-OF-DAY SCHEDULE FOR NORMAL OPERATING HOURS.
2. VERIFY OPERATING HOURS WITH OWNERS REPRESENTATIVE PRIOR TO PROGRAMMING.
3. ALL OTHER DAYS AND TIMES SHALL BE CONSIDERED "AFTER NORMAL OPERATING HOURS" FOR THE PURPOSES OF PROGRAMMING DESCRIPTIONS.
CONTROL TYPE
STAND-ALONE LIGHTING
CONTROL
STAND-ALONE LIGHTING
CONTROL
STAND-ALONE LIGHTING
CONTROL
LIGHTING CONTROL
RELAY PANEL
LIGHTING CONTROL
RELAY PANEL
WAREHOUSES
1. ON: OCCUPANT SENSORS OR TIMECLOCK. OFF: OCCUPANT SENSORS, TIMECLOCK.
2. LOCAL SWITCH(ES): MANUAL OVERRIDES.
3. OCCUPANT SENSOR SHALL REDUCE LIGHT TO 50% AFTER 20 MINUTES OF NO
OCCUPANCY.
LIGHTING CONTROL
RELAY PANEL
ALL LIGHTING SHALL BE CONTROLLED AS SPECIFIED BELOW
LIGHTING CONTROL PROGRAMMING/COMMISSIONING REQUIREMENTS
1230 Oakley Seaver Drive, Suite 100 Clermont, Florida 34711
888.850.FFAE (3323)
www.forefrontae.com
A R C H I T E C T U R E
E N G I N E E R I N G
Engineering - Consulting - Project Management 934 N Magnolia Ave, Suite 326, Orlando, FL 32803
(321) 246 - 4041 C.A. No. 33227 CEI Project # 24.86
This item has been electronically signed and sealed by francisco cabral, PE on the date and/or time stamp shown using a digital signature. Printed copies of this document are not considered signed & sealed and, the signature must be verified on any electronic copies.
C FOREFRONT ARCHITECTURE & ENGINEERING LLC 2014 THIS DOCUMENT AND/OR THE DESIGN CONCEPTS EXPRESSED HEREIN ARE THE PROPERTY OF FOREFRONT ARCHITECTURE & ENGINEERING LLC AND ALL RIGHTS OF OWNERSHIP, INCLUDING COPYRIGHT OF INTELLECTUAL PROPERTY, ARE RESERVED. ANY REPRODUCTIONS, COPYING, OR USE OF THIS DOCUMENT AND/OR THE DESIGN CONCEPT WITHOUT THE WRITTEN CONSENT OF FOREFRONT ARCHITECTURE & ENGINEERING LLC IS STRICTLY PROHIBITED AND PROTECTED BY UNITED STATES AND INTERNATIONAL LAW. IF PRINTED ON 11X17 SCALE IS HALF THE SIZE NOTED.C:sersichaelCucuta\OneDrive - cabralengineering.com\DESIGN\ACTIVE\Haven On Vine\02 Client Input\20240710 exisitng P1A, P1B\HAVEN ON VINE - Standard\TTB; Plot Date: Tuesday, December 05, 2023,1:10:09 PM; Plotted By: MichaelCucuta
ANY DISCREPANCY OR
ERROR IN DIMENSIONS OR
NOTES SHALL BE BROUGHT
TO THE ATTENTION OF THE
DESIGN PROFESSIONAL FOR
CLARIFICATION PRIOR TO
COMMENCEMENT OF
CONSTRUCTION.
JOB # :
JO
B N
A M
E
S H
E E T N
A M
E
ISSUE - REVISION LOG
AR102538 - CA30900
SHEET NUMBER :
H A V E N
O N
V
IN
E
A
W
E S T V
IN
E S
T R
E E T K
IS
S
IM
M E E F L
M A R
K D
A T E
D E S C R
IP
T
IO
N
24-13596
/1 /2
A d d e n d u m
E L
E C
T R
IC
A
L S
C H
E D
U L
E S
A N
D D
IA
G
R A
M S
E801
RISER DIAGRAM KEY NOTES
1. ALL PROTECTIVE DEVICES 1200A OR LARGER SHALL BE PROVIDED WITH
ARC ENERGY MITIGATION AS REQUIRED BY THE NEC.
2. ALL SERVICE EQUIPMENT SHAL LBE FROM THE UTIITY-APPROVED
EQUIPMENT LIST. CONSULT UTILITY COMPANY FOR REQUIREMENTS.
3. ALL EXTERIOR EQUIPMENT SHAL LHAVE A MINIMUM RATING OF NEMA 3R.
4. CONTRACTOR SHALL NOT USED DESIGN AND CALCULAITON LENGTHS FOR
BIDDING OR PROCUREMENT. CONTRACTOR SHALL PERFORM FIELD
MEASUREMENTS AND IS RESPONSUIBLE FOR PROVIDING ENOUGH
MATERIAL FOR A SAFE AND COMPLETE INSTALLATION.
5. PROVIDE 100% RATED SERVICE DISCONNECTS AND MAIN BREAKERS FOR
PANELS "H" AND "H1".
LIVING UNIT LOAD CENTER SINGLE-PHASE FEEDER SCHEDULE (MAX VD<=3%)
LOAD CENTER
AMP RATING
FEEDER LENGTH
FROM METER CENTER
TO LOAD CENTER SINGLE-PHASE ALUMINUM FEEDER SINGLE-PHASE COPPER FEEDER
100 AMP
UP TO 130' 2#1 AL,#1 AL N,#8G,1-1/2"C 2#3,#3N,#8G,1-1/4"C
131' TO 180' 2#1/0 AL,#1/0 AL N,#4G,1-1/2"C 2#2,#2N,#6G,1-1/4"C
181' TO 220' 2#2/0 AL,#2/0 AL N,#4G,2"C 2#1,#1N,#4G,1-1/2"C
221' TO 280' 2#3/0 AL,#3/0 AL N,#3G,2"C 2#1/0,#1/0N,#3G,1-1/2"C
281' TO 320' 2#4/0 AL,#4/0 AL N,#2G,2"C 2#2/0,#/0N,#2G,2"C
NOTES
1. INCREASE LUG SIZE FOR ALL METER CENTER MAINS AND LOAD CENTERS AS REQUIRED TO ACCOMMODATE ALL
CONDUCTORS.
2. ALL GROUNDS ARE CU.
3. ASSUMES LENGTH FROM TRANSFORMER TO METER CENTER IS NOT GREATER THAN 100'
SHUNT TRIP KNOCK BOX. COODRIDNATE
LOCATION WITH FIRE MARSHALL
METER CENTER MC1
1. EZ METER PAK (OR EQUAL)
2. NEMA 3R
3. MAIN SECTION:
A. 1200A, 120/208V, 3Ø, 4W
B. 1200A, 3Ø MAIN CIRCUIT
BREAKER.
4. BRANCH SECTIONS:
A. 43 - 100A, 120/208V, 1Ø, 3W
TENANT BREAKERS AND
METER CANS.
B. 2 - 400A, 120/208V, 3Ø, 4W
TENANT BREAKER AND
METER CAN.
MODEL:
ISOLITE E3-375-LC-
V1-1S-2S
SEE LIVING UNIT FEEDER SCHEDULE FOR
APARTMENT UNIT FEEER SIZING
SIZED, F&I BY UTILITY
COMPANY
CIRCUIT LENGTH TABLES NOTES
1. UON, CIRCUIT MAXIMUM DISTANCE IS BASED ON NEC CHAPTER 9, TABLE 8
CONDUCTOR PROPERTIES FOR COATED COPPER CONDUCTORS AT 75 DEGREES
CELSIUS. CONTRACTOR SHALL RECALCULATE AMPACITIES AND CIRCUIT
LENGTHS WHEN USING ALUMINUM OR IF TEMPERATURE RATINGS ARE
DIFFERENT.
2. BASED OF MAX VD=3%.
3. BASED ON UP TO 3 CURRENT-CARRYING CONDUCTORS IN A RACEWAY.
CONTRACTOR SHALL DE-RATE PER NEC AS REQUIRED WHEN INSTALLING MORE
THAN 3 CURRENT-CARRYING CONDUCTORS IN A SINGLE RACEWAY.
4. SIZE CONDUIT BASED ON TYPE FOR A MAX 40% FILL.
5. CONTRACTOR SHALL SIZE GROUND CONDUCTOR PER NEC AND INCREASE AS
REQUIRED FOR VOLTAGE DROP.
6. CONTRACTOR SHALL USE CABLE REDUCERS WHEN REQUIRED TO CONNECT
UPSIZED CONDUCTORS.
7. USE COPPER GROUND. SIZE GROUND CONDUCTOR PER NEC 250.122.
8. SIZE CONDUIT PER NEC ANNEX C TABLES. BASED ON CONDUIT TYPE, NUMBER
OF CONDUCTORS AND INSTALLATION ENVIRONMENT.
MODEL:
ISOLITE E3-375-LC-
V1-1S-2S-3S-4S
SERVICE SIZE (AMPS) 1200
DEMAND AMPS AT 208V 3-PHASE (AMPS) 1006
METER CENTER TOTAL (VA) 361987
HOUSE PANEL LOAD (VA) (H + H1) 185,910
TOTAL DWELLING DIVERSIFIED DEMAND (VA) 176077
NEC TABLE 220.84 FACTOR 0.27
NUMBER OF UNITS 43
UNIT TOTAL LOAD (VA) 652138
RESIDENTIAL UNIT 43 15166 652138
UNIT TYPE COUNT
UNIT LOAD
(VA) TOTAL (VA)
METER CENTER FEEDER CALCULATION
| Sheets |
| E801 - ELECTRICAL SCHEDULES AND DIAGRAMS |
| 2025-05-06T17:18:52-0400 | |
| Francisco J Cabral |
File details come from the government source that posted it. Updated .