This document is a COMcheck-Web compliance report for interior and exterior lighting for a new construction project located at 600 South 1st Street in Hermiston, Oregon, involving the Hermiston Concessions facility. The report details lighting power calculations and compliance with the 2021 International Energy Conservation Code (IECC), demonstrating that the interior lighting design is 6% better than code requirements. The project involves LED lighting installations in restrooms, storage areas, and sales areas, with a total of 14 light fixtures across three space types, utilizing 1x4 surface strip LED fixtures with 36-watt capabilities.
The compliance report includes comprehensive energy code inspection checklists covering various electrical and lighting system requirements, such as occupancy sensors, daylight-responsive controls, and automatic lighting controls. The document confirms compliance with energy efficiency standards through detailed calculations of allowed and proposed watts for both interior and exterior lighting zones. Key compliance areas include manual light reduction controls, time-switch controls, transformer efficiency, and electrical system voltage drop considerations. The report serves as a technical validation of the project's adherence to energy conservation standards and will likely be used in the permitting and final inspection processes for the Hermiston Concessions building.
View the file
Other files
Show all 11
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
COMcheck Software Version COMcheckWeb
Interior Lighting Compliance Certificate
Project Title:
2021 IECC
Project Type: New Construction
Construction Site:
600 SOUTH 1ST STREET
HERMISTON, Oregon 97838
Owner/Agent: Designer/Contractor:
Project Information Energy Code:
Hermiston Concessions
Credits: 10.0 Required 0.0 Proposed Additional Efficiency Package(s)
Allowed Interior Lighting Power A
Area Category B
Floor Area (ft2)
C Allowed
Watts / ft2
D Allowed Watts
1-Common Space Types:Restrooms 370 0.63 233 2-Common Space Types:Storage 150 0.38 57 3-Common Space Types:Sales Area 234 1.05 246
536Total Allowed Watts =
Proposed Interior Lighting Power E
(C X D) D
Fixture Watt.
A Fixture ID : Description / Lamp / Wattage Per Lamp / Ballast
B Lamps/ Fixture
C # of
Fixture
1-Common Space Types:Restrooms LED: F1,F1-EM: 1X4 SURFACE STRIP: Other: 1 5 36 180
2-Common Space Types:Storage LED: F1,F1-EM: 1X4 SURFACE STRIP: Other: 1 4 36 144
3-Common Space Types:Sales Area LED: F1,F1-EM: 1X4 SURFACE STRIP: Other: 1 5 36 180
504Total Proposed Watts =
Interior Lighting Compliance Statement Compliance Statement: The proposed interior lighting design represented in this document is consistent with the building plans, specifications, and other calculations submitted with this permit application. The proposed interior lighting systems have been designed to meet the 2021 IECC requirements in COMcheck Version COMcheckWeb and to comply with any applicable mandatory requirements listed in the Inspection Checklist.
Name - Title Signature Date
Interior Lighting PASSES: Design 6% better than code
Project Title:
Data filename:
Hermiston Concessions 04/25/25Report date:
61 ofPage
COMcheck Software Version COMcheckWeb
Exterior Lighting Compliance Certificate
Project Title:
2021 IECC
Project Type: New Construction
Construction Site:
600 SOUTH 1ST STREET
HERMISTON, Oregon 97838
Owner/Agent: Designer/Contractor:
Project Information Energy Code:
Hermiston Concessions
3 (Other (LZ3))Exterior Lighting Zone
Allowed Exterior Lighting Power A
Area/Surface Category B
Quantity C
Allowed Watts /
D Tradable Wattage
E Allowed Watts
(B X C)
Illuminated area of facade wall or surface 1098 ft2 0.11 No 124 Total Tradable Watts (a) =
Total Allowed Watts = Total Allowed Supplemental Watts (b) =
(a) Wattage tradeoffs are only allowed between tradable areas/surfaces.
(b) A supplemental allowance equal to 500 watts may be applied toward compliance of both non-tradable and tradable areas/surfaces.
Proposed Exterior Lighting Power E
(C X D) D
Fixture Watt.
A Fixture ID : Description / Lamp / Wattage Per Lamp / Ballast
B Lamps/ Fixture
C # of
Fixture
Illuminated area of facade wall or surface (1098 ft2): Non-tradable Wattage LED: W1: WALL PACK: Other: 1 2 32 64
0Total Tradable Proposed Watts =
Exterior Lighting Compliance Statement Compliance Statement: The proposed exterior lighting design represented in this document is consistent with the building plans, specifications, and other calculations submitted with this permit application. The proposed exterior lighting systems have been designed to meet the 2021 IECC requirements in COMcheck Version COMcheckWeb and to comply with any applicable mandatory requirements listed in the Inspection Checklist.
Name - Title Signature Date
Exterior Lighting PASSES: Design 0.0% better than code
Project Title:
Data filename:
62 ofPage
Inspection Checklist Requirements: 0.0% were addressed directly in the COMcheck software
COMcheck Software Version COMcheckWeb
Text in the "Comments/Assumptions" column is provided by the user in the COMcheck Requirements screen. For each requirement, the user certifies that a code requirement will be met and how that is documented, or that an exception is being claimed. Where compliance is itemized in a separate table, a reference to that table is provided.
Energy Code: 2021 IECC
Section
& Req.ID Plan Review Complies? Comments/Assumptions
C103.2
[PR4]1
Plans, specifications, and/or calculations provide all information with which compliance can be determined for the interior lighting and electrical systems and equipment and document where exceptions to the standard are claimed. Information provided should include interior lighting power calculations, wattage of bulbs and ballasts, transformers and control devices.
Complies Does Not Not Observable Not Applicable
C103.2
[PR8]1
Plans, specifications, and/or calculations provide all information with which compliance can be determined for the exterior lighting and electrical systems and equipment and document where exceptions to the standard are claimed. Information provided should include exterior lighting power calculations, wattage of bulbs and ballasts, transformers and control devices.
Complies Does Not Not Observable Not Applicable
C406
[PR9]1
Plans, specifications, and/or calculations provide all information with which compliance can be determined for the additional energy efficiency package options.
Complies Does Not Not Observable Not Applicable
Additional Comments/Assumptions:
1 High Impact (Tier 1) 2 Medium Impact (Tier 2) 3 Low Impact (Tier 3)
Project Title:
Data filename:
63 ofPage
Section
& Req.ID Rough-In Electrical Inspection Complies? Comments/Assumptions
C405.2.3.
[EL22]1
Spaces required to have light-reduction controls have a manual control that allows the occupant to reduce the connected lighting load in a reasonably uniform illumination pattern >= 50 percent.
Complies Does Not Not Observable Not Applicable
C405.2.1, C405.2.1.
[EL18]1
Occupancy sensors installed in classrooms/lecture/training rooms, conference/meeting/multipurpose rooms, copy/print rooms, lounges/breakrooms, enclosed offices, open plan office areas, restrooms, storage rooms, locker rooms, corridors, warehouse storage areas, and other spaces <= 300 sqft that are enclosed by floor-to-ceiling height partitions. Reference section language C405.2.1.2 for control function in warehouses and section C405.2.1.3 for open plan office spaces.
Complies Does Not Not Observable Not Applicable
C405.2.1.
[EL19]1
Occupancy sensors control function in warehouses: In warehouses, the lighting in aisleways and open areas is controlled with occupant sensors that automatically reduce lighting power by 50% or more within 20 minutes of when the areas are unoccupied. The occupant sensors control lighting in each aisleway independently and do not control lighting beyond the aisleway being controlled by the sensor. Lights not turned off by occupant sensors is done so by time-switch.
Complies Does Not Not Observable Not Applicable
C405.2.1.
[EL20]1
Occupant sensor control function in open plan office areas: Occupant sensor controls in open office spaces >= 300 sq.ft. have controls 1) configured so that general lighting can be controlled separately in control zones with floor areas <= 600 sq.ft.
within the space, 2) general lighting in each zone permitted to turn on upon occupancy in control zone, 3) automatically turn off general lighting in all control zones within 20 minutes after all occupants have left the space, 4) are configured so that general lighting power in each control zone is reduced by >= 80% of the full zone general lighting power within 20 minutes of all occupants leaving that control zone.
Complies Does Not Not Observable Not Applicable
C405.2.2, C405.2.2.
[EL21]2
Each area not served by occupancy sensors (per C405.2.1.1) have time-switch controls and functions detailed in sections C405.2.2.1.
Complies Does Not Not Observable Not Applicable
1 High Impact (Tier 1) 2 Medium Impact (Tier 2) 3 Low Impact (Tier 3)
Project Title:
Data filename:
64 ofPage
& Req.ID Rough-In Electrical Inspection Complies? Comments/Assumptions
C405.2.4, C405.2.4.
1, C405.2.4.
[EL23]2
Daylight zones provided with individual controls that control the lights independent of general area lighting. See code section C405.2.3 Daylight-responsive controls for applicable spaces, C405.2.3.1 Daylight responsive control function and section C405.2.3.2 Sidelit zone.
Complies Does Not Not Observable Not Applicable
C405.2.5
[EL27]1
Additional interior lighting power allowed for special functions per the approved lighting plans and is automatically controlled and separated from general lighting.
Complies Does Not Not Observable Not Applicable
C405.2.7
[EL28]1
Automatic lighting controls for exterior lighting installed. Controls will be daylight controlled, set based on business operation time-of-day, or reduce connected lighting > 30%.
Complies Does Not Not Observable Not Applicable
C405.7
[EL26]2
Low-voltage dry-type distribution electric transformers meet the minimum efficiency requirements of Table C405.6.
Complies Does Not Not Observable Not Applicable
C405.8
[EL27]2
Electric motors meet the minimum efficiency requirements of Tables C405.7(1) through C405.7(4).
Efficiency verified through certification under an approved certification program or the equipment efficiency ratings shall be provided by motor manufacturer (where certification programs do not exist).
Complies Does Not Not Observable Not Applicable
C405.9.1, C405.9.2
[EL28]2
Escalators and moving walks comply with ASME A17.1/CSA B44 and have automatic controls configured to reduce speed to the minimum permitted speed in accordance with ASME A17.1/CSA B44 or applicable local code when not conveying passengers.
Complies Does Not Not Observable Not Applicable
C405.10
[EL29]2
Total voltage drop across the combination of feeders and branch circuits <= 5%.
Complies Does Not Not Observable Not Applicable
C405.1.1
[EL30]2
At least 90% of dwelling unit permanently installed lighting shall have lamp efficacy >= 65 lm/W or luminaires with efficacy >= 45 lm/W or comply with C405.2.4 or C405.3.
Complies Does Not Not Observable Not Applicable
C405.11, C405.11.1
[EL31]2
50% of 15/20 amp receptacles installed in enclosed offices, conference rooms, copy rooms, break rooms, classrooms and workstations and > 25% of branch circuit feeders for modular furniture will have automatic receptacle control in accordance with C405.11.1.
Complies Does Not Not Observable Not Applicable
Additional Comments/Assumptions:
1 High Impact (Tier 1) 2 Medium Impact (Tier 2) 3 Low Impact (Tier 3)
Project Title:
Data filename:
65 ofPage
& Req.ID Final Inspection Complies? Comments/Assumptions
C303.3, C408.2.5.
[FI17]3
Furnished O&M instructions for systems and equipment to the building owner or designated representative.
Complies Does Not Not Observable Not Applicable
C405.5.1
[FI19]1
Exterior lighting power is consistent with what is shown on the approved lighting plans, demonstrating proposed watts are less than or equal to allowed watts.
Complies Does Not Not Observable Not Applicable
See the Exterior Lighting fixture schedule for values.
C408.1.1
[FI57]1
Building operations and maintenance documents will be provided to the owner. Documents will cover manufacturers' information, specifications, programming procedures and means of illustrating to owner how building, equipment and systems are intended to be installed, maintained, and operated.
Complies Does Not Not Observable Not Applicable
C408.2.5
[FI16]3
Furnished as-built drawings for electric power systems within 90 days of system acceptance.
Complies Does Not Not Observable Not Applicable
C408.3
[FI33]1
Lighting systems have been tested to ensure proper calibration, adjustment, programming, and operation.
Complies Does Not Not Observable Not Applicable