About this file
This is a Preventative Maintenance Checklist for the City of Phoenix's chiller and boiler system maintenance contract, which specifies comprehensive maintenance tasks organized across ten functional sections. The checklist covers chiller and cooling tower maintenance, boiler and burner combustion system tasks, electrical and VFD cabinet operations, piping and water system leak checks, operational testing procedures, gauge documentation, oil system maintenance, pump and mechanical movement inspections, structural and physical inspections, and chemical system monitoring. Tasks are assigned frequency intervals ranging from monthly to annually and semi-annually, with specific equipment models identified including Boiler models 300S-850A, 300A-850A, and 850. The contract term is five years beginning on the Commencement Date as approved by the Phoenix City Council, with no options to extend, and will terminate upon reaching the end of the five-year term or earlier upon contract termination provisions.
The checklist provides a standardized framework for technicians and supervisors to document completion of required maintenance activities with designated spaces for dates and sign-offs. Monthly tasks include checking chiller and condenser pumps, water temperatures, cooling tower screens and belts, inspecting oil and Freon levels, cycling water control valves, and conducting chemical testing for hardness, alkalinity, chlorides, nitrite, phosphates, pH, conductivity, and biological activity. Pre-season tasks encompass chiller and heater boiler annual inspections with startup and shutdown procedures, oil system maintenance including filter changes and oil sampling, and VFD cabinet cleaning and tightening. The document requires technicians to record alarms, amp draws, pressures, temperatures, model and serial numbers, and provide monthly monitoring data in reports, with gauge recalibration required semi-annually for specific boiler models.
View the file
Other files
Show all 11
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
SECTION 1 — CHILLER & COOLING TOWER TASKS
Completed ❑ Date: ________ ❑ Brush chiller condenser tubes (Annually) ❑Change filter in closed loop system (Monthly) ❑Check chiller and condenser pumps (Monthly) ❑Check chiller and water temperatures (Monthly) ❑Check cooler tower – clean sump screens, check belts (Monthly) ❑Check/clean cooling tower spray nozzles & hot water basins (Monthly) ❑Check/clean pumps – chiller & condenser – switch lead pump (Monthly) ❑ Inspect oil and Freon levels (Monthly) ❑Cycle/check water control valves (Monthly) ❑ Test Buildings A & B third floor temps vs chiller room (Monthly) ❑ In wintertime, check comfort boiler (Monthly)
Notes:
SECTION 2 — BOILER / BURNER COMBUSTION SYSTEM TASKS
Completed ❑ Date: ________ Combustion Chamber & Burner Cleaning ❑Clean and inspect boiler air filters (Annually) ❑Clean and inspect burner section (Annually) ❑Clean burner assemblies & ignition systems (Annually) ❑Clean combustion chamber coil (Boiler 300S-850A) (Annually) ❑ Inspect and clean burner using shop air (Boiler 300S-850A) (Annually)
Ignition & Flame Detection ❑Check igniter, clean & verify spark gap (Boiler 850) (Annually) ❑Check flame sensor (Boiler 300S-850A) (Annually) ❑ Test flame failure detection system (Boiler 300S-850A) (Annually) ❑ Verify high/low fire flame signal vs startup data (Boiler 850) (Annually) ❑Check flame failure system components (Boiler 300A-850A) (Semi Annual)
Chiller and Boiler Preventative Maintenance Check List
Gas & Air Supply ❑Check drip leg and gas strainers (Boiler 850) (Annually) ❑Check air vents for leakage (Boiler 300A-850A) (Monthly) ❑ Test intake air pressure (Boiler 300A-850A) (Monthly) ❑ Replace intake air filters when pressure ↑ by −0.5 in (Monthly)
Gas Pressures / Manifold / Firing Rate ❑Check fan speed & manifold pressure (Boiler 850) (Annually) ❑Check firing rate control vs manufacturer specs (Boiler 300A-850A) (Semi Annual) ❑ Test high and low gas pressure interlocks (Boiler 300A-850A) (Monthly)
Venting / Stack / Dampers ❑Check flue, vent, stack, or dampers (Boiler 300A-850A) (Monthly) ❑ Visually inspect burner flames (Boiler 300A-850A) (Monthly) ❑ Inspect condensation drains & traps (Boiler 300A-850A) (Monthly) ❑ Inspect venting system for leakage/deterioration (Boiler 300A-850A) (Monthly)
Safety Valves & Shutdown Devices ❑ Test safety/safety relief valves per ASME code (Boiler 850) (Annually) ❑ Replace or recondition low water cut-off device (Boiler 850) (Annually) ❑Check valve core for hum/buzz + shut-off (Boiler 300S-850A) (Annually) ❑ Perform leakage test on gas valves (Boiler 300S-850A) (Annually)
Notes:
SECTION 3 — ELECTRICAL & VFD CABINET TASKS
Completed ❑ Date: ________ ❑ Tighten all electrical connections (Annually) ❑Check and clean VFD cabinets (Pre-Season) ❑ Tighten terminals, electrical & pipe connections (Pre-Season) ❑Check condition of contactors and starters (Pre-Season) ❑ Inspect all electrical components for wear (Semi Annual)
❑ Inspect all safety switches (Semi Annual) ❑ Inspect venting/make-up/exhaust motors (Semi Annual)
Notes:
SECTION 4 — PIPING, WATER & SYSTEM LEAK CHECKS
Completed ❑ Date: ________ ❑ Inspect for water leaks (Semi Annual) ❑Check for piping leaks around pumps, mixing valves, relief valves, fittings (Monthly) ❑Check water piping for corrosion or weakness (Monthly) ❑Check expansion tank & closed loop system pressure (Monthly)
Notes:
SECTION 5 — OPERATIONAL TESTING, STARTUP & SHUTDOWN
Completed ❑ Date: ________ ❑ Turn boiler on and check ignition/operation (Semi Annual) ❑Chiller annual inspection start-up/shut-down (Pre-Season) ❑Heater boiler annual inspection start-up/shut-down (Pre-Season) ❑Walk supervisor through written start-up protocol (Pre-Season) ❑General operational comments & recommendations (Pre-Season) ❑Control operation (Pre-Season) ❑ Safety control operation (Pre-Season)
Notes:
SECTION 6 — GAUGES, RECORDING & DOCUMENTATION
❑Check and record alarms present/in history (Semi Annual) ❑ Record amp draws, pressures, temperatures (Semi Annual) ❑ Record model & serial numbers (Semi Annual) ❑ Record any repairs needed (Semi Annual) ❑ Fill out boiler tasking sheet (Semi Annual) ❑ Recalibrate gauges (Boiler 300A-850A) (Semi Annual)
Notes:
SECTION 7 — OIL SYSTEM TASKS
Completed ❑ Date: ________ ❑Oil filters (Pre-Season) ❑Oil level (Pre-Season) ❑Oil replaced — type & amount (Pre-Season) ❑Oil sample (Pre-Season)
Notes:
SECTION 8 — PUMPS & MECHANICAL MOVEMENT
❑ Inspect booster pumps for bearing wear/leakage (Semi Annual) ❑ Inspect pumps (Semi Annual)
Notes:
SECTION 9 — STRUCTURAL / PHYSICAL INSPECTION
Completed ❑ Date: ________ ❑ Inspect insulated panels for cracks/broken pieces (Annually) ❑ Inspect heat exchanger for cracks (Annually)
Notes:
SECTION 10 — CHEMICAL & SYSTEM MONITORING
Completed ❑ Date: ________ ❑Chemical testing (hardness, alkalinity, chlorides, nitrite, phosphates, pH, conductivity, biological activity) (Monthly) ❑Maintain chemical feed systems, scale/corrosion control & biocides (Monthly) ❑ Provide monthly monitoring data in reports (Monthly)
Notes:
FINAL SIGN-OFF
Technician: __________________________________________ Date: __________________ Supervisor: _________________________________________
| SECTION 1 CHILLER COOLING TOWER TASKS: |
| Date: Off |
| Brush chiller condenser tubes Annually: Off |
| toggle_3: Off |
| Check chiller and condenser pumps Monthly: Off |
| Check chiller and water temperatures Monthly: Off |
| Check cooler tower clean sump screens check belts Monthly: Off |
| Checkclean cooling tower spray nozzles hot water basins Monthly: Off |
| Checkclean pumps chiller condenser switch lead pump Monthly: Off |
| Inspect oil and Freon levels Monthly: Off |
| Cyclecheck water control valves Monthly: Off |
| toggle_11: Off |
| In wintertime check comfort boiler Monthly: Off |
| Combustion Chamber Burner Cleaning: |
| Date_2: Off |
| toggle_14: Off |
| Clean and inspect burner section Annually: Off |
| Clean burner assemblies ignition systems Annually: Off |
| Clean combustion chamber coil Boiler 300S850A Annually: Off |
| Inspect and clean burner using shop air Boiler 300S850A Annually: Off |
| Check igniter clean verify spark gap Boiler 850 Annually: Off |
| toggle_20: Off |
| toggle_21: Off |
| toggle_22: Off |
| toggle_23: Off |
| Check drip leg and gas strainers Boiler 850 Annually: Off |
| Check air vents for leakage Boiler 300A850A Monthly: Off |
| Test intake air pressure Boiler 300A850A Monthly: Off |
| toggle_4: Off |
| Check fan speed manifold pressure Boiler 850 Annually: Off |
| toggle_6: Off |
| Test high and low gas pressure interlocks Boiler 300A850A Monthly: Off |
| toggle_8: Off |
| toggle_9: Off |
| Inspect condensation drains traps Boiler 300A850A Monthly: Off |
| Inspect venting system for leakagedeterioration Boiler 300A850A Monthly: Off |
| Test safetysafety relief valves per ASME code Boiler 850 Annually: Off |
| Replace or recondition low water cutoff device Boiler 850 Annually: Off |
| Check valve core for humbuzz shutoff Boiler 300S850A Annually: Off |
| Perform leakage test on gas valves Boiler 300S850A Annually: Off |
| SECTION 3 ELECTRICAL VFD CABINET TASKS: |
| Date_3: Off |
| Tighten all electrical connections Annually: Off |
| Check and clean VFD cabinets PreSeason: Off |
| Tighten terminals electrical pipe connections PreSeason: Off |
| Check condition of contactors and starters PreSeason: Off |
| Inspect all electrical components for wear Semi Annual: Off |
| Inspect all safety switches Semi Annual: Off |
| Inspect ventingmakeupexhaust motors Semi Annual: Off |
| SECTION 4 PIPING WATER SYSTEM LEAK CHECKS: |
| Date_4: Off |
| Inspect for water leaks Semi Annual: Off |
| toggle_5: Off |
| Check water piping for corrosion or weakness Monthly: Off |
| Check expansion tank closed loop system pressure Monthly: Off |
| SECTION 5 OPERATIONAL TESTING STARTUP SHUTDOWN: |
| Date_5: Off |
| Turn boiler on and check ignitionoperation Semi Annual: Off |
| Chiller annual inspection startupshutdown PreSeason: Off |
| Heater boiler annual inspection startupshutdown PreSeason: Off |
| Walk supervisor through written startup protocol PreSeason: Off |
| General operational comments recommendations PreSeason: Off |
| Control operation PreSeason: Off |
| Safety control operation PreSeason: Off |
| SECTION 6 GAUGES RECORDING DOCUMENTATION: |
| Date_6: Off |
| Check and record alarms presentin history Semi Annual: Off |
| Record amp draws pressures temperatures Semi Annual: Off |
| Record model serial numbers Semi Annual: Off |
| Record any repairs needed Semi Annual: Off |
| Fill out boiler tasking sheet Semi Annual: Off |
| Recalibrate gauges Boiler 300A850A Semi Annual: Off |
| SECTION 7 OIL SYSTEM TASKS: |
| Date_7: Off |
| toggle_9_2: Off |
| Oil level PreSeason: Off |
| Oil replaced type amount PreSeason: Off |
| Oil sample PreSeason: Off |
| SECTION 8 PUMPS MECHANICAL MOVEMENT: |
| Date_8: Off |
| Inspect booster pumps for bearing wearleakage Semi Annual: Off |
| Inspect pumps Semi Annual: Off |
| SECTION 9 STRUCTURAL PHYSICAL INSPECTION: |
| Date_9: Off |
| Inspect insulated panels for cracksbroken pieces Annually: Off |
| Inspect heat exchanger for cracks Annually: Off |
| SECTION 10 CHEMICAL SYSTEM MONITORING: |
| Date_10: Off |
| Chemical testing hardness alkalinity chlorides nitrite phosphates pH conductivity: Off |
| Maintain chemical feed systems scalecorrosion control biocides Monthly: Off |
| Provide monthly monitoring data in reports Monthly: Off |
| Technician: |
| Date_11: |
| Supervisor: |
| Text1: |
| Text2: |
| Text3: |
| Text4: |
| Text5: |
| Text6: |
| Text7: |
| Text8: |
| Text9: |
| Text10: |
| Text12: |