Attachment_K_–_Specifications.pdf

PDF 3 MB Posted

Attached to
Haven on Vine Renovation Project State and local contract opportunity
Solicitation number
RFP2025-010
Issued by
Polk County, Lake Harbor CDP, Florida

About this file

The document is a comprehensive set of construction specification sections for the Haven on Vine Renovation Project, issued by the City of Kissimmee, Florida. These detailed technical specifications cover various construction aspects including demolition, concrete work, masonry, metal fabrication, wood treatments, roofing, waterproofing, insulation, doors, windows, interior finishes, and accessories. The project involves converting a former Super 8 hotel located at 1815 West Vine Street into affordable housing, with a total of 120 units (40 emergency housing units and 80 apartment units) across four renovation phases. The specifications provide technical requirements for transforming the existing structures into residential spaces, with extensive details on materials, installation methods, quality standards, and performance expectations for each building system.

The project is funded through multiple sources including American Rescue Funds, County and City funds, HOME Investment Partnerships American Rescue Plan, and Community Development Block Grant, with a total estimated construction cost of approximately $4.0 million. The renovation will require comprehensive infrastructure upgrades, addressing potential structural, electrical, plumbing, mold, and lead paint issues while maintaining the existing building footprints. Contractors will need to comply with federal regulations including Davis-Bacon Act wage requirements, equal employment opportunity provisions, and drug-free workplace standards. The project aims to create affordable housing for low- and moderate-income residents, with proposals evaluated across four key categories: project approach, experience and expertise, scheduling and cost control, and overall project cost. The contract term is anticipated to be 24 months from the Notice to Proceed, with proposals originally due by 2:00 pm on May 20, 2025.

View the file

Other files for this state and local contract opportunity

Other files attached to Haven on Vine Renovation Project, newest first.
File Type Posted
Notice_of_Intent_-_RFP2025-010_Haven_on_Vine_Restoration_Project.pdf PDF
abstract._RFP2025-010_Haven_on_Vine_Project_Renovation_Project.pdf PDF
Addendum_2_RFP2025-010_Haven_on_Vine_Restoration_Project.pdf PDF
2025-05-07_REV_1_Sheets.dwf.pdf PDF
E001_-_ELECTRICAL_-_GENERAL.pdf PDF
Addendum_2_RFP2025-010_Haven_on_Vine_Restoration_Project.pdf PDF
E001_-_ELECTRICAL_-_GENERAL.pdf PDF
E801_-_ELECTRICAL_SCHEDULES_AND_DIAGRAMS.pdf PDF
Addendum_2_RFP2025-010_Haven_on_Vine_Restoration_Project.pdf PDF
E801_-_ELECTRICAL_SCHEDULES_AND_DIAGRAMS.pdf PDF
E001_-_ELECTRICAL_-_GENERAL.pdf PDF
Super_8_Hotel_Structural_Inspection_Report_S&S.pdf PDF
Addendum_1_RFP2025-010_Haven_on_Vine_Restoration_Project.pdf PDF
Addendum_1_RFP2025-010_Haven_on_Vine_Restoration_Project.pdf PDF
LMA_Report.pdf PDF
1815_W_Vine_St___Sewer_Inspection.pdf PDF
City_of_Kissimmee_Super_8_Motel_Inspection_Report_2_8_23_-_Structural_Comments.pdf PDF
1815_W_Vine_St___Sewer_Inspection.pdf PDF
LMA_Report.pdf PDF
City_of_Kissimmee_Super_8_Motel_Inspection_Report_2_8_23_-_Structural_Comments.pdf PDF
City_of_Kissimmee_Super_8_Motel_Inspection_Report_2_8_23_-_Structural_Comments.pdf PDF
1815_W_Vine_St___Sewer_Inspection.pdf PDF
City_of_Kissimmee_Super_8_Motel_Inspection_Report_2_8_23_-_Structural_Comments.pdf PDF
Attachment_H_-_Phase_2A_–_Energy_Conservation_Checklist-2A-022025-Signed.pdf PDF
Attachment_I_-_Phase_2B_–_Office_Building_Renovation.pdf PDF
Attachment_D_-_Phase_1A_–_43-Efficiency_Studio_Apartment_Units.pdf PDF
Attachment_L_-_General_Wage_Decision_3.29.24.pdf PDF
Attachment_M_-_Project_Location.pdf PDF
Attachment_K_–_Specifications.pdf PDF
Attachment_L_-_General_Wage_Decision_3.29.24.pdf PDF
Attachment_F_-_Phase_1B_–_Ten_Fourplex_Apartment_Building_Renovation.pdf PDF
Attachment_G_-_Phase_2A_–_40-Efficiency_Studio_Apartment_Units.pdf PDF
Attachment_H_-_Phase_2A_–_Energy_Conservation_Checklist-2A-022025-Signed.pdf PDF
Attachment_F_-_Phase_1B_–_Ten_Fourplex_Apartment_Building_Renovation.pdf PDF
Attachment_G_-_Phase_2A_–_40-Efficiency_Studio_Apartment_Units.pdf PDF
Attachment_L_-_General_Wage_Decision_3.29.24.pdf PDF
RFP20205-010_HAVEN_ON_VINE_-_Renovation_Project.pdf PDF
Attachment_F_-_Phase_1B_–_Ten_Fourplex_Apartment_Building_Renovation.pdf PDF
Attachment_G_-_Phase_2A_–_40-Efficiency_Studio_Apartment_Units.pdf PDF
Attachment_H_-_Phase_2A_–_Energy_Conservation_Checklist-2A-022025-Signed.pdf PDF
Attachment_J_-_Phase_2B_–_Energy_Conservation_Checklist-2B-022025-Signed.pdf PDF
Attachment_K_–_Specifications.pdf PDF
RFP20205-010_HAVEN_ON_VINE_-_Renovation_Project.pdf PDF
Attachment_F_-_Phase_1B_–_Ten_Fourplex_Apartment_Building_Renovation.pdf PDF
Attachment_J_-_Phase_2B_–_Energy_Conservation_Checklist-2B-022025-Signed.pdf PDF
Attachment_M_-_Project_Location.pdf PDF
RFP20205-010_HAVEN_ON_VINE_-_Renovation_Project.pdf PDF
Attachment_J_-_Phase_2B_–_Energy_Conservation_Checklist-2B-022025-Signed.pdf PDF
Attachment_L_-_General_Wage_Decision_3.29.24.pdf PDF
Attachment_I_-_Phase_2B_–_Office_Building_Renovation.pdf PDF
Show all 50

Haven on Vine Renovation Project has more files on GovTribe.

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Haven on Vine

24-13596 & 24-14065 00 01 01 - 1 Specifications Book

SPECIFICATIONS

FOR

HAVEN ON VINE

ARCHITECT'S PROJECT NUMBER: 24-13596 & 24-14064

PROJECT LOCATION

1815 WEST VINE STREET

KISSIMMEE, FL 34741

DATE: 2024-09-10

PREPARED BY: LENNARD DAVIS

FOREFRONT ARCHITECTURE AND ENGINEERING

2025-01-13

02 41 00 - 1 Demolition

SECTION 02 41 00

DEMOLITION

PART 1 GENERAL

1.01 SECTION INCLUDES

A. Building demolition excluding removal of hazardous materials and toxic substances.

B. Selective demolition of built site elements.

C. Selective demolition of building elements for alteration purposes.

D. Abandonment and removal of existing utilities and utility structures.

1.02 SUBMITTALS

A. Site Plan: Indicate:

1. Vegetation to be protected.

2. Areas for temporary construction and field offices.

B. Project Record Documents: Accurately record actual locations of capped and active utilities and subsurface construction.

PART 2 PRODUCTS -- NOT USED

PART 3 EXECUTION

3.01 DEMOLITION

A. Remove items indicated. Retain for salvage, relocation, or recycling as directed by owner.

B. Fill excavations, open pits, and holes in ground areas generated as result of removals.

3.02 GENERAL PROCEDURES AND PROJECT CONDITIONS

A. Comply with applicable codes and regulations for demolition operations and safety of adjacent structures and the public.

1. Obtain required permits.

2. Take precautions to prevent catastrophic or uncontrolled collapse of structures to be removed; do not allow worker or public access within range of potential collapse of unstable structures.

3. Provide, erect, and maintain temporary barriers and security devices.

4. Conduct operations to minimize effects on and interference with adjacent structures and occupants.

5. Do not close or obstruct roadways or sidewalks without permits from authority having jurisdiction.

6. Conduct operations to minimize obstruction of public and private entrances and exits. Do not obstruct required exits at any time. Protect persons using entrances and exits from removal operations.

7. Obtain written permission from owners of adjacent properties when demolition equipment will traverse, infringe upon, or limit access to their property.

B. Do not begin removal until receipt of notification to proceed from Owner.

C. Protect existing structures and other elements to remain in place and not removed.

1. Provide bracing and shoring.

2. Prevent movement or settlement of adjacent structures.

3. Stop work immediately if adjacent structures appear to be in danger.

D. Minimize production of dust due to demolition operations. Do not use water if that will result in ice, flooding, sedimentation of public waterways or storm sewers, or other pollution.

E. Hazardous Materials:

1. If hazardous materials are discovered during removal operations, stop work and notify Architect and Owner; hazardous materials include regulated asbestos containing materials, lead, PCBs, and mercury.

02 41 00 - 2 Demolition

3.03 EXISTING UTILITIES

A. Coordinate work with utility companies. Notify utilities before starting work, comply with their requirements, and obtain required permits.

B. Protect existing utilities to remain from damage.

C. Do not disrupt public utilities without permit from authority having jurisdiction.

D. Do not close, shut off, or disrupt existing life safety systems that are in use without at least 7 days prior written notification to Owner.

E. Do not close, shut off, or disrupt existing utility branches or take-offs that are in use without at least 3 days prior written notification to Owner.

F. Locate and mark utilities to remain; mark using highly visible tags or flags, with identification of utility type; protect from damage due to subsequent construction, using substantial barricades if necessary.

G. Remove exposed piping, valves, meters, equipment, supports, and foundations of disconnected and abandoned utilities.

H. Prepare building demolition areas by disconnecting and capping utilities outside the demolition zone. Identify and mark, in same manner as other utilities to remain, utilities to be reconnected.

3.04 SELECTIVE DEMOLITION FOR ALTERATIONS

A. Existing construction and utilities indicated on drawings are based on casual field observation and existing record documents only.

1. Verify construction and utility arrangements are as indicated.

2. Report discrepancies to Architect before disturbing existing installation.

3. Beginning of demolition work constitutes acceptance of existing conditions that would be apparent upon examination prior to starting demolition.

B. Separate areas in which demolition is being conducted from areas that remain occupied.

1. Provide, erect, and maintain temporary dustproof partitions of construction as needed to prevent dust or debris migration into areas not a part of this scope.

C. Remove existing work as indicated and required to accomplish new work.

1. Remove items indicated on drawings.

D. Services including, but not limited to, HVAC, Plumbing, Fire Protection, Electrical, and Telecommunications: Remove existing systems and equipment as indicated.

1. Maintain existing active systems to remain in operation and maintain access to equipment and operational components.

2. Where existing active systems serve occupied facilities but are to be replaced with new services, maintain existing systems in service until new systems are complete and ready for service.

3. Verify that abandoned services serve only abandoned facilities before removal.

4. Remove abandoned pipe, ducts, conduits, and equipment, including those above accessible ceilings. Remove back to source of supply where possible, otherwise cap stub and tag with identification.

E. Protect existing work to remain.

1. Prevent movement of structure. Provide shoring and bracing as required.

2. Perform cutting to accomplish removal work neatly and as specified for cutting new work.

3. Repair adjacent construction and finishes damaged during removal work.

4. Patch to match new work.

3.05 DEBRIS AND WASTE REMOVAL

A. Remove debris, junk, and trash from site.

B. Leave site in clean condition, ready for subsequent work.

C. Clean up spillage and wind-blown debris from public and private lands.

02 41 00 - 3 Demolition

END OF SECTION

03 10 00 - 1

Concrete Forming and

Accessories

SECTION 03 10 00

CONCRETE FORMING AND ACCESSORIES

PART 1 GENERAL

1.01 RELATED REQUIREMENTS

A. Section 05 12 00 - Structural Steel Framing: Placement of embedded steel anchors and plates in cast-in-place concrete.

1.02 REFERENCE STANDARDS

A. ACI SPEC-301 - Specifications for Concrete Construction; 2020.

B. ASTM D471 - Standard Test Method for Rubber Property--Effect of Liquids; 2016a (Reapproved 2021).

C. COE CRD-C 513 - Handbook for Concrete and Cement Corps of Engineers Specifications for Rubber Waterstops; 1974.

D. COE CRD-C 572 - Handbook for Concrete and Cement Corps of Engineers Specifications for Polyvinylchloride Waterstop; 1974.

E. NSF 372 - Drinking Water System Components - Lead Content; 2022.

F. NSF 61 - Drinking Water System Components - Health Effects; 2023, with Errata.

1.03 DELIVERY, STORAGE, AND HANDLING

A. Deliver prefabricated forms and installation instructions in manufacturer's packaging.

B. Store prefabricated forms off ground in ventilated and protected manner to prevent deterioration from moisture.

C. Protect plastic foam products from damage and exposure to sunlight.

PART 2 PRODUCTS

2.01 FORMWORK - GENERAL

A. Provide concrete forms, accessories, shoring, and bracing as required to accomplish cast-in-place concrete work.

B. Design and construct concrete that complies with design with respect to shape, lines, and dimensions.

C. Comply with applicable state and local codes with respect to design, fabrication, erection, and removal of formwork.

2.02 WOOD FORM MATERIALS

A. Lumber: Southern Pine or Douglas Fir species economy grade or better; with grade stamp clearly visible.

2.03 REMOVABLE PREFABRICATED FORMS

A. Pan Type: Glass fiber, of size and profile indicated.

B. Void Forms: Moisture resistant treated paper faces, biodegradable, structurally sufficient to support weight of wet concrete mix until initial set; 2 inches thick.

2.04 FORMWORK ACCESSORIES

A. Form Ties: Removable type, galvanized metal, fixed length, cone type, with waterproofing washer.

B. Form Release Agent: Capable of releasing forms from hardened concrete without staining or discoloring concrete or forming bugholes and other surface defects, compatible with concrete and form materials, and not requiring removal for satisfactory bonding of coatings to be applied.

C. Dowel Sleeves: Plastic sleeve and nailable plastic base for smooth, round, steel load-transfer dowels.

03 10 00 - 2

Concrete Forming and

Accessories

D. Nails, Spikes, Lag Bolts, Through Bolts, Anchorages: Sized as required, of sufficient strength and character to maintain formwork in place while placing concrete.

E. Embedded Anchor Shapes, Plates, Angles and Bars: As specified in Section 05 12 00.

F. Waterstops: Rubber, complying with COE CRD-C 513, maximum possible lengths, ribbed profile, preformed corner sections, heat welded jointing.

G. Waterstops: PVC, complying with COE CRD-C 572.

1. Configuration: As indicated on drawings.

2. Size: As indicated on drawings.

PART 3 EXECUTION

3.01 EXAMINATION

A. Verify lines, levels and centers before proceeding with formwork. Ensure that dimensions agree with drawings.

3.02 EARTH FORMS

A. Hand trim sides and bottom of earth forms. Remove loose soil prior to placing concrete.

3.03 ERECTION - FORMWORK

A. Erect formwork, shoring and bracing to achieve design requirements, in accordance with requirements of ACI SPEC-301.

B. Provide bracing to ensure stability of formwork. Shore or strengthen formwork subject to overstressing by construction loads.

C. Install void forms in accordance with manufacturer's recommendations. Protect forms from moisture or crushing.

3.04 APPLICATION - FORM RELEASE AGENT

A. Apply form release agent on formwork in accordance with manufacturer's recommendations.

3.05 INSERTS, EMBEDDED PARTS, AND OPENINGS

A. Coordinate with work of other sections in forming and placing openings, slots, reglets, recesses, sleeves, bolts, anchors, other inserts, and components of other work.

B. Install waterstops in accordance with manufacturer's instructions, so they are continuous without displacing reinforcement.

3.06 FORMWORK TOLERANCES

A. Construct permanent insulated foam panel formwork to maintain tolerances required by ACI

SPEC-301.

3.07 FORM REMOVAL

A. Do not remove forms or bracing until concrete has gained sufficient strength to carry its own weight and imposed loads.

03 20 00 - 1 Concrete Reinforcing

SECTION 03 20 00

CONCRETE REINFORCING

PART 1 GENERAL

1.01 SECTION INCLUDES

A. Reinforcing steel for cast-in-place concrete.

B. Supports and accessories for steel reinforcement.

1.02 RELATED REQUIREMENTS

A. Section 03 10 00 - Concrete Forming and Accessories.

B. Section 03 30 00 - Cast-in-Place Concrete.

1.03 REFERENCE STANDARDS

A. ACI CODE-318 - Building Code Requirements for Structural Concrete and Commentary; 2019 (Reapproved 2022).

B. ACI MNL-66 - ACI Detailing Manual; 2020.

C. ASTM A615/A615M - Standard Specification for Deformed and Plain Carbon-Steel Bars for Concrete Reinforcement; 2022.

D. ASTM A704/A704M - Standard Specification for Welded Steel Plain Bar or Rod Mats for Concrete Reinforcement; 2019, with Editorial Revision.

E. ASTM A706/A706M - Standard Specification for Deformed and Plain Low-Alloy Steel Bars for Concrete Reinforcement; 2022a.

F. ASTM A767/A767M - Standard Specification for Zinc-Coated (Galvanized) Steel Bars for Concrete Reinforcement; 2019.

G. ASTM A996/A996M - Standard Specification for Rail-Steel and Axle-Steel Deformed Bars for Concrete Reinforcement; 2016.

H. ASTM A1035/A1035M - Standard Specification for Deformed and Plain, Low-Carbon, Chromium, Steel Bars for Concrete Reinforcement; 2023a.

I. ASTM A1064/A1064M - Standard Specification for Carbon-Steel Wire and Welded Wire Reinforcement, Plain and Deformed, for Concrete; 2022.

J. AWS B2.1/B2.1M - Specification for Welding Procedure and Performance Qualification; 2021.

K. CRSI (DA4) - Manual of Standard Practice; 2023.

1.04 SUBMITTALS

A. Shop Drawings: Comply with requirements of ACI MNL-66 Include bar schedules, shapes of bent bars, spacing of bars, and location of splices.

1. Prepare shop drawings under seal of a Professional Structural Engineer experienced in design of work of this type and licensed in the State in which the Project is located.

B. Manufacturer's Certificate: Certify that reinforcing steel and accessories supplied for this project meet or exceed specified requirements.

C. Welders' Qualification Statement: Welders' certificates in accordance with AWS B2.1/B2.1M and dated no more than 12 months before start of scheduled welding work.

PART 2 PRODUCTS

2.01 MANUFACTURERS

A. Reinforcing Steel:

1. Commercial Metals Company; Rebar: www.cmc.com/#sle or equal.

2.02 REINFORCEMENT

A. Reinforcing Steel: ASTM A615/A615M, Grade 60 (60,000 psi).

03 20 00 - 2 Concrete Reinforcing

1. Plain billet-steel bars.

2. Galvanized in accordance with ASTM A767/A767M, Class I.

B. Reinforcing Steel: ASTM A706/A706M, deformed low-alloy steel bars.

1. Unfinished.

C. Reinforcing Steel: Plain or deformed bars; ASTM A1035/A1035M, Grade 100 (100,000 psi), Type CL.

D. Stirrup Steel: ASTM A1064/A1064M steel wire, unfinished.

E. Steel Welded Wire Reinforcement (WWR): Galvanized, deformed type; ASTM A1064/A1064M.

1. Form: Flat Sheets.

2. WWR Style: 4 x 8-W6 x W10.

F. Reinforcement Accessories:

1. Tie Wire: Annealed, minimum 16 gauge, 0.0508 inch.

2. Chairs, Bolsters, Bar Supports, Spacers: Sized and shaped for adequate support of reinforcement during concrete placement.

2.03 RE-BAR SPLICING:

A. Coupler Systems: Mechanical devices for splicing reinforcing bars.

1. Comply with ACI CODE-318 steel reinforcing design strength requirements for splices in tension and compression.

2. Products:

a. Dayton Superior Corporation; www.daytonsuperior.com/#sle.

b. Splice Sleeve North America, Inc; NMB Splice Sleeve System: www.splicesleeve.com/#sle.

c. Or equal.

B. Dowel Bar Splicer with Dowel-Ins: Mechanical devices for splicing reinforcing bars.

1. Comply with ACI CODE-318 steel reinforcing design strength requirements for splices in tension and compression.

2. Products:

a. Dayton Superior Corporation; www.daytonsuperior.com/#sle.

3. Acceptable equal approved by architect.

C. Taper Tie Hole Plug: Mechanical device for plugging tie holes; anchors optional flush or recessed grout.

1. Products:

a. Dayton Superior Corporation; www.daytonsuperior.com/#sle.

2. Acceptable equal approved by architect.

D. Grout: Cementitious, non-metallic, non-shrink grout for use with manufacturer's grout sleeve reinforcing bar coupler system.

1. Products:

a. Dayton Superior Corporation; _______: www.daytonsuperior.com/#sle.

2. Acceptable equal approved by architect.

2.04 FABRICATION

A. Fabricate concrete reinforcing in accordance with CRSI (DA4) - Manual of Standard Practice.

B. Welding of reinforcement is not permitted.

C. Locate reinforcing splices not indicated on drawings at point of minimum stress.

PART 3 EXECUTION

3.01 PLACEMENT

A. Place, support and secure reinforcement against displacement. Do not deviate from required position.

03 20 00 - 3 Concrete Reinforcing

B. Do not displace or damage vapor barrier.

C. Accommodate placement of formed openings.

D. Maintain concrete cover around reinforcing as follows:

1. Footings and Concrete Formed Against Earth: 2 inch.

2. Slabs on Fill: 2 inch.

3.02 FIELD QUALITY CONTROL

A. An independent testing agency, as specified in Section 01 40 00 - Quality Requirements, will inspect installed reinforcement for compliance with contract documents before concrete placement.

3.03 SCHEDULES

A. Reinforcement For Superstructure Framing Members: Deformed bars, unfinished.

B. Reinforcement For Foundation Wall Framing Members and Slab-on-Grade: Deformed bars and welded wire reinforcement, galvanized finish.

C. Reinforcement For Parking Structure Framing Members: Deformed bars, epoxy coated finish.

03 30 00 - 1 Cast-in-Place Concrete

SECTION 03 30 00

CAST-IN-PLACE CONCRETE

PART 1 GENERAL

1.01 SECTION INCLUDES

A. Concrete formwork.

B. Concrete building frame members.

C. Concrete for composite floor construction.

D. Elevated concrete slabs.

E. Floors and slabs on grade.

F. Concrete shear walls, elevator shaft walls, and foundation walls.

G. Concrete foundations and anchor bolts for pre-engineered building.

H. Joint devices associated with concrete work.

I. Miscellaneous concrete elements, including equipment pads, equipment pits, light pole bases, flagpole bases, thrust blocks, and manholes.

J. Concrete curing.

1.02 RELATED REQUIREMENTS

A. Section 03 10 00 - Concrete Forming and Accessories: Forms and accessories for formwork.

B. Section 03 20 00 - Concrete Reinforcing.

C. Section 07 92 00 - Joint Sealants: Products and installation for sealants and joint fillers for saw cut joints and isolation joints in slabs.

1.03 REFERENCE STANDARDS

A. ACI 211.2 - Standard Practice for Selecting Proportions for Structural Lightweight Concrete;

1998 (Reapproved 2004).

B. ACI CODE-318 - Building Code Requirements for Structural Concrete and Commentary; 2019 (Reapproved 2022).

C. ACI PRC-211.1 - Selecting Proportions for Normal-Density and High Density-Concrete - Guide;

2022.

D. ACI PRC-302.1 - Guide to Concrete Floor and Slab Construction; 2015.

E. ACI PRC-304 - Guide for Measuring, Mixing, Transporting, and Placing Concrete; 2000 (Reapproved 2009).

F. ACI PRC-305 - Guide to Hot Weather Concreting; 2020.

G. ACI PRC-308 - Guide to External Curing of Concrete; 2016.

H. ACI SPEC-301 - Specifications for Concrete Construction; 2020.

I. ASTM C33/C33M - Standard Specification for Concrete Aggregates; 2023.

J. ASTM C39/C39M - Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens; 2023.

K. ASTM C94/C94M - Standard Specification for Ready-Mixed Concrete; 2024.

L. ASTM C109/C109M - Standard Test Method for Compressive Strength of Hydraulic Cement Mortars (Using 50 mm [2 in.] Cube Specimens); 2023.

M. ASTM C150/C150M - Standard Specification for Portland Cement; 2022.

N. ASTM C157/C157M - Standard Test Method for Length Change of Hardened Hydraulic- Cement Mortar and Concrete; 2017.

O. ASTM C173/C173M - Standard Test Method for Air Content of Freshly Mixed Concrete by the Volumetric Method; 2023.

03 30 00 - 2 Cast-in-Place Concrete

P. ASTM C260/C260M - Standard Specification for Air-Entraining Admixtures for Concrete; 2010a (Reapproved 2016).

Q. ASTM C309 - Standard Specification for Liquid Membrane-Forming Compounds for Curing Concrete; 2019.

R. ASTM C330/C330M - Standard Specification for Lightweight Aggregates for Structural Concrete; 2023.

S. ASTM C348 - Standard Test Method for Flexural Strength of Hydraulic-Cement Mortars; 2021.

T. ASTM C494/C494M - Standard Specification for Chemical Admixtures for Concrete; 2019, with Editorial Revision (2022).

U. ASTM C579 - Standard Test Methods for Compressive Strength of Chemical-Resistant Mortars, Grouts, Monolithic Surfacings, and Polymer Concretes; 2023.

V. ASTM C618 - Standard Specification for Coal Ash and Raw or Calcined Natural Pozzolan for Use in Concrete; 2023, with Editorial Revision.

W. ASTM C685/C685M - Standard Specification for Concrete Made by Volumetric Batching and Continuous Mixing; 2017.

X. ASTM C827/C827M - Standard Test Method for Change in Height at Early Ages of Cylindrical Specimens of Cementitious Mixtures; 2023.

Y. ASTM C845/C845M - Standard Specification for Expansive Hydraulic Cement; 2018.

Z. ASTM C881/C881M - Standard Specification for Epoxy-Resin-Base Bonding Systems for Concrete; 2020a.

AA. ASTM C979/C979M - Standard Specification for Pigments for Integrally Colored Concrete;

2016.

BB. ASTM C1059/C1059M - Standard Specification for Latex Agents for Bonding Fresh to Hardened Concrete; 2021.

CC. ASTM C1107/C1107M - Standard Specification for Packaged Dry, Hydraulic-Cement Grout (Nonshrink); 2020.

DD. ASTM C1116/C1116M - Standard Specification for Fiber-Reinforced Concrete; 2023.

EE. ASTM C1202 - Standard Test Method for Electrical Indication of Concrete’s Ability to Resist Chloride Ion Penetration; 2019.

FF. ASTM C1240 - Standard Specification for Silica Fume Used in Cementitious Mixtures; 2020.

GG. ASTM C1315 - Standard Specification for Liquid Membrane-Forming Compounds Having Special Properties for Curing and Sealing Concrete; 2019.

HH. ASTM C1602/C1602M - Standard Specification for Mixing Water Used in the Production of Hydraulic Cement Concrete; 2022.

II. ASTM C1708/C1708M - Standard Test Methods for Self-Leveling Mortars Containing Hydraulic Cements; 2023.

JJ. ASTM D471 - Standard Test Method for Rubber Property--Effect of Liquids; 2016a (Reapproved 2021).

KK. ASTM D695 - Standard Test Method for Compressive Properties of Rigid Plastics; 2023.

LL. ASTM D1751 - Standard Specification for Preformed Expansion Joint Filler for Concrete Paving and Structural Construction (Nonextruding and Resilient Asphalt Types); 2023.

MM. ASTM E154/E154M - Standard Test Methods for Water Vapor Retarders Used in Contact with Earth Under Concrete Slabs, on Walls, or as Ground Cover; 2008a (Reapproved 2019).

NN. ASTM E1643 - Standard Practice for Selection, Design, Installation, and Inspection of Water Vapor Retarders Used in Contact with Earth or Granular Fill Under Concrete Slabs; 2018a.

OO. ASTM E1745 - Standard Specification for Plastic Water Vapor Retarders Used in Contact with Soil or Granular Fill under Concrete Slabs; 2017 (Reapproved 2023).

03 30 00 - 3 Cast-in-Place Concrete

PP. ASTM E1993/E1993M - Standard Specification for Bituminous Water Vapor Retarders Used in Contact with Soil or Granular Fill Under Concrete Slabs; 1998 (Reapproved 2020).

QQ. COE CRD-C 48 - Handbook for Concrete and Cement Standard Test Method for Water Permeability of Concrete; 1992.

RR. COE CRD-C 513 - Handbook for Concrete and Cement Corps of Engineers Specifications for Rubber Waterstops; 1974.

SS. COE CRD-C 572 - Handbook for Concrete and Cement Corps of Engineers Specifications for Polyvinylchloride Waterstop; 1974.

TT. ICRI 310.2R - Selecting and Specifying Concrete Surface Preparation for Sealers, Coatings, Polymer Overlays, and Concrete Repair; 2013.

UU. NSF 61 - Drinking Water System Components - Health Effects; 2023, with Errata.

VV. NSF 372 - Drinking Water System Components - Lead Content; 2022.

1.04 SUBMITTALS

A. Product Data: Submit manufacturers' data on manufactured products showing compliance with specified requirements and installation instructions.

1. For curing compounds, provide data on method of removal in the event of incompatibility with floor covering adhesives.

2. For chemical-resistant waterstops, provide data on ASTM D471 test results.

3. For membrane-forming, moisture emission-reducing, curing and sealing compound, provide manufacturer's installation instructions,.

B. Mix Design: Submit proposed concrete mix design.

1. Indicate proposed mix design complies with requirements of ACI CODE-318, Chapter 5 - Concrete Quality, Mixing and Placing.

2. Indicate proposed mix design complies with fiber reinforcing manufacturer's written recommendations.

C. Test Reports: Submit report for each test or series of tests specified.

D. Project Record Documents: Accurately record actual locations of embedded utilities and components that will be concealed from view upon completion of concrete work.

1.05 QUALITY ASSURANCE

A. Perform work of this section in accordance with ACI SPEC-301 and ACI CODE-318.

B. Follow recommendations of ACI PRC-305 when concreting during hot weather.

PART 2 PRODUCTS

2.01 FORMWORK

A. Comply with requirements of Section 03 10 00.

2.02 REINFORCEMENT MATERIALS

A. Comply with requirements of Section 03 20 00.

2.03 CONCRETE MATERIALS

A. Cement: ASTM C150/C150M, Type I - Normal Portland type.

1. Acquire cement for entire project from same source.

B. Blended, Expansive Hydraulic Cement: ASTM C845/C845M, Type K.

1. Products:

a. CTS Cement Manufacturing Corporation; Type K Cement: www.ctscement.com/#sle.

b. Euclid Chemical Company; EUCON MSA: www.euclidchemical.com/#sle.

c. Acceptable equal approved by architect.

C. Fine and Coarse Aggregates: ASTM C33/C33M.

1. Acquire aggregates for entire project from same source.

03 30 00 - 4 Cast-in-Place Concrete

D. Lightweight Aggregate: ASTM C330/C330M.

E. Fly Ash: ASTM C618, Class C or F.

F. Calcined Pozzolan: ASTM C618, Class N.

G. Silica Fume: ASTM C1240, proportioned in accordance with ACI PRC-211.1.

H. Water: ASTM C1602/C1602M; clean, potable, and not detrimental to concrete.

2.04 ADMIXTURES

A. Air Entrainment Admixture: ASTM C260/C260M.

B. High Range Water Reducing and Retarding Admixture: ASTM C494/C494M Type G.

C. High Range Water Reducing Admixture: ASTM C494/C494M Type F.

D. Water Reducing and Accelerating Admixture: ASTM C494/C494M Type E.

E. Water Reducing and Retarding Admixture: ASTM C494/C494M Type D.

F. Accelerating Admixture: ASTM C494/C494M Type C.

G. Retarding Admixture: ASTM C494/C494M Type B.

H. Water Reducing Admixture: ASTM C494/C494M Type A.

I. Shrinkage Reducing Admixture:

1. ASTM C494/C494M, Type S.

J. Shrinkage Compensating Admixture: For on site production of concrete with ASTM C845/C845M, Type K cement.

K. Shrinkage Compensating Admixture with Fiber Reinforcement: For on site production of concrete with ASTM C845/C845M, Type K cement with integral fiber reinforcement.

L. Corrosion Inhibiting Admixture:

1. ASTM C494/C494M, Type C.

M. Waterproofing Admixture: Admixture formulated to reduce permeability to liquid water, with no adverse effect on concrete properties.

1. Admixture Composition: Hydrophobic polymer waterproofing and corrosion inhibitor, functioning by closing concrete pores and chemical bonding.

2. Permeability of Cured Concrete: No measurable leakage when tested in accordance with COE CRD-C 48 at 200 psi; provide test reports.

3. Potable Water Contact Approval: National Science Foundation (NSF) certification for use on structures holding potable water, based on testing in accordance with NSF 61 and NSF

4. Products:

a. Fullforce by ABC Polymers Industries, LLC; DuraForce (iwp): www.fullforcesolutions.us/#sle.

b. Hycrete, Inc; www.hycrete.com/#sle.

c. Acceptable equal approved by architect.

2.05 ACCESSORY MATERIALS

A. Non-Shrink Cementitious Grout: Premixed compound consisting of nonmetallic aggregate, cement, water reducing and plasticizing agents.

1. Grout: Comply with ASTM C1107/C1107M.

2. Height Change, Plastic State; when tested in accordance with ASTM C827/C827M:

a. Maximum: Plus 4 percent.

b. Minimum: Plus 1 percent.

3. Minimum Compressive Strength at 28 Days, ASTM C109/C109M: 7,000 pounds per square inch.

4. Products containing aluminum powder are not permitted.

5. Low-Slump, Dry Pack Products:

03 30 00 - 5 Cast-in-Place Concrete

a. Euclid Chemical Company; DRY PACK GROUT: www.euclidchemical.com/#sle.

b. Five Star Products, Inc; Five Star Grout: www.fivestarproducts.com/#sle.

c. SpecChem, LLC; SC Multipurpose Grout: www.specchemllc.com/#sle.

d. Acceptable equal approved by architect.

B. Non-Shrink Epoxy Grout: Moisture-insensitive, two-part; consisting of epoxy resin, nonmetallic aggregate, and activator.

1. Composition: High solids content material exhibiting positive expansion when tested in accordance with ASTM C827/C827M.

a. Maximum Height Change: Plus 4 percent.

b. Minimum Height Change: Plus 1 percent.

2. Minimum Compressive Strength at 7 days, ASTM C579: 12,000 pounds per square inch.

3. Minimum Compressive Strength at 7 days, ASTM D695: 12,000 pounds per square inch.

4. Products:

a. Adhesives Technology Corporation; ACCU-GROUT: www.atcepoxy.com/#sle.

b. LATICRETE International, Inc; EPOGROUT 758: www.laticrete.com/#sle.

c. Acceptable equal approved by architect.

2.06 CURING MATERIALS

A. Curing Compound, Naturally Dissipating: Clear, water-based, liquid membrane-forming compound; complying with ASTM C309.

1. Product dissipates within 4 to 6 weeks.

2. Provide product containing fugitive red dye.

3. Products:

a. Dayton Superior Corporation; www.daytonsuperior.com/#sle.

b. Euclid Chemical Company; COLOR-CRETE CURE AND SEAL VOC: www.euclidchemical.com/#sle.

c. Acceptable equal approved by architect.

B. Curing Agent, Water-Cure Equivalent Type: Clear, water-based, non-film-forming, liquid-water cure replacement agent.

1. Application: Use at __________.

2. Comply with ASTM C309 standards for water retention.

3. Compressive Strength of Treated Concrete: Equal to or greater than strength after 14-day water cure when tested in accordance with ASTM C39/C39M.

4. VOC Content: Zero.

5. Products:

a. Sinak Corporation; LithiumCure 1000: www.sinak.com/#sle.

b. Sinak Corporation; LithiumCure 2000: www.sinak.com/#sle.

c. LATICRETE International, Inc; L&M CURE: www.laticrete.com/#sle.

d. Acceptable equal approved by architect.

2.07 CONCRETE MIX DESIGN

A. Proportioning Normal Weight Concrete: Comply with ACI PRC-211.1 recommendations.

1. Replace as much Portland cement as possible with fly ash, ground granulated blast furnace slag, silica fume, or rice hull ash as is consistent with ACI recommendations.

B. Concrete Strength: Establish required average strength for each type of concrete on the basis of field experience or trial mixtures, as specified in ACI SPEC-301.

1. For trial mixtures method, employ independent testing agency acceptable to Architect for preparing and reporting proposed mix designs.

C. Admixtures: Add acceptable admixtures as recommended in ACI PRC-211.1 and at rates recommended or required by manufacturer.

D. Normal Weight Concrete:

1. Compressive Strength, when tested in accordance with ASTM C39/C39M at 28 days: 3,000 pounds per square inch.

03 30 00 - 6 Cast-in-Place Concrete

2. Fly Ash Content: Maximum 15 percent of cementitious materials by weight.

3. Calcined Pozzolan Content: Maximum 10 percent of cementitious materials by weight.

4. Silica Fume Content: Maximum 5 percent of cementitious materials by weight.

5. Cement Content: Minimum ___ pounds per cubic yard.

6. Water-Cement Ratio: Maximum 40 percent by weight.

7. Total Air Content: 4 percent, determined in accordance with ASTM C173/C173M.

8. Maximum Slump: 3 inches.

9. Maximum Aggregate Size: 5/8 inch.

2.08 MIXING

A. On Project Site: Mix in drum type batch mixer, complying with ASTM C685/C685M. Mix each batch not less than 1-1/2 minutes and not more than 5 minutes.

B. Transit Mixers: Comply with ASTM C94/C94M.

C. Adding Water: If concrete arrives on-site with slump less than suitable for placement, do not add water that exceeds the maximum water-cement ratio or exceeds the maximum permissible slump.

D. Do not use shrinkage-reducing admixture (SRA) in same concrete batch with MVRA or PIA.

PART 3 EXECUTION

3.01 EXAMINATION

A. Verify lines, levels, and dimensions before proceeding with work of this section.

3.02 PREPARATION

A. Verify that forms are clean and free of rust before applying release agent.

B. Coordinate placement of embedded items with erection of concrete formwork and placement of form accessories.

C. Prepare existing concrete surfaces to be repaired according to ICRI 310.2R.

D. Where new concrete is to be bonded to previously placed concrete, prepare existing surface by cleaning and applying bonding agent in according to bonding agent manufacturer's instructions.

1. Use epoxy bonding system for bonding to damp surfaces, for structural load-bearing applications, and where curing under humid conditions is required.

2. Use latex bonding agent only for non-load-bearing applications.

E. Where new concrete with integral waterproofing is to be bonded to previously placed concrete, prepare surfaces to be treated in accordance with waterproofing manufacturer's instructions.

Saturate cold joint surface with clean water and remove excess water before application of coat of waterproofing admixture slurry. Apply slurry coat uniformly with semi-stiff bristle brush at rate recommended by waterproofing manufacturer.

F. In locations where new concrete is doweled to existing work, drill holes in existing concrete, insert steel dowels and pack solid with non-shrink grout.

3.03 PLACING CONCRETE

A. Place concrete in accordance with ACI PRC-304.

B. Ensure reinforcement, inserts, waterstops, embedded parts, and formed construction joint devices will not be disturbed during concrete placement.

3.04 SLAB JOINTING

A. Locate joints as indicated on drawings.

B. Anchor joint fillers and devices to prevent movement during concrete placement.

C. Isolation Joints: Use preformed joint filler with removable top section for joint sealant, total height equal to thickness of slab, set flush with top of slab.

3.05 CURING AND PROTECTION

03 30 00 - 7 Cast-in-Place Concrete

A. Comply with requirements of ACI PRC-308. Immediately after placement, protect concrete from premature drying, excessively hot or cold temperatures, and mechanical injury.

B. Maintain concrete with minimal moisture loss at relatively constant temperature for period necessary for hydration of cement and hardening of concrete.

3.06 FIELD QUALITY CONTROL

A. An independent testing agency will perform field quality control tests, as specified in Section 01 40 00 - Quality Requirements.

B. Provide free access to concrete operations at project site and cooperate with appointed firm.

3.07 DEFECTIVE CONCRETE

A. Test Results: The testing agency shall report test results in writing to Architect and Contractor within 24 hours of test.

B. Defective Concrete: Concrete not complying with required lines, details, dimensions, tolerances or specified requirements.

C. Repair or replacement of defective concrete will be determined by the Architect. The cost of additional testing shall be borne by Contractor when defective concrete is identified.

040511 - 1 Masonry Mortaring and Grouting

SECTION 040511

MASONRY MORTARING AND GROUTING

PART 1 GENERAL

1.01 SECTION INCLUDES

A. Mortar for masonry.

B. Grout for masonry.

1.02 RELATED REQUIREMENTS

A. Section 042000 - Unit Masonry: Installation of mortar and grout.

B. Section 042613 - Masonry Veneer: Installation of mortar.

C. Section 081113 - Hollow Metal Doors and Frames: Products and execution for grouting steel door frames installed in masonry.

1.03 REFERENCE STANDARDS

A. ASTM C91/C91M - Standard Specification for Masonry Cement; 2023.

B. ASTM C94/C94M - Standard Specification for Ready-Mixed Concrete; 2024.

C. ASTM C144 - Standard Specification for Aggregate for Masonry Mortar; 2018.

D. ASTM C270 - Standard Specification for Mortar for Unit Masonry; 2019a, with Editorial Revision.

E. ASTM C404 - Standard Specification for Aggregates for Masonry Grout; 2024.

F. ASTM C476 - Standard Specification for Grout for Masonry; 2023.

G. ASTM C1072 - Standard Test Methods for Measurement of Masonry Flexural Bond Strength;

2022.

H. ASTM C1314 - Standard Test Method for Compressive Strength of Masonry Prisms; 2023b.

I. ASTM C1714/C1714M - Standard Specification for Preblended Dry Mortar Mix for Unit Masonry; 2019a.

J. ASTM E514/E514M - Standard Test Method for Water Penetration and Leakage Through Masonry; 2020.

K. TMS 402/602 - Building Code Requirements and Specification for Masonry Structures; 2022, with Errata (2024).

1.04 SUBMITTALS

A. Product Data: Include design mix and indicate whether the Proportion or Property specification of ASTM C270 is to be used. Also include required environmental conditions and admixture limitations.

1.05 QUALITY ASSURANCE

A. Comply with provisions of TMS 402/602, except where exceeded by requirements of Contract Documents.

1.06 DELIVERY, STORAGE, AND HANDLING

A. Maintain packaged materials clean, dry, and protected against dampness, freezing, and foreign matter.

1.07 FIELD CONDITIONS

A. Cold and Hot Weather Requirements: Comply with requirements of TMS 402/602 or applicable building code, whichever is more stringent.

040511 - 2 Masonry Mortaring and Grouting

PART 2 PRODUCTS

2.01 MORTAR AND GROUT APPLICATIONS

A. At Contractor's option, mortar and grout may be field-mixed from packaged dry materials, made from factory premixed dry materials with addition of water only, or ready-mixed.

B. Mortar Mix Designs: ASTM C270, Property Specification.

1. Masonry below grade and in contact with earth: Type S.

2. Exterior Masonry Veneer: Type N.

3. Exterior Cavity Walls: Type S mortar with Type N pointing mortar.

4. Exterior, Loadbearing Masonry: Type N.

5. Exterior, Non-loadbearing Masonry: Type N.

6. Interior, Loadbearing Masonry: Type N.

7. Interior, Non-loadbearing Masonry: Type O.

C. Grout Mix Designs:

1. Bond Beams and Lintels: 3,000 psi (21 MPa) strength at 28 days; 8-10 inches (200-250

mm) slump; provide premixed type in accordance with ASTM C 94/C 94M.

2.02 MATERIALS

A. Packaged Dry Material for Mortar for Unit Masonry: Premixed Portland cement, hydrated lime, and sand; complying with ASTM C1714/C1714M and capable of producing mortar of the specified strength in accordance with ASTM C270 with the addition of water only.

1. Type: Type N.

2. Color: Standard gray.

3. Water repellent mortar for use with water repellent masonry units.

B. Packaged Dry Material for Mortar for Repointing: Premixed Portland cement, graded sand, and chemical admixtures complying with ASTM C91/C91M with the addition of water only.

1. Color: Natural gray.

C. Packaged Dry Material for Grout for Masonry: Premixed cementitious materials and dried aggregates; capable of producing grout of the specified strength in accordance with ASTM C476 with the addition of water only.

1. Type: Fine.

D. Portland Cement: ASTM C150/C150M.

1. Type: Type I - Normal; ASTM C150/C150M.

2. Color: Standard gray.

E. Masonry Cement: ASTM C91/C91M.

1. Type: Type N; ASTM C91/C91M.

F. Mortar Aggregate: ASTM C144.

G. Grout Aggregate: ASTM C404.

H. Pigments for Colored Mortar: Pure, concentrated mineral pigments specifically intended for mixing into mortar and complying with ASTM C979/C979M.

1. Color(s): As selected by Architect from manufacturer's full range.

2. Manufacturers:

a. Davis Colors; www.daviscolors.com/#sle.

b. Solomon Colors; Solomon Colors Concentrated A, H, and X Series: www.solomoncolors.com/#sle.

c. Acceptable equal approved by architect.

I. Water: Clean and potable.

J. Bonding Agent: Latex type.

K. Integral Water Repellent Admixture: Polymeric liquid admixture added to mortar at the time of manufacture.

1. Performance of Mortar with Integral Water Repellent:

040511 - 3 Masonry Mortaring and Grouting

a. Water Permeance: When tested per ASTM E514/E514M and for a minimum of 72 hours:

1) No water visible on back of wall above flashing at the end of 24 hours.

2) No flow of water from flashing equal to or greater than 0.032 gallons per hour (0.05 L per hour) at the end of 24 hours.

3) No more than 25 percent of wall area above flashing visibly damp at end of test.

b. Flexural Bond Strength: ASTM C1072; minimum 10 percent increase.

c. Compressive Strength: ASTM C1314; maximum 5 percent decrease.

2. Use only in combination with masonry units produced with integral water repellent admixture.

3. Manufacturers:

a. Hycrete, Inc; www.hycrete.com/#sle.

b. Acceptable equal approved by architect.

2.03 MORTAR MIXING

A. Thoroughly mix mortar ingredients using mechanical batch mixer, in accordance with ASTM C270 and in quantities needed for immediate use.

B. Maintain sand uniformly damp immediately before the mixing process.

C. Colored Mortar: Proportion selected pigments and other ingredients to match Architect's sample, without exceeding manufacturer's recommended pigment-to-cement ratio; mix in accordance with manufacturer's instructions, uniform in coloration.

D. Add admixtures in accordance with manufacturer's instructions; mix uniformly.

E. Do not use anti-freeze compounds to lower the freezing point of mortar.

F. If water is lost by evaporation, re-temper only within two hours of mixing.

2.04 GROUT MIXING

A. Mix grout in accordance with ASTM C94/C94M.

B. Thoroughly mix grout ingredients in quantities needed for immediate use in accordance with ASTM C476 for fine and coarse grout.

C. Add admixtures in accordance with manufacturer's instructions; mix uniformly.

PART 3 EXECUTION

3.01 PREPARATION

A. Apply bonding agent to existing concrete surfaces.

B. Plug clean-out holes for grouted masonry with brick masonry units. Brace masonry to resist wet grout pressure.

3.02 INSTALLATION

A. Install mortar and grout to requirements of section(s) in which masonry is specified.

B. Work grout into masonry cores and cavities to eliminate voids.

C. Do not displace reinforcement while placing grout.

D. Remove excess mortar from grout spaces.

04 20 00 - 1 Unit Masonry

SECTION 04 20 00

UNIT MASONRY

PART 1 GENERAL

1.01 SECTION INCLUDES

A. Concrete block.

B. Mortar and grout.

C. Reinforcement and anchorage.

D. Accessories.

1.02 RELATED REQUIREMENTS

A. Section 03 20 00 - Concrete Reinforcing: Reinforcing steel for grouted masonry.

B. Section 04 05 11 - Masonry Mortaring and Grouting.

C. Section 06 10 00 - Rough Carpentry: Nailing strips built into masonry.

D. Section 07 25 00 - Weather Barriers: Water-resistive barriers applied to exterior face of backing sheathing or unit masonry substrate.

1.03 REFERENCE STANDARDS

A. ASTM A153/A153M - Standard Specification for Zinc Coating (Hot-Dip) on Iron and Steel Hardware; 2023.

B. ASTM A951/A951M - Standard Specification for Steel Wire for Masonry Joint Reinforcement;

2022.

C. ASTM C90 - Standard Specification for Loadbearing Concrete Masonry Units; 2023.

D. ASTM C129 - Standard Specification for Nonloadbearing Concrete Masonry Units; 2023.

E. ASTM C140/C140M - Standard Test Methods for Sampling and Testing Concrete Masonry Units and Related Units; 2023a.

F. BIA Technical Notes No. 7 - Water Penetration Resistance – Design and Detailing; 2017.

1.04 SUBMITTALS

A. Product Data: Provide data for masonry units, fabricated wire reinforcement, mortar, and masonry accessories.

B. Shop Drawings: Indicate pertinent dimensions, materials, anchorage, size and type of fasteners, and accessories for brickwork support system.

1. Include calculations or selections from the manufacturer's prescriptive design tables that indicate compliance with the applicable building code and project conditions.

C. Manufacturer's Certificate: Certify that masonry units meet or exceed specified requirements.

1.05 QUALITY ASSURANCE

A. Comply with provisions of TMS 402/602, except where exceeded by requirements of Contract Documents.

B. Installer Qualifications: Company specializing in performing work of the type specified and with at least three years of documented experience.

1.06 DELIVERY, STORAGE, AND HANDLING

A. Deliver, handle, and store masonry units by means that will prevent mechanical damage and contamination by other materials.

B. Handle and store ceramic glazed masonry units in protective cartons or trays. Do not remove from protective packaging until ready for installation.

PART 2 PRODUCTS

2.01 CONCRETE MASONRY UNITS

04 20 00 - 2 Unit Masonry

A. Concrete Block: Comply with referenced standards and as follows:

1. Size: Standard units with nominal face dimensions of 16 by 8 inches and nominal depths as indicated on drawings for specific locations.

2. Special Shapes: Provide nonstandard blocks configured for corners.

3. Load-Bearing Units: ASTM C90, normal weight.

a. Exposed Faces: Manufacturer's standard color and texture where indicated.

b. Manufacturers:

1) The Concrete Products Group; Spec-Brik:

www.concreteproductsgroup.com/#sle.

2) Substitutions: See Section 01 60 00 - Product Requirements.

4. Nonloadbearing Units: ASTM C129.

5. Pre-Faced Units: ASTM C90, hollow block, with smooth, resinous facing complying with

ASTM C744.

a. Colors and styles: As indicated on drawings.

2.02 MORTAR AND GROUT MATERIALS

A. Mortar and Grout: As specified in Section 04 05 11.

2.03 REINFORCEMENT AND ANCHORAGE

A. Manufacturers:

1. 3GEN Masonry Products; www.3genmp.com.

2. Blok-Lok Limited; www.blok-lok.com/#sle.

3. Acceptable equal approved by architect.

B. Reinforcing Steel: as specified in Section 03 20 00; size as indicated on drawings;

C. Joint Reinforcement: Use ladder type joint reinforcement where vertical reinforcement is involved and truss type elsewhere, unless otherwise indicated.

D. Single Wythe Joint Reinforcement: ASTM A951/A951M.

E. Multiple Wythe Joint Reinforcement: ASTM A951/A951M.

F. Adjustable Multiple Wythe Joint Reinforcement: ASTM A951/A951M.

G. Strap Anchors: Bent steel shapes, 1-1/2 inch width, 0.105 inch thick, 24 inch length, with 1-1/2 inch long, 90 degree bend at each end to form a U or Z shape or with cross pins, hot dip galvanized to ASTM A153/A153M Class B.

H. Flexible Anchors: 2-piece anchors that permit differential movement between masonry and building frame, sized to provide not less than 5/8 inch of mortar coverage from masonry face.

I. Two-Piece Wall Ties: Formed steel wire, 0.1875 inch thick, adjustable, eye and pintle type, hot dip galvanized to ASTM A 153/A 153M, Class B, sized to provide not less than 5/8 inch of mortar coverage from masonry face and to allow vertical adjustment of up to 1-1/4 in.

J. Masonry Veneer Anchors: 2-piece anchors that permit differential movement between masonry veneer and structural backup, hot dip galvanized to ASTM A 153/A 153M, Class B.

1. Anchor plates: Not less than 0.075 inch thick, designed for fastening to structural backup through sheathing by two fasteners; provide design with legs that penetrate sheathing and insulation to provide positive anchorage.

2. Wire ties: Manufacturer's standard shape, 0.1875 inch thick.

3. Vertical adjustment: Not less than 3-1/2 inches.

K. Metal-to-Metal Fasteners: Self-drilling, self-tapping screws; corrosion resistant finish or hot dip galvanized to ASTM A153/A153M.

2.04 ACCESSORIES

A. Cavity Mortar Control: Semi-rigid polyethylene or polyester mesh panels, sized to thickness of wall cavity, and designed to prevent mortar droppings from clogging weeps and cavity vents and allow proper cavity drainage.

04 20 00 - 3 Unit Masonry

1. Full-Height Airspace Maintenance and Drainage Material: Mesh panels fitted between masonry ties.

a. Drainage Material Thickness: 3/8 inch.

2. Full-Height Airspace Maintenance and Drainage Material with Insulation: Mesh panels factory bonded to rigid insulation of type indicated and fitted between masonry ties.

a. Drainage Material Thickness: 3/8 inch.

b. Insulation Thickness: 1 inch.

B. Building Paper: ASTM D226/D226M, Type I ("No.15") asphalt felt.

C. Nailing Strips: Softwood lumber, preservative treated; as specified in Section 06 10 00.

D. Cleaning Solution: Non-acidic, not harmful to masonry work or adjacent materials.

PART 3 EXECUTION

3.01 EXAMINATION

A. Verify that field conditions are acceptable and are ready to receive masonry.

B. Verify that related items provided under other sections are properly sized and located.

C. Verify that built-in items are in proper location, and ready for roughing into masonry work.

3.02 PREPARATION

A. Direct and coordinate placement of metal anchors supplied for installation under other sections.

B. Provide temporary bracing during installation of masonry work. Maintain in place until building structure provides permanent bracing.

3.03 COLD AND HOT WEATHER REQUIREMENTS

A. Comply with requirements of TMS 402/602 or applicable building code, whichever is more stringent.

3.04 COURSING

A. Establish lines, levels, and coursing indicated. Protect from displacement.

B. Maintain masonry courses to uniform dimension. Form vertical and horizontal joints of uniform thickness.

C. Concrete Masonry Units:

1. Bond: Running.

2. Coursing: One unit and one mortar joint to equal 8 inches.

3. Mortar Joints: Concave.

3.05 PLACING AND BONDING

A. Lay solid masonry units in full bed of mortar, with full head joints, uniformly jointed with other work.

3.06 CAVITY MORTAR CONTROL

A. Do not permit mortar to drop or accumulate into cavity air space or to plug weep/cavity vents.

3.07 REINFORCEMENT AND ANCHORAGE

A. Unless otherwise indicated on drawings or specified under specific wall type, install horizontal joint reinforcement 16 inches on center.

B. Place masonry joint reinforcement in first and second horizontal joints above and below openings. Extend minimum 16 inches each side of opening.

C. Place continuous joint reinforcement in first and second joint below top of walls.

D. Embed longitudinal wires of joint reinforcement in mortar joint with at least 5/8 inch mortar cover on each side.

E. Lap joint reinforcement ends minimum 6 inches.

04 20 00 - 4 Unit Masonry

F. Reinforce stack bonded unit joint corners and intersections with strap anchors 16 inches on center.

G. Fasten anchors to structural framing and embed in masonry joints as masonry is laid. Unless otherwise indicated on drawings or closer spacing is indicated under specific wall type, space anchors at maximum of 36 inches horizontally and 24 inches vertically.

H. Embed ties and anchors in mortar joint and extend into masonry unit a minimum of 1-1/2 inches with at least 5/8 inch mortar cover to the outside face of the anchor.

3.08 CONTROL AND EXPANSION JOINTS

A. Do not continue horizontal joint reinforcement through control or expansion joints.

B. Install preformed control joint device in continuous lengths. Seal butt and corner joints in accordance with manufacturer's instructions.

3.09 BUILT-IN WORK

A. As work progresses, install built-in metal door frames and glazed frames and other items to be built into the work and furnished under other sections.

B. Install built-in items plumb, level, and true to line.

3.10 TOLERANCES

A. Install masonry within the site tolerances found in TMS 402/602.

3.11 CLEANING

A. Remove excess mortar and mortar droppings.

B. Clean soiled surfaces with cleaning solution.

3.12 PROTECTION

A. Without damaging completed work, provide protective boards at exposed external corners that are subject to damage by construction activities.

05 52 13 - 1 Pipe and Tube Railings

SECTION 05 52 13

PIPE AND TUBE RAILINGS

PART 1 GENERAL

1.01 SECTION INCLUDES

A. Wall mounted handrails.

B. Stair railings and guardrails.

C. Free-standing railings at steps.

D. Balcony railings and guardrails.

1.02 RELATED REQUIREMENTS

A. Section 03 30 00 - Cast-in-Place Concrete: Placement of anchors in concrete.

B. Section 04 20 00 - Unit Masonry: Placement of anchors in masonry.

C. Section 05 51 00 - Metal Stairs: Attachment plates for handrails specified in this section.

D. Section 06 20 00 - Finish Carpentry: Wood handrail.

E. Section 08 80 00 - Glazing: Glass baluster infill.

F. Section 09 21 16 - Gypsum Board Assemblies: Placement of backing plates in stud wall construction.

G. Section 09…