Attachment 6 - Drawings - Phase 3B.pdf
PDF 6 MB Posted
- Attached to
- HVAC Repair Phase 2B, 3A, 3B Federal contract opportunity
- Solicitation number
- 1232SA26Q0056
View the file
Other files for this federal contract opportunity
Show all 18
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
DESIGN NEW HVAC SYSTEM AND ASSOCIATED UPGRADES
PHASE 3B
STUTTGART, ARKANSAS
SHEET NO.
INDEX OF DRAWINGS
SHEET TITLE
G-001 G-002
AD111
A-101 M-001 M-002
MD101
MD102
MH101
MH102
MP101
M-501 M-502 M-601 M-701 E-001
ED111
E-101 E-111 E-500
X OF X
X OF X
X OF X
X OF X
X OF X
X OF X
X OF X
X OF X
X OF X
X OF X
X OF X
X OF X
X OF X
X OF X
X OF X
X OF X
X OF X
X OF X
X OF X
X OF X
PHASE 3B TITLE SHEET
PHASING PLAN
PHASE 3B REFLECTED CEILING PLAN: DEMO
PHASE 3B REFLECTED CEILING PLAN
PHASE 3B MECHANICAL GENERAL NOTES
PHASE 3B MECHANICAL LEGEND AND ABBREVIATIONS
PHASE 3B MECHANICAL HVAC DEMOLITION PLAN
PHASE 3B MECHANICAL PIPING DEMOLITION PAN
PHASE 3B MECHANICAL HVAC NEW WORK PLAN
PHASE 3B MECHANICAL ROOF NEW WORK PLAN
PHASE 3B MECHANICAL PIPING NEW WORK PLAN
PHASE 3B MECHANICAL DETAILS
PHASE 3B MECHANICAL DETAILS
PHASE 3B MECHANICAL SCHEDULES
PHASE 3B MECHANICAL CONTROLS
PHASE 3B ELECTRICAL LEGEND AND NOTES
PHASE 3B LIGHTING DEMOLITION PLAN
PHASE 3B ELECTRICAL HVAC NEW WORK PLAN
PHASE 3B ELECTRICAL LIGHTING PLAN
PHASE 3B LIGHTING DETAILS AND SCHEDULES
USDA
NO SCALEVICINITY MAP
NORTH
100% DESIGN SUBMITTAL
ARKANSAS
PROJECT
LOCATION
USDA AGRICULTURAL RESEARCH SERVICE
DALE BUMPERS NATIONAL RICE RESEARCH CENTER
(DBNRRC)
AutoCAD SHX Text
PPM
AutoCAD SHX Text
REVISIONS
AutoCAD SHX Text Agricultural
AutoCAD SHX Text Service
AutoCAD SHX Text Research
AutoCAD SHX Text
DESCRIPTION
AutoCAD SHX Text
SHEET
AutoCAD SHX Text
DATE
AutoCAD SHX Text c
AutoCAD SHX Text P.A.
AutoCAD SHX Text
FIRM
AutoCAD SHX Text U
AutoCAD SHX Text
NO.
AutoCAD SHX Text D
AutoCAD SHX Text
EPM
AutoCAD SHX Text
SAFETY & HEALTH
AutoCAD SHX Text
REAL PROPERTY
AutoCAD SHX Text A
AutoCAD SHX Text
DATE
AutoCAD SHX Text
PROJECT NO.
AutoCAD SHX Text S
AutoCAD SHX Text
USDA
AutoCAD SHX Text
BY
AutoCAD SHX Text
AGRICULTURAL RESEARCH SERVICE
AutoCAD SHX Text
OF
AutoCAD SHX Text
THE
AutoCAD SHX Text
DESIGNER
AutoCAD SHX Text
PROJECT MANAGER
AutoCAD SHX Text
JOB #
AutoCAD SHX Text
CHECKED BY
AutoCAD SHX Text
A-E FIRM
AutoCAD SHX Text
P.O. BOX 513, GREENWOOD, MISSISSIPPI - (662) 455-4943
AutoCAD SHX Text Johnson M Adams
AutoCAD SHX Text
ARCHITECTS/ENGINEERS PLANNING SURVEYING MANAGEMENT
AutoCAD SHX Text
USDA AGRICULTURAL RESEARCH SERVICE
AutoCAD SHX Text
DALE BUMPERS NATIONAL RICE RESEARCH CENTER
AutoCAD SHX Text
(DBNRRC)
AutoCAD SHX Text
STUTTGART, ARKANSAS
AutoCAD SHX Text
PHASE 3B TITLE SHEET
AutoCAD SHX Text G-001
AutoCAD SHX Text X X
AutoCAD SHX Text 06/21/24
AutoCAD SHX Text
SME
AutoCAD SHX Text
SME
AutoCAD SHX Text
DRL
AutoCAD SHX Text
SOUTHEAST AREA
AutoCAD SHX Text
STONEVILLE, MS
AutoCAD SHX Text
XXX
AutoCAD SHX Text 5923-E
AutoCAD SHX Text
E. WILSON
AutoCAD SHX Text
PPM
AutoCAD SHX Text
SH
AutoCAD SHX Text
R. BRAITHWAITE
AutoCAD SHX Text
AutoCAD SHX Text p
AutoCAD SHX Text
AutoCAD SHX Text p
AutoCAD SHX Text
AutoCAD SHX Text p
AutoCAD SHX Text
AutoCAD SHX Text p
AutoCAD SHX Text
AutoCAD SHX Text p
AutoCAD SHX Text
AutoCAD SHX Text p
AutoCAD SHX Text
AutoCAD SHX Text p
AutoCAD SHX Text
AutoCAD SHX Text p
AutoCAD SHX Text
AutoCAD SHX Text p
AutoCAD SHX Text
RUSSELLVILLE
AutoCAD SHX Text
CONWAY
AutoCAD SHX Text
SEARCY
AutoCAD SHX Text
HOT SPRINGS
AutoCAD SHX Text
STUTTGART
AutoCAD SHX Text
PINE BLUFF
AutoCAD SHX Text
FAYETTEVILLE
AutoCAD SHX Text
EL DORADO
AutoCAD SHX Text
FORT SMITH
AutoCAD SHX Text
LOCKESBURG
AutoCAD SHX Text
TEXARKANA
AutoCAD SHX Text
LITTLE ROCK
PHASE 1A, 1B AND 1C (NOT IN CONTRACT):
PHASE 2A (NOT IN CONTRACT)
PHASE 2B (NOT IN CONTRACT)
PHASE 3A (NOT IN CONTRACT)
PHASE 3B;
HEADHOUSE (NOT IN CONTRACT)
PHASING LEGEND
A. ALL NON-WORK AREAS IN THE BUILDING WILL REMAIN OCCUPIED AND OPERATIONAL
DURING THE WORK. USDA WILL VACATE AREAS OF THE BUILDING WHERE WORK IS
BEING PERFORMED. THE CONTRACTOR SHALL COORDINATE HIS/HER WORK
ACTIVITIES WITH THE CONTRACTING OFFICER TO AVOID CONFLICTS WITH FACILITY
OPERATIONS. THE CONTRACTOR SHALL ERECT BARRIERS AND EMPLOY NECESSARY
MEASURES TO PROTECT PERSONNEL IN THE AREA FROM INJURY.
B. COVER AND PROTECT ALL FURNISHINGS AND EQUIPMENT REMAINING IN THE
LABORATORIES AND OFFICE SPACES.
C. THE CONTRACTOR SHALL PROVIDE BARRIERS AND SIGNAGE TO SECURE THE WORK
AREAS, TO DIRECT PERSONNEL IN WAYFINDING, AND TO ENSURE THE SAFETY OF
BUILDING OCCUPANTS AND VISITORS. THE CONTRACTOR SHALL PROVIDE A WORK
PLAN BEFORE BEGINNING THE WORK EXPLAINING AND ILLUSTRATING THE MEANS TO
BE IMPLEMENTED TO ALLOW THE BUILDING TO REMAIN OCCUPIED AND OPERATIONAL
DURING THE WORK. THE CONTRACTOR SHALL FIELD VERIFY ALL DIMENSION AND
CONDITIONS BEFORE BEGINNING WORK.
D. CONTRACTOR SHALL COORDINATE STAGING AREAS WITH USDA PERSONNEL.
GENERAL NOTES
PHASE 3B
AREA OF
WORK
101A
SCALE:
PHASE 3B
REFELECTED CEILING PLAN: DEMO
3/16" = 1'-0"
AD111
0 4' 8' 16'
SCALE: 3/16"= 1'-0"
2'
KEY PLAN
N.T.S.
LEGEND
DEMOLISH 24 x 24" SUSPENDED
ACOUSTICAL CEILING SYSTEM
COMPLETE. CONTRACTORS
OPTION TO RETAIN SUSPENSION
WIRES
DEMOLISH SUSPENDED GYPSUM
BOARD CEILING SYSTEM
COMPLETE. CONTRACTORS
OPTION TO RETAIN HANGER
WIRES
LIGHT FIXTURES. SEE
ELECTRICAL DRAWINGS FOR
ADDITIONAL WORK.
HVAC DIFFUSERS. SEE
MECHANICAL DRAWINGS FOR
ADDITIONAL WORK.
NO WORK THIS AREA
DEMOLISH 24 x 48" SUSPENDED
ACOUSTICAL CEILING SYSTEM
COMPLETE. CONTRACTORS
OPTION TO RETAIN SUSPENSION
WIRES
AREA OF
WORK
PHASE 3B
AutoCAD SHX Text
PPM
AutoCAD SHX Text
REVISIONS
AutoCAD SHX Text Agricultural
AutoCAD SHX Text Service
AutoCAD SHX Text Research
AutoCAD SHX Text
DESCRIPTION
AutoCAD SHX Text
SHEET
AutoCAD SHX Text
DATE
AutoCAD SHX Text c
AutoCAD SHX Text P.A.
AutoCAD SHX Text
FIRM
AutoCAD SHX Text U
AutoCAD SHX Text
NO.
AutoCAD SHX Text D
AutoCAD SHX Text
EPM
AutoCAD SHX Text
SAFETY & HEALTH
AutoCAD SHX Text
REAL PROPERTY
AutoCAD SHX Text A
AutoCAD SHX Text
DATE
AutoCAD SHX Text
PROJECT NO.
AutoCAD SHX Text S
AutoCAD SHX Text
USDA
AutoCAD SHX Text
BY
AutoCAD SHX Text
AGRICULTURAL RESEARCH SERVICE
AutoCAD SHX Text
OF
AutoCAD SHX Text
THE
AutoCAD SHX Text
DESIGNER
AutoCAD SHX Text
PROJECT MANAGER
AutoCAD SHX Text
JOB #
AutoCAD SHX Text
CHECKED BY
AutoCAD SHX Text
A-E FIRM
AutoCAD SHX Text
P.O. BOX 513, GREENWOOD, MISSISSIPPI - (662) 455-4943
AutoCAD SHX Text Johnson M Adams
AutoCAD SHX Text
ARCHITECTS/ENGINEERS PLANNING SURVEYING MANAGEMENT
AutoCAD SHX Text
USDA AGRICULTURAL RESEARCH SERVICE
AutoCAD SHX Text
DALE BUMPERS NATIONAL RICE RESEARCH CENTER
AutoCAD SHX Text
(DBNRRC)
AutoCAD SHX Text
STUTTGART, ARKANSAS
AutoCAD SHX Text
PHASE 3B
AutoCAD SHX Text
REFLECTED CEILING PLAN: DEMO
AutoCAD SHX Text
AD111
AutoCAD SHX Text X X
AutoCAD SHX Text 06/21/24
AutoCAD SHX Text
SME
AutoCAD SHX Text
REH
AutoCAD SHX Text
DRL
AutoCAD SHX Text
SOUTHEAST AREA
AutoCAD SHX Text
STONEVILLE, MS
AutoCAD SHX Text
XXX
AutoCAD SHX Text 5923-E
AutoCAD SHX Text
E. WILSON
AutoCAD SHX Text
PPM
AutoCAD SHX Text
SH
R. BRAITHWAITE
101A
SCALE:
PHASE 3B
REFLECTED CEILING PLAN
3/16" = 1'-0"
A-101
0 4' 8' 16'
SCALE: 3/16"= 1'-0"
2'
LEGEND
PROVIDE NEW 24 x 24"
SUSPENDED ACOUSTICAL
CEILING SYSTEM AS SPECIFIED.
CONTRACTORS OPTION TO
RETAIN SUSPENSION WIRES
PROVIDE NEW SUSPENDED
GYPSUM BOARD CEILING
SYSTEM AS SPECIFIED.
CONTRACTORS OPTION TO
RETAIN HANGER WIRES
LIGHT FIXTURES. SEE
ELECTRICAL DRAWINGS FOR
ADDITIONAL WORK.
HVAC DIFFUSERS. SEE
MECHANICAL DRAWINGS FOR
ADDITIONAL WORK.
NO WORK THIS AREA
KEY PLAN
N.T.S.
AREA OF
WORK
PHASE 3B
AutoCAD SHX Text
PPM
AutoCAD SHX Text
REVISIONS
AutoCAD SHX Text Agricultural
AutoCAD SHX Text Service
AutoCAD SHX Text Research
AutoCAD SHX Text
DESCRIPTION
AutoCAD SHX Text
SHEET
AutoCAD SHX Text
DATE
AutoCAD SHX Text c
AutoCAD SHX Text P.A.
AutoCAD SHX Text
FIRM
AutoCAD SHX Text U
AutoCAD SHX Text
NO.
AutoCAD SHX Text D
AutoCAD SHX Text
EPM
AutoCAD SHX Text
SAFETY & HEALTH
AutoCAD SHX Text
REAL PROPERTY
AutoCAD SHX Text A
AutoCAD SHX Text
DATE
AutoCAD SHX Text
PROJECT NO.
AutoCAD SHX Text S
AutoCAD SHX Text
USDA
AutoCAD SHX Text
BY
AutoCAD SHX Text
AGRICULTURAL RESEARCH SERVICE
AutoCAD SHX Text
OF
AutoCAD SHX Text
THE
AutoCAD SHX Text
DESIGNER
AutoCAD SHX Text
PROJECT MANAGER
AutoCAD SHX Text
JOB #
AutoCAD SHX Text
CHECKED BY
AutoCAD SHX Text
A-E FIRM
AutoCAD SHX Text
P.O. BOX 513, GREENWOOD, MISSISSIPPI - (662) 455-4943
AutoCAD SHX Text Johnson M Adams
AutoCAD SHX Text
ARCHITECTS/ENGINEERS PLANNING SURVEYING MANAGEMENT
AutoCAD SHX Text
USDA AGRICULTURAL RESEARCH SERVICE
AutoCAD SHX Text
DALE BUMPERS NATIONAL RICE RESEARCH CENTER
AutoCAD SHX Text
(DBNRRC)
AutoCAD SHX Text
STUTTGART, ARKANSAS
AutoCAD SHX Text
PHASE 3B
AutoCAD SHX Text
REFLECTED CEILING PLAN
AutoCAD SHX Text A-101
AutoCAD SHX Text X X
AutoCAD SHX Text 06/21/24
AutoCAD SHX Text
SME
AutoCAD SHX Text
REH
AutoCAD SHX Text
DRL
AutoCAD SHX Text
SOUTHEAST AREA
AutoCAD SHX Text
STONEVILLE, MS
AutoCAD SHX Text
XXX
AutoCAD SHX Text 5923-E
AutoCAD SHX Text
E. WILSON
AutoCAD SHX Text
PPM
AutoCAD SHX Text
SH
R. BRAITHWAITE
1. INSTALLATION OF HVAC WORK SHALL BE COORDINATED WITH OTHER TRADES BEFORE ANY WORK IS PERFORMED. DUCTWORK SHOWN ON PLANS IS SCHEMATIC. DUCTWORK SHALL BE INSTALLED TIGHT TO STRUCTURE. PROVIDE ALL TRANSITIONS, ELBOWS, ETC. REQUIRED TO AVOID CONFLICTS & MAXIMIZE CEILING HEIGHTS. EQUIPMENT, PIPING OR DUCTWORK INTERFERING WITH OTHER TRADES SHALL BE
RELOCATED AS REQUIRED AT NO ADDITIONAL COST TO THE OWNER.
2. COORDINATE MECHANICAL AND ELECTRICAL SUCH THAT MECHANICAL PIPING, DUCTWORK AND EQUIPMENT
IS NOT LOCATED OVER OR ABOVE ANY ELECTRICAL, COMMUNICATIONS, OR DATA EQUIPMENT.
3. AT START OF CONSTRUCTION, PREPARE TYPED LISTS OF EQUIPMENT THAT ARE SUPPLIED REQUIRING ELECTRICAL WORK, AND SEND LISTS TO THE ELECTRICAL CONTRACTOR FOR REVIEW AND COORDINATION.
4. EQUIPMENT SHALL BE INSTALLED IN ACCORDANCE WITH MANUFACTURER'S APPROVED CLEARANCE AND
INTERNATIONAL BUILDING CODE / INTERNATIONAL MECHANICAL CODE.
5. INSTALLATION OF EQUIPMENT SHALL PERMIT ACCESSIBILITY FOR SERVICE AND/OR REPLACEMENT WITHOUT NECESSITATING REMOVAL OR MODIFICATION TO OTHER PIPING, WIRING, OR EQUIPMENT.
6. CEILING-MOUNTED EQUIPMENT SHALL BE INSTALLED IN SUCH A MANNER THAT LIGHTS, PIPING, DUCTWORK, ETC., DO NOT BLOCK ACCESS TO EQUIPMENT AND RELATED ACCESSORIES.
7. COORDINATE WALL, FLOOR, AND ROOF PENETRATIONS WITH THE CONTRACTOR.
8. SUPPLEMENTAL STEEL MEMBERS REQUIRED TO SUPPORT HVAC EQUIPMENT FROM MAIN STRUCTURE
SHALL BE PROVIDED BY THE HVAC CONTRACTOR UNLESS SPECIFICALLY NOTED OTHERWISE.
9. DUCTWORK AIR DISTRIBUTION SYSTEMS SHALL BE INSTALLED IN ACCORDANCE WITH SMACNA STANDARDS
AND THE PRESSURE CLASSIFICATION OF EACH INDIVIDUAL DUCTWORK SYSTEM.
10. VOLUME DAMPERS SHALL BE PROVIDED AT EACH MAIN BRANCH TAKE-OFF, EACH TAKEOFF TO DIFFUSERS/GRILLS/REGISTERS, AND OTHER LOCATIONS WHERE REQUIRED TO PROPERLY BALANCE THE
SYSTEM. ALL REQUIRED VOLUME DAMPERS MAY NOT BE SHOWN ON PLANS.
11. INSTRUMENT TEST HOLES SHALL BE PROVIDED IN AIR DISTRIBUTION SYSTEMS WHEREVER VOLUME DAMPERS ARE INSTALLED. TEST HOLES SHALL BE SEALED WITH RUBBER OR PLASTIC TEST HOLE PLUGS.
12. SQUARE ELBOWS SHALL ONLY BE USED WHERE SPACE LIMITATIONS PREVENT USE OF 1.5 RADIUS ELBOW AND ONLY UPON APPROVAL OF CONTRACTING OFFICER. PROVIDE TURNING VANES IN ALL SQUARE ELBOWS GREATER THAN OR EQUAL TO 45°. TURNING VANES SHALL BE SINGLE THICKNESS TYPE WITHOUT RAILING
EDGE. TURNING VANES LONGER THAN 36 INCHES SHALL BE DOUBLE THICKNESS TYPE.
13. DUCTWORK RUNOUTS TO AIR DISTRIBUTION DEVICES SHALL BE SAME DIAMETER AS AIR DISTRIBUTION
DEVICE INLET CONNECTION UNLESS OTHERWISE NOTED ON THE DRAWINGS.
14. FLEXIBLE DUCTWORK RUNOUTS FROM BRANCH DUCTS TO AIR DISTRIBUTION DEVICES SHALL NOT EXCEED 5 FEET IN LENGTH. BENDS IN FLEXIBLE DUCTWORK SHALL NOT EXCEED A MAXIMUM OF 45 DEGREE CHANGE OF DIRECTION AND SHALL BE SUPPORTED SUCH THAT THE BEND RADIUS IS NOT RESTRICTIVE TO AIR FLOW THROUGH THE DUCT. FLEXIBLE DUCTWORK SHALL NOT BE CRUSHED OR DISTORTED IN ITS FINAL
CONFIGURATION.
15. PROVIDE SHEETMETAL TRANSITIONS AT AIR HANDLING UNITS, HEAT PUMP UNITS, FANS, AND OTHER SIMILAR HVAC EQUIPMENT. TRANSITION TO FULL SIZE OF CONNECTION ON UNIT. FLEXIBLE DUCT
CONNECTORS SHALL BE USED ON FINAL CONNECTION TO AIR HANDLING EQUIPMENT.
16. TRANSFER DUCTS SHALL BE SIZED FOR MAX VELOCITY ALLOWED OF 500 FPM. OPEN-ENDED TRANSFER
DUCTS SHALL HAVE 90° ELBOW FOR SOUND ATTENUATION.
17. LOUVERED SUPPLY AIR DIFFUSERS SHALL BE 4-WAY FLOW UNLESS OTHERWISE SHOWN BY FLOW ARROWS ON THE DRAWINGS. LINEAR DIFFUSERS SHALL BE ADJUSTABLE 2-WAY FLOW. PROVIDE BATT INSULATION
ON DIFFUSER AND GRILLES THAT ARE EXPOSED TO CEILING PLENUM.
18. EXACT LOCATION OF CEILING DIFFUSERS, GRILLES AND REGISTERS SHALL BE DETERMINED BY
ARCHITECTURAL REFLECTED CEILING PLAN.
19. LOUVER PLENUMS SHALL BE PITCHED DOWN TOWARD THE BOTTOM OF THE LOUVER.
20. PROVIDE ACCESS PANELS TO ACCESS DAMPERS, EQUIPMENT, AND VALVES LOCATED ABOVE HARD
CEILINGS OR IN WALLS. ACTUAL LOCATIONS SHALL BE FIELD DETERMINED.
21. EXACT LOCATIONS OF THERMOSTATS, CO2 SENSORS, AND EMCS SENSORS SHALL BE COORDINATED WITH
FINAL LOCATIONS OF WALL-MOUNTED ARCHITECTURAL AND ELECTRICAL EQUIPMENT. MOUNT
THERMOSTATS AND CO2 SENSORS MINIMUM 48" AFF.
22. AIR HANDLING UNITS SERVING OCCUPIED AREAS SHALL HAVE MINIMUM MERV 8 PRE-FILTERS AND MERV 13 FINAL FILTERS. UNITS NOT SERVING OCCUPIED ZONES SHALL HAVE MINIMUM MERV 8 FILTER. FILTERS SHALL BE INDUSTRY STANDARD SIZE. FILTERS SHALL NOT CREATE PRESSURE DROP EXCEEDING 10% OF
EXTERNAL STATIC PRESSURE (ESP) CAPACITY LISTED IN EQUIPMENT SCHEDULE.
23. ALL SUPPLY AIR CFM VALUES SHOWN ON THE DRAWINGS ARE THE MAXIMUM VALUES, SEE SCHEDULES TO
OBTAIN THE OCCUPIED, UNOCCUPIED VALUES
GENERAL MECHANICAL NOTES:
24. SUPPLY, RETURN, AND OUTDOOR AIR DUCTWORK SHALL BE INSULATED TO MEET OR EXCEED ASHRAE 189.1.
EXTERIOR SUPPLY AND RETURN AIR DUCTWORK SHALL BE PROVIDED WITH WEATHER-PROOF COVER.
25. PROVIDE SUPPORTS FOR PIPING AND DUCTWORK IN ACCORDANCE WITH SPECIFICATIONS.
26. PROVIDE A MANUFACTURED EXPANSION DEVICE OR FABRICATED EXPANSION LOOP ON ALL DUCTWORK AND
PIPING SYSTEMS CROSSING BUILDING EXPANSION JOINTS.
27. PROVIDE SHUT-OFF VALVES AND FLEXIBLE CONNECTIONS AT PIPE CONNECTIONS TO HVAC EQUIPMENT.
28. FOR WALL, FLOOR, AND SLAB PENETRATIONS, SEAL AND PATCH ALL UNUSED PENETRATION SPACE TO MATCH EXISTING CONSTRUCTION/FINISH OR AS SHOWN ON MECHANICAL DETAILS SHEET. PROVIDE FIRE STOPPING FOR
RATED WALLS AND FLOORS.
29. INSTALL EXPOSED CONTROL WIRING IN CONDUIT. SEE DIVISION 26 SPECIFICATIONS FOR REQUIREMENTS.
30. MANUFACTURER NAME AND MODEL NUMBERS ARE BASIS OF DESIGN AND ARE SHOWN FOR INFORMATION ONLY.
REFER TO SPECIFICATIONS FOR COMPLETE REQUIREMENTS.
31. SPECIFICATIONS TAKE PRECEDENCE OVER DRAWINGS. HOWEVER, ITEMS SHOWN ON DRAWING BUT NOT IN THE SPECIFICATIONS ARE REQUIRED WITHIN THE PROJECT SCOPE. IN ADDITION, SPECIFIC ITEMS SHOWN ON THE DRAWINGS TAKE PRECEDENCE OVER SPECIFICATIONS IN CASES WHERE THE SPECIFICATION HAS OPTIONS.
32. ALL EQUIPMENT SHALL BE INSTALLED IN ACCORDANCE WITH MANUFACTURER'S APPROVED PUBLISHED
LITERATURE.
33. DUCT SIZES SHOWN ARE INSIDE CLEAR DIMENSIONS.
34. EXPOSED DUCTWORK, WITH THE EXCEPTION OF DUCTWORK IN MECHANICAL ROOMS SHALL BE DOUBLE-WALL, DUCTWORK WITH COATING.
35. IF SUSPECT ASBESTOS IS FOUND, STOP WORK IMMEDIATELY AND NOTIFY OWNER AND GENERAL CONTRACTOR.
OWNER IS RESPONSIBLE FOR ABATEMENT OF UNFORSEEN ASBESTOS.
36. NOT ALL MECHANICAL ABBREVIATIONS SHOWN WILL BE USED FOR THIS PROJECT.
37. ALL THERMOSTATS SHALL BE WALL MOUNTED AND WIRED.
38. ALL EQUIPMENT INSTALLED IN THIS PROJECT SHALL COMPLY WITH THE "BUY AMERICAN ACT". BASIS OF DESIGN SHOWN ON SCHEDULES IS TO ESTABLISH A STANDARD OF QUALITY, NOT TO LIMIT COMPETITION. EQUIVALENT
EQUIPMENT FROM ANOTHER MANUFACTURER IS ACCEPTABLE.
39. ALL COMMUNICATIONS PREMISE WIRING AND CABLE TRAYS THROUGHOUT THE FACILITY MUST BE PROTECTED AND UNINTERRUPTED DURING CONSTRUCTION. THIS INCLUDES ELECTRICAL POWER TO COMMUNICATIONS
EQUIPMENT. NO COMMUNICATIONS OUTAGES MUST TAKE PLACE WITHOUT THE CONSENT OF THE
CONTRACTING OFFICER.
40. CONTRACTOR MUST DEMOLISH ALL THERMOSTATS AND WIRING ASSOCIATED WITH THE HVAC SYSTEM TO BE
DEMOLISHED.
41. CONTROLS CONTRACTOR SHALL PROVIDE ALL LOW VOLTAGE DEVICES, CONDUCTORS, AND PATHWAYS IN
ACCORDANCE WITH THE REQUIREMENTS OF 26 20 00.
ABBREVIATIONS:
@ AT
& AND
AHU AIR HANDLING UNIT
ARCH ARCHITECT, ARCHITECTURAL
AS AIR SEPARATOR
ASHRAE AMERICAN SOCIETY OF HEATING, REFRIGERATING,
AND AIR CONDITIONING ENGINEERS
ASTM AMERICAN SOCIETY FOR TESTING AND
MATERIALS
BDD BACKDRAFT DAMPER
BLDG BUILDING
BTU, BTUH BRITISH THERMAL UNITS, BTUs PER HOUR
CD CONDENSATE DRAIN
CFM CUBIC FEET PER MINUTE
CHW CHILLED WATER
CHWR CHILLED WATER RETURN
CHWS CHILLED WATER SUPPLY
CLG COOLING
CMU CONCRETE MASONRY UNIT
CO CLEANOUT
CO2 CARBON DIOXIDE
CONC CONCRETE
COND STEAM CONDENSATE
CONN CONNECT, CONNECTING, CONNECTION
CONT CONTINUED
CONV STEAM CONVERTER
COP COEFFICIENT OF PERFORMANCE
COR CONTRACTING OFFICER'S (OWNER'S)
REPRESENTATIVE
CT COOLING TOWER
CU CONDENSING UNIT
CWR CONDENSER WATER RETURN
CWS CONDENSER WATER SUPPLY
D DEPTH
DB, Tdb DRY BULB (TEMPERATURE) dBA DECIBELS
DCW DOMESTIC COLD WATER
DDC DIRECT DIGITAL CONTROLS
DEG. F (°F) DEGREES FAHRENHEIT
DF DESTRATIFICATION FAN
DFCU DUCTLESS FAN COIL UNIT
DH DEHUMIDIFIER
DIA, Ø DIAMETER
DIV DIVISION
DN DOWN
DP, PD DIFFERENTIAL PRESSURE, PRESSURE DROP
DSCU DUCTLESS SPLIT CONDENSING UNIT
DSHP DUCTLESS SPLIT HEAT PUMP
DWG DRAWING
DX DIRECT EXPANSION
EA EXHAUST AIR
EAG EXHAUST AIR GRILLE
EAT ENTERING AIR TEMPERATURE
EER ENERGY EFFICIENCY RATIO
EF EXHAUST FAN
EFF EFFICIENCY
ELEC ELECTRICAL
EMCS ENERGY MONITORING AND CONTROLS SYSTEM
ERU ENERGY RECOVERY UNIT
ERV ENERGY RECOVERY VENTILATOR
ESP EXTERNAL STATIC PRESSURE
ET EXPANSION TANK
EUH ELECTRIC UNIT HEATER
EWT ENTERING WATER TEMPERATURE
EXT EXTERIOR
EXH EXHAUST
EXIST. EXISTING
FCU FAN COIL UNIT
FD FIRE DAMPER
FFE FINISHED FLOOR ELEVATION
FLA FULL LOAD AMPS
FOB FLAT ON BOTTOM
FOT FLAT ON TOP
FPM FEET PER MINUTE
FSD FIRE SMOKE DAMPER
FT FOOT, FEET
FT WG FEET WATER GAUGE
FV FLUE VENT
GA GAGE
GC GENERAL CONTRACTOR
GPM GALLONS PER MINUTE
GWH GAS WATER HEATER
H HEIGHT
HPS HIGH PRESSURE STEAM
HR HOUR
HTG HEATING
HTR HEATER
HTW HEATING WATER
HWR HEATING WATER RETURN
HWS HEATING WATER SUPPLY
HVAC HEATING, VENTILATING, AND AIR CONDITIONING
HX HEAT EXCHANGER
HZ HERTZ
IMC INTERNATIONAL MECHANICAL CODE
IN INCH, INCHES
IN WC INCHES WATER COLUMN
IN WG INCHES WATER GAUGE
IPLV INTEGRATED PART LOAD VALUE
KW KILOWATTS
L LENGTH, LOUVER (WALL)
LAT LEAVING AIR TEMPERATURE
LBD LINEAR BAR DIFFUSER
LBS POUNDS
LWT LEAVING WATER TEMPERATURE
MAX MAXIMUM
MBH 1000 BRITISH THERMAL UNITS
MCA MINIMUM CIRCUIT AMPACITY
MECH MECHANICAL
MERV MINIMUM EFFICIENCY REPORTING VALUE
MFCR, MFCG MANUFACTURER, MANUFACTURING
MIN MINIMUM
MOCP, MOP MAXIMUM OVER CURRENT PROTECTION
MTWR MEDIUM TEMPERATURE WATER RETURN
MTWS MEDIUM TEMPERATURE WATER SUPPLY
MXB MIXING BOX
N.C. NORMALLY CLOSED
NC NOISE CRITERIA
NG NATURAL GAS
NO. NUMBER
N.O. NORMALLY OPEN
NTS NOT TO SCALE
OA OUTSIDE AIR
OD OUTSIDE DAMPER
PCHWR PLANT CHILLED WATER RETURN
PCHWS PLANT CHILLED WATER SUPPLY
PD PRESSURE DROP
PH PHASE
PLBG PLUMBING
PMTWR PLANT MEDIUM TEMPERATURE WATER RETURN
PMTWS PLANT MEDIUM TEMPERATURE WATER SUPPLY
PPM PARTS PER MILLION
PRV PRESSURE RELIEF VALVE
PSI POUNDS PER SQUARE INCH
QTY QUANTITY
RA RETURN AIR
RAG RETURN AIR GRILLE
RH RELATIVE HUMIDITY, ROOF HOOD
RM ROOM
RPM REVOLUTIONS PER MINUTE
SA SUPPLY AIR
SAD SUPPLY AIR DIFFUSER
SAG SUPPLY AIR GRILLE
SD SMOKE DAMPER, SMOKE DETECTOR
SEER SEASONAL ENERGY EFFICIENCY RATIO
SF SUPPLY FAN
SMACNA SHEET METAL AND AIR CONDITIONING
CONTRACTOR'S NATIONAL ASSOCIATION
SP STATIC PRESSURE
STM STEAM
SS STAINLESS STEEL
TEMP TEMPERATURE
TSTAT THERMOSTAT
TYP TYPICAL
UH UNIT HEATER
UL UNDERWRITER'S LABORATORY
UMCS UTILITY MONITORING AND CONTROL SYSTEM
V VOLTAGE, VOLTS
VAV VARIABLE AIR VOLUME
VD VOLUME DAMPER
VFD VARIABLE FREQUENCY DRIVE
VRF VARIABLE REFRIGERANT FLOW
WB, Twb WET BULB (TEMPERATURE)
MISCELLANEOUS LEGEND:
AIR DISTRIBUTION DEVICE TAGS
DIFFUSER SUB-TYPE
A
400 AIRFLOW (CFM),
"PLENUM", OR
"TRANSFER"
NORTH ARROW
A
J
SD
SP
F
CO
DUCT SMOKE DETECTOR
CARBON MONOXIDE SENSOR
OVAL OR FLAT OVAL
CONTROL WIRING
STATIC PRESSURE SENSOR
ROUND OR DIAMETER
FIRESTAT
TEMPERATURE SENSORT
120 VOLT STAND BY POWER JUNCTION
BOX PROVIDED BY THE ELECTRICAL
CONTRACTOR. JUNCTION BOX IS
DEDICATED FOR USE BY THE CONTROLS
CONTRACTOR.
VARIABLE FREQUENCY DRIVEVFD
FLOW ARROW
RETURN AIR GRILLE
SUPPLY AIR DIFFUSER
FLOW ARROWS INDICATE AIR PATTERN.
NO FLOW ARROWS SHOWN INDICATES
4-WAY PATTERN.
EXHAUST AIR GRILLE
SERVICE CLEARANCE
T THERMOSTAT
H HUMIDISTAT
$ START/ STOP SWITCH
TH THERMOSTAT/ HUMIDISTAT
HUMIDITY SENSORH
DIFFUSER TYPE
XXX-
DP DIFFERENTIAL PRESSURE SENSOR
C CARBON DIOXIDE SENSOR
AQ AIR QUALITY SENSOR
POINT OF RECONNECTION
OR EXTENT OF DEMOLITION
ELEVATION CROSS REFERENCEX
XXXXX
PIPING LEGEND:
CHILLED WATER SUPPLY
(CHWS)
HEATING WATER SUPPLY
(HWS)
HEATING WATER RETURN
(HWR)
HIGH PRESSURE STEAM SUPPLY
(HPS)
STEAM CONDENSATE RETURN
(COND)
EXISTING PIPING TO REMAIN
(EXIST.)
CONDENSATE DRAIN
(CD)
FLEXIBLE CONNECTION
THERMOMETER
PRESSURE REDUCING VALVE
MANUAL AIR VENT
PRESSURE/TEMPERATURE TAP WITH
BALL VALVE
PRESSURE SWITCH
PLUG VALVE
FLOW SWITCH
T&P RELIEF VALVE
AUTOMATIC AIR VENT
PRESSURE GAUGE WITH GAUGE COCK
PS
FS
BUTTERFLY VALVE
STRAINER WITH BLOWDOWN VALVE,
CAP, AND CHAIN
FLOW MEASURING/BALANCING/SHUT-
OFF VALVE
GATE VALVE
CHECK VALVE
BALL VALVE
CONCENTRIC REDUCER
DIRECTION OF FLOW
ECCENTRIC REDUCER
PIPE FLANGE
PIPE CAP
PIPE GUIDE (PG)
PIPE ANCHOR (PA) X
UNION
TEE OUTLET UP
BRANCH BOTTOM CONNECTION
BRANCH TOP CONNECTION
ELBOW UP
ELBOW DOWN
RISE OR DROP
TEE OUTLET DOWN
DUCTWORK LEGEND:
M
FIRE DAMPER
EXHAUST AIR DUCT DOWN
EXHAUST AIR DUCT UP
RETURN AIR DUCT DOWN
30"x14"
SQUARE TO ROUND DUCT BRANCH TAKE-OFF
WITH 45 DEGREE BRANCH INLET
ROUND DUCT BRANCH TAKE-OFF FROM
RECTANGULAR MAIN WITH CONICAL TAP
FLEXIBLE DUCT CONNECTION
DUCT SIZE TRANSITION
RECTANGULAR DUCT BRANCH TAKE-OFF
WITH 45 DEGREE BRANCH INLET
90 DEGREE DUCT ELBOW WITH TURNING VANES
24"Ø ROUND DUCT. DIAMETER INDICATED IN INCHES.
IN-LINE 90 DEGREE RISE/DROP IN
SUPPLY DUCT
FD
SD
DAMPER TYPE:
M - MOTORIZED DAMPER (ELECTRIC)
VD
SMOKE DAMPER
VOLUME/BALANCING DAMPER
(LABEL MAY BE OMITTED)
BD
BACKDRAFT DAMPER
(COUNTER-BALANCED UNLESS
OTHERWISE NOTED)
RADIUS DUCT ELBOW - ROUND OR
RECTANGULAR (MIN. 1.5 RADIUS UNLESS
OTHERWISE NOTED)
RECTANGULAR DUCT. SIZE INDICATED IN
INCHES, FIRST NUMBER IS SIDE SHOWN.
DASHED LINES INDICATE ACOUSTICAL LINER
FSD
COMBINATION
FIRE/SMOKE DAMPER
IN-LINE 90 DEGREE RISE/DROP IN
RETURN DUCT
DUCT SIZE TRANSITION RECTANGULAR TO
ROUND
30"x14" FLAT OVAL DUCT. SIZE INDICATED IN INCHES, FIRST NUMBER IS SIDE SHOWN
RETURN AIR DUCT UP
SUPPLY OR OUTSIDE AIR DUCT DOWN
SUPPLY OR OUTSIDE AIR DUCT UP
IN-LINE 90 DEGREE RISE/DROP IN
EXHAUST DUCT
SD
DUCT MOUNTED SMOKE DETECTOR
GLOBE VALVE
PLAN
NORTH
EXISTING PIPING TO BE
DEMOLISHED
L-2A L-2
L-7
L-6
101A
SCALE:
PHASE 3B MECHANICAL
HVAC DEMOLITION PLAN
3/16" = 1'-0"
MD101
0 4' 8' 16'
SCALE: 3/16"= 1'-0"
2'
1. EXISTING VAV TERMINAL BOX AND CONTROLLER
TO BE REMOVED.
2. EXISTING DUCTWORK DOWN TO WALL-MOUNTED
RETURN AIR GRILLE TO BE REMOVED.
KEYED NOTES
LEGEND:
EXISTING EQUIPTMENT TO
BE DEMOLISHED
EXISTING DUCTWORK TO BE
DEMOLISHED
EXIST. AIR TERMINAL
TO BE REMOVED (TYP.)
SCALE:
PHASE 3B MECHANICAL
PIPING DEMOLITION PLAN
3/16" = 1'-0"
MD102
0 4' 8' 16'
SCALE: 3/16"= 1'-0"
2'
1. DEMOLISH EXISTING VAV BOX. DEMOLISH PIPING
UP TO ISOLATION VALVES.
2. EXISTING VAV FROM TO REMAIN.
KEYED NOTES
2-8
2-9
2-2
2-7
1-9
2-3
1-11
1-17
2-6 2-52-4
1 1
2 1
2 2-1 1
EXIST. 3/4" HWS AND
HWR PIPING TO
REMAIN
EXIST. 1/2" HWS AND
HWR PIPING TO
REMAIN
EXIST. 1-1/2" HWR PIPING
TO REMAIN
EXIST. 1-1/2" HWR
PIPING TO REMAIN
EXIST. 1-1/4" HWR
PIPING TO REMAIN
EXIST. 3/4" HWS AND
HWR PIPING TO
REMAIN
EXIST. 3/4" HWS AND
HWR PIPING TO
REMAIN
EXIST. 2" HWS PIPING
TO REMAIN
EXIST. 1"
HWR PIPING
TO REMAIN
EXIST. 3/4" HWS AND
HWR PIPING TO
REMAIN
EXIST. 2" HWS
PIPING TO
REMAIN
1. REMOVE INSULATION FROM ALL EXISTING PIPES
AND FITTINGS WITHIN THE AREA OF WORK ON
THE FOLLOWING SYSTEMS: HEATING WATER
RETURN, HEATING WATER SUPPLY.
GENERAL NOTES
x1
8"Ø
10"Ø
10"Ø
"Ø
"Ø12
"Ø x1
14x
12" Ø
8" Ø
14"Ø 20x14
12"Ø
16x
14x
12"Ø
12"Ø 8"Ø
6" Ø
"Ø
12"Ø
16x14
14x12
12"Ø
12"Ø x1
4 20 x1 x1
12" Ø
14x x1
"Ø
18x14
38x20
18x14
"Ø
10"Ø
SCALE:
PHASE 3B MECHANICAL
HVAC NEW WORK PLAN
3/16" = 1'-0"
MH101
0 4' 8' 16'
SCALE: 3/16"= 1'-0"
2'
VAV
2-8
VAV
2-9
VAV
2-2
VAV
2-7
VAV
2-3
VAV
2-1
EXIST. 30X14 RETURN AIR
DUCT DOWN TO EXIST.
RETURN LOUVER
SAD-3
SAD-2
SAD-2
SAD-2
SAD-3
SAD-1
SAD-1
SAD-1
SAD-1
SAD-2
SAD-1
SAD-1
SAD-1
SAD-1
SEE MH102 FOR
CONTINUATION
SEE MH102 FOR
CONTINUATION
RAG-1
FD-1
FD-2
FD-3 FD-4
RAG-1
RAG-1
RAG-1
EXIST. RETURN AIR
LOUVER
EXIST. 14"X36" RETURN
DUCT DOWN TO EXIST.
RETURN LOUVER
EXIST. 30X14 RETURN AIR
DUCT DOWN TO EXIST.
RETURN LOUVER
KEYED NOTES
1. CONNECT NEW RETURN AIR DUCTWORK TO
EXISTING 30"X14" RETURN AIR DUCT IN CHASE.
2. PROVIDE CO2 SENSOR 48" AFF. SEE M-701 FOR
CONTROLS ASSOCIATED WITH DEMAND
CONTROLLED VENTILATION.
RAG-1
FD-5
T
T
T
T
T
T
T
VAV-2-9
THERMOSTAT
VAV-2-8
THERMOSTAT
VAV-2-4
VAV-2-5
VAV-2-6
THERMOSTAT
C x3 x4
20x14
14x10
8" Ø
"Ø
14x12
24x14 24x16 28x16
8" Ø
14x10 x1 x1
18x14 x1 x2
32x22
18x12
38x20
38x24 x2 x1 x2
SCALE: 1/16" = 1'-0"
48'8' 16' 32'0
PHASE 3B MECHANICAL
ROOF NEW WORK PLAN
1/16" = 1'-0"
MH102
PLAN
NORTH
KEYED NOTES
1. CONNECT NEW RETURN AIR DUCTWORK TO
EXISTING LOUVER.
2. CONNECT NEW SUPPLY AND RETURN AIR
DUCTWORK TO EXISTING AHU-2.
3. CONNECT NEW RETURN AIR DUCTWORK TO
EXISTING 36"X14" RETURN AIR DUCT IN CHASE.
4. PROVIDE NEW AIR FLOW MONITORING STATION
IN EXISTING RELIEF AIR DUCTWORK.
5. PROVIDE NEW LOW LEAKAGE MODULATING
RELIEF AIR DAMPER IN EXISTING RELIEF AIR
DUCTWORK.
EXIST. AHU-6
EXIST. AHU-5
EXIST. AHU-4
EXIST. AHU-2
EXIST. AHU-1
VAV
2-5
VAV
2-6
VAV
2-4
SAG-1
SAG-1
SAG-1
670 3
PHASE 3B MECHANICAL
MEZZANINE ENLARGED PLAN
1/4" = 1'-0"
MH102
PLAN
NORTH
EXIST. EXHAUST FAN
(TYP.)
EXIST. EXHAUST FAN
(TYP.)
EXIST. EXHAUST FAN
(TYP.)
8'0 2' 4' 12'
SCALE: 1/4"= 1'-0"
GENERAL NOTES
1. PROVIDE ALUMINUM JACKETING ON ALL
DUCTWORK INSULATION IN THE MEZZANINE
AREA.
AutoCAD SHX Text
PPM
AutoCAD SHX Text
REVISIONS
AutoCAD SHX Text Agricultural
AutoCAD SHX Text Service
AutoCAD SHX Text Research
AutoCAD SHX Text
DESCRIPTION
AutoCAD SHX Text
SHEET
AutoCAD SHX Text
DATE
AutoCAD SHX Text c
AutoCAD SHX Text P.A.
AutoCAD SHX Text
FIRM
AutoCAD SHX Text U
AutoCAD SHX Text
NO.
AutoCAD SHX Text D
AutoCAD SHX Text
EPM
AutoCAD SHX Text
SAFETY & HEALTH
AutoCAD SHX Text
REAL PROPERTY
AutoCAD SHX Text A
AutoCAD SHX Text
DATE
AutoCAD SHX Text
PROJECT NO.
AutoCAD SHX Text S
AutoCAD SHX Text
USDA
AutoCAD SHX Text
BY
AutoCAD SHX Text
AGRICULTURAL RESEARCH SERVICE
AutoCAD SHX Text
OF
AutoCAD SHX Text
THE
AutoCAD SHX Text
DESIGNER
AutoCAD SHX Text
PROJECT MANAGER
AutoCAD SHX Text
JOB #
AutoCAD SHX Text
CHECKED BY
AutoCAD SHX Text
A-E FIRM
AutoCAD SHX Text
P.O. BOX 513, GREENWOOD, MISSISSIPPI - (662) 455-4943
AutoCAD SHX Text Johnson M Adams
AutoCAD SHX Text
ARCHITECTS/ENGINEERS PLANNING SURVEYING MANAGEMENT
AutoCAD SHX Text
USDA AGRICULTURAL RESEARCH SERVICE
AutoCAD SHX Text
DALE BUMPERS NATIONAL RICE RESEARCH CENTER
AutoCAD SHX Text
(DBNRRC)
AutoCAD SHX Text
STUTTGART, ARKANSAS
AutoCAD SHX Text
PHASE 3B MECHANICAL
AutoCAD SHX Text
ROOF NEW WORK PLAN
AutoCAD SHX Text
MH102
AutoCAD SHX Text
XX XX
AutoCAD SHX Text 06/21/24
AutoCAD SHX Text
SME
AutoCAD SHX Text
SME
AutoCAD SHX Text
FEJ
AutoCAD SHX Text
SOUTHEAST AREA
AutoCAD SHX Text
STONEVILLE, MS
AutoCAD SHX Text
XXX
AutoCAD SHX Text 5923-E
AutoCAD SHX Text
XXX
AutoCAD SHX Text
XXX
AutoCAD SHX Text
XXX
AutoCAD SHX Text
XXX
AutoCAD SHX Text
SCALE:
AutoCAD SHX Text
SCALE:
AutoCAD SHX Text
MH102
SCALE:
PHASE 3B MECHANICAL
PIPING NEW WORK PLAN
3/16" = 1'-0"
MP101
0 4' 8' 16'
SCALE: 3/16"= 1'-0"
2'
VAV
2-8VAV
2-9
VAV
2-2
VAV
2-7
KEYED NOTES
1. PROVIDE TERMINAL UNIT. CONNECT TO
EXISTING HTWS AND HTWR BRANCH PIPING.
PROVIDE 3-WAY CONTROL VALVE.
EXIST.
VAV 1-9
EXIST.
VAV 1-11
EXIST.
VAV 1-17
VAV
2-5 1
VAV
2-6 1
VAV
2-4 1
VAV
2-3
VAV
2-1 1
EXIST. 3/4" HWS AND
HWR PIPING
EXIST. 1/2" HWS AND
HWR PIPING
EXIST. 1-1/2" HWR PIPING
EXIST. 1-1/2" HWR
PIPING
EXIST. 1-1/4" HWR
PIPING
EXIST. 3/4" HWS AND
HWR PIPING
EXIST. 3/4" HWS AND
HWR PIPING
EXIST. 2" HWS PIPING
EXIST. 1"
HWR PIPING
EXIST. 3/4" HWS AND
HWR PIPING
EXIST. 2" HWS
PIPING
GENERAL NOTES
1. PROVIDE INSULATION FOR ALL NEW AND
EXISTING HEATING WATER PIPING.
PIPE PENETRATION NOTES:
1. PROVIDE PITCH POCKET CONSTRUCTION, ADDITIONAL FLASHING, OR
WEATHER CAP AS REQUIRED FOR WATERPROOF CONSTRUCTION. DO NOT
MECHANICALLY ATTACH PIPE TO STRUCTURE IN ANY WAY.
2. SPACE BETWEEN PIPE AND SLEEVE SHALL BE FREE OF ANY FOREIGN
MATERIALS.
3. PIPE SHALL NOT CONTACT STRUCTURE AT ANY TIME. WEDGES ARE NOT BE
USED TO MAINTAIN PIPE POSITION.
4. PIPE MUST BE CENTERED IN OPENING.
SCALE:
PIPE PENETRATION DETAIL
NOT TO SCALE
CAULK ALL JOINTS
AND SLEEVE ENDS
WATERTIGHT
PIPING
SCH. 40 PIPE STEEL SLEEVE
FIRE STOP MATERIAL
(FOR FIRE RATED
PARTITIONS)
PIPE INSULATION AS APPLICABLE
PARTITION
TO UNISTRUT P2500 SERIES
PIPE STRAP
(TYP.)
TO UNISTRUT P3400 SERIES PIPE
CLAMPS
(TYP.)
TO UNISTRUT P 1000 12 GA
CHANNEL
(TYP.)
SECURE W/APPROVED ANCHOR TO
MATCH BASE MATERIAL AND LOAD
REQUIREMENTS
INSULATE AS REQD
CONC. OR MASONRY WALL
TO UNISTRUT P 1000 12 GA
CHANNEL
(TYP.)
SECURE W/APPROVED ANCHOR TO
MATCH BASE MATERIAL AND LOAD
REQUIREMENTS
INSULATE AS REQD
CONC OR MASONRY WALL
NOTE:
PROVIDE MIN ANCHOR
SUPPORT SPACING
EVERY 3' VERTICALLY
FOR PIPES < 4"Ø
FOR CONDUIT <
2"Ø
SCALE:
PIPING WALL SUPPORT DETAIL
NOT TO SCALE
SCALE:
SINGLE DUCT VAV BOX DETAIL
NOT TO SCALE
SCALE:
CLEVIS HANGER DETAIL
NOT TO SCALE
HEAVY DUTY CLEVIS
HANGER: MSS SP-69 AND
MSS SP-58
PIPE
RIGID INSULATION INSERT
(12" LONG, 180^ ARC)
CLEVIS HANGER WITH
INSULATION SHIELD
INSULATION
BOLT & NUT
SUPPORT NUT
LOCKING NUT
TURNBUCKLE
W/LOCKNUT
HANGER ROD
AIR FLOW
KEYED NOTES
INSTALL BALANCING VALVE WITH
MINIMUM OF 3 STRAIGHT PIPE
DIAMETERS UPSTREAM AND 1
STRAIGHT PIPE DIAMETER
DOWNSTREAM.
MAINTAIN 6" MINIMUM CLEARANCE
ABOVE TEST PLUG TO ALLOW
GAUGE TO BE INSERTED. DO NOT
COVER PLUG WITH INSULATION.
INSTALL SWING JOINTS AT COIL
CONNECTIONS.
CONNECT EXISTING BRANCH LINES
FROM TO NEW HEATING WATER
COIL.
PROVIDE COILS WITH INLET
STRAINERS AND CAPPED HOSE
CONNECTION BLOW DOWN VALVES.
INSTALL MANUAL AIR VENTS IN
SUPPLY AND RETURN COIL BRANCH
PIPING AS FOLLOWS:
A) IN PIPING HIGH POINT WHEN
PIPING IS ABOVE MAIN.
B) CLOSE TO COIL WHEN PIPING IS
NOT ABOVE MAIN (SIDE
CONNECTION).
NC
NO
C
HTWS
EXIST. SHUT-OFF
VALVE (TYP.)
BALANCING VALVE
3-WAY CONTROL VALVE
PLUG VALVE, ADJUST
TO EQUAL GPM THRU
COIL AT DESIGN FLOW
TEST PLUG (TYP.)
1/2" PLUGGED DRAIN VALVE COIL
MANUAL AIR VENT,
3/8" BALL VALE (TYP.)
SCALE:
HEATING WATER COIL DETAIL
NOT TO SCALE
12" MIN
12" MIN
SINGLE PIPE CLEVIS
HANGER
SCALE:
PIPE HANGER DETAILS
NOT TO SCALE
U-CLAMP OR
CONDUIT
CLAMP
GALVANIZED
IRON TRAPEZE
OR UNISTRUT
16 GAUGE
GALVANIZED
SHEET SHIELD
WRAPPED FULLY
AROUND
INSULATION
INSULATION
PIPE
PROVIDE A SECTION OF
HIGH COMPRESSION
STRENGTH INSULATION AT
EACH HANGER POINT.
INSULATION SHALL BE HALF
ROUND AND EXTEND 2"
BEYOND GALVANIZED
SHIELD EACH WAY.
16 GAUGE
GALVANIZED
SHEET SHIELD
WRAPPED FULLY
AROUND
INSULATION
INSULATION
PIPE
CONNECT NEW HTWR TO
EXIST. ISOLATION VALVE
HTWR
CONNECT NEW HTWS TO
EXIST. ISOLATION VALVE
EXTERNALLY
INSULATED RIGID GALV
SHT MTL ROUND DUCT
EXTERNALLY
INSULATED
PRIMARY SA
DUCTS
AIR FLOW
EXTERNALLY INSULATED
SUPPLY DUCT
TRANSITION
AS REQUIRED
HEATING WATER REHEAT
COIL
H.P. FLEX
(12" MAX
LENGTH)
CONTROL PANEL. LOCATE FOR OPTIMUM
ACCESS ABOVE CEILING. MAINTAIN MFR'S
RECOMMENDED ACCESS CLEARANCESHIGH EFF TAKE-OFF
FITTING (W/O DAMPER).
AIR FLOW
REDUCING OR ENLARGING
TRANSITION AS REQUIRED
(W/O DAMPER).
EXTERNALLY
INSULATED RIGID GALV
SHT MTL ROUND DUCT
EXTERNALLY
INSULATED GALV
SHT MTL DUCT
SEE BELOW FOR DUCT
CONTINUATION TO BOX
EXTERNALLY
INSULATED GALV
SHT MTL DUCT
ALTERNATE TAKEOFF FOR
BOXES WITH TAKEOFF
FROM END OF RECT DUCT
TRANSITION
AS REQUIRED
HARD METAL ROUND DUCT RUN OUT TO
DIFFUSER. SEE PLAN FOR SIZE
SAME SIZE AS GRILLE
NECK
REDUCER IF REQ'D.
BUTTERFLY DAMPER SHALL BE USED
AT THIS LOCATION OR AT
CONNECTION OF RUN-OUT TO MAIN
DUCT.
WORM GEAR DRIVE,
STAINLESS STEEL STRAP
LAY-IN GRILLE SHOWN.
SURFACE MOUNTED SIMILAR
SCALE:
TYPICAL RETURN/EXHAUST GRILLE CONNECTION DETAIL
NOT TO SCALE
AREAS WITH
HARD OR LAY
IN CEILINGS
PROVIDE MANUAL OPPOSED DAMPER IN EACH BRANCH LINE
UNLESS OTHERWISE NOTED ON DRAWINGS. DAMPERS SHALL
BE INSTALLED IN ACCESSIBLE LOCATION NEAR TRUNK DUCT
AND MINIMUM OF 5'-0" FROM ANY AIR INLET OR OUTLET
DEVICE. COORDINATE W/ ACCESS DOORS IN NON-ACCESSIBLE
CEILINGS.
TRUNK
DUCT
OVAL BRANCH
DUCT
45° CLINCH COLLAR PER SMACNA
USE AT ALL BRANCH TAPS
UNLESS
SPLITTER DAMPERS ARE
INDICATED.
BELL-MOUTH
FITTING
NOTE:
DAMPERS SHALL BE PROVIDED IN ALL BRANCH RUN-OUTS TO DIFFUSERS, R.A AND EXHAUST GRILLES, UNLESS SPECIFICALLY NOTED OTHERWISE ON DRAWINGS.
LOCATE DAMPERS SO THEY ARE ACCESSIBLE FROM LAY-IN CEILING OR ACCESS DOORS.
SCALE:
BRANCH DUCT TAP DETAIL
NOT TO SCALE
ROUND
DUCT
DUCT HANGERS, ATTACH TO THE
STRUCTURE ABV.
RECTANGULAR, ROUND,
OR OVAL, DUCT MAIN
WITH EXTERNAL
INSULATION
CEILING DIFFUSER
SCALE:
TYPICAL DIFFUSER CONNECTION DETAIL
NOT TO SCALE
DUCT HANGERS, ATTACH TO THE STRUCTURE ABV.
RECTANGULAR, ROUND, OR OVAL DUCT MAIN WITH
EXTERNAL INSULATION
CEILING DIFFUSER
AREAS WITH
HARD OR LAY
IN CEILINGS
AREAS ABOVE
CEILING (TYP.)
ROUND DUCT WITH EXTERNAL
INSULATION
ATTACH THE FLEXIBLE DUCT TO
THE RIGID DUCT AND THE
DIFFUSER USING TWO (2) BANDS;
ONE FOR THE DUCT AND ONE FOR
THE INSULATION.
U.L. LISTED FLEXIBLE DUCT.
SUPPORT TO PREVENT SAG.
FLEXIBLE DUCT SHALL BE LESS
THAN 5 FT. IN LENGTH AND SHALL
NOT BE USED FOR BENDS
GREATER THAN 45°.
MANUAL DAMPER WITH LOCKING
QUADRANT REGULATOR.
RIGID 90° DUCT ELBOW
WITH EXTERNAL
INSULATION
ATTACH THE FLEXIBLE DUCT TO
THE RIGID DUCT AND THE
DIFFUSER USING TWO (2) BANDS;
ONE FOR THE DUCT AND ONE FOR
THE INSULATION.
U.L. LISTED FLEXIBLE DUCT.
SUPPORT TO PREVENT SAG.
FLEXIBLE DUCT SHALL BE LESS
THAN 5 FT. IN LENGTH AND SHALL
NOT BE USED FOR BENDS
GREATER THAN 45°.
MANUAL DAMPER WITH LOCKING
QUADRANT REGULATOR.
RIGID 90° DUCT ELBOW
WITH EXTERNAL
INSULATION
ROUND DUCT WITH EXTERNAL
INSULATION
SCALE:
TURNING VANE DETAIL
NOT TO SCALE
TURNING VANES, TYPICAL
TURNS 45° OR LARGER
RUNNER
INSTALL VANES
TANGENT TO
AIRSTREAM
DOUBLE SIDED TURNING
VANES REQUIRED WHERE
DUCT HEIGHT IS 24" OR
GREATER.
TOP RUNNER NOT SHOWN FOR
CLARITY.
NUMBER AND CONFIGURATION OF
VANES PER SMACNA STANDARDS.
20% MAXIMUM
AREA REDUCTION
R=H (MIN.)
H
DIM. "D"
ELEVATION
VIEW
PLAN
VIEW
DUCT DIM.
(SEE PLAN)
DUCT "VENTURI"
DEPRESSION DETAIL
NOTE: USE DETAIL
WHERE REQUIRED BY
FIELD CONDITIONS.
H R
TRANS.
DN.
TRANS.
UP
SCALE:
DUCT DEPRESSION FOR STRUCTURAL CONFLICTS DETAIL
NOT TO SCALE
MIN. 2/3
"D"
TYPICAL
OBSTRUCTION TO
DUCT PATH
3"
CABLE WRAP
AROUND BEAM
AND BAR JOIST
CL20
DUCTMATE
CLUTCHERS
WR20 CABLE
DUCT
DUCT
INSULATION
THREADED ROD
DOUBLE NUTUNISTRUT OR
ANGLE
UNISTRUT BAR
BAR JOIST
CL20
DUCTMATE
CLUTCHER OR
EQUAL
DUCTMATE
WR20 CABLE
OR EQUAL
MINIMUM 3/8"
DIA. THREADED
ROD
12 GAUGE
GALVANIZED
STEEL
DUCT
DUCT
INSULATION
DOUBLE NUT
DUCT
EXTERNAL
INSULATION WHERE
SPECIFIED
NOTE: FOR SIZES UP TO 60"
WITH 10' MAXIMUM SPACING.
NOTE: SEMI-CIRCLE
HANGER. 61"-72" DIAMETER
WITH 10' MAXIMUM
SPACING.
END VIEW
ELEVATION VIEW
2"3 1/2" 1"
NOTE: FOR SIZES UP TO 60"
WITH 10' MAXIMUM SPACING.
SINGLE
DOUBLE
SCALE:
DUCT HANGER DETAILS
NOT TO SCALE
NOTE: 10' MAXIMUM SPACING.
97-120
85-96
72-84
61-72
DUCT SIZE (IN.) STRUT SIZE
1 5/8 X 1 5/8 X 12 GA
N/A
N/A
N/A
2 1/2 X 2 1/2 X 1/4
2 X 2 X 1/4
N/A
ANGLE SIZE
3 X 3 X 1/4
3/8
ROD SIZE
3/8
3/8
3/8
R = RADIUS OF CURVE
H = HEIGHT
D = DIAMETER
SINGLE DUCT VAV TERMINAL SCHEDULE
BOX TYPEBASIS OF
DESIGN
MFG.
BOX
MIN.
CFM
MFG.
BOX
MAX.
CFM
CFM DATA
INLET
SIZE
REHEAT/HEATING COIL DATA
MBH EWT/LWT °F EAT °F GPM
MAX.
WPD
FT.HD.
MAX
APD
IN.WC
REMARKS
SINGLE DUCT
REHEAT 6"Ø 180/145.6 55 0.510.11 SEE NOTES
1. ACTUATORS FOR VAV BOX AIR-CONTROL DAMPERS ARE TO BE FURNISHED AND INSTALLED BY THE AUTOMATIC TEMPERATURE CONTROLS SUPPLIER.
2. HEATING COIL CONTROL VALVES AND ACTUATORS ARE TO BE FURNISHED AND INSTALLED BY THE AUTOMATIC TEMPERATURE CONTROLS SUPPLIER
3. PROVIDE BOXES WITH CONTROL ENCLOSURES, INTERNALLY LINED CASINGS, HEATING COILS LOCATED ON THE DISCHARGE POSITION.
4. FOR ALL BOXES, FIELD VERIFY RIGHT-HAND OR LEFT-HAND BOX AND COIL CONFIGURATIONS, DUCT CONNECTION CONFIGURATIONS, AND ELECTRICAL & CONTROL BOX
LOCATIONS PRIOR TO SUBMITTAL.
5. PROVIDE VAV BOXES WITH DOUBLE WALL CONSTRUCTION.
6. MINIMUM AND MAXIMUM AIRFLOWS LISTED ARE SHOWN FOR SIZING OF VAV BOXES. VAV BOXES MUST BE BALANCED TO COOLING AND HEATING DESIGN AIRFLOWS LISTED.
7. PROVIDE 3-WAY MODULATING CONTROL VALVE FOR ALL VAV TERMINAL UNITS.
DUCT CONN.
COIL
POSITION
DISCHARGE
NOTES:
SEE NOTESDISCHARGE
SEE NOTESDISCHARGE
SEE NOTESDISCHARGE
COOLING/
HEATING
CFM
MARK
VAV-2-1
VAV-2-2
VAV-2-3
VAV-2-4
VAV-2-5
VAV-2-6
VAV-2-7
LAT °F
MIN.
COOLING/
HEATING
CFM
6"Ø
8"Ø
8"Ø
8"Ø SEE NOTESDISCHARGE
VAV-2-8
VAV-2-9
10"Ø SEE NOTESDISCHARGE
SEE NOTESDISCHARGE12"Ø
SEE NOTESDISCHARGE14"Ø
14"Ø SEE NOTESDISCHARGE
7560 500
0.51
0.6445
TRANE VCWF
SINGLE DUCT
REHEAT
SINGLE DUCT
REHEAT
SINGLE DUCT
REHEAT
SINGLE DUCT
REHEAT
SINGLE DUCT
REHEAT
SINGLE DUCT
REHEAT
SINGLE DUCT
REHEAT
SINGLE DUCT
REHEAT
8.73
16.890.51 0.2460 500
105 900
165 1400
240 2000
320 3000
320 3000
105 900
105 900
55180/123.8TRANE VCWF
TRANE VCWF
TRANE VCWF
TRANE VCWF
TRANE VCWF
TRANE VCWF
TRANE VCWF
TRANE VCWF
FIRE DAMPER SCHEDULE
BASIS
OF DESIGNMARK
SIZE
(IN.) ORIENTATION
FD-1 GREENHECK
DFD-110 HORIZONTAL18 x 14
FIRE RATING
(HOURS)
1-1/2
MAXIMUM
OPERATING PD
(IN. WG)
MAXIMUM
VELOCITY
(FPM)
NOTES
ALL
FD-3 GREENHECK
DFD-110 HORIZONTAL20 x 14 1-1/2 4 2000 ALL
FD-4 GREENHECK
DFD-110 HORIZONTAL18 x 14 1-1/2 4 2000 ALL
4 2000
FD-2 GREENHECK
DFD-110 HORIZONTAL20 x 14 1-1/2 4 2000 ALL
1. 165 DEGREE FAHRENHEIT FUSIBLE LINK.
2. 16 GA GALVANIZED CHANNEL FRAME.
3. CURTAIN TYPE SUITABLE FOR HORIZONTAL INSTALLATIONS.
4. 250 DEGREE FAHRENHEIT OPERATING TEMPERATURE.
5. DAMPER SHALL COMPLY WITH NFPA STANDARDS 80, 90A, 101 AND UL 555.
NOTES:
NOTES:
1. PROVIDE WITH ALUMINUM CONSTRUCTION.
GRILLE, REGISTER AND DIFFUSER SCHEDULE
MARK TYPE USE
S
PANEL
SIZE IN.
NECK
SIZE IN.
MAXFPM MAX PD
IN. WC FINISH PATTERN REMARKSR E
MAX. NOISE
CRITERIA (NC)
XSAD-1
XSAD-2
SEE NOTES24X24 10Ø 550 0.025 MATCH
ARCH.
4-WAY
SEE NOTES
RAG-1 X 24X24 550 0.025 SEE NOTES1022X22
CEILING
MOUNTED
24X24 12Ø 4-WAY 100.025550
PERF.
CEILING
MOUNTED
CEILING
MOUNTED
XSAD-3 SEE NOTES24X24 14Ø 4-WAY 100.025550CEILING
MOUNTED
XSAG-1 SEE NOTES24X10 24X10
DRUM
LOUVER
100.025550WALL
MOUNTED
MATCH
ARCH.
MATCH
ARCH.
MATCH
ARCH.
MATCH
ARCH.
1.0421.640.35 0.1055180/138.4 90
1.3125.430.45 0.1555180/141.3 90
1.3125.430.45 0.1555180/141.3 90
1.1633.780.34 0.2455180/121.9 90
2.0651.810.38 0.2555180/129.6 90
4.1459.380.17 4.3055180/151.3 85
3.9258.070.17 3.9055180/150.4 85
FD-5 GREENHECK
DFD-110 HORIZONTAL22 x 22 1-1/2 4 2000 ALL
MAXIMUM
APD
(IN. WG)
0.1
0.1
0.1
0.1
0.1
AIR
RETURN
NC EXIST.
RETURN AIR
ACTUATOR
EXIST.
OUTDOOR AIR
ACTUATOR
RELIEF AIR
ACTUATOR
AIR
RELIEF
AIR
SUPPLY
AIR
OUTDOOR
EXIST. OUTDOOR AIRFLOW
MONITORING STATION
RELIEF AIR
MONITORING STATION
AUDITORIUM DEMAND CONTROLLED VENTILATION
NOT TO SCALE
M-701
RA-F
OA-F
RA-D-MIN
RA-D-MAX OA-D-MIN
OA-D-MAX
SEQUENCE OF OPERATION
PROPORTIONAL DEMAND CONTROLLED VENTILATION AND RELIEF AIR DAMPER
SET POINTS:
OUTDOOR AIRFLOW MINIMUM - 1230 CFM
RELIEF AIRFLOW MINIMUM - 435 CFM
CO2 CONCENTRATION MINIMUM LIMIT - 350 PPM
OUTDOOR AIRFLOW MAXIMUM - 2895
RELIEF AIRFLOW MAXIMUM - 2100 CFM
CO2 CONCENTRATION MAXIMUM LIMIT - 1250 PPM
MODES OF OPERATION:
WHEN AHU-2 OUTDOOR AIR DAMPER IN THE CLOSED POSITION THE RELIEF AIR DAMPER
SHALL BE CLOSED
WHEN AHU-2 OUTDOOR AIR DAMPER IS AT MINIMUM SET POINT AND CO2 CONCENTRATION IS
BELOW MINIMUM LIMIT THE RELIEF AIR DAMPER SHALL MAINTAIN AN OFFSET OF OUTDOOR
AIR TO RELIEF AIR OF 795 CFM.
WHEN CO2 CONCENTRATION MEASURED WITHIN AUDITORIUM 101 RISES ABOVE THE
MINIMUM LIMIT THE AHU-2 OUTDOOR AIR DAMPER SHALL MODULATE PROPORTIONALLY TO
SATISFY THE AUDITORIUM 101 SPACE CO2 SENSOR. AS THE OUTDOOR AIR DAMPER
MODULATES TO GREATER THAN THE MINIMUM POSITION AS MEASURED BY THE EXISTING
OUTDOOR AIRFLOW MONITORING STATION THE RELIEF AIR DAMPER SHALL MODULATE TO
MAINTAIN AN OFFSET OF OUTDOOR AIR TO RELIEF AIR OF 795 CFM.
WHEN CO2 CONCENTRATION IN THE AUDITORIUM REACHES THE CO2 MAXIMUM LIMIT THE
AHU-2 OUTDOOR AIR DAMPER SHALL MODULATE TO THE MAXIMUM POSITION AS MEASURED
BY THE EXISTING OUTDOOR AIRFLOW MONITORING STATION. THE RELIEF AIR DAMPER
SHALL MODULATE TO MAINTAIN AN OFFSET OF OUTDOOR AIR TO RELIEF AIR OF 795 CFM.
NOTE: CONTRACTOR SHALL PROVIDE ALL ADDITIONAL CONTROLS COMPONENTS,
HARDWARE, AND PROGRAMMING NECESSARY TO INTEGRATE THE ABOVE RELIEF AIR
DAMPER SEQUENCE OF OPERATIONS INTO THE EXISTING AHU-2 CONTROLS.
ALARMING
FUNCTION POINT NAME DESCRIPTION SETTING
(WITH UNITS)
RANGE
(WITH UNITS)
IO
TYPE
ALARM CONDITION
(SEE NOTES)
ALARM
PRIORITY
PROOFS
SAFETIES
TBD MANUFACTURER'S PROOFS (SEE NOTE) TBD ALM/NORMAL TBD
TBD MANUFACTURER'S SAFETIES (SEE NOTE) TBD ALM/NORMAL TBD
HTG-V-S HEATING VALVE POSITION STATUS 0-100% OPEN AI ALM INFO
START/STOP SYS-OCC-C OCCUPANCY INPUT FROM SYSTEM SCHEDULER OCCUPIED(1)/UNOCCUPIED(2) NET-IN
ZN-OCC OCCUPANCY OVERRIDE FROM SPACE OCCUPIED(1)/UNOCCUPIED(2) BI
ZONE
TEMPERATURE
CONTROL
ZN-T ZONE TEMPERATURE 40 - 85°F AI ZONE TEMPERATURE BELOW 60°F
OR ABOVE 80°F INFO
ZN-T-SP ZONE TEMPERATURE SETPOINT OCCUPANCY
ADJUSTABLE 68 - 78°F AI
ZN-T-SP-UNOCC ZONE TEMPERATURE SETPOINT FOR UNOCCUPIED MODE 55 - 80°F NET-OUT
VAV-SA-F VAV SUPPLY AIRFLOW AS SCHEDULED AI
VAV-SA-F-SP VAV SUPPLY AIRFLOW SETPOINT RESET SCHEDULE NET-OUT
VAV-D-C VAV DAMPER COMMAND 0-100% OPEN AO
HTG-V-C VAV REHEAT VALVE COMMAND 0-100% OPEN AO
DAMPER
CONTROL
LOOP
CONFIGURATION
SETTINGS
PROPORTIONAL CONSTANT TBD
INTEGRAL CONSTANT TBD
BIAS TBD
MAXIMUM OUTPUT TBD
MINIMUM OUTPUT TBD
NOTES:
1. THE CONTRACTOR SHALL COMPLETE THE POINTS SCHEDULE AS INDICATED IN THE SPECIFICATION AND IN ACCORDANCE WITH THIS DRAWING.
2. UNIT MANUFACTURERS PROOFS AND SAFETIES: THE CONTRACTOR SHALL SHOW EACH PROOF AND SAFETY AS A SEPARATE ROW.
3. UNIT STATUS: SERVES AS A MONITORED POINT AT THE M&C SOFTWARE (FRONT-END) AND AS A HEATING/COOLING REQUEST TO THE BOILER, HEAT EXCHANGER, AND/OR
CHILLER SERVING THIS SYSTEM.
4. "TBD" = TO BE DETERMINED DURING COMMISSIONING.
DDCHTG-V-C
DA-TVAV-#-#-V
RETURN
VAV-SA-F
ZN-T
TO
H ZONE
SUPPLY
VAV-D-C
SEQUENCE OF OPERATION
VAV BOXES
RUN CONDITIONS - SCHEDULED:
THE UNIT SHALL RUN ACCORDING TO A USER DEFINABLE TIME SCHEDULE IN THE FOLLOWING MODES:
· OCCUPIED MODE: THE UNIT SHALL MAINTAIN
· A 75°F (ADJ.) COOLING SETPOINT
· A 70°F (ADJ.) HEATING SETPOINT.
· UNOCCUPIED MODE (NIGHT SETBACK): THE UNIT SHALL MAINTAIN
· A 85°F (ADJ.) COOLING SETPOINT.
· A 60°F (ADJ.) HEATING SETPOINT.
ALARMS SHALL BE PROVIDED AS FOLLOWS:
· HIGH ZONE TEMP: IF THE ZONE TEMPERATURE IS GREATER THAN THE COOLING SETPOINT BY A USER
DEFINABLE AMOUNT (ADJ.).
· LOW ZONE TEMP: IF THE ZONE TEMPERATURE IS LESS THAN THE HEATING SETPOINT BY A USER DEFINABLE
AMOUNT (ADJ.).
ZONE SETPOINT ADJUST:
THE OCCUPANT SHALL BE ABLE TO ADJUST THE ZONE TEMPERATURE HEATING AND COOLING SETPOINTS AT THE
ZONE SENSOR.
ZONE OPTIMAL START:
THE UNIT SHALL USE AN OPTIMAL START ALGORITHM FOR MORNING START-UP. THIS ALGORITHM SHALL MINIMIZE THE UNOCCUPIED WARM-UP OR COOL-DOWN PERIOD WHILE STILL ACHIEVING COMFORT CONDITIONS BY THE
START OF SCHEDULED OCCUPIED PERIOD.
ZONE UNOCCUPIED OVERRIDE:
A TIMED LOCAL OVERRIDE CONTROL SHALL ALLOW AN OCCUPANT TO OVERRIDE THE SCHEDULE AND PLACE THE UNIT INTO AN OCCUPIED MODE FOR AN ADJUSTABLE PERIOD OF TIME. AT THE EXPIRATION OF THIS TIME, CONTROL OF THE UNIT SHALL AUTOMATICALLY RETURN TO THE SCHEDULE.
SPACE OCCUPIED MODE:
· SPACE THERMOSTAT SHALL MODULATE PRIMARY AIR DAMPER TO MAINTAIN SPACE TEMPERATURE.
· UPON CALL FOR HEAT, THE PRIMARY DAMPER SHALL CLOSE TO MINIMUM POSITION. UPON FURTHER CALL
FOR HEAT WITH PRIMARY AIR DAMPER IN MINIMUM POSITION, THE REHEAT CONTROL VALVE SHALL OPEN
AND MODULATE IN SEQUENCE TO MAINTAIN SPACE TEMPERATURE SET POINT.
· UPON CALL FOR COOLING, THE REHEAT VALVE SHALL MODULATE CLOSED. UPON A FURTHER CALL FOR COOLING, THE AIR DAMPER SHALL MODULATE OPEN AS REQUESTED TO PROVIDE COOLING AS SENSED BY
THE SPACE SENSOR.
HEATING WATER REHEATING:
THE CONTROLLER SHALL MEASURE THE ZONE TEMPERATURE AND STAGE THE 3-WAY HEATING WATER VALVE TO
MAINTAIN THE HEATING AND COOLING MODE DISCHARGE AIR TEMPERATURES AS SCHEDULED.
THE REHEATING SHALL BE ENABLED WHENEVER:
· VAV BOX DAMPER IS IN THE OPEN POSITION AND IN THE HEATING MODE.
· VAV BOX DAMPER IS IN THE MINIMUM POSITION IN THE COOLING MODE.
IN THE OCCUPIED MODE WHEN SPACE TEMPERATURE CONDITIONS ARE MET AND THE VAV BOX DAMPER IS IN
THE MINIMUM
POSITION, THE CONTROLLER SHALL STAGE THE 3-WAY HEATING WATER VALVE TO MAINTAIN A DISCHARGE AIR
TEMPERATURE OF
75 °F IN THE COOLING MODE AND 70 °F IN THE HEATING MODE.
DISCHARGE AIR TEMPERATURE:
THE CONTROLLER SHALL MONITOR THE DISCHARGE AIR TEMPERATURE.
ALARMS SHALL BE PROVIDED AS FOLLOWS:
· HIGH DISCHARGE AIR TEMP: IF THE DISCHARGE AIR TEMPERATURE IS GREATER THAN 120°F (ADJ.).
· LOW DISCHARGE AIR TEMP: IF THE DISCHARGE AIR TEMPERATURE IS LESS THAN 40°F (ADJ.).
ZN-T-LL
ZN-T-SP
HTG-V-S
PROVIDE ZONE
THERMOSTAT(S) AS
SHOWN IN POINTS
SCHEDULE AND ON
PLANS
ZN-T-SP-UNOCC
VAV-SA-F-SP
TO DDC
SYS-OCC-C
ZN-OCC
NAME:
VAV BOX W/ REHEAT CONTROLS
NOT TO SCALE
M-701
OUTDOOR
AIRFLOW
MIN. CFM
OUTDOOR
AIRFLOW
MAX. CFM
C02
CONCENTRATION
MIN. LIMIT
PPM
C02
CONCENTRATION
MAX. LIMIT
PPM
A OR AMP AMPERE(S)
ACC AIR COOLED CHILLER
AC ALTERNATING CURRENT
AC AIR COMPRESSOR / AIR
CURTAIN
AF AMP FRAME
AFF ABOVE FINISHED FLOOR
AFG ABOVE FINISHED GRADE
AHU AIR HANDLING UNIT
AIC AMPERE INTERRUPTING
CAPACITY
AL ALUMINUM
AM AMMETER
ASYM ASYMMETRICAL
AT AMP TRIP
ATS AUTOMATIC TRANSFER
SWITCH
AUTO AUTOMATIC
AWG AMERICAN WIRE GAUGE
B BOILER
BC BRANCH CONTROLLER
BCW BARE COPPER WIRE
BFF BELOW FINISHED FLOOR
BFG BELOW FINISHED GRADE
BLDG BUILDING
C CONDUIT
CAT CATEGORY
CB CIRCUIT BREAKER
CCT CORRELATED COLOR
TEMPERATURE
CCTV CLOSED CIRCUIT
TELEVISION
CFCI CONTRACTOR FURNISHED
CONTRACTOR INSTALLED
CH CHILLER
CHWCP CHILLED WATER
CIRCULATING PUMP IN A
PRIMARY-SECONDARY
SYSTEM
CHWP CHILLED WATER PUMP
CHWSP CHILLED WATER SUPPLY
PUMP IN A PRIMARY-
SECONDARY SYSTEM
CKT CIRCUIT
CMH COMMUNICATIONS
MANHOLE
CP CONDENSATE PUMP
CPT CONTROL POWER
TRANSFORMER
CRAC COMPUTER ROOM AC UNIT
CRI COLOR RENDERING INDEX
CT CURRENT TRANSFORMER
CT COOLING TOWER
CU COPPER OR CONDENSING
UNIT
CWP CONDENSER WATER PUMP
D DEPTH
DC DIRECT CURRENT
DF DESTRATIFICATION FAN
DH or DUH DUCT HEATERS
DHWCP DOMESTIC HOT WATER
CIRCULATING PUMP
DISC DISCONNECT SWITCH
DOAS DEDICATED OUTSIDE AIR
SYSTEM (UNIT)
DPST DOUBLE POLE SINGLE
THROW
DPDT DOUBLE POLE DOUBLE
THROW
DSCU DUCTLESS SPLIT
CONDENSING UNIT
(POWERS THE DSS INDOOR
UNIT)
DSHP DUCTLESS SPLIT HEAT
PUMP (POWERS THE DSS
INDOOR UNIT)
DSS DUCTLESS SPLIT SYSTEM
(INDOOR UNIT)
DWBP DOMESTIC WATER
BOOSTER PUMP
DX DIRECT EXPANSION (DX)
COOLING COIL
EC EMPTY CONDUIT
EF EXHAUST FAN
ELEC ELECTRICAL
EMH ELECTRICAL MANHOLE
EMT ELECTRICAL METALLIC
TUBING
E or EMER EMERGENCY
EPA EFFECTIVE PROJECTED
AREA
EQUIP EQUIPMENT
ERV ENERGY RECOVERY
VENTILATOR
ERU ENERGY RECOVERY UNIT
EXIST or EX EXISTING
NOTE: ABBREVIATIONS ABOVE
ARE FOR ELECTRICAL SHEETS
ONLY. NOT ALL ABBREVIATIONS
SHOWN WILL BE USED ON THIS
PROJECT.
ABBREVIATIONS LIST
EUH ELECTRIC UNIT HEATER
EXP EXPLOSION PROOF
EWC ELECTRIC WATER COOLER
EWH ELECTRIC WATER HEATER
F FUSE
FACP FIRE ALARM CONTROL
PANEL
FCU FAN COIL UNIT
FLEX FLEXIBLE
FWE FURNISHED WITH
EQUIPMENT
G OR GND GROUND
GFGI GOVERNMENT FURNISHED
GOVERNMENT INSTALLED
GFI GROUND FAULT
INTERRUPTER
GRS GALVANIZED RIGID STEEL
CONDUIT
GUH GAS UNIT HEATER
GWH GAS WATER HEATER
H or HT HEIGHT
HAC HEATED AIR CURTAIN
HOA HAND-OFF AUTOMATIC
HP HORSE POWER
HP HEAT PUMP (OUTDOOR
PORTION OF SPLIT SYSTEM
HEAT PUMP, USE CU FOR
STANDARD DX OUTDOOR
UNIT)
HT HEAT TRACKING
HVU HEATING/VENTILATING UNIT
HWCP HEATING WATER
CIRCULATING PUMP IN A
PRIMARY-SECONDARY
SYSTEM
HWP HEATING WATER SUPPLY IN
A PRIMARY-ONLY SYSTEM
HWRP HOT WATER
RECIRCULATION PUMP
HWSP HEATING WATER SUPPLY
PUMP IN A PRIMARY-
SECONDARY SYSTEM
HWUH HOT WATER UNIT HEATER
HZ HERTZ
IDS INTRUSION DETECTION
SYSTEM
IMC INTERMEDIATE METAL
CONDUIT
IRH INFRARED HEATER
J OR JB JUNCTION BOX
K KILO
KAIC THOUSAND AMPERE
INTERRUPTING CAPACITY
KCM OR KCMIL THOUSAND OF CIRCULAR
MILS
KEF KITCHEN EXHAUST FAN
KH KITCHEN HOOD
KV KILOVOLT
KVA KILOVOLT-AMPERES
KW KILOWATT
KWHR KILOWATT-HOUR
L LENGTH
LA LIGHTNING ARRESTOR
LAN LOCAL AREA NETWORK
LAV LAVATORY
LM LOCKHEED MARTIN
LTG LIGHTING
MAU MAKE-UP AIR UNIT
MAX MAXIMUM
MCA MINIMUM CIRCUIT AMPACITY
MCB or MB MAIN CIRCUIT BREAKER
MCC MOTOR CONTROL CENTER
MGB MAIN GROUND BAR
MH MANHOLE or MOUNTING
HEIGHT
MIN MINIMUM
MLO MAIN LUGS ONLY
MOD MOTOR OPERATED DAMPER
MT or MTD MOUNT or MOUNTED
MRS MOTOR RATED SWITCH
N NEUTRAL
NEC NATIONAL ELECTRICAL
CODE
NEMA NATIONAL ELECTRICAL
MANUFACTURER'S
ASSOCIATION
NFPA NATIONAL FIRE
PROTECTION ASSOCIATION
NC NORMALLY CLOSED
NESC NATIONAL ELECTRICAL
SAFETY CODE
NL NIGHT LIGHT
NO NORMALLY OPEN
NTS NOT TO SCALE
P POLE(S) or PUMP
PA PUBLIC ADDRESS
PDU POWER DISTRIBUTION UNIT
PF POWER FACTOR
PH PHASE
PIU VAV TERMINAL UNIT WITH
PARALLEL OR SERIES FAN
(PRIMARY INDUCTION UNIT)
PMT PAD MOUNTED
TRANSFORMER
PNL PANEL OR PANELBOARD
PTAC PACKAGED THRU-WALL AIR
CONDITIONER
PVC POLYVINYL CHLORIDE
RECEPT or RECP RECEPTACLE
RF RETURN FAN
RH RADIANT HEATERS
(ELECTRIC)
RMC RIGID METAL CONDUIT
RMS ROOT MEAN SQUARE
RTU ROOF TOP UNIT
RVNR REDUCED VOLTAGE NON-
REVERSING
SA SURGE ARRESTOR
SCCR SHORT CIRCUIT CURRENT
RATING
SD SMOKE DAMPER
SF SUPPLY FAN
S/N SOLID NEUTRAL
SP SUMP PUMP
SPD SURGE PROTECTIVE DEVICE
SPDT SINGLE POLE DOUBLE
THROW
SPEC SPECIFICATIONS
SPST SINGLE POLE SINGLE
THROW
SWBD SWITCHBOARD
SWGR SWITCHGEAR
TMGB TELECOMMUNICATIONS
MAIN GROUNDING BUSBAR
TOL THERMAL OVERLOAD
TP TWISTED PAIR
TYP TYPICAL
U URINAL
UH UNIT HEATER
UG UNDERGROUND
UIO UNLESS INDICATED
OTHERWISE
UL UNDERWRITERS
LABORATORY
UTP UNSHIELDED TWISTED PAIR
V VOLTS
VA VOLT AMPERES
VAV VAV TERMINAL UNIT
VEF VEHICLE EXHAUST FAN
VM VOLTMETER
VRF VARIABLE REFRIGERANT
FLOW SYSTEM
W WATTS or WIRE or WIDTH
WC WATER CLOSET
WEF WELDING EXHAUST FAN
WH WATER HEATER
WHDM WATTHOUR DEMAND METER
WSHP WATER SOURCE HEAT
PUMP
WP WEATHERPROOF
XFMR TRANSFORMER
Z IMPEDANCE
GENERAL NOTES - ELECTRICAL:
1. THE DRAWINGS INDICATE THE GENERAL EXTENT OF WORK. THE DRAWINGS ARE NOT
INTENDED TO INDICATE OR DESCRIBE ALL WORK REQUIRED FOR THE FULL PERFORMANCE
AND COMPLETION OF THE REQUIREMENTS OF THE CONTRACT DOCUMENTS.
2. THE ENUMERATION OF PARTICULAR ITEMS OF WORK IN ONE PORTION OF THE CONTRACT
DOCUMENTS SHALL NOT BE CONSTRUED TO EXCLUDE OTHER ITEMS NECESSARY OR
IMPLIED THEREFROM.
3. THE CONTRACTOR IS RESPONSIBLE FOR THE COORDINATION OF WORK SEQUENCING SUCH
THAT NO WORK SHALL BE LEFT IN AN UNFINISHED OR INCOMPLETE CONDITION.
4. WORK SHALL CONFORM TO APPLICABLE INDUSTRY AND MANUFACTURER'S PUBLISHED
STANDARDS FOR QUALITY OF MATERIALS AND WORKMANSHIP, AS WELL AS, THE
REQUIREMENTS IN THESE DRAWINGS AND SPECIFICATIONS. ANY CONFLICTING
REQUIREMENTS OF THE SOURCES LISTED ABOVE SHALL BE BROUGHT TO THE
CONTRACTING OFFICER'S ATTENTION PRIOR TO PROCEEDING WITH THE WORK.
5. THE CONTRACTOR SHALL PROTECT ANY EXISTING, IN-PLACE, AND NEW WORK.
6. WORK NOTED "N.I.C." IS NOT MEANT TO BE PART OF THE CONSTRUCTION SCOPE OF WORK
AGREEMENT.
7. THE CONTRACTOR SHALL PAY FOR AND COORDINATE THE REMOVAL AND LEGAL DISPOSAL
OF MATERIALS AND RUBBISH.
8. ONCE ON SITE, THE CONTRACTOR SHALL VERIFY DIMENSIONS AND SHALL VERIFY NEW AND
EXISTING CONDITIONS, SHOWN ON THESE DRAWINGS. THE CONTRACTOR SHALL NOTIFY THE
CONTRACTING OFFICER IN WRITING OF ANY DIFFERING CONDITIONS BEFORE
COMMENCEMENT OF WORK.
9. DO NOT SCALE DRAWINGS; DIMENSIONS GOVERN, LARGE SCALE DETAILS GOVERN OVER
SMALL SCALE DETAILS. THE CONTRACTOR SHALL NOTIFY THE CONTRACTING OFFICER IN
WRITING OF ANY DIFFERING CONDITIONS BEFORE COMMENCEMENT OF WORK.
10. THE CONTRACTOR SHALL PERFORM WORK IN ACCORDANCE WITH APPLICABLE CODES,
ORDINANCES AND REGULATORY AGENCIES AND SHALL OBTAIN NECESSARY BUILDING AND
FIRE PERMITS FROM ALL AUTHORITIES HAVING JURISDICTION.
11. PIPE DUCTS AND BUS DUCTS THAT PENETRATE FLOOR SLABS OR WALL PARTITIONS SHALL
BE INSTALLED IN A MANNER THAT WILL PRESERVE THE MOISTURE RESISTIVENESS, FIRE
RATING, AND STRUCTURAL INTEGRITY OF THE BUILDING.
12. THE CONTRACTOR SHALL PLAN HIS/HER WORK TO PROVIDE ADEQUATE PROTECTION FOR
PERSONS AND PROPERTY, AND EXECUTE THE WORK IN SUCH A MANNER TO AVOID ANY
HAZARD TO PERSONS AND PROPERTY AS NECESSARY.
13. THE CONTRACTOR SHALL COORDINATE THE PHASING OF THE WORK TO BE PERFORMED IN
OR ABOUT EXISTING FACILITIES, IF APPLICABLE, WITH THE OWNER'S REPRESENTATIVE
PRIOR TO…