DESIGN NEW HVAC SYSTEM AND ASSOCIATED UPGRADES

PHASE 3A

STUTTGART, ARKANSAS

SHEET NO.

INDEX OF DRAWINGS

SHEET TITLE

USDA

NO SCALEVICINITY MAP

NORTH

ARKANSAS

PROJECT

LOCATION

USDA AGRICULTURAL RESEARCH SERVICE

DALE BUMPERS NATIONAL RICE RESEARCH CENTER

(DBNRRC)

G-001 G-002

AD111

A-101 M-001 M-002

MD101

MD102

MD103

MH101

MH102

MP101

M-501 M-502 M-601 M-701 E-001

ED102

ED111

E-101 E-102 E-111 E-500 E-600

PHASE 3A TITLE SHEET

PHASING PLAN

PHASE 3A REFLECTED CEILING PLAN: DEMO

PHASE 3A REFLECTED CEILING PLAN

PHASE 3A MECHANICAL GENERAL NOTES

PHASE 3A MECHANICAL LEGEND AND ABBREVIATIONS

PHASE 3A MECHANICAL HVAC DEMOLITION PLAN

PHASE 3A MECHANICAL PIPING DEMOLITION PAN

PHASE 3A MECHANICAL ROOF DEMOLITION PLAN

PHASE 3A MECHANICAL HVAC NEW WORK PLAN

PHASE 3A MECHANICAL ROOF NEW WORK PLAN

PHASE 3A MECHANICAL PIPING NEW WORK PLAN

PHASE 3A MECHANICAL DETAILS

PHASE 3A MECHANICAL DETAILS

PHASE 3A MECHANICAL SCHEDULES

PHASE 3A VAV BOX W/ REHEAT CONTROLS

PHASE 3A ELECTRICAL LEGEND AND NOTES

PHASE 3A ELECTRICAL ROOF DEMOLITION PLAN

PHASE 3A LIGHTING DEMOLITION PLAN

PHASE 3A ELECTRICAL POWER PLAN

PHASE 3A ELECTRICAL ROOF NEW WORK PLAN

PHASE 3A ELECTRICAL LIGHTING PLAN

PHASE 3A LIGHTING DETAILS AND SCHEDULES

PHASE 3A SCHEDULES

Dylan Mitchell 5923 sam

PHASE 1A, 1B AND 1C (NOT IN CONTRACT):

PHASE 2A (NOT IN CONTRACT)

PHASE 2B (NOT IN CONTRACT)

PHASE 3A:

PHASE 3B (NOT IN CONTRACT)

HEADHOUSE (NOT IN CONTRACT)

PHASING LEGEND

A. ALL NON-WORK AREAS IN THE BUILDING WILL REMAIN OCCUPIED AND OPERATIONAL

DURING THE WORK. USDA WILL VACATE AREAS OF THE BUILDING WHERE WORK IS

BEING PERFORMED. THE CONTRACTOR SHALL COORDINATE HIS/HER WORK

ACTIVITIES WITH THE CONTRACTING OFFICER TO AVOID CONFLICTS WITH FACILITY

OPERATIONS. THE CONTRACTOR SHALL ERECT BARRIERS AND EMPLOY NECESSARY

MEASURES TO PROTECT PERSONNEL IN THE AREA FROM INJURY.

B. COVER AND PROTECT ALL FURNISHINGS AND EQUIPMENT REMAINING IN THE

LABORATORIES AND OFFICE SPACES.

C. THE CONTRACTOR SHALL PROVIDE BARRIERS AND SIGNAGE TO SECURE THE WORK

AREAS, TO DIRECT PERSONNEL IN WAYFINDING, AND TO ENSURE THE SAFETY OF

BUILDING OCCUPANTS AND VISITORS. THE CONTRACTOR SHALL PROVIDE A WORK

PLAN BEFORE BEGINNING THE WORK EXPLAINING AND ILLUSTRATING THE MEANS TO

BE IMPLEMENTED TO ALLOW THE BUILDING TO REMAIN OCCUPIED AND OPERATIONAL

DURING THE WORK. THE CONTRACTOR SHALL FIELD VERIFY ALL DIMENSION AND

CONDITIONS BEFORE BEGINNING WORK.

D. CONTRACTOR SHALL COORDINATE STAGING AREAS WITH USDA PERSONNEL.

GENERAL NOTES

PHASE 3A

AREA OF

WORK

110A

114 110

112 111

L-21

L-1B

L-21B

L-1A

L-1C

L-1

L-18

125 126 129 L-20

L-22

L-17B

L-16

L-1D

L-19

L-17

L-21C

L-21E L-21D

L-21A

SCALE:

PHASE 3A

REFLECTED CEILING PLAN: DEMO

3/16" = 1'-0"

AD111

0 4' 8' 16'

SCALE: 3/16"= 1'-0"

2'

KEY PLAN

N.T.S.

AREA OF

WORK

PHASE 3A

LEGEND

DEMOLISH 24 x 24" SUSPENDED

ACOUSTICAL CEILING SYSTEM

COMPLETE. CONTRACTORS

OPTION TO RETAIN SUSPENSION

WIRES

DEMOLISH SUSPENDED GYPSUM

BOARD CEILING SYSTEM

COMPLETE. CONTRACTORS

OPTION TO RETAIN HANGER

WIRES

LIGHT FIXTURES. SEE

ELECTRICAL DRAWINGS FOR

ADDITIONAL WORK.

HVAC DIFFUSERS. SEE

MECHANICAL DRAWINGS FOR

ADDITIONAL WORK.

NO WORK THIS AREA

DEMOLISH 24 x 48" SUSPENDED

ACOUSTICAL CEILING SYSTEM

COMPLETE. CONTRACTORS

OPTION TO RETAIN SUSPENSION

WIRES

5923 robin seal

114 110

109 108

112 111

L-21

L-1B

L-21B

L-1A L-1C

L-1

L-18

125 126 129 L-20

L-22

L-17B

L-16

L-1D

L-19

L-21C

L-21E

L-21D

L-21A

SCALE:

PHASE 3A

REFLECTED CEILING PLAN

3/16" = 1'-0"

A-101

0 4' 8' 16'

SCALE: 3/16"= 1'-0"

2'

KEY PLAN

N.T.S.

LEGEND

PROVIDE NEW 24 x 24"

SUSPENDED ACOUSTICAL

CEILING SYSTEM AS SPECIFIED.

CONTRACTORS OPTION TO

RETAIN SUSPENSION WIRES

PROVIDE NEW SUSPENDED

GYPSUM BOARD CEILING

SYSTEM AS SPECIFIED.

CONTRACTORS OPTION TO

RETAIN HANGER WIRES

LIGHT FIXTURES. SEE

ELECTRICAL DRAWINGS FOR

ADDITIONAL WORK.

HVAC DIFFUSERS. SEE

MECHANICAL DRAWINGS FOR

ADDITIONAL WORK.

AREA OF

WORK

PHASE 3A

NO WORK THIS AREA

5923 robin seal

1. INSTALLATION OF HVAC WORK SHALL BE COORDINATED WITH OTHER TRADES BEFORE ANY WORK IS PERFORMED. DUCTWORK SHOWN ON PLANS IS SCHEMATIC. DUCTWORK SHALL BE INSTALLED TIGHT TO STRUCTURE. PROVIDE ALL TRANSITIONS, ELBOWS, ETC. REQUIRED TO AVOID CONFLICTS & MAXIMIZE CEILING HEIGHTS. EQUIPMENT, PIPING OR DUCTWORK INTERFERING WITH OTHER TRADES SHALL BE

RELOCATED AS REQUIRED AT NO ADDITIONAL COST TO THE OWNER.

2. COORDINATE MECHANICAL AND ELECTRICAL SUCH THAT MECHANICAL PIPING, DUCTWORK AND EQUIPMENT

IS NOT LOCATED OVER OR ABOVE ANY ELECTRICAL, COMMUNICATIONS, OR DATA EQUIPMENT.

3. AT START OF CONSTRUCTION, PREPARE TYPED LISTS OF EQUIPMENT THAT ARE SUPPLIED REQUIRING ELECTRICAL WORK, AND SEND LISTS TO THE ELECTRICAL CONTRACTOR FOR REVIEW AND COORDINATION.

4. EQUIPMENT SHALL BE INSTALLED IN ACCORDANCE WITH MANUFACTURER'S APPROVED CLEARANCE AND

INTERNATIONAL BUILDING CODE / INTERNATIONAL MECHANICAL CODE.

5. INSTALLATION OF EQUIPMENT SHALL PERMIT ACCESSIBILITY FOR SERVICE AND/OR REPLACEMENT WITHOUT NECESSITATING REMOVAL OR MODIFICATION TO OTHER PIPING, WIRING, OR EQUIPMENT.

6. CEILING-MOUNTED EQUIPMENT SHALL BE INSTALLED IN SUCH A MANNER THAT LIGHTS, PIPING, DUCTWORK, ETC., DO NOT BLOCK ACCESS TO EQUIPMENT AND RELATED ACCESSORIES.

7. COORDINATE WALL, FLOOR, AND ROOF PENETRATIONS WITH THE CONTRACTOR.

8. SUPPLEMENTAL STEEL MEMBERS REQUIRED TO SUPPORT HVAC EQUIPMENT FROM MAIN STRUCTURE

SHALL BE PROVIDED BY THE HVAC CONTRACTOR UNLESS SPECIFICALLY NOTED OTHERWISE.

9. DUCTWORK AIR DISTRIBUTION SYSTEMS SHALL BE INSTALLED IN ACCORDANCE WITH SMACNA STANDARDS

AND THE PRESSURE CLASSIFICATION OF EACH INDIVIDUAL DUCTWORK SYSTEM.

10. VOLUME DAMPERS SHALL BE PROVIDED AT EACH MAIN BRANCH TAKE-OFF, EACH TAKEOFF TO DIFFUSERS/GRILLS/REGISTERS, AND OTHER LOCATIONS WHERE REQUIRED TO PROPERLY BALANCE THE

SYSTEM. ALL REQUIRED VOLUME DAMPERS MAY NOT BE SHOWN ON PLANS.

11. INSTRUMENT TEST HOLES SHALL BE PROVIDED IN AIR DISTRIBUTION SYSTEMS WHEREVER VOLUME DAMPERS ARE INSTALLED. TEST HOLES SHALL BE SEALED WITH RUBBER OR PLASTIC TEST HOLE PLUGS.

12. SQUARE ELBOWS SHALL ONLY BE USED WHERE SPACE LIMITATIONS PREVENT USE OF 1.5 RADIUS ELBOW AND ONLY UPON APPROVAL OF CONTRACTING OFFICER. PROVIDE TURNING VANES IN ALL SQUARE ELBOWS GREATER THAN OR EQUAL TO 45°. TURNING VANES SHALL BE SINGLE THICKNESS TYPE WITHOUT RAILING

EDGE. TURNING VANES LONGER THAN 36 INCHES SHALL BE DOUBLE THICKNESS TYPE.

13. DUCTWORK RUNOUTS TO AIR DISTRIBUTION DEVICES SHALL BE SAME DIAMETER AS AIR DISTRIBUTION

DEVICE INLET CONNECTION UNLESS OTHERWISE NOTED ON THE DRAWINGS.

14. FLEXIBLE DUCTWORK RUNOUTS FROM BRANCH DUCTS TO AIR DISTRIBUTION DEVICES SHALL NOT EXCEED 5 FEET IN LENGTH. BENDS IN FLEXIBLE DUCTWORK SHALL NOT EXCEED A MAXIMUM OF 45 DEGREE CHANGE OF DIRECTION AND SHALL BE SUPPORTED SUCH THAT THE BEND RADIUS IS NOT RESTRICTIVE TO AIR FLOW THROUGH THE DUCT. FLEXIBLE DUCTWORK SHALL NOT BE CRUSHED OR DISTORTED IN ITS FINAL

CONFIGURATION.

15. PROVIDE SHEETMETAL TRANSITIONS AT AIR HANDLING UNITS, HEAT PUMP UNITS, FANS, AND OTHER SIMILAR HVAC EQUIPMENT. TRANSITION TO FULL SIZE OF CONNECTION ON UNIT. FLEXIBLE DUCT

CONNECTORS SHALL BE USED ON FINAL CONNECTION TO AIR HANDLING EQUIPMENT.

16. TRANSFER DUCTS SHALL BE SIZED FOR MAX VELOCITY ALLOWED OF 500 FPM. OPEN-ENDED TRANSFER

DUCTS SHALL HAVE 90° ELBOW FOR SOUND ATTENUATION.

17. LOUVERED SUPPLY AIR DIFFUSERS SHALL BE 4-WAY FLOW UNLESS OTHERWISE SHOWN BY FLOW ARROWS ON THE DRAWINGS. LINEAR DIFFUSERS SHALL BE ADJUSTABLE 2-WAY FLOW. PROVIDE BATT INSULATION

ON DIFFUSER AND GRILLES THAT ARE EXPOSED TO CEILING PLENUM.

18. EXACT LOCATION OF CEILING DIFFUSERS, GRILLES AND REGISTERS SHALL BE DETERMINED BY

ARCHITECTURAL REFLECTED CEILING PLAN.

19. LOUVER PLENUMS SHALL BE PITCHED DOWN TOWARD THE BOTTOM OF THE LOUVER.

20. PROVIDE ACCESS PANELS TO ACCESS DAMPERS, EQUIPMENT, AND VALVES LOCATED ABOVE HARD

CEILINGS OR IN WALLS. ACTUAL LOCATIONS SHALL BE FIELD DETERMINED.

21. EXACT LOCATIONS OF THERMOSTATS, CO2 SENSORS, AND EMCS SENSORS SHALL BE COORDINATED WITH

FINAL LOCATIONS OF WALL-MOUNTED ARCHITECTURAL AND ELECTRICAL EQUIPMENT. MOUNT

THERMOSTATS AND CO2 SENSORS MINIMUM 48" AFF.

22. AIR HANDLING UNITS SERVING OCCUPIED AREAS SHALL HAVE MINIMUM MERV 8 PRE-FILTERS AND MERV 13 FINAL FILTERS. UNITS NOT SERVING OCCUPIED ZONES SHALL HAVE MINIMUM MERV 8 FILTER. FILTERS SHALL BE INDUSTRY STANDARD SIZE. FILTERS SHALL NOT CREATE PRESSURE DROP EXCEEDING 10% OF

EXTERNAL STATIC PRESSURE (ESP) CAPACITY LISTED IN EQUIPMENT SCHEDULE.

GENERAL MECHANICAL NOTES:

23. SUPPLY, RETURN, AND OUTDOOR AIR DUCTWORK SHALL BE INSULATED TO MEET OR EXCEED ASHRAE 189.1.

EXTERIOR SUPPLY AND RETURN AIR DUCTWORK SHALL BE PROVIDED WITH WEATHER-PROOF COVER.

24. PROVIDE SUPPORTS FOR PIPING AND DUCTWORK IN ACCORDANCE WITH SPECIFICATIONS.

25. PROVIDE A MANUFACTURED EXPANSION DEVICE OR FABRICATED EXPANSION LOOP ON ALL DUCTWORK AND

PIPING SYSTEMS CROSSING BUILDING EXPANSION JOINTS.

26. PROVIDE SHUT-OFF VALVES AND FLEXIBLE CONNECTIONS AT PIPE CONNECTIONS TO HVAC EQUIPMENT.

27. FOR WALL, FLOOR, AND SLAB PENETRATIONS, SEAL AND PATCH ALL UNUSED PENETRATION SPACE TO MATCH EXISTING CONSTRUCTION/FINISH OR AS SHOWN ON MECHANICAL DETAILS SHEET. PROVIDE FIRE STOPPING FOR

RATED WALLS AND FLOORS.

28. INSTALL EXPOSED CONTROL WIRING IN CONDUIT. SEE DIVISION 26 SPECIFICATIONS FOR REQUIREMENTS.

29. MANUFACTURER NAME AND MODEL NUMBERS ARE BASIS OF DESIGN AND ARE SHOWN FOR INFORMATION ONLY.

REFER TO SPECIFICATIONS FOR COMPLETE REQUIREMENTS.

30. SPECIFICATIONS TAKE PRECEDENCE OVER DRAWINGS. HOWEVER, ITEMS SHOWN ON DRAWING BUT NOT IN THE SPECIFICATIONS ARE REQUIRED WITHIN THE PROJECT SCOPE. IN ADDITION, SPECIFIC ITEMS SHOWN ON THE DRAWINGS TAKE PRECEDENCE OVER SPECIFICATIONS IN CASES WHERE THE SPECIFICATION HAS OPTIONS.

31. ALL EQUIPMENT SHALL BE INSTALLED IN ACCORDANCE WITH MANUFACTURER'S APPROVED PUBLISHED

LITERATURE.

32. DUCT SIZES SHOWN ARE INSIDE CLEAR DIMENSIONS.

33. EXPOSED DUCTWORK, WITH THE EXCEPTION OF DUCTWORK IN MECHANICAL ROOMS SHALL BE DOUBLE-WALL, DUCTWORK WITH COATING.

34. IF SUSPECT ASBESTOS IS FOUND, STOP WORK IMMEDIATELY AND NOTIFY OWNER AND GENERAL CONTRACTOR.

OWNER IS RESPONSIBLE FOR ABATEMENT OF UNFORESEEN ASBESTOS.

35. NOT ALL MECHANICAL ABBREVIATIONS SHOWN WILL BE USED FOR THIS PROJECT.

36. ALL THERMOSTATS SHALL BE WALL MOUNTED AND WIRED.

37. ALL EQUIPMENT INSTALLED IN THIS PROJECT SHALL COMPLY WITH THE "BUY AMERICAN ACT". BASIS OF DESIGN SHOWN ON SCHEDULES IS TO ESTABLISH A STANDARD OF QUALITY, NOT TO LIMIT COMPETITION. EQUIVALENT

EQUIPMENT FROM ANOTHER MANUFACTURER IS ACCEPTABLE.

38. ALL COMMUNICATIONS PREMISE WIRING AND CABLE TRAYS THROUGHOUT THE FACILITY MUST BE PROTECTED AND UNINTERRUPTED DURING CONSTRUCTION. THIS INCLUDES ELECTRICAL POWER TO COMMUNICATIONS

EQUIPMENT. NO COMMUNICATIONS OUTAGES MUST TAKE PLACE WITHOUT THE CONSENT OF THE

CONTRACTING OFFICER.

39. CONTRACTOR MUST DEMOLISH ALL THERMOSTATS AND WIRING ASSOCIATED WITH THE HVAC SYSTEM TO BE

DEMOLISHED.

40. CONTROLS CONTRACTOR SHALL PROVIDE ALL LOW VOLTAGE DEVICES, CONDUCTORS, AND PATHWAYS IN

ACCORDANCE WITH THE REQUIREMENTS OF 26 20 00.

41. AFTER THE TESTING AND BALANCING OF THE AIR TERMINALS INCLUDED IN THIS PHASE IS COMPLETE, THE EXISTING AHU, DOAS, HEATING WATER, AND CHILLED WATER SYSTEM ASSOCIATED WITH AND/OR AFFECTED BY THE WORK IN THIS PHASE MUST BE ADJUSTED AND BALANCED TO ACCOMMODATE FOR THE HVAC ALTERATIONS

THAT RESULT FROM THE WORK DONE IN THIS PHASE.

ABBREVIATIONS:

@ AT

& AND

AHU AIR HANDLING UNIT

ARCH ARCHITECT, ARCHITECTURAL

AS AIR SEPARATOR

ASHRAE AMERICAN SOCIETY OF HEATING, REFRIGERATING,

AND AIR CONDITIONING ENGINEERS

ASTM AMERICAN SOCIETY FOR TESTING AND

MATERIALS

BDD BACKDRAFT DAMPER

BLDG BUILDING

BTU, BTUH BRITISH THERMAL UNITS, BTUs PER HOUR

CD CONDENSATE DRAIN

CFM CUBIC FEET PER MINUTE

CHW CHILLED WATER

CHWR CHILLED WATER RETURN

CHWS CHILLED WATER SUPPLY

CLG COOLING

CMU CONCRETE MASONRY UNIT

CO CLEANOUT

CO2 CARBON DIOXIDE

CONC CONCRETE

COND STEAM CONDENSATE

CONN CONNECT, CONNECTING, CONNECTION

CONT CONTINUED

CONV STEAM CONVERTER

COP COEFFICIENT OF PERFORMANCE

COR CONTRACTING OFFICER'S (OWNER'S)

REPRESENTATIVE

CT COOLING TOWER

CU CONDENSING UNIT

CWR CONDENSER WATER RETURN

CWS CONDENSER WATER SUPPLY

D DEPTH

DB, Tdb DRY BULB (TEMPERATURE) dBA DECIBELS

DCW DOMESTIC COLD WATER

DDC DIRECT DIGITAL CONTROLS

DEG. F (°F) DEGREES FAHRENHEIT

DF DESTRATIFICATION FAN

DFCU DUCTLESS FAN COIL UNIT

DH DEHUMIDIFIER

DIA, Ø DIAMETER

DIV DIVISION

DN DOWN

DP, PD DIFFERENTIAL PRESSURE, PRESSURE DROP

DSCU DUCTLESS SPLIT CONDENSING UNIT

DSHP DUCTLESS SPLIT HEAT PUMP

DWG DRAWING

DX DIRECT EXPANSION

EA EXHAUST AIR

EAG EXHAUST AIR GRILLE

EAT ENTERING AIR TEMPERATURE

EER ENERGY EFFICIENCY RATIO

EF EXHAUST FAN

EFF EFFICIENCY

ELEC ELECTRICAL

EMCS ENERGY MONITORING AND CONTROLS SYSTEM

ERU ENERGY RECOVERY UNIT

ERV ENERGY RECOVERY VENTILATOR

ESP EXTERNAL STATIC PRESSURE

ET EXPANSION TANK

EUH ELECTRIC UNIT HEATER

EWT ENTERING WATER TEMPERATURE

EXT EXTERIOR

EXH EXHAUST

EXIST. EXISTING

FCU FAN COIL UNIT

FD FIRE DAMPER

FFE FINISHED FLOOR ELEVATION

FLA FULL LOAD AMPS

FOB FLAT ON BOTTOM

FOT FLAT ON TOP

FPM FEET PER MINUTE

FSD FIRE SMOKE DAMPER

FT FOOT, FEET

FT WG FEET WATER GAUGE

FV FLUE VENT

GA GAGE

GC GENERAL CONTRACTOR

GPM GALLONS PER MINUTE

GWH GAS WATER HEATER

H HEIGHT

HPS HIGH PRESSURE STEAM

HR HOUR

HTG HEATING

HTR HEATER

HTW HEATING WATER

HWR HEATING WATER RETURN

HWS HEATING WATER SUPPLY

HVAC HEATING, VENTILATING, AND AIR CONDITIONING

HX HEAT EXCHANGER

HZ HERTZ

IMC INTERNATIONAL MECHANICAL CODE

IN INCH, INCHES

IN WC INCHES WATER COLUMN

IN WG INCHES WATER GAUGE

IPLV INTEGRATED PART LOAD VALUE

KW KILOWATTS

L LENGTH, LOUVER (WALL)

LAT LEAVING AIR TEMPERATURE

LBD LINEAR BAR DIFFUSER

LBS POUNDS

LWT LEAVING WATER TEMPERATURE

MAX MAXIMUM

MBH 1000 BRITISH THERMAL UNITS

MCA MINIMUM CIRCUIT AMPACITY

MECH MECHANICAL

MERV MINIMUM EFFICIENCY REPORTING VALUE

MFCR, MFCG MANUFACTURER, MANUFACTURING

MIN MINIMUM

MOCP, MOP MAXIMUM OVER CURRENT PROTECTION

MTWR MEDIUM TEMPERATURE WATER RETURN

MTWS MEDIUM TEMPERATURE WATER SUPPLY

MXB MIXING BOX

N.C. NORMALLY CLOSED

NC NOISE CRITERIA

NG NATURAL GAS

NO. NUMBER

N.O. NORMALLY OPEN

NTS NOT TO SCALE

OA OUTSIDE AIR

OD OUTSIDE DAMPER

PCHWR PLANT CHILLED WATER RETURN

PCHWS PLANT CHILLED WATER SUPPLY

PD PRESSURE DROP

PH PHASE

PLBG PLUMBING

PMTWR PLANT MEDIUM TEMPERATURE WATER RETURN

PMTWS PLANT MEDIUM TEMPERATURE WATER SUPPLY

PPM PARTS PER MILLION

PRV PRESSURE RELIEF VALVE

PSI POUNDS PER SQUARE INCH

QTY QUANTITY

RA RETURN AIR

RAG RETURN AIR GRILLE

RH RELATIVE HUMIDITY, ROOF HOOD

RM ROOM

RPM REVOLUTIONS PER MINUTE

SA SUPPLY AIR

SAD SUPPLY AIR DIFFUSER

SAG SUPPLY AIR GRILLE

SD SMOKE DAMPER, SMOKE DETECTOR

SEER SEASONAL ENERGY EFFICIENCY RATIO

SF SUPPLY FAN

SMACNA SHEET METAL AND AIR CONDITIONING

CONTRACTOR'S NATIONAL ASSOCIATION

SP STATIC PRESSURE

STM STEAM

SS STAINLESS STEEL

TEMP TEMPERATURE

TSTAT THERMOSTAT

TYP TYPICAL

UH UNIT HEATER

UL UNDERWRITER'S LABORATORY

UMCS UTILITY MONITORING AND CONTROL SYSTEM

V VOLTAGE, VOLTS

VAV VARIABLE AIR VOLUME

VD VOLUME DAMPER

VFD VARIABLE FREQUENCY DRIVE

VRF VARIABLE REFRIGERANT FLOW

WB, Twb WET BULB (TEMPERATURE)

MISCELLANEOUS LEGEND:

AIR DISTRIBUTION DEVICE TAGS

DIFFUSER SUB-TYPE

A

400 AIRFLOW (CFM),

"PLENUM", OR

"TRANSFER"

NORTH ARROW

A

J

SD

SP

F

CO

DUCT SMOKE DETECTOR

CARBON MONOXIDE SENSOR

OVAL OR FLAT OVAL

CONTROL WIRING

STATIC PRESSURE SENSOR

ROUND OR DIAMETER

FIRESTAT

TEMPERATURE SENSORT

120 VOLT STAND BY POWER JUNCTION

BOX PROVIDED BY THE ELECTRICAL

CONTRACTOR. JUNCTION BOX IS

DEDICATED FOR USE BY THE CONTROLS

CONTRACTOR.

VARIABLE FREQUENCY DRIVEVFD

FLOW ARROW

RETURN AIR GRILLE

SUPPLY AIR DIFFUSER

FLOW ARROWS INDICATE AIR PATTERN.

NO FLOW ARROWS SHOWN INDICATES

4-WAY PATTERN.

EXHAUST AIR GRILLE

SERVICE CLEARANCE

T THERMOSTAT

H HUMIDISTAT

$ START/ STOP SWITCH

TH THERMOSTAT/ HUMIDISTAT

HUMIDITY SENSORH

DIFFUSER TYPE

XXX-

DP DIFFERENTIAL PRESSURE SENSOR

C CARBON DIOXIDE SENSOR

AQ AIR QUALITY SENSOR

POINT OF RECONNECTION

OR EXTENT OF DEMOLITION

ELEVATION CROSS REFERENCEX

XXXXX

PIPING LEGEND:

CHILLED WATER SUPPLY

(CHWS)

HEATING WATER SUPPLY

(HWS)

HEATING WATER RETURN

(HWR)

HIGH PRESSURE STEAM SUPPLY

(HPS)

STEAM CONDENSATE RETURN

(COND)

EXISTING PIPING TO REMAIN

(EXIST.)

CONDENSATE DRAIN

(CD)

FLEXIBLE CONNECTION

THERMOMETER

PRESSURE REDUCING VALVE

MANUAL AIR VENT

PRESSURE/TEMPERATURE TAP WITH

BALL VALVE

PRESSURE SWITCH

PLUG VALVE

FLOW SWITCH

T&P RELIEF VALVE

AUTOMATIC AIR VENT

PRESSURE GAUGE WITH GAUGE COCK

PS

FS

BUTTERFLY VALVE

STRAINER WITH BLOWDOWN VALVE,

CAP, AND CHAIN

FLOW MEASURING/BALANCING/SHUT-

OFF VALVE

GATE VALVE

CHECK VALVE

BALL VALVE

CONCENTRIC REDUCER

DIRECTION OF FLOW

ECCENTRIC REDUCER

PIPE FLANGE

PIPE CAP

PIPE GUIDE (PG)

PIPE ANCHOR (PA) X

UNION

TEE OUTLET UP

BRANCH BOTTOM CONNECTION

BRANCH TOP CONNECTION

ELBOW UP

ELBOW DOWN

RISE OR DROP

TEE OUTLET DOWN

DUCTWORK LEGEND:

M

FIRE DAMPER

EXHAUST AIR DUCT DOWN

EXHAUST AIR DUCT UP

RETURN AIR DUCT DOWN

30"x14"

SQUARE TO ROUND DUCT BRANCH TAKE-OFF

WITH 45 DEGREE BRANCH INLET

ROUND DUCT BRANCH TAKE-OFF FROM

RECTANGULAR MAIN WITH CONICAL TAP

FLEXIBLE DUCT CONNECTION

DUCT SIZE TRANSITION

RECTANGULAR DUCT BRANCH TAKE-OFF

WITH 45 DEGREE BRANCH INLET

90 DEGREE DUCT ELBOW WITH TURNING VANES

24"Ø ROUND DUCT. DIAMETER INDICATED IN INCHES.

IN-LINE 90 DEGREE RISE/DROP IN

SUPPLY DUCT

FD

SD

DAMPER TYPE:

M - MOTORIZED DAMPER (ELECTRIC)

VD

SMOKE DAMPER

VOLUME/BALANCING DAMPER

(LABEL MAY BE OMITTED)

BD

BACKDRAFT DAMPER

(COUNTER-BALANCED UNLESS

OTHERWISE NOTED)

RADIUS DUCT ELBOW - ROUND OR

RECTANGULAR (MIN. 1.5 RADIUS UNLESS

OTHERWISE NOTED)

RECTANGULAR DUCT. SIZE INDICATED IN

INCHES, FIRST NUMBER IS SIDE SHOWN.

DASHED LINES INDICATE ACOUSTICAL LINER

FSD

COMBINATION

FIRE/SMOKE DAMPER

IN-LINE 90 DEGREE RISE/DROP IN

RETURN DUCT

DUCT SIZE TRANSITION RECTANGULAR TO

ROUND

30"x14" FLAT OVAL DUCT. SIZE INDICATED IN INCHES, FIRST NUMBER IS SIDE SHOWN

RETURN AIR DUCT UP

SUPPLY OR OUTSIDE AIR DUCT DOWN

SUPPLY OR OUTSIDE AIR DUCT UP

IN-LINE 90 DEGREE RISE/DROP IN

EXHAUST DUCT

SD

DUCT MOUNTED SMOKE DETECTOR

GLOBE VALVE

PLAN

NORTH

EXISTING PIPING TO BE

DEMOLISHED

22x10 x1

24"Ø x1 x1 x1 x1 x1 x1

14"Ø

16x12 x1

12x10

8" Ø

10"Ø

10x8 14 x1

12x10

8" Ø

10x610x6 x8 x1

10x6 14x10

12"Ø 10 "Ø

"Ø

10"Ø 14x10 x1

10x10 10x10 14x10 x6 x6

20x10 x1

18x10

8" Ø

5" Ø 10x10

5" Ø

10"Ø

"Ø

10x10

10"Ø

"Ø x1

014x6

8" Ø

10x10 8"Ø

10x8

8" Ø

8x10 x8

12"Ø 6"Ø14x10

14x10 6"

Ø

6"Ø14x10

10x8 x1

10x8

14x10 6"Ø

16"Ø

10x10

8" Ø

8" Ø x1

16x10

16x1012x10

10x6

"Ø x8 x8 x1 x1 x6

10x8 x1

"Ø14x10 6"Ø

10x8

14x10 6"Ø

10x8

14x10 6"Ø

6"Ø 10x10 x1 x8 x1

30x16 32x20 x1

5"Ø

5" Ø

5"Ø

5" Ø

10x10

10"Ø

10x10

10x6 x8

12x8

10x8 10x8 x1

8"Ø

5"Ø

"Ø x6 x810x6 10x6

10x610x6

5" Ø

10x10

48x20

16"Ø14"Ø x1 x1 x1

10x6 10x6

6" Ø

22x6

10x6

SCALE:

PHASE 3A MECHANICAL

HVAC DEMOLITION PLAN

3/16" = 1'-0"

MD101

0 4' 8' 16'

SCALE: 3/16"= 1'-0"

2'

EXIST. AIR TERMINAL TO

BE DEMOLISHED (TYP.)

1. EXISTING VAV BOX, DUCTWORK, THERMOSTAT,

AND ALL APPURTENANCES TO BE REMOVED.

2. EXISTING DUCTWORK UP TO AHU-1 IN

MEZZANINE AREA TO BE REMOVED.

3. EXISTING AHU-2 DUCTWORK TO REMAIN IN

PLACE.

4. EXISTING 10" X 10" EXHAUST DUCTWORK UP TO

EF-3 TO BE DEMOLISHED.

KEYED NOTES

LEGEND:

EXISTING EQUIPTMENT TO

BE DEMOLISHED

EXISTING DUCTWORK TO BE

DEMOLISHED

1 1

1 1

EXISTING DUCTWORK TO BE

REMAIN

EXIST. VAV BOX

TO REMAIN

T

T

T

T

T

T

T T T

T T

T

T

T

T

T

T

T

T

T

T

T

T T

T

T T

T

T

T

SCALE:

PHASE 3A MECHANICAL

PIPING DEMOLITION PLAN

3/16" = 1'-0"

MD102

0 4' 8' 16'

SCALE: 3/16"= 1'-0"

2'

1. REMOVE INSULATION FROM ALL PIPES AND

FITTINGS WITHIN THE AREA OF WORK ON THE

FOLLOWING SYSTEMS: HEATING WATER

RETURN, HEATING WATER SUPPLY.

GENERAL NOTES

2" VTR

COND. RETURN PUMP

2"

2-1/2"

2"

2" 1-1/2"

1-1/2" 1"

1-1/4"

1-1/4"

1"

3/4"

1/2"

1/2"

1/2"

1/2"

1/2"

1/2"

1/2"

1/2"

1/2"

1/2"

1-1/2"

3/4"

3/4"

1/2"

1/2" 3/4"

1/2"

1-1/2"

2"

1-1/2"

1"

1"

1" 1"

2" 1/2" 1/2"

1" 3"

2"

1/2"

1/2"

1/2"

1"

1/2"

1/2"

1/2"

1/2"

1/2"

1-2 1-281-13

1-12

1-34

1-31 1-27

1-30

1-23

1-22

1-21

1-20

1-19

1-18

1-25 1-5

1-6

1-7

1-10

1-3 1-26

1-8

1-29

1-1

1-16

1-9

2-3

1-11

1-24

1-17

1-33

1-14

1-4

1-15

1-32

2-6 2-52-4

1 1

2 2

1 2

EXIST. PIPING

TO REMAIN

(TYP.)

1-36 1

1-35

1. DEMOLISH EXISTING VAV BOX. DEMOLISH PIPING

UP TO EXISTING ISOLATION VALVES.

2. EXISTING VAV TO REMAIN.

KEYED NOTES

x3 x4

SCALE: 1/16" = 1'-0"

48'8' 16' 32'0

PHASE 3A MECHANICAL

ROOF DEMOLITION PLAN

1/16" = 1'-0"

MD103

PLAN

NORTH

1. EXISTING ROOFTOP FAN TO BE DEMOLISHED.

ROOF PENETRATION TO BE TEMPORARILY

CAPPED FOR CONNECTION TO NEW EQUIPMENT.

2. EXISTING AIR HANDLER UNIT TO REMAIN.

KEYED NOTES

EXIST. DUCTWORK

AND PIPING TO

REMAIN (TYP.)

EXIST. EXHAUST

FAN TO REMAIN

(TYP.)

EXIST. EXHAUST

FAN TO REMAIN

(TYP.)

EXIST. EXHAUST

FAN TO REMAIN

(TYP.)

EXIST. DUCTWORK

TO BE DEMOLISHED

14x12

6" Ø

"Ø

6"Ø

8"Ø

12"Ø

6" Ø

6"Ø

36x22

6" Ø

6"Ø

"Ø

6" Ø

"Ø

6"Ø 6"Ø

6"Ø 10"Ø

14"Ø

6" Ø

10"Ø

8" Ø

8"Ø

6" Ø x1

6"Ø 6"Ø

8"Ø

8" Ø

10"Ø

8"Ø 10x10

8" Ø

8" Ø

6" Ø

"Ø

8"Ø

8" Ø

10"Ø

8" Ø

10x10

"Ø

6" Ø

6"Ø x1

10"Ø12x12

"Ø

"Ø

22x16

6" Ø

6" Ø

8"Ø 8"Ø

"Ø

10"Ø

6"Ø10"Ø

"Ø

10"Ø x1

2 10"Ø

10"Ø

6" Ø

6" Ø 8"Ø

6" Ø x1

10x10

8" Ø

8" Ø

16x12

6" Ø

8"Ø

8" Ø

8"Ø6"Ø10"Ø

"Ø

6"Ø10"Ø

10"Ø 6"Ø

8" Ø

6"Ø10"Ø 22x16

"Ø x1

8"Ø8"Ø

8"Ø8"Ø

"Ø

8"Ø8"Ø

6" Ø

6" Ø

"Ø

"Ø

18x14 x1

6" Ø

"Ø

6"Ø10"Ø

6"Ø10"Ø

6"Ø

"Ø 8" Ø

6"Ø10"Ø

"Ø

8"Ø

6" Ø

12"Ø

6" Ø

6"Ø

10"Ø

10"Ø

44x24

"Ø x1

10x10 x1

6"Ø

12x10 x1

8"Ø8"Ø

10"Ø

14x1212x1010"Ø x1 x1

20x1212x12

8" Ø

12"Ø

36x20 x1 x1

"Ø x1

12"Ø12"Ø x1

10"Ø x1

12x1210"Ø

10"Ø x1

10"Ø x1

610"Ø x1

10"Ø

12"Ø

"Ø

10"Ø

8" Ø

SCALE:

PHASE 3A MECHANICAL

HVAC NEW WORK PLAN

3/16" = 1'-0"

MH101

0 4' 8' 16'

SCALE: 3/16"= 1'-0"

2'

KEYED NOTES

1. 14"x12" EXHAUST DUCTWORK DOWN FROM

ROOF.

2. SUPPLY AND RETURN AIR DUCTWORK DOWN

FROM AHU-1 ON MEZZANINE.

3. PROVIDE VAV TERMINAL BOX WITH CONTROLLER

TO INTERFACE WITH BUILDING AUTOMATION

SYSTEM.

VAV

1-2

VAV

1-28VAV

1-13

VAV

1-12

VAV

1-34

VAV

1-31

VAV

1-27

VAV

1-30

VAV

1-23

VAV

1-22

VAV

1-21

VAV

1-20

VAV

1-19

VAV

1-18

VAV

1-25

VAV

1-5

VAV

1-6

VAV

1-7

VAV

1-10

VAV

1-3

VAV

1-26

VAV

1-8

VAV

1-29

VAV

1-1

VAV

1-16

VAV

1-9

EXIST.

VAV 2-3

VAV

1-11

VAV

1-24

VAV

1-17

VAV

1-33

VAV

1-14

VAV

1-4

VAV

1-15

VAV

1-32

VAV

1-36

EAG-3

EAG-3

EAG-2

EAG-1

SAD-1

SAD-2

SAD-1

SAD-3

SAD-2

SAD-3

SAD-1

SAD-1

SAD-1

100 SAD-2

SAD-2

SAD-2

SAD-3

SAD-3

SAD-3

SAD-2

SAD-3

SAD-3

SAD-2

SAD-2

115SAD-2

SAD-2

SAD-3

VAV

1-35 3

SAD-3

SAD-3

SAD-1

SAG-1

SAD-2

SAD-3

SAD-3

SAD-3

SAD-2

SAD-4

SAD-3

SAD-3

RAG-6

RAG-1

RAG-3

RAG-3

RAG-3

RAG-2

RAG-5

RAG-3

RAG-3

RAG-2

RAG-3

RAG-5

RAG-5

RAG-5

RAG-4

RAG-4

RAG-4

RAG-5

RAG-5

RAG-5

RAG-4

RAG-3

RAG-3

RAG-4

RAG-4

RAG-4

DUCTWORK

INSTALLED IN

PHASE 2A

EXIST. DUCTWORK

TO BE REMOVED IN

PHASE 3B

(NOT IN CONTRACT)

RAG-4

RAG-4

SAD-3

SAD-3

SAD-2

RAG-3

SAD-2

RAG-3

RAG-4

SAD-3

RAG-4

SAD-3

RAG-4

SAD-3

RAG-4

SAD-3

SAD-2

SAD-2

SAD-2

SAD-2

SAD-2

EXIST. DUCTWORK

TO BE REMOVED IN

PHASE 3B

(NOT IN CONTRACT)

36x22

44x24

SCALE: 1/16" = 1'-0"

48'8' 16' 32'0

PHASE 3A MECHANICAL

ROOF NEW WORK PLAN

1/16" = 1'-0"

MH102

PLAN

NORTH

KEYED NOTES

1. PROVIDE FAN ON ROOF CURB. MODIFY EXISTING

ROOF CURB FOR INSTALLATION OF FAN AND

FOR WEATHER TIGHT INSTALLATION.

2. CONNECT NEW SUPPLY AND RETURN AIR

DUCTWORK TO EXISTING AHU-1.

3. MODIFY EXISTING STEEL GRATE PENETRATION

FOR DUCTWORK DOWN FROM MEZZANINE AREA.

EF-3 1

EXIST. DUCTWORK

EXIST. AHU-6

EXIST. AHU-5

EXIST. AHU-4

EXIST. AHU-2

EXIST. AHU-1 2

EXIST. EXHAUST FAN

(TYP.)

EXIST. EXHAUST

FAN TO REMAIN

(TYP.)

EXIST. EXHAUST FAN

(TYP.)

PHASE 3A MECHANICAL

MEZZANNE ENLARGED PLAN

1/4" = 1'-0"

MH102

PLAN

NORTH

8'0 2' 4' 12'

SCALE: 1/4"= 1'-0"

GENERAL NOTES

1. PROVIDE ALUMINUM JACKETING ON ALL

DUCTWORK INSULATION IN THE MEZZANINE

AREA.

SCALE:

PHASE 3A MECHANICAL

PIPING NEW WORK PLAN

3/16" = 1'-0"

MP101

0 4' 8' 16'

SCALE: 3/16"= 1'-0"

2'

VAV

1-2

VAV

1-28

VAV

1-13

VAV

1-12

VAV

1-34

VAV

1-31

VAV

1-27

VAV

1-30

VAV

1-23

VAV

1-22

VAV

1-21

VAV

1-20

VAV

1-19

VAV

1-18

VAV

1-25

VAV

1-5

VAV

1-6

VAV

1-7

VAV

1-10

VAV

1-3

VAV

1-26

VAV

1-8

VAV

1-29

VAV

1-1

VAV

1-16

VAV

1-9

EXIST.

VAV 2-3

VAV

1-11

VAV

1-24

VAV

1-17

VAV

1-33

VAV

1-14

VAV

1-4

VAV

1-15

VAV

1-32

EXIST.

VAV 2-6 EXIST.

VAV 2-5

EXIST.

VAV 2-4

KEYED NOTES

1. PROVIDE TERMINAL UNIT. CONNECT TO

EXISTING HTWS AND HTWR BRANCH PIPING.

PROVIDE WITH 3-WAY CONTROL VALVE.

2. HOT TAP PROVIDED AND INSTALLED PIPING

SERVING VAV BOX INTO EXISTING PIPING.1

1 1

VAV

1-36 1

VAV

1-35

EXIST. 2-1/2" HWR

EXIST. 3" HWR

EXIST. 1/2" HWS

EXIST. 3/4" HWS

EXIST. 3/4" HWS

EXIST. 1" HWS

EXIST. 1" HWS

EXIST. 1" HWS

AND HWR

EXIST. 2" HWR

EXIST. 2" HWR

EXIST. 2" HWR

EXIST. 1-1/4" HWS

EXIST. 1" HWS

EXIST. 1-1/4" HWS

EXIST. 1-1/2" HWS

EXIST. 1-1/2" HWS

EXIST. 2" HWR

EXIST. 1-1/2"

HWR

EXIST. 1-1/2" HWR

NEW 1/2" HWS

AND HWR

NEW 1/2" HWS

AND HWR

GENERAL NOTES

1. PROVIDE INSULATION FOR ALL NEW AND

EXISTING HEATING WATER PIPING.

T

T

T

T

T

T

T T T

T T

T

T

T

T

T

T

T

T

T

T

T

T T

T

T

T

T

T

T

T

T

PIPE PENETRATION NOTES:

1. PROVIDE PITCH POCKET CONSTRUCTION, ADDITIONAL FLASHING, OR

WEATHER CAP AS REQUIRED FOR WATERPROOF CONSTRUCTION. DO NOT

MECHANICALLY ATTACH PIPE TO STRUCTURE IN ANY WAY.

2. SPACE BETWEEN PIPE AND SLEEVE SHALL BE FREE OF ANY FOREIGN

MATERIALS.

3. PIPE SHALL NOT CONTACT STRUCTURE AT ANY TIME. WEDGES ARE NOT BE

USED TO MAINTAIN PIPE POSITION.

4. PIPE MUST BE CENTERED IN OPENING.

SCALE:

PIPE PENETRATION DETAIL

NOT TO SCALE

CAULK ALL JOINTS

AND SLEEVE ENDS

WATERTIGHT

PIPING

SCH. 40 PIPE STEEL SLEEVE

FIRE STOP MATERIAL

(FOR FIRE RATED

PARTITIONS)

PIPE INSULATION AS APPLICABLE

PARTITION

TO UNISTRUT P2500 SERIES

PIPE STRAP

(TYP.)

TO UNISTRUT P3400 SERIES PIPE

CLAMPS

(TYP.)

TO UNISTRUT P 1000 12 GA

CHANNEL

(TYP.)

SECURE W/APPROVED ANCHOR TO

MATCH BASE MATERIAL AND LOAD

REQUIREMENTS

INSULATE AS REQD

CONC. OR MASONRY WALL

TO UNISTRUT P 1000 12 GA

CHANNEL

(TYP.)

SECURE W/APPROVED ANCHOR TO

MATCH BASE MATERIAL AND LOAD

REQUIREMENTS

INSULATE AS REQD

CONC OR MASONRY WALL

NOTE:

PROVIDE MIN ANCHOR

SUPPORT SPACING

EVERY 3' VERTICALLY

FOR PIPES < 4"Ø

FOR CONDUIT <

2"Ø

SCALE:

PIPING WALL SUPPORT DETAIL

NOT TO SCALE

EXTERNALLY

INSULATED RIGID GALV

SHT MTL ROUND DUCT

EXTERNALLY

INSULATED

PRIMARY SA

DUCTS

AIR FLOW

EXTERNALLY INSULATED

SUPPLY DUCT

TRANSITION

AS REQUIRED

HEATING WATER REHEAT

COIL

H.P. FLEX

(12" MAX

LENGTH)

CONTROL PANEL. LOCATE FOR OPTIMUM

ACCESS ABOVE CEILING. MAINTAIN MFR'S

RECOMMENDED ACCESS CLEARANCESHIGH EFF TAKE-OFF

FITTING (W/O DAMPER).

AIR FLOW

REDUCING OR ENLARGING

TRANSITION AS REQUIRED

(W/O DAMPER).

EXTERNALLY

INSULATED RIGID GALV

SHT MTL ROUND DUCT

EXTERNALLY

INSULATED GALV

SHT MTL DUCT

SEE BELOW FOR DUCT

CONTINUATION TO BOX

EXTERNALLY

INSULATED GALV

SHT MTL DUCT

ALTERNATE TAKEOFF FOR

BOXES WITH TAKEOFF

FROM END OF RECT DUCT

SCALE:

SINGLE DUCT VAV BOX DETAIL

NOT TO SCALE

SCALE:

CLEVIS HANGER DETAIL

NOT TO SCALE

HEAVY DUTY CLEVIS

HANGER: MSS SP-69 AND

MSS SP-58

PIPE

RIGID INSULATION INSERT

(12" LONG, 180^ ARC)

CLEVIS HANGER WITH

INSULATION SHIELD

INSULATION

BOLT & NUT

SUPPORT NUT

LOCKING NUT

TURNBUCKLE

W/LOCKNUT

HANGER ROD

12" MIN

12" MIN

SINGLE PIPE CLEVIS

HANGER

SCALE:

PIPE HANGER DETAILS

NOT TO SCALE

U-CLAMP OR

CONDUIT

CLAMP

GALVANIZED

IRON TRAPEZE

OR UNISTRUT

16 GAUGE

GALVANIZED

SHEET SHIELD

WRAPPED FULLY

AROUND

INSULATION

INSULATION

PIPE

PROVIDE A SECTION OF

HIGH COMPRESSION

STRENGTH INSULATION AT

EACH HANGER POINT.

INSULATION SHALL BE HALF

ROUND AND EXTEND 2"

BEYOND GALVANIZED

SHIELD EACH WAY.

16 GAUGE

GALVANIZED

SHEET SHIELD

WRAPPED FULLY

AROUND

INSULATION

INSULATION

PIPE

AIR FLOW

KEYED NOTES

INSTALL BALANCING VALVE WITH

MINIMUM OF 3 STRAIGHT PIPE

DIAMETERS UPSTREAM AND 1

STRAIGHT PIPE DIAMETER

DOWNSTREAM.

MAINTAIN 6" MINIMUM CLEARANCE

ABOVE TEST PLUG TO ALLOW

GAUGE TO BE INSERTED. DO NOT

COVER PLUG WITH INSULATION.

INSTALL SWING JOINTS AT COIL

CONNECTIONS.

CONNECT EXISTING BRANCH LINES

FROM TO NEW HEATING WATER

COIL.

PROVIDE COILS WITH INLET

STRAINERS AND CAPPED HOSE

CONNECTION BLOW DOWN VALVES.

INSTALL MANUAL AIR VENTS IN

SUPPLY AND RETURN COIL BRANCH

PIPING AS FOLLOWS:

A) IN PIPING HIGH POINT WHEN

PIPING IS ABOVE MAIN.

B) CLOSE TO COIL WHEN PIPING IS

NOT ABOVE MAIN (SIDE

CONNECTION).

NC

NO

C

HTWS

EXIST. SHUT-OFF

VALVE (TYP.)

BALANCING VALVE

3-WAY CONTROL VALVE

PLUG VALVE, ADJUST

TO EQUAL GPM THRU

COIL AT DESIGN FLOW

TEST PLUG (TYP.)

1/2" PLUGGED DRAIN VALVE COIL

MANUAL AIR VENT,

3/8" BALL VALE (TYP.)

SCALE:

HEATING WATER COIL DETAIL

NOT TO SCALE

CONNECT NEW HTWR TO

EXIST. ISOLATION VALVE

HTWR

CONNECT NEW HTWS TO

EXIST. ISOLATION VALVE

TRANSITION

AS REQUIRED

HARD METAL ROUND DUCT RUN OUT TO

DIFFUSER. SEE PLAN FOR SIZE

SAME SIZE AS GRILLE

NECK

REDUCER IF REQ'D.

BUTTERFLY DAMPER SHALL BE USED

AT THIS LOCATION OR AT

CONNECTION OF RUN-OUT TO MAIN

DUCT.

WORM GEAR DRIVE,

STAINLESS STEEL STRAP

LAY-IN GRILLE SHOWN.

SURFACE MOUNTED SIMILAR

SCALE:

TYPICAL RETURN/EXHAUST GRILLE CONNECTION DETAIL

NOT TO SCALE

AREAS WITH

HARD OR LAY

IN CEILINGS

PROVIDE MANUAL OPPOSED DAMPER IN EACH BRANCH LINE

UNLESS OTHERWISE NOTED ON DRAWINGS. DAMPERS SHALL

BE INSTALLED IN ACCESSIBLE LOCATION NEAR TRUNK DUCT

AND MINIMUM OF 5'-0" FROM ANY AIR INLET OR OUTLET

DEVICE. COORDINATE W/ ACCESS DOORS IN NON-ACCESSIBLE

CEILINGS.

TRUNK

DUCT

OVAL BRANCH

DUCT

45° CLINCH COLLAR PER SMACNA

USE AT ALL BRANCH TAPS

UNLESS

SPLITTER DAMPERS ARE

INDICATED.

BELL-MOUTH

FITTING

NOTE:

DAMPERS SHALL BE PROVIDED IN ALL BRANCH RUN-OUTS TO DIFFUSERS, R.A AND EXHAUST GRILLES, UNLESS SPECIFICALLY NOTED OTHERWISE ON DRAWINGS.

LOCATE DAMPERS SO THEY ARE ACCESSIBLE FROM LAY-IN CEILING OR ACCESS DOORS.

SCALE:

BRANCH DUCT TAP DETAIL

NOT TO SCALE

ROUND

DUCT

DUCT HANGERS, ATTACH TO THE

STRUCTURE ABV.

RECTANGULAR, ROUND,

OR OVAL, DUCT MAIN

WITH EXTERNAL

INSULATION

CEILING DIFFUSER

SCALE:

TYPICAL DIFFUSER CONNECTION DETAIL

NOT TO SCALE

DUCT HANGERS, ATTACH TO THE STRUCTURE ABV.

RECTANGULAR, ROUND, OR OVAL DUCT MAIN WITH

EXTERNAL INSULATION

CEILING DIFFUSER

AREAS WITH

HARD OR LAY

IN CEILINGS

AREAS ABOVE

CEILING (TYP.)

ROUND DUCT WITH EXTERNAL

INSULATION

ATTACH THE FLEXIBLE DUCT TO

THE RIGID DUCT AND THE

DIFFUSER USING TWO (2) BANDS;

ONE FOR THE DUCT AND ONE FOR

THE INSULATION.

U.L. LISTED FLEXIBLE DUCT.

SUPPORT TO PREVENT SAG.

FLEXIBLE DUCT SHALL BE LESS

THAN 5 FT. IN LENGTH AND SHALL

NOT BE USED FOR BENDS

GREATER THAN 45°.

MANUAL DAMPER WITH LOCKING

QUADRANT REGULATOR.

RIGID 90° DUCT ELBOW

WITH EXTERNAL

INSULATION

ATTACH THE FLEXIBLE DUCT TO

THE RIGID DUCT AND THE

DIFFUSER USING TWO (2) BANDS;

ONE FOR THE DUCT AND ONE FOR

THE INSULATION.

U.L. LISTED FLEXIBLE DUCT.

SUPPORT TO PREVENT SAG.

FLEXIBLE DUCT SHALL BE LESS

THAN 5 FT. IN LENGTH AND SHALL

NOT BE USED FOR BENDS

GREATER THAN 45°.

MANUAL DAMPER WITH LOCKING

QUADRANT REGULATOR.

RIGID 90° DUCT ELBOW

WITH EXTERNAL

INSULATION

ROUND DUCT WITH EXTERNAL

INSULATION

SCALE:

TURNING VANE DETAIL

NOT TO SCALE

TURNING VANES, TYPICAL

TURNS 45° OR LARGER

RUNNER

INSTALL VANES

TANGENT TO

AIRSTREAM

DOUBLE SIDED TURNING

VANES REQUIRED WHERE

DUCT HEIGHT IS 24" OR

GREATER.

TOP RUNNER NOT SHOWN FOR

CLARITY.

NUMBER AND CONFIGURATION OF

VANES PER SMACNA STANDARDS.

20% MAXIMUM

AREA REDUCTION

R=H (MIN.)

H

DIM. "D"

ELEVATION

VIEW

PLAN

VIEW

DUCT DIM.

(SEE PLAN)

DUCT "VENTURI"

DEPRESSION DETAIL

NOTE: USE DETAIL

WHERE REQUIRED BY

FIELD CONDITIONS.

H R

TRANS.

DN.

TRANS.

UP

SCALE:

DUCT DEPRESSION FOR STRUCTURAL CONFLICTS DETAIL

NOT TO SCALE

MIN. 2/3

"D"

TYPICAL

OBSTRUCTION TO

DUCT PATH

3"

CABLE WRAP

AROUND BEAM

AND BAR JOIST

CL20

DUCTMATE

CLUTCHERS

WR20 CABLE

DUCT

DUCT

INSULATION

THREADED ROD

DOUBLE NUTUNISTRUT OR

ANGLE

UNISTRUT BAR

BAR JOIST

CL20

DUCTMATE

CLUTCHER OR

EQUAL

DUCTMATE

WR20 CABLE

OR EQUAL

MINIMUM 3/8"

DIA. THREADED

ROD

12 GAUGE

GALVANIZED

STEEL

DUCT

DUCT

INSULATION

DOUBLE NUT

DUCT

EXTERNAL

INSULATION WHERE

SPECIFIED

NOTE: FOR SIZES UP TO 60"

WITH 10' MAXIMUM SPACING.

NOTE: SEMI-CIRCLE

HANGER. 61"-72" DIAMETER

WITH 10' MAXIMUM

SPACING.

END VIEW

ELEVATION VIEW

2"3 1/2" 1"

NOTE: FOR SIZES UP TO 60"

WITH 10' MAXIMUM SPACING.

SINGLE

DOUBLE

SCALE:

DUCT HANGER DETAILS

NOT TO SCALE

NOTE: 10' MAXIMUM SPACING.

97-120

85-96

72-84

61-72

DUCT SIZE (IN.) STRUT SIZE

1 5/8 X 1 5/8 X 12 GA

N/A

N/A

N/A

2 1/2 X 2 1/2 X 1/4

2 X 2 X 1/4

N/A

ANGLE SIZE

3 X 3 X 1/4

3/8

ROD SIZE

3/8

3/8

3/8

R = RADIUS OF CURVE

H = HEIGHT

D = DIAMETER

EXHAUST FAN SCHEDULE

BASIS

OF DESIGN MAX

SONES

VOLTS/

PHASE

OTHER AS

NOTED

OPER.

WEIGHT

(LBS)

MARK LOCATION SERVES

RPMDRIVES.P.CFM

FAN DATA

POWER

HP

CONTROL INTERLOCKS

SWITCH

REMARKS

EF-3 GREENHECK

CUE-140HP-VG

103,104, 105,128ROOF CONSTANTNO 683/416.21,8502 -800 DIRECT

FAN

TYPE

CENTRIFUGAL 115/1

FLA MCA MOP

ELECTRICAL DATA

10 12.5 20

SINGLE DUCT VAV TERMINAL SCHEDULE

BOX TYPEBASIS OF

DESIGN

MFG.

BOX

MIN.

CFM

MFG.

BOX

MAX.

CFM

CFM DATA

INLET

SIZE

REHEAT/HEATING COIL DATA

MBH EWT/LWT °F EAT °F GPM

MAX.

WPD

FT.HD.

MAX

APD

IN.WC

REMARKS

SINGLE DUCT

REHEAT 180/160 55 0.760.02 SEE NOTES

DUCT CONN.

COIL

POSITION

DISCHARGE

SEE NOTESDISCHARGE

SEE NOTESDISCHARGE

SEE NOTESDISCHARGE

COOLING/

HEATING

CFM

MARK

VAV-1-1

VAV-1-2

VAV-1-3

VAV-1-4

VAV-1-5

VAV-1-6

VAV-1-7

LAT °F

114.42

MIN.

COOLING/

HEATING

CFM

SEE NOTESDISCHARGE

VAV-1-8

VAV-1-9

VAV-1-10

VAV-1-11

VAV-1-12

VAV-1-13

VAV-1-14

VAV-1-15

VAV-1-16

VAV-1-17

VAV-1-18

VAV-1-19

VAV-1-20

VAV-1-21

SEE NOTESDISCHARGE

SEE NOTESDISCHARGE

SEE NOTESDISCHARGE

SEE NOTESDISCHARGE

SEE NOTESDISCHARGE6"Ø

SEE NOTESDISCHARGE

SEE NOTESDISCHARGE

SEE NOTESDISCHARGE

SEE NOTESDISCHARGE

SEE NOTESDISCHARGE

SEE NOTESDISCHARGE

SEE NOTESDISCHARGE

SEE NOTESDISCHARGE

SEE NOTESDISCHARGE

SEE NOTESDISCHARGE

SEE NOTESDISCHARGE

108.49

106.65

111.25

98.33

109.94

97.86

92.51

92.24

110.05

0.64

1.0

0.95

1.14

1.15

1.1

TRANE VCWF

SINGLE DUCT

REHEAT

SINGLE DUCT

REHEAT

SINGLE DUCT

REHEAT

SINGLE DUCT

REHEAT

SINGLE DUCT

REHEAT

SINGLE DUCT

REHEAT

SINGLE DUCT

REHEAT

SINGLE DUCT

REHEAT

SINGLE DUCT

REHEAT

SINGLE DUCT

REHEAT

SINGLE DUCT

REHEAT

SINGLE DUCT

REHEAT

SINGLE DUCT

REHEAT

SINGLE DUCT

REHEAT

SINGLE DUCT

REHEAT

SINGLE DUCT

REHEAT

SINGLE DUCT

REHEAT

SINGLE DUCT

REHEAT

SINGLE DUCT

REHEAT

SINGLE DUCT

REHEAT

6.42

7.25

7.56

7.41

7.02

7.86

9.40

9.53

11.39

11.51

17.91

17.87

0.04

0.04

0.03

0.05

0.08

0.26

0.09

0.15

0.13

0.59

1.52

2.08

2.12

0.11

VAV-1-22 SEE NOTESDISCHARGESINGLE DUCT

REHEAT

VAV-1-23 SEE NOTESDISCHARGE107SINGLE DUCT

REHEAT 18.610.31 0.59

VAV-1-24 SEE NOTESDISCHARGE340 104.01135 1.0SINGLE DUCT

REHEAT 18.070.15 0.09

VAV-1-25 SEE NOTESDISCHARGE345 105.65135 1.0SINGLE DUCT

REHEAT 0.33 0.59

VAV-1-26 SEE NOTESDISCHARGE350 105.21135 1.0SINGLE DUCT

REHEAT 19.060.15 0.59

VAV-1-27 SEE NOTESDISCHARGE195 98.8170 0.93SINGLE DUCT

REHEAT 9.260.08

VAV-1-28 SEE NOTESDISCHARGE400 104.35175 1.3SINGLE DUCT

REHEAT 21.410.20 0.14

VAV-1-29 SEE NOTESDISCHARGE430 108.53430 1.0SINGLE DUCT

REHEAT 24.970.11 0.18

VAV-1-30 SEE NOTESDISCHARGE10"Ø575 99.28200 1.0SINGLE DUCT

REHEAT 27.610.17 0.18

VAV-1-31 SEE NOTESDISCHARGE12"Ø900 98.38500 1.75SINGLE DUCT

REHEAT 42.340.20 0.18

VAV-1-32 SEE NOTESDISCHARGE210 97.4180SINGLE DUCT

REHEAT 9.660.09

VAV-1-33 SEE NOTESDISCHARGE195 75SINGLE DUCT

REHEAT 9.260.08

VAV-1-34 SEE NOTESDISCHARGE200 98.3375SINGLE DUCT

REHEAT 9.400.08

VAV-1-35 SEE NOTESDISCHARGE300 125

VAV-1-36 SEE NOTESDISCHARGE6"Ø100 114.24100 6.420.02

1. ACTUATORS FOR VAV BOX AIR-CONTROL DAMPERS ARE TO BE FURNISHED AND INSTALLED BY THE AUTOMATIC TEMPERATURE CONTROLS SUPPLIER.

2. HEATING COIL CONTROL VALVES AND ACTUATORS ARE TO BE FURNISHED AND INSTALLED BY THE AUTOMATIC TEMPERATURE CONTROLS SUPPLIER.

3. MFCR'S INLET SIZE MAY NOT REPRESENT PRIMARY AIR DUCT SIZE. PROVIDE REDUCERS OR ENLARGERS FOR CONNECTING PRIMARY DUCT TO INLET.

4. PROVIDE BOXES WITH CONTROL ENCLOSURES, INTERNALLY LINED CASINGS, HEATING COILS LOCATED ON THE DISCHARGE POSITION.

5. FOR ALL BOXES, FIELD VERIFY RIGHT-HAND OR LEFT-HAND BOX AND COIL CONFIGURATIONS, DUCT CONNECTION CONFIGURATIONS, AND ELECTRICAL & CONTROL BOX

LOCATIONS PRIOR TO SUBMITTAL.

6. PROVIDE VAV BOXES WITH DOUBLE WALL CONSTRUCTION.

7. MINIMUM AND MAXIMUM AIRFLOWS LISTED ARE SHOWN FOR SIZING OF VAV BOXES. VAV BOXES MUST BE BALANCED TO COOLING AND HEATING DESIGN AIRFLOWS LISTED.

8. PROVIDE 3-WAY MODULATING CONTROL VALVES FOR ALL VAV TERMINAL UNITS.

NOTES:

60 500

320 130

320 130

320 130

320 130

320 130

330 130

165 1400

240 2000

8"Ø105 900

8"Ø105 900

6"Ø60 500

8"Ø105 900

10"Ø165 1400

6"Ø60 500

6"Ø60 500

6"Ø60 500

6"Ø60 500

6"Ø60 500

6"Ø60 500

6"Ø60 500

6"Ø60 500

6"Ø60 500

6"Ø60 500

6"Ø60 500

6"Ø60 500

6"Ø60 500

6"Ø60 500

0.940.04 0.72

180/144.27

180/147.46

180/143.87

180/142.8

180/147.09

180/141.90

180/124.75

180/131.61

180/161.32

1.480.94

1.010.76

107.54 0.980.74

1.000.75

1.090.79

0.15

1.0

18.95 180/142.12

1.45

0.96 1.56

98.81 0.93 1.45

0.94 1.48

TRANE VCWF

TRANE VCWF

TRANE VCWF

TRANE VCWF

TRANE VCWF

TRANE VCWF

TRANE VCWF

TRANE VCWF

TRANE VCWF

TRANE VCWF

TRANE VCWF

TRANE VCWF

TRANE VCWF

TRANE VCWF

TRANE VCWF

TRANE VCWF

TRANE VCWF

TRANE VCWF

TRANE VCWF

TRANE VCWF

TRANE VCWF

TRANE VCWF

TRANE VCWF

TRANE VCWF

TRANE VCWF

TRANE VCWF

TRANE VCWF

TRANE VCWF

TRANE VCWF

TRANE VCWF

TRANE VCWF

TRANE VCWF

TRANE VCWF

97.7313.900.07 1.39 3.92

0.64 0.76

SINGLE DUCT

REHEATTRANE VCWF

SINGLE DUCT

REHEATTRANE VCWF

NOTES:

1. PROVIDE WITH ALUMINUM CONSTRUCTION.

GRILLE, REGISTER AND DIFFUSER SCHEDULE

MARK TYPE USE

S

PANEL

SIZE IN.

NECK

SIZE IN.

MAX CFM MAX PD

IN. WC FINISH PATTERN REMARKSR E

MAX. NOISE

CRITERIA (NC)

24X24 4-WAY SEE NOTESXSAD-1 110 OFF

WHITE

0.025 10

SEE NOTESXSAD-2 200 0.025 10OFF

WHITE

24X24 PERF. SEE NOTESXRAG-3 200 0.025 10OFF

WHITE

24X24 PERF. SEE NOTESXRAG-4 330 0.025 10OFF

WHITE

SAD-3 X

0.02539512Ø24X24XRAG-5 OFF

WHITE

SEE NOTES

SEE NOTES10

SAD-4 X

24X24 10Ø 350 0.025 OFF

WHITE

4-WAY

SEE NOTES

RAG-1 X 12X12 110 0.025 OFF

WHITE

SEE NOTES106Ø

8Ø

10Ø

6ØCEILING

MOUNTED

24X24

24X24

8Ø

12Ø

4-WAY

4-WAY 100.025 OFF

WHITE425

24X24 SEE NOTESXRAG-2 110 OFF

WHITE

0.025 106Ø PERF.

PERF.

PERF.

CEILING

MOUNTED

CEILING

MOUNTED

CEILING

MOUNTED

CEILING

MOUNTED

CEILING

MOUNTED

CEILING

MOUNTED

CEILING

MOUNTED

CEILING

MOUNTED

0.025315XRAG-6 OFF

WHITE

SEE NOTES10SIDEWALLCEILING

MOUNTED

24X24XEAG-1 CEILING

MOUNTED

24X24XEAG-2 CEILING

MOUNTED

24X24XEAG-3 CEILING

MOUNTED

PERF. SEE NOTES200 0.025 10OFF

WHITE

8Ø

SEE NOTES110 OFF

WHITE

0.025 106Ø PERF.

SEE NOTES0.02539512Ø OFF

WHITE

10PERF.

SAG-1 XCEILING

MOUNTED

SEE NOTES10X10 10x10 SIDEWALL 120.025 OFF

WHITE315

6"Ø60 500

6"Ø60 500

6"Ø60 500

6"Ø60 500

6"Ø60 500

6"Ø60 500

6"Ø60 500

6"Ø60 500

6"Ø60 500

6"Ø60 500

6"Ø60 500

6"Ø60 500 107.94 1.018.370.29 0.59180/143.27

6"Ø500

60 500

10X10 10x10

180/160 0.760.02 114.42 0.646.42

106.657.560.04 1.010.76

106.657.560.04 1.010.76

98.339.400.08 1.480.94

180/160

180/160

180/160

180/160

180/160

180/160

180/160

180/160

107.94 1.018.370.29 0.59180/143.27

107.94 1.018.370.29 0.59180/143.27

107.94 1.018.370.29 0.59180/143.27

107.94 1.018.370.29 0.59180/143.27

92.51 1.1411.39 2.080.15

180/160

180/160

180/160

180/160

180/160

180/130.07

180/160

180/160

180/160

180/160

180/160

ALARMING

FUNCTION POINT NAME DESCRIPTION SETTING

(WITH UNITS)

RANGE

(WITH UNITS)

IO

TYPE

ALARM CONDITION

(SEE NOTES)

ALARM

PRIORITY

PROOFS

SAFETIES

TBD MANUFACTURER'S PROOFS (SEE NOTE) TBD ALM/NORMAL TBD

TBD MANUFACTURER'S SAFETIES (SEE NOTE) TBD ALM/NORMAL TBD

HTG-V-S HEATING VALVE POSITION STATUS 0-100% OPEN AI ALM INFO

START/STOP SYS-OCC-C OCCUPANCY INPUT FROM SYSTEM SCHEDULER OCCUPIED(1)/UNOCCUPIED(2) NET-IN

ZN-OCC OCCUPANCY OVERRIDE FROM SPACE OCCUPIED(1)/UNOCCUPIED(2) BI

ZONE

TEMPERATURE

CONTROL

ZN-T ZONE TEMPERATURE 40 - 85°F AI ZONE TEMPERATURE BELOW 60°F

OR ABOVE 85°F INFO

ZN-T-SP ZONE TEMPERATURE SETPOINT OCCUPANCY

ADJUSTABLE 68 - 78°F AI

ZN-T-SP-UNOCC ZONE TEMPERATURE SETPOINT FOR UNOCCUPIED MODE 60 - 85°F NET-OUT

VAV-SA-F VAV SUPPLY AIRFLOW AS SCHEDULED AI

VAV-SA-F-SP VAV SUPPLY AIRFLOW SETPOINT RESET SCHEDULE NET-OUT

VAV-D-C VAV DAMPER COMMAND 0-100% OPEN AO

HTG-V-C VAV REHEAT VALVE COMMAND 0-100% OPEN AO

DAMPER

CONTROL

LOOP

CONFIGURATION

SETTINGS

PROPORTIONAL CONSTANT TBD

INTEGRAL CONSTANT TBD

BIAS TBD

MAXIMUM OUTPUT TBD

MINIMUM OUTPUT TBD

NOTES:

1. THE CONTRACTOR SHALL COMPLETE THE POINTS SCHEDULE AS INDICATED IN THE SPECIFICATION AND IN ACCORDANCE WITH THIS DRAWING.

2. UNIT MANUFACTURERS PROOFS AND SAFETIES: THE CONTRACTOR SHALL SHOW EACH PROOF AND SAFETY AS A SEPARATE ROW.

3. UNIT STATUS: SERVES AS A MONITORED POINT AT THE M&C SOFTWARE (FRONT-END) AND AS A HEATING/COOLING REQUEST TO THE BOILER, HEAT EXCHANGER, AND/OR

CHILLER SERVING THIS SYSTEM.

4. "TBD" = TO BE DETERMINED DURING COMMISSIONING.

DDCHTG-V-C

DA-TVAV-#-#-V

RETURN

VAV-SA-F

ZN-T

TO

H ZONE

SUPPLY

VAV-D-C

SEQUENCE OF OPERATION

VAV BOXES

RUN CONDITIONS - SCHEDULED:

THE UNIT SHALL RUN ACCORDING TO A USER DEFINABLE TIME SCHEDULE IN THE FOLLOWING MODES:

· OCCUPIED MODE: THE UNIT SHALL MAINTAIN

· A 75°F (ADJ.) COOLING SETPOINT

· A 70°F (ADJ.) HEATING SETPOINT.

· UNOCCUPIED MODE (NIGHT SETBACK): THE UNIT SHALL MAINTAIN

· A 85°F (ADJ.) COOLING SETPOINT.

· A 60°F (ADJ.) HEATING SETPOINT.

ALARMS SHALL BE PROVIDED AS FOLLOWS:

· HIGH ZONE TEMP: IF THE ZONE TEMPERATURE IS GREATER THAN THE COOLING SETPOINT BY A USER

DEFINABLE AMOUNT (ADJ.).

· LOW ZONE TEMP: IF THE ZONE TEMPERATURE IS LESS THAN THE HEATING SETPOINT BY A USER DEFINABLE

AMOUNT (ADJ.).

ZONE SETPOINT ADJUST:

THE OCCUPANT SHALL BE ABLE TO ADJUST THE ZONE TEMPERATURE HEATING AND COOLING SETPOINTS AT THE

ZONE SENSOR.

ZONE OPTIMAL START:

THE UNIT SHALL USE AN OPTIMAL START ALGORITHM FOR MORNING START-UP. THIS ALGORITHM SHALL MINIMIZE THE UNOCCUPIED WARM-UP OR COOL-DOWN PERIOD WHILE STILL ACHIEVING COMFORT CONDITIONS BY THE

START OF SCHEDULED OCCUPIED PERIOD.

ZONE UNOCCUPIED OVERRIDE:

A TIMED LOCAL OVERRIDE CONTROL SHALL ALLOW AN OCCUPANT TO OVERRIDE THE SCHEDULE AND PLACE THE UNIT INTO AN OCCUPIED MODE FOR AN ADJUSTABLE PERIOD OF TIME. AT THE EXPIRATION OF THIS TIME, CONTROL OF THE UNIT SHALL AUTOMATICALLY RETURN TO THE SCHEDULE.

SPACE OCCUPIED MODE:

· SPACE THERMOSTAT SHALL MODULATE PRIMARY AIR DAMPER TO MAINTAIN SPACE TEMPERATURE.

· UPON CALL FOR HEAT, THE PRIMARY DAMPER SHALL CLOSE TO MINIMUM POSITION. UPON FURTHER CALL

FOR HEAT WITH PRIMARY AIR DAMPER IN MINIMUM POSITION, THE REHEAT CONTROL VALVE SHALL OPEN

AND MODULATE IN SEQUENCE TO MAINTAIN SPACE TEMPERATURE SET POINT.

· UPON CALL FOR COOLING, THE REHEAT VALVE SHALL MODULATE CLOSED. UPON A FURTHER CALL FOR COOLING, THE AIR DAMPER SHALL MODULATE OPEN AS REQUESTED TO PROVIDE COOLING AS SENSED BY

THE SPACE SENSOR.

HEATING WATER REHEATING:

THE CONTROLLER SHALL MEASURE THE ZONE TEMPERATURE AND STAGE THE 3-WAY HEATING WATER VALVE TO

MAINTAIN THE HEATING AND COOLING MODE DISCHARGE AIR TEMPERATURES AS SCHEDULED.

THE REHEATING SHALL BE ENABLED WHENEVER:

· VAV BOX DAMPER IS IN THE OPEN POSITION AND IN THE HEATING MODE.

· VAV BOX DAMPER IS IN THE MINIMUM POSITION IN THE COOLING MODE.

IN THE OCCUPIED MODE WHEN SPACE TEMPERATURE CONDITIONS ARE MET AND THE VAV BOX DAMPER IS IN

THE MINIMUM

POSITION, THE CONTROLLER SHALL STAGE THE 3-WAY HEATING WATER VALVE TO MAINTAIN A DISCHARGE

AIR TEMPERATURE OF

75 °F IN THE COOLING MODE AND 70 °F IN THE HEATING MODE.

DISCHARGE AIR TEMPERATURE:

THE CONTROLLER SHALL MONITOR THE DISCHARGE AIR TEMPERATURE.

ALARMS SHALL BE PROVIDED AS FOLLOWS:

· HIGH DISCHARGE AIR TEMP: IF THE DISCHARGE AIR TEMPERATURE IS GREATER THAN 120°F (ADJ.).

· LOW DISCHARGE AIR TEMP: IF THE DISCHARGE AIR TEMPERATURE IS LESS THAN 40°F (ADJ.).

ZN-T-LL

ZN-T-SP

HTG-V-S

PROVIDE ZONE

THERMOSTAT(S) AS

SHOWN IN POINTS

SCHEDULE AND ON

PLANS

ZN-T-SP-UNOCC

VAV-SA-F-SP

TO DDC

SYS-OCC-C

ZN-OCC

NAME:

VAV BOX W/ REHEAT CONTROLS

NOT TO SCALE

M-701

A OR AMP AMPERE(S)

ACC AIR COOLED CHILLER

AC ALTERNATING CURRENT

AC AIR COMPRESSOR / AIR

CURTAIN

AF AMP FRAME

AFF ABOVE FINISHED FLOOR

AFG ABOVE FINISHED GRADE

AHU AIR HANDLING UNIT

AIC AMPERE INTERRUPTING

CAPACITY

AL ALUMINUM

AM AMMETER

ASYM ASYMMETRICAL

AT AMP TRIP

ATS AUTOMATIC TRANSFER

SWITCH

AUTO AUTOMATIC

AWG AMERICAN WIRE GAUGE

B BOILER

BC BRANCH CONTROLLER

BCW BARE COPPER WIRE

BFF BELOW FINISHED FLOOR

BFG BELOW FINISHED GRADE

BLDG BUILDING

C CONDUIT

CAT CATEGORY

CB CIRCUIT BREAKER

CCT CORRELATED COLOR

TEMPERATURE

CCTV CLOSED CIRCUIT

TELEVISION

CFCI CONTRACTOR FURNISHED

CONTRACTOR INSTALLED

CH CHILLER

CHWCP CHILLED WATER

CIRCULATING PUMP IN A

PRIMARY-SECONDARY

SYSTEM

CHWP CHILLED WATER PUMP

CHWSP CHILLED WATER SUPPLY

PUMP IN A PRIMARY-

SECONDARY SYSTEM

CKT CIRCUIT

CMH COMMUNICATIONS

MANHOLE

CP CONDENSATE PUMP

CPT CONTROL POWER

TRANSFORMER

CRAC COMPUTER ROOM AC UNIT

CRI COLOR RENDERING INDEX

CT CURRENT TRANSFORMER

CT COOLING TOWER

CU COPPER OR CONDENSING

UNIT

CWP CONDENSER WATER PUMP

D DEPTH

DC DIRECT CURRENT

DF DESTRATIFICATION FAN

DH or DUH DUCT HEATERS

DHWCP DOMESTIC HOT WATER

CIRCULATING PUMP

DISC DISCONNECT SWITCH

DOAS DEDICATED OUTSIDE AIR

SYSTEM (UNIT)

DPST DOUBLE POLE SINGLE

THROW

DPDT DOUBLE POLE DOUBLE

THROW

DSCU DUCTLESS SPLIT

CONDENSING UNIT

(POWERS THE DSS INDOOR

UNIT)

DSHP DUCTLESS SPLIT HEAT

PUMP (POWERS THE DSS

INDOOR UNIT)

DSS DUCTLESS SPLIT SYSTEM

(INDOOR UNIT)

DWBP DOMESTIC WATER

BOOSTER PUMP

DX DIRECT EXPANSION (DX)

COOLING COIL

EC EMPTY CONDUIT

EF EXHAUST FAN

ELEC ELECTRICAL

EMH ELECTRICAL MANHOLE

EMT ELECTRICAL METALLIC

TUBING

E or EMER EMERGENCY

EPA EFFECTIVE PROJECTED

AREA

EQUIP EQUIPMENT

ERV ENERGY RECOVERY

VENTILATOR

ERU ENERGY RECOVERY UNIT

EXIST or EX EXISTING

NOTE: ABBREVIATIONS ABOVE

ARE FOR ELECTRICAL SHEETS

ONLY. NOT ALL ABBREVIATIONS

SHOWN WILL BE USED ON THIS

PROJECT.

ABBREVIATIONS LIST

EUH ELECTRIC UNIT HEATER

EXP EXPLOSION PROOF

EWC ELECTRIC WATER COOLER

EWH ELECTRIC WATER HEATER

F FUSE

FACP FIRE ALARM CONTROL

PANEL

FCU FAN COIL UNIT

FLEX FLEXIBLE

FWE FURNISHED WITH

EQUIPMENT

G OR GND GROUND

GFGI GOVERNMENT FURNISHED

GOVERNMENT INSTALLED

GFI GROUND FAULT

INTERRUPTER

GRS GALVANIZED RIGID STEEL

CONDUIT

GUH GAS UNIT HEATER

GWH GAS WATER HEATER

H or HT HEIGHT

HAC HEATED AIR CURTAIN

HOA HAND-OFF AUTOMATIC

HP HORSE POWER

HP HEAT PUMP (OUTDOOR

PORTION OF SPLIT SYSTEM

HEAT PUMP, USE CU FOR

STANDARD DX OUTDOOR

UNIT)

HT HEAT TRACKING

HVU HEATING/VENTILATING UNIT

HWCP HEATING WATER

CIRCULATING PUMP IN A

PRIMARY-SECONDARY

SYSTEM

HWP HEATING WATER SUPPLY IN

A PRIMARY-ONLY SYSTEM

HWRP HOT WATER

RECIRCULATION PUMP

HWSP HEATING WATER SUPPLY

PUMP IN A PRIMARY-

SECONDARY SYSTEM

HWUH HOT WATER UNIT HEATER

HZ HERTZ

IDS INTRUSION DETECTION

SYSTEM

IMC INTERMEDIATE METAL

CONDUIT

IRH INFRARED HEATER

J OR JB JUNCTION BOX

K KILO

KAIC THOUSAND AMPERE

INTERRUPTING CAPACITY

KCM OR KCMIL THOUSAND OF CIRCULAR

MILS

KEF KITCHEN EXHAUST FAN

KH KITCHEN HOOD

KV KILOVOLT

KVA KILOVOLT-AMPERES

KW KILOWATT

KWHR KILOWATT-HOUR

L LENGTH

LA LIGHTNING ARRESTOR

LAN LOCAL AREA NETWORK

LAV LAVATORY

LM LOCKHEED MARTIN

LTG LIGHTING

MAU MAKE-UP AIR UNIT

MAX MAXIMUM

MCA MINIMUM CIRCUIT AMPACITY

MCB or MB MAIN CIRCUIT BREAKER

MCC MOTOR CONTROL CENTER

MGB MAIN GROUND BAR

MH MANHOLE or MOUNTING

HEIGHT

MIN MINIMUM

MLO MAIN LUGS ONLY

MOD MOTOR OPERATED DAMPER

MT or MTD MOUNT or MOUNTED

MRS MOTOR RATED SWITCH

N NEUTRAL

NEC NATIONAL ELECTRICAL

CODE

NEMA NATIONAL ELECTRICAL

MANUFACTURER'S

ASSOCIATION

NFPA NATIONAL FIRE

PROTECTION ASSOCIATION

NC NORMALLY CLOSED

NESC NATIONAL ELECTRICAL

SAFETY CODE

NL NIGHT LIGHT

NO NORMALLY OPEN

NTS NOT TO SCALE

P POLE(S) or PUMP

PA PUBLIC ADDRESS

PDU POWER DISTRIBUTION UNIT

PF POWER FACTOR

PH PHASE

PIU VAV TERMINAL UNIT WITH

PARALLEL OR SERIES FAN

(PRIMARY INDUCTION UNIT)

PMT PAD MOUNTED

TRANSFORMER

PNL PANEL OR PANELBOARD

PTAC PACKAGED THRU-WALL AIR

CONDITIONER

PVC POLYVINYL CHLORIDE

RECEPT or RECP RECEPTACLE

RF RETURN FAN

RH RADIANT HEATERS

(ELECTRIC)

RMC RIGID METAL CONDUIT

RMS ROOT MEAN SQUARE

RTU ROOF TOP UNIT

RVNR REDUCED VOLTAGE NON-

REVERSING

SA SURGE ARRESTOR

SCCR SHORT CIRCUIT CURRENT

RATING

SD SMOKE DAMPER

SF SUPPLY FAN

S/N SOLID NEUTRAL

SP SUMP PUMP

SPD SURGE PROTECTIVE DEVICE

SPDT SINGLE POLE DOUBLE

THROW

SPEC SPECIFICATIONS

SPST SINGLE POLE SINGLE

THROW

SWBD SWITCHBOARD

SWGR SWITCHGEAR

TMGB TELECOMMUNICATIONS

MAIN GROUNDING BUSBAR

TOL THERMAL OVERLOAD

TP TWISTED PAIR

TYP TYPICAL

U URINAL

UH UNIT HEATER

UG UNDERGROUND

UIO UNLESS INDICATED

OTHERWISE

UL UNDERWRITERS

LABORATORY

UTP UNSHIELDED TWISTED PAIR

V VOLTS

VA VOLT AMPERES

VAV VAV TERMINAL UNIT

VEF VEHICLE EXHAUST FAN

VM VOLTMETER

VRF VARIABLE REFRIGERANT

FLOW SYSTEM

W WATTS or WIRE or WIDTH

WC WATER CLOSET

WEF WELDING EXHAUST FAN

WH WATER HEATER

WHDM WATTHOUR DEMAND METER

WSHP WATER SOURCE HEAT

PUMP

WP WEATHERPROOF

XFMR TRANSFORMER

Z IMPEDANCE

GENERAL NOTES - ELECTRICAL:

1. THE DRAWINGS INDICATE THE GENERAL EXTENT OF WORK. THE DRAWINGS ARE NOT

INTENDED TO INDICATE OR DESCRIBE ALL WORK REQUIRED FOR THE FULL PERFORMANCE

AND COMPLETION OF THE REQUIREMENTS OF THE CONTRACT DOCUMENTS.

2. THE ENUMERATION OF PARTICULAR ITEMS OF WORK IN ONE PORTION OF THE CONTRACT

DOCUMENTS SHALL NOT BE CONSTRUED TO EXCLUDE OTHER ITEMS NECESSARY OR

IMPLIED THEREFROM.

3. THE CONTRACTOR IS RESPONSIBLE FOR THE COORDINATION OF WORK SEQUENCING SUCH

THAT NO WORK SHALL BE LEFT IN AN UNFINISHED OR INCOMPLETE CONDITION.

4. WORK SHALL CONFORM TO APPLICABLE INDUSTRY AND MANUFACTURER'S PUBLISHED

STANDARDS FOR QUALITY OF MATERIALS AND WORKMANSHIP, AS WELL AS, THE

REQUIREMENTS IN THESE DRAWINGS AND SPECIFICATIONS. ANY CONFLICTING

REQUIREMENTS OF THE SOURCES LISTED ABOVE SHALL BE BROUGHT TO THE

CONTRACTING OFFICER'S ATTENTION PRIOR TO PROCEEDING WITH THE WORK.

5. THE CONTRACTOR SHALL PROTECT ANY EXISTING, IN-PLACE, AND NEW WORK.

6. WORK NOTED "N.I.C." IS NOT MEANT TO BE PART OF THE CONSTRUCTION SCOPE OF WORK

AGREEMENT.

7. THE CONTRACTOR SHALL PAY FOR AND COORDINATE THE REMOVAL AND LEGAL DISPOSAL

OF MATERIALS AND RUBBISH.

8. ONCE ON SITE, THE CONTRACTOR SHALL VERIFY DIMENSIONS AND SHALL VERIFY NEW AND

EXISTING CONDITIONS, SHOWN ON THESE DRAWINGS. THE CONTRACTOR SHALL NOTIFY THE

CONTRACTING OFFICER IN WRITING OF ANY DIFFERING CONDITIONS BEFORE

COMMENCEMENT OF WORK.

9. DO NOT SCALE DRAWINGS; DIMENSIONS GOVERN, LARGE SCALE DETAILS GOVERN OVER

SMALL SCALE DETAILS. THE CONTRACTOR SHALL NOTIFY THE CONTRACTING OFFICER IN

WRITING OF ANY DIFFERING CONDITIONS BEFORE COMMENCEMENT OF WORK.

10. THE CONTRACTOR SHALL PERFORM WORK IN ACCORDANCE WITH APPLICABLE CODES,

ORDINANCES AND REGULATORY AGENCIES AND SHALL OBTAIN NECESSARY BUILDING AND

FIRE PERMITS FROM ALL AUTHORITIES HAVING JURISDICTION.

11. PIPE DUCTS AND BUS DUCTS THAT PENETRATE FLOOR SLABS OR WALL PARTITIONS SHALL

BE INSTALLED IN A MANNER THAT WILL PRESERVE THE MOISTURE RESISTIVENESS, FIRE

RATING, AND STRUCTURAL INTEGRITY OF THE BUILDING.

12. THE CONTRACTOR SHALL PLAN HIS/HER WORK TO PROVIDE ADEQUATE PROTECTION FOR

PERSONS AND PROPERTY, AND EXECUTE THE WORK IN SUCH A MANNER TO AVOID ANY

HAZARD TO PERSONS AND PROPERTY AS NECESSARY.

13. THE CONTRACTOR SHALL COORDINATE THE PHASING OF THE WORK TO BE PERFORMED IN

OR ABOUT EXISTING FACILITIES, IF APPLICABLE, WITH THE OWNER'S REPRESENTATIVE

PRIOR TO START OF SUCH WORK.

14. MINIMUM RACEWAY SIZE SHALL BE 3/4". INCREASE RACEWAY SIZE AS REQUIRED TO LIMIT

RACEWAY FILL RATIO TO LESS THAN 40% FULL.

15. THE ELECTRICAL CONTRACTOR SHALL CAREFULLY COORDINATE WORK WITH OTHER

TRADES THROUGH THE GENERAL CONTRACTOR AND SHALL BE RESPONSIBLE FOR

SECURING SPACE REQUIREMENTS FOR ELECTRICAL EQUIPMENT CLEARANCE AND CORRECT

ROUGH-IN LOCATIONS OF ELECTRICAL CONNECTIONS.

16. FEEDERS AND BRANCH CIRCUITS SHALL INCLUDE A GREEN INSULATED GROUND

CONDUCTOR, SIZE PER NATIONAL ELECTRICAL CODE, OR AS SHOWN, CONNECTED TO EACH

DEVICE AND OUTLET BOX ON THE CIRCUIT AND TO THE PANELBOARD GROUND BUS.

PROVIDE A DEDICATED NEUTRAL CONDUCTOR FOR EACH BRANCH CIRCUIT. MULTIPLE

BRANCH CIRCUITS IN ONE RACEWAY REQUIRE ONLY ONE GROUND CONDUCTOR. SINGLE

GROUND CONDUCTOR IN ONE RACEWAY MUST BE SIZED FOR THE LARGEST OVERCURRENT

DEVICE.

17. EXISTING ELECTRICAL WORK (NOT SHOWN) SHALL REMAIN, UNLESS INDICATED OTHERWISE.

SHOULD ANY EXISTING ELECTRICAL POWER, LIGHTING OR AUXILIARY CIRCUIT, FEEDER OR

EQUIPMENT BE SEVERED, DISCONNECTED OR DELETED IN THE PROCESS OF

CONSTRUCTION OR REMODELING WHICH IS DONE AS A RESULT OF CONTRACT PLANS AND

SPECIFICATIONS, AND UNLESS SPECIFICALLY DESIGNATED BY THE DRAWINGS TO BE

DELETED, THEN SAID CIRCUIT OR FEEDER SHALL BE RESTORED TO WORKING CONDITION.

THE RESTORATION SHALL INCLUDE RE-ROUTING, RELOCATION, RECONNECTION OR

REPLACEMENT AS MAY BE REQUIRED BY THE NEW WORK. ANY SUCH WORK REQUIRED

SHALL BE INCLUDED IN THE CONTRACT AND NO EXTRA COMPENSATION WILL BE GRANTED.

18. NEW WORK SHALL BE MADE TO TIE INTO THE EXISTING IN A UNIFORM MANNER, SIMILAR

ITEMS OF NEW WORK SHALL BE CHECKED AGAINST EXISTING WORK.

19. REFER TO ONE-LINE DIAGRAM, SCHEDULES AND RISER DIAGRAMS FOR CONDUCTOR AND

CONDUIT SIZES NOT SHOWN ON PLANS.

20. PROVIDE IS AN INCLUSIVE TERM USED TO DESCRIBE ASPECTS OF THE WORK TO BE

ACCOMPLISHED, AND IS HEREBY DEFINED TO REQUIRE TO STORE, FURNISH, INSTALL,

MOUNT, CONNECT, CONTROL AND POWER EQUIPMENT INDICATED, AS WELL AS

APPURTENANCES REQUIRED TO MAKE ELECTRICAL SYSTEMS OPERATE AS INDICATED

WITHIN THESE DRAWINGS AND SPECIFICATIONS AND TO FULFILL THE SCOPE OF WORK.

21. DEMOLISH IS AN INCLUSIVE TERM USED TO DESCRIBE ASPECTS OF THE WORK TO BE

ACCOMPLISHED, AND IS HEREBY DEFINED TO REQUIRE CONTRACTOR TO DISCONNECT

EQUIPMENT FROM CONNECTIONS, REMOVE FROM THE OWNER'S SITE, AND DISPOSE OF IN

ACCORDANCE WITH FEDERAL, STATE AND LOCAL LAWS AND ORDINANCES. COST OF

DISPOSAL IS ENTIRELY THE CONTRACTOR'S RESPONSIBILITY.

22. ALL CONDUCTORS ARE COPPER UNLESS SPECIFICALLY NOTED AS ALUMINUM.

23. CONTRACTOR SHALL FIELD VERIFY EXISTING CONDITIONS, DIMENSIONS AND…