DESIGN NEW HVAC SYSTEM AND ASSOCIATED UPGRADES
PHASE 3A
STUTTGART, ARKANSAS
SHEET NO.
INDEX OF DRAWINGS
SHEET TITLE
USDA
NO SCALEVICINITY MAP
NORTH
ARKANSAS
PROJECT
LOCATION
USDA AGRICULTURAL RESEARCH SERVICE
DALE BUMPERS NATIONAL RICE RESEARCH CENTER
(DBNRRC)
G-001 G-002
AD111
A-101 M-001 M-002
MD101
MD102
MD103
MH101
MH102
MP101
M-501 M-502 M-601 M-701 E-001
ED102
ED111
E-101 E-102 E-111 E-500 E-600
PHASE 3A TITLE SHEET
PHASING PLAN
PHASE 3A REFLECTED CEILING PLAN: DEMO
PHASE 3A REFLECTED CEILING PLAN
PHASE 3A MECHANICAL GENERAL NOTES
PHASE 3A MECHANICAL LEGEND AND ABBREVIATIONS
PHASE 3A MECHANICAL HVAC DEMOLITION PLAN
PHASE 3A MECHANICAL PIPING DEMOLITION PAN
PHASE 3A MECHANICAL ROOF DEMOLITION PLAN
PHASE 3A MECHANICAL HVAC NEW WORK PLAN
PHASE 3A MECHANICAL ROOF NEW WORK PLAN
PHASE 3A MECHANICAL PIPING NEW WORK PLAN
PHASE 3A MECHANICAL DETAILS
PHASE 3A MECHANICAL DETAILS
PHASE 3A MECHANICAL SCHEDULES
PHASE 3A VAV BOX W/ REHEAT CONTROLS
PHASE 3A ELECTRICAL LEGEND AND NOTES
PHASE 3A ELECTRICAL ROOF DEMOLITION PLAN
PHASE 3A LIGHTING DEMOLITION PLAN
PHASE 3A ELECTRICAL POWER PLAN
PHASE 3A ELECTRICAL ROOF NEW WORK PLAN
PHASE 3A ELECTRICAL LIGHTING PLAN
PHASE 3A LIGHTING DETAILS AND SCHEDULES
PHASE 3A SCHEDULES
Dylan Mitchell 5923 sam
PHASE 1A, 1B AND 1C (NOT IN CONTRACT):
PHASE 2A (NOT IN CONTRACT)
PHASE 2B (NOT IN CONTRACT)
PHASE 3A:
PHASE 3B (NOT IN CONTRACT)
HEADHOUSE (NOT IN CONTRACT)
PHASING LEGEND
A. ALL NON-WORK AREAS IN THE BUILDING WILL REMAIN OCCUPIED AND OPERATIONAL
DURING THE WORK. USDA WILL VACATE AREAS OF THE BUILDING WHERE WORK IS
BEING PERFORMED. THE CONTRACTOR SHALL COORDINATE HIS/HER WORK
ACTIVITIES WITH THE CONTRACTING OFFICER TO AVOID CONFLICTS WITH FACILITY
OPERATIONS. THE CONTRACTOR SHALL ERECT BARRIERS AND EMPLOY NECESSARY
MEASURES TO PROTECT PERSONNEL IN THE AREA FROM INJURY.
B. COVER AND PROTECT ALL FURNISHINGS AND EQUIPMENT REMAINING IN THE
LABORATORIES AND OFFICE SPACES.
C. THE CONTRACTOR SHALL PROVIDE BARRIERS AND SIGNAGE TO SECURE THE WORK
AREAS, TO DIRECT PERSONNEL IN WAYFINDING, AND TO ENSURE THE SAFETY OF
BUILDING OCCUPANTS AND VISITORS. THE CONTRACTOR SHALL PROVIDE A WORK
PLAN BEFORE BEGINNING THE WORK EXPLAINING AND ILLUSTRATING THE MEANS TO
BE IMPLEMENTED TO ALLOW THE BUILDING TO REMAIN OCCUPIED AND OPERATIONAL
DURING THE WORK. THE CONTRACTOR SHALL FIELD VERIFY ALL DIMENSION AND
CONDITIONS BEFORE BEGINNING WORK.
D. CONTRACTOR SHALL COORDINATE STAGING AREAS WITH USDA PERSONNEL.
GENERAL NOTES
PHASE 3A
AREA OF
WORK
110A
114 110
112 111
L-21
L-1B
L-21B
L-1A
L-1C
L-1
L-18
125 126 129 L-20
L-22
L-17B
L-16
L-1D
L-19
L-17
L-21C
L-21E L-21D
L-21A
SCALE:
PHASE 3A
REFLECTED CEILING PLAN: DEMO
3/16" = 1'-0"
AD111
0 4' 8' 16'
SCALE: 3/16"= 1'-0"
2'
KEY PLAN
N.T.S.
AREA OF
WORK
PHASE 3A
LEGEND
DEMOLISH 24 x 24" SUSPENDED
ACOUSTICAL CEILING SYSTEM
COMPLETE. CONTRACTORS
OPTION TO RETAIN SUSPENSION
WIRES
DEMOLISH SUSPENDED GYPSUM
BOARD CEILING SYSTEM
COMPLETE. CONTRACTORS
OPTION TO RETAIN HANGER
WIRES
LIGHT FIXTURES. SEE
ELECTRICAL DRAWINGS FOR
ADDITIONAL WORK.
HVAC DIFFUSERS. SEE
MECHANICAL DRAWINGS FOR
ADDITIONAL WORK.
NO WORK THIS AREA
DEMOLISH 24 x 48" SUSPENDED
ACOUSTICAL CEILING SYSTEM
COMPLETE. CONTRACTORS
OPTION TO RETAIN SUSPENSION
WIRES
5923 robin seal
114 110
109 108
112 111
L-21
L-1B
L-21B
L-1A L-1C
L-1
L-18
125 126 129 L-20
L-22
L-17B
L-16
L-1D
L-19
L-21C
L-21E
L-21D
L-21A
SCALE:
PHASE 3A
REFLECTED CEILING PLAN
3/16" = 1'-0"
A-101
0 4' 8' 16'
SCALE: 3/16"= 1'-0"
2'
KEY PLAN
N.T.S.
LEGEND
PROVIDE NEW 24 x 24"
SUSPENDED ACOUSTICAL
CEILING SYSTEM AS SPECIFIED.
CONTRACTORS OPTION TO
RETAIN SUSPENSION WIRES
PROVIDE NEW SUSPENDED
GYPSUM BOARD CEILING
SYSTEM AS SPECIFIED.
CONTRACTORS OPTION TO
RETAIN HANGER WIRES
LIGHT FIXTURES. SEE
ELECTRICAL DRAWINGS FOR
ADDITIONAL WORK.
HVAC DIFFUSERS. SEE
MECHANICAL DRAWINGS FOR
ADDITIONAL WORK.
AREA OF
WORK
PHASE 3A
NO WORK THIS AREA
5923 robin seal
1. INSTALLATION OF HVAC WORK SHALL BE COORDINATED WITH OTHER TRADES BEFORE ANY WORK IS PERFORMED. DUCTWORK SHOWN ON PLANS IS SCHEMATIC. DUCTWORK SHALL BE INSTALLED TIGHT TO STRUCTURE. PROVIDE ALL TRANSITIONS, ELBOWS, ETC. REQUIRED TO AVOID CONFLICTS & MAXIMIZE CEILING HEIGHTS. EQUIPMENT, PIPING OR DUCTWORK INTERFERING WITH OTHER TRADES SHALL BE
RELOCATED AS REQUIRED AT NO ADDITIONAL COST TO THE OWNER.
2. COORDINATE MECHANICAL AND ELECTRICAL SUCH THAT MECHANICAL PIPING, DUCTWORK AND EQUIPMENT
IS NOT LOCATED OVER OR ABOVE ANY ELECTRICAL, COMMUNICATIONS, OR DATA EQUIPMENT.
3. AT START OF CONSTRUCTION, PREPARE TYPED LISTS OF EQUIPMENT THAT ARE SUPPLIED REQUIRING ELECTRICAL WORK, AND SEND LISTS TO THE ELECTRICAL CONTRACTOR FOR REVIEW AND COORDINATION.
4. EQUIPMENT SHALL BE INSTALLED IN ACCORDANCE WITH MANUFACTURER'S APPROVED CLEARANCE AND
INTERNATIONAL BUILDING CODE / INTERNATIONAL MECHANICAL CODE.
5. INSTALLATION OF EQUIPMENT SHALL PERMIT ACCESSIBILITY FOR SERVICE AND/OR REPLACEMENT WITHOUT NECESSITATING REMOVAL OR MODIFICATION TO OTHER PIPING, WIRING, OR EQUIPMENT.
6. CEILING-MOUNTED EQUIPMENT SHALL BE INSTALLED IN SUCH A MANNER THAT LIGHTS, PIPING, DUCTWORK, ETC., DO NOT BLOCK ACCESS TO EQUIPMENT AND RELATED ACCESSORIES.
7. COORDINATE WALL, FLOOR, AND ROOF PENETRATIONS WITH THE CONTRACTOR.
8. SUPPLEMENTAL STEEL MEMBERS REQUIRED TO SUPPORT HVAC EQUIPMENT FROM MAIN STRUCTURE
SHALL BE PROVIDED BY THE HVAC CONTRACTOR UNLESS SPECIFICALLY NOTED OTHERWISE.
9. DUCTWORK AIR DISTRIBUTION SYSTEMS SHALL BE INSTALLED IN ACCORDANCE WITH SMACNA STANDARDS
AND THE PRESSURE CLASSIFICATION OF EACH INDIVIDUAL DUCTWORK SYSTEM.
10. VOLUME DAMPERS SHALL BE PROVIDED AT EACH MAIN BRANCH TAKE-OFF, EACH TAKEOFF TO DIFFUSERS/GRILLS/REGISTERS, AND OTHER LOCATIONS WHERE REQUIRED TO PROPERLY BALANCE THE
SYSTEM. ALL REQUIRED VOLUME DAMPERS MAY NOT BE SHOWN ON PLANS.
11. INSTRUMENT TEST HOLES SHALL BE PROVIDED IN AIR DISTRIBUTION SYSTEMS WHEREVER VOLUME DAMPERS ARE INSTALLED. TEST HOLES SHALL BE SEALED WITH RUBBER OR PLASTIC TEST HOLE PLUGS.
12. SQUARE ELBOWS SHALL ONLY BE USED WHERE SPACE LIMITATIONS PREVENT USE OF 1.5 RADIUS ELBOW AND ONLY UPON APPROVAL OF CONTRACTING OFFICER. PROVIDE TURNING VANES IN ALL SQUARE ELBOWS GREATER THAN OR EQUAL TO 45°. TURNING VANES SHALL BE SINGLE THICKNESS TYPE WITHOUT RAILING
EDGE. TURNING VANES LONGER THAN 36 INCHES SHALL BE DOUBLE THICKNESS TYPE.
13. DUCTWORK RUNOUTS TO AIR DISTRIBUTION DEVICES SHALL BE SAME DIAMETER AS AIR DISTRIBUTION
DEVICE INLET CONNECTION UNLESS OTHERWISE NOTED ON THE DRAWINGS.
14. FLEXIBLE DUCTWORK RUNOUTS FROM BRANCH DUCTS TO AIR DISTRIBUTION DEVICES SHALL NOT EXCEED 5 FEET IN LENGTH. BENDS IN FLEXIBLE DUCTWORK SHALL NOT EXCEED A MAXIMUM OF 45 DEGREE CHANGE OF DIRECTION AND SHALL BE SUPPORTED SUCH THAT THE BEND RADIUS IS NOT RESTRICTIVE TO AIR FLOW THROUGH THE DUCT. FLEXIBLE DUCTWORK SHALL NOT BE CRUSHED OR DISTORTED IN ITS FINAL
CONFIGURATION.
15. PROVIDE SHEETMETAL TRANSITIONS AT AIR HANDLING UNITS, HEAT PUMP UNITS, FANS, AND OTHER SIMILAR HVAC EQUIPMENT. TRANSITION TO FULL SIZE OF CONNECTION ON UNIT. FLEXIBLE DUCT
CONNECTORS SHALL BE USED ON FINAL CONNECTION TO AIR HANDLING EQUIPMENT.
16. TRANSFER DUCTS SHALL BE SIZED FOR MAX VELOCITY ALLOWED OF 500 FPM. OPEN-ENDED TRANSFER
DUCTS SHALL HAVE 90° ELBOW FOR SOUND ATTENUATION.
17. LOUVERED SUPPLY AIR DIFFUSERS SHALL BE 4-WAY FLOW UNLESS OTHERWISE SHOWN BY FLOW ARROWS ON THE DRAWINGS. LINEAR DIFFUSERS SHALL BE ADJUSTABLE 2-WAY FLOW. PROVIDE BATT INSULATION
ON DIFFUSER AND GRILLES THAT ARE EXPOSED TO CEILING PLENUM.
18. EXACT LOCATION OF CEILING DIFFUSERS, GRILLES AND REGISTERS SHALL BE DETERMINED BY
ARCHITECTURAL REFLECTED CEILING PLAN.
19. LOUVER PLENUMS SHALL BE PITCHED DOWN TOWARD THE BOTTOM OF THE LOUVER.
20. PROVIDE ACCESS PANELS TO ACCESS DAMPERS, EQUIPMENT, AND VALVES LOCATED ABOVE HARD
CEILINGS OR IN WALLS. ACTUAL LOCATIONS SHALL BE FIELD DETERMINED.
21. EXACT LOCATIONS OF THERMOSTATS, CO2 SENSORS, AND EMCS SENSORS SHALL BE COORDINATED WITH
FINAL LOCATIONS OF WALL-MOUNTED ARCHITECTURAL AND ELECTRICAL EQUIPMENT. MOUNT
THERMOSTATS AND CO2 SENSORS MINIMUM 48" AFF.
22. AIR HANDLING UNITS SERVING OCCUPIED AREAS SHALL HAVE MINIMUM MERV 8 PRE-FILTERS AND MERV 13 FINAL FILTERS. UNITS NOT SERVING OCCUPIED ZONES SHALL HAVE MINIMUM MERV 8 FILTER. FILTERS SHALL BE INDUSTRY STANDARD SIZE. FILTERS SHALL NOT CREATE PRESSURE DROP EXCEEDING 10% OF
EXTERNAL STATIC PRESSURE (ESP) CAPACITY LISTED IN EQUIPMENT SCHEDULE.
GENERAL MECHANICAL NOTES:
23. SUPPLY, RETURN, AND OUTDOOR AIR DUCTWORK SHALL BE INSULATED TO MEET OR EXCEED ASHRAE 189.1.
EXTERIOR SUPPLY AND RETURN AIR DUCTWORK SHALL BE PROVIDED WITH WEATHER-PROOF COVER.
24. PROVIDE SUPPORTS FOR PIPING AND DUCTWORK IN ACCORDANCE WITH SPECIFICATIONS.
25. PROVIDE A MANUFACTURED EXPANSION DEVICE OR FABRICATED EXPANSION LOOP ON ALL DUCTWORK AND
PIPING SYSTEMS CROSSING BUILDING EXPANSION JOINTS.
26. PROVIDE SHUT-OFF VALVES AND FLEXIBLE CONNECTIONS AT PIPE CONNECTIONS TO HVAC EQUIPMENT.
27. FOR WALL, FLOOR, AND SLAB PENETRATIONS, SEAL AND PATCH ALL UNUSED PENETRATION SPACE TO MATCH EXISTING CONSTRUCTION/FINISH OR AS SHOWN ON MECHANICAL DETAILS SHEET. PROVIDE FIRE STOPPING FOR
RATED WALLS AND FLOORS.
28. INSTALL EXPOSED CONTROL WIRING IN CONDUIT. SEE DIVISION 26 SPECIFICATIONS FOR REQUIREMENTS.
29. MANUFACTURER NAME AND MODEL NUMBERS ARE BASIS OF DESIGN AND ARE SHOWN FOR INFORMATION ONLY.
REFER TO SPECIFICATIONS FOR COMPLETE REQUIREMENTS.
30. SPECIFICATIONS TAKE PRECEDENCE OVER DRAWINGS. HOWEVER, ITEMS SHOWN ON DRAWING BUT NOT IN THE SPECIFICATIONS ARE REQUIRED WITHIN THE PROJECT SCOPE. IN ADDITION, SPECIFIC ITEMS SHOWN ON THE DRAWINGS TAKE PRECEDENCE OVER SPECIFICATIONS IN CASES WHERE THE SPECIFICATION HAS OPTIONS.
31. ALL EQUIPMENT SHALL BE INSTALLED IN ACCORDANCE WITH MANUFACTURER'S APPROVED PUBLISHED
LITERATURE.
32. DUCT SIZES SHOWN ARE INSIDE CLEAR DIMENSIONS.
33. EXPOSED DUCTWORK, WITH THE EXCEPTION OF DUCTWORK IN MECHANICAL ROOMS SHALL BE DOUBLE-WALL, DUCTWORK WITH COATING.
34. IF SUSPECT ASBESTOS IS FOUND, STOP WORK IMMEDIATELY AND NOTIFY OWNER AND GENERAL CONTRACTOR.
OWNER IS RESPONSIBLE FOR ABATEMENT OF UNFORESEEN ASBESTOS.
35. NOT ALL MECHANICAL ABBREVIATIONS SHOWN WILL BE USED FOR THIS PROJECT.
36. ALL THERMOSTATS SHALL BE WALL MOUNTED AND WIRED.
37. ALL EQUIPMENT INSTALLED IN THIS PROJECT SHALL COMPLY WITH THE "BUY AMERICAN ACT". BASIS OF DESIGN SHOWN ON SCHEDULES IS TO ESTABLISH A STANDARD OF QUALITY, NOT TO LIMIT COMPETITION. EQUIVALENT
EQUIPMENT FROM ANOTHER MANUFACTURER IS ACCEPTABLE.
38. ALL COMMUNICATIONS PREMISE WIRING AND CABLE TRAYS THROUGHOUT THE FACILITY MUST BE PROTECTED AND UNINTERRUPTED DURING CONSTRUCTION. THIS INCLUDES ELECTRICAL POWER TO COMMUNICATIONS
EQUIPMENT. NO COMMUNICATIONS OUTAGES MUST TAKE PLACE WITHOUT THE CONSENT OF THE
CONTRACTING OFFICER.
39. CONTRACTOR MUST DEMOLISH ALL THERMOSTATS AND WIRING ASSOCIATED WITH THE HVAC SYSTEM TO BE
DEMOLISHED.
40. CONTROLS CONTRACTOR SHALL PROVIDE ALL LOW VOLTAGE DEVICES, CONDUCTORS, AND PATHWAYS IN
ACCORDANCE WITH THE REQUIREMENTS OF 26 20 00.
41. AFTER THE TESTING AND BALANCING OF THE AIR TERMINALS INCLUDED IN THIS PHASE IS COMPLETE, THE EXISTING AHU, DOAS, HEATING WATER, AND CHILLED WATER SYSTEM ASSOCIATED WITH AND/OR AFFECTED BY THE WORK IN THIS PHASE MUST BE ADJUSTED AND BALANCED TO ACCOMMODATE FOR THE HVAC ALTERATIONS
THAT RESULT FROM THE WORK DONE IN THIS PHASE.
ABBREVIATIONS:
@ AT
& AND
AHU AIR HANDLING UNIT
ARCH ARCHITECT, ARCHITECTURAL
AS AIR SEPARATOR
ASHRAE AMERICAN SOCIETY OF HEATING, REFRIGERATING,
AND AIR CONDITIONING ENGINEERS
ASTM AMERICAN SOCIETY FOR TESTING AND
MATERIALS
BDD BACKDRAFT DAMPER
BLDG BUILDING
BTU, BTUH BRITISH THERMAL UNITS, BTUs PER HOUR
CD CONDENSATE DRAIN
CFM CUBIC FEET PER MINUTE
CHW CHILLED WATER
CHWR CHILLED WATER RETURN
CHWS CHILLED WATER SUPPLY
CLG COOLING
CMU CONCRETE MASONRY UNIT
CO CLEANOUT
CO2 CARBON DIOXIDE
CONC CONCRETE
COND STEAM CONDENSATE
CONN CONNECT, CONNECTING, CONNECTION
CONT CONTINUED
CONV STEAM CONVERTER
COP COEFFICIENT OF PERFORMANCE
COR CONTRACTING OFFICER'S (OWNER'S)
REPRESENTATIVE
CT COOLING TOWER
CU CONDENSING UNIT
CWR CONDENSER WATER RETURN
CWS CONDENSER WATER SUPPLY
D DEPTH
DB, Tdb DRY BULB (TEMPERATURE) dBA DECIBELS
DCW DOMESTIC COLD WATER
DDC DIRECT DIGITAL CONTROLS
DEG. F (°F) DEGREES FAHRENHEIT
DF DESTRATIFICATION FAN
DFCU DUCTLESS FAN COIL UNIT
DH DEHUMIDIFIER
DIA, Ø DIAMETER
DIV DIVISION
DN DOWN
DP, PD DIFFERENTIAL PRESSURE, PRESSURE DROP
DSCU DUCTLESS SPLIT CONDENSING UNIT
DSHP DUCTLESS SPLIT HEAT PUMP
DWG DRAWING
DX DIRECT EXPANSION
EA EXHAUST AIR
EAG EXHAUST AIR GRILLE
EAT ENTERING AIR TEMPERATURE
EER ENERGY EFFICIENCY RATIO
EF EXHAUST FAN
EFF EFFICIENCY
ELEC ELECTRICAL
EMCS ENERGY MONITORING AND CONTROLS SYSTEM
ERU ENERGY RECOVERY UNIT
ERV ENERGY RECOVERY VENTILATOR
ESP EXTERNAL STATIC PRESSURE
ET EXPANSION TANK
EUH ELECTRIC UNIT HEATER
EWT ENTERING WATER TEMPERATURE
EXT EXTERIOR
EXH EXHAUST
EXIST. EXISTING
FCU FAN COIL UNIT
FD FIRE DAMPER
FFE FINISHED FLOOR ELEVATION
FLA FULL LOAD AMPS
FOB FLAT ON BOTTOM
FOT FLAT ON TOP
FPM FEET PER MINUTE
FSD FIRE SMOKE DAMPER
FT FOOT, FEET
FT WG FEET WATER GAUGE
FV FLUE VENT
GA GAGE
GC GENERAL CONTRACTOR
GPM GALLONS PER MINUTE
GWH GAS WATER HEATER
H HEIGHT
HPS HIGH PRESSURE STEAM
HR HOUR
HTG HEATING
HTR HEATER
HTW HEATING WATER
HWR HEATING WATER RETURN
HWS HEATING WATER SUPPLY
HVAC HEATING, VENTILATING, AND AIR CONDITIONING
HX HEAT EXCHANGER
HZ HERTZ
IMC INTERNATIONAL MECHANICAL CODE
IN INCH, INCHES
IN WC INCHES WATER COLUMN
IN WG INCHES WATER GAUGE
IPLV INTEGRATED PART LOAD VALUE
KW KILOWATTS
L LENGTH, LOUVER (WALL)
LAT LEAVING AIR TEMPERATURE
LBD LINEAR BAR DIFFUSER
LBS POUNDS
LWT LEAVING WATER TEMPERATURE
MAX MAXIMUM
MBH 1000 BRITISH THERMAL UNITS
MCA MINIMUM CIRCUIT AMPACITY
MECH MECHANICAL
MERV MINIMUM EFFICIENCY REPORTING VALUE
MFCR, MFCG MANUFACTURER, MANUFACTURING
MIN MINIMUM
MOCP, MOP MAXIMUM OVER CURRENT PROTECTION
MTWR MEDIUM TEMPERATURE WATER RETURN
MTWS MEDIUM TEMPERATURE WATER SUPPLY
MXB MIXING BOX
N.C. NORMALLY CLOSED
NC NOISE CRITERIA
NG NATURAL GAS
NO. NUMBER
N.O. NORMALLY OPEN
NTS NOT TO SCALE
OA OUTSIDE AIR
OD OUTSIDE DAMPER
PCHWR PLANT CHILLED WATER RETURN
PCHWS PLANT CHILLED WATER SUPPLY
PD PRESSURE DROP
PH PHASE
PLBG PLUMBING
PMTWR PLANT MEDIUM TEMPERATURE WATER RETURN
PMTWS PLANT MEDIUM TEMPERATURE WATER SUPPLY
PPM PARTS PER MILLION
PRV PRESSURE RELIEF VALVE
PSI POUNDS PER SQUARE INCH
QTY QUANTITY
RA RETURN AIR
RAG RETURN AIR GRILLE
RH RELATIVE HUMIDITY, ROOF HOOD
RM ROOM
RPM REVOLUTIONS PER MINUTE
SA SUPPLY AIR
SAD SUPPLY AIR DIFFUSER
SAG SUPPLY AIR GRILLE
SD SMOKE DAMPER, SMOKE DETECTOR
SEER SEASONAL ENERGY EFFICIENCY RATIO
SF SUPPLY FAN
SMACNA SHEET METAL AND AIR CONDITIONING
CONTRACTOR'S NATIONAL ASSOCIATION
SP STATIC PRESSURE
STM STEAM
SS STAINLESS STEEL
TEMP TEMPERATURE
TSTAT THERMOSTAT
TYP TYPICAL
UH UNIT HEATER
UL UNDERWRITER'S LABORATORY
UMCS UTILITY MONITORING AND CONTROL SYSTEM
V VOLTAGE, VOLTS
VAV VARIABLE AIR VOLUME
VD VOLUME DAMPER
VFD VARIABLE FREQUENCY DRIVE
VRF VARIABLE REFRIGERANT FLOW
WB, Twb WET BULB (TEMPERATURE)
MISCELLANEOUS LEGEND:
AIR DISTRIBUTION DEVICE TAGS
DIFFUSER SUB-TYPE
A
400 AIRFLOW (CFM),
"PLENUM", OR
"TRANSFER"
NORTH ARROW
A
J
SD
SP
F
CO
DUCT SMOKE DETECTOR
CARBON MONOXIDE SENSOR
OVAL OR FLAT OVAL
CONTROL WIRING
STATIC PRESSURE SENSOR
ROUND OR DIAMETER
FIRESTAT
TEMPERATURE SENSORT
120 VOLT STAND BY POWER JUNCTION
BOX PROVIDED BY THE ELECTRICAL
CONTRACTOR. JUNCTION BOX IS
DEDICATED FOR USE BY THE CONTROLS
CONTRACTOR.
VARIABLE FREQUENCY DRIVEVFD
FLOW ARROW
RETURN AIR GRILLE
SUPPLY AIR DIFFUSER
FLOW ARROWS INDICATE AIR PATTERN.
NO FLOW ARROWS SHOWN INDICATES
4-WAY PATTERN.
EXHAUST AIR GRILLE
SERVICE CLEARANCE
T THERMOSTAT
H HUMIDISTAT
$ START/ STOP SWITCH
TH THERMOSTAT/ HUMIDISTAT
HUMIDITY SENSORH
DIFFUSER TYPE
XXX-
DP DIFFERENTIAL PRESSURE SENSOR
C CARBON DIOXIDE SENSOR
AQ AIR QUALITY SENSOR
POINT OF RECONNECTION
OR EXTENT OF DEMOLITION
ELEVATION CROSS REFERENCEX
XXXXX
PIPING LEGEND:
CHILLED WATER SUPPLY
(CHWS)
HEATING WATER SUPPLY
(HWS)
HEATING WATER RETURN
(HWR)
HIGH PRESSURE STEAM SUPPLY
(HPS)
STEAM CONDENSATE RETURN
(COND)
EXISTING PIPING TO REMAIN
(EXIST.)
CONDENSATE DRAIN
(CD)
FLEXIBLE CONNECTION
THERMOMETER
PRESSURE REDUCING VALVE
MANUAL AIR VENT
PRESSURE/TEMPERATURE TAP WITH
BALL VALVE
PRESSURE SWITCH
PLUG VALVE
FLOW SWITCH
T&P RELIEF VALVE
AUTOMATIC AIR VENT
PRESSURE GAUGE WITH GAUGE COCK
PS
FS
BUTTERFLY VALVE
STRAINER WITH BLOWDOWN VALVE,
CAP, AND CHAIN
FLOW MEASURING/BALANCING/SHUT-
OFF VALVE
GATE VALVE
CHECK VALVE
BALL VALVE
CONCENTRIC REDUCER
DIRECTION OF FLOW
ECCENTRIC REDUCER
PIPE FLANGE
PIPE CAP
PIPE GUIDE (PG)
PIPE ANCHOR (PA) X
UNION
TEE OUTLET UP
BRANCH BOTTOM CONNECTION
BRANCH TOP CONNECTION
ELBOW UP
ELBOW DOWN
RISE OR DROP
TEE OUTLET DOWN
DUCTWORK LEGEND:
M
FIRE DAMPER
EXHAUST AIR DUCT DOWN
EXHAUST AIR DUCT UP
RETURN AIR DUCT DOWN
30"x14"
SQUARE TO ROUND DUCT BRANCH TAKE-OFF
WITH 45 DEGREE BRANCH INLET
ROUND DUCT BRANCH TAKE-OFF FROM
RECTANGULAR MAIN WITH CONICAL TAP
FLEXIBLE DUCT CONNECTION
DUCT SIZE TRANSITION
RECTANGULAR DUCT BRANCH TAKE-OFF
WITH 45 DEGREE BRANCH INLET
90 DEGREE DUCT ELBOW WITH TURNING VANES
24"Ø ROUND DUCT. DIAMETER INDICATED IN INCHES.
IN-LINE 90 DEGREE RISE/DROP IN
SUPPLY DUCT
FD
SD
DAMPER TYPE:
M - MOTORIZED DAMPER (ELECTRIC)
VD
SMOKE DAMPER
VOLUME/BALANCING DAMPER
(LABEL MAY BE OMITTED)
BD
BACKDRAFT DAMPER
(COUNTER-BALANCED UNLESS
OTHERWISE NOTED)
RADIUS DUCT ELBOW - ROUND OR
RECTANGULAR (MIN. 1.5 RADIUS UNLESS
OTHERWISE NOTED)
RECTANGULAR DUCT. SIZE INDICATED IN
INCHES, FIRST NUMBER IS SIDE SHOWN.
DASHED LINES INDICATE ACOUSTICAL LINER
FSD
COMBINATION
FIRE/SMOKE DAMPER
IN-LINE 90 DEGREE RISE/DROP IN
RETURN DUCT
DUCT SIZE TRANSITION RECTANGULAR TO
ROUND
30"x14" FLAT OVAL DUCT. SIZE INDICATED IN INCHES, FIRST NUMBER IS SIDE SHOWN
RETURN AIR DUCT UP
SUPPLY OR OUTSIDE AIR DUCT DOWN
SUPPLY OR OUTSIDE AIR DUCT UP
IN-LINE 90 DEGREE RISE/DROP IN
EXHAUST DUCT
SD
DUCT MOUNTED SMOKE DETECTOR
GLOBE VALVE
PLAN
NORTH
EXISTING PIPING TO BE
DEMOLISHED
22x10 x1
24"Ø x1 x1 x1 x1 x1 x1
14"Ø
16x12 x1
12x10
8" Ø
10"Ø
10x8 14 x1
12x10
8" Ø
10x610x6 x8 x1
10x6 14x10
12"Ø 10 "Ø
"Ø
10"Ø 14x10 x1
10x10 10x10 14x10 x6 x6
20x10 x1
18x10
8" Ø
5" Ø 10x10
5" Ø
10"Ø
"Ø
10x10
10"Ø
"Ø x1
014x6
8" Ø
10x10 8"Ø
10x8
8" Ø
8x10 x8
12"Ø 6"Ø14x10
14x10 6"
Ø
6"Ø14x10
10x8 x1
10x8
14x10 6"Ø
16"Ø
10x10
8" Ø
8" Ø x1
16x10
16x1012x10
10x6
"Ø x8 x8 x1 x1 x6
10x8 x1
"Ø14x10 6"Ø
10x8
14x10 6"Ø
10x8
14x10 6"Ø
6"Ø 10x10 x1 x8 x1
30x16 32x20 x1
5"Ø
5" Ø
5"Ø
5" Ø
10x10
10"Ø
10x10
10x6 x8
12x8
10x8 10x8 x1
8"Ø
5"Ø
"Ø x6 x810x6 10x6
10x610x6
5" Ø
10x10
48x20
16"Ø14"Ø x1 x1 x1
10x6 10x6
6" Ø
22x6
10x6
SCALE:
PHASE 3A MECHANICAL
HVAC DEMOLITION PLAN
3/16" = 1'-0"
MD101
0 4' 8' 16'
SCALE: 3/16"= 1'-0"
2'
EXIST. AIR TERMINAL TO
BE DEMOLISHED (TYP.)
1. EXISTING VAV BOX, DUCTWORK, THERMOSTAT,
AND ALL APPURTENANCES TO BE REMOVED.
2. EXISTING DUCTWORK UP TO AHU-1 IN
MEZZANINE AREA TO BE REMOVED.
3. EXISTING AHU-2 DUCTWORK TO REMAIN IN
PLACE.
4. EXISTING 10" X 10" EXHAUST DUCTWORK UP TO
EF-3 TO BE DEMOLISHED.
KEYED NOTES
LEGEND:
EXISTING EQUIPTMENT TO
BE DEMOLISHED
EXISTING DUCTWORK TO BE
DEMOLISHED
1 1
1 1
EXISTING DUCTWORK TO BE
REMAIN
EXIST. VAV BOX
TO REMAIN
T
T
T
T
T
T
T T T
T T
T
T
T
T
T
T
T
T
T
T
T
T T
T
T T
T
T
T
SCALE:
PHASE 3A MECHANICAL
PIPING DEMOLITION PLAN
3/16" = 1'-0"
MD102
0 4' 8' 16'
SCALE: 3/16"= 1'-0"
2'
1. REMOVE INSULATION FROM ALL PIPES AND
FITTINGS WITHIN THE AREA OF WORK ON THE
FOLLOWING SYSTEMS: HEATING WATER
RETURN, HEATING WATER SUPPLY.
GENERAL NOTES
2" VTR
COND. RETURN PUMP
2"
2-1/2"
2"
2" 1-1/2"
1-1/2" 1"
1-1/4"
1-1/4"
1"
3/4"
1/2"
1/2"
1/2"
1/2"
1/2"
1/2"
1/2"
1/2"
1/2"
1/2"
1-1/2"
3/4"
3/4"
1/2"
1/2" 3/4"
1/2"
1-1/2"
2"
1-1/2"
1"
1"
1" 1"
2" 1/2" 1/2"
1" 3"
2"
1/2"
1/2"
1/2"
1"
1/2"
1/2"
1/2"
1/2"
1/2"
1-2 1-281-13
1-12
1-34
1-31 1-27
1-30
1-23
1-22
1-21
1-20
1-19
1-18
1-25 1-5
1-6
1-7
1-10
1-3 1-26
1-8
1-29
1-1
1-16
1-9
2-3
1-11
1-24
1-17
1-33
1-14
1-4
1-15
1-32
2-6 2-52-4
1 1
2 2
1 2
EXIST. PIPING
TO REMAIN
(TYP.)
1-36 1
1-35
1. DEMOLISH EXISTING VAV BOX. DEMOLISH PIPING
UP TO EXISTING ISOLATION VALVES.
2. EXISTING VAV TO REMAIN.
KEYED NOTES
x3 x4
SCALE: 1/16" = 1'-0"
48'8' 16' 32'0
PHASE 3A MECHANICAL
ROOF DEMOLITION PLAN
1/16" = 1'-0"
MD103
PLAN
NORTH
1. EXISTING ROOFTOP FAN TO BE DEMOLISHED.
ROOF PENETRATION TO BE TEMPORARILY
CAPPED FOR CONNECTION TO NEW EQUIPMENT.
2. EXISTING AIR HANDLER UNIT TO REMAIN.
KEYED NOTES
EXIST. DUCTWORK
AND PIPING TO
REMAIN (TYP.)
EXIST. EXHAUST
FAN TO REMAIN
(TYP.)
EXIST. EXHAUST
FAN TO REMAIN
(TYP.)
EXIST. EXHAUST
FAN TO REMAIN
(TYP.)
EXIST. DUCTWORK
TO BE DEMOLISHED
14x12
6" Ø
"Ø
6"Ø
8"Ø
12"Ø
6" Ø
6"Ø
36x22
6" Ø
6"Ø
"Ø
6" Ø
"Ø
6"Ø 6"Ø
6"Ø 10"Ø
14"Ø
6" Ø
10"Ø
8" Ø
8"Ø
6" Ø x1
6"Ø 6"Ø
8"Ø
8" Ø
10"Ø
8"Ø 10x10
8" Ø
8" Ø
6" Ø
"Ø
8"Ø
8" Ø
10"Ø
8" Ø
10x10
"Ø
6" Ø
6"Ø x1
10"Ø12x12
"Ø
"Ø
22x16
6" Ø
6" Ø
8"Ø 8"Ø
"Ø
10"Ø
6"Ø10"Ø
"Ø
10"Ø x1
2 10"Ø
10"Ø
6" Ø
6" Ø 8"Ø
6" Ø x1
10x10
8" Ø
8" Ø
16x12
6" Ø
8"Ø
8" Ø
8"Ø6"Ø10"Ø
"Ø
6"Ø10"Ø
10"Ø 6"Ø
8" Ø
6"Ø10"Ø 22x16
"Ø x1
8"Ø8"Ø
8"Ø8"Ø
"Ø
8"Ø8"Ø
6" Ø
6" Ø
"Ø
"Ø
18x14 x1
6" Ø
"Ø
6"Ø10"Ø
6"Ø10"Ø
6"Ø
"Ø 8" Ø
6"Ø10"Ø
"Ø
8"Ø
6" Ø
12"Ø
6" Ø
6"Ø
10"Ø
10"Ø
44x24
"Ø x1
10x10 x1
6"Ø
12x10 x1
8"Ø8"Ø
10"Ø
14x1212x1010"Ø x1 x1
20x1212x12
8" Ø
12"Ø
36x20 x1 x1
"Ø x1
12"Ø12"Ø x1
10"Ø x1
12x1210"Ø
10"Ø x1
10"Ø x1
610"Ø x1
10"Ø
12"Ø
"Ø
10"Ø
8" Ø
SCALE:
PHASE 3A MECHANICAL
HVAC NEW WORK PLAN
3/16" = 1'-0"
MH101
0 4' 8' 16'
SCALE: 3/16"= 1'-0"
2'
KEYED NOTES
1. 14"x12" EXHAUST DUCTWORK DOWN FROM
ROOF.
2. SUPPLY AND RETURN AIR DUCTWORK DOWN
FROM AHU-1 ON MEZZANINE.
3. PROVIDE VAV TERMINAL BOX WITH CONTROLLER
TO INTERFACE WITH BUILDING AUTOMATION
SYSTEM.
VAV
1-2
VAV
1-28VAV
1-13
VAV
1-12
VAV
1-34
VAV
1-31
VAV
1-27
VAV
1-30
VAV
1-23
VAV
1-22
VAV
1-21
VAV
1-20
VAV
1-19
VAV
1-18
VAV
1-25
VAV
1-5
VAV
1-6
VAV
1-7
VAV
1-10
VAV
1-3
VAV
1-26
VAV
1-8
VAV
1-29
VAV
1-1
VAV
1-16
VAV
1-9
EXIST.
VAV 2-3
VAV
1-11
VAV
1-24
VAV
1-17
VAV
1-33
VAV
1-14
VAV
1-4
VAV
1-15
VAV
1-32
VAV
1-36
EAG-3
EAG-3
EAG-2
EAG-1
SAD-1
SAD-2
SAD-1
SAD-3
SAD-2
SAD-3
SAD-1
SAD-1
SAD-1
100 SAD-2
SAD-2
SAD-2
SAD-3
SAD-3
SAD-3
SAD-2
SAD-3
SAD-3
SAD-2
SAD-2
115SAD-2
SAD-2
SAD-3
VAV
1-35 3
SAD-3
SAD-3
SAD-1
SAG-1
SAD-2
SAD-3
SAD-3
SAD-3
SAD-2
SAD-4
SAD-3
SAD-3
RAG-6
RAG-1
RAG-3
RAG-3
RAG-3
RAG-2
RAG-5
RAG-3
RAG-3
RAG-2
RAG-3
RAG-5
RAG-5
RAG-5
RAG-4
RAG-4
RAG-4
RAG-5
RAG-5
RAG-5
RAG-4
RAG-3
RAG-3
RAG-4
RAG-4
RAG-4
DUCTWORK
INSTALLED IN
PHASE 2A
EXIST. DUCTWORK
TO BE REMOVED IN
PHASE 3B
(NOT IN CONTRACT)
RAG-4
RAG-4
SAD-3
SAD-3
SAD-2
RAG-3
SAD-2
RAG-3
RAG-4
SAD-3
RAG-4
SAD-3
RAG-4
SAD-3
RAG-4
SAD-3
SAD-2
SAD-2
SAD-2
SAD-2
SAD-2
EXIST. DUCTWORK
TO BE REMOVED IN
PHASE 3B
(NOT IN CONTRACT)
36x22
44x24
SCALE: 1/16" = 1'-0"
48'8' 16' 32'0
PHASE 3A MECHANICAL
ROOF NEW WORK PLAN
1/16" = 1'-0"
MH102
PLAN
NORTH
KEYED NOTES
1. PROVIDE FAN ON ROOF CURB. MODIFY EXISTING
ROOF CURB FOR INSTALLATION OF FAN AND
FOR WEATHER TIGHT INSTALLATION.
2. CONNECT NEW SUPPLY AND RETURN AIR
DUCTWORK TO EXISTING AHU-1.
3. MODIFY EXISTING STEEL GRATE PENETRATION
FOR DUCTWORK DOWN FROM MEZZANINE AREA.
EF-3 1
EXIST. DUCTWORK
EXIST. AHU-6
EXIST. AHU-5
EXIST. AHU-4
EXIST. AHU-2
EXIST. AHU-1 2
EXIST. EXHAUST FAN
(TYP.)
EXIST. EXHAUST
FAN TO REMAIN
(TYP.)
EXIST. EXHAUST FAN
(TYP.)
PHASE 3A MECHANICAL
MEZZANNE ENLARGED PLAN
1/4" = 1'-0"
MH102
PLAN
NORTH
8'0 2' 4' 12'
SCALE: 1/4"= 1'-0"
GENERAL NOTES
1. PROVIDE ALUMINUM JACKETING ON ALL
DUCTWORK INSULATION IN THE MEZZANINE
AREA.
SCALE:
PHASE 3A MECHANICAL
PIPING NEW WORK PLAN
3/16" = 1'-0"
MP101
0 4' 8' 16'
SCALE: 3/16"= 1'-0"
2'
VAV
1-2
VAV
1-28
VAV
1-13
VAV
1-12
VAV
1-34
VAV
1-31
VAV
1-27
VAV
1-30
VAV
1-23
VAV
1-22
VAV
1-21
VAV
1-20
VAV
1-19
VAV
1-18
VAV
1-25
VAV
1-5
VAV
1-6
VAV
1-7
VAV
1-10
VAV
1-3
VAV
1-26
VAV
1-8
VAV
1-29
VAV
1-1
VAV
1-16
VAV
1-9
EXIST.
VAV 2-3
VAV
1-11
VAV
1-24
VAV
1-17
VAV
1-33
VAV
1-14
VAV
1-4
VAV
1-15
VAV
1-32
EXIST.
VAV 2-6 EXIST.
VAV 2-5
EXIST.
VAV 2-4
KEYED NOTES
1. PROVIDE TERMINAL UNIT. CONNECT TO
EXISTING HTWS AND HTWR BRANCH PIPING.
PROVIDE WITH 3-WAY CONTROL VALVE.
2. HOT TAP PROVIDED AND INSTALLED PIPING
SERVING VAV BOX INTO EXISTING PIPING.1
1 1
VAV
1-36 1
VAV
1-35
EXIST. 2-1/2" HWR
EXIST. 3" HWR
EXIST. 1/2" HWS
EXIST. 3/4" HWS
EXIST. 3/4" HWS
EXIST. 1" HWS
EXIST. 1" HWS
EXIST. 1" HWS
AND HWR
EXIST. 2" HWR
EXIST. 2" HWR
EXIST. 2" HWR
EXIST. 1-1/4" HWS
EXIST. 1" HWS
EXIST. 1-1/4" HWS
EXIST. 1-1/2" HWS
EXIST. 1-1/2" HWS
EXIST. 2" HWR
EXIST. 1-1/2"
HWR
EXIST. 1-1/2" HWR
NEW 1/2" HWS
AND HWR
NEW 1/2" HWS
AND HWR
GENERAL NOTES
1. PROVIDE INSULATION FOR ALL NEW AND
EXISTING HEATING WATER PIPING.
T
T
T
T
T
T
T T T
T T
T
T
T
T
T
T
T
T
T
T
T
T T
T
T
T
T
T
T
T
T
PIPE PENETRATION NOTES:
1. PROVIDE PITCH POCKET CONSTRUCTION, ADDITIONAL FLASHING, OR
WEATHER CAP AS REQUIRED FOR WATERPROOF CONSTRUCTION. DO NOT
MECHANICALLY ATTACH PIPE TO STRUCTURE IN ANY WAY.
2. SPACE BETWEEN PIPE AND SLEEVE SHALL BE FREE OF ANY FOREIGN
MATERIALS.
3. PIPE SHALL NOT CONTACT STRUCTURE AT ANY TIME. WEDGES ARE NOT BE
USED TO MAINTAIN PIPE POSITION.
4. PIPE MUST BE CENTERED IN OPENING.
SCALE:
PIPE PENETRATION DETAIL
NOT TO SCALE
CAULK ALL JOINTS
AND SLEEVE ENDS
WATERTIGHT
PIPING
SCH. 40 PIPE STEEL SLEEVE
FIRE STOP MATERIAL
(FOR FIRE RATED
PARTITIONS)
PIPE INSULATION AS APPLICABLE
PARTITION
TO UNISTRUT P2500 SERIES
PIPE STRAP
(TYP.)
TO UNISTRUT P3400 SERIES PIPE
CLAMPS
(TYP.)
TO UNISTRUT P 1000 12 GA
CHANNEL
(TYP.)
SECURE W/APPROVED ANCHOR TO
MATCH BASE MATERIAL AND LOAD
REQUIREMENTS
INSULATE AS REQD
CONC. OR MASONRY WALL
TO UNISTRUT P 1000 12 GA
CHANNEL
(TYP.)
SECURE W/APPROVED ANCHOR TO
MATCH BASE MATERIAL AND LOAD
REQUIREMENTS
INSULATE AS REQD
CONC OR MASONRY WALL
NOTE:
PROVIDE MIN ANCHOR
SUPPORT SPACING
EVERY 3' VERTICALLY
FOR PIPES < 4"Ø
FOR CONDUIT <
2"Ø
SCALE:
PIPING WALL SUPPORT DETAIL
NOT TO SCALE
EXTERNALLY
INSULATED RIGID GALV
SHT MTL ROUND DUCT
EXTERNALLY
INSULATED
PRIMARY SA
DUCTS
AIR FLOW
EXTERNALLY INSULATED
SUPPLY DUCT
TRANSITION
AS REQUIRED
HEATING WATER REHEAT
COIL
H.P. FLEX
(12" MAX
LENGTH)
CONTROL PANEL. LOCATE FOR OPTIMUM
ACCESS ABOVE CEILING. MAINTAIN MFR'S
RECOMMENDED ACCESS CLEARANCESHIGH EFF TAKE-OFF
FITTING (W/O DAMPER).
AIR FLOW
REDUCING OR ENLARGING
TRANSITION AS REQUIRED
(W/O DAMPER).
EXTERNALLY
INSULATED RIGID GALV
SHT MTL ROUND DUCT
EXTERNALLY
INSULATED GALV
SHT MTL DUCT
SEE BELOW FOR DUCT
CONTINUATION TO BOX
EXTERNALLY
INSULATED GALV
SHT MTL DUCT
ALTERNATE TAKEOFF FOR
BOXES WITH TAKEOFF
FROM END OF RECT DUCT
SCALE:
SINGLE DUCT VAV BOX DETAIL
NOT TO SCALE
SCALE:
CLEVIS HANGER DETAIL
NOT TO SCALE
HEAVY DUTY CLEVIS
HANGER: MSS SP-69 AND
MSS SP-58
PIPE
RIGID INSULATION INSERT
(12" LONG, 180^ ARC)
CLEVIS HANGER WITH
INSULATION SHIELD
INSULATION
BOLT & NUT
SUPPORT NUT
LOCKING NUT
TURNBUCKLE
W/LOCKNUT
HANGER ROD
12" MIN
12" MIN
SINGLE PIPE CLEVIS
HANGER
SCALE:
PIPE HANGER DETAILS
NOT TO SCALE
U-CLAMP OR
CONDUIT
CLAMP
GALVANIZED
IRON TRAPEZE
OR UNISTRUT
16 GAUGE
GALVANIZED
SHEET SHIELD
WRAPPED FULLY
AROUND
INSULATION
INSULATION
PIPE
PROVIDE A SECTION OF
HIGH COMPRESSION
STRENGTH INSULATION AT
EACH HANGER POINT.
INSULATION SHALL BE HALF
ROUND AND EXTEND 2"
BEYOND GALVANIZED
SHIELD EACH WAY.
16 GAUGE
GALVANIZED
SHEET SHIELD
WRAPPED FULLY
AROUND
INSULATION
INSULATION
PIPE
AIR FLOW
KEYED NOTES
INSTALL BALANCING VALVE WITH
MINIMUM OF 3 STRAIGHT PIPE
DIAMETERS UPSTREAM AND 1
STRAIGHT PIPE DIAMETER
DOWNSTREAM.
MAINTAIN 6" MINIMUM CLEARANCE
ABOVE TEST PLUG TO ALLOW
GAUGE TO BE INSERTED. DO NOT
COVER PLUG WITH INSULATION.
INSTALL SWING JOINTS AT COIL
CONNECTIONS.
CONNECT EXISTING BRANCH LINES
FROM TO NEW HEATING WATER
COIL.
PROVIDE COILS WITH INLET
STRAINERS AND CAPPED HOSE
CONNECTION BLOW DOWN VALVES.
INSTALL MANUAL AIR VENTS IN
SUPPLY AND RETURN COIL BRANCH
PIPING AS FOLLOWS:
A) IN PIPING HIGH POINT WHEN
PIPING IS ABOVE MAIN.
B) CLOSE TO COIL WHEN PIPING IS
NOT ABOVE MAIN (SIDE
CONNECTION).
NC
NO
C
HTWS
EXIST. SHUT-OFF
VALVE (TYP.)
BALANCING VALVE
3-WAY CONTROL VALVE
PLUG VALVE, ADJUST
TO EQUAL GPM THRU
COIL AT DESIGN FLOW
TEST PLUG (TYP.)
1/2" PLUGGED DRAIN VALVE COIL
MANUAL AIR VENT,
3/8" BALL VALE (TYP.)
SCALE:
HEATING WATER COIL DETAIL
NOT TO SCALE
CONNECT NEW HTWR TO
EXIST. ISOLATION VALVE
HTWR
CONNECT NEW HTWS TO
EXIST. ISOLATION VALVE
TRANSITION
AS REQUIRED
HARD METAL ROUND DUCT RUN OUT TO
DIFFUSER. SEE PLAN FOR SIZE
SAME SIZE AS GRILLE
NECK
REDUCER IF REQ'D.
BUTTERFLY DAMPER SHALL BE USED
AT THIS LOCATION OR AT
CONNECTION OF RUN-OUT TO MAIN
DUCT.
WORM GEAR DRIVE,
STAINLESS STEEL STRAP
LAY-IN GRILLE SHOWN.
SURFACE MOUNTED SIMILAR
SCALE:
TYPICAL RETURN/EXHAUST GRILLE CONNECTION DETAIL
NOT TO SCALE
AREAS WITH
HARD OR LAY
IN CEILINGS
PROVIDE MANUAL OPPOSED DAMPER IN EACH BRANCH LINE
UNLESS OTHERWISE NOTED ON DRAWINGS. DAMPERS SHALL
BE INSTALLED IN ACCESSIBLE LOCATION NEAR TRUNK DUCT
AND MINIMUM OF 5'-0" FROM ANY AIR INLET OR OUTLET
DEVICE. COORDINATE W/ ACCESS DOORS IN NON-ACCESSIBLE
CEILINGS.
TRUNK
DUCT
OVAL BRANCH
DUCT
45° CLINCH COLLAR PER SMACNA
USE AT ALL BRANCH TAPS
UNLESS
SPLITTER DAMPERS ARE
INDICATED.
BELL-MOUTH
FITTING
NOTE:
DAMPERS SHALL BE PROVIDED IN ALL BRANCH RUN-OUTS TO DIFFUSERS, R.A AND EXHAUST GRILLES, UNLESS SPECIFICALLY NOTED OTHERWISE ON DRAWINGS.
LOCATE DAMPERS SO THEY ARE ACCESSIBLE FROM LAY-IN CEILING OR ACCESS DOORS.
SCALE:
BRANCH DUCT TAP DETAIL
NOT TO SCALE
ROUND
DUCT
DUCT HANGERS, ATTACH TO THE
STRUCTURE ABV.
RECTANGULAR, ROUND,
OR OVAL, DUCT MAIN
WITH EXTERNAL
INSULATION
CEILING DIFFUSER
SCALE:
TYPICAL DIFFUSER CONNECTION DETAIL
NOT TO SCALE
DUCT HANGERS, ATTACH TO THE STRUCTURE ABV.
RECTANGULAR, ROUND, OR OVAL DUCT MAIN WITH
EXTERNAL INSULATION
CEILING DIFFUSER
AREAS WITH
HARD OR LAY
IN CEILINGS
AREAS ABOVE
CEILING (TYP.)
ROUND DUCT WITH EXTERNAL
INSULATION
ATTACH THE FLEXIBLE DUCT TO
THE RIGID DUCT AND THE
DIFFUSER USING TWO (2) BANDS;
ONE FOR THE DUCT AND ONE FOR
THE INSULATION.
U.L. LISTED FLEXIBLE DUCT.
SUPPORT TO PREVENT SAG.
FLEXIBLE DUCT SHALL BE LESS
THAN 5 FT. IN LENGTH AND SHALL
NOT BE USED FOR BENDS
GREATER THAN 45°.
MANUAL DAMPER WITH LOCKING
QUADRANT REGULATOR.
RIGID 90° DUCT ELBOW
WITH EXTERNAL
INSULATION
ATTACH THE FLEXIBLE DUCT TO
THE RIGID DUCT AND THE
DIFFUSER USING TWO (2) BANDS;
ONE FOR THE DUCT AND ONE FOR
THE INSULATION.
U.L. LISTED FLEXIBLE DUCT.
SUPPORT TO PREVENT SAG.
FLEXIBLE DUCT SHALL BE LESS
THAN 5 FT. IN LENGTH AND SHALL
NOT BE USED FOR BENDS
GREATER THAN 45°.
MANUAL DAMPER WITH LOCKING
QUADRANT REGULATOR.
RIGID 90° DUCT ELBOW
WITH EXTERNAL
INSULATION
ROUND DUCT WITH EXTERNAL
INSULATION
SCALE:
TURNING VANE DETAIL
NOT TO SCALE
TURNING VANES, TYPICAL
TURNS 45° OR LARGER
RUNNER
INSTALL VANES
TANGENT TO
AIRSTREAM
DOUBLE SIDED TURNING
VANES REQUIRED WHERE
DUCT HEIGHT IS 24" OR
GREATER.
TOP RUNNER NOT SHOWN FOR
CLARITY.
NUMBER AND CONFIGURATION OF
VANES PER SMACNA STANDARDS.
20% MAXIMUM
AREA REDUCTION
R=H (MIN.)
H
DIM. "D"
ELEVATION
VIEW
PLAN
VIEW
DUCT DIM.
(SEE PLAN)
DUCT "VENTURI"
DEPRESSION DETAIL
NOTE: USE DETAIL
WHERE REQUIRED BY
FIELD CONDITIONS.
H R
TRANS.
DN.
TRANS.
UP
SCALE:
DUCT DEPRESSION FOR STRUCTURAL CONFLICTS DETAIL
NOT TO SCALE
MIN. 2/3
"D"
TYPICAL
OBSTRUCTION TO
DUCT PATH
3"
CABLE WRAP
AROUND BEAM
AND BAR JOIST
CL20
DUCTMATE
CLUTCHERS
WR20 CABLE
DUCT
DUCT
INSULATION
THREADED ROD
DOUBLE NUTUNISTRUT OR
ANGLE
UNISTRUT BAR
BAR JOIST
CL20
DUCTMATE
CLUTCHER OR
EQUAL
DUCTMATE
WR20 CABLE
OR EQUAL
MINIMUM 3/8"
DIA. THREADED
ROD
12 GAUGE
GALVANIZED
STEEL
DUCT
DUCT
INSULATION
DOUBLE NUT
DUCT
EXTERNAL
INSULATION WHERE
SPECIFIED
NOTE: FOR SIZES UP TO 60"
WITH 10' MAXIMUM SPACING.
NOTE: SEMI-CIRCLE
HANGER. 61"-72" DIAMETER
WITH 10' MAXIMUM
SPACING.
END VIEW
ELEVATION VIEW
2"3 1/2" 1"
NOTE: FOR SIZES UP TO 60"
WITH 10' MAXIMUM SPACING.
SINGLE
DOUBLE
SCALE:
DUCT HANGER DETAILS
NOT TO SCALE
NOTE: 10' MAXIMUM SPACING.
97-120
85-96
72-84
61-72
DUCT SIZE (IN.) STRUT SIZE
1 5/8 X 1 5/8 X 12 GA
N/A
N/A
N/A
2 1/2 X 2 1/2 X 1/4
2 X 2 X 1/4
N/A
ANGLE SIZE
3 X 3 X 1/4
3/8
ROD SIZE
3/8
3/8
3/8
R = RADIUS OF CURVE
H = HEIGHT
D = DIAMETER
EXHAUST FAN SCHEDULE
BASIS
OF DESIGN MAX
SONES
VOLTS/
PHASE
OTHER AS
NOTED
OPER.
WEIGHT
(LBS)
MARK LOCATION SERVES
RPMDRIVES.P.CFM
FAN DATA
POWER
HP
CONTROL INTERLOCKS
SWITCH
REMARKS
EF-3 GREENHECK
CUE-140HP-VG
103,104, 105,128ROOF CONSTANTNO 683/416.21,8502 -800 DIRECT
FAN
TYPE
CENTRIFUGAL 115/1
FLA MCA MOP
ELECTRICAL DATA
10 12.5 20
SINGLE DUCT VAV TERMINAL SCHEDULE
BOX TYPEBASIS OF
DESIGN
MFG.
BOX
MIN.
CFM
MFG.
BOX
MAX.
CFM
CFM DATA
INLET
SIZE
REHEAT/HEATING COIL DATA
MBH EWT/LWT °F EAT °F GPM
MAX.
WPD
FT.HD.
MAX
APD
IN.WC
REMARKS
SINGLE DUCT
REHEAT 180/160 55 0.760.02 SEE NOTES
DUCT CONN.
COIL
POSITION
DISCHARGE
SEE NOTESDISCHARGE
SEE NOTESDISCHARGE
SEE NOTESDISCHARGE
COOLING/
HEATING
CFM
MARK
VAV-1-1
VAV-1-2
VAV-1-3
VAV-1-4
VAV-1-5
VAV-1-6
VAV-1-7
LAT °F
114.42
MIN.
COOLING/
HEATING
CFM
SEE NOTESDISCHARGE
VAV-1-8
VAV-1-9
VAV-1-10
VAV-1-11
VAV-1-12
VAV-1-13
VAV-1-14
VAV-1-15
VAV-1-16
VAV-1-17
VAV-1-18
VAV-1-19
VAV-1-20
VAV-1-21
SEE NOTESDISCHARGE
SEE NOTESDISCHARGE
SEE NOTESDISCHARGE
SEE NOTESDISCHARGE
SEE NOTESDISCHARGE6"Ø
SEE NOTESDISCHARGE
SEE NOTESDISCHARGE
SEE NOTESDISCHARGE
SEE NOTESDISCHARGE
SEE NOTESDISCHARGE
SEE NOTESDISCHARGE
SEE NOTESDISCHARGE
SEE NOTESDISCHARGE
SEE NOTESDISCHARGE
SEE NOTESDISCHARGE
SEE NOTESDISCHARGE
108.49
106.65
111.25
98.33
109.94
97.86
92.51
92.24
110.05
0.64
1.0
0.95
1.14
1.15
1.1
TRANE VCWF
SINGLE DUCT
REHEAT
SINGLE DUCT
REHEAT
SINGLE DUCT
REHEAT
SINGLE DUCT
REHEAT
SINGLE DUCT
REHEAT
SINGLE DUCT
REHEAT
SINGLE DUCT
REHEAT
SINGLE DUCT
REHEAT
SINGLE DUCT
REHEAT
SINGLE DUCT
REHEAT
SINGLE DUCT
REHEAT
SINGLE DUCT
REHEAT
SINGLE DUCT
REHEAT
SINGLE DUCT
REHEAT
SINGLE DUCT
REHEAT
SINGLE DUCT
REHEAT
SINGLE DUCT
REHEAT
SINGLE DUCT
REHEAT
SINGLE DUCT
REHEAT
SINGLE DUCT
REHEAT
6.42
7.25
7.56
7.41
7.02
7.86
9.40
9.53
11.39
11.51
17.91
17.87
0.04
0.04
0.03
0.05
0.08
0.26
0.09
0.15
0.13
0.59
1.52
2.08
2.12
0.11
VAV-1-22 SEE NOTESDISCHARGESINGLE DUCT
REHEAT
VAV-1-23 SEE NOTESDISCHARGE107SINGLE DUCT
REHEAT 18.610.31 0.59
VAV-1-24 SEE NOTESDISCHARGE340 104.01135 1.0SINGLE DUCT
REHEAT 18.070.15 0.09
VAV-1-25 SEE NOTESDISCHARGE345 105.65135 1.0SINGLE DUCT
REHEAT 0.33 0.59
VAV-1-26 SEE NOTESDISCHARGE350 105.21135 1.0SINGLE DUCT
REHEAT 19.060.15 0.59
VAV-1-27 SEE NOTESDISCHARGE195 98.8170 0.93SINGLE DUCT
REHEAT 9.260.08
VAV-1-28 SEE NOTESDISCHARGE400 104.35175 1.3SINGLE DUCT
REHEAT 21.410.20 0.14
VAV-1-29 SEE NOTESDISCHARGE430 108.53430 1.0SINGLE DUCT
REHEAT 24.970.11 0.18
VAV-1-30 SEE NOTESDISCHARGE10"Ø575 99.28200 1.0SINGLE DUCT
REHEAT 27.610.17 0.18
VAV-1-31 SEE NOTESDISCHARGE12"Ø900 98.38500 1.75SINGLE DUCT
REHEAT 42.340.20 0.18
VAV-1-32 SEE NOTESDISCHARGE210 97.4180SINGLE DUCT
REHEAT 9.660.09
VAV-1-33 SEE NOTESDISCHARGE195 75SINGLE DUCT
REHEAT 9.260.08
VAV-1-34 SEE NOTESDISCHARGE200 98.3375SINGLE DUCT
REHEAT 9.400.08
VAV-1-35 SEE NOTESDISCHARGE300 125
VAV-1-36 SEE NOTESDISCHARGE6"Ø100 114.24100 6.420.02
1. ACTUATORS FOR VAV BOX AIR-CONTROL DAMPERS ARE TO BE FURNISHED AND INSTALLED BY THE AUTOMATIC TEMPERATURE CONTROLS SUPPLIER.
2. HEATING COIL CONTROL VALVES AND ACTUATORS ARE TO BE FURNISHED AND INSTALLED BY THE AUTOMATIC TEMPERATURE CONTROLS SUPPLIER.
3. MFCR'S INLET SIZE MAY NOT REPRESENT PRIMARY AIR DUCT SIZE. PROVIDE REDUCERS OR ENLARGERS FOR CONNECTING PRIMARY DUCT TO INLET.
4. PROVIDE BOXES WITH CONTROL ENCLOSURES, INTERNALLY LINED CASINGS, HEATING COILS LOCATED ON THE DISCHARGE POSITION.
5. FOR ALL BOXES, FIELD VERIFY RIGHT-HAND OR LEFT-HAND BOX AND COIL CONFIGURATIONS, DUCT CONNECTION CONFIGURATIONS, AND ELECTRICAL & CONTROL BOX
LOCATIONS PRIOR TO SUBMITTAL.
6. PROVIDE VAV BOXES WITH DOUBLE WALL CONSTRUCTION.
7. MINIMUM AND MAXIMUM AIRFLOWS LISTED ARE SHOWN FOR SIZING OF VAV BOXES. VAV BOXES MUST BE BALANCED TO COOLING AND HEATING DESIGN AIRFLOWS LISTED.
8. PROVIDE 3-WAY MODULATING CONTROL VALVES FOR ALL VAV TERMINAL UNITS.
NOTES:
60 500
320 130
320 130
320 130
320 130
320 130
330 130
165 1400
240 2000
8"Ø105 900
8"Ø105 900
6"Ø60 500
8"Ø105 900
10"Ø165 1400
6"Ø60 500
6"Ø60 500
6"Ø60 500
6"Ø60 500
6"Ø60 500
6"Ø60 500
6"Ø60 500
6"Ø60 500
6"Ø60 500
6"Ø60 500
6"Ø60 500
6"Ø60 500
6"Ø60 500
6"Ø60 500
0.940.04 0.72
180/144.27
180/147.46
180/143.87
180/142.8
180/147.09
180/141.90
180/124.75
180/131.61
180/161.32
1.480.94
1.010.76
107.54 0.980.74
1.000.75
1.090.79
0.15
1.0
18.95 180/142.12
1.45
0.96 1.56
98.81 0.93 1.45
0.94 1.48
TRANE VCWF
TRANE VCWF
TRANE VCWF
TRANE VCWF
TRANE VCWF
TRANE VCWF
TRANE VCWF
TRANE VCWF
TRANE VCWF
TRANE VCWF
TRANE VCWF
TRANE VCWF
TRANE VCWF
TRANE VCWF
TRANE VCWF
TRANE VCWF
TRANE VCWF
TRANE VCWF
TRANE VCWF
TRANE VCWF
TRANE VCWF
TRANE VCWF
TRANE VCWF
TRANE VCWF
TRANE VCWF
TRANE VCWF
TRANE VCWF
TRANE VCWF
TRANE VCWF
TRANE VCWF
TRANE VCWF
TRANE VCWF
TRANE VCWF
97.7313.900.07 1.39 3.92
0.64 0.76
SINGLE DUCT
REHEATTRANE VCWF
SINGLE DUCT
REHEATTRANE VCWF
NOTES:
1. PROVIDE WITH ALUMINUM CONSTRUCTION.
GRILLE, REGISTER AND DIFFUSER SCHEDULE
MARK TYPE USE
S
PANEL
SIZE IN.
NECK
SIZE IN.
MAX CFM MAX PD
IN. WC FINISH PATTERN REMARKSR E
MAX. NOISE
CRITERIA (NC)
24X24 4-WAY SEE NOTESXSAD-1 110 OFF
WHITE
0.025 10
SEE NOTESXSAD-2 200 0.025 10OFF
WHITE
24X24 PERF. SEE NOTESXRAG-3 200 0.025 10OFF
WHITE
24X24 PERF. SEE NOTESXRAG-4 330 0.025 10OFF
WHITE
SAD-3 X
0.02539512Ø24X24XRAG-5 OFF
WHITE
SEE NOTES
SEE NOTES10
SAD-4 X
24X24 10Ø 350 0.025 OFF
WHITE
4-WAY
SEE NOTES
RAG-1 X 12X12 110 0.025 OFF
WHITE
SEE NOTES106Ø
8Ø
10Ø
6ØCEILING
MOUNTED
24X24
24X24
8Ø
12Ø
4-WAY
4-WAY 100.025 OFF
WHITE425
24X24 SEE NOTESXRAG-2 110 OFF
WHITE
0.025 106Ø PERF.
PERF.
PERF.
CEILING
MOUNTED
CEILING
MOUNTED
CEILING
MOUNTED
CEILING
MOUNTED
CEILING
MOUNTED
CEILING
MOUNTED
CEILING
MOUNTED
CEILING
MOUNTED
0.025315XRAG-6 OFF
WHITE
SEE NOTES10SIDEWALLCEILING
MOUNTED
24X24XEAG-1 CEILING
MOUNTED
24X24XEAG-2 CEILING
MOUNTED
24X24XEAG-3 CEILING
MOUNTED
PERF. SEE NOTES200 0.025 10OFF
WHITE
8Ø
SEE NOTES110 OFF
WHITE
0.025 106Ø PERF.
SEE NOTES0.02539512Ø OFF
WHITE
10PERF.
SAG-1 XCEILING
MOUNTED
SEE NOTES10X10 10x10 SIDEWALL 120.025 OFF
WHITE315
6"Ø60 500
6"Ø60 500
6"Ø60 500
6"Ø60 500
6"Ø60 500
6"Ø60 500
6"Ø60 500
6"Ø60 500
6"Ø60 500
6"Ø60 500
6"Ø60 500
6"Ø60 500 107.94 1.018.370.29 0.59180/143.27
6"Ø500
60 500
10X10 10x10
180/160 0.760.02 114.42 0.646.42
106.657.560.04 1.010.76
106.657.560.04 1.010.76
98.339.400.08 1.480.94
180/160
180/160
180/160
180/160
180/160
180/160
180/160
180/160
107.94 1.018.370.29 0.59180/143.27
107.94 1.018.370.29 0.59180/143.27
107.94 1.018.370.29 0.59180/143.27
107.94 1.018.370.29 0.59180/143.27
92.51 1.1411.39 2.080.15
180/160
180/160
180/160
180/160
180/160
180/130.07
180/160
180/160
180/160
180/160
180/160
ALARMING
FUNCTION POINT NAME DESCRIPTION SETTING
(WITH UNITS)
RANGE
(WITH UNITS)
IO
TYPE
ALARM CONDITION
(SEE NOTES)
ALARM
PRIORITY
PROOFS
SAFETIES
TBD MANUFACTURER'S PROOFS (SEE NOTE) TBD ALM/NORMAL TBD
TBD MANUFACTURER'S SAFETIES (SEE NOTE) TBD ALM/NORMAL TBD
HTG-V-S HEATING VALVE POSITION STATUS 0-100% OPEN AI ALM INFO
START/STOP SYS-OCC-C OCCUPANCY INPUT FROM SYSTEM SCHEDULER OCCUPIED(1)/UNOCCUPIED(2) NET-IN
ZN-OCC OCCUPANCY OVERRIDE FROM SPACE OCCUPIED(1)/UNOCCUPIED(2) BI
ZONE
TEMPERATURE
CONTROL
ZN-T ZONE TEMPERATURE 40 - 85°F AI ZONE TEMPERATURE BELOW 60°F
OR ABOVE 85°F INFO
ZN-T-SP ZONE TEMPERATURE SETPOINT OCCUPANCY
ADJUSTABLE 68 - 78°F AI
ZN-T-SP-UNOCC ZONE TEMPERATURE SETPOINT FOR UNOCCUPIED MODE 60 - 85°F NET-OUT
VAV-SA-F VAV SUPPLY AIRFLOW AS SCHEDULED AI
VAV-SA-F-SP VAV SUPPLY AIRFLOW SETPOINT RESET SCHEDULE NET-OUT
VAV-D-C VAV DAMPER COMMAND 0-100% OPEN AO
HTG-V-C VAV REHEAT VALVE COMMAND 0-100% OPEN AO
DAMPER
CONTROL
LOOP
CONFIGURATION
SETTINGS
PROPORTIONAL CONSTANT TBD
INTEGRAL CONSTANT TBD
BIAS TBD
MAXIMUM OUTPUT TBD
MINIMUM OUTPUT TBD
NOTES:
1. THE CONTRACTOR SHALL COMPLETE THE POINTS SCHEDULE AS INDICATED IN THE SPECIFICATION AND IN ACCORDANCE WITH THIS DRAWING.
2. UNIT MANUFACTURERS PROOFS AND SAFETIES: THE CONTRACTOR SHALL SHOW EACH PROOF AND SAFETY AS A SEPARATE ROW.
3. UNIT STATUS: SERVES AS A MONITORED POINT AT THE M&C SOFTWARE (FRONT-END) AND AS A HEATING/COOLING REQUEST TO THE BOILER, HEAT EXCHANGER, AND/OR
CHILLER SERVING THIS SYSTEM.
4. "TBD" = TO BE DETERMINED DURING COMMISSIONING.
DDCHTG-V-C
DA-TVAV-#-#-V
RETURN
VAV-SA-F
ZN-T
TO
H ZONE
SUPPLY
VAV-D-C
SEQUENCE OF OPERATION
VAV BOXES
RUN CONDITIONS - SCHEDULED:
THE UNIT SHALL RUN ACCORDING TO A USER DEFINABLE TIME SCHEDULE IN THE FOLLOWING MODES:
· OCCUPIED MODE: THE UNIT SHALL MAINTAIN
· A 75°F (ADJ.) COOLING SETPOINT
· A 70°F (ADJ.) HEATING SETPOINT.
· UNOCCUPIED MODE (NIGHT SETBACK): THE UNIT SHALL MAINTAIN
· A 85°F (ADJ.) COOLING SETPOINT.
· A 60°F (ADJ.) HEATING SETPOINT.
ALARMS SHALL BE PROVIDED AS FOLLOWS:
· HIGH ZONE TEMP: IF THE ZONE TEMPERATURE IS GREATER THAN THE COOLING SETPOINT BY A USER
DEFINABLE AMOUNT (ADJ.).
· LOW ZONE TEMP: IF THE ZONE TEMPERATURE IS LESS THAN THE HEATING SETPOINT BY A USER DEFINABLE
AMOUNT (ADJ.).
ZONE SETPOINT ADJUST:
THE OCCUPANT SHALL BE ABLE TO ADJUST THE ZONE TEMPERATURE HEATING AND COOLING SETPOINTS AT THE
ZONE SENSOR.
ZONE OPTIMAL START:
THE UNIT SHALL USE AN OPTIMAL START ALGORITHM FOR MORNING START-UP. THIS ALGORITHM SHALL MINIMIZE THE UNOCCUPIED WARM-UP OR COOL-DOWN PERIOD WHILE STILL ACHIEVING COMFORT CONDITIONS BY THE
START OF SCHEDULED OCCUPIED PERIOD.
ZONE UNOCCUPIED OVERRIDE:
A TIMED LOCAL OVERRIDE CONTROL SHALL ALLOW AN OCCUPANT TO OVERRIDE THE SCHEDULE AND PLACE THE UNIT INTO AN OCCUPIED MODE FOR AN ADJUSTABLE PERIOD OF TIME. AT THE EXPIRATION OF THIS TIME, CONTROL OF THE UNIT SHALL AUTOMATICALLY RETURN TO THE SCHEDULE.
SPACE OCCUPIED MODE:
· SPACE THERMOSTAT SHALL MODULATE PRIMARY AIR DAMPER TO MAINTAIN SPACE TEMPERATURE.
· UPON CALL FOR HEAT, THE PRIMARY DAMPER SHALL CLOSE TO MINIMUM POSITION. UPON FURTHER CALL
FOR HEAT WITH PRIMARY AIR DAMPER IN MINIMUM POSITION, THE REHEAT CONTROL VALVE SHALL OPEN
AND MODULATE IN SEQUENCE TO MAINTAIN SPACE TEMPERATURE SET POINT.
· UPON CALL FOR COOLING, THE REHEAT VALVE SHALL MODULATE CLOSED. UPON A FURTHER CALL FOR COOLING, THE AIR DAMPER SHALL MODULATE OPEN AS REQUESTED TO PROVIDE COOLING AS SENSED BY
THE SPACE SENSOR.
HEATING WATER REHEATING:
THE CONTROLLER SHALL MEASURE THE ZONE TEMPERATURE AND STAGE THE 3-WAY HEATING WATER VALVE TO
MAINTAIN THE HEATING AND COOLING MODE DISCHARGE AIR TEMPERATURES AS SCHEDULED.
THE REHEATING SHALL BE ENABLED WHENEVER:
· VAV BOX DAMPER IS IN THE OPEN POSITION AND IN THE HEATING MODE.
· VAV BOX DAMPER IS IN THE MINIMUM POSITION IN THE COOLING MODE.
IN THE OCCUPIED MODE WHEN SPACE TEMPERATURE CONDITIONS ARE MET AND THE VAV BOX DAMPER IS IN
THE MINIMUM
POSITION, THE CONTROLLER SHALL STAGE THE 3-WAY HEATING WATER VALVE TO MAINTAIN A DISCHARGE
AIR TEMPERATURE OF
75 °F IN THE COOLING MODE AND 70 °F IN THE HEATING MODE.
DISCHARGE AIR TEMPERATURE:
THE CONTROLLER SHALL MONITOR THE DISCHARGE AIR TEMPERATURE.
ALARMS SHALL BE PROVIDED AS FOLLOWS:
· HIGH DISCHARGE AIR TEMP: IF THE DISCHARGE AIR TEMPERATURE IS GREATER THAN 120°F (ADJ.).
· LOW DISCHARGE AIR TEMP: IF THE DISCHARGE AIR TEMPERATURE IS LESS THAN 40°F (ADJ.).
ZN-T-LL
ZN-T-SP
HTG-V-S
PROVIDE ZONE
THERMOSTAT(S) AS
SHOWN IN POINTS
SCHEDULE AND ON
PLANS
ZN-T-SP-UNOCC
VAV-SA-F-SP
TO DDC
SYS-OCC-C
ZN-OCC
NAME:
VAV BOX W/ REHEAT CONTROLS
NOT TO SCALE
M-701
A OR AMP AMPERE(S)
ACC AIR COOLED CHILLER
AC ALTERNATING CURRENT
AC AIR COMPRESSOR / AIR
CURTAIN
AF AMP FRAME
AFF ABOVE FINISHED FLOOR
AFG ABOVE FINISHED GRADE
AHU AIR HANDLING UNIT
AIC AMPERE INTERRUPTING
CAPACITY
AL ALUMINUM
AM AMMETER
ASYM ASYMMETRICAL
AT AMP TRIP
ATS AUTOMATIC TRANSFER
SWITCH
AUTO AUTOMATIC
AWG AMERICAN WIRE GAUGE
B BOILER
BC BRANCH CONTROLLER
BCW BARE COPPER WIRE
BFF BELOW FINISHED FLOOR
BFG BELOW FINISHED GRADE
BLDG BUILDING
C CONDUIT
CAT CATEGORY
CB CIRCUIT BREAKER
CCT CORRELATED COLOR
TEMPERATURE
CCTV CLOSED CIRCUIT
TELEVISION
CFCI CONTRACTOR FURNISHED
CONTRACTOR INSTALLED
CH CHILLER
CHWCP CHILLED WATER
CIRCULATING PUMP IN A
PRIMARY-SECONDARY
SYSTEM
CHWP CHILLED WATER PUMP
CHWSP CHILLED WATER SUPPLY
PUMP IN A PRIMARY-
SECONDARY SYSTEM
CKT CIRCUIT
CMH COMMUNICATIONS
MANHOLE
CP CONDENSATE PUMP
CPT CONTROL POWER
TRANSFORMER
CRAC COMPUTER ROOM AC UNIT
CRI COLOR RENDERING INDEX
CT CURRENT TRANSFORMER
CT COOLING TOWER
CU COPPER OR CONDENSING
UNIT
CWP CONDENSER WATER PUMP
D DEPTH
DC DIRECT CURRENT
DF DESTRATIFICATION FAN
DH or DUH DUCT HEATERS
DHWCP DOMESTIC HOT WATER
CIRCULATING PUMP
DISC DISCONNECT SWITCH
DOAS DEDICATED OUTSIDE AIR
SYSTEM (UNIT)
DPST DOUBLE POLE SINGLE
THROW
DPDT DOUBLE POLE DOUBLE
THROW
DSCU DUCTLESS SPLIT
CONDENSING UNIT
(POWERS THE DSS INDOOR
UNIT)
DSHP DUCTLESS SPLIT HEAT
PUMP (POWERS THE DSS
INDOOR UNIT)
DSS DUCTLESS SPLIT SYSTEM
(INDOOR UNIT)
DWBP DOMESTIC WATER
BOOSTER PUMP
DX DIRECT EXPANSION (DX)
COOLING COIL
EC EMPTY CONDUIT
EF EXHAUST FAN
ELEC ELECTRICAL
EMH ELECTRICAL MANHOLE
EMT ELECTRICAL METALLIC
TUBING
E or EMER EMERGENCY
EPA EFFECTIVE PROJECTED
AREA
EQUIP EQUIPMENT
ERV ENERGY RECOVERY
VENTILATOR
ERU ENERGY RECOVERY UNIT
EXIST or EX EXISTING
NOTE: ABBREVIATIONS ABOVE
ARE FOR ELECTRICAL SHEETS
ONLY. NOT ALL ABBREVIATIONS
SHOWN WILL BE USED ON THIS
PROJECT.
ABBREVIATIONS LIST
EUH ELECTRIC UNIT HEATER
EXP EXPLOSION PROOF
EWC ELECTRIC WATER COOLER
EWH ELECTRIC WATER HEATER
F FUSE
FACP FIRE ALARM CONTROL
PANEL
FCU FAN COIL UNIT
FLEX FLEXIBLE
FWE FURNISHED WITH
EQUIPMENT
G OR GND GROUND
GFGI GOVERNMENT FURNISHED
GOVERNMENT INSTALLED
GFI GROUND FAULT
INTERRUPTER
GRS GALVANIZED RIGID STEEL
CONDUIT
GUH GAS UNIT HEATER
GWH GAS WATER HEATER
H or HT HEIGHT
HAC HEATED AIR CURTAIN
HOA HAND-OFF AUTOMATIC
HP HORSE POWER
HP HEAT PUMP (OUTDOOR
PORTION OF SPLIT SYSTEM
HEAT PUMP, USE CU FOR
STANDARD DX OUTDOOR
UNIT)
HT HEAT TRACKING
HVU HEATING/VENTILATING UNIT
HWCP HEATING WATER
CIRCULATING PUMP IN A
PRIMARY-SECONDARY
SYSTEM
HWP HEATING WATER SUPPLY IN
A PRIMARY-ONLY SYSTEM
HWRP HOT WATER
RECIRCULATION PUMP
HWSP HEATING WATER SUPPLY
PUMP IN A PRIMARY-
SECONDARY SYSTEM
HWUH HOT WATER UNIT HEATER
HZ HERTZ
IDS INTRUSION DETECTION
SYSTEM
IMC INTERMEDIATE METAL
CONDUIT
IRH INFRARED HEATER
J OR JB JUNCTION BOX
K KILO
KAIC THOUSAND AMPERE
INTERRUPTING CAPACITY
KCM OR KCMIL THOUSAND OF CIRCULAR
MILS
KEF KITCHEN EXHAUST FAN
KH KITCHEN HOOD
KV KILOVOLT
KVA KILOVOLT-AMPERES
KW KILOWATT
KWHR KILOWATT-HOUR
L LENGTH
LA LIGHTNING ARRESTOR
LAN LOCAL AREA NETWORK
LAV LAVATORY
LM LOCKHEED MARTIN
LTG LIGHTING
MAU MAKE-UP AIR UNIT
MAX MAXIMUM
MCA MINIMUM CIRCUIT AMPACITY
MCB or MB MAIN CIRCUIT BREAKER
MCC MOTOR CONTROL CENTER
MGB MAIN GROUND BAR
MH MANHOLE or MOUNTING
HEIGHT
MIN MINIMUM
MLO MAIN LUGS ONLY
MOD MOTOR OPERATED DAMPER
MT or MTD MOUNT or MOUNTED
MRS MOTOR RATED SWITCH
N NEUTRAL
NEC NATIONAL ELECTRICAL
CODE
NEMA NATIONAL ELECTRICAL
MANUFACTURER'S
ASSOCIATION
NFPA NATIONAL FIRE
PROTECTION ASSOCIATION
NC NORMALLY CLOSED
NESC NATIONAL ELECTRICAL
SAFETY CODE
NL NIGHT LIGHT
NO NORMALLY OPEN
NTS NOT TO SCALE
P POLE(S) or PUMP
PA PUBLIC ADDRESS
PDU POWER DISTRIBUTION UNIT
PF POWER FACTOR
PH PHASE
PIU VAV TERMINAL UNIT WITH
PARALLEL OR SERIES FAN
(PRIMARY INDUCTION UNIT)
PMT PAD MOUNTED
TRANSFORMER
PNL PANEL OR PANELBOARD
PTAC PACKAGED THRU-WALL AIR
CONDITIONER
PVC POLYVINYL CHLORIDE
RECEPT or RECP RECEPTACLE
RF RETURN FAN
RH RADIANT HEATERS
(ELECTRIC)
RMC RIGID METAL CONDUIT
RMS ROOT MEAN SQUARE
RTU ROOF TOP UNIT
RVNR REDUCED VOLTAGE NON-
REVERSING
SA SURGE ARRESTOR
SCCR SHORT CIRCUIT CURRENT
RATING
SD SMOKE DAMPER
SF SUPPLY FAN
S/N SOLID NEUTRAL
SP SUMP PUMP
SPD SURGE PROTECTIVE DEVICE
SPDT SINGLE POLE DOUBLE
THROW
SPEC SPECIFICATIONS
SPST SINGLE POLE SINGLE
THROW
SWBD SWITCHBOARD
SWGR SWITCHGEAR
TMGB TELECOMMUNICATIONS
MAIN GROUNDING BUSBAR
TOL THERMAL OVERLOAD
TP TWISTED PAIR
TYP TYPICAL
U URINAL
UH UNIT HEATER
UG UNDERGROUND
UIO UNLESS INDICATED
OTHERWISE
UL UNDERWRITERS
LABORATORY
UTP UNSHIELDED TWISTED PAIR
V VOLTS
VA VOLT AMPERES
VAV VAV TERMINAL UNIT
VEF VEHICLE EXHAUST FAN
VM VOLTMETER
VRF VARIABLE REFRIGERANT
FLOW SYSTEM
W WATTS or WIRE or WIDTH
WC WATER CLOSET
WEF WELDING EXHAUST FAN
WH WATER HEATER
WHDM WATTHOUR DEMAND METER
WSHP WATER SOURCE HEAT
PUMP
WP WEATHERPROOF
XFMR TRANSFORMER
Z IMPEDANCE
GENERAL NOTES - ELECTRICAL:
1. THE DRAWINGS INDICATE THE GENERAL EXTENT OF WORK. THE DRAWINGS ARE NOT
INTENDED TO INDICATE OR DESCRIBE ALL WORK REQUIRED FOR THE FULL PERFORMANCE
AND COMPLETION OF THE REQUIREMENTS OF THE CONTRACT DOCUMENTS.
2. THE ENUMERATION OF PARTICULAR ITEMS OF WORK IN ONE PORTION OF THE CONTRACT
DOCUMENTS SHALL NOT BE CONSTRUED TO EXCLUDE OTHER ITEMS NECESSARY OR
IMPLIED THEREFROM.
3. THE CONTRACTOR IS RESPONSIBLE FOR THE COORDINATION OF WORK SEQUENCING SUCH
THAT NO WORK SHALL BE LEFT IN AN UNFINISHED OR INCOMPLETE CONDITION.
4. WORK SHALL CONFORM TO APPLICABLE INDUSTRY AND MANUFACTURER'S PUBLISHED
STANDARDS FOR QUALITY OF MATERIALS AND WORKMANSHIP, AS WELL AS, THE
REQUIREMENTS IN THESE DRAWINGS AND SPECIFICATIONS. ANY CONFLICTING
REQUIREMENTS OF THE SOURCES LISTED ABOVE SHALL BE BROUGHT TO THE
CONTRACTING OFFICER'S ATTENTION PRIOR TO PROCEEDING WITH THE WORK.
5. THE CONTRACTOR SHALL PROTECT ANY EXISTING, IN-PLACE, AND NEW WORK.
6. WORK NOTED "N.I.C." IS NOT MEANT TO BE PART OF THE CONSTRUCTION SCOPE OF WORK
AGREEMENT.
7. THE CONTRACTOR SHALL PAY FOR AND COORDINATE THE REMOVAL AND LEGAL DISPOSAL
OF MATERIALS AND RUBBISH.
8. ONCE ON SITE, THE CONTRACTOR SHALL VERIFY DIMENSIONS AND SHALL VERIFY NEW AND
EXISTING CONDITIONS, SHOWN ON THESE DRAWINGS. THE CONTRACTOR SHALL NOTIFY THE
CONTRACTING OFFICER IN WRITING OF ANY DIFFERING CONDITIONS BEFORE
COMMENCEMENT OF WORK.
9. DO NOT SCALE DRAWINGS; DIMENSIONS GOVERN, LARGE SCALE DETAILS GOVERN OVER
SMALL SCALE DETAILS. THE CONTRACTOR SHALL NOTIFY THE CONTRACTING OFFICER IN
WRITING OF ANY DIFFERING CONDITIONS BEFORE COMMENCEMENT OF WORK.
10. THE CONTRACTOR SHALL PERFORM WORK IN ACCORDANCE WITH APPLICABLE CODES,
ORDINANCES AND REGULATORY AGENCIES AND SHALL OBTAIN NECESSARY BUILDING AND
FIRE PERMITS FROM ALL AUTHORITIES HAVING JURISDICTION.
11. PIPE DUCTS AND BUS DUCTS THAT PENETRATE FLOOR SLABS OR WALL PARTITIONS SHALL
BE INSTALLED IN A MANNER THAT WILL PRESERVE THE MOISTURE RESISTIVENESS, FIRE
RATING, AND STRUCTURAL INTEGRITY OF THE BUILDING.
12. THE CONTRACTOR SHALL PLAN HIS/HER WORK TO PROVIDE ADEQUATE PROTECTION FOR
PERSONS AND PROPERTY, AND EXECUTE THE WORK IN SUCH A MANNER TO AVOID ANY
HAZARD TO PERSONS AND PROPERTY AS NECESSARY.
13. THE CONTRACTOR SHALL COORDINATE THE PHASING OF THE WORK TO BE PERFORMED IN
OR ABOUT EXISTING FACILITIES, IF APPLICABLE, WITH THE OWNER'S REPRESENTATIVE
PRIOR TO START OF SUCH WORK.
14. MINIMUM RACEWAY SIZE SHALL BE 3/4". INCREASE RACEWAY SIZE AS REQUIRED TO LIMIT
RACEWAY FILL RATIO TO LESS THAN 40% FULL.
15. THE ELECTRICAL CONTRACTOR SHALL CAREFULLY COORDINATE WORK WITH OTHER
TRADES THROUGH THE GENERAL CONTRACTOR AND SHALL BE RESPONSIBLE FOR
SECURING SPACE REQUIREMENTS FOR ELECTRICAL EQUIPMENT CLEARANCE AND CORRECT
ROUGH-IN LOCATIONS OF ELECTRICAL CONNECTIONS.
16. FEEDERS AND BRANCH CIRCUITS SHALL INCLUDE A GREEN INSULATED GROUND
CONDUCTOR, SIZE PER NATIONAL ELECTRICAL CODE, OR AS SHOWN, CONNECTED TO EACH
DEVICE AND OUTLET BOX ON THE CIRCUIT AND TO THE PANELBOARD GROUND BUS.
PROVIDE A DEDICATED NEUTRAL CONDUCTOR FOR EACH BRANCH CIRCUIT. MULTIPLE
BRANCH CIRCUITS IN ONE RACEWAY REQUIRE ONLY ONE GROUND CONDUCTOR. SINGLE
GROUND CONDUCTOR IN ONE RACEWAY MUST BE SIZED FOR THE LARGEST OVERCURRENT
DEVICE.
17. EXISTING ELECTRICAL WORK (NOT SHOWN) SHALL REMAIN, UNLESS INDICATED OTHERWISE.
SHOULD ANY EXISTING ELECTRICAL POWER, LIGHTING OR AUXILIARY CIRCUIT, FEEDER OR
EQUIPMENT BE SEVERED, DISCONNECTED OR DELETED IN THE PROCESS OF
CONSTRUCTION OR REMODELING WHICH IS DONE AS A RESULT OF CONTRACT PLANS AND
SPECIFICATIONS, AND UNLESS SPECIFICALLY DESIGNATED BY THE DRAWINGS TO BE
DELETED, THEN SAID CIRCUIT OR FEEDER SHALL BE RESTORED TO WORKING CONDITION.
THE RESTORATION SHALL INCLUDE RE-ROUTING, RELOCATION, RECONNECTION OR
REPLACEMENT AS MAY BE REQUIRED BY THE NEW WORK. ANY SUCH WORK REQUIRED
SHALL BE INCLUDED IN THE CONTRACT AND NO EXTRA COMPENSATION WILL BE GRANTED.
18. NEW WORK SHALL BE MADE TO TIE INTO THE EXISTING IN A UNIFORM MANNER, SIMILAR
ITEMS OF NEW WORK SHALL BE CHECKED AGAINST EXISTING WORK.
19. REFER TO ONE-LINE DIAGRAM, SCHEDULES AND RISER DIAGRAMS FOR CONDUCTOR AND
CONDUIT SIZES NOT SHOWN ON PLANS.
20. PROVIDE IS AN INCLUSIVE TERM USED TO DESCRIBE ASPECTS OF THE WORK TO BE
ACCOMPLISHED, AND IS HEREBY DEFINED TO REQUIRE TO STORE, FURNISH, INSTALL,
MOUNT, CONNECT, CONTROL AND POWER EQUIPMENT INDICATED, AS WELL AS
APPURTENANCES REQUIRED TO MAKE ELECTRICAL SYSTEMS OPERATE AS INDICATED
WITHIN THESE DRAWINGS AND SPECIFICATIONS AND TO FULFILL THE SCOPE OF WORK.
21. DEMOLISH IS AN INCLUSIVE TERM USED TO DESCRIBE ASPECTS OF THE WORK TO BE
ACCOMPLISHED, AND IS HEREBY DEFINED TO REQUIRE CONTRACTOR TO DISCONNECT
EQUIPMENT FROM CONNECTIONS, REMOVE FROM THE OWNER'S SITE, AND DISPOSE OF IN
ACCORDANCE WITH FEDERAL, STATE AND LOCAL LAWS AND ORDINANCES. COST OF
DISPOSAL IS ENTIRELY THE CONTRACTOR'S RESPONSIBILITY.
22. ALL CONDUCTORS ARE COPPER UNLESS SPECIFICALLY NOTED AS ALUMINUM.
23. CONTRACTOR SHALL FIELD VERIFY EXISTING CONDITIONS, DIMENSIONS AND…