This is a Plumbing General Purpose specification section (Section 22 00 00) for the "Design New HVAC System and Associated Upgrades B001 & B001A" federal construction project, dated March 5, 2026 (Addendum #1). The specification establishes technical requirements, standards, and execution procedures for all plumbing work associated with the project.

The specification requires 316L stainless steel pipe and fittings for the deionized water system, with joints to be welded and press-fit fittings prohibited. Valves must be bronze with threaded bodies for connections 2.5 inches and smaller, conforming to standards including ASME B16.34, MSS SP-85, and ANSI Z21.22/CSA 4.4 for relief valves. Pipe hangers and supports must conform to MSS SP-58 with specific type restrictions and installation requirements. The specification incorporates multiple industry standards including ICC IPC (2024), AWWA standards for water disinfection (C651, C652, C606), NFPA 90A for air systems, and ASME standards for valves and boiler controls. Government approval is required for shop drawings (SD-02), product data including backflow prevention assemblies (SD-03), test reports for backflow assemblies and disinfection (SD-06), and operation and maintenance data (SD-10). All plumbing systems must pass drainage and vent tests including smoke testing (or alternative peppermint testing with approval), building sewer tests, and water supply system tests. The entire domestic water distribution system requires disinfection using hypochlorite or liquid chlorine at a minimum 50 ppm concentration, with verification of at least 25 ppm residual chlorine maintained for 24 hours and bacteriological testing confirming zero coliform organisms per 100 milliliters before system acceptance.

View the file

Other files for this federal contract opportunity

Show all 18

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Desi gn New HVAC Syst em and Associ at ed Upgr ades B001 & B001A 5923EPHASE2B

SECTI ON 22 00 00

PLUMBI NG, GENERAL PURPOSE

11/ 15, CHG 4: 05/ 21

PART 1 GENERAL

1. 1 REFERENCES

The publ i cat i ons l i s t ed bel ow f or m a par t of t hi s speci f i cat i on t o t he ext ent r ef er enced. The publ i cat i ons ar e r ef er r ed t o wi t hi n t he t ext by t he basi c desi gnat i on onl y.

AMERI CAN NATI ONAL STANDARDS I NSTI TUTE ( ANSI )

ANSI Z21. 22/ CSA 4. 4 ( 2015; R 2020) Rel i ef Val ves f or Hot Wat er Suppl y Syst ems

AMERI CAN SOCI ETY OF MECHANI CAL ENGI NEERS ( ASME)

ASME B1. 20. 1 ( 2013; R 2018) Pi pe Thr eads, Gener al Pur pose ( I nch)

ASME B16. 34 ( 2021) Val ves - Fl anged, Thr eaded and Wel di ng End

ASME CSD- 1 ( 2021) Cont r ol and Saf et y Devi ces f or Aut omat i cal l y Fi r ed Boi l er s

AMERI CAN WATER WORKS ASSOCI ATI ON ( AWWA)

AWWA 10084 ( 2017) St andar d Met hods f or t he Exami nat i on of Wat er and Wast ewat er

AWWA C606 ( 2022) Gr ooved and Shoul der ed Joi nt s

AWWA C651 ( 2014) St andar d f or Di s i nf ect i ng Wat er Mai ns

AWWA C652 ( 2019) Di s i nf ect i on of Wat er - St or age Faci l i t i es

I NTERNATI ONAL CODE COUNCI L ( I CC)

I CC I PC ( 2024) I nt er nat i onal Pl umbi ng Code

MANUFACTURERS STANDARDI ZATI ON SOCI ETY OF THE VALVE AND FI TTI NGS

I NDUSTRY ( MSS)

MSS SP- 58 ( 2018) Pi pe Hanger s and Suppor t s - Mat er i al s, Desi gn and Manuf act ur e, Sel ect i on, Appl i cat i on, and I nst al l at i on

MSS SP- 85 ( 2011) Gr ay I r on Gl obe & Angl e Val ves Fl anged and Thr eaded Ends

NATI ONAL FI RE PROTECTI ON ASSOCI ATI ON ( NFPA)

NFPA 90A ( 2024) St andar d f or t he I nst al l at i on of

SECTI ON 22 00 00 Page 1 ADDENDUM #1

MARCH 5, 2026

Ai r Condi t i oni ng and Vent i l at i ng Syst ems

PLASTI C PI PE AND FI TTI NGS ASSOCI ATI ON ( PPFA)

PPFA Fi r e Man ( 2016) Fi r est oppi ng: Pl ast i c Pi pe i n Fi r e Resi st i ve Const r uct i on

1. 2 SUBMI TTALS

Gover nment appr oval i s r equi r ed f or submi t t al s wi t h a " G" or " S" c l assi f i cat i on. Submi t t al s not havi ng a " G" or " S" c l assi f i cat i on ar e f or Cont r act or Qual i t y Cont r ol appr oval . Submi t t he f ol l owi ng i n accor dance wi t h Sect i on 01 33 00 SUBMI TTAL PROCEDURES:

SD- 02 Shop Dr awi ngs

Pl umbi ng Syst em; G

Det ai l dr awi ngs consi st i ng of schedul es, per f or mance char t s, i nst r uct i ons, di agr ams, and ot her i nf or mat i on t o i l l ust r at e t he r equi r ement s and oper at i ons of syst ems t hat ar e not cover ed by t he Pl umbi ng Code. Det ai l dr awi ngs f or t he compl et e pl umbi ng syst em i ncl udi ng pi pi ng l ayout s and l ocat i ons of connect i ons; di mensi ons f or r oughi ng- i n, f oundat i on, and suppor t poi nt s; schemat i c di agr ams and wi r i ng di agr ams or connect i on and i nt er connect i on di agr ams. Det ai l dr awi ngs shal l i ndi cat e c l ear ances r equi r ed f or mai nt enance and oper at i on. Wher e pi pi ng and equi pment ar e t o be suppor t ed ot her t han as i ndi cat ed, det ai l s shal l i ncl ude l oadi ngs and pr oposed suppor t met hods. Mechani cal dr awi ng pl ans, el evat i ons, v i ews, and det ai l s, shal l be dr awn t o scal e.

SD- 03 Pr oduct Dat a

Recycl ed Cont ent f or St eel Pi pe; S

Backf l ow Pr event i on Assembl i es; G

Fi xt ur es

Li st of i nst al l ed f i x t ur es wi t h manuf act ur er , model , and f l ow r at e.

Labor at or y Si nks

Pl umbi ng Syst em

Di agr ams, i nst r uct i ons, and ot her sheet s pr oposed f or post i ng.

Manuf act ur er ' s r ecommendat i ons f or t he i nst al l at i on of bel l and spi got and hubl ess j oi nt s f or cast i r on soi l pi pe.

SD- 06 Test Repor t s

Test s, Fl ushi ng and Di si nf ect i on

Test r epor t s i n bookl et f or m showi ng al l f i el d t est s per f or med t o adj ust each component and al l f i el d t est s per f or med t o pr ove compl i ance wi t h t he speci f i ed per f or mance cr i t er i a, compl et i on and t est i ng of t he i nst al l ed syst em. Each t est r epor t shal l i ndi cat e t he f i nal posi t i on of cont r ol s.

SECTI ON 22 00 00 Page 2 ADDENDUM #1

Test of Backf l ow Pr event i on Assembl i es; G.

Cer t i f i cat i on of pr oper oper at i on shal l be as accompl i shed i n accor dance wi t h st at e r egul at i ons by an i ndi v i dual cer t i f i ed by t he st at e t o per f or m such t est s. I f no st at e r equi r ement exi st s, t he Cont r act or shal l have t he manuf act ur er ' s r epr esent at i ve t est t he devi ce, t o ensur e t he uni t i s pr oper l y i nst al l ed and per f or mi ng as i nt ended. The Cont r act or shal l pr ovi de wr i t t en document at i on of t he t est s per f or med and si gned by t he i ndi v i dual per f or mi ng t he t est s.

SD- 07 Cer t i f i cat es

Mat er i al s and Equi pment

Wher e equi pment i s speci f i ed t o conf or m t o r equi r ement s of t he ASME Boi l er and Pr essur e Vessel Code, t he desi gn, f abr i cat i on, and i nst al l at i on shal l conf or m t o t he code.

SD- 10 Oper at i on and Mai nt enance Dat a

Pl umbi ng Syst em; G

Submi t i n accor dance wi t h Sect i on 01 78 23 OPERATI ON AND

MAI NTENANCE DATA.

1. 3 STANDARD PRODUCTS

Speci f i ed mat er i al s and equi pment shal l be st andar d pr oduct s of a manuf act ur er r egul ar l y engaged i n t he manuf act ur e of such pr oduct s.

Speci f i ed equi pment shal l essent i al l y dupl i cat e equi pment t hat has per f or med sat i sf act or i l y at l east t wo year s pr i or t o bi d openi ng.

St andar d pr oduct s shal l have been i n sat i sf act or y commer ci al or i ndust r i al use f or 2 year s pr i or t o bi d openi ng. The 2- year use shal l i ncl ude appl i cat i ons of equi pment and mat er i al s under s i mi l ar c i r cumst ances and of s i mi l ar s i ze. The pr oduct shal l have been f or sal e on t he commer ci al mar ket t hr ough adver t i sement s, manuf act ur er s ' cat al ogs, or br ochur es dur i ng t he 2 year per i od.

1. 3. 1 Al t er nat i ve Qual i f i cat i ons

Pr oduct s havi ng l ess t han a t wo- year f i el d ser vi ce r ecor d wi l l be accept abl e i f a cer t i f i ed r ecor d of sat i sf act or y f i el d oper at i on f or not l ess t han 6000 hour s, excl usi ve of t he manuf act ur er ' s f act or y or l abor at or y t est s, can be shown.

1. 3. 2 Modi f i cat i on of Ref er ences

I n each of t he publ i cat i ons r ef er r ed t o her ei n, consi der t he advi sor y pr ovi s i ons t o be mandat or y, as t hough t he wor d, " shal l " had been subst i t ut ed f or " shoul d" wher ever i t appear s. I nt er pr et r ef er ences i n t hese publ i cat i ons t o t he " aut hor i t y havi ng j ur i sdi ct i on" , or wor ds of s i mi l ar meani ng, t o mean t he Cont r act i ng Of f i cer .

1. 3. 2. 1 Def i ni t i ons

For t he I nt er nat i onal Code Counci l ( I CC) Codes r ef er enced i n t he cont r act document s, advi sor y pr ovi s i ons shal l be consi der ed mandat or y, t he wor d

SECTI ON 22 00 00 Page 3 ADDENDUM #1

" shoul d" shal l be i nt er pr et ed as " shal l . " Ref er ence t o t he " code of f i c i al " shal l be i nt er pr et ed t o mean t he " Cont r act i ng Of f i cer . " For Navy owned pr oper t y, r ef er ences t o t he " owner " shal l be i nt er pr et ed t o mean t he " Cont r act i ng Of f i cer . " For l eased f aci l i t i es, r ef er ences t o t he " owner " shal l be i nt er pr et ed t o mean t he " l essor . " Ref er ences t o t he " per mi t hol der " shal l be i nt er pr et ed t o mean t he " Cont r act or . "

1. 3. 2. 2 Admi ni st r at i ve I nt er pr et at i ons

For I CC Codes r ef er enced i n t he cont r act document s, t he pr ovi s i ons of Chapt er 1, " Admi ni st r at or , " do not appl y. These admi ni st r at i ve r equi r ement s ar e cover ed by t he appl i cabl e Feder al Acqui s i t i on Regul at i ons ( FAR) i ncl uded i n t hi s cont r act and by t he aut hor i t y gr ant ed t o t he Of f i cer i n Char ge of Const r uct i on t o admi ni st er t he const r uct i on of t hi s pr oj ect . Ref er ences i n t he I CC Codes t o sect i ons of Chapt er 1, shal l be appl i ed appr opr i at el y by t he Cont r act i ng Of f i cer as aut hor i zed by hi s admi ni st r at i ve cogni zance and t he FAR.

1. 4 DELI VERY, STORAGE, AND HANDLI NG

Handl e, st or e, and pr ot ect equi pment and mat er i al s t o pr event damage bef or e and dur i ng i nst al l at i on i n accor dance wi t h t he manuf act ur er ' s r ecommendat i ons, and as appr oved by t he Cont r act i ng Of f i cer . Repl ace damaged or def ect i ve i t ems.

1. 5 REGULATORY REQUI REMENTS

Unl ess ot her wi se r equi r ed her ei n, pl umbi ng wor k shal l be i n accor dance wi t h I CC I PC.

1. 6 I NSTRUCTI ON TO GOVERNMENT PERSONNEL

When speci f i ed i n ot her sect i ons, f ur ni sh t he ser vi ces of compet ent i nst r uct or s t o gi ve f ul l i nst r uct i on t o t he desi gnat ed Gover nment per sonnel i n t he adj ust ment , oper at i on, and mai nt enance, i ncl udi ng per t i nent saf et y r equi r ement s, of t he speci f i ed equi pment or syst em.

I nst r uct or s shal l be t hor oughl y f ami l i ar wi t h al l par t s of t he i nst al l at i on and shal l be t r ai ned i n oper at i ng t heor y as wel l as pr act i cal oper at i on and mai nt enance wor k.

I nst r uct i on shal l be gi ven dur i ng t he f i r st r egul ar wor k week af t er t he equi pment or syst em has been accept ed and t ur ned over t o t he Gover nment f or r egul ar oper at i on. The number of man- days ( 8 hour s per day) of i nst r uct i on f ur ni shed shal l be as speci f i ed i n t he i ndi v i dual sect i on.

When mor e t han 4 man- days of i nst r uct i on ar e speci f i ed, use appr oxi mat el y hal f of t he t i me f or c l assr oom i nst r uct i on. Use ot her t i me f or i nst r uct i on wi t h t he equi pment or syst em.

When si gni f i cant changes or modi f i cat i ons i n t he equi pment or syst em ar e made under t he t er ms of t he cont r act , pr ovi de addi t i onal i nst r uct i on t o acquai nt t he oper at i ng per sonnel wi t h t he changes or modi f i cat i ons.

1. 7 ACCESSI BI LI TY OF EQUI PMENT

I nst al l al l wor k so t hat par t s r equi r i ng per i odi c i nspect i on, oper at i on, mai nt enance, and r epai r ar e r eadi l y accessi bl e. I nst al l conceal ed val ves, expansi on j oi nt s, cont r ol s, damper s, and equi pment r equi r i ng access, i n l ocat i ons f r eel y accessi bl e t hr ough access door s.

SECTI ON 22 00 00 Page 4 ADDENDUM #1

PART 2 PRODUCTS

2. 1 PI PE AND FI TTI NGS

2. 1. 1 Dei oni zed Wat er Pi pi ng

Pr ovi de 316L s t ai nl ess st eel pi pe and fittings for the deionized water system. Pipe shall conform to ASTM A312/A312M, schedule 40, iron pipe size.

Fittings shall conform to ASTM A403/A403M, type 316L. Joints for deionized water piping shall be welded. Press-fit fittings shall not be permitted.

2 . 1. 2 Pi pe Joi nt Mat er i al s

Joi nt s and gasket mat er i al s shal l conf or m t o t he f ol l owi ng:

a. Coupl i ng f or St ai nl ess St eel Pi pe: AWWA C606.

2. 1. 3 Pi pe I nsul at i on Mat er i al

I nsul at i on shal l be as speci f i ed i n Sect i on 23 07 00 THERMAL I NSULATI ON

FOR MECHANI CAL SYSTEMS.

2. 2 PI PE HANGERS, I NSERTS, AND SUPPORTS

Pi pe hanger s, i nser t s, and suppor t s shal l conf or m t o MSS SP- 58.

2. 3 VALVES

Val ves shal l be pr ovi ded on suppl i es t o equi pment and f i xt ur es. Val ves 2- 1/ 2 i nches and smal l er shal l be br onze wi t h t hr eaded bodi es f or pi pe and sol der - t ype connect i ons f or t ubi ng. Pr essur e r at i ngs shal l be based upon t he appl i cat i on. Gr ooved end val ves may be pr ovi ded i f t he manuf act ur er cer t i f i es t hat t he val ves meet t he per f or mance r equi r ement s of appl i cabl e MSS st andar d. Val ves shal l conf or m t o t he f ol l owi ng st andar ds:

Descr i pt i on St andar d

St eel Val ves, Socket Wel di ng and Thr eaded Ends

ASME B16. 34

Cast - I r on Gl obe and Angl e Val ves, Fl anged and Thr eaded Ends

MSS SP- 85

Temper at ur e and Pr essur e Rel i ef Val ves f or Hot Wat er Suppl y Syst ems

ANSI Z21. 22/ CSA 4. 4

SECTI ON 22 00 00 Page 5 ADDENDUM #1

Temper at ur e and Pr essur e Rel i ef Val ves f or Aut omat i cal l y Fi r ed Hot Wat er Boi l er s

ASME CSD- 1

Saf et y Code No. , Par t CW, Ar t i c l e 5

2. 4 MI SCELLANEOUS PI PI NG I TEMS

2. 4. 1 Escut cheon Pl at es

Pr ovi de one pi ece or spl i t hi nge met al pl at es f or pi pi ng ent er i ng f l oor s, wal l s, and cei l i ngs i n exposed spaces. Pr ovi de chr omi um- pl at ed on copper al l oy pl at es or pol i shed st ai nl ess st eel f i ni sh i n f i ni shed spaces.

Pr ovi de pai nt f i ni sh on pl at es i n unf i ni shed spaces.

2. 4. 2 Pi pe Sl eeves

Pr ovi de wher e pi pi ng passes ent i r el y t hr ough wal l s, cei l i ngs, r oof s, and f l oor s. Sl eeves ar e not r equi r ed wher e suppl y dr ai n, wast e, and vent ( DWV) pi pi ng passes t hr ough concr et e f l oor s l abs l ocat ed on gr ade, except wher e penet r at i ng a membr ane wat er pr oof f l oor .

2. 4. 3 Pi pe Hanger s ( Suppor t s)

Pr ovi de MSS SP- 58 Type 1 wi t h adj ust abl e t ype st eel suppor t r ods, except as speci f i ed or i ndi cat ed ot her wi se. At t ach t o st eel j oi st s wi t h Type 19 or 23 cl amps and r et ai ni ng st r aps. At t ach t o St eel W or S beams wi t h Type 21, 28, 29, or 30 cl amps. At t ach t o st eel angl es and ver t i cal web st eel channel s wi t h Type 20 cl amp wi t h beam cl amp channel adapt er . At t ach t o hor i zont al web st eel channel and wood wi t h dr i l l ed hol e on cent er l i ne and doubl e nut and washer . At t ach t o concr et e wi t h Type 18 i nser t or dr i l l ed expansi on anchor . Pr ovi de Type 40 i nsul at i on pr ot ect i on shi el d f or i nsul at ed pi pi ng.

2. 4. 4 Namepl at es

Pr ovi de 0. 125 i nch t hi ck mel ami ne l ami nat ed pl ast i c namepl at es, bl ack mat t e f i ni sh wi t h whi t e cent er cor e, f or equi pment , gages, t her momet er s, and val ves; val ves i n suppl i es t o f aucet s wi l l not r equi r e namepl at es.

Accur at el y al i gn l et t er i ng and engr ave mi ni mum of 0. 25 i nch hi gh nor mal bl ock l et t er i ng i nt o t he whi t e cor e. Mi ni mum si ze of namepl at es shal l be

1. 0 by 2. 5 i nches. Key namepl at es t o a char t and schedul e f or each syst em. Fr ame char t s and schedul es under gl ass and pl ace wher e di r ect ed near each syst em. Fur ni sh t wo copi es of each char t and schedul e.

PART 3 EXECUTI ON

3. 1 GENERAL I NSTALLATI ON REQUI REMENTS

Pi pi ng l ocat ed i n ai r pl enums shal l conf or m t o NFPA 90A r equi r ement s.

Pi pi ng l ocat ed i n shaf t s t hat const i t ut e ai r duct s or t hat encl ose ai r duct s shal l be noncombust i bl e i n accor dance wi t h NFPA 90A. I nst al l at i on of pl ast i c pi pe wher e i n compl i ance wi t h NFPA may be i nst al l ed i n accor dance wi t h PPFA Fi r e Man. The pl umbi ng syst em shal l be i nst al l ed compl et e wi t h necessar y f i x t ur es, f i t t i ngs, t r aps, val ves, and accessor i es. Wat er and dr ai nage pi pi ng shal l be ext ended 5 f eet out si de t he bui l di ng, unl ess ot her wi se i ndi cat ed. A bal l val ve and dr ai n shal l be i nst al l ed on t he wat er ser vi ce l i ne i nsi de t he bui l di ng appr oxi mat el y 6 i nches above t he f l oor f r om poi nt of ent r y. Pi pi ng shal l be connect ed t o

SECTI ON 22 00 00 Page 6 ADDENDUM #1 t he ext er i or ser vi ce l i nes or capped or pl ugged i f t he ext er i or ser vi ce i s not i n pl ace. Sewer and wat er pi pes shal l be l ai d i n separ at e t r enches, except when ot her wi se shown.

3. 1. 1 Wat er Pi pe, Fi t t i ngs, and Connect i ons

3. 1. 1. 1 Ut i l i t i es

The pi pi ng shal l be ext ended t o f i x t ur es, out l et s, and equi pment . The hot - wat er and col d- wat er pi pi ng syst em shal l be ar r anged and i nst al l ed t o per mi t dr ai ni ng. The suppl y l i ne t o each i t em of equi pment or f i x t ur e, except f aucet s, f l ush val ves, or ot her cont r ol val ves whi ch ar e suppl i ed wi t h i nt egr al st ops, shal l be equi pped wi t h a shut of f val ve t o enabl e i sol at i on of t he i t em f or r epai r and mai nt enance wi t hout i nt er f er i ng wi t h oper at i on of ot her equi pment or f i x t ur es. Suppl y pi pi ng t o f i x t ur es, f aucet s, hydr ant s, shower heads, and f l ushi ng devi ces shal l be anchor ed t o pr event movement .

3. 1. 1. 2 Cut t i ng and Repai r i ng

The wor k shal l be car ef ul l y l ai d out i n advance, and unnecessar y cut t i ng of const r uct i on shal l be avoi ded. Damage t o bui l di ng, pi pi ng, wi r i ng, or equi pment as a r esul t of cut t i ng shal l be r epai r ed by mechani cs ski l l ed i n t he t r ade i nvol ved.

3. 1. 2 Joi nt s

I nst al l at i on of pi pe and f i t t i ngs shal l be made i n accor dance wi t h t he manuf act ur er ' s r ecommendat i ons. Mi t er i ng of j oi nt s f or el bows and not chi ng of st r ai ght r uns of pi pe f or t ees wi l l not be per mi t t ed. Joi nt s shal l be made up wi t h f i t t i ngs of compat i bl e mat er i al and made f or t he speci f i c pur pose i nt ended.

3. 1. 2. 1 Thr eaded

Thr eaded j oi nt s shal l have Amer i can St andar d t aper pi pe t hr eads conf or mi ng t o ASME B1. 20. 1. Onl y mal e pi pe t hr eads shal l be coat ed wi t h gr aphi t e or wi t h an appr oved gr aphi t e compound, or wi t h an i ner t f i l l er and oi l , or shal l have a pol yt et r af l uor oet hyl ene t ape appl i ed.

3. 1. 2. 2 Mechani cal Coupl i ngs

Mechani cal coupl i ngs may be used i n conj unct i on wi t h gr ooved pi pe f or abovegr ound, f er r ous or non- f er r ous, domest i c hot and col d wat er syst ems, i n l i eu of uni ons, br azed, sol der ed, wel ded, f l anged, or t hr eaded j oi nt s.

Mechani cal coupl i ngs ar e per mi t t ed i n accessi bl e l ocat i ons i ncl udi ng behi nd access pl at es. Fl exi bl e gr ooved j oi nt s wi l l not be per mi t t ed, except as v i br at i on i sol at or s adj acent t o mechani cal equi pment . Ri gi d gr ooved j oi nt s shal l i ncor por at e an angl e bol t pad desi gn whi ch mai nt ai ns met al - t o- met al cont act wi t h equal amount of pad of f set of housi ngs upon i nst al l at i on t o ensur e posi t i ve r i gi d c l ampi ng of t he pi pe.

Desi gns whi ch can onl y c l amp on t he bot t om of t he gr oove or whi ch ut i l i ze gr i ppi ng t eet h or j aws, or whi ch use mi sal i gned housi ng bol t hol es, or whi ch r equi r e a t or que wr ench or t or que speci f i cat i ons wi l l not be per mi t t ed.

Gr ooved f i t t i ngs and coupl i ngs, and gr oovi ng t ool s shal l be pr ovi ded f r om

SECTI ON 22 00 00 Page 7 ADDENDUM #1 t he same manuf act ur er . Segment al l y wel ded el bows shal l not be used.

Gr ooves shal l be pr epar ed i n accor dance wi t h t he coupl i ng manuf act ur er ' s l at est publ i shed st andar ds. Gr oovi ng shal l be per f or med by qual i f i ed gr oovi ng oper at or s havi ng demonst r at ed pr oper gr oovi ng pr ocedur es i n accor dance wi t h t he t ool manuf act ur er ' s r ecommendat i ons.

The Cont r act i ng Of f i cer shal l be not i f i ed 24 hour s i n advance of t est t o demonst r at e oper at or ' s capabi l i t y , and t he t est shal l be per f or med at t he wor k s i t e, i f pr act i cal , or at a s i t e agr eed upon. The oper at or shal l demonst r at e t he abi l i t y t o pr oper l y adj ust t he gr oovi ng t ool , gr oove t he pi pe, and t o ver i f y t he gr oove di mensi ons i n accor dance wi t h t he coupl i ng manuf act ur er ' s speci f i cat i ons.

3. 1. 3 Di ssi mi l ar Pi pe Mat er i al s

Connect i ons bet ween f er r ous and non- f er r ous copper wat er pi pe shal l be made wi t h di el ect r i c uni ons or f l ange wat er ways. Di el ect r i c wat er ways shal l have t emper at ur e and pr essur e r at i ng equal t o or gr eat er t han t hat speci f i ed f or t he connect i ng pi pi ng. Wat er ways shal l have met al connect i ons on bot h ends sui t ed t o mat ch connect i ng pi pi ng. Di el ect r i c wat er ways shal l be i nt er nal l y l i ned wi t h an i nsul at or speci f i cal l y desi gned t o pr event cur r ent f l ow bet ween di ssi mi l ar met al s. Di el ect r i c f l anges shal l meet t he per f or mance r equi r ement s descr i bed her ei n f or di el ect r i c wat er ways. Connect i ng j oi nt s bet ween pl ast i c and met al l i c pi pe shal l be made wi t h t r ansi t i on f i t t i ng f or t he speci f i c pur pose.

3. 1. 4 Suppor t s

3. 1. 4. 1 Gener al

Hanger s used t o suppor t pi pi ng 2 i nches and l ar ger shal l be f abr i cat ed t o per mi t adequat e adj ust ment af t er er ect i on whi l e st i l l suppor t i ng t he l oad. Pi pe gui des and anchor s shal l be i nst al l ed t o keep pi pes i n accur at e al i gnment , t o di r ect t he expansi on movement , and t o pr event buckl i ng, swayi ng, and undue st r ai n. Pi pi ng subj ect ed t o ver t i cal movement when oper at i ng t emper at ur es exceed ambi ent t emper at ur es shal l be suppor t ed by var i abl e spr i ng hanger s and suppor t s or by const ant suppor t hanger s. I n t he suppor t of mul t i pl e pi pe r uns on a common base member , a c l i p or c l amp shal l be used wher e each pi pe cr osses t he base suppor t member . Spaci ng of t he base suppor t member s shal l not exceed t he hanger and suppor t spaci ng r equi r ed f or an i ndi v i dual pi pe i n t he mul t i pl e pi pe r un. Thr eaded sect i ons of r ods shal l not be f or med or bent .

3. 1. 4. 2 Pi pe Hanger s, I nser t s, and Suppor t s

I nst al l at i on of pi pe hanger s, i nser t s and suppor t s shal l conf or m t o MSS SP- 58 except as modi f i ed her ei n.

a. Types 5, 12, and 26 shal l not be used.

b. Type 3 shal l not be used on i nsul at ed pi pe.

c. Type 18 i nser t s shal l be secur ed t o concr et e f or ms bef or e concr et e i s pl aced. Cont i nuous i nser t s whi ch al l ow mor e adj ust ment may be used i f t hey ot her wi se meet t he r equi r ement s f or t ype 18 i nser t s.

d. Type 19 and 23 C- cl amps shal l be t or qued per MSS SP- 58 and shal l have bot h l ocknut s and r et ai ni ng devi ces f ur ni shed by t he manuf act ur er .

Fi el d- f abr i cat ed C- cl amp bodi es or r et ai ni ng devi ces ar e not

SECTI ON 22 00 00 Page 8 ADDENDUM #1 accept abl e.

e. Type 20 at t achment s used on angl es and channel s shal l be f ur ni shed wi t h an added mal l eabl e- i r on heel pl at e or adapt er .

f . Type 24 may be used onl y on t r apeze hanger syst ems or on f abr i cat ed f r ames.

g. Type 39 saddl es shal l be used on i nsul at ed pi pe 4 i nches and l ar ger when t he t emper at ur e of t he medi um i s 60 degr ees F or hi gher . Type 39 saddl es shal l be wel ded t o t he pi pe.

h. Type 40 shi el ds shal l :

( 1) Be used on i nsul at ed pi pe l ess t han 4 i nches.

( 2) Be used on i nsul at ed pi pe 4 i nches and l ar ger when t he t emper at ur e of t he medi um i s 60 degr ees F or l ess.

( 3) Have a hi gh densi t y i nser t f or al l pi pe s i zes. Hi gh densi t y i nser t s shal l have a densi t y of 8 pcf or gr eat er .

i . Hor i zont al pi pe suppor t s shal l be spaced as speci f i ed i n MSS SP- 58 and a suppor t shal l be i nst al l ed not over 1 f oot f r om t he pi pe f i t t i ng j oi nt at each change i n di r ect i on of t he pi pi ng. Pi pe suppor t s shal l be spaced not over 5 f eet apar t at val ves. Oper at i ng t emper at ur es i n det er mi ni ng hanger spaci ng f or PVC or CPVC pi pe shal l be 120 degr ees F f or PVC and 180 degr ees F f or CPVC. Hor i zont al pi pe r uns shal l i ncl ude al l owances f or expansi on and cont r act i on.

j . Ver t i cal pi pe shal l be suppor t ed at each f l oor , except at s l ab- on- gr ade, at i nt er val s of not mor e t han 15 f eet nor mor e t han 8 f eet f r om end of r i ser s, and at vent t er mi nat i ons. Ver t i cal pi pe r i ser s shal l i ncl ude al l owances f or expansi on and cont r act i on.

k. Type 35 gui des usi ng st eel , r ei nf or ced pol yt et r af l uor oet hyl ene ( PTFE) or gr aphi t e s l i des shal l be pr ovi ded t o al l ow l ongi t udi nal pi pe movement . Sl i de mat er i al s shal l be sui t abl e f or t he syst em oper at i ng t emper at ur es, at mospher i c condi t i ons, and bear i ng l oads encount er ed.

Lat er al r est r ai nt s shal l be pr ovi ded as needed. Wher e st eel s l i des do not r equi r e pr ovi s i ons f or l at er al r est r ai nt t he f ol l owi ng may be used:

( 1) On pi pe 4 i nches and l ar ger when t he t emper at ur e of t he medi um i s 60 degr ees F or hi gher , a Type 39 saddl e, wel ded t o t he pi pe, may f r eel y r est on a st eel pl at e.

( 2) On pi pe l ess t han 4 i nches a Type 40 shi el d, at t ached t o t he pi pe or i nsul at i on, may f r eel y r est on a st eel pl at e.

( 3) On pi pe 4 i nches and l ar ger car r y i ng medi um l ess t hat 60 degr ees F a Type 40 shi el d, at t ached t o t he pi pe or i nsul at i on, may f r eel y r est on a st eel pl at e.

l . Pi pe hanger s on hor i zont al i nsul at ed pi pe shal l be t he s i ze of t he out si de di amet er of t he i nsul at i on. The i nsul at i on shal l be cont i nuous t hr ough t he hanger on al l pi pe s i zes and appl i cat i ons.

m. Wher e t her e ar e hi gh syst em t emper at ur es and wel di ng t o pi pi ng i s not desi r abl e, t he t ype 35 gui de shal l i ncl ude a pi pe cr adl e, wel ded t o

SECTI ON 22 00 00 Page 9 ADDENDUM #1 t he gui de st r uct ur e and st r apped secur el y t o t he pi pe. The pi pe shal l be separ at ed f r om t he sl i de mat er i al by at l east 4 i nches or by an amount adequat e f or t he i nsul at i on, whi chever i s gr eat er .

n. Hanger s and suppor t s f or pl ast i c pi pe shal l not compr ess, di st or t , cut or abr ade t he pi pi ng, and shal l al l ow f r ee movement of pi pe except wher e ot her wi se r equi r ed i n t he cont r ol of expansi on/ cont r act i on.

3. 2 ESCUTCHEONS

Escut cheons shal l be pr ovi ded at f i ni shed sur f aces wher e bar e or i nsul at ed pi pi ng, exposed t o v i ew, passes t hr ough f l oor s, wal l s, or cei l i ngs, except i n boi l er , ut i l i t y , or equi pment r ooms. Escut cheons shal l be f ast ened secur el y t o pi pe or pi pe cover i ng and shal l be sat i n- f i ni sh, cor r osi on- r esi st i ng st eel , pol i shed chr omi um- pl at ed zi nc al l oy, or pol i shed chr omi um- pl at ed copper al l oy. Escut cheons shal l be ei t her one- pi ece or spl i t - pat t er n, hel d i n pl ace by i nt er nal spr i ng t ensi on or set scr ew.

3. 3 TESTS, FLUSHI NG AND DI SI NFECTI ON

3. 3. 1 Pl umbi ng Syst em

The f ol l owi ng t est s shal l be per f or med on t he pl umbi ng syst em i n accor dance wi t h I CC I PC, except t hat t he dr ai nage and vent syst em f i nal t est shal l i ncl ude t he smoke t est . The Cont r act or has t he opt i on t o per f or m a pepper mi nt t est i n l i eu of t he smoke t est . I f a pepper mi nt t est i s chosen, t he Cont r act or must submi t a t est i ng pr ocedur e and r easons f or choosi ng t hi s opt i on i n l i eu of t he smoke t est t o t he Cont r act i ng Of f i cer f or appr oval .

a. Dr ai nage and Vent Syst ems Test . The f i nal t est shal l i ncl ude a smoke t est .

b. Bui l di ng Sewer s Test s.

c. Wat er Suppl y Syst ems Test s.

3. 3. 2 Def ect i ve Wor k

I f i nspect i on or t est shows def ect s, such def ect i ve wor k or mat er i al shal l be r epl aced or r epai r ed as necessar y and i nspect i on and t est s shal l be r epeat ed. Repai r s t o pi pi ng shal l be made wi t h new mat er i al s. Caul k i ng of scr ewed j oi nt s or hol es wi l l not be accept abl e.

3. 3. 3 Di s i nf ect i on

Af t er al l syst em component s ar e pr ovi ded and oper at i onal t est s ar e compl et e, t he ent i r e domest i c hot - and col d- wat er di st r i but i on syst em shal l be di s i nf ect ed. Bef or e i nt r oduci ng di s i nf ect i ng chl or i nat i on mat er i al , ent i r e syst em shal l be f l ushed wi t h pot abl e wat er unt i l any ent r ai ned di r t and ot her f or ei gn mat er i al s have been r emoved.

Wat er chl or i nat i on pr ocedur e shal l be i n accor dance wi t h AWWA C651 and AWWA C652 as modi f i ed and suppl ement ed by t hi s speci f i cat i on. The chl or i nat i ng mat er i al shal l be hypochl or i t es or l i qui d chl or i ne. The chl or i nat i ng mat er i al shal l be f ed i nt o t he wat er pi pi ng syst em at a const ant r at e at a concent r at i on of at l east 50 par t s per mi l l i on

SECTI ON 22 00 00 Page 10 ADDENDUM #1

( ppm) . Feed a pr oper l y adj ust ed hypochl or i t e sol ut i on i nj ect ed i nt o t he syst em wi t h a hypochl or i nat or , or i nj ect l i qui d chl or i ne i nt o t he syst em t hr ough a sol ut i on- f eed chl or i nat or and boost er pump unt i l t he ent i r e syst em i s compl et el y f i l l ed.

Test t he chl or i ne r esi dual l evel i n t he wat er at 6 hour i nt er val s f or a cont i nuous per i od of 24 hour s. I f at t he end of a 6 hour i nt er val , t he chl or i ne r esi dual has dr opped t o l ess t han 25 ppm, f l ush t he pi pi ng i ncl udi ng t anks wi t h pot abl e wat er , and r epeat t he above chl or i nat i on pr ocedur es. Dur i ng t he chl or i nat i on per i od, each val ve and f aucet shal l be opened and cl osed sever al t i mes.

Af t er t he second 24 hour per i od, ver i f y t hat no l ess t han 25 ppm chl or i ne r esi dual r emai ns i n t he t r eat ed syst em. The 24 hour chl or i nat i on pr ocedur e must be r epeat ed unt i l no l ess t han 25 ppm chl or i ne r esi dual r emai ns i n t he t r eat ed syst em.

Upon t he speci f i ed ver i f i cat i on, t he syst em i ncl udi ng t anks shal l t hen be f l ushed wi t h pot abl e wat er unt i l t he r esi dual chl or i ne l evel i s r educed t o l ess t han one par t per mi l l i on. Dur i ng t he f l ushi ng per i od, each val ve and f aucet shal l be opened and cl osed sever al t i mes.

Take addi t i onal sampl es of wat er i n di s i nf ect ed cont ai ner s, f or bact er i al exami nat i on, at l ocat i ons speci f i ed by t he Cont r act i ng Of f i cer . Test t hese sampl es f or t ot al col i f or m or gani sms ( col i f or m bact er i a, f ecal col i f or m, st r ept ococcal , and ot her bact er i a) i n accor dance wi t h AWWA 10084. The t est i ng met hod used shal l be EPA appr oved f or dr i nki ng wat er syst ems and shal l compl y wi t h appl i cabl e l ocal and st at e r equi r ement s.

Di s i nf ect i on shal l be r epeat ed unt i l bact er i al t est s i ndi cat e t he absence of col i f or m or gani sms ( zer o mean col i f or m densi t y per 100 mi l l i l i t er s) i n t he sampl es f or at l east 2 f ul l days. The syst em wi l l not be accept ed unt i l sat i sf act or y bact er i ol ogi cal r esul t s have been obt ai ned.

3. 4 POSTED I NSTRUCTI ONS

Fr amed i nst r uct i ons under gl ass or i n l ami nat ed pl ast i c, i ncl udi ng wi r i ng and cont r ol di agr ams showi ng t he compl et e l ayout of t he ent i r e syst em, shal l be post ed wher e di r ect ed. Condensed oper at i ng i nst r uct i ons expl ai ni ng pr event i ve mai nt enance pr ocedur es, met hods of checki ng t he syst em f or nor mal saf e oper at i on, and pr ocedur es f or saf el y st ar t i ng and st oppi ng t he syst em shal l be pr epar ed i n t yped f or m, f r amed as speci f i ed above f or t he wi r i ng and cont r ol di agr ams and post ed besi de t he di agr ams.

The f r amed i nst r uct i ons shal l be post ed bef or e accept ance t est i ng of t he syst ems.

- - End of Sect i on - -

SECTI ON 22 00 00 Page 11 ADDENDUM #1