DESIGN NEW HVAC SYSTEM AND ASSOCIATED UPGRADES
PHASE 2B
STUTTGART, ARKANSAS
SHEET NO.
INDEX OF DRAWINGS
SHEET TITLE
G-001 G-002
AD111
A-101 A-102 A-111 P-001
PD101
P-101 M-001 M-002
MD101
MD102
MD103
MH101
MH102
MP101
M-101 M-501 M-502
PHASE 2B TITLE SHEET
PHASING PLAN
PHASE 2B REFLECTED CEILING PLAN: DEMO
PHASE 2B ROOF NEW WORK PLAN
PHASE 2B ROOF NEW WORK PLAN
PHASE 2B REFLECTED CEILING PLAN
PHASE 2B PLUMBING GENERAL NOTES
PHASE 2B PLUMBING DEMOLITION PLAN
PHASE 2B PLUMBING NEW WORK PLAN
PHASE 2B MECHANICAL GENERAL NOTES
PHASE 2B MECHANICAL LEGEND & ABBREVIATIONS
PHASE 2B MECHANICAL DEMOLITION PLAN
PHASE 2B MECHANICAL PIPING DEMOLITION PAN
PHASE 2B MECHANICAL ROOF DEMOLITION PLAN
PHASE 2B MECHANICAL NEW WORK PLAN
PHASE 2B MECHANICAL ROOF NEW WORK PLAN
PHASE 2B MECHANICAL PIPING NEW WORK PLAN
PHASE 2B MECHANICAL GREENHOUSE PLAN
PHASE 2B MECHANICAL DETAILS
PHASE 2B MECHANICAL DETAILS
USDA
NO SCALEVICINITY MAP
NORTH
ARKANSAS
PROJECT
LOCATION
USDA AGRICULTURAL RESEARCH SERVICE
DALE BUMPERS NATIONAL RICE RESEARCH CENTER
(DBNRRC)
SHEET NO.SHEET TITLE
M-503 M-601 M-602 M-701 M-702 E-001
ED101
ED102
ED111
E-101 E-102 E-111 E-500 E-600 E-601
PHASE 2B MECHANICAL DETAILS
PHASE 2B MECHANICAL SCHEDULES
PHASE 2B MECHANICAL SCHEDULES
PHASE 2B MECHANICAL CONTROLS DIAGRAMS
PHASE 2B MECHANICAL CONTROLS DIAGRAMS
PHASE 2B ELECTRICAL LEGEND AND NOTES
PHASE 2B ELECTRICAL DEMOLITION PLAN
PHASE 2B ELECTRICAL ROOF DEMOLITION PLAN
PHASE 2B LIGHTING DEMOLITION PLAN
PHASE 2B ELECTRICAL POWER PLAN
PHASE 2B ELECTRICAL ROOF POWER PLAN
PHASE 2B ELECTRICAL LIGHTING PLAN
PHASE 2B LIGHTING DETAILS AND SCHEDULES
PHASE 2B SCHEDULES
PHASE 2B SCHEDULES
PHASE 1A, 1B AND 1C (NOT IN CONTRACT):
PHASE 2A (NOT IN CONTRACT)
PHASE 2B
PHASE 3A (NOT IN CONTRACT)
PHASE 3B (NOT IN CONTRACT)
HEADHOUSE (NOT IN CONTRACT)
PHASING LEGEND
A. ALL NON-WORK AREAS IN THE BUILDING WILL REMAIN OCCUPIED AND OPERATIONAL
DURING THE WORK. USDA WILL VACATE AREAS OF THE BUILDING WHERE WORK IS
BEING PERFORMED. THE CONTRACTOR SHALL COORDINATE HIS/HER WORK
ACTIVITIES WITH THE CONTRACTING OFFICER TO AVOID CONFLICTS WITH FACILITY
OPERATIONS. THE CONTRACTOR SHALL ERECT BARRIERS AND EMPLOY NECESSARY
MEASURES TO PROTECT PERSONNEL IN THE AREA FROM INJURY.
B. COVER AND PROTECT ALL FURNISHINGS AND EQUIPMENT REMAINING IN THE
LABORATORIES AND OFFICE SPACES.
C. THE CONTRACTOR SHALL PROVIDE BARRIERS AND SIGNAGE TO SECURE THE WORK
AREAS, TO DIRECT PERSONNEL IN WAYFINDING, AND TO ENSURE THE SAFETY OF
BUILDING OCCUPANTS AND VISITORS. THE CONTRACTOR SHALL PROVIDE A WORK
PLAN BEFORE BEGINNING THE WORK EXPLAINING AND ILLUSTRATING THE MEANS TO
BE IMPLEMENTED TO ALLOW THE BUILDING TO REMAIN OCCUPIED AND OPERATIONAL
DURING THE WORK. THE CONTRACTOR SHALL FIELD VERIFY ALL DIMENSION AND
CONDITIONS BEFORE BEGINNING WORK.
D. CONTRACTOR SHALL COORDINATE STAGING AREAS WITH USDA PERSONNEL.
GENERAL NOTES
PHASE 2B
AREA OF
WORK
L-2A L-2
L-7
L-6
L-8
101A
L-21
L-1B
L-1A
L-1C
L-1
L-18
L-3 L-4 L-5
L-12
L-14B
L-14C
L-14D
L-9
L-1D
L-21C
L-21E L-21D
SCALE:
PHASE 2B
REFLECTED CEILING PLAN: DEMO
3/16" = 1'-0"
AD111
0 4' 8' 16'
SCALE: 3/16"= 1'-0"
2'
KEY PLAN
N.T.S.
AREA OF
WORK
PHASE 2B
LEGEND
DEMOLISH 24 x 24" SUSPENDED
ACOUSTICAL CEILING SYSTEM
COMPLETE. CONTRACTORS
OPTION TO RETAIN SUSPENSION
WIRES
DEMOLISH SUSPENDED GYPSUM
BOARD CEILING SYSTEM
COMPLETE. CONTRACTORS
OPTION TO RETAIN HANGER
WIRES
LIGHT FIXTURES. SEE
ELECTRICAL DRAWINGS FOR
ADDITIONAL WORK.
HVAC DIFFUSERS. SEE
MECHANICAL DRAWINGS FOR
ADDITIONAL WORK.
NO WORK THIS AREA
DEMOLISH 24 x 48" SUSPENDED
ACOUSTICAL CEILING SYSTEM
COMPLETE. CONTRACTORS
OPTION TO RETAIN SUSPENSION
WIRES
EXISTING DUCT WORK,
ROOF TOP PIPING AND
AHU'S TO REMAIN PROTECT
DURING CONSTRUCTION.
LEGEND
EXISTING CURB MOUNTED EQUIPMENT TO REMAIN.
PROTECT DURING CONSTRUCTION.
NEW EXHAUST FAN WITH VENT STACK AND GUY WIRES
MOUNTED ON EXISTING CURB. SEE DETAIL 2/A-102 .
NEW EXHAUST FAN MOUNTED ON EXISTING CURB.
NEW EXHAUST FAN WITH VENT STACK AND GUY WIRES
MOUNTED ON NEW CURB. SEE PLAN FOR SIZE. SEE
DETAIL 1/A-102 AND 2/A-102.
GENERAL DEMOLITION NOTE:
1. AT NEW CURB PENETRATIONS REMOVE ROOF SYSTEM,
INSULATION AND STEEL DECK. SEE DETAIL 2/A-102 FOR ROOF
CURB SUPPORT STRUCTURE.
1'-9"
1'- 9"
1'-10"
1'-
1'-9"
4 1 /2"
1'-9"
1'- 9"
1'-9"
1'- 9"
SCALE: 1/16" = 1'-0"
48'8' 16' 32'0
PHASE 2B MECHANICAL
ROOF NEW WORK PLAN
1/16" = 1'-0"
A-101
PLAN
NORTH
8" M
IN
CURB MOUNTED EQUIPMENT
SEE MECHANICAL DRAWINGS
NEW PRE-MANUFACTURED ROOF CURB
TERMINATION BAR FASTENED @ 12" O.C.
ROOFING SYSTEM BONDING ADHESIVE
55 MIL TPO FLASHING
ROOFING SYSTEM FASTENER AND
PLATE @ 12" O.C.
HEAT WELDED LAP
EXISTING RIGID INSULATION
EXISTING METAL ROOF DECK
CUT OPENING FOR FAN AND CURB.
EXISTING SINGLE PLY TPO ROOF MEMBRANE
EXISTING COVER BOARD
TREATED 2x NAILER AS REQUIRED
NEW COVER BOARD
ROOFING SYSTEM FASTENER AND
PLATE @ 12" O.C.
HEAT WELDED LAP
EXISTING RIGID INSULATION
EXISTING METAL ROOF DECK
EXISTING SINGLE PLY TPO ROOF MEMBRANE
EXISTING COVER BOARD
EXISTING STRUCTURAL JOIST
PROVIDE C8x11.75 AS
INDICATED ON PLAN FOR GUY
WIRE ANCHOR.
WELD CHANNEL TO TOP CHORD
OF EXISTING JOIST BOTH SIDES
AT EACH END.
PROVIDE 3 4" DIA. GUY WIRE
ANCHOR EYE BOLT AS
INDICATED ON PLAN.
PROVIDE (2) NUTS AND LOCK
WASHERS EACH CONNECTION
PRE-MOLDED PENETRATION BOOT
SEALANT CONT. AROUND ANCHOR
STAINLESS STEEL BAND CLAMP
VENT STACK GUY WIRE
SEALANT CONT.
5'-0" ±
4"
FILL VOID WITH MINERAL
WOOL INSLATION
7'
7'
VENT STACK AND FAN SEE
MECHANICAL DRAWINGS
EQUIPMENT CURB. SEE A-101
FOR NEW AND EXISTING CURB
LOCATION.
VENT STACK GUY WIRE
(3) PER VENT STACK AS
INDICATED ON PLAN.
EXISTING ROOF SYSTEM
EXISTING STRUCTURAL JOIST
A102
PROVIDE SUPPORT AT
EACH SIDE OF CURB NOT
DIRECTLY SUPPORTED BY
JOIST SEE 3/A-102 (SIM).
PPM
REVISIONS
Agricultural
Service Research
DESCRIPTION
SHEET
DATEc P.A.
FIRM
NO.
EPM
SAFETY & HEALTH
REAL PROPERTY DATE
PROJECT NO.
USDA
BY
AGRICULTURAL RESEARCH SERVICE
OF
THE
DESIGNER
PROJECT MANAGER
JOB #
CHECKED BY
A-E FIRM
P.O. BOX 513, GREENWOOD, MISSISSIPPI - (662) 455-4943
Johnson M Adams
ARCHITECTS/ENGINEERS PLANNING SURVEYING MANAGEMENT
USDA AGRICULTURAL RESEARCH SERVICE
DALE BUMPERS NATIONAL RICE RESEARCH CENTER
(DBNRRC)
STUTTGART, ARKANSAS
5 3505/15/24
REH
SME
FEJ
SOUTHEAST AREA
STONEVILLE, MS
XXX
5923-E
E. WILSON
XXX
J. LEDBETTER
R. BRAITHWAITE
SCALE:
ROOF CURB DETAIL
3" = 1'-0"
A-102
SCALE: 3"=1'-0"
3"0 6" 1'
SCALE:
VENT STACK DETAIL
N.T.S.
A-102
SCALE:
GUY WIRE ANCHOR DETAIL
3" = 1'-0"
A-102
109 108
L-2A
L-2
L-7
L-6
L-8
101A
L-21
L-1B
L-1A L-1C
L-1
L-18
L-3 L-4
L-5
L-12
L-14B
L-14C L-14D
L-1D
L-21C
L-21E
L-21D
0 4' 8' 16'
SCALE: 3/16"= 1'-0"
2'
SCALE:
PHASE 2B
REFLECTED CEILING PLAN
3/16" = 1'-0"
A-111
KEY PLAN
N.T.S.
LEGEND
PROVIDE NEW 24 x 24" SUSPENDED
ACOUSTICAL CEILING SYSTEM AS
SPECIFIED. CONTRACTORS OPTION TO
RETAIN SUSPENSION WIRES
PROVIDE NEW SUSPENDED GYPSUM
BOARD CEILING SYSTEM AS SPECIFIED.
CONTRACTORS OPTION TO RETAIN
HANGER WIRES
LIGHT FIXTURES. SEE ELECTRICAL
DRAWINGS FOR ADDITIONAL WORK.
HVAC DIFFUSERS. SEE MECHANICAL
DRAWINGS FOR ADDITIONAL WORK.
AREA OF
WORK
PHASE 2B
NO WORK THIS AREA
PLUMBING LEGEND:
DIRECTION OF FLOW
PIPE TURNED DOWN
PIPE TURNED UP
RISE OR DROP
BRANCH BOTTOM CONNECTION
TEE OUTLET UP
TEE OUTLET DOWN
CAP ON END OF PIPE
SANITARY WASTE - ABOVE FLOOR OR GRADE
VENT PIPING
POTABLE / DOMESTIC COLD WATER PIPING
POTABLE / DOMESTIC HOT WATER SUPPLY PIPING
TEMPERATURE & PRESSURE RELIEF VALVE
FLOW MEASURING / BALANCING / SHUT-OFF VALVE
BALL VALVE
CHECK VALVE
GATE VALVE
STRAINER
UNION
HOSE BIBB
FLOOR DRAIN
PLUMBING ABBREVIATIONS:
FLOOR CLEANOUT
WALL CLEANOUT
PLAN ELEV
FCOFCO
WCO WCO
BRANCH TOP CONNECTION
POTABLE / DOMESTIC HOT WATER RETURN PIPING
PETROLEUM OILS & LUBRICANTSPOL
COMPRESSED AIR PIPINGA
COMPRESSED AIR OUTLETA
GENERAL PLUMBING NOTES:
1. THIS PROJECT IS A RENOVATION OF AN EXISTING FACILITY. IT IS THE CONTRACTOR'S RESPONSIBILITY TO FIELD VERIFY ALL DIMENSIONS
PRIOR TO FABRICATION OR PURCHASE OF EQUIPMENT, MATERIALS, AND ASSEMBLIES. ANY DEVIATIONS SHALL BE BROUGHT TO THE CONTRACTING OFFICER'S REPRESENTATIVE'S ATTENTION FOR RESOLUTION BEFORE PROCEEDING WITH ANY CONSTRUCTION, FABRICATION, OR EQUIPMENT PURCHASE.
2. THESE DRAWINGS ARE SCHEMATIC IN NATURE AND ARE NOT INTENDED TO SHOW ALL POSSIBLE CONDITIONS (DO NOT SCALE FOR LOCATIONS). THE CONTRACTOR WILL PROVIDE A COMPLETE AND FUNCTIONAL PLUMBING SYSTEM AS INDICATED WITH ALL NECESSARY
EQUIPMENT, APPURTENANCES AND CONTROLS AS INDICATED.
3. THE PLUMBING CONTRACTOR SHALL REVIEW THE DRAWINGS OF OTHER TRADES AS PART OF THIS CONTRACT FOR ADDITIONAL WORK REQUIRED AND FOR COORDINATION OF PLUMBING WORK FOR OPERATIONS OF OR CONNECTIONS TO OTHER TRADES.
4. REMOVE AND CAP CONNECTING UTILITIES (WATER, DRAINAGE, POWER, GAS, ETCETERA) AS INDICATED OR NECESSARY FOR FUTURE
RECONNECTION.
5. THE CONTRACTOR WILL EMPLOY WORKMEN WHO ARE TRAINED AND EXPERIENCED IN NECESSARY SKILLS TO PERFORM PLUMBING AND
PLUMBING DEMOLITION WORK.
6. THE CONTRACTOR WILL USE APPROPRIATE TOOLS AND SHALL NOT IMPART EXCESSIVE VIBRATIONS TO THE EXISTING STRUCTURE OR
OTHER BUILDING COMPONENTS.
7. MAKE OFFSETS AND TRANSITIONS TO COORDINATE WITH OTHER TRADES WITHOUT ANY ADDITIONAL EXPENSE TO THE OWNER. THE
CONTRACTOR WILL PROVIDE COORDINATION DRAWINGS OF TRADES.
8. ALL NEW & DEMOLISHED PIPING PENETRATIONS TO THE BUILDING ENVELOPE SHALL BE FULLY SEALED WATER TIGHT.
9. THE CONTRACTOR WILL FIELD VERIFY EXACT LOCATIONS AND POINTS OF CONNECTIONS TO THE EXISTING UTILITIES (DOMESTIC WATER &
SANITARY SEWER, NATURAL GAS, ETCETERA).
10. REFER TO SPECIFICATIONS, SHEET NOTES, DETAILS AND SCHEDULES FOR ADDITIONAL REQUIREMENTS PERTAINING TO THE PLUMBING
WORK.
11. ALL WORK (MATERIALS, EQUIPMENT, DEVICES, COMPONENTS, SYSTEMS, SUPPORTS, ETCETERA) MUST COMPLY WITH THE REQUIREMENTS OF ALL CODES, CODE AMENDMENTS, AND ORDINANCES AS USED, ADOPTED AND/OR ENFORCED BY THE LOCAL JURISDICTION, COUNTY AND STATE IN WHICH THE PROJECT IS LOCATED. WHERE INSPECTIONS ARE REQUIRED BY COR, WORK MUST NOT BE CONCEALED UNTIL INSPECTIONS AND TESTS ARE COMPLETED AND ACCEPTED. REFER TO SPECIFICATIONS FOR APPLICABLE CODES.
12. SCHEDULES, NOTES OR SPECIFICATIONS MAY REFERENCE "BASIS OF DESIGN" INFORMATION REGARDING A SPECIFIC MANUFACTURER OR MODEL NUMBER. SUCH INFORMATION IS PROVIDED SO AS TO ESTABLISH A STANDARD OF PERFORMANCE, QUALITY, FEATURES AND OPTIONS (SEE SCHEDULES AND SPECIFICATIONS). THE INTENT IS NOT TO LIMIT COMPETITION. EQUIVALENT EQUIPMENT OF OTHER MANUFACTURERS SHALL BE ACCEPTABLE PROVIDED SUCH EQUIPMENT EQUALS OR EXCEEDS THE BASIS OF DESIGN EQUIPMENT IN PERFORMANCE, QUALITY, FEATURES AND OPTIONS WHETHER SPECIFIED, SCHEDULED OR NOTED.
13. ALL EQUIPMENT FURNISHED FOR THIS PROJECT MUST COMPLY WITH THE "BUY AMERICAN ACT".
14. ALL WORK IS TO BE FABRICATED AND/OR ERECTED USING CONTRACTOR'S FIELD MEASUREMENTS FOR PROPER COORDINATION WITH
WORK OF OTHER TRADES.
15. ALL CONTRACT DOCUMENTS ARE DIAGRAMMATIC AND INDICATE THE GENERAL ARRANGEMENTS OR GEOMETRICAL RELATIONSHIPS OF THE WORK. THEY ARE NOT INTENDED TO SPECIFY OR SHOW EVERY OFFSET, SEQUENCE, DEVICE, OPTION, FITTING, OR COMPONENT. DO
NOT SCALE DRAWINGS.
16. INFORMATION AND COMPONENTS SHOWN ON DIAGRAMS OR DETAILS, BUT NOT SHOWN ON PLANS, AND VICE VERSA, MUST BE PROVIDED
AS IF EXPRESSLY REQUIRED BY BOTH.
17. EXCEPT WHERE INDICATED OTHERWISE, THE NOTATION OR DESCRIPTION OF ANY ITEM IN THE CONTRACT DOCUMENTS CARRIES WITH IT THE INSTRUCTION TO FURNISH AND INSTALL THE ITEM, WHETHER OR NOT THIS INSTRUCTION IS EXPLICITLY STATED.
18. ALL WORK SHALL BE INSTALLED SO AS MAINTAIN ANY "UL" ASSEMBLY RATINGS, FIRE RATINGS OR SMOKE BARRIER CAPABILITIES OF WALLS, PARTITIONS, FLOORS AND ROOF. SEAL AROUND AND PLACE UL RATED FIRE-STOP MATERIAL AT ANY PENETRATION OR DISTURBANCE OF SUCH ASSEMBLIES. COORDINATE WITH ARCHITECTURAL PLANS AND DESIGN BUILDER.
19. COORDINATE PLACEMENT OF ALL WORK WITH OTHER TRADES. DO NOT LOCATE, POSITION OR INSTALL ANY WORK IN SUCH A WAY THAT SYSTEM COMPONENTS OR ACCESS DOORS WILL BE INACCESSIBLE, UNUSABLE OR UN-MAINTAINABLE AFTER CONSTRUCTION IS
COMPLETED. COMPLY WITH MANUFACTURER'S MINIMUM RECOMMENDED SERVICE CLEARANCES.
20. UNLESS OTHERWISE INDICATED, ALL WORK IS TO BE SUPPORTED FROM STRUCTURE ABOVE, FROM WALLS, FROM COLUMNS, OR FROM THE FLOOR. DO NOT USE THE INSTALLED WORK OF OTHER TRADES, OR WORK RELATED TO ANY SUPPORT SYSTEMS FOR SUPPORT FOR
OTHER TRADES.
21. PROVIDE PIPE TRANSITIONS AS REQUIRED AT FIXTURE CONNECTIONS WHERE PIPE SIZES INDICATED DIFFER FROM THE FIXTURE
CONNECTION SIZE.
22. PROVIDE EQUIPMENT ACCESS PANELS FOR ALL EQUIPMENT AND VALVES THAT ARE LOCATED ABOVE HARD CEILINGS, IN WALLS, OR BEHIND SURFACES THAT ARE NOT REMOVABLE. ACCESS PANELS MUST BE 18"X18" MINIMUM UNLESS OTHERWISE NOTED. LOCATE ACCESS PANELS AS CLOSE AS POSSIBLE TO DEVICE NEEDING ACCESS, BUT NO FARTHER THAN 24" AWAY.
23. DOMESTIC WATER PIPING SHALL BE TYPE K RIGID COPPER WITH PRESS FITTINGS.
24. ALL NEW DEIONIZED WATER PIPING SHALL BE WELDED 316L STAINLESS STEEL.
NATURAL GAS PIPINGG
° DEGREES
Ø DIAMETER
AC AIR COMPRESSOR
AD AIR DRYER
AFF ABOVE FINISHED FLOOR
ASME AMERICAN SOCIETY OF MECHANICAL ENGINEERS
BFP BACKFLOW PREVENTER
BTU BRITISH THERMAL UNIT
CA COMPRESSED AIR
CO CLEANOUT
CW COLD WATER (DOMESTIC)
DI DEIONIZED WATER
DIR DEIONIZED WATER RETURN
DWV DRAIN WASTE AND VENT
EMCS ENERGY MANAGEMENT CONTROL SYSTEM
ET EXPANSION TANK
EW EYE WASH
EWC ELECTRIC WATER COOLER
F FARENHEIGHT
FCO FLOOR CLEANOUT
FD FLOOR DRAIN
FT FOOT
GAS NATURAL GAS
GCO GROUND CLEANOUT
GPM GALLONS PER MINUTE
GWH GAS WATER HEATER
HB HOSE BIBB
HP HORSEPOWER
HW HOT WATER (DOMESTIC)
HWCP HOT WATER CIRCULATION PUMP
HWR HOT WATER RETURN (DOMESTIC)
IMB ICE MAKER BOX
IPC INTERNATIONAL PLUMBING CODE
kW KILLOWATT
KS KITCHEN SINK
LV LAVATORY
MAX MAXIMUM
MIN MINIMUM
MS MOP SINK
NPT NATIONAL PIPE TAPER
P PLUMBING
PDI PLUMBING AND DRAINAGE INSTITUTE
PSI POUNDS PER SQUARE INCH
PVC POLYVINYL CHLORIDE
RPZ REDUCED PRESSURE ZONE
S SANITARY SEWER
SH SHOWER
SS SAFETY SHOWER
SSEW SAFETY SHOWER EYE WASH
TYP TYPICAL
U/G UNDERGROUND
UR URINAL
V VENT PIPING
VTR VENT THROUGH ROOF
W/ WITH
W/O WITHOUT
WC WATER CLOSET
WCO WALL CLEANOUT
WH WALL HYDRANT
WHA WATER HAMMER ARRESTOR
NOTE:
UNDERLINED FIXTURE AND EQUIPMENT MARKS (SUCH AS WC) ARE
NOT ABBREVIATIONS. REFER TO THE PLUMBING SCHEDULE SHEETS,
P601 - P699 FOR FIXTURE AND EQUIPMENT DESCRIPTIONS.
L-2A
L-2
L-7
L-6
L-8
L-1B
L-1A L-1C
L-1 L-3 L-4
L-5
L-9L-1D
L-21C
L-21E
L-21D
SCALE:
PHASE 2B PLUMBING
DEMOLITION PLAN
3/16" = 1'-0"
PD101
0 4' 8' 16'
SCALE: 3/16"= 1'-0"
2'
CAPPED DI PIPING TO
LAB TO BE DEMOLISHED
CAPPED 1/2" DI TO
BE DEMOLISHED
CAPPED 1/2" DI TO
BE DEMOLISHED
1/2" DI DOWN TO LAB
SINK TO BE DEMOLISHED
1/2" DI VALVED AND CAPPED
6" BELOW CEILING LINE TO
BE DEMOLISHED
DI DOWN TO FUME HOOD
TO BE DEMOLISHED
DI DOWN TO LAB SINK TO
BE DEMOLISHED
1/2" DI DOWN TO LAB
SINK TO BE DEMOLISHED
CAPPED 1/2" DI TO
BE DEMOLISHEDCAPPED 1/2" DI TO
BE DEMOLISHED
CAPPED 1/2" DI TO
BE DEMOLISHED
1/2" DI VALVED AND CAPPED
6" BELOW CEILING LINE TO
BE DEMOLISHED
DI DOWN TO FUME HOOD
TO BE DEMOLISHED
1" DI TO BE DEMOLISHED 1" DI TO BE DEMOLISHED
CAPPED 1/2" DI TO
BE DEMOLISHED
1" DI TO BE
DEMOLISHED
EXIST. 1" DI TO
REMAIN
1" DI TO BE
DEMOLISHED
EXIST. 1" DI TO
REMAIN
1. DEMOLISH DI PIPING TO THE POINT INDICATED
AND CAP FOR CONNECTION TO NEW PIPING.
2. DEMOLISH PIPING ABOVE CEILING UP TO
EXISTING CHASE.
KEYED NOTES
L-2A
L-2
L-7
L-6
L-8
101A
L-1B
L-1A L-1C
L-1 L-3 L-4
L-5
L-9L-1D
L-21E
L-21D
SCALE:
PHASE 2B PLUMBING
NEW WORK PLAN
3/16" = 1'-0"
P-101
0 4' 8' 16'
SCALE: 3/16"= 1'-0"
2'
CAPPED DI
PIPING TO LAB
CAPPED 1/2" DI
CAPPED 1/2" DI
1/2" DI DOWN TO LAB
SINK
1/2" DI VALVED AND CAPPED
6" BELOW CEILING LINE
DI DOWN TO FUME HOOD
DI DOWN TO LAB SINK
1/2" DI DOWN TO LAB
SINK
CAPPED 1/2" DI
CAPPED 1/2" DI
CAPPED 1/2" DI
CAPPED 1/2" DI
1/2" DI VALVED AND CAPPED
6" BELOW CEILING LINE
DI DOWN TO FUME HOOD
1" DIR
1" DI 1" DI
EXIST. 1" DI
EXIST. 1" DI
1" DIR
1. CONNECT TO EXISTING DI PIPING.
2. PROVIDE ISOLATION VALVE PRIOR TO
CONNECTION TO EXISTING PIPING ROUTED IN
CHASE.
KEYED NOTES
1. PROVIDE INSULATION ON DI AND DIR PIPING AND
FITTINGS WITHIN THE AREA OF WORK.
GENERAL NOTES
1. INSTALLATION OF HVAC WORK SHALL BE COORDINATED WITH OTHER TRADES BEFORE ANY INSTALLATION IS DONE. DUCTWORK SHOWN ON PLANS IS SCHEMATIC. DUCTWORK SHALL BE INSTALLED TIGHT TO STRUCTURE. PROVIDE ALL TRANSITIONS, ELBOWS, ETC. REQUIRED TO AVOID CONFLICTS & MAXIMIZE CEILING HEIGHTS. EQUIPMENT, PIPING OR DUCTWORK INTERFERING WITH OTHER TRADES SHALL BE
RELOCATED AS REQUIRED AT NO ADDITIONAL COST TO THE OWNER.
2. COORDINATE MECHANICAL AND ELECTRICAL SUCH THAT MECHANICAL PIPING, DUCTWORK AND EQUIPMENT
IS NOT LOCATED OVER OR ABOVE ANY ELECTRICAL, COMMUNICATIONS, OR DATA EQUIPMENT.
3. AT START OF CONSTRUCTION, PREPARE TYPED LISTS OF EQUIPMENT THAT ARE SUPPLIED REQUIRING ELECTRICAL WORK, AND SEND LISTS TO THE ELECTRICAL CONTRACTOR FOR REVIEW AND COORDINATION.
4. WRITTEN DIMENSIONS ON DRAWINGS SHALL HAVE PRECEDENCE OVER SCALED DIMENSIONS. VERIFY
DIMENSIONS ON SITE.
5. EQUIPMENT SHALL BE INSTALLED IN ACCORDANCE WITH MANUFACTURER'S APPROVED CLEARANCE AND
INTERNATIONAL BUILDING CODE / INTERNATIONAL MECHANICAL CODE.
6. INSTALLATION OF EQUIPMENT SHALL PERMIT ACCESSIBILITY FOR SERVICE AND/OR REPLACEMENT WITHOUT NECESSITATING REMOVAL OR MODIFICATION TO OTHER PIPING, WIRING, OR EQUIPMENT.
7. CEILING-MOUNTED EQUIPMENT SHALL BE INSTALLED IN SUCH A MANNER THAT LIGHTS, PIPING, DUCTWORK, ETC., DO NOT BLOCK ACCESS TO EQUIPMENT AND RELATED ACCESSORIES.
8. COORDINATE WALL, FLOOR, AND ROOF PENETRATIONS WITH THE CONTRACTOR.
9. SUPPLEMENTAL STEEL MEMBERS REQUIRED TO SUPPORT HVAC EQUIPMENT FROM MAIN STRUCTURE
SHALL BE PROVIDED BY THE HVAC CONTRACTOR UNLESS SPECIFICALLY NOTED OTHERWISE.
10. DUCTWORK AIR DISTRIBUTION SYSTEMS SHALL BE INSTALLED IN ACCORDANCE WITH SMACNA STANDARDS
AND THE PRESSURE CLASSIFICATION OF EACH INDIVIDUAL DUCTWORK SYSTEM.
11. VOLUME DAMPERS SHALL BE PROVIDED AT EACH MAIN BRANCH TAKE-OFF, EACH TAKEOFF TO DIFFUSERS/GRILLS/REGISTERS, AND OTHER LOCATIONS WHERE REQUIRED TO PROPERLY BALANCE THE
SYSTEM. ALL REQUIRED VOLUME DAMPERS MAY NOT BE SHOWN ON PLANS.
12. INSTRUMENT TEST HOLES SHALL BE PROVIDED IN AIR DISTRIBUTION SYSTEMS WHEREVER VOLUME DAMPERS ARE INSTALLED. TEST HOLES SHALL BE SEALED WITH RUBBER OR PLASTIC TEST HOLE PLUGS.
13. SQUARE ELBOWS SHALL ONLY BE USED WHERE SPACE LIMITATIONS PREVENT USE OF 1.5 RADIUS ELBOW AND ONLY UPON APPROVAL OF CONTRACTING OFFICER. PROVIDE TURNING VANES IN ALL SQUARE ELBOWS GREATER THAN OR EQUAL TO 45°. TURNING VANES SHALL BE SINGLE THICKNESS TYPE WITHOUT RAILING
EDGE. TURNING VANES LONGER THAN 36 INCHES SHALL BE DOUBLE THICKNESS TYPE.
14. DUCTWORK RUNOUTS TO AIR DISTRIBUTION DEVICES SHALL BE SAME DIAMETER AS AIR DISTRIBUTION
DEVICE INLET CONNECTION UNLESS OTHERWISE NOTED ON THE DRAWINGS.
15. FLEXIBLE DUCTWORK RUNOUTS FROM BRANCH DUCTS TO AIR DISTRIBUTION DEVICES SHALL NOT EXCEED 5 FEET IN LENGTH. BENDS IN FLEXIBLE DUCTWORK SHALL NOT EXCEED A MAXIMUM OF 45 DEGREE CHANGE OF DIRECTION AND SHALL BE SUPPORTED SUCH THAT THE BEND RADIUS IS NOT RESTRICTIVE TO AIR FLOW THROUGH THE DUCT. FLEXIBLE DUCTWORK SHALL NOT BE CRUSHED OR DISTORTED IN ITS FINAL
CONFIGURATION.
16. PROVIDE SHEETMETAL TRANSITIONS AT AIR HANDLING UNITS, HEAT PUMP UNITS, FANS, AND OTHER SIMILAR HVAC EQUIPMENT. TRANSITION TO FULL SIZE OF CONNECTION ON UNIT. FLEXIBLE DUCT
CONNECTORS SHALL BE USED ON FINAL CONNECTION TO AIR HANDLING EQUIPMENT.
17. TRANSFER DUCTS SHALL BE SIZED FOR MAX VELOCITY ALLOWED OF 500 FPM. OPEN-ENDED TRANSFER
DUCTS SHALL HAVE 90° ELBOW FOR SOUND ATTENUATION.
18. LOUVERED SUPPLY AIR DIFFUSERS SHALL BE 4-WAY FLOW UNLESS OTHERWISE SHOWN BY FLOW ARROWS ON THE DRAWINGS. LINEAR DIFFUSERS SHALL BE ADJUSTABLE 2-WAY FLOW. PROVIDE BATT INSULATION
ON DIFFUSER AND GRILLES THAT ARE EXPOSED TO CEILING PLENUM.
19. EXACT LOCATION OF CEILING DIFFUSERS, GRILLES AND REGISTERS SHALL BE DETERMINED BY
ARCHITECTURAL REFLECTED CEILING PLAN.
20. LOUVER PLENUMS SHALL BE PITCHED DOWN TOWARD THE BOTTOM OF THE LOUVER.
21. PROVIDE ACCESS PANELS TO ACCESS DAMPERS, EQUIPMENT, AND VALVES LOCATED ABOVE HARD
CEILINGS OR IN WALLS. ACTUAL LOCATIONS SHALL BE FIELD DETERMINED.
22. EXACT LOCATIONS OF THERMOSTATS, CO2 SENSORS, AND EMCS SENSORS SHALL BE COORDINATED WITH
FINAL LOCATIONS OF WALL-MOUNTED ARCHITECTURAL AND ELECTRICAL EQUIPMENT. MOUNT
THERMOSTATS AND CO2 SENSORS MINIMUM 48" AFF.
23. AIR HANDLING UNITS SERVING OCCUPIED AREAS SHALL HAVE MINIMUM MERV 8 PRE-FILTERS AND MERV 13 FINAL FILTERS. UNITS NOT SERVING OCCUPIED ZONES SHALL HAVE MINIMUM MERV 8 FILTER. FILTERS SHALL BE INDUSTRY STANDARD SIZE. FILTERS SHALL NOT CREATE PRESSURE DROP EXCEEDING 10% OF
EXTERNAL STATIC PRESSURE (ESP) CAPACITY LISTED IN EQUIPMENT SCHEDULE.
GENERAL MECHANICAL NOTES:
24. SUPPLY, RETURN, AND OUTDOOR AIR DUCTWORK SHALL BE INSULATED TO MEET OR EXCEED ASHRAE 189.1.
EXTERIOR SUPPLY AND RETURN AIR DUCTWORK SHALL BE PROVIDED WITH WEATHER-PROOF COVER.
25. COORDINATE LOCATIONS OF CONDENSATE DRAIN PIPING. PROVIDE CONDENSATE PUMPS, AS REQUIRED WHERE SUFFICIENT SLOPE IS NOT AVAILABLE FOR STANDARD GRAVITY DRAIN, WITH OVERRIDE SWITCH TO POWER DOWN THE ASSOCIATED AIR HANDLING EQUIPMENT IN CASE OF CONDENSATE PUMP FAILURE. CONDENSATE DRAIN LINE SHALL SLOPE DOWN TOWARDS DISCHARGE LOCATION AT A MINIMUM OF 1/8" PER LINEAR FOOT.
INSULATE INDOOR CONDENSATE PIPING IN ACCORDANCE WITH SPECIFICATIONS.
26. PROVIDE SUPPORTS FOR PIPING AND DUCTWORK IN ACCORDANCE WITH SPECIFICATIONS.
27. PROVIDE A MANUFACTURED EXPANSION DEVICE OR FABRICATED EXPANSION LOOP ON ALL DUCTWORK AND
PIPING SYSTEMS CROSSING BUILDING EXPANSION JOINTS.
28. PROVIDE SHUT-OFF VALVES AND FLEXIBLE CONNECTIONS AT PIPE CONNECTIONS TO HVAC EQUIPMENT.
29. FOR WALL, FLOOR, AND SLAB PENETRATIONS, SEAL AND PATCH ALL UNUSED PENETRATION SPACE TO MATCH EXISTING OR AS SHOWN ON MECHANICAL DETAILS SHEET. PROVIDE FIRE STOPPING FOR RATED WALLS AND
FLOORS.
30. INSTALL EXPOSED CONTROL WIRING IN CONDUIT. SEE DIVISION 26 SPECIFICATIONS FOR REQUIREMENTS.
31. MANUFACTURER NAME AND MODEL NUMBERS ARE BASIS OF DESIGN AND ARE SHOWN FOR INFORMATION ONLY.
REFER TO SPECIFICATIONS FOR COMPLETE REQUIREMENTS.
32. SPECIFICATIONS TAKE PRECEDENCE OVER DRAWINGS. HOWEVER, ITEMS SHOWN ON DRAWING BUT NOT IN THE SPECIFICATIONS ARE REQUIRED WITHIN THE PROJECT SCOPE. IN ADDITION, SPECIFIC ITEMS SHOWN ON THE DRAWINGS TAKE PRECEDENCE OVER SPECIFICATIONS IN CASES WHERE THE SPECIFICATION HAS OPTIONS.
33. ALL EQUIPMENT SHALL BE INSTALLED IN ACCORDANCE WITH MANUFACTURER'S APPROVED PUBLISHED
LITERATURE.
34. DUCT SIZES SHOWN ARE INSIDE CLEAR DIMENSIONS.
35. EXPOSED DUCTWORK, WITH THE EXCEPTION OF DUCTWORK IN MECHANICAL ROOMS SHALL BE DOUBLE-WALL, DUCTWORK WITH COATING.
36. IF SUSPECT ASBESTOS IS FOUND, STOP WORK IMMEDIATELY AND NOTIFY OWNER AND GENERAL CONTRACTOR.
OWNER IS RESPONSIBLE FOR ABATEMENT OF UNFORSEEN ASBESTOS.
37. NOT ALL MECHANICAL ABBREVIATIONS SHOWN WILL BE USED FOR THIS PROJECT.
38. ALL THERMOSTATS SHALL BE WALL MOUNTED AND WIRED.
39. ALL EQUIPMENT INSTALLED IN THIS PROJECT SHALL COMPLY WITH THE "BUY AMERICAN ACT". BASIS OF DESIGN SHOWN ON SCHEDULES IS TO ESTABLISH A STANDARD OF QUALITY, NOT TO LIMIT COMPETITION. EQUIVALENT
EQUIPMENT FROM ANOTHER MANUFACTURER IS ACCEPTABLE.
40. ALL COMMUNICATIONS PREMISE WIRING AND CABLE TRAYS THROUGHOUT THE FACILITY MUST BE PROTECTED AND UNINTERRUPTED DURING CONSTRUCTION. THIS INCLUDES ELECTRICAL POWER TO COMMUNICATIONS
EQUIPMENT. NO COMMUNICATIONS OUTAGES MUST TAKE PLACE WITHOUT THE CONSENT OF THE
CONTRACTING OFFICER.
41. CONTRACTOR MUST DEMOLISH ALL THERMOSTATS AND WIRING ASSOCIATED WITH THE HVAC SYSTEM TO BE
DEMOLISHED.
42. CONTROLS CONTRACTOR SHALL PROVIDE ALL LOW VOLTAGE DEVICES, CONDUCTORS, AND PATHWAYS IN
ACCORDANCE WITH THE REQUIREMENTS OF 26 20 00.
43. ALL SUPPLY AIR CFM VALUES SHOWN ON THE DRAWINGS ARE THE MAXIMUM VALUES, SEE SCHEDULES TO OBTAIN THE
OCCUPIED, UNOCCUPIED VALUES.
ABBREVIATIONS:
@ AT
& AND
AHU AIR HANDLING UNIT
ARCH ARCHITECT, ARCHITECTURAL
AS AIR SEPARATOR
ASHRAE AMERICAN SOCIETY OF HEATING, REFRIGERATING,
AND AIR CONDITIONING ENGINEERS
ASTM AMERICAN SOCIETY FOR TESTING AND
MATERIALS
BDD BACKDRAFT DAMPER
BLDG BUILDING
BTU, BTUH BRITISH THERMAL UNITS, BTUs PER HOUR
CD CONDENSATE DRAIN
CFM CUBIC FEET PER MINUTE
CHW CHILLED WATER
CHWR CHILLED WATER RETURN
CHWS CHILLED WATER SUPPLY
CLG COOLING
CMU CONCRETE MASONRY UNIT
CO CLEANOUT
CO2 CARBON DIOXIDE
CONC CONCRETE
COND STEAM CONDENSATE
CONN CONNECT, CONNECTING, CONNECTION
CONT CONTINUED
CONV STEAM CONVERTER
COP COEFFICIENT OF PERFORMANCE
COR CONTRACTING OFFICER'S (OWNER'S)
REPRESENTATIVE
CT COOLING TOWER
CU CONDENSING UNIT
CWR CONDENSER WATER RETURN
CWS CONDENSER WATER SUPPLY
D DEPTH
DB, Tdb DRY BULB (TEMPERATURE) dBA DECIBELS
DCW DOMESTIC COLD WATER
DDC DIRECT DIGITAL CONTROLS
DEG. F (°F) DEGREES FAHRENHEIT
DF DESTRATIFICATION FAN
DFCU DUCTLESS FAN COIL UNIT
DH DEHUMIDIFIER
DIA, Ø DIAMETER
DIV DIVISION
DN DOWN
DP, PD DIFFERENTIAL PRESSURE, PRESSURE DROP
DSCU DUCTLESS SPLIT CONDENSING UNIT
DSHP DUCTLESS SPLIT HEAT PUMP
DWG DRAWING
DX DIRECT EXPANSION
EA EXHAUST AIR
EAG EXHAUST AIR GRILLE
EAT ENTERING AIR TEMPERATURE
EER ENERGY EFFICIENCY RATIO
EF EXHAUST FAN
EFF EFFICIENCY
ELEC ELECTRICAL
EMCS ENERGY MONITORING AND CONTROLS SYSTEM
ERU ENERGY RECOVERY UNIT
ERV ENERGY RECOVERY VENTILATOR
ESP EXTERNAL STATIC PRESSURE
ET EXPANSION TANK
EUH ELECTRIC UNIT HEATER
EWT ENTERING WATER TEMPERATURE
EXT EXTERIOR
EXH EXHAUST
EXIST. EXISTING
FCU FAN COIL UNIT
FD FIRE DAMPER
FFE FINISHED FLOOR ELEVATION
FLA FULL LOAD AMPS
FOB FLAT ON BOTTOM
FOT FLAT ON TOP
FPM FEET PER MINUTE
FSD FIRE SMOKE DAMPER
FT FOOT, FEET
FT WG FEET WATER GAUGE
FV FLUE VENT
GA GAGE
GC GENERAL CONTRACTOR
GPM GALLONS PER MINUTE
GWH GAS WATER HEATER
H HEIGHT
HPS HIGH PRESSURE STEAM
HR HOUR
HTG HEATING
HTR HEATER
HTW HEATING WATER
HWR HEATING WATER RETURN
HWS HEATING WATER SUPPLY
HVAC HEATING, VENTILATING, AND AIR CONDITIONING
HX HEAT EXCHANGER
HZ HERTZ
IMC INTERNATIONAL MECHANICAL CODE
IN INCH, INCHES
IN WC INCHES WATER COLUMN
IN WG INCHES WATER GAUGE
IPLV INTEGRATED PART LOAD VALUE
KW KILOWATTS
L LENGTH, LOUVER (WALL)
LAT LEAVING AIR TEMPERATURE
LBD LINEAR BAR DIFFUSER
LBS POUNDS
LWT LEAVING WATER TEMPERATURE
MAX MAXIMUM
MBH 1000 BRITISH THERMAL UNITS
MCA MINIMUM CIRCUIT AMPACITY
MECH MECHANICAL
MERV MINIMUM EFFICIENCY REPORTING VALUE
MFCR, MFCG MANUFACTURER, MANUFACTURING
MIN MINIMUM
MOCP, MOP MAXIMUM OVER CURRENT PROTECTION
MTWR MEDIUM TEMPERATURE WATER RETURN
MTWS MEDIUM TEMPERATURE WATER SUPPLY
MXB MIXING BOX
N.C. NORMALLY CLOSED
NC NOISE CRITERIA
NG NATURAL GAS
NO. NUMBER
N.O. NORMALLY OPEN
NTS NOT TO SCALE
OA OUTSIDE AIR
OD OUTSIDE DAMPER
PCHWR PLANT CHILLED WATER RETURN
PCHWS PLANT CHILLED WATER SUPPLY
PD PRESSURE DROP
PH PHASE
PLBG PLUMBING
PMTWR PLANT MEDIUM TEMPERATURE WATER RETURN
PMTWS PLANT MEDIUM TEMPERATURE WATER SUPPLY
PPM PARTS PER MILLION
PRV PRESSURE RELIEF VALVE
PSI POUNDS PER SQUARE INCH
QTY QUANTITY
RA RETURN AIR
RAG RETURN AIR GRILLE
RH RELATIVE HUMIDITY, ROOF HOOD
RM ROOM
RPM REVOLUTIONS PER MINUTE
SA SUPPLY AIR
SAD SUPPLY AIR DIFFUSER
SAG SUPPLY AIR GRILLE
SD SMOKE DAMPER, SMOKE DETECTOR
SEER SEASONAL ENERGY EFFICIENCY RATIO
SF SUPPLY FAN
SMACNA SHEET METAL AND AIR CONDITIONING
CONTRACTOR'S NATIONAL ASSOCIATION
SP STATIC PRESSURE
STM STEAM
SS STAINLESS STEEL
TEMP TEMPERATURE
TSTAT THERMOSTAT
TYP TYPICAL
UH UNIT HEATER
UL UNDERWRITER'S LABORATORY
UMCS UTILITY MONITORING AND CONTROL SYSTEM
V VOLTAGE, VOLTS
VAV VARIABLE AIR VOLUME
VD VOLUME DAMPER
VFD VARIABLE FREQUENCY DRIVE
VRF VARIABLE REFRIGERANT FLOW
WB, Twb WET BULB (TEMPERATURE)
MISCELLANEOUS LEGEND:
AIR DISTRIBUTION DEVICE TAGS
DIFFUSER SUB-TYPE
A
400 AIRFLOW (CFM),
"PLENUM", OR
"TRANSFER"
NORTH ARROW
A
J
SD
SP
F
CO
DUCT SMOKE DETECTOR
CARBON MONOXIDE SENSOR
OVAL OR FLAT OVAL
CONTROL WIRING
STATIC PRESSURE SENSOR
ROUND OR DIAMETER
FIRESTAT
TEMPERATURE SENSORT
120 VOLT STAND BY POWER JUNCTION
BOX PROVIDED BY THE ELECTRICAL
CONTRACTOR. JUNCTION BOX IS
DEDICATED FOR USE BY THE CONTROLS
CONTRACTOR.
VARIABLE FREQUENCY DRIVEVFD
FLOW ARROW
RETURN AIR GRILLE
SUPPLY AIR DIFFUSER
FLOW ARROWS INDICATE AIR PATTERN.
NO FLOW ARROWS SHOWN INDICATES
4-WAY PATTERN.
EXHAUST AIR GRILLE
SERVICE CLEARANCE
T THERMOSTAT
H HUMIDISTAT
$ START/ STOP SWITCH
TH THERMOSTAT/ HUMIDISTAT
HUMIDITY SENSORH
DIFFUSER TYPE
XXX-
DP DIFFERENTIAL PRESSURE SENSOR
C CARBON DIOXIDE SENSOR
AQ AIR QUALITY SENSOR
POINT OF
RECONNECTION OR
EXTENT OF DEMOLITION
ELEVATION CROSS REFERENCEX
XXXXX
PIPING LEGEND:
CHILLED WATER SUPPLY
(CHWS)
HEATING WATER SUPPLY
(HWS)
HEATING WATER RETURN
(HWR)
HIGH PRESSURE STEAM SUPPLY
(HPS)
STEAM CONDENSATE RETURN
(COND)
EXISTING PIPING TO REMAIN
(EXIST.)
CONDENSATE DRAIN
(CD)
FLEXIBLE CONNECTION
THERMOMETER
PRESSURE REDUCING VALVE
MANUAL AIR VENT
PRESSURE/TEMPERATURE TAP WITH
BALL VALVE
PRESSURE SWITCH
PLUG VALVE
FLOW SWITCH
T&P RELIEF VALVE
AUTOMATIC AIR VENT
PRESSURE GAUGE WITH GAUGE COCK
PS
FS
BUTTERFLY VALVE
STRAINER WITH BLOWDOWN VALVE,
CAP, AND CHAIN
FLOW MEASURING/BALANCING/SHUT-
OFF VALVE
GATE VALVE
CHECK VALVE
BALL VALVE
CONCENTRIC REDUCER
DIRECTION OF FLOW
ECCENTRIC REDUCER
PIPE FLANGE
PIPE CAP
PIPE GUIDE (PG)
PIPE ANCHOR (PA) X
UNION
TEE OUTLET UP
BRANCH BOTTOM CONNECTION
BRANCH TOP CONNECTION
ELBOW UP
ELBOW DOWN
RISE OR DROP
TEE OUTLET DOWN
DUCTWORK LEGEND:
M
FIRE DAMPER
EXHAUST AIR DUCT DOWN
EXHAUST AIR DUCT UP
RETURN AIR DUCT DOWN
30"x14"
SQUARE TO ROUND DUCT BRANCH TAKE-OFF
WITH 45 DEGREE BRANCH INLET
ROUND DUCT BRANCH TAKE-OFF FROM
RECTANGULAR MAIN WITH CONICAL TAP
FLEXIBLE DUCT CONNECTION
DUCT SIZE TRANSITION
RECTANGULAR DUCT BRANCH TAKE-OFF
WITH 45 DEGREE BRANCH INLET
90 DEGREE DUCT ELBOW WITH TURNING VANES
24"Ø ROUND DUCT. DIAMETER INDICATED IN INCHES.
IN-LINE 90 DEGREE RISE/DROP IN
SUPPLY DUCT
FD
SD
DAMPER TYPE:
M - MOTORIZED DAMPER (ELECTRIC)
VD
SMOKE DAMPER
VOLUME/BALANCING DAMPER
(LABEL MAY BE OMITTED)
BD
BACKDRAFT DAMPER
(COUNTER-BALANCED UNLESS
OTHERWISE NOTED)
RADIUS DUCT ELBOW - ROUND OR
RECTANGULAR (MIN. 1.5 RADIUS UNLESS
OTHERWISE NOTED)
RECTANGULAR DUCT. SIZE INDICATED IN
INCHES, FIRST NUMBER IS SIDE SHOWN.
DASHED LINES INDICATE ACOUSTICAL LINER
FSD
COMBINATION
FIRE/SMOKE DAMPER
IN-LINE 90 DEGREE RISE/DROP IN
RETURN DUCT
DUCT SIZE TRANSITION RECTANGULAR TO
ROUND
30"/14" FLAT OVAL DUCT. SIZE INDICATED IN INCHES,
FIRST NUMBER IS SIDE SHOWN
RETURN AIR DUCT UP
SUPPLY OR OUTSIDE AIR DUCT DOWN
SUPPLY OR OUTSIDE AIR DUCT UP
IN-LINE 90 DEGREE RISE/DROP IN
EXHAUST DUCT
SD
DUCT MOUNTED SMOKE DETECTOR
GLOBE VALVE
PLAN
NORTH
EXISTING PIPING TO BE
DEMOLISHED
L-2A
L-2
L-7
L-6
L-8
101A
L-21
L-1B
L-1A L-1C
L-1
L-18
L-3 L-4
L-5
L-12
L-14B
L-14C L-14D
L-9L-1D
L-21C
L-21E
L-21D
35x16 14 x8
35x16 29x16 25x16
30x14 48x24
16"Ø x1 x2
"Ø
"Ø
12"Ø
"Ø
"Ø
6"Ø
10"Ø
18x12
"Ø
"Ø6"Ø x9
30x14
SCALE:
PHASE 2B MECHANICAL
HAVC DEMOLITION PLAN
3/16" = 1'-0"
MD101
0 4' 8' 16'
SCALE: 3/16"= 1'-0"
2'
111 1
1. EXISTING FUME HOOD TO BE DEMOLISHED.
2. EXISTING BIOSAFETY CABINET TO REMAIN.
3. EXHAUST SNORKEL TO BE DEMOLISHED.
4. EXISTING AHU-2 DUCTWORK TO REMAIN IN
PLACE.
KEYED NOTES
HWC
5-6
HWC
5-14
HWC
5-17
HWC
5-9
HWC
5-8
HWC
5-13
HWC
5-12
HWC
5-11
HWC
5-16
HWC
5-10
HWC
5-7
HWC
5-18
HWC
5-5
HWC
5-4
HWC
5-3
HWC
5-1
HWC
5-2
5-415-12
5-9
5-7
5-25-4
5-3
5-1 5-6
5-5
5-11
5-10 5-18
5-20
5-21
5-29 5-30
5-39
5-33
2-1
5-15
5-13
5-42
5-27
5-27
5-28
5-26
5-23
5-19
5-31
5-16
5-14
5-34
5-36
5-35
5-37
5-32
5-8
5-38
LEGEND:
EXISTING EQUIPTMENT TO
BE DEMOLISHED
EXISTING DUCTWORK TO BE
DEMOLISHED
4 4
L-2A L-2
L-7
L-6
L-8
101A
L-21
L-1B
L-1A
L-1C
L-1
L-18
L-3 L-4 L-5
L-12
L-14B
L-14C
L-14D
L-9
L-1D
L-21C
L-21E L-21D
SCALE:
PHASE 2B MECHANICAL
PIPING DEMOLITION PLAN
3/16" = 1'-0"
MD102
0 4' 8' 16'
SCALE: 3/16"= 1'-0"
2'
HWC
5-6
HWC
5-14
HWC
5-17
HWC
5-9
HWC
5-8
HWC
5-13
HWC
5-12
HWC
5-11
HWC
5-16
HWC
5-10
HWC
5-7
HWC
5-18
HWC
5-5HWC
5-4
HWC
5-3HWC
5-1HWC
5-2
2-1 2
1. DEMOLISH PHOENIX VALVE AND HOT WATER
REHEAT COIL. DEMOLISH PIPING, CONTROL
VALVES, AND APPURTENANCES BACK TO
ISOLATION VALVES AND PLUG.
2. EXISTING VAV TO REMAIN UNTIL PHASE 3B.
KEYED NOTES
GENERAL NOTES
1. REMOVE INSULATION FROM ALL PIPES AND
FITTINGS WITHIN THE AREA OF WORK ON THE
FOLLOWING SYSTEMS: CHILLED WATER SUPPLY,
CHILLED WATER RETURN, HEATING WATER
RETURN, AND HEATING WATER SUPPLY.
DEMO PIPING
EXISTING PIPING
LEGEND:
CHWR CHILLED WATER RETURN
CHWS CHILLED WATER SUPPLY
COND. CONDENSATE
HWR HEATING WATER RETURN
HWS HEATING WATER SUPPLY
VTR VENT THROUGH ROOF
POINT OF CONNECTION
EXIST. STEAM
PIPING TO REMAIN
HWC
5-151
EXIST. 2-1/2" HWR
TO REMAIN
EXIST. 1/2" HWR
AND 1/2" HWS TO
REMAIN EXIST. 1" HWR
AND 1" HWS TO
REMAIN
EXIST. STEAM
PIPING TO REMAIN
EXIST. 1-1/4" HWR
AND 1-1/4" HWS
TO REMAIN
EXIST. 3/4" HWS TO
REMAIN
EXIST. 1" HWS TO
REMAIN
EXIST. 1" HWS TO
REMAIN EXIST. 1-1/4"
HWS TO REMAIN
EXIST. 2-1/2"
HWR TO REMAIN
EXIST. 2" HWR
TO REMAIN
EXIST. 1-1/4"
HWS TO REMAIN
EXIST. 2" HWS
TO REMAIN
EXIST. 2" HWS
TO REMAIN
EXIST. 1" HWS TO
REMAIN
EXIST. 1" HWR
AND 1" HWS TO
REMAIN
EXIST. 1" HWR
AND 1" HWS TO
REMAIN
EXIST. 1" HWR TO
REMAIN
EXIST. 1-1/2"
HWR TO REMAIN
EXIST. 2" HWS
TO REMAIN
EXIST. 6" HWR
TO REMAIN
EXIST. 1/2" HWR
AND 1/2" HWS TO
REMAIN
EXIST. 3/4" HWR
AND 3/4" HWS TO
REMAIN
EXIST. 1/2" HWR
AND 1/2" HWS TO
REMAIN
EXIST. 1" HWR
AND 1" HWS TO
REMAIN
EXIST. 1" HWR
AND 1" HWS TO
REMAIN
EXIST. 1/2" HWR
AND 1/2" HWS TO
REMAIN
EXIST. 1/2" HWR
AND 1/2" HWS TO
REMAIN
EXIST. 1-1/4" HWR
AND 1-1/4" HWS
TO REMAIN
EXIST. 1/2" HWR
AND 1/2" HWS TO
REMAIN
EXIST. 1/2" HWR
AND 1/2" HWS TO
REMAIN
EXIST. 1/2" HWR
AND 1/2" HWS TO
REMAIN
EXIST. 1/2" HWR
AND 1/2" HWS TO
REMAIN
x3 x4
SCALE: 1/16" = 1'-0"
48'8' 16' 32'0
PHASE 2B MECHANICAL
ROOF DEMOLITION PLAN
1/16" = 1'-0"
MD103
PLAN
NORTH
1. EXISTING ROOFTOP FAN TO REMAIN.
2. EXISTING ROOFTOP FAN TO BE DEMOLISHED.
ROOF PENETRATION TO BE TEMPORARILY
CAPPED FOR CONNECTION TO NEW EQUIPMENT.
3. EXISTING AIR HANDLER UNIT TO REMAIN.
KEYED NOTES
EXIST. DUCTWORK
AND PIPING TO
REMAIN (TYP.)
1 1
8"Ø
8" Ø
8"Ø 10"Ø8" Ø
"Ø
8" Ø
"Ø
"Ø10
"Ø
8"Ø
8"Ø 8"Ø
8"Ø
8"Ø 8"Ø
8" Ø
"Ø
12"Ø
10"Ø 12"Ø
"Ø
14"Ø
"Ø
14"Ø10"Ø 12"Ø x2
"Ø
"Ø
26x18 24x16 10"Ø
12"Ø 12"Ø x1
2 14"Ø
"Ø
"Ø
8" Ø
"Ø
"Ø
"Ø 10
"Ø
"Ø
"Ø
"Ø
12"Ø 20x14 18x12
"Ø
"Ø
"Ø
"Ø
8" Ø
"Ø
10"Ø
10"Ø
12"Ø
"Ø
10"Ø
8" Ø
"Ø
"Ø
"Ø
"Ø
"Ø
10"Ø
"Ø
"Ø
8" Ø
10"Ø 14"Ø
"Ø
"Ø
"Ø
8" Ø
"Ø
"Ø
"Ø
14"Ø
8" Ø
12"Ø
"Ø
16"Ø
10"Ø 10"Ø
"Ø
10"Ø 10"Ø
"Ø
"Ø
12"Ø
"Ø
"Ø12"Ø
8" Ø
8"Ø
"Ø
"Ø
"Ø
10"Ø8"Ø 10"Ø
12"Ø
"Ø
"Ø 12
"Ø
"Ø
"Ø14
"Ø
SCALE:
PHASE 2B MECHANICAL
HAVC NEW WORK PLAN
3/16" = 1'-0"
MH101
0 4' 8' 16'
SCALE: 3/16"= 1'-0"
2'
GENERAL SHEET NOTES
1. AIR FLOWS SHOWN ON THIS SHEET INDICATE
THE OPERATING CONDITION WHERE NO FUME
HOODS OR BIO-SAFETY CABINETS ARE
ACTIVATED. SEE SCHEDULES FOR MINIMUM AND
MAXIMUM VALUES.
SAV-5-1
SAD-3
SAD-3
SAD-3
SAD-2
EAG-4
EAG-4
HC-21
H-7EAG-2
SAD-2
SAD-2
SAV-5-2
HEV-5-1 GEV-5-1
EAG-3
EAG-3
GEV-5-2
HC-22
KEYED NOTES
1. PROVIDE FUME HOOD AND CONTROLLER TO
INTERFACE WITH BAS SYSTEM. CONNECT FUME
HOOD TO EXISTING UTILITIES. FUME HOOD
SHALL BE INTERLOCKED WITH HOOD EXHAUST
VALVE FOR AIRFLOW CONTROL. CONNECT NEW
FUME HOOD TO EXISTING LAB UTILITIES.
2. INTERLOCK HOOD EXHAUST VALVE WITH
EXISTING BIOSAFETY CABINET CONTROLS.
3. 32"X20" OVAL SUPPLY DUCTWORK DOWN FROM
AHU-5.
4. 16"Ø DUCTWORK UP TO EF-11 ON ROOF.
5. 14"Ø DUCTWORK UP TO LEF-9 ON ROOF.
6. 12"Ø DUCTWORK UP TO LEF-10 ON ROOF.
7. 12"Ø DUCTWORK UP TO LEF-11 ON ROOF.
8. 10"Ø DUCTWORK UP TO LEF-12 ON ROOF.
9. 10"Ø DUCTWORK UP TO LEF-13 ON ROOF.
10. 12"Ø DUCTWORK UP TO LEF-14 ON ROOF. +
11. PROVIDE 6"Ø EXHAUST SNORKEL CONNECTION.
CONNECTION SHALL BE PROVIDED WITH
LOCKING QUADRANT DAMPER. BALANCE EACH
SNORKEL OUTLET TO 125 CFM.
EAG-4
SAD-2
SAD-2
GEV-5-3
SAV-5-3
HC-23
EAG-3
GEV-5-5
SAV-5-5
HC-25HEV-5-3
H-9
SAD-3
SAD-3
SAD-3
EAG-4
EAG-4
H-8
HEV-5-2
GEV-5-4
HC-24
SAV-5-4
SAD-3
SAD-3
SAD-3
SAD-2
SAD-2
SAD-2
EAG-4
EAG-4
GEV-5-6
SAV-5-6
HEV-5-4
HC-26
SAD-2
SAD-2
SAD-2
EAG-4
EAG-4
SAV-5-7
HC-27
GEV-5-8
GEV-5-7
SAD-2
SAD-2
SAD-2
EAG-4
EAG-4
SAD-1
100 EAG-3
110 SAV-5-9
GEV-5-10
HC-29
SAD-2
SAD-2
EAG-4
HC-30
SAV-5-10
HEV-5-5
GEV-5-11
SAD-3
SAD-3
SAD-3
SAD-3
SAV-5-11
HC-31
EAG-5
EAG-5
H-10
HEV-5-6
GEV-5-12
SAV-5-8
HC-28
GEV-5-9
SAD-3
SAD-3
SAD-3
SAD-3
SAD-3
VAV-5-1
x3 x4
SCALE: 1/16" = 1'-0"
48'8' 16' 32'0
PHASE 2B MECHANICAL
ROOF NEW WORK PLAN
1/16" = 1'-0"
MH102
PLAN
NORTH
KEYED NOTES
1. EXISTING EXHAUST FAN.
2. AIR HANDLER CONTROLLER TO BE INTERFACED
WITH NEW BAS SYSTEM.
3. PROVIDE EXHAUST FAN AND ROOF CURB.SEE
ARCH FOR ROOF CURB DETAIL.
EF-11 3
EXIST. AHU-6
EXIST. AHU-5
EXIST. AHU-4
EXIST. AHU-2
EXIST. AHU-1
LEF-9 LEF-12
LEF-11
LEF-13
LEF-14
LEF-10 3
1 1
L-2A
L-2
L-7
L-6
L-8
101A
L-21
L-1B
L-1A L-1C
L-1
L-18
L-3 L-4
L-5
L-12
L-14B
L-14C L-14D
L-9L-1D
L-21C
L-21E
L-21D
SCALE:
PHASE 2B MECHANICAL
PIPING NEW WORK PLAN
3/16" = 1'-0"
MP101
0 4' 8' 16'
SCALE: 3/16"= 1'-0"
2'
HC-21
HC-22
HC-23
HC-25
HC-24
HC-26
HC-27
HC-29
HC-30
HC-31
HC-28
EXIST. STEAM
PIPING TO REMAIN
EXIST. 2-1/2" HWR
TO REMAIN
EXIST. 1/2" HWR
AND 1/2" HWS TO
REMAIN
EXIST. 1" HWR
AND 1" HWS TO
REMAIN
EXIST. STEAM
PIPING TO REMAIN
EXIST. 1-1/4" HWR
AND 1-1/4" HWS
TO REMAIN
EXIST. 3/4" HWS TO
REMAIN
EXIST. 1" HWS TO
REMAIN
EXIST. 1" HWS TO
REMAIN EXIST. 1-1/4"
HWS TO REMAIN
EXIST. 2-1/2"
HWR TO REMAIN
EXIST. 2" HWR
TO REMAIN
EXIST. 1-1/4"
HWS TO REMAIN
EXIST. 2" HWS
TO REMAIN
EXIST. 2" HWS
TO REMAIN
EXIST. 1" HWS TO
REMAIN
EXIST. 1" HWR
AND 1" HWS TO
REMAIN
EXIST. 1" HWR
AND 1" HWS TO
REMAIN
EXIST. 1" HWR TO
REMAIN
EXIST. 1-1/2"
HWR TO REMAIN
EXIST. 2" HWS
TO REMAIN
EXIST. 6" HWR
TO REMAIN
EXIST. 1/2" HWR
AND 1/2" HWS TO
REMAIN
EXIST. 3/4" HWR
AND 3/4" HWS TO
REMAIN
EXIST. 1/2" HWR
AND 1/2" HWS TO
REMAIN
EXIST. 1" HWR
AND 1" HWS TO
REMAIN
EXIST. 1" HWR
AND 1" HWS TO
REMAIN
EXIST. 1/2" HWR
AND 1/2" HWS TO
REMAIN
EXIST. 1/2" HWR
AND 1/2" HWS TO
REMAIN
EXIST. 1-1/4" HWR
AND 1-1/4" HWS
TO REMAIN
EXIST. 1/2" HWR
AND 1/2" HWS TO
REMAIN
EXIST. 1/2" HWR
AND 1/2" HWS TO
REMAIN
EXIST. 1/2" HWR
AND 1/2" HWS TO
REMAIN
EXIST. 1/2" HWR
AND 1/2" HWS TO
REMAIN
KEYED NOTES
1. PROVIDE HOT WATER HEATING COIL WITH 3-WAY
CONTROL VALVE.
2. CONNECT NEW 1/2" HWS AND 1/2" HWR PIPING
TO EXISTING PIPING.
3. CONNECT NEW 3/4" HWS AND 3/4" HWR PIPING
TO EXISTING PIPING.
4. CONNECTION NEW 1" HWS AND 1" HWR PIPING
TO EXISTING PIPING.
5. TAP EXISTING HEATING WATER PIPING.
6. CONNECT EXISTING HWS AND HWR PIPING
TOGETHER.
GENERAL NOTES
1. PROVIDE INSULATION ON ALL NEW AND
EXISTING PIPING AND FITTINGS WITHIN THE
AREA OF WORK ON THE FOLLOWING SYSTEMS:
CHILLED WATER RETURN, CHILLED WATER
SUPPLY, HEATING WATER RETURN, HEATER
WATER SUPPLY.
2. BUILDING HEATING WATER SYSTEM MUST
REMAIN IN OPERATION THROUGHOUT
CONSTRUCTION. ANY DISRUPTION TO THE
EXISTING HEATING WATER SYSTEM MUST BE
COORDINATED WITH THE CONTRACTING
OFFICER.
1 1
2 5
VAV-5-1
SCALE:
PHASE 2B MECHANICAL
GREENHOUSE PLAN
3/16" = 1'-0"
M-101
0 4' 8' 16'
SCALE: 3/16"= 1'-0"
2'
PLAN
NORTH
GREENHOUSE
#6
GREENHOUSE
#7
GREENHOUSE
#8
SCALE:
PHASE 2B MECHANICAL
GREENHOUSE DEMO. PLAN
3/16" = 1'-0"
M-101
PLAN
NORTH
3 3
GREENHOUSE
#9
6 6
GREENHOUSE
#6
GREENHOUSE
#7
GREENHOUSE
#8
GREENHOUSE
#9
KEYED NOTES
1. EXISTING COOLING PAD TO BE DEMOLISHED.
2. EXISTING CIRCULATION PUMP TO BE
DEMOLISHED.
3. EXISTING CONTROL PANEL TO REMAIN.
4. PROVIDE NEW COOLING PAD.
5. PROVIDE NEW CIRCULATION PUMP.
6. EXISTING CONTROL PANEL.
EVAPORATIVE COOLING WALL SCHEDULE
HEIGHT
(FT)
LENGTHBASIS OF DESIGNMARK MEDIA
THICKNESS
MAX FACE
VELOCITY REMARKS
SEE NOTESECW-5
ECW-6
ECW-7
NOTES:
1. PROVIDE MAKE-UP WATER AS RECOMMENDED BY MANUFACTURER TO EACH COOLING WALL.
2. PROVIDE WITH SUBMERSIBLE PUMP BY COOLING CELL MANUFACTURER, SIZED FOR
COOLING CELL PRESSURE LOOP. COOLING CELL SHALL HAVE CELLULOSE-TYPE PADS. PUMP
POWER SHALL NOT EXCEED 3/4 HP AND SHALL BE RATED FOR 120V/ 1PH.
3. PROVIDE COOLING WALLS WITH BOTTOM TROUGH TO DRAIN BACK TO SUMP TANK.
4. PROVIDE 2-WAY CONTROL VALVE FOR EACH COOLING WALL TO INTERFACE WITH THE
EXISTING GREENHOUSE CONTROL SYSTEM.
SHAEFER 41'-4" 3 4" 400
SEE NOTES3 4" 400
SEE NOTES41'-3" 3 4" 400
41'-7"SHAEFER
SHAEFER
4 ECW-5
4ECW-6
4ECW-7
PIPE PENETRATION NOTES:
1. PROVIDE PITCH POCKET CONSTRUCTION, ADDITIONAL FLASHING, OR
WEATHER CAP AS REQUIRED FOR WATERPROOF CONSTRUCTION. DO NOT
MECHANICALLY ATTACH PIPE TO STRUCTURE IN ANY WAY.
2. SPACE BETWEEN PIPE AND SLEEVE SHALL BE FREE OF ANY FOREIGN
MATERIALS.
3. PIPE SHALL NOT CONTACT STRUCTURE AT ANY TIME. WEDGES ARE NOT BE
USED TO MAINTAIN PIPE POSITION.
4. PIPE MUST BE APPROXIMATELY CENTERED IN OPENING.
SCALE:
PIPE PENETRATION DETAIL
NOT TO SCALE
CAULK ALL JOINTS
AND SLEEVE ENDS
WATERTIGHT
PIPING
SCH. 40 PIPE STEEL SLEEVE
FOAM INSULATION OR
FIRE STOP MATERIAL
(FOR FIRE RATED
PARTITIONS)
PIPE INSULATION AS APPLICABLE
PARTITION
TO UNISTRUT P2500 SERIES
PIPE STRAP
(TYP.)
TO UNISTRUT P3400 SERIES PIPE
CLAMPS
(TYP.)
TO UNISTRUT P 1000 12 GA
CHANNEL
(TYP.)
SECURE W/APPROVED ANCHOR TO
MATCH BASE MATERIAL AND LOAD
REQUIREMENTS
INSULATE AS REQD
CONC. OR MASONRY WALL
TO UNISTRUT P 1000 12 GA
CHANNEL
(TYP.)
SECURE W/APPROVED ANCHOR TO
MATCH BASE MATERIAL AND LOAD
REQUIREMENTS
INSULATE AS REQD
CONC OR MASONRY WALL
NOTE:
PROVIDE MIN ANCHOR
SUPPORT SPACING
EVERY 3' VERTICALLY
FOR PIPES < 4"Ø
FOR CONDUIT <
2"Ø
SCALE:
PIPING WALL SUPPORT DETAIL
NOT TO SCALE
EXTERNALLY
INSULATED RIGID GALV
SHT MTL ROUND DUCT
EXTERNALLY
INSULATED
PRIMARY SA
DUCTS
AIR FLOW
EXTERNALLY INSULATED
SUPPLY DUCT
TRANSITION
AS REQUIRED
HEATING WATER REHEAT
COIL
H.P. FLEX
(12" MAX
LENGTH)
TRANSITION
AS REQUIRED
CONTROL PANEL. LOCATE FOR
OPTIMUM
ACCESS ABOVE CEILING. MAINTAIN
MFR'S
RECOMMENDED ACCESS
CLEARANCES
HIGH EFF TAKE-OFF
FITTING (W/O DAMPER).
AIR FLOW
REDUCING OR
ENLARGING
TRANSITION AS
REQUIRED
(W/O DAMPER).
EXTERNALLY
INSULATED RIGID GALV
SHT MTL ROUND DUCT
EXTERNALLY
INSULATED GALV
SHT MTL DUCT
SEE BELOW FOR DUCT
CONTINUATION TO BOX
EXTERNALLY
INSULATED GALV
SHT MTL DUCT
ALTERNATE TAKEOFF FOR
BOXES WITH TAKEOFF
FROM END OF RECT DUCT
SCALE:
SINGLE DUCT VAV BOX DETAIL
NOT TO SCALE
SCALE:
CLEVIS HANGER DETAIL
NOT TO SCALE
HEAVY DUTY
CLEVIS
HANGER: MSS
SP-69 AND MSS
SP-58
PIPE
RIGID INSULATION
INSERT (12" LONG,
180^ ARC)CLEVIS
HANGER WITH
INSULATION
SHIELD
INSULATION
BOLT & NUT
SUPPORT NUT
LOCKING NUT
TURNBUCKLE
W/LOCKNUT
HANGER ROD
AIR FLOW
KEYED NOTES
INSTALL BALANCING VALVE WITH
MINIMUM OF 3 STRAIGHT PIPE
DIAMETERS UPSTREAM AND 1
STRAIGHT PIPE DIAMETER
DOWNSTREAM.
MAINTAIN 6" MINIMUM CLEARANCE
ABOVE TEST PLUG TO ALLOW
GAUGE TO BE INSERTED. DO NOT
COVER PLUG WITH INSULATION.
INSTALL SWING JOINTS AT COIL
CONNECTIONS.
CONNECT BRANCH LINES FROM
COIL INTO TOP OR SIDE OF SUPPLY
AND RETURN MAINS. CONNECTING
INTO BOTTOM OF MAIN IS NOT
ACCEPTABLE.
PROVIDE COILS WITH INLET
STRAINERS AND CAPPED HOSE
CONNECTION BLOW DOWN VALVES.
INSTALL MANUAL AIR VENTS IN
SUPPLY AND RETURN COIL BRANCH
PIPING AS FOLLOWS:
A) IN PIPING HIGH POINT WHEN
PIPING IS ABOVE MAIN.
B) CLOSE TO COIL WHEN PIPING IS
NOT ABOVE MAIN (SIDE
CONNECTION).
NC
NO
C
HTWS
SHUT-OFF VALVE (TYP.)
HTWR
BALANCING VALVE
3-WAY CONTROL VALVE
DIRECT ACTING SIGNAL
PLUG VALVE, ADJUST
TO EQUAL GPM THRU
COIL AT DESIGN FLOW
TEST PLUG (TYP.)
1/2" PLUGGED DRAIN VALVE COIL
MANUAL AIR VENT,
3/8" BALL VALE (TYP.)
SCALE:
3-WAY HEATING WATER COIL DETAIL
NOT TO SCALE
12" MIN
12" MIN
SINGLE PIPE CLEVIS
HANGER
SCALE:
PIPE HANGER DETAILS
NOT TO SCALE
U-CLAMP OR
CONDUIT
CLAMP
GALVANIZED
IRON TRAPEZE
OR UNISTRUT
16 GAUGE
GALVANIZED
SHEET SHIELD
WRAPPED FULLY
AROUND
INSULATION
INSULATION
PIPE
PROVIDE A SECTION OF
HIGH COMPRESSION
STRENGTH INSULATION AT
EACH HANGER POINT.
INSULATION SHALL BE HALF
ROUND AND EXTEND 2"
BEYOND GALVANIZED
SHIELD EACH WAY.
16 GAUGE
GALVANIZED
SHEET SHIELD
WRAPPED FULLY
AROUND
INSULATION
INSULATION
PIPE
HARD METAL ROUND DUCT RUN OUT TO
DIFFUSER. SEE PLAN FOR SIZE
SAME SIZE AS GRILLE
NECK
REDUCER IF REQ'D.
BUTTERFLY DAMPER SHALL BE USED
AT THIS LOCATION OR AT
CONNECTION OF RUN-OUT TO MAIN
DUCT.
WORM GEAR DRIVE,
STAINLESS STEEL STRAP
LAY-IN GRILLE SHOWN.
SURFACE MOUNTED SIMILAR
SCALE:
TYPICAL RETURN/EXHAUST GRILLE CONNECTION DETAIL
NOT TO SCALE
AREAS WITH
HARD OR LAY
IN CEILINGS
AREAS OPEN
CEILINGS
(TYP.)
PROVIDE MANUAL OPPOSED DAMPER IN EACH BRANCH LINE
UNLESS OTHERWISE NOTED ON DRAWINGS. DAMPERS SHALL
BE INSTALLED IN ACCESSIBLE LOCATION NEAR TRUNK DUCT
AND MINIMUM OF 5'-0" FROM ANY AIR INLET OR OUTLET
DEVICE. COORDINATE W/ ACCESS DOORS IN NON-ACCESSIBLE
CEILINGS.
TRUNK
DUCT
OVAL BRANCH
DUCT
45° CLINCH COLLAR PER SMACNA
USE AT ALL BRANCH TAPS
UNLESS
SPLITTER DAMPERS ARE
INDICATED.
BELL-MOUTH
FITTING
NOTE:
DAMPERS SHALL BE PROVIDED IN ALL BRANCH RUN-OUTS TO DIFFUSERS, R.A AND EXHAUST GRILLES, UNLESS SPECIFICALLY NOTED OTHERWISE ON DRAWINGS.
LOCATE DAMPERS SO THEY ARE ACCESSIBLE FROM LAY-IN CEILING OR ACCESS DOORS.
SCALE:
BRANCH DUCT TAP DETAIL
NOT TO SCALE
ROUND
DUCT
DUCT HANGERS, ATTACH TO THE
STRUCTURE ABV.
RECTANGULAR, ROUND,
OR OVAL, DUCT MAIN
WITH EXTERNAL
INSULATION
CEILING DIFFUSER
SCALE:
TYPICAL DIFFUSER CONNECTION DETAIL
NOT TO SCALE
DUCT HANGERS, ATTACH TO THE STRUCTURE ABV.
RECTANGULAR, ROUND, OR OVAL DUCT MAIN WITH
EXTERNAL INSULATION
CEILING DIFFUSER
AREAS WITH
HARD OR LAY
IN CEILINGS
AREAS ABOVE
CEILING (TYP.)
ROUND DUCT WITH EXTERNAL
INSULATION
ATTACH THE FLEXIBLE DUCT TO
THE RIGID DUCT AND THE
DIFFUSER USING TWO (2) BANDS;
ONE FOR THE DUCT AND ONE FOR
THE INSULATION.
U.L. LISTED FLEXIBLE DUCT.
SUPPORT TO PREVENT SAG.
FLEXIBLE DUCT SHALL BE LESS
THAN 5 FT. IN LENGTH AND SHALL
NOT BE USED FOR BENDS
GREATER THAN 45°.
MANUAL DAMPER WITH LOCKING
QUADRANT REGULATOR.
RIGID 90° DUCT ELBOW
WITH EXTERNAL
INSULATION
ATTACH THE FLEXIBLE DUCT TO
THE RIGID DUCT AND THE
DIFFUSER USING TWO (2) BANDS;
ONE FOR THE DUCT AND ONE FOR
THE INSULATION.
U.L. LISTED FLEXIBLE DUCT.
SUPPORT TO PREVENT SAG.
FLEXIBLE DUCT SHALL BE LESS
THAN 5 FT. IN LENGTH AND SHALL
NOT BE USED FOR BENDS
GREATER THAN 45°.
MANUAL DAMPER WITH LOCKING
QUADRANT REGULATOR.
RIGID 90° DUCT ELBOW
WITH EXTERNAL
INSULATION
ROUND DUCT WITH EXTERNAL
INSULATION
SCALE:
TURNING VANE DETAIL
NOT TO SCALE
TURNING VANES, TYPICAL
TURNS 45° OR LARGER
RUNNER
INSTALL VANES
TANGENT TO
AIRSTREAM
DOUBLE SIDED TURNING
VANES REQUIRED WHERE
DUCT HEIGHT IS 24" OR
GREATER.
TOP RUNNER NOT SHOWN FOR
CLARITY.
NUMBER AND CONFIGURATION OF
VANES PER SMACNA STANDARDS.
20% MAXIMUM
AREA REDUCTION
R=H (MIN.)
L
W 15°H
W
L
DIM. "D"
ELEVATION
VIEW
PLAN
VIEW
DUCT DIM.
(SEE PLAN)
DUCT "VENTURI"
DEPRESSION DETAIL
NOTE: USE DETAIL
WHERE REQUIRED BY
FIELD CONDITIONS.
H R
TRANS.
DN.
TRANS.
UP
SCALE:
DUCT DEPRESSION FOR STRUCTURAL CONFLICTS DETAIL
NOT TO SCALE
MIN. 2/3
"D"
TYPICAL
OBSTRUCTION TO
DUCT PATH
3"
CABLE WRAP
AROUND BEAM
AND BAR JOIST
CL20
DUCTMATE
CLUTCHERS
WR20 CABLE
DUCT
DUCT
INSULATION
THREADED ROD
DOUBLE NUT
UNISTRUT OR
ANGLE
UNISTRUT BAR
BAR JOIST
CL20
DUCTMATE
CLUTCHER OR
EQUAL
DUCTMATE
WR20 CABLE
OR EQUAL
MINIMUM 3/8"
DIA. THREADED
ROD
12 GAUGE
GALVANIZED
STEEL
DUCT
DUCT
INSULATION
DOUBLE NUT
DUCT
EXTERNAL INSULATION WHERE
SPECIFIED
NOTE: FOR SIZES UP TO 60"
WITH 10' MAXIMUM SPACING.
NOTE: SEMI-CIRCLE
HANGER. 61"-72" DIAMETER
WITH 10' MAXIMUM
SPACING.
END VIEW ELEVATION VIEW
2"3 1/2" 1"
NOTE: FOR SIZES UP TO 60"
WITH 10' MAXIMUM SPACING.
SINGLE
DOUBLE
SCALE:
DUCT HANGER DETAILS
NOT TO SCALE
NOTE: 10' MAXIMUM SPACING.
97-120
85-96
72-84
61-72
DUCT SIZE (IN.) STRUT SIZE
1 5/8 X 1 5/8 X 12 GA
N/A
N/A
N/A
2 1/2 X 2 1/2 X 1/4
2 X 2 X 1/4
N/A
ANGLE SIZE
3 X 3 X 1/4
3/8
ROD SIZE
3/8
3/8
3/8
SCALE:
LAB FUME HOOD DETAIL
NOT TO SCALE
CEILING
DUCT WORK
CONNECTION
SASH
115VAC OUTLET
HAZARDOUS MATERIALS
STORAGE CABINET
HOOD UTILITIES
MONITOR
LIGHT SWITCH
CASEWORK TO BE PROVIDED
WITH ALL FUME HOODS
SCALE:
LAB EXHAUST FAN DETAIL (LEF-X & EF-X)
NOT TO SCALE
BYPASS AIR
SHIPPING SPLIT
AI
RF
LO
W
46"
CURB OVERLAP 2.5"
134.5"
12"
INLET CONNECTION DETAIL
4.8"
1.2"
WINDBAND
NOZZLE
FAN WITH MOTOR
DISCONNECT SWITCH
BYPASS PLENUM
BYPASS WEATHERHOOD
BYPASS DAMPER
DRAIN HOLE 1 INCH
MPT
Ø 40"
DRAIN HOLE 1/2 INCH FPT
ISOLATION DAMPER
FACTORY SUPPLIED
ROOF CURB
PLENUM
SKIRT
ROOF
CURBDUCT
DROP BY
OTHERS
FRONT SIDE
RIGHT SIDE
TOP VIEW
AI
RF
LO
W
PROVIDE GUY WIRES AS
RECOMMENDED BY
MANUFACTURER
FUME EXHAUST FAN SCHEDULE
BASIS
OF DESIGN MAX
SONES
VOLTS/
PHASE FLA MCA MOCP OTHER AS
NOTED
OPER.
WEIGHT
(LBS)
MARK LOCATION
RPMDRIVES.P.
IN.WC.
AIRFLOW
CFM
FAN DATA ELEC. DATA
POWER
HP
CONTROL INTERLOCKS
SWITCH
REMARKSFAN
TYPE
LEF-9 1040ROOF CONSTANTNO 4482263,2183.04 SEE NOTESCENT. 3.4 4.2 15460/3
NOTES:
1. FUME EXHAUST SYSTEM IS BE OF SPARK B RESISTANT ROOFTOP FANS.
LEF-10 ROOF CONSTANTNO SEE NOTES460/3
LEF-11 ROOF CONSTANTNO SEE NOTES460/3
LEF-12 ROOF CONSTANTNO SEE NOTES460/3
LEF-13 ROOF CONSTANTNO SEE NOTES460/3
LEF-14 ROOF CONSTANTNO SEE NOTES460/3DIRECT
DIRECT
DIRECT
DIRECT
DIRECT
DIRECTGREENHECK
VK-H-12-7
TYPE
HIGH PLUME
W/BYPASS
HIGH PLUME
W/BYPASS
HIGH PLUME
W/BYPASS
HIGH PLUME
W/BYPASS
HIGH PLUME
W/BYPASS
HIGH PLUME
W/BYPASS
3.03
3.03
3.01
3.01
3.03
CENT.
CENT.
CENT.
CENT.
CENT.
GREENHECK
VK-H-10-7
GREENHECK
VK-H-10-7
GREENHECK
VK-H-10-5
GREENHECK
VK-H-10-4
GREENHECK
VK-H-10-7
3/4243,369
3/4263,441
1263,688
1.6 2 15
1.6 2 15
2.1 2.6 15
4491253,611 2.1 2.6 15
1253,611 2.1 2.6 15 449
DUCT MOUNTED HEATING COIL SCHEDULE
BASIS
OF DESIGNMARK SERVES FUNCTION CAPACITY
MBH
AIRFLOW
CFM
COIL DATA
HC-21 MODINE LAB SUPPLY
AIR REHEAT 34.7935
2.70.21
EAT
°F
HC-22
HC-23
HC-24
HC-25
HC-26
HC-27
HC-28
HC-29
HC-30
HC-31
MODINE
MODINE
MODINE
MODINE
MODINE
MODINE
MODINE
MODINE
MODINE
MODINE
SAV-5-1
SAV-5-2
SAV-5-3
SAV-5-4
SAV-5-5
SAV-5-6
SAV-5-7
SAV-5-8
SAV-5-9
SAV-5-10
SAV-5-11
LAB SUPPLY
AIR REHEAT
LAB SUPPLY
AIR REHEAT
LAB SUPPLY
AIR REHEAT
LAB SUPPLY
AIR REHEAT
LAB SUPPLY
AIR REHEAT
LAB SUPPLY
AIR REHEAT
LAB SUPPLY
AIR REHEAT
LAB SUPPLY
AIR REHEAT
LAB SUPPLY
AIR REHEAT
LAB SUPPLY
AIR REHEAT
MAX APD
IN.WC.
MAX WPD
FT.HD.
0.03 0.2
LAT
°F
95.3
FLOW
GPM
3.10
1.10
EWT
°F
LWT
°F
SIZE
IN
16X14
61 95.5 180 157 16X14
255 10.2 0.02 0.10.9061 98.1 180 157 16X14
800 31.8 0.16 2.32.8061 97.8 180 157 16X14
61 180 157 16X14
440 16.4 0.04 0.91.5061 95.5 180 157 16X14
405 15.6 0.04 0.81.4061 96.5 180 157 16X14
390 15.2 0.04 0.71.4061 96.9 180 157 16X14
100 3.67 0.5 5.00.3261 95 180 157 12X14
325 12.1 0.03 0.21.1061 95.4 180 157 16X14
850 32.9 0.18 2.42.9061 96.8 180 157 16X14
800 97.8
HOOD EXHAUST VALVE SCHEDULE
BASIS
OF DESIGNMARK ROOM FUNCTION
MINMAX
CFM
HEV-5-1 PHOENIX L-1 FUME HOOD
EXHAUST
HEV-5-2 PHOENIX L-2
HEV-5-3 PHOENIX L-2A
HEV-5-4 PHOENIX
HEV-5-5 PHOENIX
HEV-5-6 PHOENIX
L-3
L-7
L-8
150790
VALVE
DIAMETER
(IN)
PD ACROSS
VALVE
(IN)
0.6-3.0
0.6-3.0
0.6-3.0
0.6-3.0
0.6-3.0
0.6-3.0
BIO-SAFETY
CABINET
EXHAUST
UNOCCUPIED
FUME HOOD
EXHAUST
FUME HOOD
EXHAUST
BIO-SAFETY
CABINET
EXHAUST
FUME HOOD
EXHAUST
LABORATORY EXHAUST FAN SCHEDULE
BASIS
OF DESIGN MAX
SONES
VOLTS/
PHASE
DAMPER
TYPE
DISC
SWITCH
BYPASS
PLENUM
OTHER AS
NOTED
OPER.
WEIGHT
(LBS)
MARK LOCATION MODEL
RPMDRIVES.P.CFM
FAN DATA OPTIONS ELEC. DATA
POWER
HP
CONTROL INTERLOCKS
SWITCH
REMARKSFAN
TYPE
EF-11 GREENHECK 1625CK-H-14-9ROOF CONSTANTNO 6402262,5423.27 DIRECT SEE NOTESCENT. MOTORIZED YES YES460/3
31.8 0.16 2.32.80
GENERAL EXHAUST VALVE SCHEDULE
BASIS
OF DESIGNMARK ROOM FUNCTION MIN
OCCUPIED
MAX
OCCUPIED
CFM
GEV-5-1 PHOENIX GENERAL LAB
EXHAUST
GEV-5-2 PHOENIX
GEV-5-3 PHOENIX
GEV-5-4 PHOENIX
GEV-5-5 PHOENIX
GEV-5-6 PHOENIX
GEV-5-7 PHOENIX
GEV-5-8 PHOENIX
GEV-5-9 PHOENIX
GEV-5-10 PHOENIX
GEV-5-11 PHOENIX
GEV-5-12 PHOENIX
GENERAL LAB
EXHAUST
GENERAL LAB
EXHAUST
GENERAL LAB
EXHAUST
GENERAL LAB
EXHAUST
GENERAL LAB
EXHAUST
GENERAL LAB
EXHAUST
GENERAL LAB
EXHAUST
GENERAL LAB
EXHAUST
GENERAL LAB
EXHAUST
GENERAL LAB
EXHAUST
GENERAL LAB
EXHAUST
L-1/L-1A
L-1B
L-1C/L-1D
L-2
L-2A
L-3
L-4
L-4
L-5
L-6
L-7
L-8
VALVE
DIAMETER
(IN)
PD ACROSS
VALVE
(IN)
0.6-3.0
0.6-3.0
0.6-3.0
0.6-3.0
0.6-3.0
0.6-3.0
0.6-3.0
0.6-3.0
0.6-3.0
0.6-3.0
0.6-3.0
0.6-3.0
SUPPLY AIR VALVE SCHEDULE
BASIS
OF DESIGNMARK ROOM FUNCTION MIN
OCCUPIED
MAX
OCCUPIED
CFM
SAV-5-1 PHOENIX L-1/L1A LAB SUPPLY
AIR
SAV-5-2 PHOENIX L-1B
SAV-5-3 PHOENIX L-1C/L-1D
SAV-5-4 PHOENIX
SAV-5-5 PHOENIX
SAV-5-6 PHOENIX
SAV-5-7 PHOENIX
SAV-5-8 PHOENIX
SAV-5-9 PHOENIX
SAV-5-10 PHOENIX
SAV-5-11 PHOENIX
L-2
L-2A
L-3
L-4
L-5
L-6
L-7
L-8
645935
VALVE
DIAMETER
(IN)
PD ACROSS
VALVE
(IN)
0.6-3.0
0.6-3.0
0.6-3.0
0.6-3.0
0.6-3.0
0.6-3.0
0.6-3.0
0.6-3.0
0.6-3.0
0.6-3.0
0.6-3.0
8LAB SUPPLY
AIR
LAB SUPPLY
AIR
LAB SUPPLY
AIR
LAB SUPPLY
AIR
LAB SUPPLY
AIR
LAB SUPPLY
AIR
LAB SUPPLY
AIR
LAB SUPPLY
AIR
LAB SUPPLY
AIR
LAB SUPPLY
AIR
450 450
430 430
110 110
150 100
790 150
REMARKS
SNORKEL EXHAUST
SEE CONTROLS
UNOCCUPIED
UNOCCUPIED
LAB OFFSET SCHEDULE
ROOM
CFM
REMARKSUNOCCUPIED
-35
-15
-10
-30
-15
-25
-25
-20
-10
-5
-45
OCCUPIED
-105
-35
-25
-90
-90
-50
-45
-40
-10
-35
-90
NOTES:
1. SUBMIT FINISH/FRAME STYLE OFF ALL DEVICES FOR REVIEW.
2. PROVIDE WITH ALUMINUM CONSTRUCTION.
GRILLE, REGISTER AND DIFFUSER SCHEDULE
MARK TYPE USE
S
PANEL
SIZE IN.
NECK
SIZE IN.
MAX CFM MAX PD
IN. WC FINISH PATTERN REMARKSR E
MAX. NOISE
CRITERIA (NC)
24X24 4-WAY SEE NOTESXSAD-1 110 OFF
WHITE
0.025 10
SEE NOTESXSAD-2 200 0.025 10OFF
WHITE
24X24 PERF. SEE NOTESXEAG-3 200 0.025 10OFF
WHITE
24X24 PERF. SEE NOTESXEAG-4 HARD CEILING
MOUNTED
300 0.025 10OFF
WHITE
SAD-3 X
0.02545012Ø32X32XEAG-5 OFF
WHITE
SEE NOTES
SEE NOTES10
HARD CEILING
MOUNTED
HARD CEILING
MOUNTED
SAD-4 X
24X24 10Ø 300 0.025 OFF
WH…