Appendix G - 7th St Garage High-Priority Structural Repair Bid Set - Drawings.pdf
PDF 6 MB Posted
- Solicitation number
- IFB1 GMAA 2027000031 2
- Issued by
- Denver County, Denver City, Colorado
About this file
This file consists of structural repair bid set drawings for the 7th Street Parking Garage at the Auraria Campus in Denver, Colorado, prepared by Martin/Martin, Inc. (Project No. 24.0355.S.03) with a 100% Construction Set date of April 8, 2026. The project encompasses high-priority structural repairs and waterproofing at 799 Lawrence Way, Denver, Colorado 80204, under the management of Auraria Higher Education Center (AHEC). The work includes 28 distinct work items covering concrete repair, structural reinforcement, joint sealant replacement, traffic coating application, and penetrating sealer installation across four parking levels and associated ramps. Estimated quantities include 150,900 square feet of traffic coating removal and repair, 25,100 square feet of silane sealer application, 19,300 square feet of concrete repair, 5,400 linear feet of joint sealant replacement, and approximately 131,000 square feet of traffic coating application. Construction is phased to allow 50% closure of Levels 1-3 simultaneously while permitting full closure of Level 4, with work scheduled between May 18, 2026, and August 14, 2026. The contractor must provide a detailed phasing plan for owner and engineer review prior to work commencement.
Bid pricing shall reflect specified products including SIKAEMACO, PLANITOP, VERSASPEED, and US CONCRETE PRODUCTS repair mortars for various applications, with polyurethane sealants and heavy-duty traffic coatings as specified. The contractor is responsible for all temporary shoring and bracing design, with monthly rental costs included in the bid. Concrete repair work requires compressive strength testing at 7, 28, and 56 days to achieve minimum 5,000 PSI, with a maximum water-cement ratio of 0.40. Quality assurance includes continuous or periodic inspection by a qualified inspection agency, with composite sample testing required per ASTM standards. Post-installed anchors must comply with manufacturer specifications, including Hilti HIT-HY 200A adhesive anchors and mechanical anchors as detailed. Deferred submittal items include shoring design for structural elements and penetrating sealer mockup testing, all requiring sealed structural calculations by a licensed Colorado professional engineer. The contractor must coordinate with AHEC and parking services for phasing adjustments, provide all required submittals in electronic format, and maintain current schedules of values with completed quantities for weekly owner review.
View the file
Other files
Show all 14
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
© MARTIN/MARTIN 2026
M a rt in
/M ar ti n
, I n c . c o n s id e rs t h at d es ig n d a ta is o n ly i n i ts f in a l f o rm o n p lo tt e d d ra w in g s w it h o ri g in a l s ig n a tu re s a n d p ro fe s s io n a l c er ti fi ca ti o n b ei n g v is ib ly p re s en t o n t h e d ra w in g s . D a ta s u p p lie d v ia c o m p u te r g en e ra te d f o rm a t d o es n o t c o n ta in t h is a p p ro v al o r ce rt if ic a ti o n
T h e r ec ei v er o f el e ct ro n ic a ll y tr a n s m it te d d ra w in g s is r e s p o n s ib le f o r v er if yi n g t h e in fo rm a ti o n c o n ta in e d w it h in t h e e le c tr o n ic d a ta a g a in s t th e r ec o rd e d o r ap p ro v ed d o cu m en ts
T h e u se o f el e ct ro n ic a lly t ra ns m itt e d d ra w in g s is c on si d e re d to b e a t yo u r o w n r is k.
M a rt in
/M a rt in
In c.
a ss u m e s n o re sp on si b ili ty f o r a ny c la im s o r da m a ge s re su lti ng f ro m y o u r us e o f t h is in fo rm a tio n.
E le ct ro ni c in fo rm a tio n is p ro vi d ed fo r th e co nv en ie nc e o f th e r e ci p ie nt o nl y.
T h e r ec ip ie n t of t hi s fil e a gr ee s th a t th e in fo rm a tio n m ay n ot b e tr a ns fe rr ed t o a ny o th e r p ar ty
AERIAL PHOTO
VICINITY MAP
CONSULTANT
OWNER'S REPRESENTATIVE
DRAWING INDEX
HIGH PRIORITY STRUCTURAL REPAIRS AND WATERPROOFING
AURARIA CAMPUS
7th STREET PARKING GARAGE
799 LAWRENCE WAY
DENVER, COLORADO 80204
MARTIN/MARTIN PROJECT NO. 24.0355.S.03
100% CONSTRUCTION SET: 04/08/2026
CONTACT: ARTURO GARCIA, PE
AURARIA HIGHER EDUCATION CENTER
1156 7th STREET, SUITE 103
DENVER, COLORADO 80204
CONTACT: LEAH BYERS
303.556.8056
303.431.6100
STRUCTURAL SHEET LIST
SHEET
NUMBER SHEET NAME
S0.1 GENERAL NOTES
S0.2 GENERAL NOTES
S0.3 QUALITY ASSURANCE
S0.4 WORK LIST
S1.0 LEVEL 1 PLAN - NORTH
S1.1 LEVEL 1 PLAN - SOUTH
S1.2 LEVEL 2 PLAN - NORTH
S1.3 LEVEL 2 PLAN - SOUTH
S1.4 LEVEL 3 PLAN - NORTH
S1.5 LEVEL 3 PLAN - SOUTH
S1.6 LEVEL 4 PLAN - NORTH
S1.7 LEVEL 4 PLAN - SOUTH
S2.0 LEVEL 1 RCP - NORTH
S2.1 LEVEL 1 RCP - SOUTH
S2.2 LEVEL 2 RCP - NORTH
S2.3 LEVEL 2 RCP - SOUTH
S2.4 LEVEL 3 RCP - NORTH
S2.5 LEVEL 3 RCP - SOUTH
S3.0 DETAILS
S3.1 DETAILS
S3.2 DETAILS
SP0.1 JOINT SEALANT SPECIFICATION
SP0.2 SILANE SEALER SPECIFICATION
SP0.3 TRAFFIC COATING SPECIFICATION
SP0.4 EPOXY OVERLAY SPECIFICATION
NORTH
NORTH
799 LAWRENCE WAY
7th STREET PARKING GARAGE a rt in
/M ar ti n
, I n c . c o n s id e rs t h at d es ig n d a ta is o n ly i n i ts f in a l f o rm o n p lo tt e d d ra w in g s w it h o ri g in a l s ig n a tu re s a n d p ro fe s s io n a l c er ti fi ca ti o n b ei n g v is ib ly p re s en t o n t h e d ra w in g s . D a ta s u p p lie d v ia c o m p u te r g en e ra te d f o rm a t d o es n o t c o n ta in t h is a p p ro v al o r ce rt if ic a ti o n
T h e r ec ei v er o f el e ct ro n ic a ll y tr a n s m it te d d ra w in g s is r e s p o n s ib le f o r v er if yi n g t h e in fo rm a ti o n c o n ta in e d w it h in t h e e le c tr o n ic d a ta a g a in s t th e r ec o rd e d o r ap p ro v ed d o cu m en ts
T h e u se o f el e ct ro n ic a lly t ra ns m itt e d d ra w in g s is c on si d e re d to b e a t yo u r o w n r is k.
M a rt in
/M a rt in
In c.
a ss u m e s n o re sp on si b ili ty f o r a ny c la im s o r da m a ge s re su lti ng f ro m y o u r us e o f t h is in fo rm a tio n.
E le ct ro ni c in fo rm a tio n is p ro vi d ed fo r th e co nv en ie nc e o f th e r e ci p ie nt o nl y.
T h e r ec ip ie n t of t hi s fil e a gr ee s th a t th e in fo rm a tio n m ay n ot b e tr a ns fe rr ed t o a ny o th e r p ar ty
PROJECT NO:
DATE:
REVISIONS
SHEET TITLE:
SHEET NUMBER:
M M
J O
B
P
R
IN
C
IP
A L:
E O
R
P R
O
JE
C T
M A
N A
G E
R
D E
S
IG
N E
R S
LE
A D
R E
V
IT
T E
C H
D
A T
E P
R
IN
T E
D
F
IL
E P
A T
H
4/
/2
4:
:1
P
M A ut od es k
D oc s:
//A
C C
-M M
S
/2 4.
.S .0
3-
La w re nc e
W ay
H ig h P rio rit y- S
.rv t
H
IG
H P
R
IO
R
IT
Y S
T R
U C
T U
R A
L R
E P
A
IR
S A
N D
W A
T E
R P
R O
O F
IN
G
A U
R A
R
IA
C A
M P
U S
7t h
S T
R E
E T
P A
R K
IN
G
G A
R A
G E
LA
W
R E
N C
E W
A Y
D E
N V
E R
, C O
LO
R
A D
O
04/08/2026
S0.1
GENERAL NOTES
© MARTIN/MARTIN 2026
A R
T G
A R
C
IA
B E
N E
S T
R
IC
H
T A
M I
W O
R K
E R
.0
5.
S .0
T A
M I
W O
R K
E R
J.
W
IL
LI
A M
S
24.0355.S.03
1) CONNECTIONS AND ASSEMBLIES:
1A) PROVIDE CONNECTIONS AND ASSEMBLIES AS SHOWN IN THE DETAILS HEREIN.
1B) FABRICATE AND ASSEMBLE IN SHOP TO GREATEST EXTENT POSSIBLE. FABRICATE ACCORDING TO AISC’S “CODE OF
STANDARD PRACTICE FOR STEEL BUILDINGS AND BRIDGES” AND AISC 360.
2) BOLTING REQUIREMENTS:
2A) BOLT HOLES: CUT, DRILL, MECHANICALLY THERMAL CUT, OR PUNCH STANDARD BOLT HOLES PERPENDICULAR TO METAL
SURFACES. DO NOT ENLARGE BOLTS BY BURNING.
- BOLT HOLE SIZES SHALL BE INSTALLED AS REQUIRED BY ANSI/AISC 360-16 TABLE J3.3 INCLUDING STANDARD, OVERSIZE, SHORT-SLOT, OR LONG-SLOT. HOLES ARE STANDARD SIZE UNLESS NOTED OTHERWISE.
2B) UNLESS INDICATED OTHERWISE, SNUG TIGHTEN ALL JOINTS AS DEFINED BY AISC.
3) WELDING REQUIREMENTS:
3A) HAVE IN POSSESSION CURRENT EVIDENCE OF PASSING THE APPROPRIATE AWS QUALIFICATION TESTS.
3B) MINIMUM WELDS: AISC SPECIFICATION, NOT LESS THAN 3/16” FILLET, CONTINUOUS UNLESS OTHERWISE NOTED.
3C)WELD SIZES AND LENGTHS CALLED FOR ON THE DRAWINGS ARE THE NET EFFECTIVE REQUIRED. INCREASE WELD SIZE IF
GAPS EXIST AT THE FAYING SURFACE.
3D)WELD SIZES SHALL BE AS SHOWN UNLESS A GREATER SIZE IS REQUIRED BY ANSI/AISC 360-16 TABLES J2.3 AND J2.4.
3E) ALL GROOVE WELDS SHALL BE COMPLETE PENETRATION UNLESS NOTED.
3F) FIELD WELDING SYMBOLS INDICATE SEQUENCE CONSIDERED DURING DESIGN.
4) STEEL FINISHES:
4A) UNLESS OTHERWISE NOTED, PRIME STEEL ASSEMBLIES WITH RUST-INHIBITING SHOP PRIMER, TOUCH UP PRIMER
DAMAGED DURING FIELD WELDING OPERATIONS.
STEEL NOTES
METAL DECKING A1008/A653 50 - -
WELDING ELECTRODES E70 - - PER AWS
RECT HSS A500 GR C 50 62 -
PLATES A36 36 58 -
OTHER SHAPES
A36 36 58 A572 WITH Fy=50 KSI AND Fu=65 KSI
ACCEPTABLE AT CONTRACTOR'S
OPTION
BOLTS F3125 - GRADE
A325
- 120 BOLTS ARE 3/4"Ø UNO
ANCHOR RODS
- - - SEE "POST-INSTALLED ANCHOR NOTES"
STEEL ELEMENT ASTM/TYPE Fy (KSI) Fu
(KSI)
COMMENTS
STEEL MATERIAL TABLE
1) GENERAL:
1A) ENGINEER: REFERENCES ON THE STRUCTURAL DRAWINGS TO ‘ENGINEER’ MEAN THE STRUCTURAL ENGINEER OF RECORD. OTHER ENTITIES ARE SPECIFICALLY NOTED AS “CONTRACTOR’S ENGINEER”, “MECHANICAL ENGINEER”, ETC.
1B) THESE NOTES SUPPLEMENT THE SPECIFICATIONS, WHICH SHALL BE REFERENCED FOR ADDITIONAL REQUIREMENTS.
1C)STRUCTURAL ELEMENTS ARE CENTERED ON GRID LINES AND GRID LINE INTERSECTIONS UNLESS DIMENSIONED
OTHERWISE.
2) USE OF DRAWINGS:
2A) DO NOT SCALE DRAWINGS.
2B) DETAILS ON DRAWINGS TAKE PRECEDENCE OVER GENERAL NOTES AND TYPICAL DETAILS.
2C)DETAILS NOTED TYPICAL APPLY TO ALL SIMILAR CONDITIONS. WHERE NO SPECIFIC DETAILS ARE SHOWN, CONSTRUCTION
SHALL CONFORM TO SIMILAR WORK ELSEWHERE ON THE PROJECT.
2D)WHERE DISCREPANCIES OCCUR BETWEEN PLANS, DETAILS, GENERAL NOTES AND SPECIFICATIONS:
- CONTACT THE ENGINEER PRIOR TO PROCEEDING WITH CONSTRUCTION
- THE MORE STRINGENT REQUIREMENTS SHALL GOVERN FOR PRICING
3) EXISTING STRUCTURES:
3A) CONTRACT DOCUMENTS HAVE BEEN PREPARED USING AVAILABLE DRAWINGS AND SITE OBSERVATION AS PERMITTED BY
ACCESS RESTRICTIONS DURING DESIGN.
3B) DURING CONSTRUCTION, THE CONTRACTOR MAY ENCOUNTER EXISTING CONDITIONS WHICH ARE NOT KNOWN OR ARE AT VARIANCE WITH PROJECT DOCUMENTATION. CONTRACTOR SHALL NOTIFY THE ENGINEER OF ALL CONDITIONS NOT PER THE
CONTRACT DOCUMENTS. EXAMPLES INCLUDE:
- SIZES OR DIMENSIONS OTHER THAN THOSE SHOWN
- DAMAGE OR DETERIORATION TO MATERIALS AND COMPONENTS
- CONDITIONS OF INSTABILITY OR LACK OF SUPPORT
- ITEMS NOTED AS EXISTING ON THE DRAWINGS BUT NOT FOUND IN THE FIELD
3C)CONTRACTOR SHALL FIELD VERIFY ALL EXISTING STRUCTURAL CONDITIONS PRIOR TO SUBMITTING SHOP DRAWINGS.
4) SUBMITTALS, SUBSTITUTIONS AND SITE VISITS:
4A) SUBMITTALS:
- REFER TO SPECIFICATIONS FOR DETAILED REQUIREMENTS. PROVIDE THE FOLLOWING SUBMITTALS:
---- ALL PRODUCT DATA AND MATERIALS INCLUDING BUT NOT LIMITED TO: CONCRETE REPAIR PRODUCTS, SLIDE BEARING
PRODUCTS, GALVANIC ANODE PRODUCTS, SEALANTS, TRAFFIC COATING, ETC.
-----PHASING PLAN
---- DEFERRED SHORING DESIGN SUBMITTAL
---- WELDER AWS CERTIFICATIONS
---- JOINT SEALANT ADHESION TEST RESULTS
---- TRAFFIC COATING MOCK-UP PLAN WITH ADHESION TESTING
---- MOCKUP FOR RAMP TRACTION FINISH TO MATCH ORIGINAL TEXTURED FINISH
---- CONVENTIONAL CONCRETE MIX DESIGN
---- STEEL MATERIAL MILL CERTIFICATIONS
---- PENETRATING SEALER MOCKUP TO DETERMINE APPLICATION RATE AND NUMBER OF COATS
---- STEEL SHOP DRAWINGS COORDINATED WITH EXISTING CONDITIONS
- IF THE CONTRACTOR REQUESTS A CHANGE FROM THE STRUCTURAL DRAWINGS, IT SHALL BE APPROVED BY THE ENGINEER AND DESIGNED BY MARTIN/MARTIN, INC. PRIOR TO SUBMITTING SHOP DRAWINGS. VARIATION SHALL BE INDICATED ON THE SHOP DRAWINGS. CONTRACTOR SHALL COMPENSATE MARTIN/MARTIN, INC. FOR MAKING THE CHANGE.
- CONSTRUCTION DOCUMENTS SHALL NOT BE REPRODUCED FOR USE IN SUBMITTALS
- ALL SHOP DRAWINGS SHALL REFERENCE THE STRUCTURAL DRAWING NUMBER AND DETAIL USED TO PREPARE THE
SUBMITTAL
4B) SUBSTITUTIONS: ENGINEER’S APPROVAL SHALL BE SECURED FOR ALL SUBSTITUTIONS
4C)NONCONFORMANCE: NOTIFY ENGINEER OF CONDITIONS NOT CONSTRUCTED PER THE CONTRACT DOCUMENTS PRIOR TO PROCEEDING WITH CORRECTIVE WORK. SUBMIT PROPOSED REPAIR TO THE ENGINEER FOR ACCEPTANCE. CONTRACTOR
SHALL COMPENSATE MARTIN/MARTIN, INC. FOR DESIGNING THE REPAIR.
4D)ALL SHOP DRAWINGS SHALL BE SUBMITTED IN ELECTRONIC FORMAT ONLY.
4E) SITE VISITS: PROVIDE THE ENGINEER WITH ADEQUATE NOTICE FOR SITE OBSERVATIONS.
5) TEMPORARY CONDITIONS AND CONSTRUCTION ENGINEERING
5A) THE STRUCTURE IS DESIGNED TO FUNCTION AS A UNIT UPON COMPLETION AND ONLY FOR LOADS ANTICIPATED DURING
THE STRUCTURE’S SERVICE LIFE.
5B) THE CONTRACTOR IS RESPONSIBLE FOR FURNISHING ALL TEMPORARY BRACING AND/OR SUPPORT THAT MAY BE REQUIRED AS THE RESULT OF THE CONTRACTOR’S CONSTRUCTION METHODS AND/OR SEQUENCES. CONTRACTOR SHALL PROVIDE ALL REQUIRED ENGINEERING AND OTHER MEASURES TO ACHIEVE THE MEANS, METHODS, AND SEQUENCES OF
WORK WHICH MAY INCLUDE, BUT IS NOT LIMITED TO:
- LAYOUT
- DESIGN FOR FORM WORK, SHORING, AND RESHORING
- WELD PROCEDURES
- SURVEYING TO VERIFY CONSTRUCTION TOLERANCES
- EVALUATION OF TEMPORARY CONSTRUCTION LOADS ON STRUCTURE DUE TO EQUIPMENT AND MATERIALS
- STRUCTURAL ENGINEERING TO RESIST ANY OTHER LOADS NOT IDENTIFIED ON DESIGN DRAWINGS
5C)CONTRACTOR’S CONSTRUCTION AND/OR ERECTION SEQUENCES SHALL RECOGNIZE AND CONSIDER THE EFFECTS OF
THERMAL MOVEMENTS OF STRUCTURAL ELEMENTS DURING THE CONSTRUCTION PERIOD.
6) OSHA STANDARDS:
6A) NOTHING SHOWN ON THE STRUCTURAL DRAWINGS SHALL BE CONSTRUED AS ELIMINATING THE NEED FOR THE CONTRACTOR TO COMPLY WITH ALL OSHA REQUIREMENTS. WHERE THE STRUCTURAL DRAWINGS APPEAR TO CONFLICT WITH
OSHA REQUIREMENTS, THE STRUCTURAL DRAWINGS REPRESENT FINAL CONDITIONS ONLY.
GENERAL NOTES
1) CODES AND STANDARDS:
1A) GENERAL DESIGN
- INTERNATIONAL EXISTING BUILDING CODE 2024 WITH CITY AND COUNTY OF DENVER 2025 AMENDMENTS.
2) LATERAL LOAD RESISTING SYSTEM DESCRIPTION:
- THE WORK SHOWN ON THESE DRAWINGS DOES NOT INCREASE THE EXISTING LATERAL LOADS ACTING ON THE STRUCTURE
OR ALTER THE EXISTING LATERAL SYSTEM.
3) GRAVITY LOADS
- DEAD LOADS = CONCRETE SELF-WEIGHT
- GARAGE LIVE LOAD = 40 PSF
- GARAGE COMBINED ROOF SNOW AND LIVE LOAD = 90 PSF
DESIGN CRITERIA
1) GENERAL:
1A) EMPLOY A SPECIALTY ENGINEER TO DESIGN ALL SHORING AND BRACING NECESSARY TO COMPLETE THE REPAIR WORK.
DESIGN LOADS SHALL BE IN ACCORDANCE WITH THE DESIGN-BASIS CODE REQUIREMENTS, OR IF THE AREA IS BLOCKED
FROM PUBLIC ACCESS IT IS ACCEPTABLE TO USE ASCE 37-14 LOADS.
1B) PROVIDE BASE BEAMS, WOOD CRIBBING, OR BOTH AT LOWEST LEVEL AS NECESSARY TO LIMIT SERVICE LEVEL REACTION
TO 1500 PSF.
1C)LOCATE ALL EXISTING BURIED UTILITIES/DRAIN PIPING AND NOTIFY SPECIALTY ENGINEER IF LOCATIONS CONFLICT WITH
PROPOSED SHORING.
2) PRODUCTS:
2A) USE COMMERCIALLY MANUFACTURED AND PRE-ENGINEERED SHORING AND BRACING SYSTEMS AND COMPONENTS
WHENEVER POSSIBLE.
- COMMERCIALLY AVAILABLE REUSABLE SHORING EQUIPMENT SHALL INCLUDE A MINIMUM SAFETY FACTOR OF 2.5:1.
- DO NOT INSTALL STEEL SHORING PRODUCTS WITH EXCESSIVE CORROSION, BENT OR BROKEN FLANGES OR WEBS, DENTED TUBE WALLS, OR OTHER DETERIORATION WHICH MAY AFFECT MEMBER CAPACITY.
2B) DESIGN MEMBERS OF SHORING SYSTEMS THAT ARE NOT PRE-ENGINEERED IN ACCORDANCE WITH THE DESIGN-BASIS
CODE.
3) SUBMITTALS:
3A) SUBMIT SHORING LAYOUT SHOP DRAWINGS DEPICTING THE ARRANGEMENT OF EQUIPMENT FOR SHORING, INCLUSIVE OF INSTALLATION DETAILS, TIGHTENING PROCEDURE, AND MAINTENANCE REQUIREMENTS SEALED BY THE SPECIALTY
DESIGNER.
3B) SUBMIT DEFERRED SUBMITTAL STRUCTURAL CALCULATIONS SEALED BY THE SPECIALTY DESIGNER.
4) INSTALLATION REQUIREMENTS:
4A) THE TRIBUTARY AREA OF EACH SHORED STRUCTURAL MEMBER SHALL BE BLOCKED OFF AND CLEAR OF ALL VEHICLES
AND PUBLIC OR EMPLOYEE ACCESS.
4B) INSTALL SHORING AND BRACING IN ACCORDANCE WITH SEQUENCING DOCUMENTATION.
4C)SHORING SHALL EXTEND DOWN ALL LEVELS TO GRADE AT THE LOWEST LEVEL AND BE ALIGNED VERTICALLY BETWEEN
LEVELS.
4D)THE SPECIALTY ENGINEER WHO DESIGNED THE SHORING SHALL INSPECT THE INSTALLATION AND CERTIFY THAT THE
SHORING AND BRACING, AS INSTALLED, MEETS THE INTENT OF THEIR DESIGN.
5) SHORING REMOVAL:
5A) UNLESS OTHERWISE SPECIFIED, REMOVE SHORING AND BRACING ONLY AFTER ALL CONCRETE REPAIRS ACHIEVE SPECIFIED STRENGTH (5,000PSI MINIMUM), ENGINEER REVIEWS AND ACCEPTS TEST RESULTS.
SHORING NOTES
1) GENERAL:
1A) THE FOLLOWING PORTIONS OF THE STRUCTURAL DESIGN WILL NOT BE SUBMITTED AT THE TIME OF PERMIT APPLICATION.
WHEN RECEIVED AND REVIEWED, THESE DEFERRED SUBMITTAL ITEMS SHALL BE SUBMITTED TO THE BUILDING OFFICIAL BY
THE CONTRACTOR:
- SHORING DESIGN AND DETAILS FOR DOUBLE-TEES, BEAMS, SPANDREL, AND RAIL SUPPORT POSTS
1B) SUBMIT STAMPED STRUCTURAL CALCULATIONS BY A PROFESSIONAL ENGINEER LICENSED IN THE STATE OF COLORADO FOR ALL DEFERRED SUBMITTAL ITEMS PRIOR TO OR CONCURRENTLY WITH DRAWINGS OR PRODUCT DATA. INCLUDE ANALYSIS OF ATTACHMENT TO PRIMARY STRUCTURE. INCLUDE CURRENT ICC REPORT WITH ALL PROPRIETARY STRUCTURAL
ELEMENTS AND ANCHORS/FASTENERS.
DEFERRED SUBMITTALS
1) PERSONNEL REQUIREMENTS:
1A) THE CONTRACTOR SHALL ARRANGE AN ANCHOR MANUFACTURER’S REPRESENTATIVE TO PROVIDE ONSITE INSTALLATION TRAINING FOR ALL OF THEIR ANCHORING PRODUCTS SPECIFIED. SUBMIT DOCUMENTED CONFIRMATION THAT ALL OF THE CONTRACTOR’S PERSONNEL WHO INSTALL ANCHORS HAVE PASSED THE TRAINING COURSE PRIOR TO THE COMMENCEMENT
OF INSTALLING ANCHORS.
2) INSTALLATION REQUIREMENTS:
2A) ALL POST-INSTALLED ANCHORS SHALL BE INSTALLED ACCORDING TO MANUFACTURER'S PRINTED INSTALLATION
INSTRUCTIONS AND PER MANUFACTURER'S ON-SITE TRAINING.
2B) ALL ADHESIVE ANCHORS AND ADHESIVE ANCHORED REINFORCEMENT DESIGNS ARE FOR INSTALLATION IN THE FOLLOWING CONDITIONS, UNLESS NOTED OTHERWISE. WRITTEN APPROVAL MUST BE RECEIVED FROM ENGINEER PRIOR TO
INSTALLATION IN ALTERNATE CONDITIONS.
- DRY CONCRETE, UNLESS NOTED OTHERWISE.
- CONCRETE TEMPERATURE AT TIME OF INSTALLATION THROUGH CURE TIME MUST BE WITHIN THE TEMPERATURE RANGE SPECIFIED IN MANUFACTURER'S PRINTED INSTALLATION INSTRUCTION FOR ADHESIVE GEL AND CURE TIMES.
- ANCHOR HOLES TO BE HAMMER DRILLED AND CLEANED.
- CONCRETE MUST BE AT LEAST 21 DAYS OLD BEFORE INSTALLATION OF ANCHORS.
- HOLES TO BE CLEANED AND PREPARED IN STRICT ACCORDANCE WITH MANUFACTURER'S PRINTED INSTALLATION
INSTRUCTIONS AND EVALUATION REPORT PRIOR TO ADHESIVE INJECTION.
2C)THE POSITION OF EXISTING REINFORCING BARS IN THE CONCRETE STRUCTURE SHALL BE LOCATED PRIOR TO INSTALLING POST INSTALLED ANCHORS OR REINFORCEMENT. EXISTING REINFORCEMENT SHALL BE LOCATED USING A SCANNER, GPR, X-
RAY, CHIPPING OR OTHER MEANS.
3) ADHESIVE ANCHORS:
3A) ADHESIVE
- ADHESIVE (IN CONCRETE) #5 OR SMALLER: HILTI HIT-HY 200A (THREADED ROD) 200R V3 (REBAR)
- ADHESIVE (IN CONCRETE) #6 OR LARGER: HILTI HIT-RE 500 V3
3B) ANCHORS
- THREADED RODS: ASTM F1554 GR. 55 KSI
-----TIGHTEN NUT TO TORQUE SPECIFIED BY ADHESIVE MANUFACTURER
-----DAMAGE ANCHOR THREADS OR TACK WELD NUT TO ROD FOLLOWING NUT INSTALLATION
-----CUT ROD EXTENSION 1/2" FROM BOLT FACE FOR FINAL CONDITION, UNLESS NOTED OTHERWISE
- REBAR: ASTM A615, ASTM A706 (FIELD WELDED)
4) MECHANICAL ANCHORS:
4A) SCREW ANCHORS (IN CONCRETE)
- HILTI KWIK HUS-EZ
4B) GALVANIZED SCREW ANCHORS
- SIMPSON TITEN HD
- HILTI KH-EZ CRC
4C)EXPANSION ANCHORS (IN CONCRETE)
- HILTI KWIK BOLT TZ2
- SIMPSON STRONG BOLT
POST-INSTALLED ANCHOR NOTES
1) GENERAL:
1A) THE FOLLOWING PHASING NOTES ARE FOR PRICING AND A RESULT OF A VIRTUAL MEETING WITH AHEC ON JANUARY 22, 2026. ADDITIONAL COORDINATION WITH AHEC AND PARKING SERVICES WILL BE REQUIRED DURING CONSTRUCTION.
1B) THE UPPER LEVEL (LEVEL 4) AND RAMP FROM LEVEL 3 TO 4 CAN BE CLOSED ENTIRELY FOR THE DURATION OF THE
PROJECT.
1C) LEVELS 1 TO 3 CAN BE CLOSED 50% AT A TIME. NO MORE THAN TWO LEVELS CAN BE WORKED ON AT A TIME, WITH EXCEPTION OF RESHORING. CONTRACTOR TO PROVIDE SIGNAGE AND BARRIERS TO DIRECT TRAFFIC RE-ROUTES AND
TEMPORARY PARKING SPACE CLOSURES.
1D)PROVIDE PHASING PLAN WITH BID FOR OWNER AND ENGINEER REVIEW.
1E) PER AHEC, CONSTRUCTION CANNOT START EARLIER THAN MAY 18, 2026, AND CANNOT EXTEND PAST AUGUST 14, 2026.
PHASING NOTES
NO. ISSUE DATE
CONCRETE MIX TABLE ABBREVIATIONS:
- NWC = NORMAL WEIGHT CONCRETE
- SCM = SUPPLEMENTARY CEMENTITIOUS MATERIAL
- THK = 2 1/4" MINIMUM THICK PLACEMENT
CONCRETE MIX TABLE NOTES:
1) CONCRETE MIX DESIGNS ARE A PERFORMANCE SPECIFIED ITEM DESIGNED BY THE CONTRACTOR. THE CONTRACTOR SHALL PROVIDE A CONCRETE MIX MEETING THE PERFORMANCE REQUIREMENTS SPECIFIED IN THE "CONCRETE MIX TABLE" IN
ADDITION TO THE REQUIREMENTS BELOW
2) PROPORTIONS OF MATERIALS IN CONCRETE MIXES SHALL BE ESTABLISHED TO:
2A) PROVIDE THE MINIMUM COMPRESSIVE STRENGTH AS INDICATED IN THE MIX TABLE. DO NOT EXCEED THE MAXIMUM
WATER-CEMENT RATIO
2B) PROVIDE WORKABILITY AND CONSISTENCY FOR SLAB FINISHING AND TO PERMIT CONCRETE TO BE WORKED READILY INTO FORMS AND AROUND REINFORCEMENT UNDER CONDITIONS OF PLACEMENT TO BE EMPLOYED WITHOUT SEGREGATION OR EXCESSIVE BLEEDING. CONTRACTOR SHALL SELECT APPROPRIATE SLUMP. USE ADMIXTURES AS REQUIRED TO OBTAIN
DESIRED RESULTS
2C) FOR CONCRETE PLACED BY PUMPING, PROVIDE CONCRETE MIX FLOWABILITY TO FACILITATE PUMPING. ENTRAINED AIR
MAY BE USED TO FACILITATE PUMPING SUBJECT TO THE PROVISIONS OF NOTE 4 BELOW
3) FOR THE MAXIMUM COARSE AGGREGATE SIZE INDICATED, USE THE FOLLOWING AGGREGATE SIZE NUMBERS PER ASTM C33:
- 3/4": #67 AGGREGATE
4) WHERE AIR CONTENT IS INDICATED IN THE MIX TABLE, PROVIDE AIR ENTRAINING ADMIXTURE TO MEET THE SPECIFIED AIR PERCENTAGE. TOTAL AIR CONTENT LIMITS INCLUDE BOTH ENTRAINED AND ENTRAPPED AIR ±1 1/2%. AIR CONTENT NOTED IS
BASED ON 3/4" AGGREGATE.
5) THE MAXIMUM PERCENTAGE OF CEMENTITIOUS MATERIAL WHICH IS CLASSIFIED AS SCM (INCLUDING FLY ASH, NATURAL POZZOLANS, SILICA FUME, AND SLAG CEMENT) SHALL BE AS FOLLOWS. THE INDIVIDUAL LIMITS SHOWN BELOW SHALL APPLY
REGARDLESS OF THE NUMBER OF CEMENTITIOUS MATERIALS IN THE CONCRETE MIXTURE.
- FLY ASH OR NATURAL POZZOLANS CONFORMING TO ASTM C618 = 25%
- SLAG CEMENT CONFORMING TO ASTM C989 = 50%
- SILICA FUME CONFORMING TO ASTM C1240 = 10%
- TOTAL OF FLY ASH OR OTHER POZZOLANS AND SILICA FUME = 35%
- TOTAL OF FLY ASH OR OTHER POZZOLANS, SLAG CEMENT, AND SILICA FUME = 50%
6) EVIDENCE SHALL BE SUBMITTED THAT THE CONCRETE MIXTURE COMPLIES WITH THE FOLLOWING:
6A) AGGREGATES ARE NOT ALKALI-SILICA REACTIVE OR MEASURES TO MITIGATE ALKALI-SILICA REACTIVITY HAVE BEEN
ESTABLISHED
6B) AGGREGATES ARE NOT ALKALI-CARBONATE REACTIVE
7) MAXIMUM CHLORIDE ION LIMITS (PERCENTAGE BY MASS OF CEMENTITIOUS MATERIALS INCLUDING SCM) = 0.15
M a rt in
/M ar ti n
, I n c . c o n s id e rs t h at d es ig n d a ta is o n ly i n i ts f in a l f o rm o n p lo tt e d d ra w in g s w it h o ri g in a l s ig n a tu re s a n d p ro fe s s io n a l c er ti fi ca ti o n b ei n g v is ib ly p re s en t o n t h e d ra w in g s . D a ta s u p p lie d v ia c o m p u te r g en e ra te d f o rm a t d o es n o t c o n ta in t h is a p p ro v al o r ce rt if ic a ti o n
T h e r ec ei v er o f el e ct ro n ic a ll y tr a n s m it te d d ra w in g s is r e s p o n s ib le f o r v er if yi n g t h e in fo rm a ti o n c o n ta in e d w it h in t h e e le c tr o n ic d a ta a g a in s t th e r ec o rd e d o r ap p ro v ed d o cu m en ts
T h e u se o f el e ct ro n ic a lly t ra ns m itt e d d ra w in g s is c on si d e re d to b e a t yo u r o w n r is k.
M a rt in
/M a rt in
In c.
a ss u m e s n o re sp on si b ili ty f o r a ny c la im s o r da m a ge s re su lti ng f ro m y o u r us e o f t h is in fo rm a tio n.
E le ct ro ni c in fo rm a tio n is p ro vi d ed fo r th e co nv en ie nc e o f th e r e ci p ie nt o nl y.
T h e r ec ip ie n t of t hi s fil e a gr ee s th a t th e in fo rm a tio n m ay n ot b e tr a ns fe rr ed t o a ny o th e r p ar ty
PROJECT NO:
DATE:
REVISIONS
SHEET TITLE:
SHEET NUMBER:
M M
J O
B
P
R
IN
C
IP
A L:
E O
R
P R
O
JE
C T
M A
N A
G E
R
D E
S
IG
N E
R S
LE
A D
R E
V
IT
T E
C H
D
A T
E P
R
IN
T E
D
F
IL
E P
A T
H
4/
/2
4:
:1
P
M A ut od es k
D oc s:
//A
C C
-M M
S
/2 4.
.S .0
3-
La w re nc e
W ay
H ig h P rio rit y- S
.rv t
H
IG
H P
R
IO
R
IT
Y S
T R
U C
T U
R A
L R
E P
A
IR
S A
N D
W A
T E
R P
R O
O F
IN
G
A U
R A
R
IA
C A
M P
U S
7t h
S T
R E
E T
P A
R K
IN
G
G A
R A
G E
LA
W
R E
N C
E W
A Y
D E
N V
E R
, C O
LO
R
A D
O
04/08/2026
S0.2
GENERAL NOTES
© MARTIN/MARTIN 2026
A R
T G
A R
C
IA
B E
N E
S T
R
IC
H
T A
M I
W O
R K
E R
.0
5.
S .0
T A
M I
W O
R K
E R
J.
W
IL
LI
A M
S
24.0355.S.03
CONCRETE REPAIR NOTES
BAR LOCK COUPLER
TYPE 2/CLASS L
PER ACI 318
WELDED A706 60 80 1030 -
TYP REINFORCING A615 60 90 1030 -
REINF ELEMENT ASTM Fy (KSI) Fu (KSI) GWP LIMITS (kg CO2e / METRIC
TON) - NOTE 1
COMMENTS
REINFORCING MATERIAL TABLE
#11 25 39 26 43 75 58 47 97 75 61 126 97 80
#10 21 33 23 39 63 49 39 82 63 51 107 82 66
#9 18 28 21 34 52 40 32 68 52 42 88 67 54
#8 15 24 18 30 43 32 26 56 42 34 72 54 44
#7 12 19 16 27 34 26 23 45 33 29 58 43 38
#6 10 15 14 23 21 16 28 20 36 26
#5 8 12 12 19 16 13 20 17 26 22
#4 6 9 9 15 12 14 18
#3 6 6 8 12 12 12 13
BAR SIZE LDH
SPACING
s≥ 6db s< 6db LCE LCS LTE
LTE TOP
& LTS
LTS TOP
CLEAR COVER 1" 1.5" 2"+ 1" 1.5" 2"+ 1" 1.5" 2"+
LAP SPLICE & DEVELOPMENT LENGTHS (INCHES)
F'c=5,000 PSI, Fy=60,000 PSI
1) GENERAL:
1A) ALL WORK SHALL CONFORM WITH ACI 563-18 (SPECIFICATION FOR REPAIR OF CONCRETE IN BUILDINGS) REFERENCE THE
SPECIFICATION FOR DETAILED REQUIREMENTS.
1B) CONSTRUCTION TOLERANCES FOR REPAIR WORK SHALL CONFORM TO ACI 117.
1C)HOT AND COLD WEATHER CONCRETE WORK SHALL CONFORM TO THE REQUIREMENTS OF ACI 305R AND ACI 306R, RESPECTIVELY.
1D)PROTECT THE STRUCTURE AND ADJACENT CONSTRUCTION FROM RISKS ASSOCIATED WITH WORK, INCLUDING IMPACT, MARRING OF SURFACES, STAINING, AND OTHER TYPES OF DAMAGE.
1E) DURING CURING PERIOD, PROTECT REPAIR MATERIALS FROM DAMAGE BY MECHANICAL DISTURBANCES, INCLUDING LOAD- INDUCED STRESSES, SHOCK, VIBRATION, AND FROM TEMPERATURE, HUMIDITY, SUNLIGHT, WIND, PRECIPITATION, WATER, AND DELETERIOUS MATERIALS.
1F) PROVIDE TEMPORARY COVER OVER OPENINGS WHEN NOT IN USE.
2) SPALLED/DELAMINATED CONCRETE REMOVAL:
2A) WITHIN THE WORK AREA, PERFORM VISUAL INSPECTION AND HAMMER SOUNDING, CHAIN DRAG SOUNDING, OR OTHER METHODS ACCEPTABLE TO THE ENGINEER TO IDENTIFY CRACKED, DELAMINATED, SPALLED, DISINTEGRATED, AND
OTHERWISE UNSOUND CONCRETE FOR REMOVAL.
- CONFIGURE GEOMETRY OF REMOVAL AREA TO MAXIMIZE THE USE OF RIGHT-ANGLE GEOMETRY, AVOIDING REENTRANT
CORNERS, AND TO OBTAIN UNIFORMITY OF DEPTH.
- REMOVAL OF SOME SOUND CONCRETE MAY BE NECESSARY TO ACHIEVE THE REQUIRED REPAIR AREA GEOMETRY.
2B) LOCATE AND VERIFY DEPTH OF ALL EXISTING REINFORCING BARS, PRE-STRESSING TENDONS, CONDUIT, ETC. PRIOR TO CONCRETE REMOVAL IN AREA TO BE REPAIRED USING GROUND PENETRATING RADAR SCANNING, PACHOMETER, OR OTHER
NON-DESTRUCTIVE MEANS ACCEPTABLE TO ENGINEER.
2C)PERFORM CONCRETE REMOVAL WITH SMALL CONCRETE CHIPPING HAMMERS TO MINIMIZE DAMAGE TO CONCRETE SUBSTRATE, ADJOINING CONSTRUCTION, AND TO PREVENT BRUISING OF OTHERWISE SOUND CONCRETE SURFACES.
- CONCRETE CHIPPING HAMMERS SHALL BE LIMITED TO 15 POUND ELECTRIC STYLE HANDHELD HAMMERS. PROVIDE SHARP
TIPS ON EQUIPMENT TO MINIMIZE BRUISED SURFACES IN PARTIAL DEPTH REMOVAL.
- AVOID DIRECTLY STRIKING REINFORCEMENT AND OTHER EMBEDDED ITEMS WITH IMPACT TOOLS USED FOR CONCRETE
REMOVAL, CAREFULLY HAND CHIP AROUND SUCH ITEMS.
- DO NOT CUT OR DAMAGE EXISTING EMBEDDED REINFORCEMENT OR OTHER EMBEDDED ITEMS.
2D)EXTEND CONCRETE REMOVAL ALONG THE REINFORCEMENT TO WHERE THERE IS NO FURTHER CONCRETE DELAMINATION, CONCRETE CRACKING, OR BOND INHIBITING REINFORCEMENT CORROSION, AND WHERE THE
REINFORCEMENT IS BONDED TO THE SURROUNDING CONCRETE.
3) EXISTING CONCRETE SUBSTRATE PREPARATION:
3A) ALL REINFORCING BARS WHICH HAVE MORE THAN 1/2 OF THEIR DIAMETER EXPOSED OR WHICH ARE CORRODED SHALL BE
UNDERCUT BY 3/4 INCH MINIMUM.
- UNLESS NOTED OTHERWISE IN DETAILS DO NOT REMOVE CONCRETE BEHIND VERTICAL REINFORCING BARS IN COLUMNS, WALLS, OR OTHER VERTICAL LOAD BEARING MEMBERS
3B) CHIP OUT ENTIRE REPAIR AREA TO REMOVE ALL UNSOUND CONCRETE. REPAIR AREA SHALL NOT BE LESS THAN 1/2” IN
DEPTH.
3C)CONCRETE REPAIR AREAS SHOULD BE SQUARE OR RECTANGULAR IN SHAPE WITH A 1/2 INCH SAW CUT AT THE
PERIMETER. DO NOT CUT OR DAMAGE EMBEDDED REINFORCING OR OTHER EMBEDDED ITEMS.
3D)DO NOT TERMINATE CEMENTITIOUS REPAIR MORTAR AT A FEATHER EDGE. ADHERE TO REPAIR MORTAR PRODUCT
MANUFACTURER’S MINIMUM AND MAXIMUM MATERIAL THICKNESS REQUIREMENTS.
3E) PREPARE CONCRETE SURFACES TO RECEIVE REPAIR MORTAR WITH MECHANICAL MEANS TO OBTAIN AN EXPOSED AGGREGATE SURFACE WITH A MINIMUM SURFACE PROFILE OF ± 1/4 INCH (ICRI DEGREE OF ROUGHNESS = CSP-9 MINIMUM).
4) EXISTING STEEL REINFORCING PREPARATION:
4A) CLEAN ALL EXPOSED REINFORCING STEEL IN REPAIR AREA TO REMOVE ALL TRACES OF CORROSION BY MEDIA BLASTING OR OTHER APPROVED MEANS. IF MEDIA BLASTING IS USED, CLEAN SHOT MEDIA FROM REPAIR AREA. PREPARE EXISTING STEEL SURFACES TO MEET OR EXCEED THE REQUIREMENTS OF ICRI GUIDELINE 210.5R-23 LEVEL 2 CLEAN.
- THIS ALSO APPLIES TO STEEL PLATES, STEEL CONDUITS, OR ANY OTHER METAL ITEMS WHICH WILL BE ENCAPSULATED IN
THE REPAIR AREA.
4B) IF OVER 10% OF REINFORCING BAR CROSS-SECTIONAL AREA IS LOST DUE TO DAMAGE OR CORROSION AT ANY LOCATION, CONTACT ENGINEER FOR REVIEW AND SUPPLEMENTAL REINFORCING REQUIREMENTS.
4C)COAT ALL EXISTING EXPOSED REINFORCING STEEL WITH CORROSION RESISTANT STEEL PRIMER. FOLLOW PRIMER PRODUCT MANUFACTURER’S REQUIREMENTS FOR APPLICATION TIMING, APPLICATION RATE, AND RECOMMENDED NUMBER
OF COATS.
4D)WHERE EXISTING CONDITIONS DO NOT PERMIT COMPLIANCE WITH CONCRETE COVER LIMITS, NOTIFY ENGINEER FOR
SUPPLEMENTAL INSTRUCTIONS.
5) ACCEPTABLE REPAIR PRODUCTS:
5A) HORIZONTAL SURFACE PARTIAL DEPTH CONCRETE REPAIR MORTAR
- SIKAEMACO T 1060/1061 BY SIKA CORPORATION
- PLANITOP 18TG/18ES BY MAPEI CORPORATION
- VERSASPEED 100/LS100 BY EUCLID CHEMICAL COMPANY
- HP CONCRETE (EXTENDED) OR HP DOT MORTAR (NEAT) BY US CONCRETE PRODUCTS
5B) TROWEL APPLIED VERTICAL AND OVERHEAD PARTIAL DEPTH CONCRETE REPAIR MORTAR (2" MAX THICKNESS)
- SIKAEMACO N 425 CI BY SIKA CORPORATION
- PLANITOP X/XS BY MAPEI CORPORATION
- EUCOREPAIR V100 BY EUCLID CHEMICAL COMPANY
- US THIN PATCH V/O BY US CONCRETE PRODUCTS
5C)FORM AND POUR VERTICAL AND OVERHEAD PARTIAL DEPTH CONCRETE REPAIR MORTAR
- SIKAEMACO S 466 CI BY SIKA CORPORATION
- PLANITOP FD/15 BY MAPEI CORPORATION
- EUCOCRETE BY EUCLID CHEMICAL COMPANY
- DECK MIX FP BY US CONCRETE PRODUCTS
5D)FORM AND POUR FULL DEPTH CONCRETE REPAIR MORTAR
- SIKACRETE 211 SCC PLUS BY SIKA CORPORATION
- PLANITOP 11 SCC BY MAPEI CORPORATION
- EUCOREPAIR SCC BY EUCLID CHEMICAL COMPANY
- DECK MIX SCC OR AE BY US CONCRETE PRODUCTS
5E) FORM AND PUMP AT PRESSURE VERTICAL AND OVERHEAD CONCRETE REPAIR MORTAR
- SIKACRETE 211 SCC PLUS BY SIKA CORPORATION
- PLANITOP 11 SCC BY MAPEI CORPORATION
- EUCOREPAIR SCC BY EUCLID CHEMICAL COMPANY
5F) EMBEDDED REINFORCING STEEL PRIMER
- ARMATEC 110 EPOCEM BY SIKA CORPORATION
- PLANIBOND 3C BY MAPEI CORPORATION
- DURALPREP A.C. BY EUCLID CHEMICAL COMPANY
- HP BONDIT III BY US CONCRETE PRODUCTS
5G)SUBSTITUTIONS:
- ALL SUBSTITUTIONS MUST BE SUBMITTED AND APPROVED BY THE ENGINEER IN WRITING PRIOR TO USE. ALTERNATE PRODUCTS MUST HAVE SIMILAR PERFORMANCE CRITERIA TO THE BASIS OF DESIGN PRODUCTS LISTED.
5H)DELIVER PACKAGED MATERIALS CLEARLY MARKED WITH LEGIBLE AND INTACT LABELS WITH MANUFACTURER’S NAME, BRAND NAME, LOT NUMBER, AND IDENTIFYING CONTENTS OF CONTAINERS.
- THE REPAIR MORTAR SHALL BE SUPPLIED IN A FACTORY PROPORTIONED UNIT.
- IF EXTENSION OF THE MORTAR WITH ADDED AGGREGATE WILL BE USED, PROVIDE FACTORY PROPORTIONED UNITS BY THE SAME MANUFACTURER. UNLESS OTHERWISE REQUIRED BY THE MANUFACTURER, AGGREGATE SHOULD BE 3/8” CLEAN, WELL- GRADED, SATURATED SURFACE DRY MATERIAL, HAVING LOW ABSORPTION AND HIGH DENSITY. AGGREGATE SHALL CONFORM
TO ASTM C33.
5I) WEIGH CEMENTITIOUS PACKAGED REPAIR MATERIALS. THE CONTENTS OF ANY PACKAGED CONTAINER SHOULD NOT VARY BY MORE THAN 2% FROM THE WEIGHT STATED ON THE PACKAGE MARKINGS. IF THE WEIGHT IS OUTSIDE THE 2 PERCENT
TOLERANCE, CONTACT THE REPAIR MATERIAL MANUFACTURER FOR RECOMMENDATIONS.
5J) STORE MATERIALS IN AREAS WHERE CONDITIONS CONFORM WITH REPAIR MATERIAL MANUFACTURER’S RECOMMENDATIONS AND INSTRUCTIONS. MATERIALS SHALL BE SUPPLIED AND APPLIED WITHIN THEIR STATED SHELF LIFE OR BY THEIR EFFECTIVE “USE BY” DATE. PROTECT REPAIR MATERIAL COMPONENTS FROM FREEZING AND FROM TEMPERATURE
CHANGES THAT WOULD ADVERSELY AFFECT THEIR PERFORMANCE AND PROPERTIES.
5K) THE MATERIAL SHALL NOT CONTAIN ASBESTOS, NITRATES, ADDED GYPSUM, ADDED LIME, OR HIGH ALUMINUM CEMENT.
REPAIR MATERIAL SHALL NOT CONTAIN SOLUBLE CHLORIDES OR OTHER INGREDIENTS IN SUFFICIENT QUANTITY TO CAUSE
CORROSION OF EMBEDDED REINFORCING STEEL. MATERIALS SHALL BE NON-COMBUSTIBLE.
5L) COLOR TO BE PRODUCT STANDARD AND CLOSELY MATCH EXISTING CONCRETE SURFACE COLOR UNLESS DIRECTED
OTHERWISE BY ENGINEER.
6) FORMWORK:
6A) FORM-FACING MATERIAL IN CONTACT WITH REPAIR MATERIAL SHALL BE LUMBER, PLYWOOD, TEMPERED CONCRETE-FORM- GRADE HARDBOARD, METAL, PLASTIC, OR PAPER THAT MATCHES THE APPEARANCE AND TEXTURE OF ADJACENT EXISTING
SURFACES.
6B) ANCHOR BOLTS USED TO SECURE FORM WORK SHALL BE ABLE TO BE REMOVED WITHOUT SPALLING CONCRETE.
6C)DESIGN FORM WORK TO WITHSTAND REPAIR MATERIAL PRESSURES, AS WELL AS PRESSURE RESULTING FROM
PLACEMENT.
6D)PROVIDE FORM WORK SURFACES WHICH DO NOT BOND TO REPAIR MATERIAL. USE OF OSB FOR FORM FACING MATERIAL IS NOT ALLOWED. IF RELEASE AGENT IS USED, DO NOT ALLOW FORM WORK RELEASE AGENT TO PUDDLE IN FORMS, CONTACT REINFORCEMENT, OR CONTACT HARDENED CONCRETE. RELEASE AGENT SHALL BE NON-STAINING.
7) CONDITIONING, MIXING, AND PLACEMENT:
7A) ADHERE TO ALL LIMITATIONS AND CAUTIONS AND FOLLOW ALL RECOMMENDATIONS FOR “BEST PERFORMANCE” IN THE
MANUFACTURER’S PRINTED INSTALLATION INSTRUCTIONS.
7B) REMOVE ALL LAITANCE, DEBRIS, ABRASIVE BLAST MEDIA, AND BOND-INHIBITING MATERIALS FROM THE REPAIR AREA.
7C)MIXING AND PLACEMENT REQUIREMENTS ARE CONTINGENT ON PLACEMENT METHOD AND SELECTED REPAIR MORTAR PRODUCT. MIX AND PLACE MATERIALS IN STRICT ACCORDANCE WITH MANUFACTURER’S PRINTED INSTALLATION INSTRUCTIONS. IN THE ABSENCE OF PRINTED INSTALLATION INSTRUCTIONS, CONTACT THE ENGINEER FOR ADDITIONAL
DIRECTION PRIOR TO APPLICATION.
7D)ADHERE TO ALL MANUFACTURER TIME-FRAME/POT-LIFE REQUIREMENTS.
7E) CONDITION REPAIR AREA SUBSTRATE TO SATURATED SURFACE DRY (SSD) CONDITION.
7F) PLACE AND CONSOLIDATE MATERIAL WITH MEANS ACCEPTABLE TO THE MANUFACTURER TO PROVIDE A WELL-COMPACTED REPAIR, CONSOLIDATED AROUND REINFORCEMENT, AND WITHOUT SEGREGATION. DO NOT VIBRATE SELF-CONSOLIDATING
(SCC) REPAIR MORTAR.
7G)FINISHING:
- FLOAT THEN BROOM, SWIRL, OR TROWEL FINISH REPAIRS TO MATCH EXISTING SURROUNDING CONCRETE SURFACES.
- MAINTAIN ALL EXISTING JOINTS BY TOOLING OR FORMING JOINTS IN UNCURED REPAIR MATERIAL. SAW CUTTING JOINTS IN CURED REPAIR MATERIAL IS NOT AN ACCEPTABLE METHOD UNLESS PERFORMED WITH EARLY ENTRY SAW EQUIPMENT PRIOR
TO CONCRETE CURE.
- MAINTAIN ALL EXISTING CHAMFERED EDGES TO MATCH ADJACENT CONSTRUCTION.
7H)CURING:
- WET CURE CEMENTITIOUS REPAIR MATERIALS WITH ABSORBENT COVERING (BURLAP) AND WATER-RETENTION SHEETING.
TAPE SHEETING TOGETHER OR LAP SHEETS, REPAIR HOLES AND GAPS, AND KEEP SHEETS IN PLACE. CONTINUE CURING
MEASURES FOR AT LEAST 7 DAYS AFTER PLACEMENT.
8) FINAL CONDITIONS:
8A) REMOVE ALL FORM WORK AND ATTACHMENT HARDWARE FROM REPAIR AREA.
- REMOVE FORMWORK ONLY AFTER REPAIR MATERIAL CURE IS COMPLETE AND CONCRETE HAS REACHED A MINIMUM
STRENGTH OF 5,000 PSI
8B) REFER TO SHORING DESIGN FOR SHORING REMOVAL REQUIREMENTS AND LIMITATIONS.
8C)LEAVE FINISHED WORK AND WORK AREA IN A NEAT, CLEAN CONDITION WITHOUT EVIDENCE OF SPILLOVERS ONTO ADJACENT AREAS. SPILLOVERS SHOULD BE REMOVED BY GRINDING AND CHAMFERING AT EDGES OF REPAIR AND HOLES FROM
ATTACHMENT HARDWARE FILLED WITH AN APPROVED EPOXY OR CONCRETE REPAIR PRODUCT.
8D)PROVIDE RECORD SET COPY OF FINAL REPAIR AREAS WITH QUANTITIES TO ENGINEER.
9) QUALITY ASSURANCE QUALITY CONTROL:
9A) OBTAIN AND COORDINATE SERVICES OF A FIELD TECHNICIAN QUALIFIED BY THE MANUFACTURER AT THE PROJECT SITE BEFORE MIXING OR INSTALLING PROPRIETARY MATERIALS OR COMPONENTS TO TRAIN PERSONNEL IN PREPARATION, INSTALLATION, AND QUALITY CONTROL PROCEDURES.
9B) COMPLETED AND CURED CONCRETE REPAIR AREAS SHOULD BE HAMMER-SOUNDED. REPLACE DELAMINATED OR POORLY
CONSOLIDATED REPAIR AREAS IDENTIFIED DURING SOUNDING AT NO COST TO THE OWNER.
CONCRETE MIX TABLE
CONC
MIX
TYPE INTENDED USE
COMPRESSIVE
STRENGTH f'c
(KSI)
TEST AVG
(DAYS)
CONC
WEIGHT
MAX W/C
RATIO,
INCLUDING
SCM, NOTE 6
MAX
AGGREGATE
SIZE (IN),
NOTE 3
TOTAL AIR
CONTENT
(%), NOTE 4 OTHER REQTS
1 STAIR LANDING
INFILL AND
HORIZONTAL
REPAIRS
5 28 NWC 0.40 3/4 6 THK
NO. ISSUE DATE
JOISTS 1 1/2
COLUMNS, GIRDERS, AND BEAMS 1 1/2
TOP SURFACE OF SLABS EXPOSED TO WEATHER 2
CONCRETE PLACED IN FORMS, EXPOSED TO WEATHER OR EARTH 2
CASE COVER (IN)
REBAR COVER TABLE
NOTES:
1. GLOBAL WARMING POTENTIAL LIMITS ARE BASED ON THE FOLLOWING CRITERIA:
- VALUES HAVE BEEN SET BASED ON THE REQUIREMENTS OF BUY CLEAN COLORADO (C.R.S 24-92117)
- VALUES REPRESENT FABRICATED MATERIAL SCOPE, AS DEFINED BY BUY CLEAN COLORADO'S GLOBAL WARMING
POTENTIAL LIMITS GUIDANCE
a rt in
/M ar ti n
, I n c . c o n s id e rs t h at d es ig n d a ta is o n ly i n i ts f in a l f o rm o n p lo tt e d d ra w in g s w it h o ri g in a l s ig n a tu re s a n d p ro fe s s io n a l c er ti fi ca ti o n b ei n g v is ib ly p re s en t o n t h e d ra w in g s . D a ta s u p p lie d v ia c o m p u te r g en e ra te d f o rm a t d o es n o t c o n ta in t h is a p p ro v al o r ce rt if ic a ti o n
T h e r ec ei v er o f el e ct ro n ic a ll y tr a n s m it te d d ra w in g s is r e s p o n s ib le f o r v er if yi n g t h e in fo rm a ti o n c o n ta in e d w it h in t h e e le c tr o n ic d a ta a g a in s t th e r ec o rd e d o r ap p ro v ed d o cu m en ts
T h e u se o f el e ct ro n ic a lly t ra ns m itt e d d ra w in g s is c on si d e re d to b e a t yo u r o w n r is k.
M a rt in
/M a rt in
In c.
a ss u m e s n o re sp on si b ili ty f o r a ny c la im s o r da m a ge s re su lti ng f ro m y o u r us e o f t h is in fo rm a tio n.
E le ct ro ni c in fo rm a tio n is p ro vi d ed fo r th e co nv en ie nc e o f th e r e ci p ie nt o nl y.
T h e r ec ip ie n t of t hi s fil e a gr ee s th a t th e in fo rm a tio n m ay n ot b e tr a ns fe rr ed t o a ny o th e r p ar ty
PROJECT NO:
DATE:
REVISIONS
SHEET TITLE:
SHEET NUMBER:
M M
J O
B
P
R
IN
C
IP
A L:
E O
R
P R
O
JE
C T
M A
N A
G E
R
D E
S
IG
N E
R S
LE
A D
R E
V
IT
T E
C H
D
A T
E P
R
IN
T E
D
F
IL
E P
A T
H
4/
/2
4:
:1
P
M A ut od es k
D oc s:
//A
C C
-M M
S
/2 4.
.S .0
3-
La w re nc e
W ay
H ig h P rio rit y- S
.rv t
H
IG
H P
R
IO
R
IT
Y S
T R
U C
T U
R A
L R
E P
A
IR
S A
N D
W A
T E
R P
R O
O F
IN
G
A U
R A
R
IA
C A
M P
U S
7t h
S T
R E
E T
P A
R K
IN
G
G A
R A
G E
LA
W
R E
N C
E W
A Y
D E
N V
E R
, C O
LO
R
A D
O
04/08/2026
S0.3
QUALITY
ASSURANCE
© MARTIN/MARTIN 2026
A R
T G
A R
C
IA
B E
N E
S T
R
IC
H
T A
M I
W O
R K
E R
.0
5.
S .0
T A
M I
W O
R K
E R
J.
W
IL
LI
A M
S
24.0355.S.03
1. GENERAL:
A. SCOPE OF WORK
• THE OWNER WILL ENGAGE A QUALIFIED INSPECTION AND TESTING AGENCY(S) TO
PERFORM INSPECTIONS AND TESTING FOR ALL STRUCTURAL MEMBERS AND
ASSEMBLIES AS NOTED HEREIN.
B. INSPECTIONS AND TESTING ARE APPLICABLE TO ALL REVISIONS AND/OR FUTURE WORK
ADDED BY AMENDMENTS TO THESE DOCUMENTS.
C. DEFINITIONS
• INSPECTOR: THE AGENCY ENGAGED BY THE OWNER TO PERFORM INSPECTIONS.
• (P) PERIODIC INSPECTION: THE PART-TIME OR INTERMITTENT OBSERVATION BY THE
INSPECTOR OF WORK BEING PERFORMED. INSPECTOR SHALL BE PRESENT IN THE
AREA WHERE THE WORK IS BEING PERFORMED. OBSERVATION OF ALL WORK (100%
VISUAL) SHALL BE MADE AT THE COMPLETION OF THE WORK.
• (C) CONTINUOUS INSPECTION: THE FULL-TIME OBSERVATION BY THE INSPECTOR OF
WORK BEING PERFORMED. INSPECTOR SHALL BE PRESENT IN THE AREA WHERE
THE WORK IS BEING PERFORMED. OBSERVATION OF ALL WORK (100% VISUAL) SHALL
BE MADE AT THE COMPLETION OF THE WORK.
D. DEFICIENCIES IN WORK
• CORRECT DEFICIENCIES IN WORK THAT TESTS AND INSPECTIONS INDICATE DO NOT
COMPLY WITH THE CONTRACT DOCUMENTS AND REFERENCED STANDARDS.
• ALL COST OF ADDITIONAL TESTING AND/OR INSPECTIONS FOR CORRECTIVE WORK
SHALL BE BORNE BY THE CONTRACTOR.
2. CONCRETE REPAIR
A. GENERAL
• PERFORM INSPECTIONS AND TESTING FOR ALL CONCRETE REPAIR AREAS AS NOTED
HEREIN.
• SEE ACI 563-18 SPECIFICATION FOR REPAIR OF CONCRETE IN BUILDINGS FOR
DETAILED REQUIREMENTS.
• REPAIR INSPECTOR QUALIFICATIONS FOR INSPECTION OF CONCRETE REPAIRS
SHOULD BE DEMONSTRATED BY CERTIFICATION OR PREVIOUS WORK HISTORY AND
AS REQUIRED BY THE AUTHORITY HAVING JURISDICTION BEFORE BEING RETAINED.
AN INDIVIDUAL WHO HAS BEEN CERTIFIED AS AN ICRI CONCRETE SURFACE REPAIR
TECHNICIAN (ICRI CSRT) OR AS AN ACI CONSTRUCTION INSPECTOR (ACI C630) ARE
EXAMPLES OF QUALIFIED INSPECTORS.
• CONCRETE REPAIR MATERIALS TESTING PERSONNEL SHOULD BE QUALIFIED BY
DEMONSTRATING COMPETENCE TO THE SATISFACTION OF THE LICENSED DESIGN
PROFESSIONAL AND BUILDING CODE OFFICIAL FOR TESTING TYPES REQUIRED OF
CONCRETE REPAIR AND REHABILITATION WORK. AS A MINIMUM LEVEL OF RECORD
KEEPING, THE TESTING AGENCY SHOULD MAINTAIN A RECORD OF THE TESTS
PERFORMED AND THE RESULTS CONSISTENT WITH THE REQUIREMENTS FOR
RECORDS IN ASTM E329.
• FAILURE TO DETECT DEFECTIVE WORK OR MATERIAL WILL NOT PREVENT REJECTION
IF A DEFECT IS DISCOVERED LATER NOR SHALL IT OBLIGATE ARCHITECT/ENGINEER
FOR FINAL ACCEPTANCE.
- PRECONDITIONING OF
MATERIALS, MIXING,
PLACEMENT,
FINISHING, AND
CURING OF REPAIR
MATERIALS
P
ACI 563-18
SECTION 8
VERIFY THAT PRECONDITIONING, MIXING,
PLACING, FINISHING, AND CURING OF
PRE-PACKAGED REPAIR MORTAR IS
PERFORMED IN ACCORDANCE WITH
REPAIR MORTAR MANUFACTURER'S
REQUIREMENTS
- SUPPLEMENTAL
MATERIALS BATCHED
WITH PRE-PACKAGED
REPAIR MORTAR P
ACI 563-18
SECTION 8
VERIFY THAT SUPPLEMENTAL MATERIALS
(3/8" AGGREGATES, FIBERS, OTHER ADD
MIXTURES, ETC) WHICH WILL BE COMBINED
WITH PRE-PACKAGED REPAIR MORTAR ARE
CONDITIONED AND BATCHED IN
ACCORDANCE WITH REPAIR MORTAR
MANUFACTURER'S REQUIREMENTS
- DELIVERY AND
STORAGE
P
ACI 563-18
SECTION 8
VERIFY APPROVED PRODUCTS ARE
DELIVERED AND STORED IN ACCORDANCE
WITH REPAIR MORTAR MANUFACTURER'S
REQUIREMENTS
PREPACKAGED REPAIR MORTAR
- REMOVAL OF
FORMWORK
P
ACI 563-18
SECTION 4
VERIFY THAT FORMWORK INCLUDING
NECESSARY RE-SHORES TO SUPPORT,
CONFINE, AND SHAPE REPAIR MATERIALS
TO REQUIRED DIMENSIONS ARE NOT
REMOVED UNTIL REPAIR MATERIALS ARE
FULLY CURED
- SURFACE
CONDITIONING PRIOR
TO REPAIR MATERIAL
PLACEMENT
P
ACI 563-18
SECTION 3
VERIFY THAT SURFACE IS CLEAN AND
SOUND AND VERIFY THAT SUBSTRATE
CONDITIONING WAS APPLIED WITHIN
SPECIFIED TIME PRIOR TO REPAIR
MATERIAL PLACEMENT
- CONCRETE REMOVAL
AND SURFACE
PREPARATION
CONCRETE REMOVAL
AND SURFACE
PREPARATION
P
ACI 563-18
SECTION 3
VERIFY CONCRETE REMOVAL FROM
REPAIR AREAS IS PERFORMED TO
INDICATED REPAIR AREA SHAPE, DEPTH,
AND THAT SURFACE PROFILE IS ACHIEVED
WITHOUT DAMAGE/MICROBRUISING OF
SOUND SUBSTRATE
- PLACEMENT OF
BRACING AND
SHORING P
ACI 563-18
SECTION 2
VERIFY PLACEMENT OF BRACING AND
SHORING TO SUPPORT THE
DETERIORATED STRUCTURE BEFORE,
DURING, AND AFTER THE WORK UNTIL THE
STRUCTURE IS SELF-SUPPORTING
DETERIORATED CONCRETE REMOVAL AND SURFACE PREPARATION
- DURING PLACEMENT
P
ACI 563-18
SECTION 5
VERIFY THAT EXISTING REINFORCEMENT IS
PREPARED AS INDICATED AND VERIFY NEW
REINFORCEMENT TYPE, FINISH, DIAMETER,
LENGTH, QUANTITY, EMBEDMENT LENGTH,
SPACING AND EDGE DISTANCES. VERIFY
USE OF PLACING TEMPLATE WHERE
SPECIFIED
REINFORCEMENT
- CONSTRUCTION
LOADS
P
ACI 563-18
1.5.1, 4.1.2.1(d),
4.3.2.5 & 4.3.3.1
VERIFY THAT CONSTRUCTION LOADS
INCLUDING EQUIPMENT, MATERIALS, ETC.
DO NOT OVERLOAD EXISTING STRUCTURE
CAPACITY
- LOCATION OF REPAIR
P
ACI 563-18 1.5.2
& 1.5.4.1
VERIFY WORK IS ONLY BEING PERFORMED
IN AREAS INDICATED AND THAT EXISTING
CONSTRUCTION ADJACENT TO WORK AREA
IS PROTECTED FROM DAMAGE
EXISTING CONDITIONS
ITEM FREQUENCY STANDARD CRITERIA
STRUCTURAL CONCRETE REPAIR INSPECTIONS
NOTE:
1. PROVIDE MINIMUM NUMBER OF COMPOSITE SAMPLES AS REQUIRED TO PERFORM THE
COMPRESSIVE STRENGTH TESTING LISTED.
2. CONVENTIONAL
CONCRETE OR
PRE-PACKAGED REPAIR
MORTAR
EACH
COMPOSITE
SAMPLE
ASTM C31
ASTM C39
EITHER:
(4)6X12 OR
(6)4X8
CYLINDERS
TEST PER SCHEDULE BELOW:
- 7DAYS: (1) 6x12 OR (1) 4x8
- 28 DAYS: (2) 6x12 OR (3) 4x8
- 56 DAYS: (1) 6x12 OR (2) 4x8 (IF 28-DAY
TESTS DO NOT ACHIEVE SPECIFIED 28 DAY
STRENGTH) ACCEPTANCE CRITERIA PER
ACI 318
1. PRE-PACKAGED
REPAIR MORTAR EACH
COMPOSITE
SAMPLE
ASTM C109: 2IN
CUBE
SPECIMENS
PROVIDE 7-DAY AND 28-DAY COMPRESSIVE
STRENGTH TEST RESULTS WHICH MEET OR
EXCEED REPAIR MORTAR
MANUFACTURER'S LISTED PERFORMANCE
TEST VALUES
- COMPRESSIVE STRENGTH (EITHER 1 OR 2)
- COMPOSITE SAMPLE
1 MINIMUM
PER DAY,
NOTE 1
ASTM C172
OBTAIN AT POINT OF PLACEMENT
COMPOSITE MATERIAL (PRE-PACKAGED REPAIR MORTAR OR CONVENTIONAL CONCRETE)
ITEM FREQUENCY STANDARD CRITERIA
STRUCTURAL CONCRETE REPAIR TESTING
- CURE TIME
100% VISUAL -
VERIFY FULL CURE TIME HAS ELAPSED
PRIOR TO APPLICATION OF TORQUE OR
LOAD TO ANCHOR
- AFTER INSTALLATION
OF ATTACHED
ASSEMBLY 100% VISUAL -
VERIFY NUMBER, EDGE DISTANCES, AND
ANCHOR FLUSH WITH AND PERPENDICULAR
TO THE RECEIVING SURFACE
- DURING INSTALLATION
OF ANCHOR
P
ICC-ES
REPORT
VERIFY HOLE DIMENSIONS, HOLE
CLEANING, ANCHOR EMBEDMENT, EDGE
DISTANCES AND SPACING
- PRIOR TO
INSTALLATION OF
ANCHOR EACH ANCHOR
ICC-ES
REPORT
VERIFY TYPE, DIAMETER, LENGTH, FINISH,
AND BASE MATERIAL. VERIFY SOLID
GROUTED AREA AROUND ANCHORS IN
GROUTED MASONRY
- PRIOR TO START OF
WORK -
ICC-ES
REPORT
REVIEW CONTRACTOR'S INSTALLATION
PROCEDURE
ADHESIVE ANCHORS, REINFORCING STEEL ANCHORED INTO HARDENED CONCRETE
- AFTER INSTALLATION
OF ATTACHED
ASSEMBLY
100% VISUAL -
VERIFY NUMBER, EDGE DISTANCES, AND
ANCHOR FLUSH WITH AND PERPENDICULAR
TO THE RECEIVING SURFACE
- DURING INSTALLATION
OF ANCHOR P
ICC-ES
REPORT
VERIFY HOLE DIMENSIONS, HOLE
CLEANING, ANCHOR EMBEDMENT, EDGE
DISTANCES AND SPACING
- PRIOR TO
INSTALLATION OF
ANCHOR
EACH ANCHOR
ICC-ES
REPORT
VERIFY TYPE, DIAMETER, LENGTH, FINISH,
AND BASE MATERIAL. VERIFY SOLID
GROUTED AREA AROUND ANCHORS IN
GROUTED MASONRY. VERIFY MAXIMUM
IMPACT WRENCH TORQUE RATING FOR
SCREW ANCHORS
- PRIOR TO START OF
WORK -
ICC-ES
REPORT
REVIEW CONTRACTOR'S INSTALLATION
PROCEDURE
EXPANSION ANCHORS, SLEEVE ANCHORS, SCREW ANCHORS
ITEM FREQUENCY STANDARD CRITERIA
POST-INSTALLED ANCHORS/REINFORCING STEEL INSPECTIONS
- TORQUE TEST
(WHERE APPLICABLE)
100% -
TEST ANCHOR WITH CALIBRATED TORQUE
WRENCH TO 100% OF THE INSTALLATION
TORQUE NOTED IN ICC-ES REPORT. ATTAIN
SPECIFIED TORQUE WITHIN 1/2 TURN OF
THE NUT
EXPANSION ANCHORS, SLEEVE ANCHORS, SCREW ANCHORS
ITEM FREQUENCY STANDARD CRITERIA
POST-INSTALLED ANCHOR/REINFORCING STEEL TESTING
QUALITY ASSURANCE GENERAL NOTES STATEMENT OF
STRUCTURAL INSPECTIONS AND TESTING
ADHESION TEST
10 FIRST 1000 LF
1 EACH SUBSEQUENT 1000 LF
SEE SPECIFICATION FOR
DETAILED REQUIREMENTS
ITEM FREQUENCY STANDARD CRITERIA
HORIZONTAL JOINT SEALANT TESTING
WET MIL THICKNESS EVERY 600 SF -
SEE SPECIFICATION FOR DETAILED
REQUIREMENTS
ADHESION TEST 1 AT MOCK-UP -
SEE SPECIFICATION FOR DETAILED
REQUIREMENTS
ITEM FREQUENCY STANDARD CRITERIA
TRAFFIC COATING TESTING
WORK LIST
DESCRIPTION
REFERENCE
DETAIL
ESTIMATED
QUANTITY
WORK
ITEM
INSTALL SHORING TO GRADE AT DOUBLE-TEE STEM PRIOR TO PERFORMING REPAIR. 23 LOCS
INSTALL SHORING AT INVERTED-TEE BEAM TO GRADE PRIOR TO PERFORMING REPAIR. 3 LOCS
2/S3.0
2/S3.0
REMOVE DETERIORATED CONCRETE AND RE-ENCASE STEEL HAUNCH SUPPORTING INVERTED-TEE BEAM WITH FORM AND POUR REPAIR MORTAR. IF STEEL SECTION LOSS EXCEEDS 10% CROSS SECTIONAL AREA
NOTIFY ENGINEER FOR OBSERVATION.
CONTRACTOR TO PROVIDE AN ALLOWANCE TO REMOVE DETERIORATED STEEL HAUNCH AND REPLACE
WITH STEEL POST.
REMOVE AND REPLACE DETERIORATED CONCRETE AND REINFORCING STEEL AT BEAM LEDGE. FOR
EACH LOCATION, ASSUME 3 LINEAR FEET OF REPAIR AND INSTALLATION OF SUPPLEMENTAL
REINFORCEMENT.
REMOVE DETERIORATED CONCRETE AT DAPPED DOUBLE-TEE STEM NEAR BEARING LOCATION AND
PROVIDE DAPPED ENLARGEMENT STRENGTHENING WITH SLIDE BEARING DETAILING.
INSTALL SUPPLEMENTAL BEARING SEAT BENEATH DAPPED DOUBLE-TEE STEMS.
INSTALL SUPPLEMENTAL CONNECTION TO REPLACE BROKEN OR LOOSE CONNECTION BETWEEN
DOUBLE-TEE FLANGE AND BEAM.
INSTALL SHORING TO GRADE AT RAMP SPANDREL. LIFT SPANDREL TO CALIBRATED LOAD RATING AND
SECURE SHORING IN PLACE.
PERFORM CONCRETE REPAIR AT RAMP SPANDREL. FOR PRICING PURPOSES, ASSUME FULL THICKNESS REPAIR, INSTALLATION OF SUPPLEMENTAL STEEL IS REQUIRED, AND THAT THE USE OF AN AERIAL LIFT
OR OTHER METHODS MAY BE NEEDED FOR ACCESS.
INSTALL SUPPLEMENTAL SPANDREL TIEBACK CONNECTION WHERE EXISTING CONNECTION IS BROKEN.
REMOVE AND REPLACE EXISTING DELAMINATED CONCRETE FROM RAIL SUPPORT POST. FOR PRICING PURPOSES, ASSUME THE DETAIL CONDITION WHICH PRODUCES THE HIGHEST COST, AND ASSUME FORM AND PUMP APPLICATION METHOD WILL BE REQUIRED. INCLUDE COST TO INSTALL GALVANIC ANODES AT
CONDITION B, AS SHOWN IN DETAIL.
CONTRACTOR TO PROVIDE AN ALLOWANCE TO INSTALL CFRP BISCUITS AT FAILED DOUBLE-TEE FLANGE CONNECTIONS. CONNECTION IS FAILED IF SIGNIFICANT CONCRETE SPALLING HAS OCCURRED IN THE
VICINITY OF THE CONNECTION. IF ONE OR MORE CONNECTIONS IS DAMAGED ALONG A JOINT
SUPPLEMENT ALL CONNECTIONS ALONG JOINT. FOR PRICING PURPOSES, INCLUDE 12 BISCUITS PER
JOINT.
REPAIR DELAMINATED CONCRETE SPALLS AND CORRODED REINFORCING BARS ON OVERHEAD AND
VERTICAL SURFACES OF DOUBLE-TEE FLANGES AND STEMS, INVERTED-TEE BEAMS, WALLS AND
COLUMNS. FOR PRICING PURPOSES, ASSUME 2" AVERAGE REPAIR DEPTH WITH FORM AND POUR REPAIR MORTAR. INCLUDE COST TO INSTALL GALVANIC ANODES AT LEVEL 1 RCP AND LEVEL 2 RCP, AS SHOWN IN
DETAILS.
REMOVE EXISTING TRAFFIC COATING FROM CONCRETE SURFACE.
REPAIR ALL SPALLED AND DELAMINATED HORIZONTAL CONCRETE SURFACES. FOR PRICING PURPOSES, ASSUME THE QUANTITY LISTED HAS A 3" REPAIR DEPTH. ASSUME 4x4-W4.0xW4.0 WWR IN REPAIR AREA AND #3 REBAR PERIMETER ADHESIVE DOWELS ARE REQUIRED TO SUPPLEMENT EXISTING CORRODED
REINFORCING.
CONTRACTOR TO PROVIDE AN ALLOWANCE TO PERFORM FULL DEPTH CONCRETE SLAB REPAIR WHERE DAMAGE IS DISCOVERED TO EXTEND FULL DEPTH. FOR PRICING PURPOSES, ASSUME 4x4xW4.0xW4.0
WWR IN REPAIR AREA AND #3 PERIMETER ADHESIVE DOWELS ARE REQUIRED TO SUPPLEMENT
DAMAGED STEEL.
REMOVE AND REPLACE EXISTING HORIZONTAL JOINT SEALANT WITH A POLYURETHANE SEALANT.
PERFORM ADHESION TESTING IN ACCORDANCE WITH THE SPECIFICATION.
REMOVE AND REPLACE EXISTING COVE JOINT SEALANT WITH POLYURETHANE SEALANT. COVE SEALANT
TO BE LOCATED AT HORIZONTAL TO VERTICAL SURFACE TRANSITIONS, INCLUDING CURBS.
PREPARE SURFACE AND APPLY HEAVY DUTY TRAFFIC COATING. INCLUDE THE PRICE OF A MOCKUP FOR ENGINEER AND OWNER REVIEW. EXTEND TRAFFIC COATING UP AND OVER CURBS AND 4" UP VERTICAL
SURFACES.
PERFORM PARTIAL DEPTH HORIZONTAL SURFACE CONCRETE REPAIR AT THE RAMP WITH AN INTEGRAL TRACTION FINISH TEXTURE. FOR PRICING PURPOSES, ASSUME A 4" DEPTH OF REPAIR AND INCLUDE THE COST OF A MOCK-UP FOR OWNER AND ENGINEER REVIEW. INCLUDE COST TO INSTALL GALVANIC ANODES, AS SHOWN IN DETAIL
REMOVE AND REPLACE CONCRETE SLAB AT STAIR LANDING.
PERFORM FULL DEPTH CONCRETE REPAIR AT SLAB ON GRADE. FOR PRICING PURPOSES, ASSUME A 5"
SLAB ON GRADE.
REMOVE AND REPLACE EXISTING WING TYPE EXPANSION JOINT. PERFORM CONCRETE REPAIR TO REPROFILE THE JOINT SHOULDER PRIOR TO REPLACING THE NEW GLAND. WIDTH OF NEW JOINT TO
MATCH EXISTING.
REMOVE DETERIORATED VERTICAL ELASTOMERIC EXPANSION JOINT AND REPLACE WITH SILICONE
FACED FOAM SEAL. WIDTH OF NEW JOINT TO MATCH EXISTING.
PREPARE CONCRETE SURFACE AND APPLY 100% SOLIDS SILANE SEALER IN AREAS THAT WILL NOT RECEIVE TRAFFIC COATING. FOR PRICING PURPOSES, ASSUME 2 APPLICATIONS AT 250-400 SQUARE
FEET PER GALLON. INCLUDE PRICING FOR A MOCKUP FOR ENGINEER AND OWNER REVIEW.
RE-STRIPE AREAS THAT RECEIVED TRAFFIC COATING TO MATCH THE ORIGINAL PARKING LAYOUT. LINE
STRIPING SHALL BE COMPATIBLE WITH APPLICATION SUBSTRATE.
2 LOCS
150,900 SF
3 LOCS
3 LOCS
NOTE 4
2 LOCS
7 LOCS
2 LOCS
2 LOCS
20 SF
4 LOCS
125 LOCS
15 JOINTS
1,200 SF
19,300 SF
650 SF
150 SF
5,400 LF
2,800 LF
25,100 SF
225 SF
70 SF
10 SF
1,600 LF
125 LF
131,000 SF
WORK LIST NOTES:
1. THE VALUES IN THE "ESTIMATED QUANTITY" COLUMN OF THE WORK LISTS MAY BE GREATER THAN OR LESS THAN THE AMOUNTS SHOWN ON PLAN.
USE THE QUANTITIES LISTED IN THE WORK LIST FOR BID PURPOSES AND PROVIDE UNIT COSTS. CONTRACTOR SHALL FIELD VERIFY QUANTITIES
AND LOCATIONS PRIOR TO WORK.
2. BID PRICING SHALL REFLECT THE PRODUCTS SPECIFIED IN THIS DOCUMENT. SUBSTITUTIONS AND ASSOCIATED PRICING MAY BE SUBMITTED IN ADDITION TO THE UNIT COST PRICES FOR THE SPECIFIED MATERIALS. THE ENGINEER SHALL REVIEW AND DETERMINE IF THE ALTERNATE PRODUCT
IS CONSIDERED "EQUAL" AND IF IT WILL BE ALLOWED AS A SUBSTITUTION.
3. CONTRACTOR SHALL KEEP A CURRENT SCHEDULE OF VALUES FOR ALL WORK ITEMS BEING PERFORMED WITH QUANTITIES COMPLETED TO DATE FOR OWNER REVIEW AT WEEKLY MEETINGS. ANY ANTICIPATED OVERAGES OR SHORTAGES TO THE BID QUANTITIES LISTED ABOVE SHOULD BE
PRESENTED AS WELL.
4. WORK ITEMS NOTED AS ALLOWANCE MAY NOT BE SHOWN ON PLAN.
5/S3.0
10/S3.1
9/S3.0
10/S3.0
12/S3.0
18/S3.0
4/S3.0
5/S3.1
8/S3.1
6/S3.1
4/S3.1
17/S3.0
7/S3.2
9/S3.2
10/S3.2
12/S3.1
17/S3.1
11/S3.2
1/S3.2
6/S3.2
20/S3.0
19/S3.1
17/S3.0 20/S3.0
17/S3.0
18/S3.1
8/S3.2
3/S3.2 4/S3.2
5/S3.2
20/S3.1
SP0.2
INCLUDE COST FOR MONTHLY SHORING RENTAL. MONTHLY3
19/S3.0
2/S3.0
ADD ALTERNATE
ADD ALTERNATE
ADD ALTERNATE
ADD ALTERNATE
ADD ALTERNATE
ADD ALTERNATE
M a rt in
/M ar ti n
, I n c . c o n s id e rs t h at d es ig n d a ta is o n ly i n i ts f in a l f o rm o n p lo tt e d d ra w in g s w it h o ri g in a l s ig n a tu re s a n d p ro fe s s io n a l c er ti fi ca ti o n b ei n g v is ib ly p re s en t o n t h e d ra w in g s . D a ta s u p p lie d v ia c o m p u te r g en e ra te d f o rm a t d o es n o t c o n ta in t h is a p p ro v al o r ce rt if ic a ti o n
T h e r ec ei v er o f el e ct ro n ic a ll y tr a n s m it te d d ra w in g s is r e s p o n s ib le f o r v er if yi n g t h e in fo rm a ti o n c o n ta in e d w it h in t h e e le c tr o n ic d a ta a g a in s t th e r ec o rd e d o r ap p ro v ed d o cu m en ts
T h e u se o f el e ct ro n ic a lly t ra ns m itt e d d ra w in g s is c on si d e re d to b e a t yo u r o w n r is k.
M a rt in
/M a rt in
In c.