238126_Split-System_Air-Conditioners.pdf
PDF 35 KB Posted
- Solicitation number
- AG-9702-S-10-0335
About this file
specifications
View the file
Other files
| File | Type | Posted |
|---|---|---|
| CONSTRUCTION_IFB.docx | DOCX document | |
| sf25a_e.pdf | ||
| sf25.pdf | ||
| 233713_Diffusers Registers Grilles.pdf | ||
| 230553_Identification_For_HVAC_Piping Equipment.pdf | ||
| 230513_Common_Motor_Requirements_For_HVAC_Equipment.pdf | ||
| sf25b.pdf | ||
| 230529_Hangers Supports_For_HVAC_Piping Equipment.pdf | ||
| M100 100 .pdf | ||
| 233300_Air_Duct_Accessories.pdf | ||
| 233113_Metal_Ducts.pdf | ||
| 230100 HVAC System.doc | DOC document | |
| 230700_HVAC_Insulation.pdf | ||
| CONSTRUCTION_IFB.docx | DOCX document | |
| 231126_Facility_Liquefied-Petroleum_Gas_Piping.pdf | ||
| sf24_e.pdf | ||
| Titlesheet | — | |
| M201 100 .pdf | ||
| 232300_Refrigerant_Piping.pdf | ||
| USFS CR MECH CUTSHEETS.PDF | ||
| DB General Decision Number.docx | DOCX document | |
| M301 100 .pdf | ||
| 230548_Vibration Seismic_Controls_For_HVAC_Piping Equipment.pdf | ||
| Camino_ Real_titlesheet Layout1 | — | |
| 235400_Furnaces.pdf | ||
| 230593_Testing Adjusting Balancing_For_HVAC.pdf |
Show all 26
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
USDA Forest Service – Camino Real Office Building 238126 - 1
SPLIT-SYSTEM AIR-CONDITIONERS
SECTION 238126
SPLIT-SYSTEM AIR-CONDITIONERS
PART 1 – GENERAL
1.1 SUMMARY
A. This Section includes split-system air-conditioning and heat pump units consisting of separate evaporator-fan and compressor-condenser components. Units are designed for exposed or concealed mounting, and may be connected to ducts.
1.2 SUBMITTALS
A. Product Data: For each unit indicated. Include performance data in terms of capaci-ties, outlet velocities, static pressures, sound power characteristics, motor require-ments, and electrical characteristics.
B. Operation and maintenance data.
1.3 QUALITY ASSURANCE
A. Electrical Components, Devices, and Accessories: Listed and labeled as defined in
NFPA 70, Article 100, by a testing agency acceptable to authorities having jurisdic-tion, and marked for intended use.
B. ASHRAE Compliance: Applicable requirements in ASHRAE 62.1-2004, Section 5 -
"Systems and Equipment" and Section 7 - "Construction and Startup."
C. ASHRAE/IESNA 90.1-2004 Compliance: Applicable requirements in
ASHRAE/IESNA 90.1-2004, Section 6 - "Heating, Ventilating, and Air-
Conditioning."
D. All products to be manufactured in the US and comply with the Buy American Act.
1.4 WARRANTY
A. Special Warranty: Manufacturer's standard form in which manufacturer agrees to re-pair or replace split-system air-conditioning units that fail in materials and workman-ship within five years from date of Substantial Completion.
PART 2 – PRODUCTS
2.1 MANUFACTURERS
A. Available Manufacturers: Subject to compliance with requirements, manufacturers of-fering products that may be incorporated into the Work include, but are not limited to, the following:
USDA Forest Service – Camino Real Office Building 238126 - 2
B. Manufacturers: Subject to compliance with requirements, provide products by one of the following:
1. Carrier Air Conditioning; Div. of Carrier Corp.
2. Trane Co. (The); Unitary Products Group.
3. York International Corp.
2.2 EVAPORATOR-FAN UNIT
A. Unit Chassis: Galvanized steel with flanged edges, removable panels for servicing, and insulation on back of panel.
1. Insulation: Faced, glass-fiber duct liner.
2. Drain Pans: Galvanized steel, with connection for drain; insulated and comply-ing with ASHRAE 62.1-2004.
3. Airstream Surfaces: Surfaces in contact with the airstream shall comply with requirements in ASHRAE 62.1-2004.
B. Refrigerant Coil: Copper tube, with mechanically bonded aluminum fins, complying with ARI 210/240, and with thermal-expansion valve.
C. Evaporator Fan: Forward-curved, double-width wheel of galvanized steel; directly connected to motor.
D. Fan Motor: Multispeed.
E. Filters: Permanent, cleanable.
2.3 AIR-COOLED, COMPRESSOR-CONDENSER UNIT
A. Casing steel, finished with baked enamel, with removable panels for access to con-trols, weep holes for water drainage, and mounting holes in base. Provide brass ser-vice valves, fittings, and gage ports on exterior of casing.
B. Compressor: Hermetically sealed reciprocating or scroll type with crankcase heater and mounted on vibration isolation. Compressor motor shall have thermal- and cur-rent-sensitive overload devices, start capacitor, relay, and contactor..
1. Refrigerant: R-410A.
2. Refrigerant: R-410A.
C. Refrigerant Coil: Copper tube, with mechanically bonded aluminum fins, complying with ARI 210/240, and with liquid subcooler.
D. Fan: Aluminum-propeller type, directly connected to motor.
E. Motor: Permanently lubricated, with integral thermal-overload protection.
F. Low Ambient Kit: Permits operation down to -20 deg F.
USDA Forest Service – Camino Real Office Building 238126 - 3
G. Mounting Base: Polyethylene.
H. Minimum Energy Efficiency: Comply with ASHRAE/IESNA 90.1-2004, "Energy
Standard for Buildings except Low-Rise Residential Buildings."
2.4 ACCESSORIES
A. Thermostat: Low voltage with subbase to control compressor and evaporator fan.
B. Refrigerant Line Kits: Soft-annealed copper suction and liquid lines factory cleaned, dried, pressurized, and sealed; factory-insulated suction line with flared fittings at both ends.
1. Minimum Insulation Thickness: 1 inch (25 mm) thick.
PART 3 – EXECUTION
3.1 INSTALLATION
A. Install evaporator-fan components using manufacturer's standard mounting devices se-curely fastened to building structure.
B. Install ground-mounted, compressor-condenser components on 4-inch- (100-mm-) thick, reinforced concrete base; 4 inches (100 mm) larger on each side than unit. Con-crete, reinforcement, and formwork are specified in Division 03 Section "Cast-in-
Place Concrete." Coordinate anchor installation with concrete base.
3.2 CONNECTIONS
A. Connect precharged refrigerant tubing to component's quick-connect fittings. Install tubing to allow access to unit.
B. Install piping adjacent to unit to allow service and maintenance.
3.3 FIELD QUALITY CONTROL
A. Manufacturer's Field Service: Engage a factory-authorized service representative to inspect field-assembled components and equipment installation, including connec-tions.
B. Leak Test: After installation, charge system and test for leaks. Repair leaks and retest until no leaks exist.
C. Operational Test: After electrical circuitry has been energized, start units to confirm proper motor rotation and unit operation. Remove malfunctioning units, replace with new components, and retest.
USDA Forest Service – Camino Real Office Building 238126 - 4
D. Test and adjust controls and safeties. Replace damaged and malfunctioning controls and equipment.
END OF SECTION 238126