238126_Split-System_Air-Conditioners.pdf

PDF 35 KB Posted

Attached to
RECOVERY - HVAC System for Camino Real Office Project
Solicitation number
AG-9702-S-10-0335
Issued by

About this file

specifications

View the file

Other files

File Type Posted
CONSTRUCTION_IFB.docx DOCX document
sf25a_e.pdf PDF
sf25.pdf PDF
233713_Diffusers Registers Grilles.pdf PDF
230553_Identification_For_HVAC_Piping Equipment.pdf PDF
230513_Common_Motor_Requirements_For_HVAC_Equipment.pdf PDF
sf25b.pdf PDF
230529_Hangers Supports_For_HVAC_Piping Equipment.pdf PDF
M100 100 .pdf PDF
233300_Air_Duct_Accessories.pdf PDF
233113_Metal_Ducts.pdf PDF
230100 HVAC System.doc DOC document
230700_HVAC_Insulation.pdf PDF
CONSTRUCTION_IFB.docx DOCX document
231126_Facility_Liquefied-Petroleum_Gas_Piping.pdf PDF
sf24_e.pdf PDF
Titlesheet —
M201 100 .pdf PDF
232300_Refrigerant_Piping.pdf PDF
USFS CR MECH CUTSHEETS.PDF PDF
DB General Decision Number.docx DOCX document
M301 100 .pdf PDF
230548_Vibration Seismic_Controls_For_HVAC_Piping Equipment.pdf PDF
Camino_ Real_titlesheet Layout1 —
235400_Furnaces.pdf PDF
230593_Testing Adjusting Balancing_For_HVAC.pdf PDF
Show all 26

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

USDA Forest Service – Camino Real Office Building 238126 - 1

SPLIT-SYSTEM AIR-CONDITIONERS

SECTION 238126

SPLIT-SYSTEM AIR-CONDITIONERS

PART 1 – GENERAL

1.1 SUMMARY

A. This Section includes split-system air-conditioning and heat pump units consisting of separate evaporator-fan and compressor-condenser components. Units are designed for exposed or concealed mounting, and may be connected to ducts.

1.2 SUBMITTALS

A. Product Data: For each unit indicated. Include performance data in terms of capaci-ties, outlet velocities, static pressures, sound power characteristics, motor require-ments, and electrical characteristics.

B. Operation and maintenance data.

1.3 QUALITY ASSURANCE

A. Electrical Components, Devices, and Accessories: Listed and labeled as defined in

NFPA 70, Article 100, by a testing agency acceptable to authorities having jurisdic-tion, and marked for intended use.

B. ASHRAE Compliance: Applicable requirements in ASHRAE 62.1-2004, Section 5 -

"Systems and Equipment" and Section 7 - "Construction and Startup."

C. ASHRAE/IESNA 90.1-2004 Compliance: Applicable requirements in

ASHRAE/IESNA 90.1-2004, Section 6 - "Heating, Ventilating, and Air-

Conditioning."

D. All products to be manufactured in the US and comply with the Buy American Act.

1.4 WARRANTY

A. Special Warranty: Manufacturer's standard form in which manufacturer agrees to re-pair or replace split-system air-conditioning units that fail in materials and workman-ship within five years from date of Substantial Completion.

PART 2 – PRODUCTS

2.1 MANUFACTURERS

A. Available Manufacturers: Subject to compliance with requirements, manufacturers of-fering products that may be incorporated into the Work include, but are not limited to, the following:

USDA Forest Service – Camino Real Office Building 238126 - 2

B. Manufacturers: Subject to compliance with requirements, provide products by one of the following:

1. Carrier Air Conditioning; Div. of Carrier Corp.

2. Trane Co. (The); Unitary Products Group.

3. York International Corp.

2.2 EVAPORATOR-FAN UNIT

A. Unit Chassis: Galvanized steel with flanged edges, removable panels for servicing, and insulation on back of panel.

1. Insulation: Faced, glass-fiber duct liner.

2. Drain Pans: Galvanized steel, with connection for drain; insulated and comply-ing with ASHRAE 62.1-2004.

3. Airstream Surfaces: Surfaces in contact with the airstream shall comply with requirements in ASHRAE 62.1-2004.

B. Refrigerant Coil: Copper tube, with mechanically bonded aluminum fins, complying with ARI 210/240, and with thermal-expansion valve.

C. Evaporator Fan: Forward-curved, double-width wheel of galvanized steel; directly connected to motor.

D. Fan Motor: Multispeed.

E. Filters: Permanent, cleanable.

2.3 AIR-COOLED, COMPRESSOR-CONDENSER UNIT

A. Casing steel, finished with baked enamel, with removable panels for access to con-trols, weep holes for water drainage, and mounting holes in base. Provide brass ser-vice valves, fittings, and gage ports on exterior of casing.

B. Compressor: Hermetically sealed reciprocating or scroll type with crankcase heater and mounted on vibration isolation. Compressor motor shall have thermal- and cur-rent-sensitive overload devices, start capacitor, relay, and contactor..

1. Refrigerant: R-410A.

2. Refrigerant: R-410A.

C. Refrigerant Coil: Copper tube, with mechanically bonded aluminum fins, complying with ARI 210/240, and with liquid subcooler.

D. Fan: Aluminum-propeller type, directly connected to motor.

E. Motor: Permanently lubricated, with integral thermal-overload protection.

F. Low Ambient Kit: Permits operation down to -20 deg F.

USDA Forest Service – Camino Real Office Building 238126 - 3

G. Mounting Base: Polyethylene.

H. Minimum Energy Efficiency: Comply with ASHRAE/IESNA 90.1-2004, "Energy

Standard for Buildings except Low-Rise Residential Buildings."

2.4 ACCESSORIES

A. Thermostat: Low voltage with subbase to control compressor and evaporator fan.

B. Refrigerant Line Kits: Soft-annealed copper suction and liquid lines factory cleaned, dried, pressurized, and sealed; factory-insulated suction line with flared fittings at both ends.

1. Minimum Insulation Thickness: 1 inch (25 mm) thick.

PART 3 – EXECUTION

3.1 INSTALLATION

A. Install evaporator-fan components using manufacturer's standard mounting devices se-curely fastened to building structure.

B. Install ground-mounted, compressor-condenser components on 4-inch- (100-mm-) thick, reinforced concrete base; 4 inches (100 mm) larger on each side than unit. Con-crete, reinforcement, and formwork are specified in Division 03 Section "Cast-in-

Place Concrete." Coordinate anchor installation with concrete base.

3.2 CONNECTIONS

A. Connect precharged refrigerant tubing to component's quick-connect fittings. Install tubing to allow access to unit.

B. Install piping adjacent to unit to allow service and maintenance.

3.3 FIELD QUALITY CONTROL

A. Manufacturer's Field Service: Engage a factory-authorized service representative to inspect field-assembled components and equipment installation, including connec-tions.

B. Leak Test: After installation, charge system and test for leaks. Repair leaks and retest until no leaks exist.

C. Operational Test: After electrical circuitry has been energized, start units to confirm proper motor rotation and unit operation. Remove malfunctioning units, replace with new components, and retest.

USDA Forest Service – Camino Real Office Building 238126 - 4

D. Test and adjust controls and safeties. Replace damaged and malfunctioning controls and equipment.

END OF SECTION 238126