233300_Air_Duct_Accessories.pdf
PDF 44 KB Posted
- Solicitation number
- AG-9702-S-10-0335
About this file
specifications
View the file
Other files
Show all 26
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
USDA Forest Service – Camino Real Office Building 233300 - 1
AIR DUCT ACCESSORIES
SECTION 233300
AIR DUCT ACCESSORIES
PART 1 – GENERAL
1.1 SUMMARY
A. Section Includes:
1. Backdraft and pressure relief dampers.
2. Manual volume dampers.
3. Control dampers.
4. Turning vanes.
5. Flexible connectors.
6. Duct accessory hardware.
1.2 SUBMITTALS
A. Product Data: None
1.3 QUALITY ASSURANCE
A. Comply with NFPA 90A, "Installation of Air Conditioning and Ventilating Systems," and with NFPA 90B, "Installation of Warm Air Heating and Air Conditioning Sys-tems."
B. Comply with AMCA 500-D testing for damper rating.
C. All products to be manufactured in the US and comply with the Buy American Act.
PART 2 – PRODUCTS
2.1 MATERIALS
A. Comply with SMACNA's "HVAC Duct Construction Standards - Metal and Flexible" for acceptable materials, material thicknesses, and duct construction methods unless otherwise indicated. Sheet metal materials shall be free of pitting, seam marks, roller marks, stains, discolorations, and other imperfections.
B. Galvanized Sheet Steel: Comply with ASTM A 653/A 653M.
1. Galvanized Coating Designation: G60 (Z180).
2. Exposed-Surface Finish: Mill phosphatized.
2.2 BACKDRAFT AND PRESSURE RELIEF DAMPERS
USDA Forest Service – Camino Real Office Building 233300 - 2
A. Manufacturers: Subject to compliance with requirements, available manufacturers of-fering products that may be incorporated into the Work include, but are not limited to, the following:
1. Air Balance Inc.; a division of Mestek, Inc.
2. American Warming and Ventilating; a division of Mestek, Inc.
3. Cesco Products; a division of Mestek, Inc.
4. Duro Dyne Inc.
5. Greenheck Fan Corporation.
6. Lloyd Industries, Inc.
7. Nailor Industries Inc.
8. NCA Manufacturing, Inc.
9. Pottorff; a division of PCI Industries, Inc.
10. Ruskin Company.
11. SEMCO Incorporated.
12. Vent Products Company, Inc.
B. Description: Gravity balanced.
C. Maximum Air Velocity: 2000 fpm (10 m/s).
D. Maximum System Pressure: 1-inch wg (0.25 kPa).
E. Frame: 0.052-inch- (1.3-mm-) thick, galvanized sheet steel, with welded corners.
F. Blades: Multiple single-piece blades, center-pivoted, maximum 6-inch (150-mm) width, 0.025-inch- (0.6-mm-) thick, roll-formed aluminum with sealed edges.
G. Blade Action: Parallel.
H. Blade Seals: Vinyl foam.
I. Blade Axles:
1. Material: Nonferrous metal.
2. Diameter: 0.20 inch (5 mm).
J. Tie Bars and Brackets: Galvanized steel.
K. Return Spring: Adjustable tension.
L. Bearings: Steel ball.
2.3 MANUAL VOLUME DAMPERS
A. Standard, Steel, Manual Volume Dampers:
USDA Forest Service – Camino Real Office Building 233300 - 3
1. Manufacturers: Subject to compliance with requirements, available manufactur-ers offering products that may be incorporated into the Work include, but are not limited to, the following:
a. Air Balance Inc.; a division of Mestek, Inc.
b. American Warming and Ventilating; a division of Mestek, Inc.
c. Flexmaster U.S.A., Inc.
d. McGill AirFlow LLC.
e. METALAIRE, Inc.
f. Nailor Industries Inc.
g. Pottorff; a division of PCI Industries, Inc.
h. Ruskin Company.
i. Trox USA Inc.
j. Vent Products Company, Inc.
2. Standard leakage rating.
3. Suitable for horizontal or vertical applications.
4. Frames:
a. Hat-shaped, galvanized-steel channels, 0.064-inch (1.62-mm) minimum thickness.
b. Mitered and welded corners.
c. Flanges for attaching to walls and flangeless frames for installing in ducts.
5. Blades:
a. Multiple or single blade.
b. Parallel- or opposed-blade design.
c. Stiffen damper blades for stability.
d. Galvanized-steel, 0.064 inch (1.62 mm) thick.
6. Blade Axles: Galvanized steel.
7. Bearings:
a. Oil-impregnated bronze.
b. Dampers in ducts with pressure classes of 3-inch wg (750 Pa) or less shall have axles full length of damper blades and bearings at both ends of oper-ating shaft.
8. Tie Bars and Brackets: Galvanized steel.
B. Damper Hardware:
1. Zinc-plated, die-cast core with dial and handle made of 3/32-inch- (2.4-mm-) thick zinc-plated steel, and a 3/4-inch (19-mm) hexagon locking nut.
2. Include center hole to suit damper operating-rod size.
3. Include elevated platform for insulated duct mounting.
USDA Forest Service – Camino Real Office Building 233300 - 4
2.4 TURNING VANES
A. Manufacturers: Subject to compliance with requirements, available manufacturers of-fering products that may be incorporated into the Work include, but are not limited to, the following:
1. Ductmate Industries, Inc.
2. Duro Dyne Inc.
3. METALAIRE, Inc.
4. SEMCO Incorporated.
5. Ward Industries, Inc.; a division of Hart & Cooley, Inc.
B. Manufactured Turning Vanes for Metal Ducts: Curved blades of galvanized sheet steel; support with bars perpendicular to blades set; set into vane runners suitable for duct mounting.
1. Acoustic Turning Vanes: Fabricate airfoil-shaped aluminum extrusions with perforated faces and fibrous-glass fill.
C. General Requirements: Comply with SMACNA's "HVAC Duct Construction Stan-dards - Metal and Flexible"; Figures 2-3, "Vanes and Vane Runners," and 2-4, "Vane
Support in Elbows."
D. Vane Construction: Single wall.
2.5 FLEXIBLE CONNECTORS
A. Manufacturers: Subject to compliance with requirements, available manufacturers of-fering products that may be incorporated into the Work include, but are not limited to, the following:
1. Ductmate Industries, Inc.
2. Duro Dyne Inc.
3. Ventfabrics, Inc.
4. Ward Industries, Inc.; a division of Hart & Cooley, Inc.
B. Materials: Flame-retardant or noncombustible fabrics.
C. Coatings and Adhesives: Comply with UL 181, Class 1.
D. Metal-Edged Connectors: Factory fabricated with a fabric strip 3-1/2 inches (89 mm) wide attached to 2 strips of 2-3/4-inch- (70-mm-) wide, 0.028-inch- (0.7-mm-) thick, galvanized sheet steel or 0.032-inch- (0.8-mm-) thick aluminum sheets. Provide metal compatible with connected ducts.
E. Indoor System, Flexible Connector Fabric: Glass fabric double coated with neoprene.
1. Minimum Weight: 26 oz./sq. yd. (880 g/sq. m).
USDA Forest Service – Camino Real Office Building 233300 - 5
2. Tensile Strength: 480 lbf/inch (84 N/mm) in the warp and 360 lbf/inch
(63 N/mm) in the filling.
3. Service Temperature: Minus 40 to plus 200 deg F (Minus 40 to plus 93 deg C).
PART 3 – EXECUTION
3.1 INSTALLATION
A. Install duct accessories according to applicable details in SMACNA's "HVAC Duct
Construction Standards - Metal and Flexible" for metal ducts and in NAIMA AH116, "Fibrous Glass Duct Construction Standards," for fibrous-glass ducts.
B. Install duct accessories of materials suited to duct materials; use galvanized-steel ac-cessories in galvanized-steel and fibrous-glass ducts, stainless-steel accessories in stainless-steel ducts, and aluminum accessories in aluminum ducts.
C. Install backdraft dampers at inlet of exhaust fans or exhaust ducts as close as possible to exhaust fan unless otherwise indicated.
D. Install volume dampers at points on supply, return, and exhaust systems where branches extend from larger ducts. Where dampers are installed in ducts having duct liner, install dampers with hat channels of same depth as liner, and terminate liner with nosing at hat channel.
1. Install steel volume dampers in steel ducts.
2. Install aluminum volume dampers in aluminum ducts.
E. Set dampers to fully open position before testing, adjusting, and balancing.
F. Install test holes at fan inlets and outlets and elsewhere as indicated.
G. Install duct access doors on sides of ducts to allow for inspecting, adjusting, and main-taining accessories and equipment at the following locations:
1. On both sides of duct coils.
2. Upstream from duct filters.
3. At outdoor-air intakes and mixed-air plenums.
4. At drain pans and seals.
5. Downstream from manual volume dampers, control dampers, backdraft dam-pers, and equipment.
6. Adjacent to and close enough to fire or smoke dampers, to reset or reinstall fusi-ble links. Access doors for access to fire or smoke dampers having fusible links shall be pressure relief access doors; and shall be outward operation for access doors installed upstream from dampers and inward operation for access doors installed downstream from dampers.
7. At each change in direction and at maximum 50-foot (15-m) spacing.
8. Upstream from turning vanes.
USDA Forest Service – Camino Real Office Building 233300 - 6
9. Control devices requiring inspection.
10. Elsewhere as indicated.
H. Install access doors with swing against duct static pressure.
I. Access Door Sizes:
1. One-Hand or Inspection Access: 8 by 5 inches (200 by 125 mm).
2. Two-Hand Access: 12 by 6 inches (300 by 150 mm).
3. Head and Hand Access: 18 by 10 inches (460 by 250 mm).
4. Head and Shoulders Access: 21 by 14 inches (530 by 355 mm).
5. Body Access: 25 by 14 inches (635 by 355 mm).
6. Body plus Ladder Access: 25 by 17 inches (635 by 430 mm).
J. Label access doors according to Division 23 Section "Identification for HVAC Piping and Equipment" to indicate the purpose of access door.
K. Install flexible connectors to connect ducts to equipment.
L. Install duct test holes where required for testing and balancing purposes.
END OF SECTION 233300
File details come from the government source that posted it. Updated .