233713_Diffusers Registers Grilles.pdf

PDF 30 KB Posted

Attached to
RECOVERY - HVAC System for Camino Real Office Project
Solicitation number
AG-9702-S-10-0335
Issued by

About this file

specifications

View the file

Other files

File Type Posted
CONSTRUCTION_IFB.docx DOCX document
sf25a_e.pdf PDF
sf25.pdf PDF
230553_Identification_For_HVAC_Piping Equipment.pdf PDF
230513_Common_Motor_Requirements_For_HVAC_Equipment.pdf PDF
sf25b.pdf PDF
230529_Hangers Supports_For_HVAC_Piping Equipment.pdf PDF
M100 100 .pdf PDF
233300_Air_Duct_Accessories.pdf PDF
233113_Metal_Ducts.pdf PDF
230100 HVAC System.doc DOC document
230700_HVAC_Insulation.pdf PDF
CONSTRUCTION_IFB.docx DOCX document
231126_Facility_Liquefied-Petroleum_Gas_Piping.pdf PDF
sf24_e.pdf PDF
Titlesheet —
M201 100 .pdf PDF
232300_Refrigerant_Piping.pdf PDF
USFS CR MECH CUTSHEETS.PDF PDF
DB General Decision Number.docx DOCX document
M301 100 .pdf PDF
230548_Vibration Seismic_Controls_For_HVAC_Piping Equipment.pdf PDF
Camino_ Real_titlesheet Layout1 —
235400_Furnaces.pdf PDF
238126_Split-System_Air-Conditioners.pdf PDF
230593_Testing Adjusting Balancing_For_HVAC.pdf PDF
Show all 26

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

USDA Forest Service – Camino Real Office Building 233713 - 1

DIFFUSERS, REGISTERS, AND GRILLES

SECTION 233713

DIFFUSERS, REGISTERS, AND GRILLES

PART 1 – GENERAL

1.1 SUMMARY

A. Section Includes:

1. Adjustable bar registers.

2. Fixed face grilles.

B. Related Sections:

1. Division 23 Section "Air Duct Accessories" for fire and smoke dampers and vo-lume-control dampers not integral to diffusers, registers, and grilles.

1.2 SUBMITTALS

A. Product Data: For each type of product indicated, include the following:

1. Data Sheet: Indicate materials of construction, finish, and mounting details; and performance data including throw and drop, static-pressure drop, and noise rat-ings.

2. Diffuser, Register, and Grille Schedule: Indicate drawing designation, room lo-cation, quantity, model number, size, and accessories furnished.

1.3 QUALITY ASSURANCE

A. All products to be manufactured in the US and comply with the Buy American Act.

PART 2 – PRODUCTS

2.1 REGISTERS AND GRILLES

A. Adjustable Bar Register:

1. Basis-of-Design Product: Subject to compliance with requirements, provide product indicated on Drawings Hart and Cooley or comparable product by one of the following:

a. A-J Manufacturing Co., Inc.

b. Anemostat Products; a Mestek company.

c. Carnes.

d. Dayus Register & Grille Inc.

e. Krueger.

f. METALAIRE, Inc.

g. Nailor Industries Inc.

USDA Forest Service – Camino Real Office Building 233713 - 2

h. Price Industries.

i. Titus.

j. Tuttle & Bailey.

2. Finish: Baked enamel, color selected by CO.

3. Frame: 1-1/4 inches (32 mm) wide.

4. Accessories:

a. Front Rear-blade gang operator.

B. Fixed Face Grille Insert drawing designation:

1. Basis-of-Design Product: Subject to compliance with requirements, provide product indicated on Drawings Hart and Cooley or comparable product by one of the following:

a. A-J Manufacturing Co., Inc.

b. Anemostat Products; a Mestek company.

c. Carnes.

d. Dayus Register & Grille Inc.

e. Hart & Cooley Inc.

f. Krueger.

g. Nailor Industries Inc.

h. Price Industries.

i. Titus.

j. Tuttle & Bailey.

2. Finish: Baked enamel, color selected by CO.

3. Frame: 1-1/4 inches (32 mm) wide.

2.2 SOURCE QUALITY CONTROL

A. Verification of Performance: Rate diffusers, registers, and grilles according to

ASHRAE 70, "Method of Testing for Rating the Performance of Air Outlets and In-lets."

PART 3 – EXECUTION

3.1 INSTALLATION

A. Install diffusers, registers, and grilles level and plumb.

B. Ceiling-Mounted Outlets and Inlets: Drawings indicate general arrangement of ducts, fittings, and accessories. Air outlet and inlet locations have been indicated to achieve design requirements for air volume, noise criteria, airflow pattern, throw, and pressure drop. Make final locations where indicated, as much as practical. For units installed in lay-in ceiling panels, locate units in the center of panel. Where Architectural fea-tures or other items conflict with installation, notify CO for a determination of final location.

USDA Forest Service – Camino Real Office Building 233713 - 3

C. Install diffusers, registers, and grilles with airtight connections to ducts and to allow service and maintenance of dampers, air extractors, and fire dampers.

3.2 ADJUSTING

A. After installation, adjust diffusers, registers, and grilles to air patterns indicated, or as directed, before starting air balancing.

END OF SECTION 233713