230548_Vibration Seismic_Controls_For_HVAC_Piping Equipment.pdf
PDF 32 KB Posted
- Solicitation number
- AG-9702-S-10-0335
About this file
specifications
View the file
Other files
| File | Type | Posted |
|---|---|---|
| CONSTRUCTION_IFB.docx | DOCX document | |
| sf25a_e.pdf | ||
| sf25.pdf | ||
| 233713_Diffusers Registers Grilles.pdf | ||
| 230553_Identification_For_HVAC_Piping Equipment.pdf | ||
| 230513_Common_Motor_Requirements_For_HVAC_Equipment.pdf | ||
| sf25b.pdf | ||
| 230529_Hangers Supports_For_HVAC_Piping Equipment.pdf | ||
| M100 100 .pdf | ||
| 233300_Air_Duct_Accessories.pdf | ||
| 233113_Metal_Ducts.pdf | ||
| 230100 HVAC System.doc | DOC document | |
| 230700_HVAC_Insulation.pdf | ||
| CONSTRUCTION_IFB.docx | DOCX document | |
| 231126_Facility_Liquefied-Petroleum_Gas_Piping.pdf | ||
| sf24_e.pdf | ||
| Titlesheet | — | |
| M201 100 .pdf | ||
| 232300_Refrigerant_Piping.pdf | ||
| USFS CR MECH CUTSHEETS.PDF | ||
| DB General Decision Number.docx | DOCX document | |
| M301 100 .pdf | ||
| Camino_ Real_titlesheet Layout1 | — | |
| 235400_Furnaces.pdf | ||
| 238126_Split-System_Air-Conditioners.pdf | ||
| 230593_Testing Adjusting Balancing_For_HVAC.pdf |
Show all 26
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
USDA Forest Service – Camino Real Office Building 230548 - 1
VIBRATION AND SEISMIC CONTROLS FOR HVAC PIPING AND EQUIPMENT
SECTION 230548
VIBRATION AND SEISMIC CONTROLS FOR HVAC PIPING AND EQUIPMENT
PART 1 – GENERAL
1.1 SUMMARY
A. This Section includes the following:
1. Elastomeric hangers.
1.2 PERFORMANCE REQUIREMENTS
A. Seismic-Restraint Loading:
1. Site Class as Defined in the IBC: C.
2. Assigned Seismic Design Building Category as Defined in the IBC: B
1.3 SUBMITTALS
A. Product Data: For each product indicated.
B. Delegated-Design Submittal: For vibration isolation and seismic-restraint calculations and details indicated to comply with performance requirements and design criteria, in-cluding analysis data signed and sealed by the qualified professional engineer respon-sible for their preparation. If no seismic restraints are required a letter stating so form the aforementioned engineer is still required.
C. Qualification Data: For professional engineer.
D. Field quality-control test reports.
1.4 QUALITY ASSURANCE
A. Comply with seismic-restraint requirements in the IBC unless requirements in this
Section are more stringent.
B. Seismic-restraint devices shall have horizontal and vertical load testing and analysis and shall bear anchorage preapproval OPA number from OSHPD, preapproval by
ICC-ES, or preapproval by another agency acceptable to authorities having jurisdic-tion, showing maximum seismic-restraint ratings. Ratings based on independent test-ing are preferred to ratings based on calculations. If preapproved ratings are not avail-able, submittals based on independent testing are preferred. Calculations (including combining shear and tensile loads) to support seismic-restraint designs must be signed and sealed by a qualified professional engineer.
C. All products to be manufactured in the US and comply with the Buy American Act.
USDA Forest Service – Camino Real Office Building 230548 - 2
PART 2 – PRODUCTS
2.1 VIBRATION ISOLATORS
A. Available Manufacturers: Subject to compliance with requirements, manufacturers of-fering products that may be incorporated into the Work include, but are not limited to, the following:
B. Manufacturers: Subject to compliance with requirements, provide products by one of the following:
C. Basis-of-Design Product: Subject to compliance with requirements, provide one of the following:
1. Ace Mountings Co., Inc.
2. Amber/Booth Company, Inc.
3. California Dynamics Corporation.
4. Isolation Technology, Inc.
5. Kinetics Noise Control.
6. Mason Industries.
7. Vibration Eliminator Co., Inc.
8. Vibration Isolation.
9. Vibration Mountings & Controls, Inc.
D. Elastomeric Hangers: Single or double-deflection type, fitted with molded, oil-resistant elastomeric isolator elements bonded to steel housings with threaded connec-tions for hanger rods. Color-code or otherwise identify to indicate capacity range.
PART 3 – EXECUTION
3.1 FIELD QUALITY CONTROL
A. Perform tests and inspections.
B. Tests and Inspections:
1. Test at least four of each type and size of installed anchors and fasteners selected by CO.
2. Test to 90 percent of rated proof load of device.
3. Measure isolator restraint clearance.
4. Measure isolator deflection.
5. If a device fails test, modify all installations of same type and retest until satis-factory results are achieved.
C. Remove and replace malfunctioning units and retest as specified above.
D. Prepare test and inspection reports.
USDA Forest Service – Camino Real Office Building 230548 - 3
3.2 ADJUSTING
A. Adjust isolators after piping system is at operating weight.
B. Adjust restraints to permit free movement of equipment within normal mode of opera-tion.
3.3 HVAC VIBRATION-CONTROL AND SEISMIC-RESTRAINT DEVICE
SCHEDULE
A. Supported or Suspended Equipment: F-#.
1. Equipment Location: Basement
a. Material: Rubber.
b. Thickness: 1”.
2. Isolator Type: Elastomeric Hangers.
3. Minimum Deflection: 0.5”.
END OF SECTION 230548