Addendum No1 _Drawings - Building 55.pdf
PDF 4 MB Posted
- Solicitation number
- CRFQ 0211 GSD2700000019 2
- Issued by
- Kanawha County, West Virginia
About this file
This Addendum No. 1 for drawings constitutes design documentation for the Building 55 Security System Upgrades project managed by the West Virginia General Services Division. The project, located at 130 Stratton Street, Logan, WV 25601, involves comprehensive security system upgrades across a multi-story facility consisting of six levels (First Floor through Penthouse). The scope includes installation of new access control systems with integrated card readers, security cameras, door contacts, electrified locks, wireless panic buttons, and network infrastructure. The project incorporates demolition of existing security devices, replacement with new equipment, and migration of doors from the existing access control system to the new system on a phased basis to ensure no doors remain unsecured during the transition. The design specifies security network racks at multiple locations (SNR001-SNR005) with fiber optic connectivity, networked switches, uninterruptible power supplies, and network video recorders. All communication cables are required to be installed in conduit or cable tray with proper labeling and certification.
The security device schedule specifies approximately 50 multi-technology card readers (MTB15 model), multiple camera types ranging from 4MP dome cameras to 12MP fisheye and 5MP multi-head configurations, over 38 door contacts, and 16 wireless panic buttons distributed across the facility. Two dedicated 120-volt, 20-ampere circuits must be provided to each security network rack from the nearest electrical panel. The design requires compliance with fire-rated assembly penetration standards (UL systems WL 1001, 1002, or 1003) for all conduit penetrations through fire-rated walls, floors, and shaft enclosures. All exterior cameras require surge protection, and the existing fire alarm relay systems must be retained and reconnected to interface with the new access control system. The project requires coordination with the owner regarding lock schedules, field verification of exact hardware requirements, and adherence to National Electrical Code standards for all electrical installations and conduit work.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
ZDS Design/ Consulting Services
Mechanical * Electrical * IAQ * Energy * Commissioning
135 Corporate Center Dr., Suite 532 Scott Depot, WV 25560
Ph: (304) 755-0075 Fx: (304) 755-0076
Web: www.zdsdesign.com Email: contact@zdsdesign.com
C :\U se rs
\e di so n.
ad ki ns \D oc um en ts
\G
SD
2C
_2
4-
-3 0_
BL
D
G
L O
G
AN
_e di so n.
ad ki ns .rv t
WEST VIRGINIA GENERAL SERVICES DIVISION
BUILDING 55 SECURITY SYSTEM UPGRADES
ZDS Project Number: GSD-252-C 8/5/2026
130 STRATTON STREET
LOGAN, WV 25601
PROJECT VICINITY MAP
OS
DL
CO
T
CO
LC
F
F
F
DH
DCL
XXX
XXXX
XX
J
J F1
DO
M
N
X
TV
XXXX
CK
CK
TV
CC
DC
ES
IC
ML
RX
REX
MD
XXX
OS
1P 1 Pole (2P, 3P, 4P, ETC.)
A, Amp Ampere AC Above Counter ACLG Above Ceiling ADO Automatic Door Opener AF Amp Frame AFF Above Finished Floor AFG Above Finished Grade AFI Arc Fault Circuit
Interrupter AHU Air Handling Unit AL Aluminum ALT Alternate AMP Ampere AMPL Amplifier ANNUN Annunciator APPROX Approximately AQ-STAT Aquastat ARCH Architect, Architectural AS Amp Switch AT Amp Trip ATS Automatic Transfer Switch AUTO Automatic AUX Auxiliary AV Audio Visual AWG American Wire Gauge BATT Battery BD Board BLDG Building BMS Building Management System C Conduit CAB Cabinet CAT Catalog CATV Cable Television CB Circuit Breaker CCTV Closed Circuit Television CKT Circuit CLG Ceiling COMB Combination CMPR Compressor CONN Connection CONST Construction CONT Continuation Or Continuous CONTR Contractor CONV Convector CP Circulating Pump CRT Cathode-Ray Tube CT Current Transformer CTR Center CU Copper DCP Domestic Water Circulating Pump DEPT Department DET Detail DIA Diameter DISC Disconnect DIST Distribution DN Down DPR Damper DS Safety Disconnect Switch DT Double Throw DWG Drawing EC Electrical Contractor ELEC Electric, Electrical ELEV Elevator ELU Emergency Lighting Unit EM Emergency EMS Energy Management System EMT Electrical Metallic Tubing EP Electric Pneumatic EQUIP Equipment EWC Electric Water Cooler EXIST Existing EXH Exhaust EXP Explosion Proof FA Fire Alarm FABP Fire Alarm Booster Power
Supply Panel FACP Fire Alarm Control Panel FCU Fan Coil Unit FIXT Fixture FLR Floor FLUOR Fluorescent FU Fuse FUDS Fused Safety Disconnect Switch GA Gauge GAL Gallon GALV Galvanized GC General Contractor GEN Generator GFI Ground Fault Circuit Interrupter GFP Ground Fault Protector GND Ground GRS Galvanized Rigid Steel (Conduit) GYP BD Gypsum Board HOA Hands-Off-Automatic Switch HORIZ Horizontal HP Horsepower HPF High Power Factor HT Height HTG Heating HTR Heater HV High Voltage HVAC Heating, Ventilating And Air
Conditioning IC Interrupting Capacity IG Isolated Ground IMC Intermediate Metal Conduit INCAND Incandescent IR Infrared I/W Interlock With J-BOX Junction Box KV Kilovolt KVA Kilovolt-Ampere KVAR Kilovolt-Ampere Reactive KW Kilowatt KWH Kilowatt Hour LOC Locate Or Location LT Light LTG Lighting LTNG Lightning LV Low Voltage MAX Maximum MAG.S Magnetic Starter M/C Momentary Contact MC Mechanical Contractor
Electrical Abbreviations
Electrical DeviceTags: Uppercase letter(s) indicates Panel ID and circuit number. Lowercase letter indicates designation of controlling switch (where applicable).
Switch ID indicated by a lowercase letter. Switch IDs are unique per space. A switch with an ID "a" controls all devices within the space in which it is located tagged with "a". A switch without a tagged ID controls all lighting fixtures within a space. ID tags may be used on control devices other than switches, such as occupancy sensors or contactors.
Equipment Tags: Equipment ID is indicated by an underlined tag adjacent to the equipment. See the equipment connection schedule for description, electrical requirements, and panel and circuit number. Symbols/graphic appearance of equipment varies.
Solid, arced lines connecting equipment, devices, or fixtures indicate unswitched power circuiting. Wires are only intended to indicate to what circuit devices are connected. Actual connections, circuit routing, installtion, junction boxes, etc. shall be field-determined by the contractor.
Home run to branch circuit panelboard. The equipment name and circuit number(s) are indicated, separated by a hyphen. Homeruns are only intended to indicate panel and circuit number. Actual homerun location shall be field-determined by the contractor.
Power Symbols
Electrical Symbol Legend
Room
MCB Main Circuit Breaker MCC Motor Control Center MDC Main Distribution Center MDP Main Distribution Panel MFR Manufacturer MFS Main Fused Disconnect Switch MH Manhole MIC Microphone MIN Minimum MISC Miscellaneous MLO Main Lugs Only MMS Manual Motor Starter MOA Multioutlet Assembly MSP Motor Starter Panelboard MSBD Main Switchboard MSS Motor Starter Switch MT Mount MT.C Empty Conduit MTS Manual Transfer Switch MTR Motor, Motorized N.C. Normally Closed NEC National Electrical Code NEMA National Electrical
Manufacturer's Association NFDS Non-Fused Safety Disconnect
Switch NIC Not In Contract NL Night Light N.O. Normally Open NPF Normal Power Factor NTS Not To Scale OC On Center OH Overhead OL Overloads PA Public Address PB Pull Box Or Pushbutton PE Pneumatic Electric PED Pedestal PF Power Factor PH Phase PIV Post Indicating Valve PNL Panel PP Power Pole PR Pair PRI Primary PROJ Projection PRV Power Roof Ventilator PT Potential Transformer PVC Polyvinyl Chloride (Conduit) PWR Power QUAN Quantity RCPT Receptacle REQD Required RM Room RSC Rigid Steel Conduit RTU Roof Top Unit SC Surface Conduit SEC Secondary SHT Sheet SIM Similar SLD Single-Line Diagram S/N Solid Neutral SPEC Specification SPKR Speaker SP Spare SPP Single-Point Power SR Surface Raceway SS Stainless Steel SSW Selector Switch S/S Stop/Start Pushbuttons STA Station STD Standard SURF Surface Mounted SW Switch SWBD Switchboard SYM Symmetrical SYS System TEL Telephone TERM Terminal TL Twist Lock TR Tamper Resistant T-STAT Thermostat TTC Telephone Terminal Cabinet TV Television TVTC Television Terminal Cabinet TYP Typical UC Under Counter UE Underground Electrical UG Underground UH Unit Heater UT Underground Telephone UTIL Utility UV Ultraviolet V Volt VA Volt-Amperes VDT Video Display Terminal VERT Vertical VFD Variable Frequency Drive VOL Volume W Watt W/ With WG Wire Guard WH Water Heater W/O Without WP Weatherproof XFMR Transformer XFR Transfer
∠ Angle @ At ▲ Delta ' Feet " Inches # Number Ø Phase C Center Line P Plate
Exit Light, Wall-Mounted.
Shading and arrows indicate faces and directional chevrons.
Wall-mounted fixtures, Typical (Various Symbols)
Emergency Lighting Unit, Wall-Mounted, Remote Battery
Emergency Lighting Unit, Wall-Mounted, Integral Battery
Emergency Lighting Unit, Ceiling-Mounted, Integral Battery Emergency Lighting Unit, Ceiling-Mounted, Remote Battery
Lighting Fixtures, Typical, Rectangular (Various Symbols) Filled circles indicate recessed.
Open circles indicate surface-mounted.
Diagonal line indicates lensed.
Outer dots indicate suspended.
Lighting Fixtures, Typical, Round (Various Symbols) Center dot indicates pendant.
Diagonal line indicates lensed.
Chevron indicates wall wash.
Strip Fixture
Directional Light, Track Light, Flood Light
Exit Light, Ceiling-Mounted.
Shading and arrows indicate faces and directional chevrons.
Linear Light, Tape Light
Exit/ELU Combo
Diagonal hatch indicates light on a critical circuit.
Solid hatch indicates light on an emergency or life safety circuit.
Pole/Area Lights
Post-Top Area Light
Bollard Light
Single-Pole Switch Two-Pole Switch Three-Pole Switch Switch Modifiers:
3: 3-Way 4: 4-Way K: Keyed D: Dimming T: Timer
OS: Occupancy Sensor VS: Vacancy Sensor AC: Above-Counter LV: Low-Voltage M: Motor-Rated
Lighting Contactor
Lighting Control Panel
Occupancy Sensor
Daylight Harvesting Sensor
Smoke Detector
Heat Detector
Carbon Monoxide Detector
Beam Detector T: Transmitter R: Receiver
Combination Detector (Up to Three)
Duct Smoke Detector
Manual Pull Station
Horn, Wall
Horn, Ceiling
Strobe, Wall, Candela as indicated
Strobe, Ceiling, Candela as indicated
Horn/Strobe, Wall, Candela as indicated
Horn/Strobe, Ceiling, Candela as indicated
Remote Indicator w/ Test Switch, Wall
Remote Indicate w/ Test Switch, Ceiling
Door Holder
Door Closer
Fire Service Phone
Addressible Module AIM: Addressible Input Module AOM:Addressible Output Control Module AIO: Addressible Input/Output Module
Fire Alarm Control Unit EVAC: Voice Evacuation Control Panel FAA: Fire Alarm Annunciator FACP: Fire Alarm Control Panel FATC: Fire Alarm Terminal Cabinet NACP: Notification Appliance Circuit Panel FAMN: Fire Alarm Mass Notification Control Panel
Supervisory or Interface Device PIV: Post Indicator Valve Supervisory PS: Pressure Switch R: Non-Addressible Relay VS: Valve Supervisory Switch WF: Water Flow Switch
Simplex Receptacle
Duplex Receptacle
Quadruplex Receptacle
Special Receptacle, Type as Indicated
W all
Ce ilin g
Flo or
Receptacle Modifiers:
##": Height AFF OC AC: Above Counter GFI: Ground-Fault Circuit Interrupter WP: Weatherproof In-Use Cover
Half shading indicates split (typically switched) Outside shading indicates emergency circuit Center shading indicates isolated ground
Multioutlet Assembly Filled squares indicate 120V outlet Open squares indicate with USB
Cord Reel, Device Varies
Drop Cord, Device Varies
Junction Box Floor Box, see schedule for type
Emergency Power Off
Door Opener Push Plate
Power Meter Safety Switch, Fused
Safety Switch, Unfused
Motor Starter
Combination Starter/Disconnect
Ground Rod
Ground Rod with Test Well
Lightning Protection Air Terminal
Lightning Protection Conductor Splice
Static Ground Receptacle
Data Outlet
Telephone Outlet
Data/Telephone Outlet
W all
Ce ilin g
Flo or
Outlet Modifiers:
##": Height AFF OC AC: Above Counter
Wireless Access Point
Nurse Call Corridor Light Number of lights as indicated
Nurse Call Device B: Code Blue D: Duty Station E: Emergency P: Patient Call S: Staff
TV Outlet
Nurse Call Control Unit NCAP: Nurse Call Annunciator Panel NCHS: Nurse Call Host Constroller NCPA: Nurse Call Power Supply NCTC: Nurse Call Terminal Cabinet NCUPS: Uninterruptable Power Supply
Lighting Symbols
Contactor
Single-Pole Switch Two-Pole Switch Three-Pole Switch Switch Modifiers:
K: Keyed T: Timer AC: Above-Counter M: Motor-Rated
Fire Alarm Symbols
Grounding and Lightning Protection Symbols
Security Camera PTZ: Pan/Tilt/Zoom
Card Reader
Card Reader with Keypad
Closed Circuit TV Outlet
Door Contact
Electric Strike
Intercom
Magnetic Lock
Request to Exit Button
Request to Exit Sensor
Motion Detector
Security Control Unit SCP: Security Control Panel SPS: Security Power Supply Unit ACP: Access Control Panel WIU: Wiegand Interface Unit PIB: Panel Interface Board IAC: Networked Lock with Integrated
Reader SWKS: Security Workstation MON: Video Monitor ICE: Intercom Exchange
Telecom Symbols
Nurse Call Symbols
Security Symbols a
A A1a
Equipment is tagged with Panel Name and with Panel ID in parentheses. Panel ID is intended as a design documentation aid only. Do not include Panel ID in field-applied circuit directories or labels.
Hatched fill indicates distribution panel or switchboard.
Solid fill indicates branch panel or load center.
Dashed box indicates code-required clearance (width and depth).
Door indicates front of recessed panel.
Panelboards are assigned an abbreviated indicator (or Panel ID) for use with circuit numbers. Panel ID is listed within the panel schedule and in the panel abbreviation schedule.
Power Distribution Equipment
HP
1A
(B
LP
1A
(C
MD
P(
A)
SB1(S)
Devices and fixtures are tagged with Panel ID and circuit number. For example, a device tagged with "A1" indicates the device is circuited to panel designated "A," circuit number 1. The panel schedule circuit number contans both the panel abbreviation and the circuit number.
XX-1
Transformer: Typically transformer names begin with or contain the letter "T". See Single-Line Diagram for description and requirements.
T1
Dashed, arced lines connecting equipment, devices, or fixtures indicate switched power.
Absence of a switch designation on a lighting fixture indicates fixture is controlled by the only switch in the space. An "x" in place of the switch designation indicates unswitched.
Bottom Value, Lowercase Letter: Switch ID
Lighting Tags
Top Value: Fixture Type ID (Underlined)
Bottom Value, Uppercase Letter(s): Panel ID Bottom Value, Number(s): Circuit Number a a
C1a
Wiring
Power Device and Equipment Tags
Construction Phasing
Existing to Remain
Existing to Be Demolished
New
(Typical All Symbols and Equipment)
Existing to Be Demolished
Area Not in Contract
Miscellaneous
Keynote
Callout:
Top Value: Detail Number on Sheet Bottom Value: Sheet Number of Detail
Room Name and Number
Smoke Damper
FILE:
DRAWN BY:
CHECKED BY:
PROJ. NO:
DRAWING NO:
DRAWING TITLE:
PROJECT NAME:
http://www.ZDSDesign.com
135 Corporate Center Drive Suite 532 Scott Depot, WV 25560
TEL 304/755-0075
FAX 304/755-0076
THIS SQUARE APPEARS 1/2"x1/2"
ON FULL SIZE SHEETS
CLIENT:
XXX
C :\U se rs
\e di so n.
ad ki ns \D oc um en ts
\G
SD
2C
_2
4-
-3 0_
BL
D
G
L O
G
AN
_e di so n.
ad ki ns .rv t 8/
/2
:3
1:
P M
55-E-001
EA
TZ3
GSD-252-C
ELECTRICAL TITLE
SHEET
BUILDING 55 SECURITY
SYSTEM UPGRADES
130 STRATTON STREET
LOGAN, WV 25601
WEST VIRGINIA
GENERAL SERVICES
DIVISION
Electrical Sheet List
55-C001 COVER SHEET
55-E-001 ELECTRICAL TITLE SHEET
55-TD-101 DEMO PLAN FIRST FLOOR
55-TD-102 DEMO PLAN SECOND FLOOR
55-TD-103 DEMO PLAN THIRD FLOOR
55-TD-104 DEMO PLAN FOURTH FLOOR
55-TD-105 DEMO PLAN FIFTH FLOOR
55-TD-106 DEMO PLAN PENTHOUSE
55-TY-101 FIRST FLOOR SECURITY PLAN
55-TY-102 SECOND FLOOR SECURITY PLAN
55-TY-103 THIRD FLOOR SECURITY PLAN
55-TY-104 FOURTH FLOOR SECURITY PLAN
55-TY-105 FIFTH FLOOR SECURITY PLAN
55-TY-106 PENTHOUSE SECURITY PLAN
55-TY-501 SECURITY DETAILS
55-TY-502 SECURITY DETAILS
55-TY-601 SECURITY SCHEDULES
NO DATE REVISION
RECEIVING
VESTIBULE
RECEPTION
CONFERENCE
CONFERENCE
STORAGE
STAIR "A"
RECEIVING/RECYCLING
MECH. ROOM
STAIR "B"
CORRIDOR
GENERALSERVICES
OFFICE
TAX RECEPTION
OFFICE
WAITING
ELEVATORLOBBY
I.T.
JAN.CLOS.
M.T.
W.T.
HOSP.AREA
CONFERENCE
CORRIDOR
CORRIDOR
CK
CK
CK
CK
CK
CK
CK
KP
KP KP
KP
KP KP
MD
MD
MD
MD
MD
DCDCDC
DC
DC DC
DC
DC
DC
DC
DC
DC
DC
DCDCDCDC
DC
HS
HS
SC
P
CK
CK
HS
IC
M
ICM
DR
IC CK
IC CK ICCK
CK
CK
KP
AC
P
PS
IC
E
PS
PS
SWKS
HS
Aiphone AX-084C
2 - PS-2420UL
Network switch for security in this room credentialing workstation and camera monitor
1 3
FILE:
DRAWN BY:
CHECKED BY:
PROJ. NO:
DRAWING NO:
DRAWING TITLE:
PROJECT NAME:
http://www.ZDSDesign.com
135 Corporate Center Drive Suite 532 Scott Depot, WV 25560
TEL 304/755-0075
FAX 304/755-0076
THIS SQUARE APPEARS 1/2"x1/2"
ON FULL SIZE SHEETS
CLIENT:
XXX
C :\U se rs
\e di so n.
ad ki ns \D oc um en ts
\G
SD
2C
_2
4-
-3 0_
BL
D
G
L O
G
AN
_e di so n.
ad ki ns .rv t 8/
/2
:3
1:
P M
55-TD-101
EA
TZ3
GSD-252-C
DEMO PLAN FIRST
FLOOR
BUILDING 55 SECURITY
SYSTEM UPGRADES
130 STRATTON STREET
LOGAN, WV 25601
WEST VIRGINIA
GENERAL SERVICES
DIVISION
# KEYNOTES
1 INTERCOM AND CARD READER FOR VEHICLE GATE
2 INTERCOM AND CARD READER FOR PEDESTRIAN GATE
3 RELOCATE INTERCOM AND CARD READER TO CORRECT SIDE OF GATE FOR
OPERATION BY VEHICLE DRIVER.
1/8" = 1'-0"55-TD-101
1 Demo Security Plan-First Floor
SYSTEMS DEMOLITION NOTES
1 DISCONNECT AND REMOVE ONLY SYSTEM DEVICES SHOWN TO BE DEMOLISHED.
2 DISCONNECT AND REMOVE ASSOCIATED CONDUIT AND WIRE BACK TO LAST
REMAINING DEVICE. FURNISH AND INSTALL CONDUIT AND WIRE AS NECESSARY
FOR CONTINUITY OF CIRCUIT(S) TO ANY EXISTING DEVICES TO REMAIN.
COORDINATE AND VERIFY REQUIREMENTS WITH NEW WORK IN AREA.
3 FURNISH AND INSTALL CONDUIT AND/OR SYSTEMS WIRING AS NECESSARY FOR
CONTINUITY OF ANY SYSTEMS EQUIPMENT OR DEVICES TO REMAIN. MODIFY OR
REPLACE AS REQUIRED.
4 FURNISH AND INSTALL BLANK COVER PLATES FOR ALL EXISTING UNUSED
OPENINGS.
5 BUILDINGS THAT HAVE CAMERAS THAT WORK OR WOULD WORK IF THE
SOFTWARE AND LICENSES WERE CURRENT SHOULD HAVE NEW NVRS INSTALLED
AND THE EXISTING CAMERAS CONNECTED TO THEM. AS NEW CAMERAS ARE
INSTALLED, REMOVE OLD CAMERAS FROM THE SYSTEM.
6 THE EXISTING ACCESS CONTROL SYSTEM IS TO REMAIN IN USE UNTIL THE NEW
SYSTEM IS COMPLETE. DOORS SHOULD BE MIGRATED TO THE NEW SYSTEM ONE
AT A TIME UNTIL ALL ARE ON THE NEW SYSTEM. DURING THIS MIGRATION, NO
DOOR IS TO REMAIN UNSECURED OR INOPERABLE AT THE END OF A WORKDAY.
216 217
231A
228229
217A
CONFERENCE
WORK FORCE WAITING
CONFERENCE
OFFICE
OFFICE
RECEPTION
HOSP.AREA
WORK FORCE OPEN OFFICE
COPY
OFFICE
OFFICE
OFFICE
STAIR "A"
STORAGE INSURANCE COMMISSION
MECH. ROOM
STAIR "B"
CORRIDOR
HOSP.AREA
RECEPT.
REHAB SERV.WAITING
CORR.
CONFERENCE
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
OFFICEOFFICE
OFFICE
COPY/FILES
OFFICE
I.T.
J.C.
W.T.
M.T.
W.T.
M.T.
CORRIDOR
ELEV.LOBBY
FILE STORAGE
EVIDENCE
CK
CK
MD
MD
MD
HS
CK
CK
ES
DR
CK
ES
CK
CK
CK
CK
ES
CK
AC
P
PS
EL 1
FILE:
DRAWN BY:
CHECKED BY:
PROJ. NO:
DRAWING NO:
DRAWING TITLE:
PROJECT NAME:
http://www.ZDSDesign.com
135 Corporate Center Drive Suite 532 Scott Depot, WV 25560
TEL 304/755-0075
FAX 304/755-0076
THIS SQUARE APPEARS 1/2"x1/2"
ON FULL SIZE SHEETS
CLIENT:
XXX
C :\U se rs
\e di so n.
ad ki ns \D oc um en ts
\G
SD
2C
_2
4-
-3 0_
BL
D
G
L O
G
AN
_e di so n.
ad ki ns .rv t 8/
/2
:3
1:
P M
55-TD-102
EA
TZ3
GSD-252-C
DEMO PLAN SECOND
FLOOR
BUILDING 55 SECURITY
SYSTEM UPGRADES
130 STRATTON STREET
LOGAN, WV 25601
WEST VIRGINIA
GENERAL SERVICES
DIVISION
# KEYNOTES
1 REPLACE WITH NEW LOCK
1/8" = 1'-0"55-TD-102
1 Demo Security Plan-Second Floor
SYSTEMS DEMOLITION NOTES
1 DISCONNECT AND REMOVE ONLY SYSTEM DEVICES SHOWN TO BE DEMOLISHED.
2 DISCONNECT AND REMOVE ASSOCIATED CONDUIT AND WIRE BACK TO LAST
REMAINING DEVICE. FURNISH AND INSTALL CONDUIT AND WIRE AS NECESSARY
FOR CONTINUITY OF CIRCUIT(S) TO ANY EXISTING DEVICES TO REMAIN.
COORDINATE AND VERIFY REQUIREMENTS WITH NEW WORK IN AREA.
3 FURNISH AND INSTALL CONDUIT AND/OR SYSTEMS WIRING AS NECESSARY FOR
CONTINUITY OF ANY SYSTEMS EQUIPMENT OR DEVICES TO REMAIN. MODIFY OR
REPLACE AS REQUIRED.
4 FURNISH AND INSTALL BLANK COVER PLATES FOR ALL EXISTING UNUSED
OPENINGS.
5 BUILDINGS THAT HAVE CAMERAS THAT WORK OR WOULD WORK IF THE
SOFTWARE AND LICENSES WERE CURRENT SHOULD HAVE NEW NVRS INSTALLED
AND THE EXISTING CAMERAS CONNECTED TO THEM. AS NEW CAMERAS ARE
INSTALLED, REMOVE OLD CAMERAS FROM THE SYSTEM.
6 THE EXISTING ACCESS CONTROL SYSTEM IS TO REMAIN IN USE UNTIL THE NEW
SYSTEM IS COMPLETE. DOORS SHOULD BE MIGRATED TO THE NEW SYSTEM ONE
AT A TIME UNTIL ALL ARE ON THE NEW SYSTEM. DURING THIS MIGRATION, NO
304 303
305 306
308 307
311 310
312 313
315 314
301A 334
VISITATION
DHHR WAITING
CORRIDOR
INTERVIEW INTERVIEW(ADA)
INTERVIEW INTERVIEW(ADA)
INTERVIEW INTERVIEW
INTERVIEW INTERVIEW
INTERVIEW INTERVIEW
INTERVIEW INTERVIEW
OFFICE
SM.COPY
STAIR "A"
FILING
MECH. ROOM
CORRIDOR
STAIR "B"
OFFICE
HOSP.AREA
OFFICE
OFFICE
COPY/MAIL
M.D.T.
VIDEO
CORR. TOIL.
DHHR OPEN PLAN
W.T.
W.T.
M.T.
I.T.
J.C.
M.T.
ELEV.LOBBY
STOR.
RECEPTION
STOR.
OFFICE
CK
CK
CK
CK
DC DC
MD
MD
DR
PB
PB
PB PB
PB
PB
PB PB
PB PB
PB PB
MD
HS
HS
IAC
CK
IAC
CK
ES
ES
CK
IAC
AC
P
PS
PS
1 1
FILE:
DRAWN BY:
CHECKED BY:
PROJ. NO:
DRAWING NO:
DRAWING TITLE:
PROJECT NAME:
http://www.ZDSDesign.com
135 Corporate Center Drive Suite 532 Scott Depot, WV 25560
TEL 304/755-0075
FAX 304/755-0076
THIS SQUARE APPEARS 1/2"x1/2"
ON FULL SIZE SHEETS
CLIENT:
XXX
C :\U se rs
\e di so n.
ad ki ns \D oc um en ts
\G
SD
2C
_2
4-
-3 0_
BL
D
G
L O
G
AN
_e di so n.
ad ki ns .rv t 8/
/2
:3
1:
P M
55-TD-103
EA
TZ3
GSD-252-C
DEMO PLAN THIRD
FLOOR
BUILDING 55 SECURITY
SYSTEM UPGRADES
130 STRATTON STREET
LOGAN, WV 25601
WEST VIRGINIA
GENERAL SERVICES
DIVISION
# KEYNOTES
1 REMOVE AND TURN OVER TO DOHS.
1/8" = 1'-0"55-TD-103
1 Demo Security Plan-Third Floor
SYSTEMS DEMOLITION NOTES
1 DISCONNECT AND REMOVE ONLY SYSTEM DEVICES SHOWN TO BE DEMOLISHED.
2 DISCONNECT AND REMOVE ASSOCIATED CONDUIT AND WIRE BACK TO LAST
REMAINING DEVICE. FURNISH AND INSTALL CONDUIT AND WIRE AS NECESSARY
FOR CONTINUITY OF CIRCUIT(S) TO ANY EXISTING DEVICES TO REMAIN.
COORDINATE AND VERIFY REQUIREMENTS WITH NEW WORK IN AREA.
3 FURNISH AND INSTALL CONDUIT AND/OR SYSTEMS WIRING AS NECESSARY FOR
CONTINUITY OF ANY SYSTEMS EQUIPMENT OR DEVICES TO REMAIN. MODIFY OR
REPLACE AS REQUIRED.
4 FURNISH AND INSTALL BLANK COVER PLATES FOR ALL EXISTING UNUSED
OPENINGS.
5 BUILDINGS THAT HAVE CAMERAS THAT WORK OR WOULD WORK IF THE
SOFTWARE AND LICENSES WERE CURRENT SHOULD HAVE NEW NVRS INSTALLED
AND THE EXISTING CAMERAS CONNECTED TO THEM. AS NEW CAMERAS ARE
INSTALLED, REMOVE OLD CAMERAS FROM THE SYSTEM.
6 THE EXISTING ACCESS CONTROL SYSTEM IS TO REMAIN IN USE UNTIL THE NEW
SYSTEM IS COMPLETE. DOORS SHOULD BE MIGRATED TO THE NEW SYSTEM ONE
AT A TIME UNTIL ALL ARE ON THE NEW SYSTEM. DURING THIS MIGRATION, NO
406407
419420
422 416
BREAK ROOM
HOSP.AREA
DHHR OPENOFFICE PLAN
OFFICE
OFFICE
OFFICE
OFFICEOFFICE
STAIR "A"
UNDESIGNATED
GEN. SERVICES
MECH. ROOM
STAIR "B"
OFFICE
OFFICE
OFFICE
OFFICE
OFFICECOPY/STOR.
W.T.
W.T.
M.T.
M.T. HOSP.AREA
J.C.
I.T.
CORRIDOR
ELEV.LOBBY
HS
HS
CK
CK
CK
CK
CK
DC DC
DC DC
MD
MD
MD
AC
P
CK
CK
ES
SWKS
PS
ES005
FILE:
DRAWN BY:
CHECKED BY:
PROJ. NO:
DRAWING NO:
DRAWING TITLE:
PROJECT NAME:
http://www.ZDSDesign.com
135 Corporate Center Drive Suite 532 Scott Depot, WV 25560
TEL 304/755-0075
FAX 304/755-0076
THIS SQUARE APPEARS 1/2"x1/2"
ON FULL SIZE SHEETS
CLIENT:
XXX
C :\U se rs
\e di so n.
ad ki ns \D oc um en ts
\G
SD
2C
_2
4-
-3 0_
BL
D
G
L O
G
AN
_e di so n.
ad ki ns .rv t 8/
/2
:3
1:
P M
55-TD-104
EA
TZ3
GSD-252-C
DEMO PLAN FOURTH
FLOOR
BUILDING 55 SECURITY
SYSTEM UPGRADES
130 STRATTON STREET
LOGAN, WV 25601
WEST VIRGINIA
GENERAL SERVICES
DIVISION
# KEYNOTES
1/8" = 1'-0"55-TD-104
1 Demo Security Plan-Fourth Floor
SYSTEMS DEMOLITION NOTES
1 DISCONNECT AND REMOVE ONLY SYSTEM DEVICES SHOWN TO BE DEMOLISHED.
2 DISCONNECT AND REMOVE ASSOCIATED CONDUIT AND WIRE BACK TO LAST
REMAINING DEVICE. FURNISH AND INSTALL CONDUIT AND WIRE AS NECESSARY
FOR CONTINUITY OF CIRCUIT(S) TO ANY EXISTING DEVICES TO REMAIN.
COORDINATE AND VERIFY REQUIREMENTS WITH NEW WORK IN AREA.
3 FURNISH AND INSTALL CONDUIT AND/OR SYSTEMS WIRING AS NECESSARY FOR
CONTINUITY OF ANY SYSTEMS EQUIPMENT OR DEVICES TO REMAIN. MODIFY OR
REPLACE AS REQUIRED.
4 FURNISH AND INSTALL BLANK COVER PLATES FOR ALL EXISTING UNUSED
OPENINGS.
5 BUILDINGS THAT HAVE CAMERAS THAT WORK OR WOULD WORK IF THE
SOFTWARE AND LICENSES WERE CURRENT SHOULD HAVE NEW NVRS INSTALLED
AND THE EXISTING CAMERAS CONNECTED TO THEM. AS NEW CAMERAS ARE
INSTALLED, REMOVE OLD CAMERAS FROM THE SYSTEM.
6 THE EXISTING ACCESS CONTROL SYSTEM IS TO REMAIN IN USE UNTIL THE NEW
SYSTEM IS COMPLETE. DOORS SHOULD BE MIGRATED TO THE NEW SYSTEM ONE
AT A TIME UNTIL ALL ARE ON THE NEW SYSTEM. DURING THIS MIGRATION, NO
516517
UNDESIGNATED
DEPT.DIRECTOR
OFFICE
CONFERENCE
UNDESIGNATED
STAIR "A"
STAIR "C"
MECH.ROOM
STAIR "B"
HOSP.AREA
CORRIDOR
DHHR OPENOFFICE PLAN
OFFICE
OFFICE
OFFICECOPY/STOR.
CORRIDOR
M.T.
M.T.
W.T.
W.T.
I.T.
J.C.
CORRIDOR
ELEV.LOBBY
A B E F
C D
2.2
A.1 A.7
2.3
2.7
E.9E.3
2.1
2.5
THE COLUMN SIZES HAVE BEEN CHANGED TO MATCH THE 90% REVIEW SET
HS
CK
CK
CK
CK
CK
CK
DC DC
DC DC
MD
MD
MD
CK
ES
CK
AC
P
PS
CK
FILE:
DRAWN BY:
CHECKED BY:
PROJ. NO:
DRAWING NO:
DRAWING TITLE:
PROJECT NAME:
http://www.ZDSDesign.com
135 Corporate Center Drive Suite 532 Scott Depot, WV 25560
TEL 304/755-0075
FAX 304/755-0076
THIS SQUARE APPEARS 1/2"x1/2"
ON FULL SIZE SHEETS
CLIENT:
XXX
C :\U se rs
\e di so n.
ad ki ns \D oc um en ts
\G
SD
2C
_2
4-
-3 0_
BL
D
G
L O
G
AN
_e di so n.
ad ki ns .rv t 8/
/2
:3
1:
P M
55-TD-105
EA
TZ3
GSD-252-C
DEMO PLAN FIFTH
FLOOR
BUILDING 55 SECURITY
SYSTEM UPGRADES
130 STRATTON STREET
LOGAN, WV 25601
WEST VIRGINIA
GENERAL SERVICES
DIVISION
# KEYNOTES
1/8" = 1'-0"55-TD-105
1 Demo Security Plan-Fifth Floor
SYSTEMS DEMOLITION NOTES
1 DISCONNECT AND REMOVE ONLY SYSTEM DEVICES SHOWN TO BE DEMOLISHED.
2 DISCONNECT AND REMOVE ASSOCIATED CONDUIT AND WIRE BACK TO LAST
REMAINING DEVICE. FURNISH AND INSTALL CONDUIT AND WIRE AS NECESSARY
FOR CONTINUITY OF CIRCUIT(S) TO ANY EXISTING DEVICES TO REMAIN.
COORDINATE AND VERIFY REQUIREMENTS WITH NEW WORK IN AREA.
3 FURNISH AND INSTALL CONDUIT AND/OR SYSTEMS WIRING AS NECESSARY FOR
CONTINUITY OF ANY SYSTEMS EQUIPMENT OR DEVICES TO REMAIN. MODIFY OR
REPLACE AS REQUIRED.
4 FURNISH AND INSTALL BLANK COVER PLATES FOR ALL EXISTING UNUSED
OPENINGS.
5 BUILDINGS THAT HAVE CAMERAS THAT WORK OR WOULD WORK IF THE
SOFTWARE AND LICENSES WERE CURRENT SHOULD HAVE NEW NVRS INSTALLED
AND THE EXISTING CAMERAS CONNECTED TO THEM. AS NEW CAMERAS ARE
INSTALLED, REMOVE OLD CAMERAS FROM THE SYSTEM.
6 THE EXISTING ACCESS CONTROL SYSTEM IS TO REMAIN IN USE UNTIL THE NEW
SYSTEM IS COMPLETE. DOORS SHOULD BE MIGRATED TO THE NEW SYSTEM ONE
AT A TIME UNTIL ALL ARE ON THE NEW SYSTEM. DURING THIS MIGRATION, NO
P01
P02
P03
MECHANICAL EQUIP.
ELEV.MACH.
STAIR "C"
A B E F
C D
2.2
A.1 A.7
2.3
2.7
E.9E.3
2.1
2.5
THE COLUMN SIZES HAVE BEEN CHANGED TO MATCH THE 90% REVIEW SET
DC
CK
AC
P
PS
SF-1
STAIR PRESSURIZATION FAN
SF-1
STAIR PRESSURIZATION FAN
FILE:
DRAWN BY:
CHECKED BY:
PROJ. NO:
DRAWING NO:
DRAWING TITLE:
PROJECT NAME:
http://www.ZDSDesign.com
135 Corporate Center Drive Suite 532 Scott Depot, WV 25560
TEL 304/755-0075
FAX 304/755-0076
THIS SQUARE APPEARS 1/2"x1/2"
ON FULL SIZE SHEETS
CLIENT:
XXX
C :\U se rs
\e di so n.
ad ki ns \D oc um en ts
\G
SD
2C
_2
4-
-3 0_
BL
D
G
L O
G
AN
_e di so n.
ad ki ns .rv t 8/
/2
:3
1:
P M
55-TD-106
EA
TZ3
GSD-252-C
DEMO PLAN
PENTHOUSE
BUILDING 55 SECURITY
SYSTEM UPGRADES
130 STRATTON STREET
LOGAN, WV 25601
WEST VIRGINIA
GENERAL SERVICES
DIVISION
# KEYNOTES
1/8" = 1'-0"55-TD-106
1 Demo Security Plan-Penthouse
SYSTEMS DEMOLITION NOTES
1 DISCONNECT AND REMOVE ONLY SYSTEM DEVICES SHOWN TO BE DEMOLISHED.
2 DISCONNECT AND REMOVE ASSOCIATED CONDUIT AND WIRE BACK TO LAST
REMAINING DEVICE. FURNISH AND INSTALL CONDUIT AND WIRE AS NECESSARY
FOR CONTINUITY OF CIRCUIT(S) TO ANY EXISTING DEVICES TO REMAIN.
COORDINATE AND VERIFY REQUIREMENTS WITH NEW WORK IN AREA.
3 FURNISH AND INSTALL CONDUIT AND/OR SYSTEMS WIRING AS NECESSARY FOR
CONTINUITY OF ANY SYSTEMS EQUIPMENT OR DEVICES TO REMAIN. MODIFY OR
REPLACE AS REQUIRED.
4 FURNISH AND INSTALL BLANK COVER PLATES FOR ALL EXISTING UNUSED
OPENINGS.
5 BUILDINGS THAT HAVE CAMERAS THAT WORK OR WOULD WORK IF THE
SOFTWARE AND LICENSES WERE CURRENT SHOULD HAVE NEW NVRS INSTALLED
AND THE EXISTING CAMERAS CONNECTED TO THEM. AS NEW CAMERAS ARE
INSTALLED, REMOVE OLD CAMERAS FROM THE SYSTEM.
6 THE EXISTING ACCESS CONTROL SYSTEM IS TO REMAIN IN USE UNTIL THE NEW
SYSTEM IS COMPLETE. DOORS SHOULD BE MIGRATED TO THE NEW SYSTEM ONE
AT A TIME UNTIL ALL ARE ON THE NEW SYSTEM. DURING THIS MIGRATION, NO
RECEIVING
VESTIBULE
RECEPTION
CONFERENCE
CONFERENCE
STORAGE
STAIR "A"
RECEIVING/RECYCLING
MECH. ROOM
STAIR "B"
CORRIDOR
GENERALSERVICES
OFFICE
TAX RECEPTION
OFFICE
WAITING
ELEVATORLOBBY
I.T.
JAN.CLOS.
M.T.
W.T.
HOSP.AREA
CONFERENCE
CORRIDOR
CORRIDOR
KP
KP KP
KP KP
MD
MD
MD
MD
MD
HS
HS
SC
P
HS
IC
M
ICM
IC
IC IC
KP
IC
E
HS
CR
CR
CR
CR
CR
CR
CR
CR
CR
CR
CR
AC
P
CR
CR
CR
DC
DC
DC
DC
DC DC DC DC
DC
DC
DC
DC
DCDCDC
DC DC
SW
KS
MO
N
MO
N
DR
DC DC
DC
MO
N
KP
SCP
CWKS
Aiphone AX-084C
2 - PS-2420UL
Existing Network switch for security in this room
C001
TYPE J
C004
TYPE J
C015
TYPE L
C003
TYPE J
C002
TYPE K
C006
TYPE A
C007
TYPE A
C010
TYPE A
C009
TYPE C
C008
TYPE C
C013
TYPE A
C011
TYPE A
C012
TYPE A
C005
TYPE J
DC013
DC012 DC011 DC010 DC009 DC008
DC006
DC005
DC021
DC019 DC020
DC014
DC016
DC015
DC018
DC017
DC001 DC002 DC003 DC004
CR001
CR014
CR012
CR013CR010
CR009
CR006
CR005
CR003
CR004 CR015
CR002
CR008
CR007
M001
M002SWKS01
DR001
ACP001
IC001
IC002
IC004
IC003
IC005
IC006
6 8
SNR001
M003
CWKS01
FILE:
DRAWN BY:
CHECKED BY:
PROJ. NO:
DRAWING NO:
DRAWING TITLE:
PROJECT NAME:
http://www.ZDSDesign.com
135 Corporate Center Drive Suite 532 Scott Depot, WV 25560
TEL 304/755-0075
FAX 304/755-0076
THIS SQUARE APPEARS 1/2"x1/2"
ON FULL SIZE SHEETS
CLIENT:
XXX
C :\U se rs
\e di so n.
ad ki ns \D oc um en ts
\G
SD
2C
_2
4-
-3 0_
BL
D
G
L O
G
AN
_e di so n.
ad ki ns .rv t 8/
/2
:3
1:
P M
55-TY-101
EA
TZ3
GSD-252-C
FIRST FLOOR SECURITY
PLAN
BUILDING 55 SECURITY
SYSTEM UPGRADES
130 STRATTON STREET
LOGAN, WV 25601
WEST VIRGINIA
GENERAL SERVICES
DIVISION
1/8" = 1'-0"55-TY-101
1 Security Plan-First Floor
KEYNOTES
1 EXISTING FIRE ALARM RELAY TO UNLOCK DOOR IN EVENT OF FIRE ALARM. RETAIN
AND RECONNECT TO NEW ACCESS CONTROL SYSTEM.
2 EXISTING ELECTRIFIED HARDWARE AND MAGLOCKS WITH DELAYED EGRESS TO
REMAIN. VERIFY FUNCTIONALITY WITH OWNER AND RETAIN.
3 EXISTING ELECTRIFIED HARDWARE WITH SCHEDULED LOCKING (UNLOCKED
DURING NORMAL BUSINESS HOURS) AND REMOTE RELEASE TO REMAIN. PROVIDE
NEW DOOR RELEASE BUTTON. VERIFY LOCK SCHEDULE WITH OWNER.
4 EXISTING ELECTRIFIED HARDWARE WITH REMOTE RELEASE TO REMAIN. PROVIDE
NEW DOOR RELEASE BUTTON.
5 PROVIDE TWO 120V, 20A CIRCUITS FOR NEW SECURITY NETWORK RACK. CIRCUIT
TO NEAREST ELECTRICAL PANEL.
6 INTERCOM AND CARD READER FOR VEHICLE GATE
7 INTERCOM AND CARD READER FOR PEDESTRIAN GATE
8 RELOCATE INTERCOM AND CARD READER TO CORRECT SIDE OF GATE FOR
OPERATION BY VEHICLE DRIVER.
9 4 BUTTON DOOR RELEASE PANEL
10 SECURITY WORKSTATION WITH QTY 3 - 34" CURVED MONITORS
11 KEYPAD FOR NEW PANIC ALARM SYSTEM
12 NEW INTRUSION DETECTION/PANIC ALARM CONTROL PANEL
13 NEW SECURITY NETWORK RACK. PROVIDE 12 STRAND MM OM4 ARMOURED FIBER
TO SNR002. TERMINATE FIBER IN FIBER TERMINATION PANEL AT BOTH ENDS. SEE
SPECIFICATIONS AND DETAIL 1 ON SHEET 55-TY-501.
14 NEW CREDENTIALLING WORKSTATION. COORDINATE EXACT LOCATION WITH
OWNER.
SECURITY SYSTEM SHEET NOTES
A SEE DETAIL SHEET FOR SECURITY CAMERA MOUNTING
B SEE SECURITY DEVICE SCHEDULE FOR ADDITIONAL INFORMATION
C ALL COMMUNICATION CABLES SHALL BE INSTALLED IN CONDUIT, CABLE TRAY, OR
SUPPORTED BY CABLE HOOKS. PROVIDE BUSHINGS AT THE ENDS OF ALL
CONDUITS WHERE STUBBED ABOVE ACCESSIBLE CEILINGS OR WHERE DROPPED
INTO CABLE TRAYS. PROVIDE CABLE HOOKS ABOVE ACCESSIBLE CEILINGS FOR
CABLE INSTALLATION WHERE NOT INSTALLED IN A CONDUIT OR CABLE TRAY.
D BUILDINGS THAT HAVE CAMERAS THAT WORK OR WOULD WORK IF THE
SOFTWARE AND LICENSES WERE CURRENT SHOULD HAVE NEW NVRS INSTALLED
AND THE EXISTING CAMERAS CONNECTED TO THEM. AS NEW CAMERAS ARE
INSTALLED, REMOVE OLD CAMERAS FROM THE SYSTEM.
E ALL CABLES AND DEVICES TO BE LABELED. SEE SPECIFICATION AND DETAILS
FOR SPECIFIC REQUIREMENTS.
F THE EXISTING ACCESS CONTROL SYSTEM IS TO REMAIN IN USE UNTIL THE NEW
SYSTEM IS COMPLETE. DOORS SHOULD BE MIGRATED TO THE NEW SYSTEM ONE
AT A TIME UNTIL ALL ARE ON THE NEW SYSTEM. DURING THIS MIGRATION, NO
DOOR IS TO REMAIN UNSECURED OR INOPERABLE AT THE END OF A WORKDAY.
G PROVIDE SURGE PROTECTION FOR ALL EXTERIOR CAMERAS.
216 217
231A
228229
217A
CONFERENCE
WORK FORCE WAITING
CONFERENCE
OFFICE
OFFICE
RECEPTION
HOSP.AREA
WORK FORCE OPEN OFFICE
COPY
OFFICE
OFFICE
OFFICE
STAIR "A"
STORAGE INSURANCE COMMISSION
MECH. ROOM
STAIR "B"
CORRIDOR
HOSP.AREA
RECEPT.
REHAB SERV.WAITING
CORR.
CONFERENCE
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
OFFICEOFFICE
OFFICE
COPY/FILES
OFFICE
I.T.
J.C.
W.T.
M.T.
W.T.
M.T.
CORRIDOR
ELEV.LOBBY
FILE STORAGE
EVIDENCE
MD
MD
MD
HS
ES
ES
ES
CR
CR
CR
CR
CR
CR
CR
CR
CR
EL
AC
P
DR
CR
CR
EL EL
DC DC
DCDC
C019
TYPE A
C020
TYPE A
C023
TYPE C
C021
TYPE A
C022
TYPE C
CR016
CR017
CR020
CR021
CR022
CR019
CR018
CR023
CR024
DR002
ACP002
EL001
REPLACE
EXISTING
CR049
ES002
ES001
ES006
SNR002
CR050
EL004
NEW
EL005
NEW
DC037 DC038
DC035
DC036
FILE:
DRAWN BY:
CHECKED BY:
PROJ. NO:
DRAWING NO:
DRAWING TITLE:
PROJECT NAME:
http://www.ZDSDesign.com
135 Corporate Center Drive Suite 532 Scott Depot, WV 25560
TEL 304/755-0075
FAX 304/755-0076
THIS SQUARE APPEARS 1/2"x1/2"
ON FULL SIZE SHEETS
CLIENT:
XXX
C :\U se rs
\e di so n.
ad ki ns \D oc um en ts
\G
SD
2C
_2
4-
-3 0_
BL
D
G
L O
G
AN
_e di so n.
ad ki ns .rv t 8/
/2
:3
1:
P M
55-TY-102
EA
TZ3
GSD-252-C
SECOND FLOOR
SECURITY PLAN
BUILDING 55 SECURITY
SYSTEM UPGRADES
130 STRATTON STREET
LOGAN, WV 25601
WEST VIRGINIA
GENERAL SERVICES
DIVISION
1/8" = 1'-0"55-TY-102
1 Security Plan-Second Floor
KEYNOTES
1 EXISTING FIRE ALARM RELAY TO UNLOCK DOOR IN EVENT OF FIRE ALARM. RETAIN
AND RECONNECT TO NEW ACCESS CONTROL SYSTEM.
2 EXISTING ELECTRIFIED HARDWARE AND MAGLOCKS WITH DELAYED EGRESS TO
REMAIN. VERIFY FUNCTIONALITY WITH OWNER AND RETAIN.
3 REPLACE WITH NEW ELECTRIFIED LOCK. MATCH EXISTING.
4 NEW ELECTRIFIED HARDWARE WITH SCHEDULED LOCKING (UNLOCKED DURING
NORMAL BUSINESS HOURS). FURNISH HARDWARE TO MATCH EXISTING.
CONTRACTOR TO FIELD VERIFY EXACT HARDWARE REQUIREMENTS.
COORDINATE LOCK SCHEDULE WITH OWNER.
5 EXISTING ELECTRIFIED HARDWARE WITH REMOTE RELEASE TO REMAIN. PROVIDE
NEW DOOR RELEASE BUTTON.
6 NEW SECURITY NETWORK RACK. PROVIDE 12 STRAND MM OM4 ARMOURED FIBER
TO SNR001 AND SNR003. TERMINATE FIBER IN FIBER TERMINATION PANEL AT
BOTH ENDS. SEE SPECIFICATIONS AND DETAIL 1 ON SHEET 55-TY-501.
7 EXISTING ELECTRIFIED HARDWARE WITH SCHEDULED LOCKING (UNLOCKED
DURING NORMAL BUSINESS HOURS). TO REMAIN. VERIFY LOCK SCHEDULE WITH
OWNER.
8 PROVIDE TWO 120V, 20A CIRCUITS FOR NEW SECURITY NETWORK RACK. CIRCUIT
TO NEAREST ELECTRICAL PANEL.
SECURITY SYSTEM SHEET NOTES
A SEE DETAIL SHEET FOR SECURITY CAMERA MOUNTING
B SEE SECURITY DEVICE SCHEDULE FOR ADDITIONAL INFORMATION
C ALL COMMUNICATION CABLES SHALL BE INSTALLED IN CONDUIT, CABLE TRAY, OR
SUPPORTED BY CABLE HOOKS. PROVIDE BUSHINGS AT THE ENDS OF ALL
CONDUITS WHERE STUBBED ABOVE ACCESSIBLE CEILINGS OR WHERE DROPPED
INTO CABLE TRAYS. PROVIDE CABLE HOOKS ABOVE ACCESSIBLE CEILINGS FOR
CABLE INSTALLATION WHERE NOT INSTALLED IN A CONDUIT OR CABLE TRAY.
D BUILDINGS THAT HAVE CAMERAS THAT WORK OR WOULD WORK IF THE
SOFTWARE AND LICENSES WERE CURRENT SHOULD HAVE NEW NVRS INSTALLED
AND THE EXISTING CAMERAS CONNECTED TO THEM. AS NEW CAMERAS ARE
INSTALLED, REMOVE OLD CAMERAS FROM THE SYSTEM.
E ALL CABLES AND DEVICES TO BE LABELED. SEE SPECIFICATION AND DETAILS
FOR SPECIFIC REQUIREMENTS.
F THE EXISTING ACCESS CONTROL SYSTEM IS TO REMAIN IN USE UNTIL THE NEW
SYSTEM IS COMPLETE. DOORS SHOULD BE MIGRATED TO THE NEW SYSTEM ONE
AT A TIME UNTIL ALL ARE ON THE NEW SYSTEM. DURING THIS MIGRATION, NO
DOOR IS TO REMAIN UNSECURED OR INOPERABLE AT THE END OF A WORKDAY.
304 303
305 306
308 307
311 310
312 313
315 314
301A 334
VISITATION
DHHR WAITING
CORRIDOR
INTERVIEW INTERVIEW(ADA)
INTERVIEW INTERVIEW(ADA)
INTERVIEW INTERVIEW
INTERVIEW INTERVIEW
INTERVIEW INTERVIEW
INTERVIEW INTERVIEW
OFFICE
SM.COPY
STAIR "A"
FILING
MECH. ROOM
CORRIDOR
STAIR "B"
OFFICE
HOSP.AREA
OFFICE
OFFICE
COPY/MAIL
M.D.T.
VIDEO
CORR. TOIL.
DHHR OPEN PLAN
W.T.
W.T.
M.T.
I.T.
J.C.
M.T.
ELEV.LOBBY
STOR.
RECEPTION
STOR.
OFFICE
MD
MD
MD
HS
HS
IAC
IAC
ES
ES
IAC
CR
CR
CR
CR
CR
CR
CR
DC DC
DC DC
AC
P
EL EL
DR
PB PB
PB PB
PB PB
PB
PB
PB PB
PB
PB
PB
PB
PB
PB
SWR
C024
TYPE A
C025
TYPE A
C026
TYPE A
C027
TYPE A
C029
TYPE A
C028
TYPE C
CR025
CR026
CR027
CR028
CR029
CR030
CR031
EL002
NEW
EL003
NEW
DC024 DC025
ACP003
DC022
DC023
DR003
IAC003
IAC001
IAC002
SNR003
C039
TYPE C
C040
TYPE C
C041
TYPE A
C042
TYPE A
PB001
PB002
PB003 PB004
PB006PB005
PB007 PB008
PB009 PB010
PB011 PB012
PB013
PB016
PB015PB014
FILE:
DRAWN BY:
CHECKED BY:
PROJ. NO:
DRAWING NO:
DRAWING TITLE:
PROJECT NAME:
http://www.ZDSDesign.com
135 Corporate Center Drive Suite 532 Scott Depot, WV 25560
TEL 304/755-0075
FAX 304/755-0076
THIS SQUARE APPEARS 1/2"x1/2"
ON FULL SIZE SHEETS
CLIENT:
XXX
C :\U se rs
\e di so n.
ad ki ns \D oc um en ts
\G
SD
2C
_2
4-
-3 0_
BL
D
G
L O
G
AN
_e di so n.
ad ki ns .rv t 8/
/2
:3
1:
P M
55-TY-103
EA
TZ3
GSD-252-C
THIRD FLOOR SECURITY
PLAN
BUILDING 55 SECURITY
SYSTEM UPGRADES
130 STRATTON STREET
LOGAN, WV 25601
WEST VIRGINIA
GENERAL SERVICES
DIVISION
1/8" = 1'-0"55-TY-103
1 Security Plan-Third Floor
KEYNOTES
1 EXISTING FIRE ALARM RELAY TO UNLOCK DOOR IN EVENT OF FIRE ALARM. RETAIN
AND RECONNECT TO NEW ACCESS CONTROL SYSTEM.
2 EXISTING ELECTRIFIED HARDWARE AND MAGLOCKS WITH DELAYED EGRESS TO
REMAIN. VERIFY FUNCTIONALITY WITH OWNER AND RETAIN.
3 NEW ELECTRIFIED HARDWARE WITH SCHEDULED LOCKING (UNLOCKED DURING
NORMAL BUSINESS HOURS). FURNISH HARDWARE TO MATCH EXISTING.
CONTRACTOR TO FIELD VERIFY EXACT HARDWARE REQUIREMENTS.
COORDINATE LOCK SCHEDULE WITH OWNER.
4 EXISTING ELECTRIFIED HARDWARE WITH REMOTE RELEASE TO REMAIN. PROVIDE
NEW DOOR RELEASE BUTTON.
5 2 BUTTON DOOR RELEASE PANEL
6 SECURITY SYSTEM WIRELESS RECEIVER FOR WIRELESS PANIC BUTTONS.
7 NEW SECURITY NETWORK RACK. PROVIDE 12 STRAND MM OM4 ARMOURED FIBER
TO SNR002 AND SNR004. TERMINATE FIBER IN FIBER TERMINATION PANEL AT
BOTH ENDS. SEE SPECIFICATIONS AND DETAIL 1 ON SHEET 55-TY-501.
8 PROVIDE TWO 120V, 20A CIRCUITS FOR NEW SECURITY NETWORK RACK. CIRCUIT
TO NEAREST ELECTRICAL PANEL.
9 EXISTING SCHLAGE AD-300 WIRED NETWORK LOCK. PROVIDE REQUIRED
INTERFACE TO INTEGRATE INTO NEW SYSTEM.
SECURITY SYSTEM SHEET NOTES
A SEE DETAIL SHEET FOR SECURITY CAMERA MOUNTING
B SEE SECURITY DEVICE SCHEDULE FOR ADDITIONAL INFORMATION
C ALL COMMUNICATION CABLES SHALL BE INSTALLED IN CONDUIT, CABLE TRAY, OR
SUPPORTED BY CABLE HOOKS. PROVIDE BUSHINGS AT THE ENDS OF ALL
CONDUITS WHERE STUBBED ABOVE ACCESSIBLE CEILINGS OR WHERE DROPPED
INTO CABLE TRAYS. PROVIDE CABLE HOOKS ABOVE ACCESSIBLE CEILINGS FOR
CABLE INSTALLATION WHERE NOT INSTALLED IN A CONDUIT OR CABLE TRAY.
D BUILDINGS THAT HAVE CAMERAS THAT WORK OR WOULD WORK IF THE
SOFTWARE AND LICENSES WERE CURRENT SHOULD HAVE NEW NVRS INSTALLED
AND THE EXISTING CAMERAS CONNECTED TO THEM. AS NEW CAMERAS ARE
INSTALLED, REMOVE OLD CAMERAS FROM THE SYSTEM.
E ALL CABLES AND DEVICES TO BE LABELED. SEE SPECIFICATION AND DETAILS
FOR SPECIFIC REQUIREMENTS.
F THE EXISTING ACCESS CONTROL SYSTEM IS TO REMAIN IN USE UNTIL THE NEW
SYSTEM IS COMPLETE. DOORS SHOULD BE MIGRATED TO THE NEW SYSTEM ONE
AT A TIME UNTIL ALL ARE ON THE NEW SYSTEM. DURING THIS MIGRATION, NO
DOOR IS TO REMAIN UNSECURED OR INOPERABLE AT THE END OF A WORKDAY.
406407
419420
422 416
BREAK ROOM
HOSP.AREA
DHHR OPENOFFICE PLAN
OFFICE
OFFICE
OFFICE
OFFICEOFFICE
STAIR "A"
UNDESIGNATED
GEN. SERVICES
MECH. ROOM
STAIR "B"
OFFICE
OFFICE
OFFICE
OFFICE
OFFICECOPY/STOR.
W.T.
W.T.
M.T.
M.T. HOSP.AREA
J.C.
I.T.
CORRIDOR
ELEV.LOBBY
HS
HS
MD
MD
MD
ES
SWKS
AC
P
CR
CR
CR
CR
CR
CR
CR
DC DC
DCDC
C033
TYPE A
C034
TYPE A
DC026
DC027
CR035
CR034
CR036
CR037
CR032
CR033
CR038
DC029DC028
ES005
ACP004
SNR004
FILE:
DRAWN BY:
CHECKED BY:
PROJ. NO:
DRAWING NO:
DRAWING TITLE:
PROJECT NAME:
http://www.ZDSDesign.com
135 Corporate Center Drive Suite 532 Scott Depot, WV 25560
TEL 304/755-0075
FAX 304/755-0076
THIS SQUARE APPEARS 1/2"x1/2"
ON FULL SIZE SHEETS
CLIENT:
XXX
C :\U se rs
\e di so n.
ad ki ns \D oc um en ts
\G
SD
2C
_2
4-
-3 0_
BL
D
G
L O
G
AN
_e di so n.
ad ki ns .rv t 8/
/2
:3
1:
P M
55-TY-104
EA
TZ3
GSD-252-C
FOURTH FLOOR
SECURITY PLAN
BUILDING 55 SECURITY
SYSTEM UPGRADES
130 STRATTON STREET
LOGAN, WV 25601
WEST VIRGINIA
GENERAL SERVICES
DIVISION
1/8" = 1'-0"55-TY-104
1 Security Plan-Fourth Floor
KEYNOTES
1 EXISTING FIRE ALARM RELAY TO UNLOCK DOOR IN EVENT OF FIRE ALARM. RETAIN
AND RECONNECT TO NEW ACCESS CONTROL SYSTEM.
2 EXISTING ELECTRIFIED HARDWARE AND MAGLOCKS WITH DELAYED EGRESS TO
REMAIN. VERIFY FUNCTIONALITY WITH OWNER AND RETAIN.
3 NEW SECURITY NETWORK RACK. PROVIDE 12 STRAND MM OM4 ARMOURED FIBER
TO SNR003 AND SNR005. TERMINATE FIBER IN FIBER TERMINATION PANEL AT
BOTH ENDS. SEE SPECIFICATIONS AND DETAIL 1 ON SHEET 55-TY-501.
4 PROVIDE TWO 120V, 20A CIRCUITS FOR NEW SECURITY NETWORK RACK. CIRCUIT
TO NEAREST ELECTRICAL PANEL.
SECURITY SYSTEM SHEET NOTES
A SEE DETAIL SHEET FOR SECURITY CAMERA MOUNTING
B SEE SECURITY DEVICE SCHEDULE FOR ADDITIONAL INFORMATION
C ALL COMMUNICATION CABLES SHALL BE INSTALLED IN CONDUIT, CABLE TRAY, OR
SUPPORTED BY CABLE HOOKS. PROVIDE BUSHINGS AT THE ENDS OF ALL
CONDUITS WHERE STUBBED ABOVE ACCESSIBLE CEILINGS OR WHERE DROPPED
INTO CABLE TRAYS. PROVIDE CABLE HOOKS ABOVE ACCESSIBLE CEILINGS FOR
CABLE INSTALLATION WHERE NOT INSTALLED IN A CONDUIT OR CABLE TRAY.
D BUILDINGS THAT HAVE CAMERAS THAT WORK OR WOULD WORK IF THE
SOFTWARE AND LICENSES WERE CURRENT SHOULD HAVE NEW NVRS INSTALLED
AND THE EXISTING CAMERAS CONNECTED TO THEM. AS NEW CAMERAS ARE
INSTALLED, REMOVE OLD CAMERAS FROM THE SYSTEM.
E ALL CABLES AND DEVICES TO BE LABELED. SEE SPECIFICATION AND DETAILS
FOR SPECIFIC REQUIREMENTS.
F THE EXISTING ACCESS CONTROL SYSTEM IS TO REMAIN IN USE UNTIL THE NEW
SYSTEM IS COMPLETE. DOORS SHOULD BE MIGRATED TO THE NEW SYSTEM ONE
AT A TIME UNTIL ALL ARE ON THE NEW SYSTEM. DURING THIS MIGRATION, NO
DOOR IS TO REMAIN UNSECURED OR INOPERABLE AT THE END OF A WORKDAY.
516517
UNDESIGNATED
DEPT.DIRECTOR
OFFICE
CONFERENCE
UNDESIGNATED
STAIR "A"
STAIR "C"
MECH.ROOM
STAIR "B"
HOSP.AREA
CORRIDOR
DHHR OPENOFFICE PLAN
OFFICE
OFFICE
OFFICECOPY/STOR.
CORRIDOR
M.T.
M.T.
W.T.
W.T.
I.T.
J.C.
CORRIDOR
ELEV.LOBBY
A B E F
C D
2.2
A.1 A.7
2.3
2.7
E.9E.3
2.1
2.5
THE COLUMN SIZES HAVE BEEN CHANGED TO MATCH THE 90% REVIEW SET
HS
MD
MD
MD
ES
CR
CR
CR
CR
CR
CR
CR
CR
DC DC
DC DC
AC
P
CR039
CR040
CR041
CR043
CR042
DC030
DC031
C037
TYPE A
CR044
ACP005
C038
TYPE A
DC032 DC033
CR046
C035
TYPE B
CR047
ES007
SNR005
FILE:
DRAWN BY:
CHECKED BY:
PROJ. NO:
DRAWING NO:
DRAWING TITLE:
PROJECT NAME:
http://www.ZDSDesign.com
135 Corporate Center Drive Suite 532 Scott Depot, WV 25560
TEL 304/755-0075
FAX 304/755-0076
THIS SQUARE APPEARS 1/2"x1/2"
ON FULL SIZE SHEETS
CLIENT:
XXX
C :\U se rs
\e di so n.
ad ki ns \D oc um en ts
\G
SD
2C
_2
4-
-3 0_
BL
D
G
L O
G
AN
_e di so n.
ad ki ns .rv t 8/
/2
:3
1:
P M
55-TY-105
EA
TZ3
GSD-252-C
FIFTH FLOOR SECURITY
PLAN
BUILDING 55 SECURITY
SYSTEM UPGRADES
130 STRATTON STREET
LOGAN, WV 25601
WEST VIRGINIA
GENERAL SERVICES
DIVISION
1/8" = 1'-0"55-TY-105
1 Security Plan-Fifth Floor
KEYNOTES
1 EXISTING FIRE ALARM RELAY TO UNLOCK DOOR IN EVENT OF FIRE ALARM. RETAIN
AND RECONNECT TO NEW ACCESS CONTROL SYSTEM.
2 EXISTING ELECTRIFIED HARDWARE AND MAGLOCKS WITH DELAYED EGRESS TO
REMAIN. VERIFY FUNCTIONALITY WITH OWNER AND RETAIN.
3 IN-CAB CARD READER. CURRENT CONFIGURATION LIMITS ACCESS TO THE
FOURTH, AND FIFTH FLOORS WITHOUT A VALID CREDENTIAL.
4 NEW SECURITY NETWORK RACK. PROVIDE 12 STRAND MM OM4 ARMOURED FIBER
TO SNR004. TERMINATE FIBER IN FIBER TERMINATION PANEL AT BOTH ENDS.
SEE SPECIFICATIONS AND DETAIL 1 ON SHEET 55-TY-501.
5 PROVIDE TWO 120V, 20A CIRCUITS FOR NEW SECURITY NETWORK RACK. CIRCUIT
TO NEAREST ELECTRICAL PANEL.
SECURITY SYSTEM SHEET NOTES
A SEE DETAIL SHEET FOR SECURITY CAMERA MOUNTING
B SEE SECURITY DEVICE SCHEDULE FOR ADDITIONAL INFORMATION
C ALL COMMUNICATION CABLES SHALL BE INSTALLED IN CONDUIT, CABLE TRAY, OR
SUPPORTED BY CABLE HOOKS. PROVIDE BUSHINGS AT THE ENDS OF ALL
CONDUITS WHERE STUBBED ABOVE ACCESSIBLE CEILINGS OR WHERE DROPPED
INTO CABLE TRAYS. PROVIDE CABLE HOOKS ABOVE ACCESSIBLE CEILINGS FOR
CABLE INSTALLATION WHERE NOT INSTALLED IN A CONDUIT OR CABLE TRAY.
D BUILDINGS THAT HAVE CAMERAS THAT WORK OR WOULD WORK IF THE
SOFTWARE AND LICENSES WERE CURRENT SHOULD HAVE NEW NVRS INSTALLED
AND THE EXISTING CAMERAS CONNECTED TO THEM. AS NEW CAMERAS ARE
INSTALLED, REMOVE OLD CAMERAS FROM THE SYSTEM.
E ALL CABLES AND DEVICES TO BE LABELED. SEE SPECIFICATION AND DETAILS
FOR SPECIFIC REQUIREMENTS.
F THE EXISTING ACCESS CONTROL SYSTEM IS TO REMAIN IN USE UNTIL THE NEW
SYSTEM IS COMPLETE. DOORS SHOULD BE MIGRATED TO THE NEW SYSTEM ONE
AT A TIME UNTIL ALL ARE ON THE NEW SYSTEM. DURING THIS MIGRATION, NO
DOOR IS TO REMAIN UNSECURED OR INOPERABLE AT THE END OF A WORKDAY.
P01
P02
P03
MECHANICAL EQUIP.
ELEV.MACH.
STAIR "C"
A B E F
C D
2.2
A.1 A.7
2.3
2.7
E.9E.3
2.1
2.5
THE COLUMN SIZES HAVE BEEN CHANGED TO MATCH THE 90% REVIEW SET
DC
CR
AC
P
SF-1
STAIR PRESSURIZATION FAN
SF-1
STAIR PRESSURIZATION FAN
CR048
ACP006
DC034
FILE:
DRAWN BY:
CHECKED BY:
PROJ. NO:
DRAWING NO:
DRAWING TITLE:
PROJECT NAME:
http://www.ZDSDesign.com
135 Corporate Center Drive Suite 532 Scott Depot, WV 25560
TEL 304/755-0075
FAX 304/755-0076
THIS SQUARE APPEARS 1/2"x1/2"
ON FULL SIZE SHEETS
CLIENT:
XXX
C :\U se rs
\e di so n.
ad ki ns \D oc um en ts
\G
SD
2C
_2
4-
-3 0_
BL
D
G
L O
G
AN
_e di so n.
ad ki ns .rv t 8/
/2
:3
1:
P M
55-TY-106
EA
TZ3
GSD-252-C
PENTHOUSE SECURITY
PLAN
BUILDING 55 SECURITY
SYSTEM UPGRADES
130 STRATTON STREET
LOGAN, WV 25601
WEST VIRGINIA
GENERAL SERVICES
DIVISION
1/8" = 1'-0"55-TY-106
1 Security Plan-Penthouse
KEYNOTES
1 IN-CAB CARD READER. CURRENT CONFIGURATION LIMITS ACCESS TO 4TH AND
5TH FLOORS, PENTHOUSE, AND REAR DOOR ON ALL FLOORS.
2 ACCESS CONTROL PANEL FOR IN-CAB CARD READERS. PROVIDE OUTPUTS FOR
ALL FLOORS SERVED BY THE ELEVATORS FOR BOTH FRONT AND REAR DOORS.
ACCESS SHALL BE CONTROLLABLE BY THE INDIVIDUAL FLOOR. CURRENT
CONFIGURATION LIMITS ACCESS TO THE 4TH AND 5TH FLOORS, PENTHOUSE, AND
REAR DOOR ON ALL FLOORS WITHOUT A VALID CREDENTIAL.
SECURITY SYSTEM SHEET NOTES
A SEE DETAIL SHEET FOR SECURITY CAMERA MOUNTING
B SEE SECURITY DEVICE SCHEDULE FOR ADDITIONAL INFORMATION
C ALL COMMUNICATION CABLES SHALL BE INSTALLED IN CONDUIT, CABLE TRAY, OR
SUPPORTED BY CABLE HOOKS. PROVIDE BUSHINGS AT THE ENDS OF ALL
CONDUITS WHERE STUBBED ABOVE ACCESSIBLE CEILINGS OR WHERE DROPPED
INTO CABLE TRAYS. PROVIDE CABLE HOOKS ABOVE ACCESSIBLE CEILINGS FOR
CABLE INSTALLATION WHERE NOT INSTALLED IN A CONDUIT OR CABLE TRAY.
D BUILDINGS THAT HAVE CAMERAS THAT WORK OR WOULD WORK IF THE
SOFTWARE AND LICENSES WERE CURRENT SHOULD HAVE NEW NVRS INSTALLED
AND THE EXISTING CAMERAS CONNECTED TO THEM. AS NEW CAMERAS ARE
INSTALLED, REMOVE OLD CAMERAS FROM THE SYSTEM.
E ALL CABLES AND DEVICES TO BE LABELED. SEE SPECIFICATION AND DETAILS
FOR SPECIFIC REQUIREMENTS.
F THE EXISTING ACCESS CONTROL SYSTEM IS TO REMAIN IN USE UNTIL THE NEW
SYSTEM IS COMPLETE. DOORS SHOULD BE MIGRATED TO THE NEW SYSTEM ONE
AT A TIME UNTIL ALL ARE ON THE NEW SYSTEM. DURING THIS MIGRATION, NO
DOOR IS TO REMAIN UNSECURED OR INOPERABLE AT THE END OF A WORKDAY.
FIBER TERMINATION PANEL
96TB NVR
2000VA UPS FOR NVR
2000VA UPS FOR APP. AND
SWITCH
BLANK PANEL
24 PORT SWITCH
CAT 6 PATCH PANEL
VENT PANEL
VENT PANEL
VENT PANEL
BRUSH GROMMET PANEL
BLANK PANEL
BLANK PANEL
BLANK PANEL
VENT PANEL
24 PORT SWITCH
CAT 6 PATCH PANEL
12U WALL MOUNTED
SECURITY NETWORK
RACK SNR005
12-STRAND
FIBER OPTIC CABLE
12-STRAND
FIBER OPTIC CABLE
12-STRAND
FIBER OPTIC CABLE
12-STRAND
FIBER OPTIC CABLE
ACCESS
CONTROL
PANEL
ACP001
ACCESS
CONTROL
PANEL
ACP002
ACCESS
CONTROL
PANEL
ACP003
ACCESS
CONTROL
PANEL
ACP004
ACCESS
CONTROL
PANEL
ACP005
ACCESS
CONTROL
PANEL
ACP006
12U WALL MOUNTED
SECURITY NETWORK
RACK SNR004
12 U WALL MOUNTED
SECURITY NETWORK
RACK SNR003
12U WALL MOUNTED
SECURITY NETWORK
RACK SNR002
24U FREE STANDING
SECURITY SERVER RACK
SNR001
ROOM 241
ROOM 341
ROOM 427
ROOM 527
PENTHOUSE
ELEVATOR MACHINE ROOM
ROOM 124FIRST FLOOR
SECOND FLOOR
THIRD FLOOR
FOURTH FLOOR
FIFTH FLOOR
PENTHOUSE
CR CR CR IAC
CR CR CR IAC
CR CR CR IAC
CR CR CR IAC
CR CR CR IAC
CR CR
CAT 6A(TYPICAL)
COMPOSITE CABLE (TYPICAL)
CAT 6A(TYPICAL)
CAT 6A(TYPICAL)
CAT 6A(TYPICAL)
CAT 6A(TYPICAL)
COMPOSITE CABLE (TYPICAL)
COMPOSITE CABLE (TYPICAL)
COMPOSITE CABLE (TYPICAL)
COMPOSITE CABLE (TYPICAL)
CAT 6ATO OIT NETWORK AND
INTERNET PROVIDER
JB
JB
JB
JB
JB
JB
JB
JB
JB
JB
JB
JB
JB
JB
JB
JB
JB
JB
JB
JB
JB
JB
ELEVATOR CARD READERS
COMPOSITE CABLE (TYPICAL)
ELEVATOR TRAVEL CABLE
CCTV CAMERAS
CARD READERS
INTEGRATED
LOCK AND READER
CCTV CAMERAS
CCTV CAMERAS
CCTV CAMERAS
CCTV CAMERAS
INTEGRATED
LOCK AND READER
INTEGRATED
LOCK AND READER
INTEGRATED
LOCK AND READER
INTEGRATED
LOCK AND READER
CARD READERS
CARD READERS
CARD READERS
CARD READERS
CAT 6
EL
JB
ELECTRIFIED LOCK WITH
SCHEDULED LOCK/UNLOCK
EL
JB
ELECTRIFIED LOCK WITH
SCHEDULED LOCK/UNLOCK
EL
JB
ELECTRIFIED LOCK WITH
SCHEDULED LOCK/UNLOCK
EL
JB
ELECTRIFIED LOCK WITH
SCHEDULED LOCK/UNLOCK
EL
JB
ELECTRIFIED LOCK WITH
SCHEDULED LOCK/UNLOCK
PENTHOUSE ROOF
SECURITY
WORKSTATION
CAT 6A
SECURITY DESK
RECEPTION 102
FIBER TERMINATION PANEL
1000VA UPS FOR SWITCH
BLANK PANEL
BLANK PANEL
BLANK PANEL
BLANK PANEL
24 PORT SWITCH
CAT 6 PATCH PANEL
FIBER TERMINATION PANEL
1000VA UPS FOR SWITCH
BLANK PANEL
BLANK PANEL
BLANK PANEL
BLANK PANEL
24 PORT SWITCH
CAT 6 PATCH PANEL
FIBER TERMINATION PANEL
1000VA UPS FOR SWITCH
BLANK PANEL
BLANK PANEL
BLANK PANEL
BLANK PANEL
24 PORT SWITCH
CAT 6 PATCH PANEL
FIBER TERMINATION PANEL
1000VA UPS FOR SWITCH
BLANK PANEL
BLANK PANEL
BLANK PANEL
BLANK PANEL
NOTES:
1. PROVIDE ALL PATCH CABLES, GBICS, AND SFP ADAPTERS TO CONNECT FIBER TO NETWORK SWITCHES.
2. PROVIDE ALL PATCH CABLES, GBICS, AND SFP ADAPTERS TO MAKE 10G CONNECTION FROM NVR TO NETWORK SWITCH.
3. PROVIDE UPS FOR NVR, ACCESS CONTROL APPLIANCE AND NETWORK SWITCHES. SEE SPECIFICATIONS.
4. PROVIDE BACK-UP BATTERIES FOR ALL ACCESS CONTROL PANELS AND POWER SUPPLIES.
5. TERMINATE ALL 12 STRANDS OF FIBER AT EACH FIBER TERMINATION PANEL.
6. PROVIDE 2 DEDICATED 120V 20A CIRCUITS TO EACH RACK LOCATION. CIRCUIT TO NEAREST ELECTRIAL PANEL.
7. ALL CAT 6 AND FIBER OPTIC CABLE TO BE CERTIFIED. PROVIDE CERTIFICATION TEST REPORTS.
8. GROUND RACKS TO A SUITABLE ELECTRICAL BUILDING GROUND. SEE SPECIFICATIONS.
9. INSTALL READERS USING OSDP SECURE COMMUNICATIONS PROTOCOL.
CREDENTIALING
WORKSTATION
FLOOR
A.
B.
GENERAL DETAIL NOTES (TYPICAL ACCESS DOOR DIAGRAM ONLY):
DETAIL REPRESENTS ALL HARDWARE OPTIONS. QUANTITY AND TYPE OF DEVICES VARY PER LOCATION AS INDICATED ON PLANS.
INSTALL EMT FOR EACH RACEWAY - SEE ROUGH-IN DETAILS.
FIRE ALARM INTERFACE
1 46
2REX
TO ACCESS CONTROL PANEL 7
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.
14.
15.
16.
17.
18.
DETAIL NOTES:
CARD READERS.
REQUEST TO EXIT DEVICE.
ELECTRIC STRIKE.
POWER TRANSFER DEVICE.
DOOR CONTACT.
EMERGENCY EXIT DEVICE.
READER JUNCTION BOX OR DOOR POWER SUPPLY. WHERE REQUIRED, FURNISH 120 VOLT POWER FROM NEAREST CIRCUIT.
DOOR OPERATOR. FURNISH 120V POWER FROM NEAREST CIRCUIT.
DOOR OPERATOR PUSHBUTTONS. INTERFACE CARD READER WITH DOOR OPERATOR TO ENABLE NON-SECURE SIDE OPERATOR BUTTON ONLY
AFTER VALID CREDENTIAL IS PRESENTED.
ELECTRIFIED DOOR HARDWARE
POWER CONDUCTORS IN EMT RACEWAY
CONTROL CONDUCTORS IN EMT RACEWAY
CEILING HEIGHT VARIES.
ACCESSIBLE CEILING SPACE.
POWER FROM NEAREST CIRCUIT.
CONDUCTORS IN RACEWAY ABOVE CEILING.
CONDUCTORS IN RACEWAY TYPICAL - SEE SECURITY DEVICE ROUGH-IN DETAIL.
PLENUM RATED CABLE SUPPORTED ABOVE CEILING.
1'-0" MAXIMUM
6" MIN
6" MAX
1'-0" MAX
CAT 6
RJ45
JACK
1 8
FF1-001-G
IDF CLOSET (FF1)
FACEPLATE
NUMBER (001)
JACK COLOR (G, R, Y)
WHITE LABEL AND BLACK
LETTERS WITH CLEAR
TAPE COVERING ON BOTH
ENDS OF CABLE
IDF #(FF1)
OUTLET #
FF1-003G
JACK # (G, R, Y)
1-001G 1-001R
1-001Y 1-002G 1-002R
1-002Y 1-003G 1-003R
1-003Y
4x4 METAL BOX WITH
COVER - MTD TO WALL
PATCH CABLE BY
SYSTEMS
CONTRACTORWALL ABOVE CEILING
HORIZONTAL CABLE
SEE SPECIFICATIONS
SURFACE MOUNT
KEYSTONE (BISCUIT) JACK
4x4 METAL BOX WITH
COVER - MTD TO WALL
HORIZONTAL CABLE
SEE SPECIFICATIONS
SURFACE MOUNT
KEYSTONE (BISCUIT) JACK
PATCH CABLE BY
SYSTEMS
CONTRACTOR
1"⌀ EMT CONDUIT
METAL ELECTRICAL
BOX - SEE
SPECIFICATIONS
CEILING AS INDICATED
WITHIN ARCH PLANS
SET SCREW
CONNECTOR
WITH INSULATING
BUSHING
SET SCREW
CONNECTOR WITH
INSULATING BUSHING
1'-0"
6"
SE
E
AR
C
H
IT
EC
TU
R
AL
D R
AW
IN
G S
FO
R
C
EI
LI
N
G H
EI
G
H T
3' -4
1.
2.
NOTES:
THE DEVICE SHALL NOT SPAN MORE
THAN ONE FINISH MATERIAL
BOX SHALL BE FLUSH WITH THE
FINISH MATERIAL
SECTION
PLAN
CEILING SEE ARCHITECTURAL
DRAWINGS
ELECTRICAL BOX T-BAR
FASTENER
SURVEILLANCE DEVICE
ELECTRICAL BOX T-BAR
FASTENER
ACOUSTICAL TILE SEE
ARCHITECTURAL
DRAWINGS
CEILING STRUCTURE SEE
ARCHITECTURAL DRAWINGS
CEILING SUPPORT STRUCTURE
SEE ARCHITECTURAL DRAWINGS
HORIZONTAL CABLING TO
CABLING SUPPORT SYSTEM
EQUAL EQUAL
EQ
UA
L
SUPPORT CABLE ON ALL
FOUR CORNERS OF GRID
SUPPORT CABLE ON ALL
FOUR CORNERS OF CEILING
SUPPORT STRUCTURE
METAL BOX SIZE AS
REQUIRED BY NEC
METAL BOX SIZE AS
REQUIRED BY NEC
EQ
UA
L SURVEILLANCE DEVICE
PATCH
CABLE
FLOOR
A.
B.
C.
D.
GENERAL DETAIL NOTES (TYPICAL ACCESS DOOR DIAGRAM ONLY):
DETAIL REPRESENTS ALL HARDWARE OPTIONS. QUANTITY AND TYPE OF DEVICES VARY PER LOCATION AS INDICATED ON PLANS.
PROVIDE SHOP DRAWING SUBMITTAL AND WIRING DIAGRAMS FOR EACH POWER ASSISTED/ACCESS DOOR LOCATION.
ALL EQUIPMENT FURNISHED AND INSTALLED BY SECURITY CONTRACTOR.
INSTALL EMT FOR EACH RACEWAY - SEE ROUGH-IN DETAILS.
FIRE ALARM INTERFACE
1 46
2REX
TO ACCESS CONTROL PANEL
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.
14.
15.
16.
DETAIL NOTES:
CARD READERS.
REQUEST TO EXIT DEVICE.
ELECTRIC STRIKE.
ELECTRIFIED DOOR HARDWARE AND POWER TRANSFER DEVICE.
EMERGENCY EXIT DEVICE.
DOOR POWER SUPPLY. POWER SUPPLY TO BE USED AS ACCESS CONTROL JUNCTION BOX. 120 VOLT POWER FROM NEAREST CIRCUIT.
DOOR OPERATOR. FURNISH 120V POWER FROM NEAREST CIRCUIT. ON ACCESS CONTROL DOORS INTERFACE WITH ACCESS CONTROL SYSTEM.
DOOR OPERATOR PUSHBUTTONS. INTERFACE CARD READER WITH DOOR OPERATOR TO ENABLE NON-SECURE SIDE OPERATOR BUTTON ONLY
AFTER VALID CREDENTIAL IS PRESENTED.
SINGLE DOOR LOCATION
ELECTRIFIED DOOR HARDWARE
POWER CONDUCTORS IN EMT RACEWAY
CONTROL CONDUCTORS IN EMT…