Addendum No1 _Drawings - Building 55.pdf

PDF 4 MB Posted

Attached to
Satellite Buildings Security Systems Upgrades Project
Solicitation number
CRFQ 0211 GSD2700000019 2
Issued by
Kanawha County, West Virginia

About this file

This Addendum No. 1 for drawings constitutes design documentation for the Building 55 Security System Upgrades project managed by the West Virginia General Services Division. The project, located at 130 Stratton Street, Logan, WV 25601, involves comprehensive security system upgrades across a multi-story facility consisting of six levels (First Floor through Penthouse). The scope includes installation of new access control systems with integrated card readers, security cameras, door contacts, electrified locks, wireless panic buttons, and network infrastructure. The project incorporates demolition of existing security devices, replacement with new equipment, and migration of doors from the existing access control system to the new system on a phased basis to ensure no doors remain unsecured during the transition. The design specifies security network racks at multiple locations (SNR001-SNR005) with fiber optic connectivity, networked switches, uninterruptible power supplies, and network video recorders. All communication cables are required to be installed in conduit or cable tray with proper labeling and certification.

The security device schedule specifies approximately 50 multi-technology card readers (MTB15 model), multiple camera types ranging from 4MP dome cameras to 12MP fisheye and 5MP multi-head configurations, over 38 door contacts, and 16 wireless panic buttons distributed across the facility. Two dedicated 120-volt, 20-ampere circuits must be provided to each security network rack from the nearest electrical panel. The design requires compliance with fire-rated assembly penetration standards (UL systems WL 1001, 1002, or 1003) for all conduit penetrations through fire-rated walls, floors, and shaft enclosures. All exterior cameras require surge protection, and the existing fire alarm relay systems must be retained and reconnected to interface with the new access control system. The project requires coordination with the owner regarding lock schedules, field verification of exact hardware requirements, and adherence to National Electrical Code standards for all electrical installations and conduit work.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

ZDS Design/ Consulting Services

Mechanical * Electrical * IAQ * Energy * Commissioning

135 Corporate Center Dr., Suite 532 Scott Depot, WV 25560

Ph: (304) 755-0075 Fx: (304) 755-0076

Web: www.zdsdesign.com Email: contact@zdsdesign.com

C :\U se rs

\e di so n.

ad ki ns \D oc um en ts

\G

SD

2C

_2

4-

-3 0_

BL

D

G

L O

G

AN

_e di so n.

ad ki ns .rv t

WEST VIRGINIA GENERAL SERVICES DIVISION

BUILDING 55 SECURITY SYSTEM UPGRADES

ZDS Project Number: GSD-252-C 8/5/2026

130 STRATTON STREET

LOGAN, WV 25601

PROJECT VICINITY MAP

OS

DL

CO

T

CO

LC

F

F

F

DH

DCL

XXX

XXXX

XX

J

J F1

DO

M

N

X

TV

XXXX

CK

CK

TV

CC

DC

ES

IC

ML

RX

REX

MD

XXX

OS

1P 1 Pole (2P, 3P, 4P, ETC.)

A, Amp Ampere AC Above Counter ACLG Above Ceiling ADO Automatic Door Opener AF Amp Frame AFF Above Finished Floor AFG Above Finished Grade AFI Arc Fault Circuit

Interrupter AHU Air Handling Unit AL Aluminum ALT Alternate AMP Ampere AMPL Amplifier ANNUN Annunciator APPROX Approximately AQ-STAT Aquastat ARCH Architect, Architectural AS Amp Switch AT Amp Trip ATS Automatic Transfer Switch AUTO Automatic AUX Auxiliary AV Audio Visual AWG American Wire Gauge BATT Battery BD Board BLDG Building BMS Building Management System C Conduit CAB Cabinet CAT Catalog CATV Cable Television CB Circuit Breaker CCTV Closed Circuit Television CKT Circuit CLG Ceiling COMB Combination CMPR Compressor CONN Connection CONST Construction CONT Continuation Or Continuous CONTR Contractor CONV Convector CP Circulating Pump CRT Cathode-Ray Tube CT Current Transformer CTR Center CU Copper DCP Domestic Water Circulating Pump DEPT Department DET Detail DIA Diameter DISC Disconnect DIST Distribution DN Down DPR Damper DS Safety Disconnect Switch DT Double Throw DWG Drawing EC Electrical Contractor ELEC Electric, Electrical ELEV Elevator ELU Emergency Lighting Unit EM Emergency EMS Energy Management System EMT Electrical Metallic Tubing EP Electric Pneumatic EQUIP Equipment EWC Electric Water Cooler EXIST Existing EXH Exhaust EXP Explosion Proof FA Fire Alarm FABP Fire Alarm Booster Power

Supply Panel FACP Fire Alarm Control Panel FCU Fan Coil Unit FIXT Fixture FLR Floor FLUOR Fluorescent FU Fuse FUDS Fused Safety Disconnect Switch GA Gauge GAL Gallon GALV Galvanized GC General Contractor GEN Generator GFI Ground Fault Circuit Interrupter GFP Ground Fault Protector GND Ground GRS Galvanized Rigid Steel (Conduit) GYP BD Gypsum Board HOA Hands-Off-Automatic Switch HORIZ Horizontal HP Horsepower HPF High Power Factor HT Height HTG Heating HTR Heater HV High Voltage HVAC Heating, Ventilating And Air

Conditioning IC Interrupting Capacity IG Isolated Ground IMC Intermediate Metal Conduit INCAND Incandescent IR Infrared I/W Interlock With J-BOX Junction Box KV Kilovolt KVA Kilovolt-Ampere KVAR Kilovolt-Ampere Reactive KW Kilowatt KWH Kilowatt Hour LOC Locate Or Location LT Light LTG Lighting LTNG Lightning LV Low Voltage MAX Maximum MAG.S Magnetic Starter M/C Momentary Contact MC Mechanical Contractor

Electrical Abbreviations

Electrical DeviceTags: Uppercase letter(s) indicates Panel ID and circuit number. Lowercase letter indicates designation of controlling switch (where applicable).

Switch ID indicated by a lowercase letter. Switch IDs are unique per space. A switch with an ID "a" controls all devices within the space in which it is located tagged with "a". A switch without a tagged ID controls all lighting fixtures within a space. ID tags may be used on control devices other than switches, such as occupancy sensors or contactors.

Equipment Tags: Equipment ID is indicated by an underlined tag adjacent to the equipment. See the equipment connection schedule for description, electrical requirements, and panel and circuit number. Symbols/graphic appearance of equipment varies.

Solid, arced lines connecting equipment, devices, or fixtures indicate unswitched power circuiting. Wires are only intended to indicate to what circuit devices are connected. Actual connections, circuit routing, installtion, junction boxes, etc. shall be field-determined by the contractor.

Home run to branch circuit panelboard. The equipment name and circuit number(s) are indicated, separated by a hyphen. Homeruns are only intended to indicate panel and circuit number. Actual homerun location shall be field-determined by the contractor.

Power Symbols

Electrical Symbol Legend

Room

MCB Main Circuit Breaker MCC Motor Control Center MDC Main Distribution Center MDP Main Distribution Panel MFR Manufacturer MFS Main Fused Disconnect Switch MH Manhole MIC Microphone MIN Minimum MISC Miscellaneous MLO Main Lugs Only MMS Manual Motor Starter MOA Multioutlet Assembly MSP Motor Starter Panelboard MSBD Main Switchboard MSS Motor Starter Switch MT Mount MT.C Empty Conduit MTS Manual Transfer Switch MTR Motor, Motorized N.C. Normally Closed NEC National Electrical Code NEMA National Electrical

Manufacturer's Association NFDS Non-Fused Safety Disconnect

Switch NIC Not In Contract NL Night Light N.O. Normally Open NPF Normal Power Factor NTS Not To Scale OC On Center OH Overhead OL Overloads PA Public Address PB Pull Box Or Pushbutton PE Pneumatic Electric PED Pedestal PF Power Factor PH Phase PIV Post Indicating Valve PNL Panel PP Power Pole PR Pair PRI Primary PROJ Projection PRV Power Roof Ventilator PT Potential Transformer PVC Polyvinyl Chloride (Conduit) PWR Power QUAN Quantity RCPT Receptacle REQD Required RM Room RSC Rigid Steel Conduit RTU Roof Top Unit SC Surface Conduit SEC Secondary SHT Sheet SIM Similar SLD Single-Line Diagram S/N Solid Neutral SPEC Specification SPKR Speaker SP Spare SPP Single-Point Power SR Surface Raceway SS Stainless Steel SSW Selector Switch S/S Stop/Start Pushbuttons STA Station STD Standard SURF Surface Mounted SW Switch SWBD Switchboard SYM Symmetrical SYS System TEL Telephone TERM Terminal TL Twist Lock TR Tamper Resistant T-STAT Thermostat TTC Telephone Terminal Cabinet TV Television TVTC Television Terminal Cabinet TYP Typical UC Under Counter UE Underground Electrical UG Underground UH Unit Heater UT Underground Telephone UTIL Utility UV Ultraviolet V Volt VA Volt-Amperes VDT Video Display Terminal VERT Vertical VFD Variable Frequency Drive VOL Volume W Watt W/ With WG Wire Guard WH Water Heater W/O Without WP Weatherproof XFMR Transformer XFR Transfer

∠ Angle @ At ▲ Delta ' Feet " Inches # Number Ø Phase C Center Line P Plate

Exit Light, Wall-Mounted.

Shading and arrows indicate faces and directional chevrons.

Wall-mounted fixtures, Typical (Various Symbols)

Emergency Lighting Unit, Wall-Mounted, Remote Battery

Emergency Lighting Unit, Wall-Mounted, Integral Battery

Emergency Lighting Unit, Ceiling-Mounted, Integral Battery Emergency Lighting Unit, Ceiling-Mounted, Remote Battery

Lighting Fixtures, Typical, Rectangular (Various Symbols) Filled circles indicate recessed.

Open circles indicate surface-mounted.

Diagonal line indicates lensed.

Outer dots indicate suspended.

Lighting Fixtures, Typical, Round (Various Symbols) Center dot indicates pendant.

Diagonal line indicates lensed.

Chevron indicates wall wash.

Strip Fixture

Directional Light, Track Light, Flood Light

Exit Light, Ceiling-Mounted.

Shading and arrows indicate faces and directional chevrons.

Linear Light, Tape Light

Exit/ELU Combo

Diagonal hatch indicates light on a critical circuit.

Solid hatch indicates light on an emergency or life safety circuit.

Pole/Area Lights

Post-Top Area Light

Bollard Light

Single-Pole Switch Two-Pole Switch Three-Pole Switch Switch Modifiers:

3: 3-Way 4: 4-Way K: Keyed D: Dimming T: Timer

OS: Occupancy Sensor VS: Vacancy Sensor AC: Above-Counter LV: Low-Voltage M: Motor-Rated

Lighting Contactor

Lighting Control Panel

Occupancy Sensor

Daylight Harvesting Sensor

Smoke Detector

Heat Detector

Carbon Monoxide Detector

Beam Detector T: Transmitter R: Receiver

Combination Detector (Up to Three)

Duct Smoke Detector

Manual Pull Station

Horn, Wall

Horn, Ceiling

Strobe, Wall, Candela as indicated

Strobe, Ceiling, Candela as indicated

Horn/Strobe, Wall, Candela as indicated

Horn/Strobe, Ceiling, Candela as indicated

Remote Indicator w/ Test Switch, Wall

Remote Indicate w/ Test Switch, Ceiling

Door Holder

Door Closer

Fire Service Phone

Addressible Module AIM: Addressible Input Module AOM:Addressible Output Control Module AIO: Addressible Input/Output Module

Fire Alarm Control Unit EVAC: Voice Evacuation Control Panel FAA: Fire Alarm Annunciator FACP: Fire Alarm Control Panel FATC: Fire Alarm Terminal Cabinet NACP: Notification Appliance Circuit Panel FAMN: Fire Alarm Mass Notification Control Panel

Supervisory or Interface Device PIV: Post Indicator Valve Supervisory PS: Pressure Switch R: Non-Addressible Relay VS: Valve Supervisory Switch WF: Water Flow Switch

Simplex Receptacle

Duplex Receptacle

Quadruplex Receptacle

Special Receptacle, Type as Indicated

W all

Ce ilin g

Flo or

Receptacle Modifiers:

##": Height AFF OC AC: Above Counter GFI: Ground-Fault Circuit Interrupter WP: Weatherproof In-Use Cover

Half shading indicates split (typically switched) Outside shading indicates emergency circuit Center shading indicates isolated ground

Multioutlet Assembly Filled squares indicate 120V outlet Open squares indicate with USB

Cord Reel, Device Varies

Drop Cord, Device Varies

Junction Box Floor Box, see schedule for type

Emergency Power Off

Door Opener Push Plate

Power Meter Safety Switch, Fused

Safety Switch, Unfused

Motor Starter

Combination Starter/Disconnect

Ground Rod

Ground Rod with Test Well

Lightning Protection Air Terminal

Lightning Protection Conductor Splice

Static Ground Receptacle

Data Outlet

Telephone Outlet

Data/Telephone Outlet

W all

Ce ilin g

Flo or

Outlet Modifiers:

##": Height AFF OC AC: Above Counter

Wireless Access Point

Nurse Call Corridor Light Number of lights as indicated

Nurse Call Device B: Code Blue D: Duty Station E: Emergency P: Patient Call S: Staff

TV Outlet

Nurse Call Control Unit NCAP: Nurse Call Annunciator Panel NCHS: Nurse Call Host Constroller NCPA: Nurse Call Power Supply NCTC: Nurse Call Terminal Cabinet NCUPS: Uninterruptable Power Supply

Lighting Symbols

Contactor

Single-Pole Switch Two-Pole Switch Three-Pole Switch Switch Modifiers:

K: Keyed T: Timer AC: Above-Counter M: Motor-Rated

Fire Alarm Symbols

Grounding and Lightning Protection Symbols

Security Camera PTZ: Pan/Tilt/Zoom

Card Reader

Card Reader with Keypad

Closed Circuit TV Outlet

Door Contact

Electric Strike

Intercom

Magnetic Lock

Request to Exit Button

Request to Exit Sensor

Motion Detector

Security Control Unit SCP: Security Control Panel SPS: Security Power Supply Unit ACP: Access Control Panel WIU: Wiegand Interface Unit PIB: Panel Interface Board IAC: Networked Lock with Integrated

Reader SWKS: Security Workstation MON: Video Monitor ICE: Intercom Exchange

Telecom Symbols

Nurse Call Symbols

Security Symbols a

A A1a

Equipment is tagged with Panel Name and with Panel ID in parentheses. Panel ID is intended as a design documentation aid only. Do not include Panel ID in field-applied circuit directories or labels.

Hatched fill indicates distribution panel or switchboard.

Solid fill indicates branch panel or load center.

Dashed box indicates code-required clearance (width and depth).

Door indicates front of recessed panel.

Panelboards are assigned an abbreviated indicator (or Panel ID) for use with circuit numbers. Panel ID is listed within the panel schedule and in the panel abbreviation schedule.

Power Distribution Equipment

HP

1A

(B

LP

1A

(C

MD

P(

A)

SB1(S)

Devices and fixtures are tagged with Panel ID and circuit number. For example, a device tagged with "A1" indicates the device is circuited to panel designated "A," circuit number 1. The panel schedule circuit number contans both the panel abbreviation and the circuit number.

XX-1

Transformer: Typically transformer names begin with or contain the letter "T". See Single-Line Diagram for description and requirements.

T1

Dashed, arced lines connecting equipment, devices, or fixtures indicate switched power.

Absence of a switch designation on a lighting fixture indicates fixture is controlled by the only switch in the space. An "x" in place of the switch designation indicates unswitched.

Bottom Value, Lowercase Letter: Switch ID

Lighting Tags

Top Value: Fixture Type ID (Underlined)

Bottom Value, Uppercase Letter(s): Panel ID Bottom Value, Number(s): Circuit Number a a

C1a

Wiring

Power Device and Equipment Tags

Construction Phasing

Existing to Remain

Existing to Be Demolished

New

(Typical All Symbols and Equipment)

Existing to Be Demolished

Area Not in Contract

Miscellaneous

Keynote

Callout:

Top Value: Detail Number on Sheet Bottom Value: Sheet Number of Detail

Room Name and Number

Smoke Damper

FILE:

DRAWN BY:

CHECKED BY:

PROJ. NO:

DRAWING NO:

DRAWING TITLE:

PROJECT NAME:

http://www.ZDSDesign.com

135 Corporate Center Drive Suite 532 Scott Depot, WV 25560

TEL 304/755-0075

FAX 304/755-0076

THIS SQUARE APPEARS 1/2"x1/2"

ON FULL SIZE SHEETS

CLIENT:

XXX

C :\U se rs

\e di so n.

ad ki ns \D oc um en ts

\G

SD

2C

_2

4-

-3 0_

BL

D

G

L O

G

AN

_e di so n.

ad ki ns .rv t 8/

/2

:3

1:

P M

55-E-001

EA

TZ3

GSD-252-C

ELECTRICAL TITLE

SHEET

BUILDING 55 SECURITY

SYSTEM UPGRADES

130 STRATTON STREET

LOGAN, WV 25601

WEST VIRGINIA

GENERAL SERVICES

DIVISION

Electrical Sheet List

55-C001 COVER SHEET

55-E-001 ELECTRICAL TITLE SHEET

55-TD-101 DEMO PLAN FIRST FLOOR

55-TD-102 DEMO PLAN SECOND FLOOR

55-TD-103 DEMO PLAN THIRD FLOOR

55-TD-104 DEMO PLAN FOURTH FLOOR

55-TD-105 DEMO PLAN FIFTH FLOOR

55-TD-106 DEMO PLAN PENTHOUSE

55-TY-101 FIRST FLOOR SECURITY PLAN

55-TY-102 SECOND FLOOR SECURITY PLAN

55-TY-103 THIRD FLOOR SECURITY PLAN

55-TY-104 FOURTH FLOOR SECURITY PLAN

55-TY-105 FIFTH FLOOR SECURITY PLAN

55-TY-106 PENTHOUSE SECURITY PLAN

55-TY-501 SECURITY DETAILS

55-TY-502 SECURITY DETAILS

55-TY-601 SECURITY SCHEDULES

NO DATE REVISION

RECEIVING

VESTIBULE

RECEPTION

CONFERENCE

CONFERENCE

STORAGE

STAIR "A"

RECEIVING/RECYCLING

MECH. ROOM

STAIR "B"

CORRIDOR

GENERALSERVICES

OFFICE

TAX RECEPTION

OFFICE

WAITING

ELEVATORLOBBY

I.T.

JAN.CLOS.

M.T.

W.T.

HOSP.AREA

CONFERENCE

CORRIDOR

CORRIDOR

CK

CK

CK

CK

CK

CK

CK

KP

KP KP

KP

KP KP

MD

MD

MD

MD

MD

DCDCDC

DC

DC DC

DC

DC

DC

DC

DC

DC

DC

DCDCDCDC

DC

HS

HS

SC

P

CK

CK

HS

IC

M

ICM

DR

IC CK

IC CK ICCK

CK

CK

KP

AC

P

PS

IC

E

PS

PS

SWKS

HS

Aiphone AX-084C

2 - PS-2420UL

Network switch for security in this room credentialing workstation and camera monitor

1 3

FILE:

DRAWN BY:

CHECKED BY:

PROJ. NO:

DRAWING NO:

DRAWING TITLE:

PROJECT NAME:

http://www.ZDSDesign.com

135 Corporate Center Drive Suite 532 Scott Depot, WV 25560

TEL 304/755-0075

FAX 304/755-0076

THIS SQUARE APPEARS 1/2"x1/2"

ON FULL SIZE SHEETS

CLIENT:

XXX

C :\U se rs

\e di so n.

ad ki ns \D oc um en ts

\G

SD

2C

_2

4-

-3 0_

BL

D

G

L O

G

AN

_e di so n.

ad ki ns .rv t 8/

/2

:3

1:

P M

55-TD-101

EA

TZ3

GSD-252-C

DEMO PLAN FIRST

FLOOR

BUILDING 55 SECURITY

SYSTEM UPGRADES

130 STRATTON STREET

LOGAN, WV 25601

WEST VIRGINIA

GENERAL SERVICES

DIVISION

# KEYNOTES

1 INTERCOM AND CARD READER FOR VEHICLE GATE

2 INTERCOM AND CARD READER FOR PEDESTRIAN GATE

3 RELOCATE INTERCOM AND CARD READER TO CORRECT SIDE OF GATE FOR

OPERATION BY VEHICLE DRIVER.

1/8" = 1'-0"55-TD-101

1 Demo Security Plan-First Floor

SYSTEMS DEMOLITION NOTES

1 DISCONNECT AND REMOVE ONLY SYSTEM DEVICES SHOWN TO BE DEMOLISHED.

2 DISCONNECT AND REMOVE ASSOCIATED CONDUIT AND WIRE BACK TO LAST

REMAINING DEVICE. FURNISH AND INSTALL CONDUIT AND WIRE AS NECESSARY

FOR CONTINUITY OF CIRCUIT(S) TO ANY EXISTING DEVICES TO REMAIN.

COORDINATE AND VERIFY REQUIREMENTS WITH NEW WORK IN AREA.

3 FURNISH AND INSTALL CONDUIT AND/OR SYSTEMS WIRING AS NECESSARY FOR

CONTINUITY OF ANY SYSTEMS EQUIPMENT OR DEVICES TO REMAIN. MODIFY OR

REPLACE AS REQUIRED.

4 FURNISH AND INSTALL BLANK COVER PLATES FOR ALL EXISTING UNUSED

OPENINGS.

5 BUILDINGS THAT HAVE CAMERAS THAT WORK OR WOULD WORK IF THE

SOFTWARE AND LICENSES WERE CURRENT SHOULD HAVE NEW NVRS INSTALLED

AND THE EXISTING CAMERAS CONNECTED TO THEM. AS NEW CAMERAS ARE

INSTALLED, REMOVE OLD CAMERAS FROM THE SYSTEM.

6 THE EXISTING ACCESS CONTROL SYSTEM IS TO REMAIN IN USE UNTIL THE NEW

SYSTEM IS COMPLETE. DOORS SHOULD BE MIGRATED TO THE NEW SYSTEM ONE

AT A TIME UNTIL ALL ARE ON THE NEW SYSTEM. DURING THIS MIGRATION, NO

DOOR IS TO REMAIN UNSECURED OR INOPERABLE AT THE END OF A WORKDAY.

216 217

231A

228229

217A

CONFERENCE

WORK FORCE WAITING

CONFERENCE

OFFICE

OFFICE

RECEPTION

HOSP.AREA

WORK FORCE OPEN OFFICE

COPY

OFFICE

OFFICE

OFFICE

STAIR "A"

STORAGE INSURANCE COMMISSION

MECH. ROOM

STAIR "B"

CORRIDOR

HOSP.AREA

RECEPT.

REHAB SERV.WAITING

CORR.

CONFERENCE

OFFICE

OFFICE

OFFICE

OFFICE

OFFICE

OFFICEOFFICE

OFFICE

COPY/FILES

OFFICE

I.T.

J.C.

W.T.

M.T.

W.T.

M.T.

CORRIDOR

ELEV.LOBBY

FILE STORAGE

EVIDENCE

CK

CK

MD

MD

MD

HS

CK

CK

ES

DR

CK

ES

CK

CK

CK

CK

ES

CK

AC

P

PS

EL 1

FILE:

DRAWN BY:

CHECKED BY:

PROJ. NO:

DRAWING NO:

DRAWING TITLE:

PROJECT NAME:

http://www.ZDSDesign.com

135 Corporate Center Drive Suite 532 Scott Depot, WV 25560

TEL 304/755-0075

FAX 304/755-0076

THIS SQUARE APPEARS 1/2"x1/2"

ON FULL SIZE SHEETS

CLIENT:

XXX

C :\U se rs

\e di so n.

ad ki ns \D oc um en ts

\G

SD

2C

_2

4-

-3 0_

BL

D

G

L O

G

AN

_e di so n.

ad ki ns .rv t 8/

/2

:3

1:

P M

55-TD-102

EA

TZ3

GSD-252-C

DEMO PLAN SECOND

FLOOR

BUILDING 55 SECURITY

SYSTEM UPGRADES

130 STRATTON STREET

LOGAN, WV 25601

WEST VIRGINIA

GENERAL SERVICES

DIVISION

# KEYNOTES

1 REPLACE WITH NEW LOCK

1/8" = 1'-0"55-TD-102

1 Demo Security Plan-Second Floor

SYSTEMS DEMOLITION NOTES

1 DISCONNECT AND REMOVE ONLY SYSTEM DEVICES SHOWN TO BE DEMOLISHED.

2 DISCONNECT AND REMOVE ASSOCIATED CONDUIT AND WIRE BACK TO LAST

REMAINING DEVICE. FURNISH AND INSTALL CONDUIT AND WIRE AS NECESSARY

FOR CONTINUITY OF CIRCUIT(S) TO ANY EXISTING DEVICES TO REMAIN.

COORDINATE AND VERIFY REQUIREMENTS WITH NEW WORK IN AREA.

3 FURNISH AND INSTALL CONDUIT AND/OR SYSTEMS WIRING AS NECESSARY FOR

CONTINUITY OF ANY SYSTEMS EQUIPMENT OR DEVICES TO REMAIN. MODIFY OR

REPLACE AS REQUIRED.

4 FURNISH AND INSTALL BLANK COVER PLATES FOR ALL EXISTING UNUSED

OPENINGS.

5 BUILDINGS THAT HAVE CAMERAS THAT WORK OR WOULD WORK IF THE

SOFTWARE AND LICENSES WERE CURRENT SHOULD HAVE NEW NVRS INSTALLED

AND THE EXISTING CAMERAS CONNECTED TO THEM. AS NEW CAMERAS ARE

INSTALLED, REMOVE OLD CAMERAS FROM THE SYSTEM.

6 THE EXISTING ACCESS CONTROL SYSTEM IS TO REMAIN IN USE UNTIL THE NEW

SYSTEM IS COMPLETE. DOORS SHOULD BE MIGRATED TO THE NEW SYSTEM ONE

AT A TIME UNTIL ALL ARE ON THE NEW SYSTEM. DURING THIS MIGRATION, NO

304 303

305 306

308 307

311 310

312 313

315 314

301A 334

VISITATION

DHHR WAITING

CORRIDOR

INTERVIEW INTERVIEW(ADA)

INTERVIEW INTERVIEW(ADA)

INTERVIEW INTERVIEW

INTERVIEW INTERVIEW

INTERVIEW INTERVIEW

INTERVIEW INTERVIEW

OFFICE

SM.COPY

STAIR "A"

FILING

MECH. ROOM

CORRIDOR

STAIR "B"

OFFICE

HOSP.AREA

OFFICE

OFFICE

COPY/MAIL

M.D.T.

VIDEO

CORR. TOIL.

DHHR OPEN PLAN

W.T.

W.T.

M.T.

I.T.

J.C.

M.T.

ELEV.LOBBY

STOR.

RECEPTION

STOR.

OFFICE

CK

CK

CK

CK

DC DC

MD

MD

DR

PB

PB

PB PB

PB

PB

PB PB

PB PB

PB PB

MD

HS

HS

IAC

CK

IAC

CK

ES

ES

CK

IAC

AC

P

PS

PS

1 1

FILE:

DRAWN BY:

CHECKED BY:

PROJ. NO:

DRAWING NO:

DRAWING TITLE:

PROJECT NAME:

http://www.ZDSDesign.com

135 Corporate Center Drive Suite 532 Scott Depot, WV 25560

TEL 304/755-0075

FAX 304/755-0076

THIS SQUARE APPEARS 1/2"x1/2"

ON FULL SIZE SHEETS

CLIENT:

XXX

C :\U se rs

\e di so n.

ad ki ns \D oc um en ts

\G

SD

2C

_2

4-

-3 0_

BL

D

G

L O

G

AN

_e di so n.

ad ki ns .rv t 8/

/2

:3

1:

P M

55-TD-103

EA

TZ3

GSD-252-C

DEMO PLAN THIRD

FLOOR

BUILDING 55 SECURITY

SYSTEM UPGRADES

130 STRATTON STREET

LOGAN, WV 25601

WEST VIRGINIA

GENERAL SERVICES

DIVISION

# KEYNOTES

1 REMOVE AND TURN OVER TO DOHS.

1/8" = 1'-0"55-TD-103

1 Demo Security Plan-Third Floor

SYSTEMS DEMOLITION NOTES

1 DISCONNECT AND REMOVE ONLY SYSTEM DEVICES SHOWN TO BE DEMOLISHED.

2 DISCONNECT AND REMOVE ASSOCIATED CONDUIT AND WIRE BACK TO LAST

REMAINING DEVICE. FURNISH AND INSTALL CONDUIT AND WIRE AS NECESSARY

FOR CONTINUITY OF CIRCUIT(S) TO ANY EXISTING DEVICES TO REMAIN.

COORDINATE AND VERIFY REQUIREMENTS WITH NEW WORK IN AREA.

3 FURNISH AND INSTALL CONDUIT AND/OR SYSTEMS WIRING AS NECESSARY FOR

CONTINUITY OF ANY SYSTEMS EQUIPMENT OR DEVICES TO REMAIN. MODIFY OR

REPLACE AS REQUIRED.

4 FURNISH AND INSTALL BLANK COVER PLATES FOR ALL EXISTING UNUSED

OPENINGS.

5 BUILDINGS THAT HAVE CAMERAS THAT WORK OR WOULD WORK IF THE

SOFTWARE AND LICENSES WERE CURRENT SHOULD HAVE NEW NVRS INSTALLED

AND THE EXISTING CAMERAS CONNECTED TO THEM. AS NEW CAMERAS ARE

INSTALLED, REMOVE OLD CAMERAS FROM THE SYSTEM.

6 THE EXISTING ACCESS CONTROL SYSTEM IS TO REMAIN IN USE UNTIL THE NEW

SYSTEM IS COMPLETE. DOORS SHOULD BE MIGRATED TO THE NEW SYSTEM ONE

AT A TIME UNTIL ALL ARE ON THE NEW SYSTEM. DURING THIS MIGRATION, NO

406407

419420

422 416

BREAK ROOM

HOSP.AREA

DHHR OPENOFFICE PLAN

OFFICE

OFFICE

OFFICE

OFFICEOFFICE

STAIR "A"

UNDESIGNATED

GEN. SERVICES

MECH. ROOM

STAIR "B"

OFFICE

OFFICE

OFFICE

OFFICE

OFFICECOPY/STOR.

W.T.

W.T.

M.T.

M.T. HOSP.AREA

J.C.

I.T.

CORRIDOR

ELEV.LOBBY

HS

HS

CK

CK

CK

CK

CK

DC DC

DC DC

MD

MD

MD

AC

P

CK

CK

ES

SWKS

PS

ES005

FILE:

DRAWN BY:

CHECKED BY:

PROJ. NO:

DRAWING NO:

DRAWING TITLE:

PROJECT NAME:

http://www.ZDSDesign.com

135 Corporate Center Drive Suite 532 Scott Depot, WV 25560

TEL 304/755-0075

FAX 304/755-0076

THIS SQUARE APPEARS 1/2"x1/2"

ON FULL SIZE SHEETS

CLIENT:

XXX

C :\U se rs

\e di so n.

ad ki ns \D oc um en ts

\G

SD

2C

_2

4-

-3 0_

BL

D

G

L O

G

AN

_e di so n.

ad ki ns .rv t 8/

/2

:3

1:

P M

55-TD-104

EA

TZ3

GSD-252-C

DEMO PLAN FOURTH

FLOOR

BUILDING 55 SECURITY

SYSTEM UPGRADES

130 STRATTON STREET

LOGAN, WV 25601

WEST VIRGINIA

GENERAL SERVICES

DIVISION

# KEYNOTES

1/8" = 1'-0"55-TD-104

1 Demo Security Plan-Fourth Floor

SYSTEMS DEMOLITION NOTES

1 DISCONNECT AND REMOVE ONLY SYSTEM DEVICES SHOWN TO BE DEMOLISHED.

2 DISCONNECT AND REMOVE ASSOCIATED CONDUIT AND WIRE BACK TO LAST

REMAINING DEVICE. FURNISH AND INSTALL CONDUIT AND WIRE AS NECESSARY

FOR CONTINUITY OF CIRCUIT(S) TO ANY EXISTING DEVICES TO REMAIN.

COORDINATE AND VERIFY REQUIREMENTS WITH NEW WORK IN AREA.

3 FURNISH AND INSTALL CONDUIT AND/OR SYSTEMS WIRING AS NECESSARY FOR

CONTINUITY OF ANY SYSTEMS EQUIPMENT OR DEVICES TO REMAIN. MODIFY OR

REPLACE AS REQUIRED.

4 FURNISH AND INSTALL BLANK COVER PLATES FOR ALL EXISTING UNUSED

OPENINGS.

5 BUILDINGS THAT HAVE CAMERAS THAT WORK OR WOULD WORK IF THE

SOFTWARE AND LICENSES WERE CURRENT SHOULD HAVE NEW NVRS INSTALLED

AND THE EXISTING CAMERAS CONNECTED TO THEM. AS NEW CAMERAS ARE

INSTALLED, REMOVE OLD CAMERAS FROM THE SYSTEM.

6 THE EXISTING ACCESS CONTROL SYSTEM IS TO REMAIN IN USE UNTIL THE NEW

SYSTEM IS COMPLETE. DOORS SHOULD BE MIGRATED TO THE NEW SYSTEM ONE

AT A TIME UNTIL ALL ARE ON THE NEW SYSTEM. DURING THIS MIGRATION, NO

516517

UNDESIGNATED

DEPT.DIRECTOR

OFFICE

CONFERENCE

UNDESIGNATED

STAIR "A"

STAIR "C"

MECH.ROOM

STAIR "B"

HOSP.AREA

CORRIDOR

DHHR OPENOFFICE PLAN

OFFICE

OFFICE

OFFICECOPY/STOR.

CORRIDOR

M.T.

M.T.

W.T.

W.T.

I.T.

J.C.

CORRIDOR

ELEV.LOBBY

A B E F

C D

2.2

A.1 A.7

2.3

2.7

E.9E.3

2.1

2.5

THE COLUMN SIZES HAVE BEEN CHANGED TO MATCH THE 90% REVIEW SET

HS

CK

CK

CK

CK

CK

CK

DC DC

DC DC

MD

MD

MD

CK

ES

CK

AC

P

PS

CK

FILE:

DRAWN BY:

CHECKED BY:

PROJ. NO:

DRAWING NO:

DRAWING TITLE:

PROJECT NAME:

http://www.ZDSDesign.com

135 Corporate Center Drive Suite 532 Scott Depot, WV 25560

TEL 304/755-0075

FAX 304/755-0076

THIS SQUARE APPEARS 1/2"x1/2"

ON FULL SIZE SHEETS

CLIENT:

XXX

C :\U se rs

\e di so n.

ad ki ns \D oc um en ts

\G

SD

2C

_2

4-

-3 0_

BL

D

G

L O

G

AN

_e di so n.

ad ki ns .rv t 8/

/2

:3

1:

P M

55-TD-105

EA

TZ3

GSD-252-C

DEMO PLAN FIFTH

FLOOR

BUILDING 55 SECURITY

SYSTEM UPGRADES

130 STRATTON STREET

LOGAN, WV 25601

WEST VIRGINIA

GENERAL SERVICES

DIVISION

# KEYNOTES

1/8" = 1'-0"55-TD-105

1 Demo Security Plan-Fifth Floor

SYSTEMS DEMOLITION NOTES

1 DISCONNECT AND REMOVE ONLY SYSTEM DEVICES SHOWN TO BE DEMOLISHED.

2 DISCONNECT AND REMOVE ASSOCIATED CONDUIT AND WIRE BACK TO LAST

REMAINING DEVICE. FURNISH AND INSTALL CONDUIT AND WIRE AS NECESSARY

FOR CONTINUITY OF CIRCUIT(S) TO ANY EXISTING DEVICES TO REMAIN.

COORDINATE AND VERIFY REQUIREMENTS WITH NEW WORK IN AREA.

3 FURNISH AND INSTALL CONDUIT AND/OR SYSTEMS WIRING AS NECESSARY FOR

CONTINUITY OF ANY SYSTEMS EQUIPMENT OR DEVICES TO REMAIN. MODIFY OR

REPLACE AS REQUIRED.

4 FURNISH AND INSTALL BLANK COVER PLATES FOR ALL EXISTING UNUSED

OPENINGS.

5 BUILDINGS THAT HAVE CAMERAS THAT WORK OR WOULD WORK IF THE

SOFTWARE AND LICENSES WERE CURRENT SHOULD HAVE NEW NVRS INSTALLED

AND THE EXISTING CAMERAS CONNECTED TO THEM. AS NEW CAMERAS ARE

INSTALLED, REMOVE OLD CAMERAS FROM THE SYSTEM.

6 THE EXISTING ACCESS CONTROL SYSTEM IS TO REMAIN IN USE UNTIL THE NEW

SYSTEM IS COMPLETE. DOORS SHOULD BE MIGRATED TO THE NEW SYSTEM ONE

AT A TIME UNTIL ALL ARE ON THE NEW SYSTEM. DURING THIS MIGRATION, NO

P01

P02

P03

MECHANICAL EQUIP.

ELEV.MACH.

STAIR "C"

A B E F

C D

2.2

A.1 A.7

2.3

2.7

E.9E.3

2.1

2.5

THE COLUMN SIZES HAVE BEEN CHANGED TO MATCH THE 90% REVIEW SET

DC

CK

AC

P

PS

SF-1

STAIR PRESSURIZATION FAN

SF-1

STAIR PRESSURIZATION FAN

FILE:

DRAWN BY:

CHECKED BY:

PROJ. NO:

DRAWING NO:

DRAWING TITLE:

PROJECT NAME:

http://www.ZDSDesign.com

135 Corporate Center Drive Suite 532 Scott Depot, WV 25560

TEL 304/755-0075

FAX 304/755-0076

THIS SQUARE APPEARS 1/2"x1/2"

ON FULL SIZE SHEETS

CLIENT:

XXX

C :\U se rs

\e di so n.

ad ki ns \D oc um en ts

\G

SD

2C

_2

4-

-3 0_

BL

D

G

L O

G

AN

_e di so n.

ad ki ns .rv t 8/

/2

:3

1:

P M

55-TD-106

EA

TZ3

GSD-252-C

DEMO PLAN

PENTHOUSE

BUILDING 55 SECURITY

SYSTEM UPGRADES

130 STRATTON STREET

LOGAN, WV 25601

WEST VIRGINIA

GENERAL SERVICES

DIVISION

# KEYNOTES

1/8" = 1'-0"55-TD-106

1 Demo Security Plan-Penthouse

SYSTEMS DEMOLITION NOTES

1 DISCONNECT AND REMOVE ONLY SYSTEM DEVICES SHOWN TO BE DEMOLISHED.

2 DISCONNECT AND REMOVE ASSOCIATED CONDUIT AND WIRE BACK TO LAST

REMAINING DEVICE. FURNISH AND INSTALL CONDUIT AND WIRE AS NECESSARY

FOR CONTINUITY OF CIRCUIT(S) TO ANY EXISTING DEVICES TO REMAIN.

COORDINATE AND VERIFY REQUIREMENTS WITH NEW WORK IN AREA.

3 FURNISH AND INSTALL CONDUIT AND/OR SYSTEMS WIRING AS NECESSARY FOR

CONTINUITY OF ANY SYSTEMS EQUIPMENT OR DEVICES TO REMAIN. MODIFY OR

REPLACE AS REQUIRED.

4 FURNISH AND INSTALL BLANK COVER PLATES FOR ALL EXISTING UNUSED

OPENINGS.

5 BUILDINGS THAT HAVE CAMERAS THAT WORK OR WOULD WORK IF THE

SOFTWARE AND LICENSES WERE CURRENT SHOULD HAVE NEW NVRS INSTALLED

AND THE EXISTING CAMERAS CONNECTED TO THEM. AS NEW CAMERAS ARE

INSTALLED, REMOVE OLD CAMERAS FROM THE SYSTEM.

6 THE EXISTING ACCESS CONTROL SYSTEM IS TO REMAIN IN USE UNTIL THE NEW

SYSTEM IS COMPLETE. DOORS SHOULD BE MIGRATED TO THE NEW SYSTEM ONE

AT A TIME UNTIL ALL ARE ON THE NEW SYSTEM. DURING THIS MIGRATION, NO

RECEIVING

VESTIBULE

RECEPTION

CONFERENCE

CONFERENCE

STORAGE

STAIR "A"

RECEIVING/RECYCLING

MECH. ROOM

STAIR "B"

CORRIDOR

GENERALSERVICES

OFFICE

TAX RECEPTION

OFFICE

WAITING

ELEVATORLOBBY

I.T.

JAN.CLOS.

M.T.

W.T.

HOSP.AREA

CONFERENCE

CORRIDOR

CORRIDOR

KP

KP KP

KP KP

MD

MD

MD

MD

MD

HS

HS

SC

P

HS

IC

M

ICM

IC

IC IC

KP

IC

E

HS

CR

CR

CR

CR

CR

CR

CR

CR

CR

CR

CR

AC

P

CR

CR

CR

DC

DC

DC

DC

DC DC DC DC

DC

DC

DC

DC

DCDCDC

DC DC

SW

KS

MO

N

MO

N

DR

DC DC

DC

MO

N

KP

SCP

CWKS

Aiphone AX-084C

2 - PS-2420UL

Existing Network switch for security in this room

C001

TYPE J

C004

TYPE J

C015

TYPE L

C003

TYPE J

C002

TYPE K

C006

TYPE A

C007

TYPE A

C010

TYPE A

C009

TYPE C

C008

TYPE C

C013

TYPE A

C011

TYPE A

C012

TYPE A

C005

TYPE J

DC013

DC012 DC011 DC010 DC009 DC008

DC006

DC005

DC021

DC019 DC020

DC014

DC016

DC015

DC018

DC017

DC001 DC002 DC003 DC004

CR001

CR014

CR012

CR013CR010

CR009

CR006

CR005

CR003

CR004 CR015

CR002

CR008

CR007

M001

M002SWKS01

DR001

ACP001

IC001

IC002

IC004

IC003

IC005

IC006

6 8

SNR001

M003

CWKS01

FILE:

DRAWN BY:

CHECKED BY:

PROJ. NO:

DRAWING NO:

DRAWING TITLE:

PROJECT NAME:

http://www.ZDSDesign.com

135 Corporate Center Drive Suite 532 Scott Depot, WV 25560

TEL 304/755-0075

FAX 304/755-0076

THIS SQUARE APPEARS 1/2"x1/2"

ON FULL SIZE SHEETS

CLIENT:

XXX

C :\U se rs

\e di so n.

ad ki ns \D oc um en ts

\G

SD

2C

_2

4-

-3 0_

BL

D

G

L O

G

AN

_e di so n.

ad ki ns .rv t 8/

/2

:3

1:

P M

55-TY-101

EA

TZ3

GSD-252-C

FIRST FLOOR SECURITY

PLAN

BUILDING 55 SECURITY

SYSTEM UPGRADES

130 STRATTON STREET

LOGAN, WV 25601

WEST VIRGINIA

GENERAL SERVICES

DIVISION

1/8" = 1'-0"55-TY-101

1 Security Plan-First Floor

KEYNOTES

1 EXISTING FIRE ALARM RELAY TO UNLOCK DOOR IN EVENT OF FIRE ALARM. RETAIN

AND RECONNECT TO NEW ACCESS CONTROL SYSTEM.

2 EXISTING ELECTRIFIED HARDWARE AND MAGLOCKS WITH DELAYED EGRESS TO

REMAIN. VERIFY FUNCTIONALITY WITH OWNER AND RETAIN.

3 EXISTING ELECTRIFIED HARDWARE WITH SCHEDULED LOCKING (UNLOCKED

DURING NORMAL BUSINESS HOURS) AND REMOTE RELEASE TO REMAIN. PROVIDE

NEW DOOR RELEASE BUTTON. VERIFY LOCK SCHEDULE WITH OWNER.

4 EXISTING ELECTRIFIED HARDWARE WITH REMOTE RELEASE TO REMAIN. PROVIDE

NEW DOOR RELEASE BUTTON.

5 PROVIDE TWO 120V, 20A CIRCUITS FOR NEW SECURITY NETWORK RACK. CIRCUIT

TO NEAREST ELECTRICAL PANEL.

6 INTERCOM AND CARD READER FOR VEHICLE GATE

7 INTERCOM AND CARD READER FOR PEDESTRIAN GATE

8 RELOCATE INTERCOM AND CARD READER TO CORRECT SIDE OF GATE FOR

OPERATION BY VEHICLE DRIVER.

9 4 BUTTON DOOR RELEASE PANEL

10 SECURITY WORKSTATION WITH QTY 3 - 34" CURVED MONITORS

11 KEYPAD FOR NEW PANIC ALARM SYSTEM

12 NEW INTRUSION DETECTION/PANIC ALARM CONTROL PANEL

13 NEW SECURITY NETWORK RACK. PROVIDE 12 STRAND MM OM4 ARMOURED FIBER

TO SNR002. TERMINATE FIBER IN FIBER TERMINATION PANEL AT BOTH ENDS. SEE

SPECIFICATIONS AND DETAIL 1 ON SHEET 55-TY-501.

14 NEW CREDENTIALLING WORKSTATION. COORDINATE EXACT LOCATION WITH

OWNER.

SECURITY SYSTEM SHEET NOTES

A SEE DETAIL SHEET FOR SECURITY CAMERA MOUNTING

B SEE SECURITY DEVICE SCHEDULE FOR ADDITIONAL INFORMATION

C ALL COMMUNICATION CABLES SHALL BE INSTALLED IN CONDUIT, CABLE TRAY, OR

SUPPORTED BY CABLE HOOKS. PROVIDE BUSHINGS AT THE ENDS OF ALL

CONDUITS WHERE STUBBED ABOVE ACCESSIBLE CEILINGS OR WHERE DROPPED

INTO CABLE TRAYS. PROVIDE CABLE HOOKS ABOVE ACCESSIBLE CEILINGS FOR

CABLE INSTALLATION WHERE NOT INSTALLED IN A CONDUIT OR CABLE TRAY.

D BUILDINGS THAT HAVE CAMERAS THAT WORK OR WOULD WORK IF THE

SOFTWARE AND LICENSES WERE CURRENT SHOULD HAVE NEW NVRS INSTALLED

AND THE EXISTING CAMERAS CONNECTED TO THEM. AS NEW CAMERAS ARE

INSTALLED, REMOVE OLD CAMERAS FROM THE SYSTEM.

E ALL CABLES AND DEVICES TO BE LABELED. SEE SPECIFICATION AND DETAILS

FOR SPECIFIC REQUIREMENTS.

F THE EXISTING ACCESS CONTROL SYSTEM IS TO REMAIN IN USE UNTIL THE NEW

SYSTEM IS COMPLETE. DOORS SHOULD BE MIGRATED TO THE NEW SYSTEM ONE

AT A TIME UNTIL ALL ARE ON THE NEW SYSTEM. DURING THIS MIGRATION, NO

DOOR IS TO REMAIN UNSECURED OR INOPERABLE AT THE END OF A WORKDAY.

G PROVIDE SURGE PROTECTION FOR ALL EXTERIOR CAMERAS.

216 217

231A

228229

217A

CONFERENCE

WORK FORCE WAITING

CONFERENCE

OFFICE

OFFICE

RECEPTION

HOSP.AREA

WORK FORCE OPEN OFFICE

COPY

OFFICE

OFFICE

OFFICE

STAIR "A"

STORAGE INSURANCE COMMISSION

MECH. ROOM

STAIR "B"

CORRIDOR

HOSP.AREA

RECEPT.

REHAB SERV.WAITING

CORR.

CONFERENCE

OFFICE

OFFICE

OFFICE

OFFICE

OFFICE

OFFICEOFFICE

OFFICE

COPY/FILES

OFFICE

I.T.

J.C.

W.T.

M.T.

W.T.

M.T.

CORRIDOR

ELEV.LOBBY

FILE STORAGE

EVIDENCE

MD

MD

MD

HS

ES

ES

ES

CR

CR

CR

CR

CR

CR

CR

CR

CR

EL

AC

P

DR

CR

CR

EL EL

DC DC

DCDC

C019

TYPE A

C020

TYPE A

C023

TYPE C

C021

TYPE A

C022

TYPE C

CR016

CR017

CR020

CR021

CR022

CR019

CR018

CR023

CR024

DR002

ACP002

EL001

REPLACE

EXISTING

CR049

ES002

ES001

ES006

SNR002

CR050

EL004

NEW

EL005

NEW

DC037 DC038

DC035

DC036

FILE:

DRAWN BY:

CHECKED BY:

PROJ. NO:

DRAWING NO:

DRAWING TITLE:

PROJECT NAME:

http://www.ZDSDesign.com

135 Corporate Center Drive Suite 532 Scott Depot, WV 25560

TEL 304/755-0075

FAX 304/755-0076

THIS SQUARE APPEARS 1/2"x1/2"

ON FULL SIZE SHEETS

CLIENT:

XXX

C :\U se rs

\e di so n.

ad ki ns \D oc um en ts

\G

SD

2C

_2

4-

-3 0_

BL

D

G

L O

G

AN

_e di so n.

ad ki ns .rv t 8/

/2

:3

1:

P M

55-TY-102

EA

TZ3

GSD-252-C

SECOND FLOOR

SECURITY PLAN

BUILDING 55 SECURITY

SYSTEM UPGRADES

130 STRATTON STREET

LOGAN, WV 25601

WEST VIRGINIA

GENERAL SERVICES

DIVISION

1/8" = 1'-0"55-TY-102

1 Security Plan-Second Floor

KEYNOTES

1 EXISTING FIRE ALARM RELAY TO UNLOCK DOOR IN EVENT OF FIRE ALARM. RETAIN

AND RECONNECT TO NEW ACCESS CONTROL SYSTEM.

2 EXISTING ELECTRIFIED HARDWARE AND MAGLOCKS WITH DELAYED EGRESS TO

REMAIN. VERIFY FUNCTIONALITY WITH OWNER AND RETAIN.

3 REPLACE WITH NEW ELECTRIFIED LOCK. MATCH EXISTING.

4 NEW ELECTRIFIED HARDWARE WITH SCHEDULED LOCKING (UNLOCKED DURING

NORMAL BUSINESS HOURS). FURNISH HARDWARE TO MATCH EXISTING.

CONTRACTOR TO FIELD VERIFY EXACT HARDWARE REQUIREMENTS.

COORDINATE LOCK SCHEDULE WITH OWNER.

5 EXISTING ELECTRIFIED HARDWARE WITH REMOTE RELEASE TO REMAIN. PROVIDE

NEW DOOR RELEASE BUTTON.

6 NEW SECURITY NETWORK RACK. PROVIDE 12 STRAND MM OM4 ARMOURED FIBER

TO SNR001 AND SNR003. TERMINATE FIBER IN FIBER TERMINATION PANEL AT

BOTH ENDS. SEE SPECIFICATIONS AND DETAIL 1 ON SHEET 55-TY-501.

7 EXISTING ELECTRIFIED HARDWARE WITH SCHEDULED LOCKING (UNLOCKED

DURING NORMAL BUSINESS HOURS). TO REMAIN. VERIFY LOCK SCHEDULE WITH

OWNER.

8 PROVIDE TWO 120V, 20A CIRCUITS FOR NEW SECURITY NETWORK RACK. CIRCUIT

TO NEAREST ELECTRICAL PANEL.

SECURITY SYSTEM SHEET NOTES

A SEE DETAIL SHEET FOR SECURITY CAMERA MOUNTING

B SEE SECURITY DEVICE SCHEDULE FOR ADDITIONAL INFORMATION

C ALL COMMUNICATION CABLES SHALL BE INSTALLED IN CONDUIT, CABLE TRAY, OR

SUPPORTED BY CABLE HOOKS. PROVIDE BUSHINGS AT THE ENDS OF ALL

CONDUITS WHERE STUBBED ABOVE ACCESSIBLE CEILINGS OR WHERE DROPPED

INTO CABLE TRAYS. PROVIDE CABLE HOOKS ABOVE ACCESSIBLE CEILINGS FOR

CABLE INSTALLATION WHERE NOT INSTALLED IN A CONDUIT OR CABLE TRAY.

D BUILDINGS THAT HAVE CAMERAS THAT WORK OR WOULD WORK IF THE

SOFTWARE AND LICENSES WERE CURRENT SHOULD HAVE NEW NVRS INSTALLED

AND THE EXISTING CAMERAS CONNECTED TO THEM. AS NEW CAMERAS ARE

INSTALLED, REMOVE OLD CAMERAS FROM THE SYSTEM.

E ALL CABLES AND DEVICES TO BE LABELED. SEE SPECIFICATION AND DETAILS

FOR SPECIFIC REQUIREMENTS.

F THE EXISTING ACCESS CONTROL SYSTEM IS TO REMAIN IN USE UNTIL THE NEW

SYSTEM IS COMPLETE. DOORS SHOULD BE MIGRATED TO THE NEW SYSTEM ONE

AT A TIME UNTIL ALL ARE ON THE NEW SYSTEM. DURING THIS MIGRATION, NO

DOOR IS TO REMAIN UNSECURED OR INOPERABLE AT THE END OF A WORKDAY.

304 303

305 306

308 307

311 310

312 313

315 314

301A 334

VISITATION

DHHR WAITING

CORRIDOR

INTERVIEW INTERVIEW(ADA)

INTERVIEW INTERVIEW(ADA)

INTERVIEW INTERVIEW

INTERVIEW INTERVIEW

INTERVIEW INTERVIEW

INTERVIEW INTERVIEW

OFFICE

SM.COPY

STAIR "A"

FILING

MECH. ROOM

CORRIDOR

STAIR "B"

OFFICE

HOSP.AREA

OFFICE

OFFICE

COPY/MAIL

M.D.T.

VIDEO

CORR. TOIL.

DHHR OPEN PLAN

W.T.

W.T.

M.T.

I.T.

J.C.

M.T.

ELEV.LOBBY

STOR.

RECEPTION

STOR.

OFFICE

MD

MD

MD

HS

HS

IAC

IAC

ES

ES

IAC

CR

CR

CR

CR

CR

CR

CR

DC DC

DC DC

AC

P

EL EL

DR

PB PB

PB PB

PB PB

PB

PB

PB PB

PB

PB

PB

PB

PB

PB

SWR

C024

TYPE A

C025

TYPE A

C026

TYPE A

C027

TYPE A

C029

TYPE A

C028

TYPE C

CR025

CR026

CR027

CR028

CR029

CR030

CR031

EL002

NEW

EL003

NEW

DC024 DC025

ACP003

DC022

DC023

DR003

IAC003

IAC001

IAC002

SNR003

C039

TYPE C

C040

TYPE C

C041

TYPE A

C042

TYPE A

PB001

PB002

PB003 PB004

PB006PB005

PB007 PB008

PB009 PB010

PB011 PB012

PB013

PB016

PB015PB014

FILE:

DRAWN BY:

CHECKED BY:

PROJ. NO:

DRAWING NO:

DRAWING TITLE:

PROJECT NAME:

http://www.ZDSDesign.com

135 Corporate Center Drive Suite 532 Scott Depot, WV 25560

TEL 304/755-0075

FAX 304/755-0076

THIS SQUARE APPEARS 1/2"x1/2"

ON FULL SIZE SHEETS

CLIENT:

XXX

C :\U se rs

\e di so n.

ad ki ns \D oc um en ts

\G

SD

2C

_2

4-

-3 0_

BL

D

G

L O

G

AN

_e di so n.

ad ki ns .rv t 8/

/2

:3

1:

P M

55-TY-103

EA

TZ3

GSD-252-C

THIRD FLOOR SECURITY

PLAN

BUILDING 55 SECURITY

SYSTEM UPGRADES

130 STRATTON STREET

LOGAN, WV 25601

WEST VIRGINIA

GENERAL SERVICES

DIVISION

1/8" = 1'-0"55-TY-103

1 Security Plan-Third Floor

KEYNOTES

1 EXISTING FIRE ALARM RELAY TO UNLOCK DOOR IN EVENT OF FIRE ALARM. RETAIN

AND RECONNECT TO NEW ACCESS CONTROL SYSTEM.

2 EXISTING ELECTRIFIED HARDWARE AND MAGLOCKS WITH DELAYED EGRESS TO

REMAIN. VERIFY FUNCTIONALITY WITH OWNER AND RETAIN.

3 NEW ELECTRIFIED HARDWARE WITH SCHEDULED LOCKING (UNLOCKED DURING

NORMAL BUSINESS HOURS). FURNISH HARDWARE TO MATCH EXISTING.

CONTRACTOR TO FIELD VERIFY EXACT HARDWARE REQUIREMENTS.

COORDINATE LOCK SCHEDULE WITH OWNER.

4 EXISTING ELECTRIFIED HARDWARE WITH REMOTE RELEASE TO REMAIN. PROVIDE

NEW DOOR RELEASE BUTTON.

5 2 BUTTON DOOR RELEASE PANEL

6 SECURITY SYSTEM WIRELESS RECEIVER FOR WIRELESS PANIC BUTTONS.

7 NEW SECURITY NETWORK RACK. PROVIDE 12 STRAND MM OM4 ARMOURED FIBER

TO SNR002 AND SNR004. TERMINATE FIBER IN FIBER TERMINATION PANEL AT

BOTH ENDS. SEE SPECIFICATIONS AND DETAIL 1 ON SHEET 55-TY-501.

8 PROVIDE TWO 120V, 20A CIRCUITS FOR NEW SECURITY NETWORK RACK. CIRCUIT

TO NEAREST ELECTRICAL PANEL.

9 EXISTING SCHLAGE AD-300 WIRED NETWORK LOCK. PROVIDE REQUIRED

INTERFACE TO INTEGRATE INTO NEW SYSTEM.

SECURITY SYSTEM SHEET NOTES

A SEE DETAIL SHEET FOR SECURITY CAMERA MOUNTING

B SEE SECURITY DEVICE SCHEDULE FOR ADDITIONAL INFORMATION

C ALL COMMUNICATION CABLES SHALL BE INSTALLED IN CONDUIT, CABLE TRAY, OR

SUPPORTED BY CABLE HOOKS. PROVIDE BUSHINGS AT THE ENDS OF ALL

CONDUITS WHERE STUBBED ABOVE ACCESSIBLE CEILINGS OR WHERE DROPPED

INTO CABLE TRAYS. PROVIDE CABLE HOOKS ABOVE ACCESSIBLE CEILINGS FOR

CABLE INSTALLATION WHERE NOT INSTALLED IN A CONDUIT OR CABLE TRAY.

D BUILDINGS THAT HAVE CAMERAS THAT WORK OR WOULD WORK IF THE

SOFTWARE AND LICENSES WERE CURRENT SHOULD HAVE NEW NVRS INSTALLED

AND THE EXISTING CAMERAS CONNECTED TO THEM. AS NEW CAMERAS ARE

INSTALLED, REMOVE OLD CAMERAS FROM THE SYSTEM.

E ALL CABLES AND DEVICES TO BE LABELED. SEE SPECIFICATION AND DETAILS

FOR SPECIFIC REQUIREMENTS.

F THE EXISTING ACCESS CONTROL SYSTEM IS TO REMAIN IN USE UNTIL THE NEW

SYSTEM IS COMPLETE. DOORS SHOULD BE MIGRATED TO THE NEW SYSTEM ONE

AT A TIME UNTIL ALL ARE ON THE NEW SYSTEM. DURING THIS MIGRATION, NO

DOOR IS TO REMAIN UNSECURED OR INOPERABLE AT THE END OF A WORKDAY.

406407

419420

422 416

BREAK ROOM

HOSP.AREA

DHHR OPENOFFICE PLAN

OFFICE

OFFICE

OFFICE

OFFICEOFFICE

STAIR "A"

UNDESIGNATED

GEN. SERVICES

MECH. ROOM

STAIR "B"

OFFICE

OFFICE

OFFICE

OFFICE

OFFICECOPY/STOR.

W.T.

W.T.

M.T.

M.T. HOSP.AREA

J.C.

I.T.

CORRIDOR

ELEV.LOBBY

HS

HS

MD

MD

MD

ES

SWKS

AC

P

CR

CR

CR

CR

CR

CR

CR

DC DC

DCDC

C033

TYPE A

C034

TYPE A

DC026

DC027

CR035

CR034

CR036

CR037

CR032

CR033

CR038

DC029DC028

ES005

ACP004

SNR004

FILE:

DRAWN BY:

CHECKED BY:

PROJ. NO:

DRAWING NO:

DRAWING TITLE:

PROJECT NAME:

http://www.ZDSDesign.com

135 Corporate Center Drive Suite 532 Scott Depot, WV 25560

TEL 304/755-0075

FAX 304/755-0076

THIS SQUARE APPEARS 1/2"x1/2"

ON FULL SIZE SHEETS

CLIENT:

XXX

C :\U se rs

\e di so n.

ad ki ns \D oc um en ts

\G

SD

2C

_2

4-

-3 0_

BL

D

G

L O

G

AN

_e di so n.

ad ki ns .rv t 8/

/2

:3

1:

P M

55-TY-104

EA

TZ3

GSD-252-C

FOURTH FLOOR

SECURITY PLAN

BUILDING 55 SECURITY

SYSTEM UPGRADES

130 STRATTON STREET

LOGAN, WV 25601

WEST VIRGINIA

GENERAL SERVICES

DIVISION

1/8" = 1'-0"55-TY-104

1 Security Plan-Fourth Floor

KEYNOTES

1 EXISTING FIRE ALARM RELAY TO UNLOCK DOOR IN EVENT OF FIRE ALARM. RETAIN

AND RECONNECT TO NEW ACCESS CONTROL SYSTEM.

2 EXISTING ELECTRIFIED HARDWARE AND MAGLOCKS WITH DELAYED EGRESS TO

REMAIN. VERIFY FUNCTIONALITY WITH OWNER AND RETAIN.

3 NEW SECURITY NETWORK RACK. PROVIDE 12 STRAND MM OM4 ARMOURED FIBER

TO SNR003 AND SNR005. TERMINATE FIBER IN FIBER TERMINATION PANEL AT

BOTH ENDS. SEE SPECIFICATIONS AND DETAIL 1 ON SHEET 55-TY-501.

4 PROVIDE TWO 120V, 20A CIRCUITS FOR NEW SECURITY NETWORK RACK. CIRCUIT

TO NEAREST ELECTRICAL PANEL.

SECURITY SYSTEM SHEET NOTES

A SEE DETAIL SHEET FOR SECURITY CAMERA MOUNTING

B SEE SECURITY DEVICE SCHEDULE FOR ADDITIONAL INFORMATION

C ALL COMMUNICATION CABLES SHALL BE INSTALLED IN CONDUIT, CABLE TRAY, OR

SUPPORTED BY CABLE HOOKS. PROVIDE BUSHINGS AT THE ENDS OF ALL

CONDUITS WHERE STUBBED ABOVE ACCESSIBLE CEILINGS OR WHERE DROPPED

INTO CABLE TRAYS. PROVIDE CABLE HOOKS ABOVE ACCESSIBLE CEILINGS FOR

CABLE INSTALLATION WHERE NOT INSTALLED IN A CONDUIT OR CABLE TRAY.

D BUILDINGS THAT HAVE CAMERAS THAT WORK OR WOULD WORK IF THE

SOFTWARE AND LICENSES WERE CURRENT SHOULD HAVE NEW NVRS INSTALLED

AND THE EXISTING CAMERAS CONNECTED TO THEM. AS NEW CAMERAS ARE

INSTALLED, REMOVE OLD CAMERAS FROM THE SYSTEM.

E ALL CABLES AND DEVICES TO BE LABELED. SEE SPECIFICATION AND DETAILS

FOR SPECIFIC REQUIREMENTS.

F THE EXISTING ACCESS CONTROL SYSTEM IS TO REMAIN IN USE UNTIL THE NEW

SYSTEM IS COMPLETE. DOORS SHOULD BE MIGRATED TO THE NEW SYSTEM ONE

AT A TIME UNTIL ALL ARE ON THE NEW SYSTEM. DURING THIS MIGRATION, NO

DOOR IS TO REMAIN UNSECURED OR INOPERABLE AT THE END OF A WORKDAY.

516517

UNDESIGNATED

DEPT.DIRECTOR

OFFICE

CONFERENCE

UNDESIGNATED

STAIR "A"

STAIR "C"

MECH.ROOM

STAIR "B"

HOSP.AREA

CORRIDOR

DHHR OPENOFFICE PLAN

OFFICE

OFFICE

OFFICECOPY/STOR.

CORRIDOR

M.T.

M.T.

W.T.

W.T.

I.T.

J.C.

CORRIDOR

ELEV.LOBBY

A B E F

C D

2.2

A.1 A.7

2.3

2.7

E.9E.3

2.1

2.5

THE COLUMN SIZES HAVE BEEN CHANGED TO MATCH THE 90% REVIEW SET

HS

MD

MD

MD

ES

CR

CR

CR

CR

CR

CR

CR

CR

DC DC

DC DC

AC

P

CR039

CR040

CR041

CR043

CR042

DC030

DC031

C037

TYPE A

CR044

ACP005

C038

TYPE A

DC032 DC033

CR046

C035

TYPE B

CR047

ES007

SNR005

FILE:

DRAWN BY:

CHECKED BY:

PROJ. NO:

DRAWING NO:

DRAWING TITLE:

PROJECT NAME:

http://www.ZDSDesign.com

135 Corporate Center Drive Suite 532 Scott Depot, WV 25560

TEL 304/755-0075

FAX 304/755-0076

THIS SQUARE APPEARS 1/2"x1/2"

ON FULL SIZE SHEETS

CLIENT:

XXX

C :\U se rs

\e di so n.

ad ki ns \D oc um en ts

\G

SD

2C

_2

4-

-3 0_

BL

D

G

L O

G

AN

_e di so n.

ad ki ns .rv t 8/

/2

:3

1:

P M

55-TY-105

EA

TZ3

GSD-252-C

FIFTH FLOOR SECURITY

PLAN

BUILDING 55 SECURITY

SYSTEM UPGRADES

130 STRATTON STREET

LOGAN, WV 25601

WEST VIRGINIA

GENERAL SERVICES

DIVISION

1/8" = 1'-0"55-TY-105

1 Security Plan-Fifth Floor

KEYNOTES

1 EXISTING FIRE ALARM RELAY TO UNLOCK DOOR IN EVENT OF FIRE ALARM. RETAIN

AND RECONNECT TO NEW ACCESS CONTROL SYSTEM.

2 EXISTING ELECTRIFIED HARDWARE AND MAGLOCKS WITH DELAYED EGRESS TO

REMAIN. VERIFY FUNCTIONALITY WITH OWNER AND RETAIN.

3 IN-CAB CARD READER. CURRENT CONFIGURATION LIMITS ACCESS TO THE

FOURTH, AND FIFTH FLOORS WITHOUT A VALID CREDENTIAL.

4 NEW SECURITY NETWORK RACK. PROVIDE 12 STRAND MM OM4 ARMOURED FIBER

TO SNR004. TERMINATE FIBER IN FIBER TERMINATION PANEL AT BOTH ENDS.

SEE SPECIFICATIONS AND DETAIL 1 ON SHEET 55-TY-501.

5 PROVIDE TWO 120V, 20A CIRCUITS FOR NEW SECURITY NETWORK RACK. CIRCUIT

TO NEAREST ELECTRICAL PANEL.

SECURITY SYSTEM SHEET NOTES

A SEE DETAIL SHEET FOR SECURITY CAMERA MOUNTING

B SEE SECURITY DEVICE SCHEDULE FOR ADDITIONAL INFORMATION

C ALL COMMUNICATION CABLES SHALL BE INSTALLED IN CONDUIT, CABLE TRAY, OR

SUPPORTED BY CABLE HOOKS. PROVIDE BUSHINGS AT THE ENDS OF ALL

CONDUITS WHERE STUBBED ABOVE ACCESSIBLE CEILINGS OR WHERE DROPPED

INTO CABLE TRAYS. PROVIDE CABLE HOOKS ABOVE ACCESSIBLE CEILINGS FOR

CABLE INSTALLATION WHERE NOT INSTALLED IN A CONDUIT OR CABLE TRAY.

D BUILDINGS THAT HAVE CAMERAS THAT WORK OR WOULD WORK IF THE

SOFTWARE AND LICENSES WERE CURRENT SHOULD HAVE NEW NVRS INSTALLED

AND THE EXISTING CAMERAS CONNECTED TO THEM. AS NEW CAMERAS ARE

INSTALLED, REMOVE OLD CAMERAS FROM THE SYSTEM.

E ALL CABLES AND DEVICES TO BE LABELED. SEE SPECIFICATION AND DETAILS

FOR SPECIFIC REQUIREMENTS.

F THE EXISTING ACCESS CONTROL SYSTEM IS TO REMAIN IN USE UNTIL THE NEW

SYSTEM IS COMPLETE. DOORS SHOULD BE MIGRATED TO THE NEW SYSTEM ONE

AT A TIME UNTIL ALL ARE ON THE NEW SYSTEM. DURING THIS MIGRATION, NO

DOOR IS TO REMAIN UNSECURED OR INOPERABLE AT THE END OF A WORKDAY.

P01

P02

P03

MECHANICAL EQUIP.

ELEV.MACH.

STAIR "C"

A B E F

C D

2.2

A.1 A.7

2.3

2.7

E.9E.3

2.1

2.5

THE COLUMN SIZES HAVE BEEN CHANGED TO MATCH THE 90% REVIEW SET

DC

CR

AC

P

SF-1

STAIR PRESSURIZATION FAN

SF-1

STAIR PRESSURIZATION FAN

CR048

ACP006

DC034

FILE:

DRAWN BY:

CHECKED BY:

PROJ. NO:

DRAWING NO:

DRAWING TITLE:

PROJECT NAME:

http://www.ZDSDesign.com

135 Corporate Center Drive Suite 532 Scott Depot, WV 25560

TEL 304/755-0075

FAX 304/755-0076

THIS SQUARE APPEARS 1/2"x1/2"

ON FULL SIZE SHEETS

CLIENT:

XXX

C :\U se rs

\e di so n.

ad ki ns \D oc um en ts

\G

SD

2C

_2

4-

-3 0_

BL

D

G

L O

G

AN

_e di so n.

ad ki ns .rv t 8/

/2

:3

1:

P M

55-TY-106

EA

TZ3

GSD-252-C

PENTHOUSE SECURITY

PLAN

BUILDING 55 SECURITY

SYSTEM UPGRADES

130 STRATTON STREET

LOGAN, WV 25601

WEST VIRGINIA

GENERAL SERVICES

DIVISION

1/8" = 1'-0"55-TY-106

1 Security Plan-Penthouse

KEYNOTES

1 IN-CAB CARD READER. CURRENT CONFIGURATION LIMITS ACCESS TO 4TH AND

5TH FLOORS, PENTHOUSE, AND REAR DOOR ON ALL FLOORS.

2 ACCESS CONTROL PANEL FOR IN-CAB CARD READERS. PROVIDE OUTPUTS FOR

ALL FLOORS SERVED BY THE ELEVATORS FOR BOTH FRONT AND REAR DOORS.

ACCESS SHALL BE CONTROLLABLE BY THE INDIVIDUAL FLOOR. CURRENT

CONFIGURATION LIMITS ACCESS TO THE 4TH AND 5TH FLOORS, PENTHOUSE, AND

REAR DOOR ON ALL FLOORS WITHOUT A VALID CREDENTIAL.

SECURITY SYSTEM SHEET NOTES

A SEE DETAIL SHEET FOR SECURITY CAMERA MOUNTING

B SEE SECURITY DEVICE SCHEDULE FOR ADDITIONAL INFORMATION

C ALL COMMUNICATION CABLES SHALL BE INSTALLED IN CONDUIT, CABLE TRAY, OR

SUPPORTED BY CABLE HOOKS. PROVIDE BUSHINGS AT THE ENDS OF ALL

CONDUITS WHERE STUBBED ABOVE ACCESSIBLE CEILINGS OR WHERE DROPPED

INTO CABLE TRAYS. PROVIDE CABLE HOOKS ABOVE ACCESSIBLE CEILINGS FOR

CABLE INSTALLATION WHERE NOT INSTALLED IN A CONDUIT OR CABLE TRAY.

D BUILDINGS THAT HAVE CAMERAS THAT WORK OR WOULD WORK IF THE

SOFTWARE AND LICENSES WERE CURRENT SHOULD HAVE NEW NVRS INSTALLED

AND THE EXISTING CAMERAS CONNECTED TO THEM. AS NEW CAMERAS ARE

INSTALLED, REMOVE OLD CAMERAS FROM THE SYSTEM.

E ALL CABLES AND DEVICES TO BE LABELED. SEE SPECIFICATION AND DETAILS

FOR SPECIFIC REQUIREMENTS.

F THE EXISTING ACCESS CONTROL SYSTEM IS TO REMAIN IN USE UNTIL THE NEW

SYSTEM IS COMPLETE. DOORS SHOULD BE MIGRATED TO THE NEW SYSTEM ONE

AT A TIME UNTIL ALL ARE ON THE NEW SYSTEM. DURING THIS MIGRATION, NO

DOOR IS TO REMAIN UNSECURED OR INOPERABLE AT THE END OF A WORKDAY.

FIBER TERMINATION PANEL

96TB NVR

2000VA UPS FOR NVR

2000VA UPS FOR APP. AND

SWITCH

BLANK PANEL

24 PORT SWITCH

CAT 6 PATCH PANEL

VENT PANEL

VENT PANEL

VENT PANEL

BRUSH GROMMET PANEL

BLANK PANEL

BLANK PANEL

BLANK PANEL

VENT PANEL

24 PORT SWITCH

CAT 6 PATCH PANEL

12U WALL MOUNTED

SECURITY NETWORK

RACK SNR005

12-STRAND

FIBER OPTIC CABLE

12-STRAND

FIBER OPTIC CABLE

12-STRAND

FIBER OPTIC CABLE

12-STRAND

FIBER OPTIC CABLE

ACCESS

CONTROL

PANEL

ACP001

ACCESS

CONTROL

PANEL

ACP002

ACCESS

CONTROL

PANEL

ACP003

ACCESS

CONTROL

PANEL

ACP004

ACCESS

CONTROL

PANEL

ACP005

ACCESS

CONTROL

PANEL

ACP006

12U WALL MOUNTED

SECURITY NETWORK

RACK SNR004

12 U WALL MOUNTED

SECURITY NETWORK

RACK SNR003

12U WALL MOUNTED

SECURITY NETWORK

RACK SNR002

24U FREE STANDING

SECURITY SERVER RACK

SNR001

ROOM 241

ROOM 341

ROOM 427

ROOM 527

PENTHOUSE

ELEVATOR MACHINE ROOM

ROOM 124FIRST FLOOR

SECOND FLOOR

THIRD FLOOR

FOURTH FLOOR

FIFTH FLOOR

PENTHOUSE

CR CR CR IAC

CR CR CR IAC

CR CR CR IAC

CR CR CR IAC

CR CR CR IAC

CR CR

CAT 6A(TYPICAL)

COMPOSITE CABLE (TYPICAL)

CAT 6A(TYPICAL)

CAT 6A(TYPICAL)

CAT 6A(TYPICAL)

CAT 6A(TYPICAL)

COMPOSITE CABLE (TYPICAL)

COMPOSITE CABLE (TYPICAL)

COMPOSITE CABLE (TYPICAL)

COMPOSITE CABLE (TYPICAL)

CAT 6ATO OIT NETWORK AND

INTERNET PROVIDER

JB

JB

JB

JB

JB

JB

JB

JB

JB

JB

JB

JB

JB

JB

JB

JB

JB

JB

JB

JB

JB

JB

ELEVATOR CARD READERS

COMPOSITE CABLE (TYPICAL)

ELEVATOR TRAVEL CABLE

CCTV CAMERAS

CARD READERS

INTEGRATED

LOCK AND READER

CCTV CAMERAS

CCTV CAMERAS

CCTV CAMERAS

CCTV CAMERAS

INTEGRATED

LOCK AND READER

INTEGRATED

LOCK AND READER

INTEGRATED

LOCK AND READER

INTEGRATED

LOCK AND READER

CARD READERS

CARD READERS

CARD READERS

CARD READERS

CAT 6

EL

JB

ELECTRIFIED LOCK WITH

SCHEDULED LOCK/UNLOCK

EL

JB

ELECTRIFIED LOCK WITH

SCHEDULED LOCK/UNLOCK

EL

JB

ELECTRIFIED LOCK WITH

SCHEDULED LOCK/UNLOCK

EL

JB

ELECTRIFIED LOCK WITH

SCHEDULED LOCK/UNLOCK

EL

JB

ELECTRIFIED LOCK WITH

SCHEDULED LOCK/UNLOCK

PENTHOUSE ROOF

SECURITY

WORKSTATION

CAT 6A

SECURITY DESK

RECEPTION 102

FIBER TERMINATION PANEL

1000VA UPS FOR SWITCH

BLANK PANEL

BLANK PANEL

BLANK PANEL

BLANK PANEL

24 PORT SWITCH

CAT 6 PATCH PANEL

FIBER TERMINATION PANEL

1000VA UPS FOR SWITCH

BLANK PANEL

BLANK PANEL

BLANK PANEL

BLANK PANEL

24 PORT SWITCH

CAT 6 PATCH PANEL

FIBER TERMINATION PANEL

1000VA UPS FOR SWITCH

BLANK PANEL

BLANK PANEL

BLANK PANEL

BLANK PANEL

24 PORT SWITCH

CAT 6 PATCH PANEL

FIBER TERMINATION PANEL

1000VA UPS FOR SWITCH

BLANK PANEL

BLANK PANEL

BLANK PANEL

BLANK PANEL

NOTES:

1. PROVIDE ALL PATCH CABLES, GBICS, AND SFP ADAPTERS TO CONNECT FIBER TO NETWORK SWITCHES.

2. PROVIDE ALL PATCH CABLES, GBICS, AND SFP ADAPTERS TO MAKE 10G CONNECTION FROM NVR TO NETWORK SWITCH.

3. PROVIDE UPS FOR NVR, ACCESS CONTROL APPLIANCE AND NETWORK SWITCHES. SEE SPECIFICATIONS.

4. PROVIDE BACK-UP BATTERIES FOR ALL ACCESS CONTROL PANELS AND POWER SUPPLIES.

5. TERMINATE ALL 12 STRANDS OF FIBER AT EACH FIBER TERMINATION PANEL.

6. PROVIDE 2 DEDICATED 120V 20A CIRCUITS TO EACH RACK LOCATION. CIRCUIT TO NEAREST ELECTRIAL PANEL.

7. ALL CAT 6 AND FIBER OPTIC CABLE TO BE CERTIFIED. PROVIDE CERTIFICATION TEST REPORTS.

8. GROUND RACKS TO A SUITABLE ELECTRICAL BUILDING GROUND. SEE SPECIFICATIONS.

9. INSTALL READERS USING OSDP SECURE COMMUNICATIONS PROTOCOL.

CREDENTIALING

WORKSTATION

FLOOR

A.

B.

GENERAL DETAIL NOTES (TYPICAL ACCESS DOOR DIAGRAM ONLY):

DETAIL REPRESENTS ALL HARDWARE OPTIONS. QUANTITY AND TYPE OF DEVICES VARY PER LOCATION AS INDICATED ON PLANS.

INSTALL EMT FOR EACH RACEWAY - SEE ROUGH-IN DETAILS.

FIRE ALARM INTERFACE

1 46

2REX

TO ACCESS CONTROL PANEL 7

1.

2.

3.

4.

5.

6.

7.

8.

9.

10.

11.

12.

13.

14.

15.

16.

17.

18.

DETAIL NOTES:

CARD READERS.

REQUEST TO EXIT DEVICE.

ELECTRIC STRIKE.

POWER TRANSFER DEVICE.

DOOR CONTACT.

EMERGENCY EXIT DEVICE.

READER JUNCTION BOX OR DOOR POWER SUPPLY. WHERE REQUIRED, FURNISH 120 VOLT POWER FROM NEAREST CIRCUIT.

DOOR OPERATOR. FURNISH 120V POWER FROM NEAREST CIRCUIT.

DOOR OPERATOR PUSHBUTTONS. INTERFACE CARD READER WITH DOOR OPERATOR TO ENABLE NON-SECURE SIDE OPERATOR BUTTON ONLY

AFTER VALID CREDENTIAL IS PRESENTED.

ELECTRIFIED DOOR HARDWARE

POWER CONDUCTORS IN EMT RACEWAY

CONTROL CONDUCTORS IN EMT RACEWAY

CEILING HEIGHT VARIES.

ACCESSIBLE CEILING SPACE.

POWER FROM NEAREST CIRCUIT.

CONDUCTORS IN RACEWAY ABOVE CEILING.

CONDUCTORS IN RACEWAY TYPICAL - SEE SECURITY DEVICE ROUGH-IN DETAIL.

PLENUM RATED CABLE SUPPORTED ABOVE CEILING.

1'-0" MAXIMUM

6" MIN

6" MAX

1'-0" MAX

CAT 6

RJ45

JACK

1 8

FF1-001-G

IDF CLOSET (FF1)

FACEPLATE

NUMBER (001)

JACK COLOR (G, R, Y)

WHITE LABEL AND BLACK

LETTERS WITH CLEAR

TAPE COVERING ON BOTH

ENDS OF CABLE

IDF #(FF1)

OUTLET #

FF1-003G

JACK # (G, R, Y)

1-001G 1-001R

1-001Y 1-002G 1-002R

1-002Y 1-003G 1-003R

1-003Y

4x4 METAL BOX WITH

COVER - MTD TO WALL

PATCH CABLE BY

SYSTEMS

CONTRACTORWALL ABOVE CEILING

HORIZONTAL CABLE

SEE SPECIFICATIONS

SURFACE MOUNT

KEYSTONE (BISCUIT) JACK

4x4 METAL BOX WITH

COVER - MTD TO WALL

HORIZONTAL CABLE

SEE SPECIFICATIONS

SURFACE MOUNT

KEYSTONE (BISCUIT) JACK

PATCH CABLE BY

SYSTEMS

CONTRACTOR

1"⌀ EMT CONDUIT

METAL ELECTRICAL

BOX - SEE

SPECIFICATIONS

CEILING AS INDICATED

WITHIN ARCH PLANS

SET SCREW

CONNECTOR

WITH INSULATING

BUSHING

SET SCREW

CONNECTOR WITH

INSULATING BUSHING

1'-0"

6"

SE

E

AR

C

H

IT

EC

TU

R

AL

D R

AW

IN

G S

FO

R

C

EI

LI

N

G H

EI

G

H T

3' -4

1.

2.

NOTES:

THE DEVICE SHALL NOT SPAN MORE

THAN ONE FINISH MATERIAL

BOX SHALL BE FLUSH WITH THE

FINISH MATERIAL

SECTION

PLAN

CEILING SEE ARCHITECTURAL

DRAWINGS

ELECTRICAL BOX T-BAR

FASTENER

SURVEILLANCE DEVICE

ELECTRICAL BOX T-BAR

FASTENER

ACOUSTICAL TILE SEE

ARCHITECTURAL

DRAWINGS

CEILING STRUCTURE SEE

ARCHITECTURAL DRAWINGS

CEILING SUPPORT STRUCTURE

SEE ARCHITECTURAL DRAWINGS

HORIZONTAL CABLING TO

CABLING SUPPORT SYSTEM

EQUAL EQUAL

EQ

UA

L

SUPPORT CABLE ON ALL

FOUR CORNERS OF GRID

SUPPORT CABLE ON ALL

FOUR CORNERS OF CEILING

SUPPORT STRUCTURE

METAL BOX SIZE AS

REQUIRED BY NEC

METAL BOX SIZE AS

REQUIRED BY NEC

EQ

UA

L SURVEILLANCE DEVICE

PATCH

CABLE

FLOOR

A.

B.

C.

D.

GENERAL DETAIL NOTES (TYPICAL ACCESS DOOR DIAGRAM ONLY):

DETAIL REPRESENTS ALL HARDWARE OPTIONS. QUANTITY AND TYPE OF DEVICES VARY PER LOCATION AS INDICATED ON PLANS.

PROVIDE SHOP DRAWING SUBMITTAL AND WIRING DIAGRAMS FOR EACH POWER ASSISTED/ACCESS DOOR LOCATION.

ALL EQUIPMENT FURNISHED AND INSTALLED BY SECURITY CONTRACTOR.

INSTALL EMT FOR EACH RACEWAY - SEE ROUGH-IN DETAILS.

FIRE ALARM INTERFACE

1 46

2REX

TO ACCESS CONTROL PANEL

1.

2.

3.

4.

5.

6.

7.

8.

9.

10.

11.

12.

13.

14.

15.

16.

DETAIL NOTES:

CARD READERS.

REQUEST TO EXIT DEVICE.

ELECTRIC STRIKE.

ELECTRIFIED DOOR HARDWARE AND POWER TRANSFER DEVICE.

EMERGENCY EXIT DEVICE.

DOOR POWER SUPPLY. POWER SUPPLY TO BE USED AS ACCESS CONTROL JUNCTION BOX. 120 VOLT POWER FROM NEAREST CIRCUIT.

DOOR OPERATOR. FURNISH 120V POWER FROM NEAREST CIRCUIT. ON ACCESS CONTROL DOORS INTERFACE WITH ACCESS CONTROL SYSTEM.

DOOR OPERATOR PUSHBUTTONS. INTERFACE CARD READER WITH DOOR OPERATOR TO ENABLE NON-SECURE SIDE OPERATOR BUTTON ONLY

AFTER VALID CREDENTIAL IS PRESENTED.

SINGLE DOOR LOCATION

ELECTRIFIED DOOR HARDWARE

POWER CONDUCTORS IN EMT RACEWAY

CONTROL CONDUCTORS IN EMT…