Addendum No 1_Drawings - Building 54.pdf
PDF 4 MB Posted
- Solicitation number
- CRFQ 0211 GSD2700000019 2
- Issued by
- Kanawha County, West Virginia
About this file
This addendum consists of architectural and electrical drawings for the Building 54 Security System Upgrades project at 416 Adams Street in Fairmont, West Virginia, prepared by the West Virginia General Services Division. The project encompasses comprehensive security system upgrades across a six-story building, including demolition plans for all floors and roof, proposed security plans with detailed specifications for camera placement, access control systems, and associated infrastructure. The scope includes approximately 46 security cameras of various types (dome, multi-head, bullet, and fisheye configurations), multiple access control panels and card readers, door contacts, electric strikes, and networked locks throughout the facility. The drawings specify detailed security network infrastructure, including five wall-mounted equipment racks distributed across multiple floors, fiber optic cabling connections, and a central security operations center with monitoring workstations. Installation details address conduit penetrations, cable management, device mounting heights, and integration with existing systems, including the retention and integration of existing Schlage AD-300 network locks and associated panel interface boards where compatible with the new system architecture.
The project documentation details specifications for equipment including multi-technology card readers, door release systems, uninterruptible power supplies for critical equipment, network switches, and a 96-terabyte network video recorder. All existing access control systems are to remain operational during migration to the new system, with doors being transitioned one at a time to ensure no door remains unsecured or inoperable at the end of each workday. The drawings mandate that all communication cables be installed in conduit or cable trays with proper labeling, that surge protection be provided for exterior cameras, and that all network cabling and fiber optic installations receive certification testing. Equipment specifications include specific model numbers for cameras, control panels, door hardware, and monitoring equipment, with detailed requirements for power distribution, grounding, and backup battery systems for access control panels and power supplies.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
ZDS Design/ Consulting Services
Mechanical * Electrical * IAQ * Energy * Commissioning 135 Corporate Center Dr., Suite 532 Scott Depot, WV 25560
Ph: (304) 755-0075 Fx: (304) 755-0076
Web: www.zdsdesign.com Email: contact@zdsdesign.com
C :\U se rs
\e di so n.
ad ki ns \D oc um en ts
\G
SD
2C
_2
4-
-1 0_
BL
D
G
FA
IR
M
O N
T_ ed is on
.a dk in s.
rv t
WEST VIRGINIA GENERAL SERVICES DIVISION
BUILDING 54 SECURITY SYSTEM UPGRADES
ZDS Project Number: GSD-252-C 8/5/2026
416 Adams Street Fairmont, WV 26301
PROJECT VICINITY MAP
OS
DL
CO
T
CO
LC
F
F
F
DH
DCL
XXX
XXXX
XX
J
J F1
DO
M
N
X
TV
XXXX
CR
CK
TV
CC
DC
ES
IC
ML
RX
REX
MD
XXX
OS
1P 1 Pole (2P, 3P, 4P, ETC.)
A, Amp Ampere AC Above Counter ACLG Above Ceiling ADO Automatic Door Opener AF Amp Frame AFF Above Finished Floor AFG Above Finished Grade AFI Arc Fault Circuit
Interrupter AHU Air Handling Unit AL Aluminum ALT Alternate AMP Ampere AMPL Amplifier ANNUN Annunciator APPROX Approximately AQ-STAT Aquastat ARCH Architect, Architectural AS Amp Switch AT Amp Trip ATS Automatic Transfer Switch AUTO Automatic AUX Auxiliary AV Audio Visual AWG American Wire Gauge BATT Battery BD Board BLDG Building BMS Building Management System C Conduit CAB Cabinet CAT Catalog CATV Cable Television CB Circuit Breaker CCTV Closed Circuit Television CKT Circuit CLG Ceiling COMB Combination CMPR Compressor CONN Connection CONST Construction CONT Continuation Or Continuous CONTR Contractor CONV Convector CP Circulating Pump CRT Cathode-Ray Tube CT Current Transformer CTR Center CU Copper DCP Domestic Water Circulating Pump DEPT Department DET Detail DIA Diameter DISC Disconnect DIST Distribution DN Down DPR Damper DS Safety Disconnect Switch DT Double Throw DWG Drawing EC Electrical Contractor ELEC Electric, Electrical ELEV Elevator ELU Emergency Lighting Unit EM Emergency EMS Energy Management System EMT Electrical Metallic Tubing EP Electric Pneumatic EQUIP Equipment EWC Electric Water Cooler EXIST Existing EXH Exhaust EXP Explosion Proof FA Fire Alarm FABP Fire Alarm Booster Power
Supply Panel FACP Fire Alarm Control Panel FCU Fan Coil Unit FIXT Fixture FLR Floor FLUOR Fluorescent FU Fuse FUDS Fused Safety Disconnect Switch GA Gauge GAL Gallon GALV Galvanized GC General Contractor GEN Generator GFI Ground Fault Circuit Interrupter GFP Ground Fault Protector GND Ground GRS Galvanized Rigid Steel (Conduit) GYP BD Gypsum Board HOA Hands-Off-Automatic Switch HORIZ Horizontal HP Horsepower HPF High Power Factor HT Height HTG Heating HTR Heater HV High Voltage HVAC Heating, Ventilating And Air
Conditioning IC Interrupting Capacity IG Isolated Ground IMC Intermediate Metal Conduit INCAND Incandescent IR Infrared I/W Interlock With J-BOX Junction Box KV Kilovolt KVA Kilovolt-Ampere KVAR Kilovolt-Ampere Reactive KW Kilowatt KWH Kilowatt Hour LOC Locate Or Location LT Light LTG Lighting LTNG Lightning LV Low Voltage MAX Maximum MAG.S Magnetic Starter M/C Momentary Contact MC Mechanical Contractor
Electrical Abbreviations
Electrical DeviceTags: Uppercase letter(s) indicates Panel ID and circuit number. Lowercase letter indicates designation of controlling switch (where applicable).
Switch ID indicated by a lowercase letter. Switch IDs are unique per space. A switch with an ID "a" controls all devices within the space in which it is located tagged with "a". A switch without a tagged ID controls all lighting fixtures within a space. ID tags may be used on control devices other than switches, such as occupancy sensors or contactors.
Equipment Tags: Equipment ID is indicated by an underlined tag adjacent to the equipment. See the equipment connection schedule for description, electrical requirements, and panel and circuit number. Symbols/graphic appearance of equipment varies.
Solid, arced lines connecting equipment, devices, or fixtures indicate unswitched power circuiting. Wires are only intended to indicate to what circuit devices are connected. Actual connections, circuit routing, installtion, junction boxes, etc. shall be field-determined by the contractor.
Home run to branch circuit panelboard. The equipment name and circuit number(s) are indicated, separated by a hyphen. Homeruns are only intended to indicate panel and circuit number. Actual homerun location shall be field-determined by the contractor.
Power Symbols
Electrical Symbol Legend
Room
MCB Main Circuit Breaker MCC Motor Control Center MDC Main Distribution Center MDP Main Distribution Panel MFR Manufacturer MFS Main Fused Disconnect Switch MH Manhole MIC Microphone MIN Minimum MISC Miscellaneous MLO Main Lugs Only MMS Manual Motor Starter MOA Multioutlet Assembly MSP Motor Starter Panelboard MSBD Main Switchboard MSS Motor Starter Switch MT Mount MT.C Empty Conduit MTS Manual Transfer Switch MTR Motor, Motorized N.C. Normally Closed NEC National Electrical Code NEMA National Electrical
Manufacturer's Association NFDS Non-Fused Safety Disconnect
Switch NIC Not In Contract NL Night Light N.O. Normally Open NPF Normal Power Factor NTS Not To Scale OC On Center OH Overhead OL Overloads PA Public Address PB Pull Box Or Pushbutton PE Pneumatic Electric PED Pedestal PF Power Factor PH Phase PIV Post Indicating Valve PNL Panel PP Power Pole PR Pair PRI Primary PROJ Projection PRV Power Roof Ventilator PT Potential Transformer PVC Polyvinyl Chloride (Conduit) PWR Power QUAN Quantity RCPT Receptacle REQD Required RM Room RSC Rigid Steel Conduit RTU Roof Top Unit SC Surface Conduit SEC Secondary SHT Sheet SIM Similar SLD Single-Line Diagram S/N Solid Neutral SPEC Specification SPKR Speaker SP Spare SPP Single-Point Power SR Surface Raceway SS Stainless Steel SSW Selector Switch S/S Stop/Start Pushbuttons STA Station STD Standard SURF Surface Mounted SW Switch SWBD Switchboard SYM Symmetrical SYS System TEL Telephone TERM Terminal TL Twist Lock TR Tamper Resistant T-STAT Thermostat TTC Telephone Terminal Cabinet TV Television TVTC Television Terminal Cabinet TYP Typical UC Under Counter UE Underground Electrical UG Underground UH Unit Heater UT Underground Telephone UTIL Utility UV Ultraviolet V Volt VA Volt-Amperes VDT Video Display Terminal VERT Vertical VFD Variable Frequency Drive VOL Volume W Watt W/ With WG Wire Guard WH Water Heater W/O Without WP Weatherproof XFMR Transformer XFR Transfer
∠ Angle @ At ▲ Delta ' Feet " Inches # Number Ø Phase C Center Line P Plate
Exit Light, Wall-Mounted.
Shading and arrows indicate faces and directional chevrons.
Wall-mounted fixtures, Typical (Various Symbols)
Emergency Lighting Unit, Wall-Mounted, Remote Battery
Emergency Lighting Unit, Wall-Mounted, Integral Battery
Emergency Lighting Unit, Ceiling-Mounted, Integral Battery Emergency Lighting Unit, Ceiling-Mounted, Remote Battery
Lighting Fixtures, Typical, Rectangular (Various Symbols) Filled circles indicate recessed.
Open circles indicate surface-mounted.
Diagonal line indicates lensed.
Outer dots indicate suspended.
Lighting Fixtures, Typical, Round (Various Symbols) Center dot indicates pendant.
Diagonal line indicates lensed.
Chevron indicates wall wash.
Strip Fixture
Directional Light, Track Light, Flood Light
Exit Light, Ceiling-Mounted.
Shading and arrows indicate faces and directional chevrons.
Linear Light, Tape Light
Exit/ELU Combo
Diagonal hatch indicates light on a critical circuit.
Solid hatch indicates light on an emergency or life safety circuit.
Pole/Area Lights
Post-Top Area Light
Bollard Light
Single-Pole Switch Two-Pole Switch Three-Pole Switch Switch Modifiers:
3: 3-Way 4: 4-Way K: Keyed D: Dimming T: Timer
OS: Occupancy Sensor VS: Vacancy Sensor AC: Above-Counter LV: Low-Voltage M: Motor-Rated
Lighting Contactor
Lighting Control Panel
Occupancy Sensor
Daylight Harvesting Sensor
Smoke Detector
Heat Detector
Carbon Monoxide Detector
Beam Detector T: Transmitter R: Receiver
Combination Detector (Up to Three)
Duct Smoke Detector
Manual Pull Station
Horn, Wall
Horn, Ceiling
Strobe, Wall, Candela as indicated
Strobe, Ceiling, Candela as indicated
Horn/Strobe, Wall, Candela as indicated
Horn/Strobe, Ceiling, Candela as indicated
Remote Indicator w/ Test Switch, Wall
Remote Indicate w/ Test Switch, Ceiling
Door Holder
Door Closer
Fire Service Phone
Addressible Module AIM: Addressible Input Module AOM:Addressible Output Control Module AIO: Addressible Input/Output Module
Fire Alarm Control Unit EVAC: Voice Evacuation Control Panel FAA: Fire Alarm Annunciator FACP: Fire Alarm Control Panel FATC: Fire Alarm Terminal Cabinet NACP: Notification Appliance Circuit Panel FAMN: Fire Alarm Mass Notification Control Panel
Supervisory or Interface Device PIV: Post Indicator Valve Supervisory PS: Pressure Switch R: Non-Addressible Relay VS: Valve Supervisory Switch WF: Water Flow Switch
Simplex Receptacle
Duplex Receptacle
Quadruplex Receptacle
Special Receptacle, Type as Indicated
W all
Ce ilin g
Flo or
Receptacle Modifiers:
##": Height AFF OC AC: Above Counter GFI: Ground-Fault Circuit Interrupter WP: Weatherproof In-Use Cover
Half shading indicates split (typically switched) Outside shading indicates emergency circuit Center shading indicates isolated ground
Multioutlet Assembly Filled squares indicate 120V outlet Open squares indicate with USB
Cord Reel, Device Varies
Drop Cord, Device Varies
Junction Box Floor Box, see schedule for type
Emergency Power Off
Door Opener Push Plate
Power Meter Safety Switch, Fused
Safety Switch, Unfused
Motor Starter
Combination Starter/Disconnect
Ground Rod
Ground Rod with Test Well
Lightning Protection Air Terminal
Lightning Protection Conductor Splice
Static Ground Receptacle
Data Outlet
Telephone Outlet
Data/Telephone Outlet
W all
Ce ilin g
Flo or
Outlet Modifiers:
##": Height AFF OC AC: Above Counter
Wireless Access Point
Nurse Call Corridor Light Number of lights as indicated
Nurse Call Device B: Code Blue D: Duty Station E: Emergency P: Patient Call S: Staff
TV Outlet
Nurse Call Control Unit NCAP: Nurse Call Annunciator Panel NCHS: Nurse Call Host Constroller NCPA: Nurse Call Power Supply NCTC: Nurse Call Terminal Cabinet NCUPS: Uninterruptable Power Supply
Lighting Symbols
Contactor
Single-Pole Switch Two-Pole Switch Three-Pole Switch Switch Modifiers:
K: Keyed T: Timer AC: Above-Counter M: Motor-Rated
Fire Alarm Symbols
Grounding and Lightning Protection Symbols
Security Camera PTZ: Pan/Tilt/Zoom
Card Reader
Card Reader with Keypad
Closed Circuit TV Outlet
Door Contact
Electric Strike
Intercom
Magnetic Lock
Request to Exit Button
Request to Exit Sensor
Motion Detector
Security Control Unit SCP: Security Control Panel SPS: Security Power Supply Unit ACP: Access Control Panel WIU: Wiegand Interface Unit PIB: Panel Interface Board IAC: Networked Lock with Integrated
Reader SWKS: Security Workstation MON: Video Monitor ARAM: Area of Rescue Assistance
Master Station ARAR: Area of Rescue Assistance
Remote Station
Telecom Symbols
Nurse Call Symbols
Security Symbols a
A A1a
Equipment is tagged with Panel Name and with Panel ID in parentheses. Panel ID is intended as a design documentation aid only. Do not include Panel ID in field-applied circuit directories or labels.
Hatched fill indicates distribution panel or switchboard.
Solid fill indicates branch panel or load center.
Dashed box indicates code-required clearance (width and depth).
Door indicates front of recessed panel.
Panelboards are assigned an abbreviated indicator (or Panel ID) for use with circuit numbers. Panel ID is listed within the panel schedule and in the panel abbreviation schedule.
Power Distribution Equipment
HP
1A
(B
LP
1A
(C
MD
P(
A)
SB1(S)
Devices and fixtures are tagged with Panel ID and circuit number. For example, a device tagged with "A1" indicates the device is circuited to panel designated "A," circuit number 1. The panel schedule circuit number contans both the panel abbreviation and the circuit number.
XX-1
Transformer: Typically transformer names begin with or contain the letter "T". See Single-Line Diagram for description and requirements.
T1
Dashed, arced lines connecting equipment, devices, or fixtures indicate switched power.
Absence of a switch designation on a lighting fixture indicates fixture is controlled by the only switch in the space. An "x" in place of the switch designation indicates unswitched.
Bottom Value, Lowercase Letter: Switch ID
Lighting Tags
Top Value: Fixture Type ID (Underlined)
Bottom Value, Uppercase Letter(s): Panel ID Bottom Value, Number(s): Circuit Number a a
C1a
Wiring
Power Device and Equipment Tags
Construction Phasing
Existing to Remain
Existing to Be Demolished
New
(Typical All Symbols and Equipment)
Existing to Be Demolished
Area Not in Contract
Miscellaneous
Keynote
Callout:
Top Value: Detail Number on Sheet Bottom Value: Sheet Number of Detail
Room Name and Number
Smoke Damper
FILE:
DRAWN BY:
CHECKED BY:
PROJ. NO:
DRAWING NO:
DRAWING TITLE:
PROJECT NAME:
http://www.ZDSDesign.com
135 Corporate Center Drive Suite 532 Scott Depot, WV 25560
TEL 304/755-0075
FAX 304/755-0076
THIS SQUARE APPEARS 1/2"x1/2"
ON FULL SIZE SHEETS
CLIENT:
XXX
C :\U se rs
\e di so n.
ad ki ns \D oc um en ts
\G
SD
2C
_2
4-
-1 0_
BL
D
G
FA
IR
M
O N
T_ ed is on
.a dk in s.
rv t
8/
/2
:2 5:
P
M
54-E-001
EA
TZ3
GSD-252-C
ELECTRICAL TITLE
SHEET
BUILDING 54 SECURITY
SYSTEM UPGRADES
416 Adams Street Fairmont, WV 26301
WEST VIRGINIA
GENERAL SERVICES
DIVISION
Electrical Sheet List
54-C001 COVER SHEET
54-E-001 ELECTRICAL TITLE SHEET
54-TD-101 DEMO PLAN FIRST FLOOR
54-TD-102 DEMO PLAN SECOND FLOOR
54-TD-103 DEMO PLAN THIRD FLOOR
54-TD-104 DEMO PLAN FOURTH FLOOR
54-TD-105 DEMO PLAN FIFTH FLOOR
54-TD-106 DEMO PLAN ROOF
54-TY-101 FIRST FLOOR SECURITY PLAN
54-TY-102 SECOND FLOOR SECURITY PLAN
54-TY-103 THIRD FLOOR SECURITY PLAN
54-TY-104 FOURTH FLOOR SECURITY PLAN
54-TY-105 FIFTH FLOOR SECURITY PLAN
54-TY-106 ROOF SECURITY PLAN
54-TY-501 SECURITY DETAILS
54-TY-502 SECURITY DETAILS
54-TY-601 SECURITY SCHEDULES
NO DATE REVISION
MECH
WATER SERVICE
UPS EQUIPMENT
LOBBY
ELEV A
A-1
ELEV B
B-1
STAIR 1
ST1-1 PLENUM
105 PLENUM
DATA
ATS ROOM
ELECTRICAL
EXTERIOR MECH /
ELECTRICAL
ME
ELEVATOR EQUIPMENT
UP
DC
DCDC
DC DC DC DC DC
CR
ES
IA
C
JB
PIB
AR
AM
EXT
IAC
WIU WIU
IAC
PIB
IAC
PIB
PIB
AC
P
PS
EX
T
EX
T
WIU
WIU
WIU
WIU
PI
B
W
IU IAC
CR CR
(E)IAC001
WI001
(E)IAC003
WI005
(E)PI003
(E)IAC002
WI004
(E)PI002
WI003WI002
(E)IAC005
(E)PI005
WI007
(E)IAC004
(E)PI004
WI006
(E)PI001
(E)ES002
1 2
FILE:
DRAWN BY:
CHECKED BY:
PROJ. NO:
DRAWING NO:
DRAWING TITLE:
PROJECT NAME:
http://www.ZDSDesign.com
135 Corporate Center Drive Suite 532 Scott Depot, WV 25560
TEL 304/755-0075
FAX 304/755-0076
THIS SQUARE APPEARS 1/2"x1/2"
ON FULL SIZE SHEETS
CLIENT:
XXX
C :\U se rs
\e di so n.
ad ki ns \D oc um en ts
\G
SD
2C
_2
4-
-1 0_
BL
D
G
FA
IR
M
O N
T_ ed is on
.a dk in s.
rv t
8/
/2
:2 5:
P
M
54-TD-101
EA
TZ3
GSD-252-C
DEMO PLAN FIRST
FLOOR
BUILDING 54 SECURITY
SYSTEM UPGRADES
416 Adams Street Fairmont, WV 26301
WEST VIRGINIA
GENERAL SERVICES
DIVISION
# KEYNOTES
1 READER JUNCTION BOXES FOR ELEVATOR CARD READERS.
2 EXISTING PANEL INTERFACE BOARDS (SCHLAGE PIB-300-2D) FOR EXISTING
SCHLAGE AD-300 WIRED NETWORK LOCKS TO REMAIN UNLESS NEW SYSTEM IS
CAPABLE OF COMMUNICATING DIRECTLY WITH THE LOCKS VIA RS-485.
INTEGRATE EXISTING NETWORK LOCKS INTO NEW SYSTEM.
1/8" = 1'-0"54-TD-101
1 DEMO PLAN FIRST FLOOR SECURITY
SYSTEMS DEMOLITION NOTES
1 DISCONNECT AND REMOVE ONLY SYSTEM DEVICES SHOWN TO BE DEMOLISHED.
2 DISCONNECT AND REMOVE ASSOCIATED CONDUIT AND WIRE BACK TO LAST
REMAINING DEVICE. FURNISH AND INSTALL CONDUIT AND WIRE AS NECESSARY
FOR CONTINUITY OF CIRCUIT(S) TO ANY EXISTING DEVICES TO REMAIN.
COORDINATE AND VERIFY REQUIREMENTS WITH NEW WORK IN AREA.
3 FURNISH AND INSTALL CONDUIT AND/OR SYSTEMS WIRING AS NECESSARY FOR
CONTINUITY OF ANY SYSTEMS EQUIPMENT OR DEVICES TO REMAIN. MODIFY OR
REPLACE AS REQUIRED.
4 FURNISH AND INSTALL BLANK COVER PLATES FOR ALL EXISTING UNUSED
OPENINGS.
5 BUILDINGS THAT HAVE CAMERAS THAT WORK OR WOULD WORK IF THE
SOFTWARE AND LICENSES WERE CURRENT SHOULD HAVE NEW NVRS INSTALLED
AND THE EXISTING CAMERAS CONNECTED TO THEM. AS NEW CAMERAS ARE
INSTALLED, REMOVE OLD CAMERAS FROM THE SYSTEM.
6 THE EXISTING ACCESS CONTROL SYSTEM IS TO REMAIN IN USE UNTIL THE NEW
SYSTEM IS COMPLETE. DOORS SHOULD BE MIGRATED TO THE NEW SYSTEM ONE
AT A TIME UNTIL ALL ARE ON THE NEW SYSTEM. DURING THIS MIGRATION, NO
DOOR IS TO REMAIN UNSECURED OR INOPERABLE AT THE END OF A WORKDAY.
CONF
OPEN
SECOND FLOOR
VESTIBULE
VESTIBULE
200A
STAIR 1
ST1-2
ELEV A
A-2
ELEV B
B-2
WOMEN'S PUBLIC
MEN'S PUBLIC
CENTRAL CONTROL
RECEPTION
WORKFORCE
COFFEE
HALL
COMPUTER TRAINING
STORAGE
212A
JAN
OFFICE
OFFICE
OFFICE
OFFICE
CONFERENCE
BREAK
CONF
OFFICE
OFFICE
WORK
STORAGE
HALL
HALL
ELEC
HALL
BREAK
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
HALL
REHAB
TENANT STORAGE
STORAGE
MAINTENANCE OFFICE
MECH
MAINTENANCE
MAIL ROOM
261WOMEN'S
MEN'S
STAIR 2
ST2-2
DATA
DC
DC
DC
DC
DC
DC
DC DC
CR
DC
ES
IAC IAC
IAC
IAC
IAC
EXT
DB
JB
WIU
PIB
WIU
PIB
PI
B
PIB PIB
PIB
PIB PIB PIB PIB
EXT
EX
T
PIB
WIU
W
IU
WIU
IAC
WIU
WIU
IAC
WIU IAC IACIAC
WIUWIU WIU WIUIA
C
PSACP
IAC
IA
CPIB
WIU
PIB
WIU
SECURITY DESK
(E)IAC006
(E)PI006
WI008
WI009
(E)PI007
(E)IAC007
(E)IAC008
WI010
(E)PI008
WI011
(E)PI009
(E)IAC009 (E)IAC010
WI012
(E)PI010
(E)IAC011
WI013
(E)PI011
(E)IAC014
WI017
(E)PI014
WI016
(E)PI013
(E)IAC013
(E)IAC012
WI015
(E)PI012
WI018
(E)PI015
(E)IAC015 (E)IAC016
(E)PI016
WI019
(E)IAC017 (E)PI017
WI020
(E)IAC018(E)PI018
WI021
(E)ES003
WI014
1 1 1
1 1 1
(E)SNR002
FILE:
DRAWN BY:
CHECKED BY:
PROJ. NO:
DRAWING NO:
DRAWING TITLE:
PROJECT NAME:
http://www.ZDSDesign.com
135 Corporate Center Drive Suite 532 Scott Depot, WV 25560
TEL 304/755-0075
FAX 304/755-0076
THIS SQUARE APPEARS 1/2"x1/2"
ON FULL SIZE SHEETS
CLIENT:
XXX
C :\U se rs
\e di so n.
ad ki ns \D oc um en ts
\G
SD
2C
_2
4-
-1 0_
BL
D
G
FA
IR
M
O N
T_ ed is on
.a dk in s.
rv t
8/
/2
:2 5:
P
M
54-TD-102
EA
TZ3
GSD-252-C
DEMO PLAN SECOND
FLOOR
BUILDING 54 SECURITY
SYSTEM UPGRADES
416 Adams Street Fairmont, WV 26301
WEST VIRGINIA
GENERAL SERVICES
DIVISION
# KEYNOTES
1 EXISTING PANEL INTERFACE BOARDS (SCHLAGE PIB-300-2D) FOR EXISTING
SCHLAGE AD-300 WIRED NETWORK LOCKS TO REMAIN UNLESS NEW SYSTEM IS
CAPABLE OF COMMUNICATING DIRECTLY WITH THE LOCKS VIA RS-485.
INTEGRATE EXISTING NETWORK LOCKS INTO NEW SYSTEM.
2 EXISTING SECURITY RACK TO REMAIN AND BE REUSED.
3 EXISTING DURESS BUTTON TO BE REMOVED. CONTRACTOR SHALL PATCH AND
PAINT AS REQUIRED TO RESTORE TO ORIGINAL CONDITION.
4 INSTALL NEW NVR IN RACK AND CONNECT THE EXISTING CAMERAS. AS NEW
CAMERAS ARE INSTALLED, REMOVE OLD CAMERAS FROM THE SYSTEM.
1/8" = 1'-0"54-TD-102
1 DEMO PLAN SECOND FLOOR SECURITY
SYSTEMS DEMOLITION NOTES
1 DISCONNECT AND REMOVE ONLY SYSTEM DEVICES SHOWN TO BE DEMOLISHED.
2 DISCONNECT AND REMOVE ASSOCIATED CONDUIT AND WIRE BACK TO LAST
REMAINING DEVICE. FURNISH AND INSTALL CONDUIT AND WIRE AS NECESSARY
FOR CONTINUITY OF CIRCUIT(S) TO ANY EXISTING DEVICES TO REMAIN.
COORDINATE AND VERIFY REQUIREMENTS WITH NEW WORK IN AREA.
3 FURNISH AND INSTALL CONDUIT AND/OR SYSTEMS WIRING AS NECESSARY FOR
CONTINUITY OF ANY SYSTEMS EQUIPMENT OR DEVICES TO REMAIN. MODIFY OR
REPLACE AS REQUIRED.
4 FURNISH AND INSTALL BLANK COVER PLATES FOR ALL EXISTING UNUSED
OPENINGS.
5 BUILDINGS THAT HAVE CAMERAS THAT WORK OR WOULD WORK IF THE
SOFTWARE AND LICENSES WERE CURRENT SHOULD HAVE NEW NVRS INSTALLED
AND THE EXISTING CAMERAS CONNECTED TO THEM. AS NEW CAMERAS ARE
INSTALLED, REMOVE OLD CAMERAS FROM THE SYSTEM.
6 THE EXISTING ACCESS CONTROL SYSTEM IS TO REMAIN IN USE UNTIL THE NEW
SYSTEM IS COMPLETE. DOORS SHOULD BE MIGRATED TO THE NEW SYSTEM ONE
AT A TIME UNTIL ALL ARE ON THE NEW SYSTEM. DURING THIS MIGRATION, NO
FAMILY VISITATION
VIDEO
MDT OFFICE
CONF
HALL
RESTROOM
INT
INT
INT
HALL
RECEPT
309 MAIL
SWBRD
HALL
INT
INT
INT
INT
WOMEN'S PUBLIC
MEN'S PUBLIC
THIRD FLOOR
DHHR LOBBY
HALL
HIGH DENSITY
OPEN
OPEN
OPEN
JAN
ELEC
CSM OFFICE
CSM ADMIN
FINANCE (2PP)
STORAGE
OPS OFFICE
HALL
YS OFFICE
SS COORD
WVW OFFICE
CPS OFFICE
AS OFFICE
INCOME OFFICE
HALL
CPS OFFICE
STORAGE
INCOME OFFICE
OPEN
BREAK
MEN'S
WOMEN'S
STAIR 2
ST2-3
DATA
CORRIDOR
301A
DB DB DB DB
DB
DB DB
DB
DB DBDB
EX
T
EXT
EXT
EX
T
EX
T
AR
AR
PI
B
PI
B
PIB PIB
PIB
WIU
IAC
WIU WIU
IAC IACIAC
PIB
WIU
ACP PS
IA
C
W
IU
PI
B
W
IU
IA
C
IA
C
W
IU
(E)IAC019
(E)PI019
WI022
WI023
(E)PI020
(E)IAC020
(E)IAC021 WI024
(E)PI021
(E)IAC022
(E)PI022
WI025
(E)IAC023
PI023
WI026
(E)IAC024
(E)PI024
WI027
(E)PI025
WI028
(E)IAC025
1 1 1 1
3 3 3
3 3 3
FILE:
DRAWN BY:
CHECKED BY:
PROJ. NO:
DRAWING NO:
DRAWING TITLE:
PROJECT NAME:
http://www.ZDSDesign.com
135 Corporate Center Drive Suite 532 Scott Depot, WV 25560
TEL 304/755-0075
FAX 304/755-0076
THIS SQUARE APPEARS 1/2"x1/2"
ON FULL SIZE SHEETS
CLIENT:
XXX
C :\U se rs
\e di so n.
ad ki ns \D oc um en ts
\G
SD
2C
_2
4-
-1 0_
BL
D
G
FA
IR
M
O N
T_ ed is on
.a dk in s.
rv t
8/
/2
:2 5:
P
M
54-TD-103
EA
TZ3
GSD-252-C
DEMO PLAN THIRD
FLOOR
BUILDING 54 SECURITY
SYSTEM UPGRADES
416 Adams Street Fairmont, WV 26301
WEST VIRGINIA
GENERAL SERVICES
DIVISION
1/8" = 1'-0"54-TD-103
1 DEMO PLAN THIRD FLOOR SECURITY
KEYNOTES
1 EXISTING PANEL INTERFACE BOARDS (SCHLAGE PIB-300-2D) FOR EXISTING
SCHLAGE AD-300 WIRED NETWORK LOCKS TO REMAIN UNLESS NEW SYSTEM IS
CAPABLE OF COMMUNICATING DIRECTLY WITH THE LOCKS VIA RS-485.
INTEGRATE EXISTING NETWORK LOCKS INTO NEW SYSTEM.
2 THIS DOOR DOES NOT LOCK. REPLACE EXISTING LOCK AND INTERFACE WITH NEW
TO MATCH EXISTING. CONNECT TO NEW SYSTEM.
3 EXISTING DURESS BUTTON TO BE REMOVED. CONTRACTOR SHALL PATCH AND
PAINT AS REQUIRED TO RESTORE TO ORIGINAL CONDITION.
SYSTEMS DEMOLITION NOTES
1 DISCONNECT AND REMOVE ONLY SYSTEM DEVICES SHOWN TO BE DEMOLISHED.
2 DISCONNECT AND REMOVE ASSOCIATED CONDUIT AND WIRE BACK TO LAST
REMAINING DEVICE. FURNISH AND INSTALL CONDUIT AND WIRE AS NECESSARY
FOR CONTINUITY OF CIRCUIT(S) TO ANY EXISTING DEVICES TO REMAIN.
COORDINATE AND VERIFY REQUIREMENTS WITH NEW WORK IN AREA.
3 FURNISH AND INSTALL CONDUIT AND/OR SYSTEMS WIRING AS NECESSARY FOR
CONTINUITY OF ANY SYSTEMS EQUIPMENT OR DEVICES TO REMAIN. MODIFY OR
REPLACE AS REQUIRED.
4 FURNISH AND INSTALL BLANK COVER PLATES FOR ALL EXISTING UNUSED
OPENINGS.
5 BUILDINGS THAT HAVE CAMERAS THAT WORK OR WOULD WORK IF THE
SOFTWARE AND LICENSES WERE CURRENT SHOULD HAVE NEW NVRS INSTALLED
AND THE EXISTING CAMERAS CONNECTED TO THEM. AS NEW CAMERAS ARE
INSTALLED, REMOVE OLD CAMERAS FROM THE SYSTEM.
6 THE EXISTING ACCESS CONTROL SYSTEM IS TO REMAIN IN USE UNTIL THE NEW
SYSTEM IS COMPLETE. DOORS SHOULD BE MIGRATED TO THE NEW SYSTEM ONE
AT A TIME UNTIL ALL ARE ON THE NEW SYSTEM. DURING THIS MIGRATION, NO
STAIR 1
ST1-4
FOURTH FLOOR
ELEV A
A-4
ELEV B
B-4
OFFICE
OFFICE
OFFICE
S.O.S. OFFICES
RESTROOM
OFFICE
OFFICE
OFFICE
428 OFFICE
HALL
420ASTOR
EVIDENCE
424 STORAGE
POLYGRAPH
CONFERENCE
I.C.I.G.
OFFICE
OFFICE
RESEARCH & COMPLIANCE
COMPUTER TRAINING
CONFERENCE B
409 CONFERENCE B
WOMEN'S PUBLIC
402 MEN'S PUBLIC
403 JAN
TRAINING
ELEC
CONFERENCE C
HALL
HALL
OPEN
OPEN
TITLE IV-E (3 PPL)
CSC OFFICE
OIG
FINGER PRINTING
CSC OFFICE
OIG
STORAGE
CSC HOTEL OFFICE
HALL
BREAK ROOM
MEN'S
WOMEN'S
STAIR 2
ST2-4
DATA
AR
AR
CR
IAC
JB
PIB PIB PIB
PI
B
PIB PIB
PIB PIB
PI
B
W
IU
IAC
PS
ACP
IAC IAC
WIU WIU
WIU
IAC IAC
WIU WIU
IAC IAC
WIUWIU
W
IU
IA
C
CR
JB
ES
ES
IAC
PIB
WIU
(E)IAC027
WI030
(E)PI027
WI031
(E)PI028
(E)IAC028
(E)IAC029
(E)PI029
WI032 WI033
(E)PI030
(E)IAC030
(E)IAC031
WI034
(E)PI031
(E)IAC032
WI035
(E)PI032
WI036
(E)PI033(E)IAC033
(E)IAC034
WI037
(E)PI034
(E)IAC026
WI029
(E)PI026
1 1 1
1 1
FILE:
DRAWN BY:
CHECKED BY:
PROJ. NO:
DRAWING NO:
DRAWING TITLE:
PROJECT NAME:
http://www.ZDSDesign.com
135 Corporate Center Drive Suite 532 Scott Depot, WV 25560
TEL 304/755-0075
FAX 304/755-0076
THIS SQUARE APPEARS 1/2"x1/2"
ON FULL SIZE SHEETS
CLIENT:
XXX
C :\U se rs
\e di so n.
ad ki ns \D oc um en ts
\G
SD
2C
_2
4-
-1 0_
BL
D
G
FA
IR
M
O N
T_ ed is on
.a dk in s.
rv t
8/
/2
:2 5:
P
M
54-TD-104
EA
TZ3
GSD-252-C
DEMO PLAN FOURTH
FLOOR
BUILDING 54 SECURITY
SYSTEM UPGRADES
416 Adams Street Fairmont, WV 26301
WEST VIRGINIA
GENERAL SERVICES
DIVISION
# KEYNOTES
1 EXISTING PANEL INTERFACE BOARDS (SCHLAGE PIB-300-2D) FOR EXISTING
SCHLAGE AD-300 WIRED NETWORK LOCKS TO REMAIN UNLESS NEW SYSTEM IS
CAPABLE OF COMMUNICATING DIRECTLY WITH THE LOCKS VIA RS-485.
INTEGRATE EXISTING NETWORK LOCKS INTO NEW SYSTEM.
1/8" = 1'-0"54-TD-104
1 DEMO PLAN FOURTH FLOOR SECURITY
SYSTEMS DEMOLITION NOTES
1 DISCONNECT AND REMOVE ONLY SYSTEM DEVICES SHOWN TO BE DEMOLISHED.
2 DISCONNECT AND REMOVE ASSOCIATED CONDUIT AND WIRE BACK TO LAST
REMAINING DEVICE. FURNISH AND INSTALL CONDUIT AND WIRE AS NECESSARY
FOR CONTINUITY OF CIRCUIT(S) TO ANY EXISTING DEVICES TO REMAIN.
COORDINATE AND VERIFY REQUIREMENTS WITH NEW WORK IN AREA.
3 FURNISH AND INSTALL CONDUIT AND/OR SYSTEMS WIRING AS NECESSARY FOR
CONTINUITY OF ANY SYSTEMS EQUIPMENT OR DEVICES TO REMAIN. MODIFY OR
REPLACE AS REQUIRED.
4 FURNISH AND INSTALL BLANK COVER PLATES FOR ALL EXISTING UNUSED
OPENINGS.
5 BUILDINGS THAT HAVE CAMERAS THAT WORK OR WOULD WORK IF THE
SOFTWARE AND LICENSES WERE CURRENT SHOULD HAVE NEW NVRS INSTALLED
AND THE EXISTING CAMERAS CONNECTED TO THEM. AS NEW CAMERAS ARE
INSTALLED, REMOVE OLD CAMERAS FROM THE SYSTEM.
6 THE EXISTING ACCESS CONTROL SYSTEM IS TO REMAIN IN USE UNTIL THE NEW
SYSTEM IS COMPLETE. DOORS SHOULD BE MIGRATED TO THE NEW SYSTEM ONE
AT A TIME UNTIL ALL ARE ON THE NEW SYSTEM. DURING THIS MIGRATION, NO
OPEN
FIFTH FLOOR
OFFICE
OFFICE
OFFICE
OFFICE
STORAGE
ADMIN
574OFFICE
HALL
STAIR 1
ST1-5
OFFICE
OFFICE
LAB
PLAN ROOM
FILES
REGIONAL
OFFICE
OFFICE
ELEV A
A-5
ELEV B
B-5
STAIR 2
ST2-5
OFFICE
OFFICE
OFFICE
OFFICE
STORAGE
CONF
OFFICE
OFFICE
OFFICE
OFFICE
BREAK
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
WORK
OFFICE
CONF
STORAGE
WOMEN'S PUBLIC
MEN'S PUBLIC
JAN
STORAGE
DATA
ELEC
HALL
HALL
HALL
HALL
HALL
OFFICE
578 HALL
WORK
OFFICE
BREAK
CONF
OFFICE
BCSE
MENS
WOMEN'S
OEHS
BREAK
HALL
AR
AR
IAC
WIU
PIB
PIB PIB
PIB
PI
B
PIB
CR
JB
ES
CR
JB
ES
IA
C
W
IU
WIU
WIU
IAC
IAC
IAC IAC
WIU WIU
PIB IAC
WIU
PIBIAC
WIU
IACIAC PIB PIB
WIU WIU
IAC
PIB
WIU
ACP PS
(E)IAC035
WI038
(E)PI035
WI039
(E)PI036
(E)IAC036
(E)IAC037
WI040
(E)PI037 (E)IAC038
WI041
(E)PI038
(E)IAC039
WI042
(E)PI039
WI043
(E)PI040(E)IAC040
(E)IAC041 (E)IAC042
WI044 WI045
(E)PI042
(E)PI041
(E)IAC043
(E)PI043
WI046
(E)IAC044
WI047
(E)PI044
WI048
(E)PI045
(E)IAC045
FILE:
DRAWN BY:
CHECKED BY:
PROJ. NO:
DRAWING NO:
DRAWING TITLE:
PROJECT NAME:
http://www.ZDSDesign.com
135 Corporate Center Drive Suite 532 Scott Depot, WV 25560
TEL 304/755-0075
FAX 304/755-0076
THIS SQUARE APPEARS 1/2"x1/2"
ON FULL SIZE SHEETS
CLIENT:
XXX
C :\U se rs
\e di so n.
ad ki ns \D oc um en ts
\G
SD
2C
_2
4-
-1 0_
BL
D
G
FA
IR
M
O N
T_ ed is on
.a dk in s.
rv t
8/
/2
:2 5:
P
M
54-TD-105
EA
TZ3
GSD-252-C
DEMO PLAN FIFTH
FLOOR
BUILDING 54 SECURITY
SYSTEM UPGRADES
416 Adams Street Fairmont, WV 26301
WEST VIRGINIA
GENERAL SERVICES
DIVISION
1/8" = 1'-0"54-TD-105
1 DEMO PLAN FIFTH FLOOR SECURITY
KEYNOTES
1 EXISTING PANEL INTERFACE BOARDS (SCHLAGE PIB-300-2D) FOR EXISTING
SCHLAGE AD-300 WIRED NETWORK LOCKS TO REMAIN UNLESS NEW SYSTEM IS
CAPABLE OF COMMUNICATING DIRECTLY WITH THE LOCKS VIA RS-485.
INTEGRATE EXISTING NETWORK LOCKS INTO NEW SYSTEM.
SYSTEMS DEMOLITION NOTES
1 DISCONNECT AND REMOVE ONLY SYSTEM DEVICES SHOWN TO BE DEMOLISHED.
2 DISCONNECT AND REMOVE ASSOCIATED CONDUIT AND WIRE BACK TO LAST
REMAINING DEVICE. FURNISH AND INSTALL CONDUIT AND WIRE AS NECESSARY
FOR CONTINUITY OF CIRCUIT(S) TO ANY EXISTING DEVICES TO REMAIN.
COORDINATE AND VERIFY REQUIREMENTS WITH NEW WORK IN AREA.
3 FURNISH AND INSTALL CONDUIT AND/OR SYSTEMS WIRING AS NECESSARY FOR
CONTINUITY OF ANY SYSTEMS EQUIPMENT OR DEVICES TO REMAIN. MODIFY OR
REPLACE AS REQUIRED.
4 FURNISH AND INSTALL BLANK COVER PLATES FOR ALL EXISTING UNUSED
OPENINGS.
5 BUILDINGS THAT HAVE CAMERAS THAT WORK OR WOULD WORK IF THE
SOFTWARE AND LICENSES WERE CURRENT SHOULD HAVE NEW NVRS INSTALLED
AND THE EXISTING CAMERAS CONNECTED TO THEM. AS NEW CAMERAS ARE
INSTALLED, REMOVE OLD CAMERAS FROM THE SYSTEM.
6 THE EXISTING ACCESS CONTROL SYSTEM IS TO REMAIN IN USE UNTIL THE NEW
SYSTEM IS COMPLETE. DOORS SHOULD BE MIGRATED TO THE NEW SYSTEM ONE
AT A TIME UNTIL ALL ARE ON THE NEW SYSTEM. DURING THIS MIGRATION, NO
CR
CR
DC
DC
JB
JB
ES
ES
FILE:
DRAWN BY:
CHECKED BY:
PROJ. NO:
DRAWING NO:
DRAWING TITLE:
PROJECT NAME:
http://www.ZDSDesign.com
135 Corporate Center Drive Suite 532 Scott Depot, WV 25560
TEL 304/755-0075
FAX 304/755-0076
THIS SQUARE APPEARS 1/2"x1/2"
ON FULL SIZE SHEETS
CLIENT:
XXX
C :\U se rs
\e di so n.
ad ki ns \D oc um en ts
\G
SD
2C
_2
4-
-1 0_
BL
D
G
FA
IR
M
O N
T_ ed is on
.a dk in s.
rv t
8/
/2
:2 5:
P
M
54-TD-106
EA
TZ3
GSD-252-C
DEMO PLAN ROOF
BUILDING 54 SECURITY
SYSTEM UPGRADES
416 Adams Street Fairmont, WV 26301
WEST VIRGINIA
GENERAL SERVICES
DIVISION
# KEYNOTES
1/8" = 1'-0"54-TD-106
1 DEMO PLAN ROOF SECURITY
SYSTEMS DEMOLITION NOTES
1 DISCONNECT AND REMOVE ONLY SYSTEM DEVICES SHOWN TO BE DEMOLISHED.
2 DISCONNECT AND REMOVE ASSOCIATED CONDUIT AND WIRE BACK TO LAST
REMAINING DEVICE. FURNISH AND INSTALL CONDUIT AND WIRE AS NECESSARY
FOR CONTINUITY OF CIRCUIT(S) TO ANY EXISTING DEVICES TO REMAIN.
COORDINATE AND VERIFY REQUIREMENTS WITH NEW WORK IN AREA.
3 FURNISH AND INSTALL CONDUIT AND/OR SYSTEMS WIRING AS NECESSARY FOR
CONTINUITY OF ANY SYSTEMS EQUIPMENT OR DEVICES TO REMAIN. MODIFY OR
REPLACE AS REQUIRED.
4 FURNISH AND INSTALL BLANK COVER PLATES FOR ALL EXISTING UNUSED
OPENINGS.
5 BUILDINGS THAT HAVE CAMERAS THAT WORK OR WOULD WORK IF THE
SOFTWARE AND LICENSES WERE CURRENT SHOULD HAVE NEW NVRS INSTALLED
AND THE EXISTING CAMERAS CONNECTED TO THEM. AS NEW CAMERAS ARE
INSTALLED, REMOVE OLD CAMERAS FROM THE SYSTEM.
6 THE EXISTING ACCESS CONTROL SYSTEM IS TO REMAIN IN USE UNTIL THE NEW
SYSTEM IS COMPLETE. DOORS SHOULD BE MIGRATED TO THE NEW SYSTEM ONE
AT A TIME UNTIL ALL ARE ON THE NEW SYSTEM. DURING THIS MIGRATION, NO
MECH
WATER SERVICE
UPS EQUIPMENT
LOBBY
ELEV A
A-1
ELEV B
B-1
STAIR 1
ST1-1 PLENUM
105 PLENUM
DATA
ATS ROOM
ELECTRICAL
EXTERIOR MECH /
ELECTRICAL
ME
ELEVATOR EQUIPMENT
UP
ES
IA
C
JB
PIB
AR
AM
IAC
IAC
PIB
IAC
PIB
PIBPI
B IAC
CR
ES
JB
DC
DCDC
DC DC DC DCDC
CR
CR CR
AC
P
CR
ES
ACP
DC001
CR001
NEW
ES001
NEW
(E)IAC001
DC003
DC002
CR002
C002
TYPE M
C001
TYPE F
14' AFF
DC004 DC005
(E)IAC003
(E)PI003
(E)IAC002
(E)PI002
(E)IAC005
(E)PI005
(E)IAC004
(E)PI004
DC006
DC007
ACP001
DC008
C005
TYPE A
CR003 CR004
(E)PI001
C003
TYPE F
14' AFF
(E)ES002
1 2
SNR001
ES021
NEW
CR020
NEW
ACP007
7 7
FILE:
DRAWN BY:
CHECKED BY:
PROJ. NO:
DRAWING NO:
DRAWING TITLE:
PROJECT NAME:
http://www.ZDSDesign.com
135 Corporate Center Drive Suite 532 Scott Depot, WV 25560
TEL 304/755-0075
FAX 304/755-0076
THIS SQUARE APPEARS 1/2"x1/2"
ON FULL SIZE SHEETS
CLIENT:
XXX
C :\U se rs
\e di so n.
ad ki ns \D oc um en ts
\G
SD
2C
_2
4-
-1 0_
BL
D
G
FA
IR
M
O N
T_ ed is on
.a dk in s.
rv t
8/
/2
:2 5:
P
M
54-TY-101
EA
TZ3
GSD-252-C
FIRST FLOOR SECURITY
PLAN
BUILDING 54 SECURITY
SYSTEM UPGRADES
416 Adams Street Fairmont, WV 26301
WEST VIRGINIA
GENERAL SERVICES
DIVISION
1/8" = 1'-0"54-TY-101
1 PROPOSED SECURITY PLAN FIRST FLOOR
KEYNOTES
1 ACCESS CONTROL PANEL FOR IN-CAB CARD READERS. PROVIDE OUTPUTS FOR
ALL FLOORS SERVED BY THE ELEVATOR. ACCESS SHALL BE CONTROLLABLE BY
THE INDIVIDUAL FLOOR. CURRENT CONFIGURATION LIMITS ACCESS TO THE
FIRST, FOURTH, AND FIFTH FLOORS WITHOUT A VALID CREDENTIAL.
2 EXISTING PANEL INTERFACE BOARDS (SCHLAGE PIB-300-2D) FOR EXISTING
SCHLAGE AD-300 WIRED NETWORK LOCKS TO REMAIN UNLESS NEW SYSTEM IS
CAPABLE OF COMMUNICATING DIRECTLY WITH THE LOCKS VIA RS-485.
INTEGRATE EXISTING NETWORK LOCKS INTO NEW SYSTEM.
3 IN-CAB CARD READER. CURRENT CONFIGURATION LIMITS ACCESS TO THE FIRST,
FOURTH, AND FIFTH FLOORS WITHOUT A VALID CREDENTIAL.
4 PROVIDE 12 STRAND MM OM4 ARMORED FIBER TO SNR002. TERMINATE FIBER IN
FIBER TERMINATION PANEL AT BOTH ENDS.
5 NEW SECURITY NETWORK RACK. SEE SPECIFICATIONS AND DETAIL 1 ON SHEET
54-TY-501.
7 APPROXIMATE ELEVATION ABOVE GRADE. MOUNT NEW CAMERA AT THE SAME
ELEVATION AS THE EXISTING.
SECURITY SYSTEM SHEET NOTES
A SEE DETAIL SHEET FOR SECURITY CAMERA MOUNTING
B SEE SECURITY DEVICE SCHEDULE FOR ADDITIONAL INFORMATION
C ALL COMMUNICATION CABLES SHALL BE INSTALLED IN CONDUIT, CABLE TRAY, OR
SUPPORTED BY CABLE HOOKS. PROVIDE BUSHINGS AT THE ENDS OF ALL
CONDUITS WHERE STUBBED ABOVE ACCESSIBLE CEILINGS OR WHERE DROPPED
INTO CABLE TRAYS. PROVIDE CABLE HOOKS ABOVE ACCESSIBLE CEILINGS FOR
CABLE INSTALLATION WHERE NOT INSTALLED IN A CONDUIT OR CABLE TRAY.
D BUILDINGS THAT HAVE CAMERAS THAT WORK OR WOULD WORK IF THE
SOFTWARE AND LICENSES WERE CURRENT SHOULD HAVE NEW NVRS INSTALLED
AND THE EXISTING CAMERAS CONNECTED TO THEM. AS NEW CAMERAS ARE
INSTALLED, REMOVE OLD CAMERAS FROM THE SYSTEM.
E ALL CABLES AND DEVICES TO BE LABELED. SEE SPECIFICATION AND DETAILS
FOR SPECIFIC REQUIREMENTS.
F THE EXISTING ACCESS CONTROL SYSTEM IS TO REMAIN IN USE UNTIL THE NEW
SYSTEM IS COMPLETE. DOORS SHOULD BE MIGRATED TO THE NEW SYSTEM ONE
AT A TIME UNTIL ALL ARE ON THE NEW SYSTEM. DURING THIS MIGRATION, NO
DOOR IS TO REMAIN UNSECURED OR INOPERABLE AT THE END OF A WORKDAY.
G PROVIDE SURGE PROTECTION FOR ALL EXTERIOR CAMERAS.
CONF
OPEN
SECOND FLOOR
VESTIBULE
VESTIBULE
200A
STAIR 1
ST1-2
ELEV A
A-2
ELEV B
B-2
WOMEN'S PUBLIC
MEN'S PUBLIC
CENTRAL CONTROL
RECEPTION
WORKFORCE
COFFEE
HALL
COMPUTER TRAINING
STORAGE
212A
JAN
OFFICE
OFFICE
OFFICE
OFFICE
CONFERENCE
BREAK
CONF
OFFICE
OFFICE
WORK
STORAGE
HALL
HALL
ELEC
HALL
BREAK
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
HALL
REHAB
TENANT STORAGE
STORAGE
MAINTENANCE OFFICE
MECH
MAINTENANCE
MAIL ROOM
261WOMEN'S
MEN'S
STAIR 2
ST2-2
DATA
ES
IAC IAC
IAC
IAC
IAC
JB
PIB
PIB
PI
B
PIB PIB
PIB
PIB PIB PIB PIB
PIB
IAC
IAC
IAC IACIAC
IA
C
IAC
IA
C
SWKS
CR
ES
JB
CR
ES
JB
CR
ES
JB
PIB
PIB
DC
DC
DC
DC
DC DC
DC
DC
DC
CR
ACP
ACP
MO
N
MON
MO
N
DR
CW
KS
SECURITY DESK
C006
TYPE F
14' AFF
DC009
DC010
CR005
DC011
DC012
SWKS01
CR007
NEW
C014
TYPE A
ES004
NEW
ES005
NEW
(E)IAC006
(E)PI006
C007
TYPE F
8' AFF
C012
TYPE A
C011
TYPE B
C013
TYPE A
(E)PI007
(E)IAC007
(E)IAC008
(E)PI008
(E)PI009
(E)IAC009 (E)IAC010
(E)PI010
(E)IAC011
(E)PI011
C008
TYPE F
8' AFF
C009
TYPE B
(E)IAC014
(E)PI014
(E)PI013
(E)IAC013
(E)IAC012
(E)PI012
(E)PI015
(E)IAC015 (E)IAC016
(E)PI016 (E)IAC017 (E)PI017
DC016
(E)IAC018
(E)PI018
(E)ES003
CR008
NEW
ES006
NEW
CR006
NEW
DC014
DC013
DC015
DC017
ACP002
ACP003
1 1
M003
M001
M002
(E)SNR002
C040
TYPE P
28' AFF
C041
TYPE P
28' AFF
C042
TYPE P
14' AFF
DR001
CWKS01
FILE:
DRAWN BY:
CHECKED BY:
PROJ. NO:
DRAWING NO:
DRAWING TITLE:
PROJECT NAME:
http://www.ZDSDesign.com
135 Corporate Center Drive Suite 532 Scott Depot, WV 25560
TEL 304/755-0075
FAX 304/755-0076
THIS SQUARE APPEARS 1/2"x1/2"
ON FULL SIZE SHEETS
CLIENT:
XXX
C :\U se rs
\e di so n.
ad ki ns \D oc um en ts
\G
SD
2C
_2
4-
-1 0_
BL
D
G
FA
IR
M
O N
T_ ed is on
.a dk in s.
rv t
8/
/2
:2 5:
P
M
54-TY-102
EA
TZ3
GSD-252-C
SECOND FLOOR
SECURITY PLAN
BUILDING 54 SECURITY
SYSTEM UPGRADES
416 Adams Street Fairmont, WV 26301
WEST VIRGINIA
GENERAL SERVICES
DIVISION
1/8" = 1'-0"54-TY-102
1 PROPOSED SECURITY PLAN SECOND FLOOR
KEYNOTES
1 EXISTING PANEL INTERFACE BOARDS (SCHLAGE PIB-300-2D) FOR EXISTING
SCHLAGE AD-300 WIRED NETWORK LOCKS TO REMAIN UNLESS NEW SYSTEM IS
CAPABLE OF COMMUNICATING DIRECTLY WITH THE LOCKS VIA RS-485.
INTEGRATE EXISTING NETWORK LOCKS INTO NEW SYSTEM.
2 EXISTING SECURITY RACK TO REMAIN AND BE REUSED. REMOVE ALL UNUSED
EQUIPMENT. SEE DETAIL 1 ON SHEET 54-TY-501 FOR NEW EQUIPMENT LAYOUT.
3 SECURITY WORKSTATION WITH QTY 3 - 34" CURVED DESKTOP MONITORS
4 THIS DOOR LOCKS ON A SCHEDULE (UNLOCKED DURING NORMAL BUSINESS
HOURS). VERIFY SCHEDULE REQUIREMENTS WITH OWNER.
5 PROVIDE 12 STRAND MM OM4 ARMOURED FIBER TO SNR001 AND SNR003.
TERMINATE FIBER IN FIBER TERMINATION PANEL AT BOTH ENDS.
6 MOUNT ON CANOPY.
7 APPROXIMATE ELEVATION ABOVE GRADE. MOUNT NEW CAMERA AT THE SAME
ELEVATION AS THE EXISTING.
8 CREDENTIALING WORKSTATION. COORDINATE EXACT LOCATION WITH OWNER.
SECURITY SYSTEM SHEET NOTES
A SEE DETAIL SHEET FOR SECURITY CAMERA MOUNTING
B SEE SECURITY DEVICE SCHEDULE FOR ADDITIONAL INFORMATION
C ALL COMMUNICATION CABLES SHALL BE INSTALLED IN CONDUIT, CABLE TRAY, OR
SUPPORTED BY CABLE HOOKS. PROVIDE BUSHINGS AT THE ENDS OF ALL
CONDUITS WHERE STUBBED ABOVE ACCESSIBLE CEILINGS OR WHERE DROPPED
INTO CABLE TRAYS. PROVIDE CABLE HOOKS ABOVE ACCESSIBLE CEILINGS FOR
CABLE INSTALLATION WHERE NOT INSTALLED IN A CONDUIT OR CABLE TRAY.
D BUILDINGS THAT HAVE CAMERAS THAT WORK OR WOULD WORK IF THE
SOFTWARE AND LICENSES WERE CURRENT SHOULD HAVE NEW NVRS INSTALLED
AND THE EXISTING CAMERAS CONNECTED TO THEM. AS NEW CAMERAS ARE
INSTALLED, REMOVE OLD CAMERAS FROM THE SYSTEM.
E ALL CABLES AND DEVICES TO BE LABELED. SEE SPECIFICATION AND DETAILS
FOR SPECIFIC REQUIREMENTS.
F THE EXISTING ACCESS CONTROL SYSTEM IS TO REMAIN IN USE UNTIL THE NEW
SYSTEM IS COMPLETE. DOORS SHOULD BE MIGRATED TO THE NEW SYSTEM ONE
AT A TIME UNTIL ALL ARE ON THE NEW SYSTEM. DURING THIS MIGRATION, NO
DOOR IS TO REMAIN UNSECURED OR INOPERABLE AT THE END OF A WORKDAY.
FAMILY VISITATION
VIDEO
MDT OFFICE
CONF
HALL
RESTROOM
INT
INT
INT
HALL
RECEPT
309 MAIL
SWBRD
HALL
INT
INT
INT
INT
WOMEN'S PUBLIC
MEN'S PUBLIC
THIRD FLOOR
DHHR LOBBY
HALL
HIGH DENSITY
OPEN
OPEN
OPEN
JAN
ELEC
CSM OFFICE
CSM ADMIN
FINANCE (2PP)
STORAGE
OPS OFFICE
HALL
YS OFFICE
SS COORD
WVW OFFICE
CPS OFFICE
AS OFFICE
INCOME OFFICE
HALL
CPS OFFICE
STORAGE
INCOME OFFICE
OPEN
BREAK
MEN'S
WOMEN'S
STAIR 2
ST2-3
DATA
CORRIDOR
301A
AR
AR
PI
B
PI
B
PIB
PIB
IAC
IACIAC
PIB
IA
C
PI
B
IA
C
IA
C
CR
ES
JB
CR
ES
JB
CR
ES
JB
CR CR
ES ES
JB JB
ACP
IAC
ACP004
CR009
NEW
ES007
NEW
ES008
NEW
CR010
NEW
ES009
NEW
CR011
NEW
(E)IAC019
(E)PI019
(E)PI020
(E)IAC020
(E)IAC021
(E)PI021
CR012
NEW
ES010
NEW
CR013
NEW
ES011
NEW
(E)IAC022
(E)PI022
(E)IAC024
(E)PI024
C021
TYPE F
14' AFF
(E)PI025
(E)IAC025
C020
TYPE BC018
TYPE B
C022
TYPE F
8' AFF
C024
TYPE E
14' AFF
C023
TYPE E
12' AFF
C039
TYPE C
1 1 1
SNR003
C045
TYPE C
4 5
IAC023
FILE:
DRAWN BY:
CHECKED BY:
PROJ. NO:
DRAWING NO:
DRAWING TITLE:
PROJECT NAME:
http://www.ZDSDesign.com
135 Corporate Center Drive Suite 532 Scott Depot, WV 25560
TEL 304/755-0075
FAX 304/755-0076
THIS SQUARE APPEARS 1/2"x1/2"
ON FULL SIZE SHEETS
CLIENT:
XXX
C :\U se rs
\e di so n.
ad ki ns \D oc um en ts
\G
SD
2C
_2
4-
-1 0_
BL
D
G
FA
IR
M
O N
T_ ed is on
.a dk in s.
rv t
8/
/2
:2 5:
P
M
54-TY-103
EA
TZ3
GSD-252-C
THIRD FLOOR SECURITY
PLAN
BUILDING 54 SECURITY
SYSTEM UPGRADES
416 Adams Street Fairmont, WV 26301
WEST VIRGINIA
GENERAL SERVICES
DIVISION
1/8" = 1'-0"54-TY-103
1 PROPOSED SECURITY PLAN THIRD FLOOR
KEYNOTES
1 EXISTING PANEL INTERFACE BOARDS (SCHLAGE PIB-300-2D) FOR EXISTING
SCHLAGE AD-300 WIRED NETWORK LOCKS TO REMAIN UNLESS NEW SYSTEM IS
CAPABLE OF COMMUNICATING DIRECTLY WITH THE LOCKS VIA RS-485.
INTEGRATE EXISTING NETWORK LOCKS INTO NEW SYSTEM.
2 THIS DOOR DOES NOT LOCK. REPLACE EXISTING LOCK AND INTERFACE WITH NEW
TO MATCH EXISTING. CONNECT TO NEW SYSTEM.
3 THIS DOOR LOCKS ON A SCHEDULE. VERIFY SCHEDULE REQUIREMENTS WITH
DHHR.
4 NEW SECURITY NETWORK RACK. SEE SPECIFICATIONS AND DETAIL 1 ON SHEET
54-TY-501.
5 PROVIDE 12 STRAND MM OM4 ARMOURED FIBER TO SNR002 AND SNR004.
TERMINATE FIBER IN FIBER TERMINATION PANEL AT BOTH ENDS.
6 APPROXIMATE ELEVATION ABOVE GRADE. MOUNT NEW CAMERA AT THE SAME
ELEVATION AS THE EXISTING.
SECURITY SYSTEM SHEET NOTES
A SEE DETAIL SHEET FOR SECURITY CAMERA MOUNTING
B SEE SECURITY DEVICE SCHEDULE FOR ADDITIONAL INFORMATION
C ALL COMMUNICATION CABLES SHALL BE INSTALLED IN CONDUIT, CABLE TRAY, OR
SUPPORTED BY CABLE HOOKS. PROVIDE BUSHINGS AT THE ENDS OF ALL
CONDUITS WHERE STUBBED ABOVE ACCESSIBLE CEILINGS OR WHERE DROPPED
INTO CABLE TRAYS. PROVIDE CABLE HOOKS ABOVE ACCESSIBLE CEILINGS FOR
CABLE INSTALLATION WHERE NOT INSTALLED IN A CONDUIT OR CABLE TRAY.
D BUILDINGS THAT HAVE CAMERAS THAT WORK OR WOULD WORK IF THE
SOFTWARE AND LICENSES WERE CURRENT SHOULD HAVE NEW NVRS INSTALLED
AND THE EXISTING CAMERAS CONNECTED TO THEM. AS NEW CAMERAS ARE
INSTALLED, REMOVE OLD CAMERAS FROM THE SYSTEM.
E ALL CABLES AND DEVICES TO BE LABELED. SEE SPECIFICATION AND DETAILS
FOR SPECIFIC REQUIREMENTS.
F THE EXISTING ACCESS CONTROL SYSTEM IS TO REMAIN IN USE UNTIL THE NEW
SYSTEM IS COMPLETE. DOORS SHOULD BE MIGRATED TO THE NEW SYSTEM ONE
AT A TIME UNTIL ALL ARE ON THE NEW SYSTEM. DURING THIS MIGRATION, NO
DOOR IS TO REMAIN UNSECURED OR INOPERABLE AT THE END OF A WORKDAY.
STAIR 1
ST1-4
FOURTH FLOOR
ELEV A
A-4
ELEV B
B-4
OFFICE
OFFICE
OFFICE
S.O.S. OFFICES
RESTROOM
OFFICE
OFFICE
OFFICE
428 OFFICE
HALL
420ASTOR
EVIDENCE
424 STORAGE
POLYGRAPH
CONFERENCE
I.C.I.G.
OFFICE
OFFICE
RESEARCH & COMPLIANCE
COMPUTER TRAINING
CONFERENCE B
409 CONFERENCE B
WOMEN'S PUBLIC
402 MEN'S PUBLIC
403 JAN
TRAINING
ELEC
CONFERENCE C
HALL
HALL
OPEN
OPEN
TITLE IV-E (3 PPL)
CSC OFFICE
OIG
FINGER PRINTING
CSC OFFICE
OIG
STORAGE
CSC HOTEL OFFICE
HALL
BREAK ROOM
MEN'S
WOMEN'S
STAIR 2
ST2-4
DATA
AR
AR
IAC
JB
PIB PIB PIB
PI
B
PIB PIB
PIB PIB
PI
B
IAC
IAC IAC
IAC IAC
IAC IAC
IA
C
JB
ES
ES
ACP
CR
CR
IAC
PIB
(E)IAC027
(E)PI027 (E)PI028
(E)IAC028
(E)IAC029
(E)PI029 (E)PI030
(E)IAC030
(E)IAC031
(E)PI031
C025
TYPE B
(E)IAC032(E)PI032
ACP005
(E)PI033(E)IAC033
CR014
CR015
(E)IAC034
(E)PI034
(E)IAC026
(E)PI026
1 1 1
1 1(E)ES012
(E)ES013
SNR004
(E)PI046
(E)IAC046
C043
TYPE H
2 3
FILE:
DRAWN BY:
CHECKED BY:
PROJ. NO:
DRAWING NO:
DRAWING TITLE:
PROJECT NAME:
http://www.ZDSDesign.com
135 Corporate Center Drive Suite 532 Scott Depot, WV 25560
TEL 304/755-0075
FAX 304/755-0076
THIS SQUARE APPEARS 1/2"x1/2"
ON FULL SIZE SHEETS
CLIENT:
XXX
C :\U se rs
\e di so n.
ad ki ns \D oc um en ts
\G
SD
2C
_2
4-
-1 0_
BL
D
G
FA
IR
M
O N
T_ ed is on
.a dk in s.
rv t
8/
/2
:2 5:
P
M
54-TY-104
EA
TZ3
GSD-252-C
FOURTH FLOOR
SECURITY PLAN
BUILDING 54 SECURITY
SYSTEM UPGRADES
416 Adams Street Fairmont, WV 26301
WEST VIRGINIA
GENERAL SERVICES
DIVISION
1/8" = 1'-0"54-TY-104
1 PROPOSED SECURITY PLAN FOURTH FLOOR
KEYNOTES
1 EXISTING PANEL INTERFACE BOARDS (SCHLAGE PIB-300-2D) FOR EXISTING
SCHLAGE AD-300 WIRED NETWORK LOCKS TO REMAIN UNLESS NEW SYSTEM IS
CAPABLE OF COMMUNICATING DIRECTLY WITH THE LOCKS VIA RS-485.
INTEGRATE EXISTING NETWORK LOCKS INTO NEW SYSTEM.
2 NEW SECURITY NETWORK RACK. SEE SPECIFICATIONS AND DETAIL 1 ON SHEET
54-TY-501.
3 PROVIDE 12 STRAND MM OM4 ARMOURED FIBER TO SNR003 AND SNR005.
TERMINATE FIBER IN FIBER TERMINATION PANEL AT BOTH ENDS.
SECURITY SYSTEM SHEET NOTES
A SEE DETAIL SHEET FOR SECURITY CAMERA MOUNTING
B SEE SECURITY DEVICE SCHEDULE FOR ADDITIONAL INFORMATION
C ALL COMMUNICATION CABLES SHALL BE INSTALLED IN CONDUIT, CABLE TRAY, OR
SUPPORTED BY CABLE HOOKS. PROVIDE BUSHINGS AT THE ENDS OF ALL
CONDUITS WHERE STUBBED ABOVE ACCESSIBLE CEILINGS OR WHERE DROPPED
INTO CABLE TRAYS. PROVIDE CABLE HOOKS ABOVE ACCESSIBLE CEILINGS FOR
CABLE INSTALLATION WHERE NOT INSTALLED IN A CONDUIT OR CABLE TRAY.
D BUILDINGS THAT HAVE CAMERAS THAT WORK OR WOULD WORK IF THE
SOFTWARE AND LICENSES WERE CURRENT SHOULD HAVE NEW NVRS INSTALLED
AND THE EXISTING CAMERAS CONNECTED TO THEM. AS NEW CAMERAS ARE
INSTALLED, REMOVE OLD CAMERAS FROM THE SYSTEM.
E ALL CABLES AND DEVICES TO BE LABELED. SEE SPECIFICATION AND DETAILS
FOR SPECIFIC REQUIREMENTS.
F THE EXISTING ACCESS CONTROL SYSTEM IS TO REMAIN IN USE UNTIL THE NEW
SYSTEM IS COMPLETE. DOORS SHOULD BE MIGRATED TO THE NEW SYSTEM ONE
AT A TIME UNTIL ALL ARE ON THE NEW SYSTEM. DURING THIS MIGRATION, NO
DOOR IS TO REMAIN UNSECURED OR INOPERABLE AT THE END OF A WORKDAY.
OPEN
FIFTH FLOOR
OFFICE
OFFICE
OFFICE
OFFICE
STORAGE
ADMIN
574OFFICE
HALL
STAIR 1
ST1-5
OFFICE
OFFICE
LAB
PLAN ROOM
FILES
REGIONAL
OFFICE
OFFICE
ELEV A
A-5
ELEV B
B-5
STAIR 2
ST2-5
OFFICE
OFFICE
OFFICE
OFFICE
STORAGE
CONF
OFFICE
OFFICE
OFFICE
OFFICE
BREAK
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
WORK
OFFICE
CONF
STORAGE
WOMEN'S PUBLIC
MEN'S PUBLIC
JAN
STORAGE
DATA
ELEC
HALL
HALL
HALL
HALL
HALL
OFFICE
578 HALL
WORK
OFFICE
BREAK
CONF
OFFICE
BCSE
MENS
WOMEN'S
OEHS
BREAK
HALL
AR
AR
IAC
PIB
PIB PIB
PIB
PI
B
PIB
JB
ES
JB
ES
IA
C
IAC
IAC
IAC IAC
PIB IACPIBIAC
IACIAC PIB PIB
IAC
PIB
CR
ACP
CR
CR016
C035
TYPE C
(E)IAC035
(E)PI035
(E)PI036
(E)IAC036
(E)IAC037
(E)PI037
(E)IAC038
(E)PI038 (E)IAC039
(E)PI039 (E)PI040
(E)IAC040
(E)IAC041 (E)IAC042
(E)PI042(E)PI041
CR017
(E)IAC043
(E)PI043
(E)IAC044
(E)PI044
(E)PI045
(E)IAC045
ACP006
(E)ES014
(E)ES015
SNR005
C046
TYPE B 2
3 4
FILE:
DRAWN BY:
CHECKED BY:
PROJ. NO:
DRAWING NO:
DRAWING TITLE:
PROJECT NAME:
http://www.ZDSDesign.com
135 Corporate Center Drive Suite 532 Scott Depot, WV 25560
TEL 304/755-0075
FAX 304/755-0076
THIS SQUARE APPEARS 1/2"x1/2"
ON FULL SIZE SHEETS
CLIENT:
XXX
C :\U se rs
\e di so n.
ad ki ns \D oc um en ts
\G
SD
2C
_2
4-
-1 0_
BL
D
G
FA
IR
M
O N
T_ ed is on
.a dk in s.
rv t
8/
/2
:2 6:
P
M
54-TY-105
EA
TZ3
GSD-252-C
FIFTH FLOOR SECURITY
PLAN
BUILDING 54 SECURITY
SYSTEM UPGRADES
416 Adams Street Fairmont, WV 26301
WEST VIRGINIA
GENERAL SERVICES
DIVISION
1/8" = 1'-0"54-TY-105
1 PROPOSED SECURITY PLAN FIFTH FLOOR
KEYNOTES
1 EXISTING PANEL INTERFACE BOARDS (SCHLAGE PIB-300-2D) FOR EXISTING
SCHLAGE AD-300 WIRED NETWORK LOCKS TO REMAIN UNLESS NEW SYSTEM IS
CAPABLE OF COMMUNICATING DIRECTLY WITH THE LOCKS VIA RS-485.
INTEGRATE EXISTING NETWORK LOCKS INTO NEW SYSTEM.
2 THIS LOCK TO BE LEFT IN AN UNLOCKED STATE. OWNER WISHES TO HAVE FREE
ACCESS AT THIS DOOR WITH THE ABILITY TO RESTRICT ACCESS IN THE FUTURE.
INTEGRATE THE EXISTING LOCK INTO NEW SYSTEM, VERIFY PROPER OPERATION
AND PLACE IN AN UNLOCKED STATE VIA THE ACCESS CONTROL SOFTWARE.
3 NEW SECURITY NETWORK RACK. SEE SPECIFICATIONS AND DETAIL 1 ON SHEET
54-TY-501.
4 PROVIDE 12 STRAND MM OM4 ARMOURED FIBER TO SNR004. TERMINATE FIBER IN
FIBER TERMINATION PANEL AT BOTH ENDS.
SECURITY SYSTEM SHEET NOTES
A SEE DETAIL SHEET FOR SECURITY CAMERA MOUNTING
B SEE SECURITY DEVICE SCHEDULE FOR ADDITIONAL INFORMATION
C ALL COMMUNICATION CABLES SHALL BE INSTALLED IN CONDUIT, CABLE TRAY, OR
SUPPORTED BY CABLE HOOKS. PROVIDE BUSHINGS AT THE ENDS OF ALL
CONDUITS WHERE STUBBED ABOVE ACCESSIBLE CEILINGS OR WHERE DROPPED
INTO CABLE TRAYS. PROVIDE CABLE HOOKS ABOVE ACCESSIBLE CEILINGS FOR
CABLE INSTALLATION WHERE NOT INSTALLED IN A CONDUIT OR CABLE TRAY.
D BUILDINGS THAT HAVE CAMERAS THAT WORK OR WOULD WORK IF THE
SOFTWARE AND LICENSES WERE CURRENT SHOULD HAVE NEW NVRS INSTALLED
AND THE EXISTING CAMERAS CONNECTED TO THEM. AS NEW CAMERAS ARE
INSTALLED, REMOVE OLD CAMERAS FROM THE SYSTEM.
E ALL CABLES AND DEVICES TO BE LABELED. SEE SPECIFICATION AND DETAILS
FOR SPECIFIC REQUIREMENTS.
F THE EXISTING ACCESS CONTROL SYSTEM IS TO REMAIN IN USE UNTIL THE NEW
SYSTEM IS COMPLETE. DOORS SHOULD BE MIGRATED TO THE NEW SYSTEM ONE
AT A TIME UNTIL ALL ARE ON THE NEW SYSTEM. DURING THIS MIGRATION, NO
DOOR IS TO REMAIN UNSECURED OR INOPERABLE AT THE END OF A WORKDAY.
JB
JB
ES
ES
CR
DC
CR
DC
CR018
DC018
CR019
DC019
(E)ES016
(E)ES017
FILE:
DRAWN BY:
CHECKED BY:
PROJ. NO:
DRAWING NO:
DRAWING TITLE:
PROJECT NAME:
http://www.ZDSDesign.com
135 Corporate Center Drive Suite 532 Scott Depot, WV 25560
TEL 304/755-0075
FAX 304/755-0076
THIS SQUARE APPEARS 1/2"x1/2"
ON FULL SIZE SHEETS
CLIENT:
XXX
C :\U se rs
\e di so n.
ad ki ns \D oc um en ts
\G
SD
2C
_2
4-
-1 0_
BL
D
G
FA
IR
M
O N
T_ ed is on
.a dk in s.
rv t
8/
/2
:2 6:
P
M
54-TY-106
EA
TZ3
GSD-252-C
ROOF SECURITY PLAN
BUILDING 54 SECURITY
SYSTEM UPGRADES
416 Adams Street Fairmont, WV 26301
WEST VIRGINIA
GENERAL SERVICES
DIVISION
1/8" = 1'-0"54-TY-106
1 PROPOSED SECURITY PLAN PARTIAL ROOF
KEYNOTES#
SECURITY SYSTEM SHEET NOTES
A SEE DETAIL SHEET FOR SECURITY CAMERA MOUNTING
B SEE SECURITY DEVICE SCHEDULE FOR ADDITIONAL INFORMATION
C ALL COMMUNICATION CABLES SHALL BE INSTALLED IN CONDUIT, CABLE TRAY, OR
SUPPORTED BY CABLE HOOKS. PROVIDE BUSHINGS AT THE ENDS OF ALL
CONDUITS WHERE STUBBED ABOVE ACCESSIBLE CEILINGS OR WHERE DROPPED
INTO CABLE TRAYS. PROVIDE CABLE HOOKS ABOVE ACCESSIBLE CEILINGS FOR
CABLE INSTALLATION WHERE NOT INSTALLED IN A CONDUIT OR CABLE TRAY.
D BUILDINGS THAT HAVE CAMERAS THAT WORK OR WOULD WORK IF THE
SOFTWARE AND LICENSES WERE CURRENT SHOULD HAVE NEW NVRS INSTALLED
AND THE EXISTING CAMERAS CONNECTED TO THEM. AS NEW CAMERAS ARE
INSTALLED, REMOVE OLD CAMERAS FROM THE SYSTEM.
E ALL CABLES AND DEVICES TO BE LABELED. SEE SPECIFICATION AND DETAILS
FOR SPECIFIC REQUIREMENTS.
F THE EXISTING ACCESS CONTROL SYSTEM IS TO REMAIN IN USE UNTIL THE NEW
SYSTEM IS COMPLETE. DOORS SHOULD BE MIGRATED TO THE NEW SYSTEM ONE
AT A TIME UNTIL ALL ARE ON THE NEW SYSTEM. DURING THIS MIGRATION, NO
DOOR IS TO REMAIN UNSECURED OR INOPERABLE AT THE END OF A WORKDAY.
FIBER TERMINATION PANEL
96TB NVR
2000VA UPS FOR NVR
2000VA UPS FOR APP. AND
SWITCH
BLANK PANEL
24 PORT SWITCH
CAT 6 PATCH PANEL
VENT PANEL
VENT PANEL
VENT PANEL
BRUSH GROMMET PANEL
BLANK PANEL
BLANK PANEL
BLANK PANEL
VENT PANEL
24 PORT SWITCH
CAT 6 PATCH PANEL
12U WALL MOUNTED
SECURITY NETWORK
RACK SNR005
12-STRAND
FIBER OPTIC CABLE
12-STRAND
FIBER OPTIC CABLE
12-STRAND
FIBER OPTIC CABLE
12-STRAND
FIBER OPTIC CABLE
ACCESS
CONTROL
PANEL
ACP003
ACCESS
CONTROL
PANEL
ACP001
ACCESS
CONTROL
PANEL
ACP004
ACCESS
CONTROL
PANEL
ACP005
ACCESS
CONTROL
PANEL
ACP006
12U WALL MOUNTED
SECURITY NETWORK
RACK SNR004
12U WALL MOUNTED
SECURITY NETWORK
RACK SNR003
12U WALL MOUNTED
SECURITY NETWORK
RACK SNR001
EXISTING 24U FREE STANDING
SECURITY SERVER RACK
SNR002
REMOVE ALL UNUSED
EQUIPMENT
ROOM 205
ROOM 305
ROOM 405
ROOM 505
ROOM 110FIRST FLOOR
SECOND FLOOR
THIRD FLOOR
FOURTH FLOOR
FIFTH FLOOR
ROOF
CR CR IAC IAC
CR CR IAC IAC
CR CR IAC IAC
CR CR IAC IAC
CR CR IAC IAC
CR CR
CAT 6A(TYPICAL)
COMPOSITE CABLE (TYPICAL)
CAT 6A(TYPICAL)
CAT 6A(TYPICAL)
CAT 6A(TYPICAL)
CAT 6(TYPICAL)
COMPOSITE CABLE (TYPICAL)
COMPOSITE CABLE (TYPICAL)
COMPOSITE CABLE (TYPICAL)
COMPOSITE CABLE (TYPICAL)
CAT 6ATO OIT NETWORK AND
INTERNET PROVIDER
PIB
PIB
PIB
JB
JB
PIB
JB
JB
PIB
PIB
JB
JB
PIB
PIB
JB
JB
PIB
PIB
JB
JB
JB
JB
COMPOSITE CABLE (TYPICAL)
CCTV CAMERAS
CARD READERS
CCTV CAMERAS
CCTV CAMERAS
CCTV CAMERAS
CCTV CAMERAS
INTEGRATED
LOCK AND READER
(SCHLAGE AD300)
CARD READERS
CARD READERS
CARD READERS
CARD READERS
EL
JB
ELECTRIFIED LOCK WITH
SCHEDULED LOCK/UNLOCK
EL
JB
ELECTRIFIED LOCK WITH
SCHEDULED LOCK/UNLOCK
EL
JB
ELECTRIFIED LOCK WITH
SCHEDULED LOCK/UNLOCK
EL
JB
ELECTRIFIED LOCK WITH
SCHEDULED LOCK/UNLOCK
EL
JB
ELECTRIFIED LOCK WITH
SCHEDULED LOCK/UNLOCK
STAIRWELL ROOF
PANEL INTERFACE BOARD
(SCHLAGE PIB300)
4 CONDUCTOR CABLE
INTEGRATED
LOCK AND READER
(SCHLAGE AD300)
PANEL INTERFACE BOARD
(SCHLAGE PIB300)
4 CONDUCTOR CABLE
INTEGRATED
LOCK AND READER
(SCHLAGE AD300)
INTEGRATED
LOCK AND READER
(SCHLAGE AD300)
INTEGRATED
LOCK AND READER
(SCHLAGE AD300)
4 CONDUCTOR CABLE
PANEL INTERFACE BOARD
(SCHLAGE PIB300)
PANEL INTERFACE BOARD
(SCHLAGE PIB300)
4 CONDUCTOR CABLE
PANEL INTERFACE BOARD
(SCHLAGE PIB300)
4 CONDUCTOR CABLE
ACCESS
CONTROL
PANEL
ACP002SECURITY
WORKSTATION
CAT 6A
CRCR
ELEVATOR
CARD READERS
ELEVATOR
TRAVEL CABLES
LOCATED IN
ELEVATOR
MACHINE ROOM
ROOF ACCESS
CARD READERS
SECURITY DESK
LOBBY 201
BLANK PANEL
BLANK PANEL
BLANK PANEL
BLANK PANEL
1000 VA UPS FOR SWITCH
FIBER TERMINATION PANEL
24 PORT SWITCH
CAT 6 PATCH PANEL
BLANK PANEL
BLANK PANEL
BLANK PANEL
BLANK PANEL
1000VA UPS FOR SWITCH
FIBER TERMINATION PANEL
24 PORT SWITCH
CAT 6 PATCH PANEL
BLANK PANEL
BLANK PANEL
BLANK PANEL
BLANK PANEL
1000VA UPS FOR SWITCH
FIBER TERMINATION PANEL
24 PORT SWITCH
CAT 6 PATCH PANEL
BLANK PANEL
BLANK PANEL
BLANK PANEL
BLANK PANEL
1000VA UPS FOR SWITCH
FIBER TERMINATION PANEL
NOTES:
1. PROVIDE ALL PATCH CABLES, GBICS, AND SFP ADAPTERS TO CONNECT FIBER TO NETWORK SWITCHES.
2. PROVIDE ALL PATCH CABLES, GBICS, AND SFP ADAPTERS TO MAKE 10G CONNECTION FROM NVR TO NETWORK SWITCH.
3. PROVIDE UPS FOR NVR, ACCESS CONTROL APPLIANCE AND NETWORK SWITCHES. SEE SPECIFICATIONS.
4. PROVIDE BACK-UP BATTERIES FOR ALL ACCESS CONTROL PANELS AND POWER SUPPLIES.
5. TERMINATE ALL 12 STRANDS OF FIBER AT EACH FIBER TERMINATION PANEL.
6. PROVIDE 2 DEDICATED 120V 20A CIRCUITS TO EACH RACK LOCATION. CIRCUIT TO NEAREST ELECTRIAL PANEL.
7. ALL CAT 6 AND FIBER OPTIC CABLE TO BE CERTIFIED. PROVIDE CERTIFICATION TEST REPORTS.
8. GROUND RACKS TO A SUITABLE ELECTRICAL BUILDING GROUND. SEE SPECIFICATIONS.
9. INSTALL READERS USING OSDP SECURE COMMUNICATIONS PROTOCOL.
CREDENTIALING
WORKSTATION
ACCESS
CONTROL
PANEL
ACP007
FLOOR
A.
B.
GENERAL DETAIL NOTES (TYPICAL ACCESS DOOR DIAGRAM ONLY):
DETAIL REPRESENTS ALL HARDWARE OPTIONS. QUANTITY AND TYPE OF DEVICES VARY PER LOCATION AS INDICATED ON PLANS.
INSTALL EMT FOR EACH RACEWAY - SEE ROUGH-IN DETAILS.
FIRE ALARM INTERFACE
1 46
2REX
TO ACCESS CONTROL PANEL 7
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.
14.
15.
16.
17.
18.
DETAIL NOTES:
CARD READERS.
REQUEST TO EXIT DEVICE.
ELECTRIC STRIKE.
POWER TRANSFER DEVICE.
DOOR CONTACT.
EMERGENCY EXIT DEVICE.
READER JUNCTION BOX OR DOOR POWER SUPPLY. WHERE REQUIRED, FURNISH 120 VOLT POWER FROM NEAREST CIRCUIT.
DOOR OPERATOR. FURNISH 120V POWER FROM NEAREST CIRCUIT.
DOOR OPERATOR PUSHBUTTONS. INTERFACE CARD READER WITH DOOR OPERATOR TO ENABLE NON-SECURE SIDE OPERATOR BUTTON ONLY
AFTER VALID CREDENTIAL IS PRESENTED.
ELECTRIFIED DOOR HARDWARE
POWER CONDUCTORS IN EMT RACEWAY
CONTROL…