This addendum contains electrical design drawings and specifications for Building 34 Security System Upgrades located at 100 Municipal Plaza in Weirton, West Virginia, prepared by ZDS Design/Consulting Services for West Virginia General Services. The project scope encompasses comprehensive security system upgrades across two floors of the building, including the installation of new closed-circuit television (CCTV) cameras, access control systems, card readers, electric door strikes, automatic door operators, and associated network infrastructure. The security system design includes 37 new multi-technology card readers of varying types (Types A, B, C, H, and J), 25 CCTV cameras with different specifications (ranging from 4MP dome cameras to 12MP fisheye and 5MP dual-head cameras mounted at various heights including 14 feet above finished floor), eight automatic door operators, eight door operator pushbuttons, fourteen door contacts, seven electric door strikes, and three wall-mounted security network racks (12U, 16U, and 24U configurations) equipped with network switches, fiber optic termination panels, uninterruptible power supplies (UPS), and patch panels. The project includes demolition of existing obsolete security equipment while maintaining operational continuity of existing systems during the phased migration to the new unified access control and video surveillance systems.
The work involves complex electrical and communication infrastructure including the installation of 12-strand multimode OM4 armored fiber optic cable runs to multiple data racks, CAT 6A cabling for network connectivity, conduit and raceway systems, and power distribution from existing electrical panels to support all new security devices. The project specifies detailed requirements for firestop systems at fire-rated wall penetrations, surge protection for exterior cameras, proper grounding of equipment racks to building grounds, and certification of all data and fiber optic cable installations. The design requires coordination among multiple existing building systems and departments, including the West Virginia Department of Motor Vehicles (DMV), West Virginia Lottery, Department of Human Services, and Child Support Services, each with distinct security needs and equipment to be retained, removed, or integrated. Contractors are required to furnish all necessary components for complete installation, obtain shop drawing approvals, provide wiring diagrams, ensure system labeling and documentation, and maintain door security protocols throughout the implementation period to prevent any doors from remaining unsecured or inoperable at the end of each workday.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
NOT FOR CONSTRUCTION
ZDS Design/ Consulting Services
Mechanical * Electrical * IAQ * Energy * Commissioning
135 Corporate Center Dr., Suite 532 Scott Depot, WV 25560
Ph: (304) 755-0075 Fx: (304) 755-0076
Web: www.zdsdesign.com Email: contact@zdsdesign.com
OWNER REVIEW SET
C :\U se rs
\e di so n.
ad ki ns \D oc um en ts
\G
SD
2C
_2
4-
-2 3_
BL
D
G
W
EI
R
TO
N _e di so n.
ad ki ns
.rv t
WEST VIRGINIA GENERAL SERVICES
BUILDING 34 SECURITY SYSTEM UPGRADES
ZDS Project Number: GSD-252-C 8/5/2026
100 Municipal Plaza Weirton, WV 26062
PROJECT VICINITY MAP
OS
DL
CO
T
CO
LC
F
F
F
DH
DCL
XXX
XXXX
XX
J
J F1
DO
M
N
X
TV
XXXX
CR
CK
TV
CC
DC
ES
IC
ML
RX
REX
MD
XXX
OS
1P 1 Pole (2P, 3P, 4P, ETC.)
A, Amp Ampere AC Above Counter ACLG Above Ceiling ADO Automatic Door Opener AF Amp Frame AFF Above Finished Floor AFG Above Finished Grade AFI Arc Fault Circuit
Interrupter AHU Air Handling Unit AL Aluminum ALT Alternate AMP Ampere AMPL Amplifier ANNUN Annunciator APPROX Approximately AQ-STAT Aquastat ARCH Architect, Architectural AS Amp Switch AT Amp Trip ATS Automatic Transfer Switch AUTO Automatic AUX Auxiliary AV Audio Visual AWG American Wire Gauge BATT Battery BD Board BLDG Building BMS Building Management System C Conduit CAB Cabinet CAT Catalog CATV Cable Television CB Circuit Breaker CCTV Closed Circuit Television CKT Circuit CLG Ceiling COMB Combination CMPR Compressor CONN Connection CONST Construction CONT Continuation Or Continuous CONTR Contractor CONV Convector CP Circulating Pump CRT Cathode-Ray Tube CT Current Transformer CTR Center CU Copper DCP Domestic Water Circulating Pump DEPT Department DET Detail DIA Diameter DISC Disconnect DIST Distribution DN Down DPR Damper DS Safety Disconnect Switch DT Double Throw DWG Drawing EC Electrical Contractor ELEC Electric, Electrical ELEV Elevator ELU Emergency Lighting Unit EM Emergency EMS Energy Management System EMT Electrical Metallic Tubing EP Electric Pneumatic EQUIP Equipment EWC Electric Water Cooler EXIST Existing EXH Exhaust EXP Explosion Proof FA Fire Alarm FABP Fire Alarm Booster Power
Supply Panel FACP Fire Alarm Control Panel FCU Fan Coil Unit FIXT Fixture FLR Floor FLUOR Fluorescent FU Fuse FUDS Fused Safety Disconnect Switch GA Gauge GAL Gallon GALV Galvanized GC General Contractor GEN Generator GFI Ground Fault Circuit Interrupter GFP Ground Fault Protector GND Ground GRS Galvanized Rigid Steel (Conduit) GYP BD Gypsum Board HOA Hands-Off-Automatic Switch HORIZ Horizontal HP Horsepower HPF High Power Factor HT Height HTG Heating HTR Heater HV High Voltage HVAC Heating, Ventilating And Air
Conditioning IC Interrupting Capacity IG Isolated Ground IMC Intermediate Metal Conduit INCAND Incandescent IR Infrared I/W Interlock With J-BOX Junction Box KV Kilovolt KVA Kilovolt-Ampere KVAR Kilovolt-Ampere Reactive KW Kilowatt KWH Kilowatt Hour LOC Locate Or Location LT Light LTG Lighting LTNG Lightning LV Low Voltage MAX Maximum MAG.S Magnetic Starter M/C Momentary Contact MC Mechanical Contractor
Electrical Abbreviations
Electrical DeviceTags: Uppercase letter(s) indicates Panel ID and circuit number. Lowercase letter indicates designation of controlling switch (where applicable).
Switch ID indicated by a lowercase letter. Switch IDs are unique per space. A switch with an ID "a" controls all devices within the space in which it is located tagged with "a". A switch without a tagged ID controls all lighting fixtures within a space. ID tags may be used on control devices other than switches, such as occupancy sensors or contactors.
Equipment Tags: Equipment ID is indicated by an underlined tag adjacent to the equipment. See the equipment connection schedule for description, electrical requirements, and panel and circuit number. Symbols/graphic appearance of equipment varies.
Solid, arced lines connecting equipment, devices, or fixtures indicate unswitched power circuiting. Wires are only intended to indicate to what circuit devices are connected. Actual connections, circuit routing, installtion, junction boxes, etc. shall be field-determined by the contractor.
Home run to branch circuit panelboard. The equipment name and circuit number(s) are indicated, separated by a hyphen. Homeruns are only intended to indicate panel and circuit number. Actual homerun location shall be field-determined by the contractor.
Power Symbols
Electrical Symbol Legend
Room
MCB Main Circuit Breaker MCC Motor Control Center MDC Main Distribution Center MDP Main Distribution Panel MFR Manufacturer MFS Main Fused Disconnect Switch MH Manhole MIC Microphone MIN Minimum MISC Miscellaneous MLO Main Lugs Only MMS Manual Motor Starter MOA Multioutlet Assembly MSP Motor Starter Panelboard MSBD Main Switchboard MSS Motor Starter Switch MT Mount MT.C Empty Conduit MTS Manual Transfer Switch MTR Motor, Motorized N.C. Normally Closed NEC National Electrical Code NEMA National Electrical
Manufacturer's Association NFDS Non-Fused Safety Disconnect
Switch NIC Not In Contract NL Night Light N.O. Normally Open NPF Normal Power Factor NTS Not To Scale OC On Center OH Overhead OL Overloads PA Public Address PB Pull Box Or Pushbutton PE Pneumatic Electric PED Pedestal PF Power Factor PH Phase PIV Post Indicating Valve PNL Panel PP Power Pole PR Pair PRI Primary PROJ Projection PRV Power Roof Ventilator PT Potential Transformer PVC Polyvinyl Chloride (Conduit) PWR Power QUAN Quantity RCPT Receptacle REQD Required RM Room RSC Rigid Steel Conduit RTU Roof Top Unit SC Surface Conduit SEC Secondary SHT Sheet SIM Similar SLD Single-Line Diagram S/N Solid Neutral SPEC Specification SPKR Speaker SP Spare SPP Single-Point Power SR Surface Raceway SS Stainless Steel SSW Selector Switch S/S Stop/Start Pushbuttons STA Station STD Standard SURF Surface Mounted SW Switch SWBD Switchboard SYM Symmetrical SYS System TEL Telephone TERM Terminal TL Twist Lock TR Tamper Resistant T-STAT Thermostat TTC Telephone Terminal Cabinet TV Television TVTC Television Terminal Cabinet TYP Typical UC Under Counter UE Underground Electrical UG Underground UH Unit Heater UT Underground Telephone UTIL Utility UV Ultraviolet V Volt VA Volt-Amperes VDT Video Display Terminal VERT Vertical VFD Variable Frequency Drive VOL Volume W Watt W/ With WG Wire Guard WH Water Heater W/O Without WP Weatherproof XFMR Transformer XFR Transfer
∠ Angle @ At ▲ Delta ' Feet " Inches # Number Ø Phase C Center Line P Plate
Exit Light, Wall-Mounted.
Shading and arrows indicate faces and directional chevrons.
Wall-mounted fixtures, Typical (Various Symbols)
Emergency Lighting Unit, Wall-Mounted, Remote Battery
Emergency Lighting Unit, Wall-Mounted, Integral Battery
Emergency Lighting Unit, Ceiling-Mounted, Integral Battery Emergency Lighting Unit, Ceiling-Mounted, Remote Battery
Lighting Fixtures, Typical, Rectangular (Various Symbols) Filled circles indicate recessed.
Open circles indicate surface-mounted.
Diagonal line indicates lensed.
Outer dots indicate suspended.
Lighting Fixtures, Typical, Round (Various Symbols) Center dot indicates pendant.
Diagonal line indicates lensed.
Chevron indicates wall wash.
Strip Fixture
Directional Light, Track Light, Flood Light
Exit Light, Ceiling-Mounted.
Shading and arrows indicate faces and directional chevrons.
Linear Light, Tape Light
Exit/ELU Combo
Diagonal hatch indicates light on a critical circuit.
Solid hatch indicates light on an emergency or life safety circuit.
Pole/Area Lights
Post-Top Area Light
Bollard Light
Single-Pole Switch Two-Pole Switch Three-Pole Switch Switch Modifiers:
3: 3-Way 4: 4-Way K: Keyed D: Dimming T: Timer
OS: Occupancy Sensor VS: Vacancy Sensor AC: Above-Counter LV: Low-Voltage M: Motor-Rated
Lighting Contactor
Lighting Control Panel
Occupancy Sensor
Daylight Harvesting Sensor
Smoke Detector
Heat Detector
Carbon Monoxide Detector
Beam Detector T: Transmitter R: Receiver
Combination Detector (Up to Three)
Duct Smoke Detector
Manual Pull Station
Horn, Wall
Horn, Ceiling
Strobe, Wall, Candela as indicated
Strobe, Ceiling, Candela as indicated
Horn/Strobe, Wall, Candela as indicated
Horn/Strobe, Ceiling, Candela as indicated
Remote Indicator w/ Test Switch, Wall
Remote Indicate w/ Test Switch, Ceiling
Door Holder
Door Closer
Fire Service Phone
Addressible Module AIM: Addressible Input Module AOM:Addressible Output Control Module AIO: Addressible Input/Output Module
Fire Alarm Control Unit EVAC: Voice Evacuation Control Panel FAA: Fire Alarm Annunciator FACP: Fire Alarm Control Panel FATC: Fire Alarm Terminal Cabinet NACP: Notification Appliance Circuit Panel FAMN: Fire Alarm Mass Notification Control Panel
Supervisory or Interface Device PIV: Post Indicator Valve Supervisory PS: Pressure Switch R: Non-Addressible Relay VS: Valve Supervisory Switch WF: Water Flow Switch
Simplex Receptacle
Duplex Receptacle
Quadruplex Receptacle
Special Receptacle, Type as Indicated
W all
Ce ilin g
Flo or
Receptacle Modifiers:
##": Height AFF OC AC: Above Counter GFI: Ground-Fault Circuit Interrupter WP: Weatherproof In-Use Cover
Half shading indicates split (typically switched) Outside shading indicates emergency circuit Center shading indicates isolated ground
Multioutlet Assembly Filled squares indicate 120V outlet Open squares indicate with USB
Cord Reel, Device Varies
Drop Cord, Device Varies
Junction Box Floor Box, see schedule for type
Emergency Power Off
Door Opener Push Plate
Power Meter Safety Switch, Fused
Safety Switch, Unfused
Motor Starter
Combination Starter/Disconnect
Ground Rod
Ground Rod with Test Well
Lightning Protection Air Terminal
Lightning Protection Conductor Splice
Static Ground Receptacle
Data Outlet
Telephone Outlet
Data/Telephone Outlet
W all
Ce ilin g
Flo or
Outlet Modifiers:
##": Height AFF OC AC: Above Counter
Wireless Access Point
Nurse Call Corridor Light Number of lights as indicated
Nurse Call Device B: Code Blue D: Duty Station E: Emergency P: Patient Call S: Staff
TV Outlet
Nurse Call Control Unit NCAP: Nurse Call Annunciator Panel NCHS: Nurse Call Host Constroller NCPA: Nurse Call Power Supply NCTC: Nurse Call Terminal Cabinet NCUPS: Uninterruptable Power Supply
Lighting Symbols
Contactor
Single-Pole Switch Two-Pole Switch Three-Pole Switch Switch Modifiers:
K: Keyed T: Timer AC: Above-Counter M: Motor-Rated
Fire Alarm Symbols
Grounding and Lightning Protection Symbols
Security Camera PTZ: Pan/Tilt/Zoom
Card Reader
Card Reader with Keypad
Closed Circuit TV Outlet
Door Contact
Electric Strike
Intercom
Magnetic Lock
Request to Exit Button
Request to Exit Sensor
Motion Detector
Security Control Unit SCP: Security Control Panel SPS: Security Power Supply Unit ACP: Access Control Panel SWKS: Security Workstation MON: Video Monitor
Telecom Symbols
Nurse Call Symbols
Security Symbols a
A A1a
Equipment is tagged with Panel Name and with Panel ID in parentheses. Panel ID is intended as a design documentation aid only. Do not include Panel ID in field-applied circuit directories or labels.
Hatched fill indicates distribution panel or switchboard.
Solid fill indicates branch panel or load center.
Dashed box indicates code-required clearance (width and depth).
Door indicates front of recessed panel.
Panelboards are assigned an abbreviated indicator (or Panel ID) for use with circuit numbers. Panel ID is listed within the panel schedule and in the panel abbreviation schedule.
Power Distribution Equipment
HP
1A
(B
LP
1A
(C
MD
P(
A)
SB1(S)
Devices and fixtures are tagged with Panel ID and circuit number. For example, a device tagged with "A1" indicates the device is circuited to panel designated "A," circuit number 1. The panel schedule circuit number contans both the panel abbreviation and the circuit number.
XX-1
Transformer: Typically transformer names begin with or contain the letter "T". See Single-Line Diagram for description and requirements.
T1
Dashed, arced lines connecting equipment, devices, or fixtures indicate switched power.
Absence of a switch designation on a lighting fixture indicates fixture is controlled by the only switch in the space. An "x" in place of the switch designation indicates unswitched.
Bottom Value, Lowercase Letter: Switch ID
Lighting Tags
Top Value: Fixture Type ID (Underlined)
Bottom Value, Uppercase Letter(s): Panel ID Bottom Value, Number(s): Circuit Number a a
C1a
Wiring
Power Device and Equipment Tags
Construction Phasing
Existing to Remain
Existing to Be Demolished
New
(Typical All Symbols and Equipment)
Existing to Be Demolished
Area Not in Contract
Miscellaneous
Keynote
Callout:
Top Value: Detail Number on Sheet Bottom Value: Sheet Number of Detail
Room Name and Number
Smoke Damper
FILE:
DRAWN BY:
CHECKED BY:
PROJ. NO:
DRAWING NO:
DRAWING TITLE:
PROJECT NAME:
http://www.ZDSDesign.com
135 Corporate Center Drive Suite 532 Scott Depot, WV 25560
TEL 304/755-0075
FAX 304/755-0076
THIS SQUARE APPEARS 1/2"x1/2"
ON FULL SIZE SHEETS
CLIENT:
XXX
C :\U se rs
\e di so n.
ad ki ns \D oc um en ts
\G
SD
2C
_2
4-
-2 3_
BL
D
G
W
EI
R
TO
N _e di so n.
ad ki ns
.rv t
8/
/2
:4 2:
P
M
34-E-001
ELA
TZ3
GSD-252-C
ELECTRICAL TITLE
SHEET
BUILDING 34 SECURITY
SYSTEM UPGRADES
100 Municipal Plaza Weirton, WV 26062
WEST VIRGINIA
GENERAL SERVICES
Electrical Sheet List
34-C-001 COVER SHEET
34-E-001 ELECTRICAL TITLE SHEET
34-TD-101 DEMO PLAN FIRST FLOOR SECURITY
34-TD-102 DEMO PLAN SECOND FLOOR SECURITY
34-TY-101 FIRST FLOOR SECURITY PLAN
34-TY-102 SECOND FLOOR SECURITY PLAN
34-TY-501 SECURITY DETAILS
34-TY-502 SECURITY DETAILS
34-TY-601 SECURITY SCHEDULES
NO DATE REVISION
CR
CR
CR
CR
CR
CR
CRCR
CR
CRCR
CRCR
CR
C-3
C-3
C-3
C-3
C-
DC
DC
DC
MD
MD
MD
CR
AC
P
AC
P
KP
KP
KP
CR
MD
MD
MD
SCP
KP
DBW
DB W
SWKS
CR CR
CR
ACP
MD
SWKS
ACP
PS
PS
PS PS
CR
SWKS
5 D
3 D
5 D
IP
IP
0 D
104 D1
403 D140 5 D
2 D
504 D1
2 D
501 D1
1 D
PLATE/STORAGE
CHECK OUT
DATA
BREAK ROOM
CORRIDOR
MANAGER
105SUPERVISOR
WAITING
INFO/PHOTO
LICENSE CTR.
DRIVER TESTING
EXAMINER SUPER.
HEARING
INVESTIGATOR
CLOSET
OFFICE
200 OFFICE
OFFICE
OFFICE
CORRIDOR
OFFICE
OFFICE
SERV.
STORAGE
COPY/FAX
STOR.
CLERICAL
OFFICE
WIRING CL.
CONFERENCE
REHAB. SERVICES WAITING
SERVER
MAIL/FAX/STORAGE
TRAINING ROOM
HEARING ROOM
STORAGE
AMERICAN JOB CENTER
UI MANAGE OFFICE
WAITING
WORKFORCE
OFF. COUNSELOR
OFFICE MANAGER
BREAK ROOM
MECH.
ENTRY
SECURITY
LOBBY
STAIR
WOMEN
WOMEN
MEN
409 MEN
CORRIDOR
STAIR
SHIPPING/RECEIVING
BUILDING SERVICES
HALL
JAN. CLST.
CONFERENCE
WV LOTTERY OPEN OFFICE
SECURITY
502 CONSULTANT
LOBBY
SERVER
ELEVATORS
ELEVATOR
RECALL
WORKFORCE
DIV. OF REHAB
(E)CR009
1 1 1 1 1
FILE:
DRAWN BY:
CHECKED BY:
PROJ. NO:
DRAWING NO:
DRAWING TITLE:
PROJECT NAME:
http://www.ZDSDesign.com
135 Corporate Center Drive Suite 532 Scott Depot, WV 25560
TEL 304/755-0075
FAX 304/755-0076
THIS SQUARE APPEARS 1/2"x1/2"
ON FULL SIZE SHEETS
CLIENT:
XXX
C :\U se rs
\e di so n.
ad ki ns \D oc um en ts
\G
SD
2C
_2
4-
-2 3_
BL
D
G
W
EI
R
TO
N _e di so n.
ad ki ns
.rv t
8/
/2
:4 2:
P
M
34-TD-101
EA
TZ3
GSD-252-C
DEMO PLAN FIRST
FLOOR SECURITY
BUILDING 34 SECURITY
SYSTEM UPGRADES
100 Municipal Plaza Weirton, WV 26062
WEST VIRGINIA
GENERAL SERVICES
KEYNOTES
1 EXISTING VIDEO CAMERAS INSTALLED BY DMV TO BE REMOVED. CONFIRM WITH
DMV MANAGER WHICH CAMERAS ARE TO BE REMOVED. DMV CONTACT: CASSIE
FETZER (304-740-0055 CASSANDRA.J.FETZER@WV.GOV
2 EXISTING VIDEO SWITCHER AND MONITOR INSTALLED BY DMV TO BE REMOVED.
CONFIRM WITH DMV MANAGER WHICH SYSTEM IS TO BE REMOVED.
3 EXISTING WIRELESS PANIC PENDANT INSTALLED BY DMV TO REMAIN
4 EXISTING SECURITY PANEL AND KEYPAD INSTALLED BY DMV TO REMAIN.
5 EXISTING SECURITY RACK TO REMAIN. CLEAN AND REUSE.
7 EXISTING VIDEO RECORDER AND NETWORK SWITCH INSTALLED BY DMV TO
REMAIN.
8 EXISTING CARD READERS INSTALLED BY WV LOTTERY TO REMAIN. CONFIRM WITH
LOTTERY PERSONNEL BEFORE REMOVING DEVICES IN THIS AREA.
9 EXISTING CONTROL PANELS SHOWN TO REMAIN SUPPORT THE EXISTING CARD
READERS IN THE LOTTERY AREA THAT ARE TO REMAIN. FIELD VERIFY THAT THE
EXISTING DOOR POWER SUPPLIES DO NOT SUPPORT THE LOCKS ON THE DOORS
ASSOCIATED WITH THESE READERS PRIOR TO REMOVAL.
10 EXISTING VIDEO CAMERA INSTALLED BY WV LOTTERY TO REMAIN.
11 NEW CAMERA SYSTEM INSTALLED BY DMV TO REMAIN. CONFIRM WITH DMV
MANAGER WHICH CAMERAS ARE TO BE REMOVED.
1/8" = 1'-0"34-TD-101
1 FIRST FLOOR SECURITY PLAN
SYSTEMS DEMOLITION NOTES
1 DISCONNECT AND REMOVE ONLY SYSTEM DEVICES SHOWN TO BE DEMOLISHED.
2 DISCONNECT AND REMOVE ASSOCIATED CONDUIT AND WIRE BACK TO LAST
REMAINING DEVICE. FURNISH AND INSTALL CONDUIT AND WIRE AS NECESSARY
FOR CONTINUITY OF CIRCUIT(S) TO ANY EXISTING DEVICES TO REMAIN.
COORDINATE AND VERIFY REQUIREMENTS WITH NEW WORK IN AREA.
3 FURNISH AND INSTALL CONDUIT AND/OR SYSTEMS WIRING AS NECESSARY FOR
CONTINUITY OF ANY SYSTEMS EQUIPMENT OR DEVICES TO REMAIN. MODIFY OR
REPLACE AS REQUIRED.
4 FURNISH AND INSTALL BLANK COVER PLATES FOR ALL EXISTING UNUSED
OPENINGS.
5 BUILDINGS THAT HAVE CAMERAS THAT WORK OR WOULD WORK IF THE
SOFTWARE AND LICENSES WERE CURRENT SHOULD HAVE NEW NVRS INSTALLED
AND THE EXISTING CAMERAS CONNECTED TO THEM. AS NEW CAMERAS ARE
INSTALLED, REMOVE OLD CAMERAS FROM THE SYSTEM.
6 THE EXISTING ACCESS CONTROL SYSTEM IS TO REMAIN IN USE UNTIL THE NEW
SYSTEM IS COMPLETE. DOORS SHOULD BE MIGRATED TO THE NEW SYSTEM ONE
AT A TIME UNTIL ALL ARE ON THE NEW SYSTEM. DURING THIS MIGRATION, NO
DOOR IS TO REMAIN UNSECURED OR INOPERABLE AT THE END OF A WORKDAY.
CR
CR
CR
CR
CR
CR
CR
C-
C-3
C-3
C-2
C-2
C-1
C-1
AC
P
MD
MD
MD
PS PS
0 D
610 D1
627 D1
9 D
1 D
611 D1
9 D
810 D1
1 D
800 D1
CONFERENCE
STORAGE
VIDEO
INTERVIEW
INTERVIEW
FAMILY VISIT.
CORRIDOR
INTERVIEW
INTERVIEW
613 OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
WORK STATIONS
DEPT OF HUMAN SERVICES
DEPT OF HUMAN SERVICES
CORRIDOR
CORRIDOR
CORRIDOR
STORAGE
SERVER
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
RECEPTION
WAITING
OFFICE
OFFICE
SERVER
702 OFFICE
CLASSROOM/CONFERENCS
RESOURCE ROOM
CHILD SUPPORT SERVICES
RECEPTION/OPEN OFFICE
ELEVATORS
LOBBY
STAIR
OFFICE
OFFICE
BREAK ROOM
CONFERENCE
MEN
WOMEN
STAIR
JAN. CLOSET
JAN. CLOSET
WOMEN
MEN
IP
CHILD SUPPORT SERVICES
DHHR CPS
FILE:
DRAWN BY:
CHECKED BY:
PROJ. NO:
DRAWING NO:
DRAWING TITLE:
PROJECT NAME:
http://www.ZDSDesign.com
135 Corporate Center Drive Suite 532 Scott Depot, WV 25560
TEL 304/755-0075
FAX 304/755-0076
THIS SQUARE APPEARS 1/2"x1/2"
ON FULL SIZE SHEETS
CLIENT:
XXX
C :\U se rs
\e di so n.
ad ki ns \D oc um en ts
\G
SD
2C
_2
4-
-2 3_
BL
D
G
W
EI
R
TO
N _e di so n.
ad ki ns
.rv t
8/
/2
:4 2:
P
M
34-TD-102
EA
TZ3
GSD-252-C
DEMO PLAN SECOND
FLOOR SECURITY
BUILDING 34 SECURITY
SYSTEM UPGRADES
100 Municipal Plaza Weirton, WV 26062
WEST VIRGINIA
GENERAL SERVICES
KEYNOTES
1 COVER UNUSED BOXES AND PATCH AND RESTORE ANCHOR HOLES TO ORIGINAL
CONDITION.
1/8" = 1'-0"34-TD-102
1 SECOND FLOOR SECURITY PLAN
SYSTEMS DEMOLITION NOTES
1 DISCONNECT AND REMOVE ONLY SYSTEM DEVICES SHOWN TO BE DEMOLISHED.
2 DISCONNECT AND REMOVE ASSOCIATED CONDUIT AND WIRE BACK TO LAST
REMAINING DEVICE. FURNISH AND INSTALL CONDUIT AND WIRE AS NECESSARY
FOR CONTINUITY OF CIRCUIT(S) TO ANY EXISTING DEVICES TO REMAIN.
COORDINATE AND VERIFY REQUIREMENTS WITH NEW WORK IN AREA.
3 FURNISH AND INSTALL CONDUIT AND/OR SYSTEMS WIRING AS NECESSARY FOR
CONTINUITY OF ANY SYSTEMS EQUIPMENT OR DEVICES TO REMAIN. MODIFY OR
REPLACE AS REQUIRED.
4 FURNISH AND INSTALL BLANK COVER PLATES FOR ALL EXISTING UNUSED
OPENINGS.
5 BUILDINGS THAT HAVE CAMERAS THAT WORK OR WOULD WORK IF THE
SOFTWARE AND LICENSES WERE CURRENT SHOULD HAVE NEW NVRS INSTALLED
AND THE EXISTING CAMERAS CONNECTED TO THEM. AS NEW CAMERAS ARE
INSTALLED, REMOVE OLD CAMERAS FROM THE SYSTEM.
6 THE EXISTING ACCESS CONTROL SYSTEM IS TO REMAIN IN USE UNTIL THE NEW
SYSTEM IS COMPLETE. DOORS SHOULD BE MIGRATED TO THE NEW SYSTEM ONE
AT A TIME UNTIL ALL ARE ON THE NEW SYSTEM. DURING THIS MIGRATION, NO
DOOR IS TO REMAIN UNSECURED OR INOPERABLE AT THE END OF A WORKDAY.
CR
CR
CR
SCP
KP
DBW
DB W
CR
ACP ACP
SWKS
MON
MO
N CR
CR
CR
CRCR
CR
CR
CR
CRCRCRCRCR
CR
CR
CR
ACP
AC
P
CR
DC
DC
DC
ES
ES
DC
DC
DC
DC
DC DC
CR
CR
MON
CR
ES
DR
CR
ES
SWKS
ES
ES
DC
DCDC DC
DB
DB
ADO
AD
O
DB
DB
ADO
DB
DB
2 CWKS2
5 D
3 D
5 D
0 D
104 D1
403 D1
5 D
2 D
504 D1
2 D
501 D1
1 D
PLATE/STORAGE
CHECK OUT
DATA
BREAK ROOM
CORRIDOR
MANAGER
105SUPERVISOR
WAITING
INFO/PHOTO
LICENSE CTR.
DRIVER TESTING
EXAMINER SUPER.
HEARING
INVESTIGATOR
CLOSET
OFFICE
200 OFFICE
OFFICE
OFFICE
CORRIDOR
OFFICE
OFFICE
SERV.
STORAGE
COPY/FAX
STOR.
CLERICAL
OFFICE
WIRING CL.
CONFERENCE
REHAB. SERVICES WAITING
SERVER
MAIL/FAX/STORAGE
TRAINING ROOM
HEARING ROOM
STORAGE
AMERICAN JOB CENTER
UI MANAGE OFFICE
WAITING
WORKFORCE
OFF. COUNSELOR
OFFICE MANAGER
BREAK ROOM
MECH.
ENTRY
SECURITY
LOBBY
STAIR
WOMEN
WOMEN
MEN
409 MEN
CORRIDOR
STAIR
SHIPPING/RECEIVING
BUILDING SERVICES
HALL
JAN. CLST.
CONFERENCE
WV LOTTERY OPEN OFFICE
SECURITY
502 CONSULTANT
LOBBY
SERVER
ELEVATORS
WORKFORCE
C002
TYPE C
C005
TYPE C
C007
TYPE B
C003
TYPE H
C008
TYPE B
C001
TYPE A
CR021
CR020
CR019 CR018
CR017
CR016 CR015 CR014 CR013 CR012
CR011
CR010
(E)CR009
CR001
CR003 CR002
M001
M002 SWKS01
DC009
DC008
DC007
DC006
DC005
DC004
DC003
DC002DC001
ACP001
ACP002
ES001 1
M003
8 15
5 5
CR033
CR036
CR034ES004
CR035ES005
CR037
ES007
(E)CR038
(E)CR042
(E)CR041
(E)CR039 (E)CR040
DC011
DC012DC013DC014
ES003
ES006
DR001
(E) SNR002
ADO01
ADO02
ADO03
SNR001
CWKS01
DB005
DB006
DB003
DB004
DB001
DB002
FILE:
DRAWN BY:
CHECKED BY:
PROJ. NO:
DRAWING NO:
DRAWING TITLE:
PROJECT NAME:
http://www.ZDSDesign.com
135 Corporate Center Drive Suite 532 Scott Depot, WV 25560
TEL 304/755-0075
FAX 304/755-0076
THIS SQUARE APPEARS 1/2"x1/2"
ON FULL SIZE SHEETS
CLIENT:
XXX
C :\U se rs
\e di so n.
ad ki ns \D oc um en ts
\G
SD
2C
_2
4-
-2 3_
BL
D
G
W
EI
R
TO
N _e di so n.
ad ki ns
.rv t
8/
/2
:4 2:
P
M
34-TY-101
EA
TZ3
GSD-252-C
FIRST FLOOR SECURITY
PLAN
BUILDING 34 SECURITY
SYSTEM UPGRADES
100 Municipal Plaza Weirton, WV 26062
WEST VIRGINIA
GENERAL SERVICES
1/8" = 1'-0"34-TY-101
1 FIRST FLOOR SECURITY PLAN
KEYNOTES
1 EXISTING SECURITY NETWORK RACK TO BE REUSED. REMOVE ALL UNUSED
EQUIPMENT. FILL UNUSED SPACES WITH BLANK PANELS . SEE SPECIFICATIONS
AND DETAIL 1 ON SHEET 34-TY-501.
2 NEW CAMERA SYSTEM INSTALL BY DMV TO REMAIN. CONFIRM WITH DMV
MANAGER WHICH CAMERAS ARE TO REMAIN. DMV CONTACT: CASSIE FETZER
(304-740-0055 CASSANDRA.J.FETZER@WV.GOV
3 EXISTING WIRELESS PANIC PENDANT INSTALLED BY DMV TO REMAIN
4 EXISTING SECURITY PANEL AND KEYPAD INSTALLED BY DMV TO REMAIN.
5 EXISTING CARD READERS INSTALLED BY WV LOTTERY TO REMAIN. CONFIRM WITH
LOTTERY PERSONNEL BEFORE REMOVING DEVICES IN THIS AREA.
6 GSD SECURITY NETWORK RACK WITH LOCKING DOOR.
7 CONTRACTOR SHALL FURNISH WITH ALL REQUIRED COMPONENTS FOR A
COMPLETE INSTALLATION. FURNISH 120V POWER FROM NEAREST CIRCUIT.
INTERLOCK DOOR OPERATOR BUTTONS WITH ACCESS CONTROL SYSTEM. SEE
DETAIL ON SHEET 34-TY-501.
8 THIS DOOR LOCKS ON A SCHEDULE. CONFIRM REQUIRED OPERATION WITH
OWNER.
9 EXISTING VIDEO CAMERA INSTALLED BY WV LOTTERY TO REMAIN.
10 EXISTING VIDEO RECORDER AND NETWORK SWITCH INSTALLED BY DMV TO
REMAIN.
11 PROVIDE 12 STRAND MM OM4 ARMOURED FIBER TO DATA RACKS IN SECURITY 403
AND SERVER 601. PROVIDE FIBER TERMINATION PANELS AT EACH RACK
LOCATION.
12 PROVIDE 12 STRAND MM OM4 ARMOURED FIBER TO DATA RACK IN BUILDING
SERVICES 414. PROVIDE FIBER TERMINATION PANELS AT EACH RACK LOCATION.
13 CREDENTIALLING WORKSTATION. COORDINATE WITH OWNER FOR EXACT
LOCATION.
14 PROVIDE 3 - 34" CURVED DESKTOP MONITORS FOR SECURITY WORKSTATION.
15 INTERLOCK DOOR OPERATOR BUTTONS WITH ACCESS CONTROL SYSTEM. SEE
DETAIL ON SHEET 34-TY-501.
SECURITY SYSTEM SHEET NOTES
A SEE DETAIL SHEET FOR SECURITY CAMERA MOUNTING
B SEE SECURITY DEVICE SCHEDULE FOR ADDITIONAL INFORMATION
C ALL COMMUNICATION CABLES SHALL BE INSTALLED IN CONDUIT, CABLE TRAY, OR
SUPPORTED BY CABLE HOOKS. PROVIDE BUSHINGS AT THE ENDS OF ALL
CONDUITS WHERE STUBBED ABOVE ACCESSIBLE CEILINGS OR WHERE DROPPED
INTO CABLE TRAYS. PROVIDE CABLE HOOKS ABOVE ACCESSIBLE CEILINGS FOR
CABLE INSTALLATION WHERE NOT INSTALLED IN A CONDUIT OR CABLE TRAY.
D BUILDINGS THAT HAVE CAMERAS THAT WORK OR WOULD WORK IF THE
SOFTWARE AND LICENSES WERE CURRENT SHOULD HAVE NEW NVRS INSTALLED
AND THE EXISTING CAMERAS CONNECTED TO THEM. AS NEW CAMERAS ARE
INSTALLED, REMOVE OLD CAMERAS FROM THE SYSTEM.
E ALL CABLES AND DEVICES TO BE LABELED. SEE SPECIFICATION AND DETAILS
FOR SPECIFIC REQUIREMENTS.
F THE EXISTING ACCESS CONTROL SYSTEM IS TO REMAIN IN USE UNTIL THE NEW
SYSTEM IS COMPLETE. DOORS SHOULD BE MIGRATED TO THE NEW SYSTEM ONE
AT A TIME UNTIL ALL ARE ON THE NEW SYSTEM. DURING THIS MIGRATION, NO
DOOR IS TO REMAIN UNSECURED OR INOPERABLE AT THE END OF A WORKDAY.
G PROVIDE SURGE PROTECTION FOR ALL EXTERIOR CAMERAS.
CR
CR
CR
CR
CR
CR
CR
AC
P
DC
CR
ES
ADO
DB
DB
0 D
610 D1
627 D1
9 D
1 D
611 D1
9 D
810 D1
1 D
800 D1
CONFERENCE
STORAGE
VIDEO
INTERVIEW
INTERVIEW
FAMILY VISIT.
CORRIDOR
INTERVIEW
INTERVIEW
613 OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
WORK STATIONS
DEPT OF HUMAN SERVICES
DEPT OF HUMAN SERVICES
CORRIDOR
CORRIDOR
CORRIDOR
STORAGE
SERVER
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
RECEPTION
WAITING
OFFICE
OFFICE
SERVER
702 OFFICE
CLASSROOM/CONFERENCS
RESOURCE ROOM
CHILD SUPPORT SERVICES
RECEPTION/OPEN OFFICE
706 ELEVATORS
LOBBY
STAIR
OFFICE
OFFICE
BREAK ROOM
CONFERENCE
MEN
WOMEN
STAIR
JAN. CLOSET
JAN. CLOSET
WOMEN
MEN
DHHR CPS
C015
TYPE B
C014
TYPE B
C011
TYPE C
C020
TYPE J
C016
TYPE J
14' AFF
CR027
CR026
CR025CR031
CR024
CR023
CR029
CR030
CR028
ACP003
DC010
3SNR003
CR032
ES002
C025
TYPE J
14' AFF
C024
TYPE C
C006
TYPE B
ADO04
DB007
DB008
FILE:
DRAWN BY:
CHECKED BY:
PROJ. NO:
DRAWING NO:
DRAWING TITLE:
PROJECT NAME:
http://www.ZDSDesign.com
135 Corporate Center Drive Suite 532 Scott Depot, WV 25560
TEL 304/755-0075
FAX 304/755-0076
THIS SQUARE APPEARS 1/2"x1/2"
ON FULL SIZE SHEETS
CLIENT:
XXX
C :\U se rs
\e di so n.
ad ki ns \D oc um en ts
\G
SD
2C
_2
4-
-2 3_
BL
D
G
W
EI
R
TO
N _e di so n.
ad ki ns
.rv t
8/
/2
:4 2:
P
M
34-TY-102
EA
TZ3
GSD-252-C
SECOND FLOOR
SECURITY PLAN
BUILDING 34 SECURITY
SYSTEM UPGRADES
100 Municipal Plaza Weirton, WV 26062
WEST VIRGINIA
GENERAL SERVICES
KEYNOTES
1 MATCH MOUNTING HEIGHT TO EXISTING CAMERAS (20'-24' AFF). COVER UNUSED
BOXES AND PATCH AND RESTORE ANCHOR HOLES TO ORIGINAL CONDITION.
CONTRACTOR SHALL FIELD VERIFY PRIOR TO BIDDING AND INCLUDE ALL COSTS IN
BASE-BID.
2 NEW CAMERA MOUNTED 14' AFF.
3 NEW SECURITY NETWORK RACK. SEE SPECIFICATIONS AND DETAIL 1 ON SHEET
34-TY-501.
4 THIS DOOR LOCKS ON A SCHEDULE (UNLOCK DURING NORMAL BUSINESS HOURS).
CONFIRM REQUIRED SCHEDULE WITH CHILD SUPPORT SERVICES.
5 CONTRACTOR SHALL FURNISH WITH ALL REQUIRED COMPONENTS FOR A
COMPLETE INSTALLATION. FURNISH 120V POWER FROM NEAREST CIRCUIT.
INTERLOCK DOOR OPERATOR BUTTONS WITH ACCESS CONTROL SYSTEM. SEE
DETAIL ON SHEET 34-TY-501.
1/8" = 1'-0"34-TY-102
1 SECOND FLOOR SECURITY PLAN
SECURITY SYSTEM SHEET NOTES
A SEE DETAIL SHEET FOR SECURITY CAMERA MOUNTING
B SEE SECURITY DEVICE SCHEDULE FOR ADDITIONAL INFORMATION
C ALL COMMUNICATION CABLES SHALL BE INSTALLED IN CONDUIT, CABLE TRAY, OR
SUPPORTED BY CABLE HOOKS. PROVIDE BUSHINGS AT THE ENDS OF ALL
CONDUITS WHERE STUBBED ABOVE ACCESSIBLE CEILINGS OR WHERE DROPPED
INTO CABLE TRAYS. PROVIDE CABLE HOOKS ABOVE ACCESSIBLE CEILINGS FOR
CABLE INSTALLATION WHERE NOT INSTALLED IN A CONDUIT OR CABLE TRAY.
D BUILDINGS THAT HAVE CAMERAS THAT WORK OR WOULD WORK IF THE
SOFTWARE AND LICENSES WERE CURRENT SHOULD HAVE NEW NVRS INSTALLED
AND THE EXISTING CAMERAS CONNECTED TO THEM. AS NEW CAMERAS ARE
INSTALLED, REMOVE OLD CAMERAS FROM THE SYSTEM.
E ALL CABLES AND DEVICES TO BE LABELED. SEE SPECIFICATION AND DETAILS
FOR SPECIFIC REQUIREMENTS.
F THE EXISTING ACCESS CONTROL SYSTEM IS TO REMAIN IN USE UNTIL THE NEW
SYSTEM IS COMPLETE. DOORS SHOULD BE MIGRATED TO THE NEW SYSTEM ONE
AT A TIME UNTIL ALL ARE ON THE NEW SYSTEM. DURING THIS MIGRATION, NO
DOOR IS TO REMAIN UNSECURED OR INOPERABLE AT THE END OF A WORKDAY.
G PROVIDE SURGE PROTECTION FOR ALL EXTERIOR CAMERAS.
FIBER TERMINATION PANEL
72TB NVR
2000VA UPS FOR NVR
2000VA UPS FOR APP. AND
SWITCH
BLANK PANEL
VENT PANEL
VENT PANEL
VENT PANEL
BLANK PANEL
BLANK PANEL
BLANK PANEL
VENT PANEL
24 PORT SWITCH
CAT 6 PATCH PANEL
12-STRAND
FIBER OPTIC CABLE
ACCESS
CONTROL
PANEL
ACP002
ACCESS
CONTROL
PANEL
ACP001
ACCESS
CONTROL
PANEL
ACP003
12U WALL MOUNTED
SECURITY NETWORK
RACK SNR003
16U WALL MOUNTED
SECURITY NETWORK
RACK SNR001
24U FREE STANDING
SECURITY SERVER RACK
SNR002
ROOM 601
ROOM 414FIRST FLOOR
SECOND FLOOR
CR CR CR EL
CR CR CR EL
CAT 6A(TYPICAL)
CAT 6A(TYPICAL)
COMPOSITE CABLE (TYPICAL)
COMPOSITE CABLE (TYPICAL) JB
JB
JB
JB
JB
JB
JB
JB
CCTV CAMERAS
CARD READERS
CARD READERS
ELECTRIFIED LOCK WITH
SCHEDULED LOCK/UNLOCK
SECURITY ROOM 403
12-STRAND
FIBER OPTIC CABLE
FIBER TERMINATION PANEL
BLANK PANEL
BLANK PANEL
BLANK PANEL
24 PORT SWITCH
CAT 6 PATCH PANEL
FIBER TERMINATION PANEL
BLANK PANEL
1000VA UPS FOR SWITCH
BLANK PANEL
BLANK PANEL
BLANK PANEL
CAT 6 PATCH PANEL
24 PORT SWITCH
ROOF
BLANK PANEL
2000VA UPS FOR SWITCHES
24 PORT SWITCH
CAT 6 PATCH PANEL
BLANK PANEL
BLANK PANEL
TO OIT NETWORK AND
INTERNET PROVIDER
SECURITY
WORKSTATION
SECURITY DESK
ENTRY 402
NOTES:
1. PROVIDE ALL PATCH CABLES, GBICS, AND SFP ADAPTERS TO CONNECT FIBER TO NETWORK SWITCHES.
2. PROVIDE ALL PATCH CABLES, GBICS, AND SFP ADAPTERS TO MAKE 10G CONNECTION FROM NVR TO NETWORK SWITCH.
3. PROVIDE UPS FOR NVR, ACCESS CONTROL APPLIANCE AND NETWORK SWITCHES.
4. PROVIDE BACK-UP BATTERIES FOR ALL ACCESS CONTROL PANELS AND POWER SUPPLIES.
5. TERMINATE ALL 12 STRANDS OF FIBER AT EACH FIBER TERMINATION PANEL.
6. PROVIDE 2 DEDICATED 120V 20A CIRCUITS TO EACH RACK LOCATION. CIRCUIT TO NEAREST ELECTRIAL PANEL.
7. ALL CAT 6 AND FIBER OPTIC CABLE TO BE CERTIFIED. PROVIDE CERTIFICATION TEST REPORTS.
8. GROUND RACKS TO A SUITABLE ELECTRICAL BUILDING GROUND. SEE SPECIFICATIONS.
9. INSTALL READERS USING OSDP SECURE COMMUNICATIONS PROTOCOL.
BRUSH GROMMET PANELCREDENTIALING
WORKSTATION
CAT 6A(TYPICAL)
FLOOR
A.
B.
GENERAL DETAIL NOTES (TYPICAL ACCESS DOOR DIAGRAM ONLY):
DETAIL REPRESENTS ALL HARDWARE OPTIONS. QUANTITY AND TYPE OF DEVICES VARY PER LOCATION AS INDICATED ON PLANS.
INSTALL EMT FOR EACH RACEWAY - SEE ROUGH-IN DETAILS.
FIRE ALARM INTERFACE
1 46
2REX
TO ACCESS CONTROL PANEL 7
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.
14.
15.
16.
17.
18.
DETAIL NOTES:
CARD READERS.
REQUEST TO EXIT DEVICE.
ELECTRIC STRIKE.
POWER TRANSFER DEVICE.
DOOR CONTACT.
EMERGENCY EXIT DEVICE.
READER JUNCTION BOX OR DOOR POWER SUPPLY. WHERE REQUIRED, FURNISH 120 VOLT POWER FROM NEAREST CIRCUIT.
DOOR OPERATOR. FURNISH 120V POWER FROM NEAREST CIRCUIT.
DOOR OPERATOR PUSHBUTTONS. INTERFACE CARD READER WITH DOOR OPERATOR TO ENABLE NON-SECURE SIDE OPERATOR BUTTON ONLY
AFTER VALID CREDENTIAL IS PRESENTED.
ELECTRIFIED DOOR HARDWARE
POWER CONDUCTORS IN EMT RACEWAY
CONTROL CONDUCTORS IN EMT RACEWAY
CEILING HEIGHT VARIES.
ACCESSIBLE CEILING SPACE.
POWER FROM NEAREST CIRCUIT.
CONDUCTORS IN RACEWAY ABOVE CEILING.
CONDUCTORS IN RACEWAY TYPICAL - SEE SECURITY DEVICE ROUGH-IN DETAIL.
PLENUM RATED CABLE SUPPORTED ABOVE CEILING.
1'-0" MAXIMUM
6" MIN
6" MAX
1'-0" MAX
IDF #(FF1)
OUTLET #
FF1-003G
JACK # (G, R, Y)
1-001G 1-001R
1-001Y 1-002G 1-002R
1-002Y 1-003G 1-003R
1-003Y
CAT 6
RJ45
JACK
1 8
FF1-001-G
IDF CLOSET (FF1)
FACEPLATE
NUMBER (001)
JACK COLOR (G, R, Y)
WHITE LABEL AND BLACK
LETTERS WITH CLEAR
TAPE COVERING ON BOTH
ENDS OF CABLE
SECTION
PLAN
CEILING SEE ARCHITECTURAL
DRAWINGS
ELECTRICAL BOX T-BAR
FASTENER
SURVEILLANCE DEVICE
ELECTRICAL BOX T-BAR
FASTENER
ACOUSTICAL TILE SEE
ARCHITECTURAL
DRAWINGS
CEILING STRUCTURE SEE
ARCHITECTURAL DRAWINGS
CEILING SUPPORT STRUCTURE
SEE ARCHITECTURAL DRAWINGS
HORIZONTAL CABLING TO
CABLING SUPPORT SYSTEM
EQUAL EQUAL
EQ
UA
L
SUPPORT CABLE ON ALL
FOUR CORNERS OF GRID
SUPPORT CABLE ON ALL
FOUR CORNERS OF CEILING
SUPPORT STRUCTURE
METAL BOX SIZE AS
REQUIRED BY NEC
METAL BOX SIZE AS
REQUIRED BY NEC
EQ
UA
L SURVEILLANCE DEVICE
PATCH
CABLE
4x4 METAL BOX WITH
COVER - MTD TO WALL
PATCH CABLE BY
SYSTEMS
CONTRACTORWALL ABOVE CEILING
HORIZONTAL CABLE
SEE SPECIFICATIONS
SURFACE MOUNT
KEYSTONE (BISCUIT) JACK
4x4 METAL BOX WITH
COVER - MTD TO WALL
HORIZONTAL CABLE
SEE SPECIFICATIONS
SURFACE MOUNT
KEYSTONE (BISCUIT) JACK
PATCH CABLE BY
SYSTEMS
CONTRACTOR
FLOOR
A.
B.
C.
D.
GENERAL DETAIL NOTES (TYPICAL ACCESS DOOR DIAGRAM ONLY):
DETAIL REPRESENTS ALL HARDWARE OPTIONS. QUANTITY AND TYPE OF DEVICES VARY PER LOCATION AS INDICATED ON PLANS.
PROVIDE SHOP DRAWING SUBMITTAL AND WIRING DIAGRAMS FOR EACH POWER ASSISTED/ACCESS DOOR LOCATION.
ALL EQUIPMENT FURNISHED AND INSTALLED BY SECURITY CONTRACTOR.
INSTALL EMT FOR EACH RACEWAY - SEE ROUGH-IN DETAILS.
FIRE ALARM INTERFACE
1 46
2REX
TO ACCESS CONTROL PANEL
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.
14.
15.
16.
DETAIL NOTES:
CARD READERS.
REQUEST TO EXIT DEVICE.
ELECTRIC STRIKE.
ELECTRIFIED DOOR HARDWARE AND POWER TRANSFER DEVICE.
EMERGENCY EXIT DEVICE.
DOOR POWER SUPPLY. POWER SUPPLY TO BE USED AS ACCESS CONTROL JUNCTION BOX. 120 VOLT POWER FROM NEAREST CIRCUIT.
DOOR OPERATOR. FURNISH 120V POWER FROM NEAREST CIRCUIT. ON ACCESS CONTROL DOORS INTERFACE WITH ACCESS CONTROL SYSTEM.
DOOR OPERATOR PUSHBUTTONS. INTERFACE CARD READER WITH DOOR OPERATOR TO ENABLE NON-SECURE SIDE OPERATOR BUTTON ONLY
AFTER VALID CREDENTIAL IS PRESENTED.
SINGLE DOOR LOCATION
ELECTRIFIED DOOR HARDWARE
POWER CONDUCTORS IN EMT RACEWAY
CONTROL CONDUCTORS IN EMT RACEWAY
CEILING HEIGHT VARIES.
POWER FROM NEAREST CIRCUIT.
CONDUCTORS IN RACEWAY TYPICAL - SEE SECURITY DEVICE ROUGH-IN DETAIL.
CONDUCTORS IN RACEWAY 9'-0" AFF.
1'-0" MAXIMUM
6" MAX
1'-0" MAX
6" MIN
1"⌀ EMT CONDUIT
METAL ELECTRICAL
BOX - SEE
SPECIFICATIONS
CEILING AS INDICATED
WITHIN ARCH PLANS
SET SCREW
CONNECTOR
WITH INSULATING
BUSHING
SET SCREW
CONNECTOR WITH
INSULATING BUSHING
1'-0"
6"
SE
E
AR
C
H
IT
EC
TU
R
AL
D R
AW
IN
G S
FO
R
C
EI
LI
N
G H
EI
G
H T
3' -4
1.
2.
NOTES:
THE DEVICE SHALL NOT SPAN MORE
THAN ONE FINISH MATERIAL
BOX SHALL BE FLUSH WITH THE
FINISH MATERIAL
FILE:
DRAWN BY:
CHECKED BY:
PROJ. NO:
DRAWING NO:
DRAWING TITLE:
PROJECT NAME:
http://www.ZDSDesign.com
135 Corporate Center Drive Suite 532 Scott Depot, WV 25560
TEL 304/755-0075
FAX 304/755-0076
THIS SQUARE APPEARS 1/2"x1/2"
ON FULL SIZE SHEETS
CLIENT:
XXX
C :\U se rs
\e di so n.
ad ki ns \D oc um en ts
\G
SD
2C
_2
4-
-2 3_
BL
D
G
W
EI
R
TO
N _e di so n.
ad ki ns
.rv t
8/
/2
:4 2:
P
M
34-TY-501
EA
TZ3
GSD-252-C
SECURITY DETAILS
BUILDING 34 SECURITY
SYSTEM UPGRADES
100 Municipal Plaza Weirton, WV 26062
WEST VIRGINIA
GENERAL SERVICES
NOT TO SCALE34-TY-501
1 ACCESS CONTROL SYSTEM RISER SCHEMATIC
NOT TO SCALE34-TY-501
2 TYPICAL ACCESS CONTROL DOOR DETAIL FOR SPACES WITH ACCESSIBLE CEILINGS
NOT TO SCALE34-TY-501
3 TYPICAL 48 PORT PATCH PANEL DETAIL
NOT TO SCALE34-TY-501
4 VOICE AND DATA CABLE LABELING DETAIL
NOT TO SCALE34-TY-501
8 CAMERA INSTALLATION DETAIL
NOT TO SCALE34-TY-501
6 BISCUIT BOX
1/8" = 1'-0"34-TY-501
5 TYPICAL ACCESS CONTROL DOOR DETAIL FOR SPACES WITHOUT ACCESSIBLE CEILINGS
1/2" = 1'-0"34-TY-501
7 SECURITY DEVICE ROUGH-IN DETAIL
A
4 3 1
NOTE:
F) CORRIDORS
J) BOILER, CENTRAL HEATING PLANT, OR
HOT WATER SUPPLY ROOM ENCLOSURES.
I) "TYPE OF CONSTUCTION SEPARATION"
H) EXIT PASSAGEWAYS
G) STAIR ENCLOSURES
E) SHAFT ENCLOSURES
D) JANITOR CLOSETS
C) AREA SEPARATIONS
B) EXTERIOR WALLS
A) OCCUPANCY SEPARATIONS
PENETRATIONS OF FIRE RATED ASSEMBLIES MUST BE
PROTECTED BY U.L. SYSTEM WL 1001, 1002 OR 1003.
SUCH PENETRATIONS ARE TYPICALLY FOUND AT:
1A
1.
A.
B.
2.
PIPE OR CONDUIT-NOM 12 IN. DIA. (OR SMALLER) SCHEDULE 10 (OR HEAVIER) STEEL PIPE, NOM.6 IN. DIA. (OR SMALLER) STEEL CONDUIT, NOM. 4 IN. DIA. (OR SMALLER) STEEL ELECTRICAL METALLIC TUBING OR TYPE L (OR HEAVIER) COPPER TUBING OR NOM 1 IN. DIA. (OR SMALLER) FLEXIBLE STEEL CONDUIT. WHEN COPPER PIPE OR FLEXIBLE STEEL CONDUIT IS USED, MAX. F RATING OF FIRESTOP SYSTEM (ITEM 3) IS 2 HR. STEEL PIPES OR CONDUITS LARGER THAN NOM 4 IN. DIA. MAY ONLY BE USED IN WALLS CONSTRUCTED USING STEEL CHANNEL STUDS. A MAX OF ONE PIPE OR CONDUIT IS PERMITTED IN THE FIRESTOP SYSTEM. PIPE OR CONDUIT TO BE INSTALLED NEAR CENTER OF STUD CAVITY WIDTH AND TO BE RIGIDLY SUPPORTED ON BOTH
SIDES OF WALL ASSEMBLY.
WALLBOARD, GYPSUM* -NOM 1/2 OR 5/8 IN. THICK, 4 FT. WIDE WITH SQUARE OR TAPERED EDGES. THE GYPSUM WALLBOARD TYPE, THICKNESS, NUMBER OF LAYERS, FASTENER TYPE AND SHEET ORIENTATION SHALL BE AS SPECIFIED IN THE INDIVIDUAL U300 OR U400 SERIES DESIGN IN THE U.L. FIRE RESISTANCE DIRECTORY. MAXIMUM DIAMETER OF OPENING IS 13-1/2 IN.
STUDS-WALL FRAMING MAY CONSIST OF EITHER WOOD STUDS (MAX. 2 HR. FIRE RATED ASSEMBLIES) OR STEEL CHANNEL STUDS. WOOD STUDS TO CONSIST OF NOMINAL 2 BY 4 IN. LUMBER SPACED 16 IN. OC WITH NOMINAL 2 BY 4 IN. LUMBER END PLATES AND CROSS BRACES. STEEL STUDS TO BE MINIMUM 3-5/8 IN. WIDE BY 1-3/8 IN.
DEEP CHANNELS SPACED MAX. 24 IN. O.C.
WALL ASSEMBLY - THE 1,2,3 OR 4 HR. FIRE-RATED GYPSUM WALLBOARD/STUD WALL ASSEMBLY SHALL BE CONSTRUCTED OF THE MATERIALS AND IN THE MANNER DESCRIBED IN THE INDIVIDUAL U300 OR U400 SERIES WALL OR PARTITION DESIGNS IN THE U.L. FIRE RESISTANCE DIRECTORY AND SHALL INCLUDE THE FOLLOWING
CONSTRUCTION FEATURES:
A
A
T
RATING
HOUR
3 OR 4
F
RATING
HOUR
1 OR 2
1 OR 2
1 OR 2
3 OR 4
3 OR 4
0 TO 1/4
3/16 TO 3/8
1/4 TO 1/2
0 TO 3/16
1/4 TO 1/2
ANNULAR
SPACE, IN.
3.
SYSTEM NO. FA1002
(FORMERLY SYSTEM NO.152)
F RATING-2 HR
T RATING-0 HR
L RATING AT AMBIENT-2 CFM/sq ft (SEE ITEM 4) L RATING AT 400 F- LESS THAN 1 CFM/sq ft (SEE ITEM 4)
FILL, VOID OR CAVITY MATERIAL* - CAULK** - CAULK FILL MATERIAL INSTALLED TO COMPLETELY FILL ANNULAR SPACE BETWEEN PIPE OR CONDUIT AND GYPSUM WALLBOARD AND WITH A MIN. 1/4 IN. DIA. BEAD OF CAULK APPLIED TO PERIMETER OF PIPE OR CONDUIT AT ITS EGRESS FROM THE WALL. CAULK INSTALLED SYMMETRICALLY ON BOTH SIDES OF WALL ASSEMBLY. THE HOURLY F RATING OF THE FIRESTOP SYSTEM IS DEPENDENT UPON THE HOURLY FIRE RATING OF WALL ASSEMBLY IN WHICH IT IS INSTALLED AS SHOWN IN THE FOLLOWING TABLE. THE HOURLY T RATING OF THE FIRE STOP SYSTEM IS DEPENDENT UPON THE TYPE OR SIZE OF THE PIPE OR CONDUIT AND THE HOURLY FIRE RATING OF THE WALL ASSEMBLY IN WHICH IT IS INSTALLED, AS TABULATED
BELOW:
+WHEN COPPER PIPE IS USED, T RATING IS 0 HOUR.
* BEARING THE UL CLASSIFICATION MARKING.
**MING & MFG. CO. - TYPES CP-25 S/L, CP-25 N/S, CP-25 WB, CP-25 WB+.
MAX PIPE
OR CONDUIT
DIAMETER, IN.
1B
*BEARING THE UL CLASSIFICATION MARKING
MINNESOTA MINING & MFG. CO. - TYPES CP-25 WB. CP-25 WB +. (NOTE: L RATINGS
APPLY ONLY WHEN TYPE CP-25 WB+ CAULK IS USED).
4) FILL, VOID, OR CAVITY MATERIALS* - CAULK - APPLIED TO FILL THROUGH OPENING TO A MIN. DEPTH OF 1 IN., FLUSH WITH TOP SURFACE OF FLOOR.
3) PACKING MATERIAL - MIN. 1 IN. THICK MINERAL-WOOL BATT MATERIAL INSULATION FIRMLY PACKED INTO OPENING AS A PERMANENT FORM WITH ITS TOP SURFACE RECESSED MIN. 1 IN. FROM TOP SURFACE OF FLOOR.
2) PIPE - NOM 4 IN. DIAMETER (OR SMALLER) TYPE L (OR HEAVIER) COPPER TUBING SCHEDULE 10 (OR HEAVIER) STEEL PIPE, STEEL CONDUIT OR STEEL EMT TO BE INSTALLED WITH A MIN. CLEARANCE OF 1 IN. AND A MAX.
CLEARANCE OF 2 IN. FROM THE SIDES OF THE THROUGH OPENING. A MIN. SEPARATION OF 1 IN. SHALL BE MAINTAINED BETWEEN ADJACENT PIPES. PIPES TO BE RIGIDLY SUPPORTED ON BOTH SIDES OF FLOOR
ASSEMBLY.
1) FLOOR ASSEMBLY - MIN. 4-1/2 IN. THICK LIGHTWEIGHT OR NORMAL WEIGHT (100-150 PCF) CONCRETE.
MAX. AREA OF OPENING 192 SQ. IN. WITH MAX. LENGTH OF 24 IN. AND MAX WIDTH OF 8 IN.
THROUGH-PENETRATION FIRESTOP SYSTEMS (XHEZ)
FIRESTOP METHOD
SYSTEMS NO. WL1001-CAULK ONLY
(FORMERLY SYSTEM NO. 147A)
F RATINGS--1,2,3 AND 4 HR (SEE ITEMS 2 AND 3)
T RATINGS--0,1,2,3 AND 4 HR (SEE ITEM 3)
SECTION A-A
THROUGH-PENETRATION FIRESTOP SYSTEMS (XHEZ)
0+, 1 OR 2
1/8" = 1'-0"34-TY-502
1 ELECTRICAL CONDUIT PENETRATION DETAIL
FILE:
DRAWN BY:
CHECKED BY:
PROJ. NO:
DRAWING NO:
DRAWING TITLE:
PROJECT NAME:
http://www.ZDSDesign.com
135 Corporate Center Drive Suite 532 Scott Depot, WV 25560
TEL 304/755-0075
FAX 304/755-0076
THIS SQUARE APPEARS 1/2"x1/2"
ON FULL SIZE SHEETS
CLIENT:
XXX
C :\U se rs
\e di so n.
ad ki ns \D oc um en ts
\G
SD
2C
_2
4-
-2 3_
BL
D
G
W
EI
R
TO
N _e di so n.
ad ki ns
.rv t
8/
/2
:4 2:
P
M
34-TY-502
EA
TZ3
GSD-252-C
SECURITY DETAILS
BUILDING 34 SECURITY
SYSTEM UPGRADES
100 Municipal Plaza Weirton, WV 26062
WEST VIRGINIA
GENERAL SERVICES
FILE:
DRAWN BY:
CHECKED BY:
PROJ. NO:
DRAWING NO:
DRAWING TITLE:
PROJECT NAME:
http://www.ZDSDesign.com
135 Corporate Center Drive Suite 532 Scott Depot, WV 25560
TEL 304/755-0075
FAX 304/755-0076
THIS SQUARE APPEARS 1/2"x1/2"
ON FULL SIZE SHEETS
CLIENT:
XXX
C :\U se rs
\e di so n.
ad ki ns \D oc um en ts
\G
SD
2C
_2
4-
-2 3_
BL
D
G
W
EI
R
TO
N _e di so n.
ad ki ns
.rv t
8/
/2
:4 2:
P
M
34-TY-601
EA
TZ3
GSD-252-C
SECURITY SCHEDULES
BUILDING 34 SECURITY
SYSTEM UPGRADES
100 Municipal Plaza Weirton, WV 26062
WEST VIRGINIA
GENERAL SERVICES
Security Device Schedule
Mark Identity Type
Mark Description Model Comments
ACP001 ACCESS CONTROL PANEL UNIFIED POWER SUPPLY ENCLOSURE WITH
ACCESS CONTROL BOARDS
ACP002 ACCESS CONTROL PANEL UNIFIED POWER SUPPLY ENCLOSURE WITH
ACCESS CONTROL BOARDS
ACP003 ACCESS CONTROL PANEL UNIFIED POWER SUPPLY ENCLOSURE WITH
ACCESS CONTROL BOARDS
ADO01 AUTOMATIC DOOR OPERATOR LCN 4630/4640 SERIES
ADO02 AUTOMATIC DOOR OPERATOR LCN 4630/4640 SERIES
ADO03 AUTOMATIC DOOR OPERATOR LCN 4630/4640 SERIES
ADO04 AUTOMATIC DOOR OPERATOR LCN 4630/4640 SERIES
C001 TYPE A 4MP DOME CAMERA, 4.4 - 9.3MM LENS, IR, IN-CEILING MOUNT 4.0C-H6A-D1-IR
C002 TYPE C 12MP FISHEYE CAMERA, IR SURFACE MOUNT 12.0W-H6A-FE-DO1-IR
C003 TYPE H 3 X 5MP MULTI-HEAD CAMERA, IN-CEILING MOUNT 15C-H5A-3MH
C005 TYPE C 12MP FISHEYE CAMERA, IR SURFACE MOUNT 12.0W-H6A-FE-DO1-IR
C006 TYPE B 5MP DUAL HEAD CAMERA, SURFACE MOUNT 10.0C-H6DH-DO1-IR
C007 TYPE B 5MP DUAL HEAD CAMERA, SURFACE MOUNT 10.0C-H6DH-DO1-IR
C008 TYPE B 5MP DUAL HEAD CAMERA, SURFACE MOUNT 10.0C-H6DH-DO1-IR
C011 TYPE C 12MP FISHEYE CAMERA, IR SURFACE MOUNT 12.0W-H6A-FE-DO1-IR
C014 TYPE B 5MP DUAL HEAD CAMERA, SURFACE MOUNT 10.0C-H6DH-DO1-IR
C015 TYPE B 5MP DUAL HEAD CAMERA, SURFACE MOUNT 10.0C-H6DH-DO1-IR
C016 TYPE J 3 X 5MP MULTI-HEAD CAMERA, IR, CORNER MOUNT 15C-H5A-3MH 14' AFF
C020 TYPE J 3 X 5MP MULTI-HEAD CAMERA, IR, CORNER MOUNT 15C-H5A-3MH
C024 TYPE C 12MP FISHEYE CAMERA, IR SURFACE MOUNT 12.0W-H6A-FE-DO1-IR
C025 TYPE J 3 X 5MP MULTI-HEAD CAMERA, IR, CORNER MOUNT 15C-H5A-3MH 14' AFF
CR001 MULTI-TECHNOLOGY CARD READER MTB15
CR002 MULTI-TECHNOLOGY CARD READER MTB15
CR003 MULTI-TECHNOLOGY CARD READER MTB15
CR010 MULTI-TECHNOLOGY CARD READER MTB15
CR011 MULTI-TECHNOLOGY CARD READER MTB15
CR012 MULTI-TECHNOLOGY CARD READER MTB15
CR013 MULTI-TECHNOLOGY CARD READER MTB15
CR014 MULTI-TECHNOLOGY CARD READER MTB15
CR015 MULTI-TECHNOLOGY CARD READER MTB15
CR016 MULTI-TECHNOLOGY CARD READER MTB15
CR017 MULTI-TECHNOLOGY CARD READER MTB15
CR018 MULTI-TECHNOLOGY CARD READER MTB15
CR019 MULTI-TECHNOLOGY CARD READER MTB15
CR020 MULTI-TECHNOLOGY CARD READER MTB15
CR021 MULTI-TECHNOLOGY CARD READER MTB15
CR023 MULTI-TECHNOLOGY CARD READER MTB15
CR024 MULTI-TECHNOLOGY CARD READER MTB15
CR025 MULTI-TECHNOLOGY CARD READER MTB15
CR026 MULTI-TECHNOLOGY CARD READER MTB15
CR027 MULTI-TECHNOLOGY CARD READER MTB15
CR028 MULTI-TECHNOLOGY CARD READER MTB15
CR029 MULTI-TECHNOLOGY CARD READER MTB15
CR030 MULTI-TECHNOLOGY CARD READER MTB15
CR031 MULTI-TECHNOLOGY CARD READER MTB15
CR032 MULTI-TECHNOLOGY CARD READER MTB15
CR033 MULTI-TECHNOLOGY CARD READER MTB15
CR034 MULTI-TECHNOLOGY CARD READER MTB15
CR035 MULTI-TECHNOLOGY CARD READER MTB15
CR036 MULTI-TECHNOLOGY CARD READER MTB15
CR037 MULTI-TECHNOLOGY CARD READER MTB15
CWKS01 CREDENTIALING WORKSTATION COMPUTER WITH MOUSE, KEYBOARD, 24"
MONITOR AND USB ENROLLMENT READER
DB001 DOOR OPERATOR PUSHBUTTON LCN 8310-3856TWF/WS
DB002 DOOR OPERATOR PUSHBUTTON LCN 8310-3856TWF/WS
DB003 DOOR OPERATOR PUSHBUTTON LCN 8310-3856TWF/WS
DB004 DOOR OPERATOR PUSHBUTTON LCN 8310-3856TWF/WS
DB005 DOOR OPERATOR PUSHBUTTON LCN 8310-3856TWF/WS
DB006 DOOR OPERATOR PUSHBUTTON LCN 8310-3856TWF/WS
DB007 DOOR OPERATOR PUSHBUTTON LCN 8310-3856TWF/WS
DB008 DOOR OPERATOR PUSHBUTTON LCN 8310-3856TWF/WS
DC001 DOOR CONTACT GRI MODEL 195-12WG OR 4463
DC002 DOOR CONTACT GRI MODEL 195-12WG OR 4463
DC003 DOOR CONTACT GRI MODEL 195-12WG OR 4463
DC004 DOOR CONTACT GRI MODEL 195-12WG OR 4463
DC005 DOOR CONTACT GRI MODEL 195-12WG OR 4463
DC006 DOOR CONTACT GRI MODEL 195-12WG OR 4463
DC007 DOOR CONTACT GRI MODEL 195-12WG OR 4463
DC008 DOOR CONTACT GRI MODEL 195-12WG OR 4463
DC009 DOOR CONTACT GRI MODEL 195-12WG OR 4463
DC010 DOOR CONTACT GRI MODEL 195-12WG OR 4463
DC011 DOOR CONTACT GRI MODEL 195-12WG OR 4463
DC012 DOOR CONTACT GRI MODEL 195-12WG OR 4463
DC013 DOOR CONTACT GRI MODEL 195-12WG OR 4463
DC014 DOOR CONTACT GRI MODEL 195-12WG OR 4463
DR001 DOOR RELEASE BUTTON ALARM CONTROLS DTC SERIES
ES001 ELECTRIC DOOR STRIKE HESS 8000 SERIES/HESS 9700 SERIES
ES002 ELECTRIC DOOR STRIKE HESS 8000 SERIES/HESS 9700 SERIES
ES003 ELECTRIC DOOR STRIKE HESS 8000 SERIES/HESS 9700 SERIES
ES004 ELECTRIC DOOR STRIKE HESS 8000 SERIES/HESS 9700 SERIES
ES005 ELECTRIC DOOR STRIKE HESS 8000 SERIES/HESS 9700 SERIES
ES006 ELECTRIC DOOR STRIKE HESS 8000 SERIES/HESS 9700 SERIES
ES007 ELECTRIC DOOR STRIKE HESS 8000 SERIES/HESS 9700 SERIES
M001 DESK MOUNT CCTV MONITOR DELL S3425DW
M002 DESK MOUNT CCTV MONITOR DELL S3425DW
M003 DESK MOUNT CCTV MONITOR DELL S3425DW
SNR001 WALL MOUNT EQUIPMENT RACK DWR-16-22
SNR003 WALL MOUNT EQUIPMENT RACK DWR-12-22
SWKS01 SECURITY WORKSTATION COMPUTER WITH MOUSE AND KEYBOARD
| 34-C-001 - COVER SHEET |
| 34-E-001 - ELECTRICAL TITLE SHEET |
| 34-TD-101 - DEMO PLAN FIRST FLOOR SECURITY |
| 34-TD-102 - DEMO PLAN SECOND FLOOR SECURITY |
| 34-TY-101 - FIRST FLOOR SECURITY PLAN |
| 34-TY-102 - SECOND FLOOR SECURITY PLAN |
| 34-TY-501 - SECURITY DETAILS |
| 34-TY-502 - SECURITY DETAILS |
| 34-TY-601 - SECURITY SCHEDULES |