Addendum No 1_Drawings - Building 34.pdf

PDF 1 MB Posted

Attached to
Satellite Buildings Security Systems Upgrades Project
Solicitation number
CRFQ 0211 GSD2700000019 2
Issued by
Kanawha County, West Virginia

About this file

This addendum contains electrical design drawings and specifications for Building 34 Security System Upgrades located at 100 Municipal Plaza in Weirton, West Virginia, prepared by ZDS Design/Consulting Services for West Virginia General Services. The project scope encompasses comprehensive security system upgrades across two floors of the building, including the installation of new closed-circuit television (CCTV) cameras, access control systems, card readers, electric door strikes, automatic door operators, and associated network infrastructure. The security system design includes 37 new multi-technology card readers of varying types (Types A, B, C, H, and J), 25 CCTV cameras with different specifications (ranging from 4MP dome cameras to 12MP fisheye and 5MP dual-head cameras mounted at various heights including 14 feet above finished floor), eight automatic door operators, eight door operator pushbuttons, fourteen door contacts, seven electric door strikes, and three wall-mounted security network racks (12U, 16U, and 24U configurations) equipped with network switches, fiber optic termination panels, uninterruptible power supplies (UPS), and patch panels. The project includes demolition of existing obsolete security equipment while maintaining operational continuity of existing systems during the phased migration to the new unified access control and video surveillance systems.

The work involves complex electrical and communication infrastructure including the installation of 12-strand multimode OM4 armored fiber optic cable runs to multiple data racks, CAT 6A cabling for network connectivity, conduit and raceway systems, and power distribution from existing electrical panels to support all new security devices. The project specifies detailed requirements for firestop systems at fire-rated wall penetrations, surge protection for exterior cameras, proper grounding of equipment racks to building grounds, and certification of all data and fiber optic cable installations. The design requires coordination among multiple existing building systems and departments, including the West Virginia Department of Motor Vehicles (DMV), West Virginia Lottery, Department of Human Services, and Child Support Services, each with distinct security needs and equipment to be retained, removed, or integrated. Contractors are required to furnish all necessary components for complete installation, obtain shop drawing approvals, provide wiring diagrams, ensure system labeling and documentation, and maintain door security protocols throughout the implementation period to prevent any doors from remaining unsecured or inoperable at the end of each workday.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

NOT FOR CONSTRUCTION

ZDS Design/ Consulting Services

Mechanical * Electrical * IAQ * Energy * Commissioning

135 Corporate Center Dr., Suite 532 Scott Depot, WV 25560

Ph: (304) 755-0075 Fx: (304) 755-0076

Web: www.zdsdesign.com Email: contact@zdsdesign.com

OWNER REVIEW SET

C :\U se rs

\e di so n.

ad ki ns \D oc um en ts

\G

SD

2C

_2

4-

-2 3_

BL

D

G

W

EI

R

TO

N _e di so n.

ad ki ns

.rv t

WEST VIRGINIA GENERAL SERVICES

BUILDING 34 SECURITY SYSTEM UPGRADES

ZDS Project Number: GSD-252-C 8/5/2026

100 Municipal Plaza Weirton, WV 26062

PROJECT VICINITY MAP

OS

DL

CO

T

CO

LC

F

F

F

DH

DCL

XXX

XXXX

XX

J

J F1

DO

M

N

X

TV

XXXX

CR

CK

TV

CC

DC

ES

IC

ML

RX

REX

MD

XXX

OS

1P 1 Pole (2P, 3P, 4P, ETC.)

A, Amp Ampere AC Above Counter ACLG Above Ceiling ADO Automatic Door Opener AF Amp Frame AFF Above Finished Floor AFG Above Finished Grade AFI Arc Fault Circuit

Interrupter AHU Air Handling Unit AL Aluminum ALT Alternate AMP Ampere AMPL Amplifier ANNUN Annunciator APPROX Approximately AQ-STAT Aquastat ARCH Architect, Architectural AS Amp Switch AT Amp Trip ATS Automatic Transfer Switch AUTO Automatic AUX Auxiliary AV Audio Visual AWG American Wire Gauge BATT Battery BD Board BLDG Building BMS Building Management System C Conduit CAB Cabinet CAT Catalog CATV Cable Television CB Circuit Breaker CCTV Closed Circuit Television CKT Circuit CLG Ceiling COMB Combination CMPR Compressor CONN Connection CONST Construction CONT Continuation Or Continuous CONTR Contractor CONV Convector CP Circulating Pump CRT Cathode-Ray Tube CT Current Transformer CTR Center CU Copper DCP Domestic Water Circulating Pump DEPT Department DET Detail DIA Diameter DISC Disconnect DIST Distribution DN Down DPR Damper DS Safety Disconnect Switch DT Double Throw DWG Drawing EC Electrical Contractor ELEC Electric, Electrical ELEV Elevator ELU Emergency Lighting Unit EM Emergency EMS Energy Management System EMT Electrical Metallic Tubing EP Electric Pneumatic EQUIP Equipment EWC Electric Water Cooler EXIST Existing EXH Exhaust EXP Explosion Proof FA Fire Alarm FABP Fire Alarm Booster Power

Supply Panel FACP Fire Alarm Control Panel FCU Fan Coil Unit FIXT Fixture FLR Floor FLUOR Fluorescent FU Fuse FUDS Fused Safety Disconnect Switch GA Gauge GAL Gallon GALV Galvanized GC General Contractor GEN Generator GFI Ground Fault Circuit Interrupter GFP Ground Fault Protector GND Ground GRS Galvanized Rigid Steel (Conduit) GYP BD Gypsum Board HOA Hands-Off-Automatic Switch HORIZ Horizontal HP Horsepower HPF High Power Factor HT Height HTG Heating HTR Heater HV High Voltage HVAC Heating, Ventilating And Air

Conditioning IC Interrupting Capacity IG Isolated Ground IMC Intermediate Metal Conduit INCAND Incandescent IR Infrared I/W Interlock With J-BOX Junction Box KV Kilovolt KVA Kilovolt-Ampere KVAR Kilovolt-Ampere Reactive KW Kilowatt KWH Kilowatt Hour LOC Locate Or Location LT Light LTG Lighting LTNG Lightning LV Low Voltage MAX Maximum MAG.S Magnetic Starter M/C Momentary Contact MC Mechanical Contractor

Electrical Abbreviations

Electrical DeviceTags: Uppercase letter(s) indicates Panel ID and circuit number. Lowercase letter indicates designation of controlling switch (where applicable).

Switch ID indicated by a lowercase letter. Switch IDs are unique per space. A switch with an ID "a" controls all devices within the space in which it is located tagged with "a". A switch without a tagged ID controls all lighting fixtures within a space. ID tags may be used on control devices other than switches, such as occupancy sensors or contactors.

Equipment Tags: Equipment ID is indicated by an underlined tag adjacent to the equipment. See the equipment connection schedule for description, electrical requirements, and panel and circuit number. Symbols/graphic appearance of equipment varies.

Solid, arced lines connecting equipment, devices, or fixtures indicate unswitched power circuiting. Wires are only intended to indicate to what circuit devices are connected. Actual connections, circuit routing, installtion, junction boxes, etc. shall be field-determined by the contractor.

Home run to branch circuit panelboard. The equipment name and circuit number(s) are indicated, separated by a hyphen. Homeruns are only intended to indicate panel and circuit number. Actual homerun location shall be field-determined by the contractor.

Power Symbols

Electrical Symbol Legend

Room

MCB Main Circuit Breaker MCC Motor Control Center MDC Main Distribution Center MDP Main Distribution Panel MFR Manufacturer MFS Main Fused Disconnect Switch MH Manhole MIC Microphone MIN Minimum MISC Miscellaneous MLO Main Lugs Only MMS Manual Motor Starter MOA Multioutlet Assembly MSP Motor Starter Panelboard MSBD Main Switchboard MSS Motor Starter Switch MT Mount MT.C Empty Conduit MTS Manual Transfer Switch MTR Motor, Motorized N.C. Normally Closed NEC National Electrical Code NEMA National Electrical

Manufacturer's Association NFDS Non-Fused Safety Disconnect

Switch NIC Not In Contract NL Night Light N.O. Normally Open NPF Normal Power Factor NTS Not To Scale OC On Center OH Overhead OL Overloads PA Public Address PB Pull Box Or Pushbutton PE Pneumatic Electric PED Pedestal PF Power Factor PH Phase PIV Post Indicating Valve PNL Panel PP Power Pole PR Pair PRI Primary PROJ Projection PRV Power Roof Ventilator PT Potential Transformer PVC Polyvinyl Chloride (Conduit) PWR Power QUAN Quantity RCPT Receptacle REQD Required RM Room RSC Rigid Steel Conduit RTU Roof Top Unit SC Surface Conduit SEC Secondary SHT Sheet SIM Similar SLD Single-Line Diagram S/N Solid Neutral SPEC Specification SPKR Speaker SP Spare SPP Single-Point Power SR Surface Raceway SS Stainless Steel SSW Selector Switch S/S Stop/Start Pushbuttons STA Station STD Standard SURF Surface Mounted SW Switch SWBD Switchboard SYM Symmetrical SYS System TEL Telephone TERM Terminal TL Twist Lock TR Tamper Resistant T-STAT Thermostat TTC Telephone Terminal Cabinet TV Television TVTC Television Terminal Cabinet TYP Typical UC Under Counter UE Underground Electrical UG Underground UH Unit Heater UT Underground Telephone UTIL Utility UV Ultraviolet V Volt VA Volt-Amperes VDT Video Display Terminal VERT Vertical VFD Variable Frequency Drive VOL Volume W Watt W/ With WG Wire Guard WH Water Heater W/O Without WP Weatherproof XFMR Transformer XFR Transfer

∠ Angle @ At ▲ Delta ' Feet " Inches # Number Ø Phase C Center Line P Plate

Exit Light, Wall-Mounted.

Shading and arrows indicate faces and directional chevrons.

Wall-mounted fixtures, Typical (Various Symbols)

Emergency Lighting Unit, Wall-Mounted, Remote Battery

Emergency Lighting Unit, Wall-Mounted, Integral Battery

Emergency Lighting Unit, Ceiling-Mounted, Integral Battery Emergency Lighting Unit, Ceiling-Mounted, Remote Battery

Lighting Fixtures, Typical, Rectangular (Various Symbols) Filled circles indicate recessed.

Open circles indicate surface-mounted.

Diagonal line indicates lensed.

Outer dots indicate suspended.

Lighting Fixtures, Typical, Round (Various Symbols) Center dot indicates pendant.

Diagonal line indicates lensed.

Chevron indicates wall wash.

Strip Fixture

Directional Light, Track Light, Flood Light

Exit Light, Ceiling-Mounted.

Shading and arrows indicate faces and directional chevrons.

Linear Light, Tape Light

Exit/ELU Combo

Diagonal hatch indicates light on a critical circuit.

Solid hatch indicates light on an emergency or life safety circuit.

Pole/Area Lights

Post-Top Area Light

Bollard Light

Single-Pole Switch Two-Pole Switch Three-Pole Switch Switch Modifiers:

3: 3-Way 4: 4-Way K: Keyed D: Dimming T: Timer

OS: Occupancy Sensor VS: Vacancy Sensor AC: Above-Counter LV: Low-Voltage M: Motor-Rated

Lighting Contactor

Lighting Control Panel

Occupancy Sensor

Daylight Harvesting Sensor

Smoke Detector

Heat Detector

Carbon Monoxide Detector

Beam Detector T: Transmitter R: Receiver

Combination Detector (Up to Three)

Duct Smoke Detector

Manual Pull Station

Horn, Wall

Horn, Ceiling

Strobe, Wall, Candela as indicated

Strobe, Ceiling, Candela as indicated

Horn/Strobe, Wall, Candela as indicated

Horn/Strobe, Ceiling, Candela as indicated

Remote Indicator w/ Test Switch, Wall

Remote Indicate w/ Test Switch, Ceiling

Door Holder

Door Closer

Fire Service Phone

Addressible Module AIM: Addressible Input Module AOM:Addressible Output Control Module AIO: Addressible Input/Output Module

Fire Alarm Control Unit EVAC: Voice Evacuation Control Panel FAA: Fire Alarm Annunciator FACP: Fire Alarm Control Panel FATC: Fire Alarm Terminal Cabinet NACP: Notification Appliance Circuit Panel FAMN: Fire Alarm Mass Notification Control Panel

Supervisory or Interface Device PIV: Post Indicator Valve Supervisory PS: Pressure Switch R: Non-Addressible Relay VS: Valve Supervisory Switch WF: Water Flow Switch

Simplex Receptacle

Duplex Receptacle

Quadruplex Receptacle

Special Receptacle, Type as Indicated

W all

Ce ilin g

Flo or

Receptacle Modifiers:

##": Height AFF OC AC: Above Counter GFI: Ground-Fault Circuit Interrupter WP: Weatherproof In-Use Cover

Half shading indicates split (typically switched) Outside shading indicates emergency circuit Center shading indicates isolated ground

Multioutlet Assembly Filled squares indicate 120V outlet Open squares indicate with USB

Cord Reel, Device Varies

Drop Cord, Device Varies

Junction Box Floor Box, see schedule for type

Emergency Power Off

Door Opener Push Plate

Power Meter Safety Switch, Fused

Safety Switch, Unfused

Motor Starter

Combination Starter/Disconnect

Ground Rod

Ground Rod with Test Well

Lightning Protection Air Terminal

Lightning Protection Conductor Splice

Static Ground Receptacle

Data Outlet

Telephone Outlet

Data/Telephone Outlet

W all

Ce ilin g

Flo or

Outlet Modifiers:

##": Height AFF OC AC: Above Counter

Wireless Access Point

Nurse Call Corridor Light Number of lights as indicated

Nurse Call Device B: Code Blue D: Duty Station E: Emergency P: Patient Call S: Staff

TV Outlet

Nurse Call Control Unit NCAP: Nurse Call Annunciator Panel NCHS: Nurse Call Host Constroller NCPA: Nurse Call Power Supply NCTC: Nurse Call Terminal Cabinet NCUPS: Uninterruptable Power Supply

Lighting Symbols

Contactor

Single-Pole Switch Two-Pole Switch Three-Pole Switch Switch Modifiers:

K: Keyed T: Timer AC: Above-Counter M: Motor-Rated

Fire Alarm Symbols

Grounding and Lightning Protection Symbols

Security Camera PTZ: Pan/Tilt/Zoom

Card Reader

Card Reader with Keypad

Closed Circuit TV Outlet

Door Contact

Electric Strike

Intercom

Magnetic Lock

Request to Exit Button

Request to Exit Sensor

Motion Detector

Security Control Unit SCP: Security Control Panel SPS: Security Power Supply Unit ACP: Access Control Panel SWKS: Security Workstation MON: Video Monitor

Telecom Symbols

Nurse Call Symbols

Security Symbols a

A A1a

Equipment is tagged with Panel Name and with Panel ID in parentheses. Panel ID is intended as a design documentation aid only. Do not include Panel ID in field-applied circuit directories or labels.

Hatched fill indicates distribution panel or switchboard.

Solid fill indicates branch panel or load center.

Dashed box indicates code-required clearance (width and depth).

Door indicates front of recessed panel.

Panelboards are assigned an abbreviated indicator (or Panel ID) for use with circuit numbers. Panel ID is listed within the panel schedule and in the panel abbreviation schedule.

Power Distribution Equipment

HP

1A

(B

LP

1A

(C

MD

P(

A)

SB1(S)

Devices and fixtures are tagged with Panel ID and circuit number. For example, a device tagged with "A1" indicates the device is circuited to panel designated "A," circuit number 1. The panel schedule circuit number contans both the panel abbreviation and the circuit number.

XX-1

Transformer: Typically transformer names begin with or contain the letter "T". See Single-Line Diagram for description and requirements.

T1

Dashed, arced lines connecting equipment, devices, or fixtures indicate switched power.

Absence of a switch designation on a lighting fixture indicates fixture is controlled by the only switch in the space. An "x" in place of the switch designation indicates unswitched.

Bottom Value, Lowercase Letter: Switch ID

Lighting Tags

Top Value: Fixture Type ID (Underlined)

Bottom Value, Uppercase Letter(s): Panel ID Bottom Value, Number(s): Circuit Number a a

C1a

Wiring

Power Device and Equipment Tags

Construction Phasing

Existing to Remain

Existing to Be Demolished

New

(Typical All Symbols and Equipment)

Existing to Be Demolished

Area Not in Contract

Miscellaneous

Keynote

Callout:

Top Value: Detail Number on Sheet Bottom Value: Sheet Number of Detail

Room Name and Number

Smoke Damper

FILE:

DRAWN BY:

CHECKED BY:

PROJ. NO:

DRAWING NO:

DRAWING TITLE:

PROJECT NAME:

http://www.ZDSDesign.com

135 Corporate Center Drive Suite 532 Scott Depot, WV 25560

TEL 304/755-0075

FAX 304/755-0076

THIS SQUARE APPEARS 1/2"x1/2"

ON FULL SIZE SHEETS

CLIENT:

XXX

C :\U se rs

\e di so n.

ad ki ns \D oc um en ts

\G

SD

2C

_2

4-

-2 3_

BL

D

G

W

EI

R

TO

N _e di so n.

ad ki ns

.rv t

8/

/2

:4 2:

P

M

34-E-001

ELA

TZ3

GSD-252-C

ELECTRICAL TITLE

SHEET

BUILDING 34 SECURITY

SYSTEM UPGRADES

100 Municipal Plaza Weirton, WV 26062

WEST VIRGINIA

GENERAL SERVICES

Electrical Sheet List

34-C-001 COVER SHEET

34-E-001 ELECTRICAL TITLE SHEET

34-TD-101 DEMO PLAN FIRST FLOOR SECURITY

34-TD-102 DEMO PLAN SECOND FLOOR SECURITY

34-TY-101 FIRST FLOOR SECURITY PLAN

34-TY-102 SECOND FLOOR SECURITY PLAN

34-TY-501 SECURITY DETAILS

34-TY-502 SECURITY DETAILS

34-TY-601 SECURITY SCHEDULES

NO DATE REVISION

CR

CR

CR

CR

CR

CR

CRCR

CR

CRCR

CRCR

CR

C-3

C-3

C-3

C-3

C-

DC

DC

DC

MD

MD

MD

CR

AC

P

AC

P

KP

KP

KP

CR

MD

MD

MD

SCP

KP

DBW

DB W

SWKS

CR CR

CR

ACP

MD

SWKS

ACP

PS

PS

PS PS

CR

SWKS

5 D

3 D

5 D

IP

IP

0 D

104 D1

403 D140 5 D

2 D

504 D1

2 D

501 D1

1 D

PLATE/STORAGE

CHECK OUT

DATA

BREAK ROOM

CORRIDOR

MANAGER

105SUPERVISOR

WAITING

INFO/PHOTO

LICENSE CTR.

DRIVER TESTING

EXAMINER SUPER.

HEARING

INVESTIGATOR

CLOSET

OFFICE

200 OFFICE

OFFICE

OFFICE

CORRIDOR

OFFICE

OFFICE

SERV.

STORAGE

COPY/FAX

STOR.

CLERICAL

OFFICE

WIRING CL.

CONFERENCE

REHAB. SERVICES WAITING

SERVER

MAIL/FAX/STORAGE

TRAINING ROOM

HEARING ROOM

STORAGE

AMERICAN JOB CENTER

UI MANAGE OFFICE

WAITING

WORKFORCE

OFF. COUNSELOR

OFFICE MANAGER

BREAK ROOM

MECH.

ENTRY

SECURITY

LOBBY

STAIR

WOMEN

WOMEN

MEN

409 MEN

CORRIDOR

STAIR

SHIPPING/RECEIVING

BUILDING SERVICES

HALL

JAN. CLST.

CONFERENCE

WV LOTTERY OPEN OFFICE

SECURITY

502 CONSULTANT

LOBBY

SERVER

ELEVATORS

ELEVATOR

RECALL

WORKFORCE

DIV. OF REHAB

(E)CR009

1 1 1 1 1

FILE:

DRAWN BY:

CHECKED BY:

PROJ. NO:

DRAWING NO:

DRAWING TITLE:

PROJECT NAME:

http://www.ZDSDesign.com

135 Corporate Center Drive Suite 532 Scott Depot, WV 25560

TEL 304/755-0075

FAX 304/755-0076

THIS SQUARE APPEARS 1/2"x1/2"

ON FULL SIZE SHEETS

CLIENT:

XXX

C :\U se rs

\e di so n.

ad ki ns \D oc um en ts

\G

SD

2C

_2

4-

-2 3_

BL

D

G

W

EI

R

TO

N _e di so n.

ad ki ns

.rv t

8/

/2

:4 2:

P

M

34-TD-101

EA

TZ3

GSD-252-C

DEMO PLAN FIRST

FLOOR SECURITY

BUILDING 34 SECURITY

SYSTEM UPGRADES

100 Municipal Plaza Weirton, WV 26062

WEST VIRGINIA

GENERAL SERVICES

KEYNOTES

1 EXISTING VIDEO CAMERAS INSTALLED BY DMV TO BE REMOVED. CONFIRM WITH

DMV MANAGER WHICH CAMERAS ARE TO BE REMOVED. DMV CONTACT: CASSIE

FETZER (304-740-0055 CASSANDRA.J.FETZER@WV.GOV

2 EXISTING VIDEO SWITCHER AND MONITOR INSTALLED BY DMV TO BE REMOVED.

CONFIRM WITH DMV MANAGER WHICH SYSTEM IS TO BE REMOVED.

3 EXISTING WIRELESS PANIC PENDANT INSTALLED BY DMV TO REMAIN

4 EXISTING SECURITY PANEL AND KEYPAD INSTALLED BY DMV TO REMAIN.

5 EXISTING SECURITY RACK TO REMAIN. CLEAN AND REUSE.

7 EXISTING VIDEO RECORDER AND NETWORK SWITCH INSTALLED BY DMV TO

REMAIN.

8 EXISTING CARD READERS INSTALLED BY WV LOTTERY TO REMAIN. CONFIRM WITH

LOTTERY PERSONNEL BEFORE REMOVING DEVICES IN THIS AREA.

9 EXISTING CONTROL PANELS SHOWN TO REMAIN SUPPORT THE EXISTING CARD

READERS IN THE LOTTERY AREA THAT ARE TO REMAIN. FIELD VERIFY THAT THE

EXISTING DOOR POWER SUPPLIES DO NOT SUPPORT THE LOCKS ON THE DOORS

ASSOCIATED WITH THESE READERS PRIOR TO REMOVAL.

10 EXISTING VIDEO CAMERA INSTALLED BY WV LOTTERY TO REMAIN.

11 NEW CAMERA SYSTEM INSTALLED BY DMV TO REMAIN. CONFIRM WITH DMV

MANAGER WHICH CAMERAS ARE TO BE REMOVED.

1/8" = 1'-0"34-TD-101

1 FIRST FLOOR SECURITY PLAN

SYSTEMS DEMOLITION NOTES

1 DISCONNECT AND REMOVE ONLY SYSTEM DEVICES SHOWN TO BE DEMOLISHED.

2 DISCONNECT AND REMOVE ASSOCIATED CONDUIT AND WIRE BACK TO LAST

REMAINING DEVICE. FURNISH AND INSTALL CONDUIT AND WIRE AS NECESSARY

FOR CONTINUITY OF CIRCUIT(S) TO ANY EXISTING DEVICES TO REMAIN.

COORDINATE AND VERIFY REQUIREMENTS WITH NEW WORK IN AREA.

3 FURNISH AND INSTALL CONDUIT AND/OR SYSTEMS WIRING AS NECESSARY FOR

CONTINUITY OF ANY SYSTEMS EQUIPMENT OR DEVICES TO REMAIN. MODIFY OR

REPLACE AS REQUIRED.

4 FURNISH AND INSTALL BLANK COVER PLATES FOR ALL EXISTING UNUSED

OPENINGS.

5 BUILDINGS THAT HAVE CAMERAS THAT WORK OR WOULD WORK IF THE

SOFTWARE AND LICENSES WERE CURRENT SHOULD HAVE NEW NVRS INSTALLED

AND THE EXISTING CAMERAS CONNECTED TO THEM. AS NEW CAMERAS ARE

INSTALLED, REMOVE OLD CAMERAS FROM THE SYSTEM.

6 THE EXISTING ACCESS CONTROL SYSTEM IS TO REMAIN IN USE UNTIL THE NEW

SYSTEM IS COMPLETE. DOORS SHOULD BE MIGRATED TO THE NEW SYSTEM ONE

AT A TIME UNTIL ALL ARE ON THE NEW SYSTEM. DURING THIS MIGRATION, NO

DOOR IS TO REMAIN UNSECURED OR INOPERABLE AT THE END OF A WORKDAY.

CR

CR

CR

CR

CR

CR

CR

C-

C-3

C-3

C-2

C-2

C-1

C-1

AC

P

MD

MD

MD

PS PS

0 D

610 D1

627 D1

9 D

1 D

611 D1

9 D

810 D1

1 D

800 D1

CONFERENCE

STORAGE

VIDEO

INTERVIEW

INTERVIEW

FAMILY VISIT.

CORRIDOR

INTERVIEW

INTERVIEW

613 OFFICE

OFFICE

OFFICE

OFFICE

OFFICE

WORK STATIONS

DEPT OF HUMAN SERVICES

DEPT OF HUMAN SERVICES

CORRIDOR

CORRIDOR

CORRIDOR

STORAGE

SERVER

OFFICE

OFFICE

OFFICE

OFFICE

OFFICE

OFFICE

RECEPTION

WAITING

OFFICE

OFFICE

SERVER

702 OFFICE

CLASSROOM/CONFERENCS

RESOURCE ROOM

CHILD SUPPORT SERVICES

RECEPTION/OPEN OFFICE

ELEVATORS

LOBBY

STAIR

OFFICE

OFFICE

BREAK ROOM

CONFERENCE

MEN

WOMEN

STAIR

JAN. CLOSET

JAN. CLOSET

WOMEN

MEN

IP

CHILD SUPPORT SERVICES

DHHR CPS

FILE:

DRAWN BY:

CHECKED BY:

PROJ. NO:

DRAWING NO:

DRAWING TITLE:

PROJECT NAME:

http://www.ZDSDesign.com

135 Corporate Center Drive Suite 532 Scott Depot, WV 25560

TEL 304/755-0075

FAX 304/755-0076

THIS SQUARE APPEARS 1/2"x1/2"

ON FULL SIZE SHEETS

CLIENT:

XXX

C :\U se rs

\e di so n.

ad ki ns \D oc um en ts

\G

SD

2C

_2

4-

-2 3_

BL

D

G

W

EI

R

TO

N _e di so n.

ad ki ns

.rv t

8/

/2

:4 2:

P

M

34-TD-102

EA

TZ3

GSD-252-C

DEMO PLAN SECOND

FLOOR SECURITY

BUILDING 34 SECURITY

SYSTEM UPGRADES

100 Municipal Plaza Weirton, WV 26062

WEST VIRGINIA

GENERAL SERVICES

KEYNOTES

1 COVER UNUSED BOXES AND PATCH AND RESTORE ANCHOR HOLES TO ORIGINAL

CONDITION.

1/8" = 1'-0"34-TD-102

1 SECOND FLOOR SECURITY PLAN

SYSTEMS DEMOLITION NOTES

1 DISCONNECT AND REMOVE ONLY SYSTEM DEVICES SHOWN TO BE DEMOLISHED.

2 DISCONNECT AND REMOVE ASSOCIATED CONDUIT AND WIRE BACK TO LAST

REMAINING DEVICE. FURNISH AND INSTALL CONDUIT AND WIRE AS NECESSARY

FOR CONTINUITY OF CIRCUIT(S) TO ANY EXISTING DEVICES TO REMAIN.

COORDINATE AND VERIFY REQUIREMENTS WITH NEW WORK IN AREA.

3 FURNISH AND INSTALL CONDUIT AND/OR SYSTEMS WIRING AS NECESSARY FOR

CONTINUITY OF ANY SYSTEMS EQUIPMENT OR DEVICES TO REMAIN. MODIFY OR

REPLACE AS REQUIRED.

4 FURNISH AND INSTALL BLANK COVER PLATES FOR ALL EXISTING UNUSED

OPENINGS.

5 BUILDINGS THAT HAVE CAMERAS THAT WORK OR WOULD WORK IF THE

SOFTWARE AND LICENSES WERE CURRENT SHOULD HAVE NEW NVRS INSTALLED

AND THE EXISTING CAMERAS CONNECTED TO THEM. AS NEW CAMERAS ARE

INSTALLED, REMOVE OLD CAMERAS FROM THE SYSTEM.

6 THE EXISTING ACCESS CONTROL SYSTEM IS TO REMAIN IN USE UNTIL THE NEW

SYSTEM IS COMPLETE. DOORS SHOULD BE MIGRATED TO THE NEW SYSTEM ONE

AT A TIME UNTIL ALL ARE ON THE NEW SYSTEM. DURING THIS MIGRATION, NO

DOOR IS TO REMAIN UNSECURED OR INOPERABLE AT THE END OF A WORKDAY.

CR

CR

CR

SCP

KP

DBW

DB W

CR

ACP ACP

SWKS

MON

MO

N CR

CR

CR

CRCR

CR

CR

CR

CRCRCRCRCR

CR

CR

CR

ACP

AC

P

CR

DC

DC

DC

ES

ES

DC

DC

DC

DC

DC DC

CR

CR

MON

CR

ES

DR

CR

ES

SWKS

ES

ES

DC

DCDC DC

DB

DB

ADO

AD

O

DB

DB

ADO

DB

DB

2 CWKS2

5 D

3 D

5 D

0 D

104 D1

403 D1

5 D

2 D

504 D1

2 D

501 D1

1 D

PLATE/STORAGE

CHECK OUT

DATA

BREAK ROOM

CORRIDOR

MANAGER

105SUPERVISOR

WAITING

INFO/PHOTO

LICENSE CTR.

DRIVER TESTING

EXAMINER SUPER.

HEARING

INVESTIGATOR

CLOSET

OFFICE

200 OFFICE

OFFICE

OFFICE

CORRIDOR

OFFICE

OFFICE

SERV.

STORAGE

COPY/FAX

STOR.

CLERICAL

OFFICE

WIRING CL.

CONFERENCE

REHAB. SERVICES WAITING

SERVER

MAIL/FAX/STORAGE

TRAINING ROOM

HEARING ROOM

STORAGE

AMERICAN JOB CENTER

UI MANAGE OFFICE

WAITING

WORKFORCE

OFF. COUNSELOR

OFFICE MANAGER

BREAK ROOM

MECH.

ENTRY

SECURITY

LOBBY

STAIR

WOMEN

WOMEN

MEN

409 MEN

CORRIDOR

STAIR

SHIPPING/RECEIVING

BUILDING SERVICES

HALL

JAN. CLST.

CONFERENCE

WV LOTTERY OPEN OFFICE

SECURITY

502 CONSULTANT

LOBBY

SERVER

ELEVATORS

WORKFORCE

C002

TYPE C

C005

TYPE C

C007

TYPE B

C003

TYPE H

C008

TYPE B

C001

TYPE A

CR021

CR020

CR019 CR018

CR017

CR016 CR015 CR014 CR013 CR012

CR011

CR010

(E)CR009

CR001

CR003 CR002

M001

M002 SWKS01

DC009

DC008

DC007

DC006

DC005

DC004

DC003

DC002DC001

ACP001

ACP002

ES001 1

M003

8 15

5 5

CR033

CR036

CR034ES004

CR035ES005

CR037

ES007

(E)CR038

(E)CR042

(E)CR041

(E)CR039 (E)CR040

DC011

DC012DC013DC014

ES003

ES006

DR001

(E) SNR002

ADO01

ADO02

ADO03

SNR001

CWKS01

DB005

DB006

DB003

DB004

DB001

DB002

FILE:

DRAWN BY:

CHECKED BY:

PROJ. NO:

DRAWING NO:

DRAWING TITLE:

PROJECT NAME:

http://www.ZDSDesign.com

135 Corporate Center Drive Suite 532 Scott Depot, WV 25560

TEL 304/755-0075

FAX 304/755-0076

THIS SQUARE APPEARS 1/2"x1/2"

ON FULL SIZE SHEETS

CLIENT:

XXX

C :\U se rs

\e di so n.

ad ki ns \D oc um en ts

\G

SD

2C

_2

4-

-2 3_

BL

D

G

W

EI

R

TO

N _e di so n.

ad ki ns

.rv t

8/

/2

:4 2:

P

M

34-TY-101

EA

TZ3

GSD-252-C

FIRST FLOOR SECURITY

PLAN

BUILDING 34 SECURITY

SYSTEM UPGRADES

100 Municipal Plaza Weirton, WV 26062

WEST VIRGINIA

GENERAL SERVICES

1/8" = 1'-0"34-TY-101

1 FIRST FLOOR SECURITY PLAN

KEYNOTES

1 EXISTING SECURITY NETWORK RACK TO BE REUSED. REMOVE ALL UNUSED

EQUIPMENT. FILL UNUSED SPACES WITH BLANK PANELS . SEE SPECIFICATIONS

AND DETAIL 1 ON SHEET 34-TY-501.

2 NEW CAMERA SYSTEM INSTALL BY DMV TO REMAIN. CONFIRM WITH DMV

MANAGER WHICH CAMERAS ARE TO REMAIN. DMV CONTACT: CASSIE FETZER

(304-740-0055 CASSANDRA.J.FETZER@WV.GOV

3 EXISTING WIRELESS PANIC PENDANT INSTALLED BY DMV TO REMAIN

4 EXISTING SECURITY PANEL AND KEYPAD INSTALLED BY DMV TO REMAIN.

5 EXISTING CARD READERS INSTALLED BY WV LOTTERY TO REMAIN. CONFIRM WITH

LOTTERY PERSONNEL BEFORE REMOVING DEVICES IN THIS AREA.

6 GSD SECURITY NETWORK RACK WITH LOCKING DOOR.

7 CONTRACTOR SHALL FURNISH WITH ALL REQUIRED COMPONENTS FOR A

COMPLETE INSTALLATION. FURNISH 120V POWER FROM NEAREST CIRCUIT.

INTERLOCK DOOR OPERATOR BUTTONS WITH ACCESS CONTROL SYSTEM. SEE

DETAIL ON SHEET 34-TY-501.

8 THIS DOOR LOCKS ON A SCHEDULE. CONFIRM REQUIRED OPERATION WITH

OWNER.

9 EXISTING VIDEO CAMERA INSTALLED BY WV LOTTERY TO REMAIN.

10 EXISTING VIDEO RECORDER AND NETWORK SWITCH INSTALLED BY DMV TO

REMAIN.

11 PROVIDE 12 STRAND MM OM4 ARMOURED FIBER TO DATA RACKS IN SECURITY 403

AND SERVER 601. PROVIDE FIBER TERMINATION PANELS AT EACH RACK

LOCATION.

12 PROVIDE 12 STRAND MM OM4 ARMOURED FIBER TO DATA RACK IN BUILDING

SERVICES 414. PROVIDE FIBER TERMINATION PANELS AT EACH RACK LOCATION.

13 CREDENTIALLING WORKSTATION. COORDINATE WITH OWNER FOR EXACT

LOCATION.

14 PROVIDE 3 - 34" CURVED DESKTOP MONITORS FOR SECURITY WORKSTATION.

15 INTERLOCK DOOR OPERATOR BUTTONS WITH ACCESS CONTROL SYSTEM. SEE

DETAIL ON SHEET 34-TY-501.

SECURITY SYSTEM SHEET NOTES

A SEE DETAIL SHEET FOR SECURITY CAMERA MOUNTING

B SEE SECURITY DEVICE SCHEDULE FOR ADDITIONAL INFORMATION

C ALL COMMUNICATION CABLES SHALL BE INSTALLED IN CONDUIT, CABLE TRAY, OR

SUPPORTED BY CABLE HOOKS. PROVIDE BUSHINGS AT THE ENDS OF ALL

CONDUITS WHERE STUBBED ABOVE ACCESSIBLE CEILINGS OR WHERE DROPPED

INTO CABLE TRAYS. PROVIDE CABLE HOOKS ABOVE ACCESSIBLE CEILINGS FOR

CABLE INSTALLATION WHERE NOT INSTALLED IN A CONDUIT OR CABLE TRAY.

D BUILDINGS THAT HAVE CAMERAS THAT WORK OR WOULD WORK IF THE

SOFTWARE AND LICENSES WERE CURRENT SHOULD HAVE NEW NVRS INSTALLED

AND THE EXISTING CAMERAS CONNECTED TO THEM. AS NEW CAMERAS ARE

INSTALLED, REMOVE OLD CAMERAS FROM THE SYSTEM.

E ALL CABLES AND DEVICES TO BE LABELED. SEE SPECIFICATION AND DETAILS

FOR SPECIFIC REQUIREMENTS.

F THE EXISTING ACCESS CONTROL SYSTEM IS TO REMAIN IN USE UNTIL THE NEW

SYSTEM IS COMPLETE. DOORS SHOULD BE MIGRATED TO THE NEW SYSTEM ONE

AT A TIME UNTIL ALL ARE ON THE NEW SYSTEM. DURING THIS MIGRATION, NO

DOOR IS TO REMAIN UNSECURED OR INOPERABLE AT THE END OF A WORKDAY.

G PROVIDE SURGE PROTECTION FOR ALL EXTERIOR CAMERAS.

CR

CR

CR

CR

CR

CR

CR

AC

P

DC

CR

ES

ADO

DB

DB

0 D

610 D1

627 D1

9 D

1 D

611 D1

9 D

810 D1

1 D

800 D1

CONFERENCE

STORAGE

VIDEO

INTERVIEW

INTERVIEW

FAMILY VISIT.

CORRIDOR

INTERVIEW

INTERVIEW

613 OFFICE

OFFICE

OFFICE

OFFICE

OFFICE

WORK STATIONS

DEPT OF HUMAN SERVICES

DEPT OF HUMAN SERVICES

CORRIDOR

CORRIDOR

CORRIDOR

STORAGE

SERVER

OFFICE

OFFICE

OFFICE

OFFICE

OFFICE

OFFICE

RECEPTION

WAITING

OFFICE

OFFICE

SERVER

702 OFFICE

CLASSROOM/CONFERENCS

RESOURCE ROOM

CHILD SUPPORT SERVICES

RECEPTION/OPEN OFFICE

706 ELEVATORS

LOBBY

STAIR

OFFICE

OFFICE

BREAK ROOM

CONFERENCE

MEN

WOMEN

STAIR

JAN. CLOSET

JAN. CLOSET

WOMEN

MEN

DHHR CPS

C015

TYPE B

C014

TYPE B

C011

TYPE C

C020

TYPE J

C016

TYPE J

14' AFF

CR027

CR026

CR025CR031

CR024

CR023

CR029

CR030

CR028

ACP003

DC010

3SNR003

CR032

ES002

C025

TYPE J

14' AFF

C024

TYPE C

C006

TYPE B

ADO04

DB007

DB008

FILE:

DRAWN BY:

CHECKED BY:

PROJ. NO:

DRAWING NO:

DRAWING TITLE:

PROJECT NAME:

http://www.ZDSDesign.com

135 Corporate Center Drive Suite 532 Scott Depot, WV 25560

TEL 304/755-0075

FAX 304/755-0076

THIS SQUARE APPEARS 1/2"x1/2"

ON FULL SIZE SHEETS

CLIENT:

XXX

C :\U se rs

\e di so n.

ad ki ns \D oc um en ts

\G

SD

2C

_2

4-

-2 3_

BL

D

G

W

EI

R

TO

N _e di so n.

ad ki ns

.rv t

8/

/2

:4 2:

P

M

34-TY-102

EA

TZ3

GSD-252-C

SECOND FLOOR

SECURITY PLAN

BUILDING 34 SECURITY

SYSTEM UPGRADES

100 Municipal Plaza Weirton, WV 26062

WEST VIRGINIA

GENERAL SERVICES

KEYNOTES

1 MATCH MOUNTING HEIGHT TO EXISTING CAMERAS (20'-24' AFF). COVER UNUSED

BOXES AND PATCH AND RESTORE ANCHOR HOLES TO ORIGINAL CONDITION.

CONTRACTOR SHALL FIELD VERIFY PRIOR TO BIDDING AND INCLUDE ALL COSTS IN

BASE-BID.

2 NEW CAMERA MOUNTED 14' AFF.

3 NEW SECURITY NETWORK RACK. SEE SPECIFICATIONS AND DETAIL 1 ON SHEET

34-TY-501.

4 THIS DOOR LOCKS ON A SCHEDULE (UNLOCK DURING NORMAL BUSINESS HOURS).

CONFIRM REQUIRED SCHEDULE WITH CHILD SUPPORT SERVICES.

5 CONTRACTOR SHALL FURNISH WITH ALL REQUIRED COMPONENTS FOR A

COMPLETE INSTALLATION. FURNISH 120V POWER FROM NEAREST CIRCUIT.

INTERLOCK DOOR OPERATOR BUTTONS WITH ACCESS CONTROL SYSTEM. SEE

DETAIL ON SHEET 34-TY-501.

1/8" = 1'-0"34-TY-102

1 SECOND FLOOR SECURITY PLAN

SECURITY SYSTEM SHEET NOTES

A SEE DETAIL SHEET FOR SECURITY CAMERA MOUNTING

B SEE SECURITY DEVICE SCHEDULE FOR ADDITIONAL INFORMATION

C ALL COMMUNICATION CABLES SHALL BE INSTALLED IN CONDUIT, CABLE TRAY, OR

SUPPORTED BY CABLE HOOKS. PROVIDE BUSHINGS AT THE ENDS OF ALL

CONDUITS WHERE STUBBED ABOVE ACCESSIBLE CEILINGS OR WHERE DROPPED

INTO CABLE TRAYS. PROVIDE CABLE HOOKS ABOVE ACCESSIBLE CEILINGS FOR

CABLE INSTALLATION WHERE NOT INSTALLED IN A CONDUIT OR CABLE TRAY.

D BUILDINGS THAT HAVE CAMERAS THAT WORK OR WOULD WORK IF THE

SOFTWARE AND LICENSES WERE CURRENT SHOULD HAVE NEW NVRS INSTALLED

AND THE EXISTING CAMERAS CONNECTED TO THEM. AS NEW CAMERAS ARE

INSTALLED, REMOVE OLD CAMERAS FROM THE SYSTEM.

E ALL CABLES AND DEVICES TO BE LABELED. SEE SPECIFICATION AND DETAILS

FOR SPECIFIC REQUIREMENTS.

F THE EXISTING ACCESS CONTROL SYSTEM IS TO REMAIN IN USE UNTIL THE NEW

SYSTEM IS COMPLETE. DOORS SHOULD BE MIGRATED TO THE NEW SYSTEM ONE

AT A TIME UNTIL ALL ARE ON THE NEW SYSTEM. DURING THIS MIGRATION, NO

DOOR IS TO REMAIN UNSECURED OR INOPERABLE AT THE END OF A WORKDAY.

G PROVIDE SURGE PROTECTION FOR ALL EXTERIOR CAMERAS.

FIBER TERMINATION PANEL

72TB NVR

2000VA UPS FOR NVR

2000VA UPS FOR APP. AND

SWITCH

BLANK PANEL

VENT PANEL

VENT PANEL

VENT PANEL

BLANK PANEL

BLANK PANEL

BLANK PANEL

VENT PANEL

24 PORT SWITCH

CAT 6 PATCH PANEL

12-STRAND

FIBER OPTIC CABLE

ACCESS

CONTROL

PANEL

ACP002

ACCESS

CONTROL

PANEL

ACP001

ACCESS

CONTROL

PANEL

ACP003

12U WALL MOUNTED

SECURITY NETWORK

RACK SNR003

16U WALL MOUNTED

SECURITY NETWORK

RACK SNR001

24U FREE STANDING

SECURITY SERVER RACK

SNR002

ROOM 601

ROOM 414FIRST FLOOR

SECOND FLOOR

CR CR CR EL

CR CR CR EL

CAT 6A(TYPICAL)

CAT 6A(TYPICAL)

COMPOSITE CABLE (TYPICAL)

COMPOSITE CABLE (TYPICAL) JB

JB

JB

JB

JB

JB

JB

JB

CCTV CAMERAS

CARD READERS

CARD READERS

ELECTRIFIED LOCK WITH

SCHEDULED LOCK/UNLOCK

SECURITY ROOM 403

12-STRAND

FIBER OPTIC CABLE

FIBER TERMINATION PANEL

BLANK PANEL

BLANK PANEL

BLANK PANEL

24 PORT SWITCH

CAT 6 PATCH PANEL

FIBER TERMINATION PANEL

BLANK PANEL

1000VA UPS FOR SWITCH

BLANK PANEL

BLANK PANEL

BLANK PANEL

CAT 6 PATCH PANEL

24 PORT SWITCH

ROOF

BLANK PANEL

2000VA UPS FOR SWITCHES

24 PORT SWITCH

CAT 6 PATCH PANEL

BLANK PANEL

BLANK PANEL

TO OIT NETWORK AND

INTERNET PROVIDER

SECURITY

WORKSTATION

SECURITY DESK

ENTRY 402

NOTES:

1. PROVIDE ALL PATCH CABLES, GBICS, AND SFP ADAPTERS TO CONNECT FIBER TO NETWORK SWITCHES.

2. PROVIDE ALL PATCH CABLES, GBICS, AND SFP ADAPTERS TO MAKE 10G CONNECTION FROM NVR TO NETWORK SWITCH.

3. PROVIDE UPS FOR NVR, ACCESS CONTROL APPLIANCE AND NETWORK SWITCHES.

4. PROVIDE BACK-UP BATTERIES FOR ALL ACCESS CONTROL PANELS AND POWER SUPPLIES.

5. TERMINATE ALL 12 STRANDS OF FIBER AT EACH FIBER TERMINATION PANEL.

6. PROVIDE 2 DEDICATED 120V 20A CIRCUITS TO EACH RACK LOCATION. CIRCUIT TO NEAREST ELECTRIAL PANEL.

7. ALL CAT 6 AND FIBER OPTIC CABLE TO BE CERTIFIED. PROVIDE CERTIFICATION TEST REPORTS.

8. GROUND RACKS TO A SUITABLE ELECTRICAL BUILDING GROUND. SEE SPECIFICATIONS.

9. INSTALL READERS USING OSDP SECURE COMMUNICATIONS PROTOCOL.

BRUSH GROMMET PANELCREDENTIALING

WORKSTATION

CAT 6A(TYPICAL)

FLOOR

A.

B.

GENERAL DETAIL NOTES (TYPICAL ACCESS DOOR DIAGRAM ONLY):

DETAIL REPRESENTS ALL HARDWARE OPTIONS. QUANTITY AND TYPE OF DEVICES VARY PER LOCATION AS INDICATED ON PLANS.

INSTALL EMT FOR EACH RACEWAY - SEE ROUGH-IN DETAILS.

FIRE ALARM INTERFACE

1 46

2REX

TO ACCESS CONTROL PANEL 7

1.

2.

3.

4.

5.

6.

7.

8.

9.

10.

11.

12.

13.

14.

15.

16.

17.

18.

DETAIL NOTES:

CARD READERS.

REQUEST TO EXIT DEVICE.

ELECTRIC STRIKE.

POWER TRANSFER DEVICE.

DOOR CONTACT.

EMERGENCY EXIT DEVICE.

READER JUNCTION BOX OR DOOR POWER SUPPLY. WHERE REQUIRED, FURNISH 120 VOLT POWER FROM NEAREST CIRCUIT.

DOOR OPERATOR. FURNISH 120V POWER FROM NEAREST CIRCUIT.

DOOR OPERATOR PUSHBUTTONS. INTERFACE CARD READER WITH DOOR OPERATOR TO ENABLE NON-SECURE SIDE OPERATOR BUTTON ONLY

AFTER VALID CREDENTIAL IS PRESENTED.

ELECTRIFIED DOOR HARDWARE

POWER CONDUCTORS IN EMT RACEWAY

CONTROL CONDUCTORS IN EMT RACEWAY

CEILING HEIGHT VARIES.

ACCESSIBLE CEILING SPACE.

POWER FROM NEAREST CIRCUIT.

CONDUCTORS IN RACEWAY ABOVE CEILING.

CONDUCTORS IN RACEWAY TYPICAL - SEE SECURITY DEVICE ROUGH-IN DETAIL.

PLENUM RATED CABLE SUPPORTED ABOVE CEILING.

1'-0" MAXIMUM

6" MIN

6" MAX

1'-0" MAX

IDF #(FF1)

OUTLET #

FF1-003G

JACK # (G, R, Y)

1-001G 1-001R

1-001Y 1-002G 1-002R

1-002Y 1-003G 1-003R

1-003Y

CAT 6

RJ45

JACK

1 8

FF1-001-G

IDF CLOSET (FF1)

FACEPLATE

NUMBER (001)

JACK COLOR (G, R, Y)

WHITE LABEL AND BLACK

LETTERS WITH CLEAR

TAPE COVERING ON BOTH

ENDS OF CABLE

SECTION

PLAN

CEILING SEE ARCHITECTURAL

DRAWINGS

ELECTRICAL BOX T-BAR

FASTENER

SURVEILLANCE DEVICE

ELECTRICAL BOX T-BAR

FASTENER

ACOUSTICAL TILE SEE

ARCHITECTURAL

DRAWINGS

CEILING STRUCTURE SEE

ARCHITECTURAL DRAWINGS

CEILING SUPPORT STRUCTURE

SEE ARCHITECTURAL DRAWINGS

HORIZONTAL CABLING TO

CABLING SUPPORT SYSTEM

EQUAL EQUAL

EQ

UA

L

SUPPORT CABLE ON ALL

FOUR CORNERS OF GRID

SUPPORT CABLE ON ALL

FOUR CORNERS OF CEILING

SUPPORT STRUCTURE

METAL BOX SIZE AS

REQUIRED BY NEC

METAL BOX SIZE AS

REQUIRED BY NEC

EQ

UA

L SURVEILLANCE DEVICE

PATCH

CABLE

4x4 METAL BOX WITH

COVER - MTD TO WALL

PATCH CABLE BY

SYSTEMS

CONTRACTORWALL ABOVE CEILING

HORIZONTAL CABLE

SEE SPECIFICATIONS

SURFACE MOUNT

KEYSTONE (BISCUIT) JACK

4x4 METAL BOX WITH

COVER - MTD TO WALL

HORIZONTAL CABLE

SEE SPECIFICATIONS

SURFACE MOUNT

KEYSTONE (BISCUIT) JACK

PATCH CABLE BY

SYSTEMS

CONTRACTOR

FLOOR

A.

B.

C.

D.

GENERAL DETAIL NOTES (TYPICAL ACCESS DOOR DIAGRAM ONLY):

DETAIL REPRESENTS ALL HARDWARE OPTIONS. QUANTITY AND TYPE OF DEVICES VARY PER LOCATION AS INDICATED ON PLANS.

PROVIDE SHOP DRAWING SUBMITTAL AND WIRING DIAGRAMS FOR EACH POWER ASSISTED/ACCESS DOOR LOCATION.

ALL EQUIPMENT FURNISHED AND INSTALLED BY SECURITY CONTRACTOR.

INSTALL EMT FOR EACH RACEWAY - SEE ROUGH-IN DETAILS.

FIRE ALARM INTERFACE

1 46

2REX

TO ACCESS CONTROL PANEL

1.

2.

3.

4.

5.

6.

7.

8.

9.

10.

11.

12.

13.

14.

15.

16.

DETAIL NOTES:

CARD READERS.

REQUEST TO EXIT DEVICE.

ELECTRIC STRIKE.

ELECTRIFIED DOOR HARDWARE AND POWER TRANSFER DEVICE.

EMERGENCY EXIT DEVICE.

DOOR POWER SUPPLY. POWER SUPPLY TO BE USED AS ACCESS CONTROL JUNCTION BOX. 120 VOLT POWER FROM NEAREST CIRCUIT.

DOOR OPERATOR. FURNISH 120V POWER FROM NEAREST CIRCUIT. ON ACCESS CONTROL DOORS INTERFACE WITH ACCESS CONTROL SYSTEM.

DOOR OPERATOR PUSHBUTTONS. INTERFACE CARD READER WITH DOOR OPERATOR TO ENABLE NON-SECURE SIDE OPERATOR BUTTON ONLY

AFTER VALID CREDENTIAL IS PRESENTED.

SINGLE DOOR LOCATION

ELECTRIFIED DOOR HARDWARE

POWER CONDUCTORS IN EMT RACEWAY

CONTROL CONDUCTORS IN EMT RACEWAY

CEILING HEIGHT VARIES.

POWER FROM NEAREST CIRCUIT.

CONDUCTORS IN RACEWAY TYPICAL - SEE SECURITY DEVICE ROUGH-IN DETAIL.

CONDUCTORS IN RACEWAY 9'-0" AFF.

1'-0" MAXIMUM

6" MAX

1'-0" MAX

6" MIN

1"⌀ EMT CONDUIT

METAL ELECTRICAL

BOX - SEE

SPECIFICATIONS

CEILING AS INDICATED

WITHIN ARCH PLANS

SET SCREW

CONNECTOR

WITH INSULATING

BUSHING

SET SCREW

CONNECTOR WITH

INSULATING BUSHING

1'-0"

6"

SE

E

AR

C

H

IT

EC

TU

R

AL

D R

AW

IN

G S

FO

R

C

EI

LI

N

G H

EI

G

H T

3' -4

1.

2.

NOTES:

THE DEVICE SHALL NOT SPAN MORE

THAN ONE FINISH MATERIAL

BOX SHALL BE FLUSH WITH THE

FINISH MATERIAL

FILE:

DRAWN BY:

CHECKED BY:

PROJ. NO:

DRAWING NO:

DRAWING TITLE:

PROJECT NAME:

http://www.ZDSDesign.com

135 Corporate Center Drive Suite 532 Scott Depot, WV 25560

TEL 304/755-0075

FAX 304/755-0076

THIS SQUARE APPEARS 1/2"x1/2"

ON FULL SIZE SHEETS

CLIENT:

XXX

C :\U se rs

\e di so n.

ad ki ns \D oc um en ts

\G

SD

2C

_2

4-

-2 3_

BL

D

G

W

EI

R

TO

N _e di so n.

ad ki ns

.rv t

8/

/2

:4 2:

P

M

34-TY-501

EA

TZ3

GSD-252-C

SECURITY DETAILS

BUILDING 34 SECURITY

SYSTEM UPGRADES

100 Municipal Plaza Weirton, WV 26062

WEST VIRGINIA

GENERAL SERVICES

NOT TO SCALE34-TY-501

1 ACCESS CONTROL SYSTEM RISER SCHEMATIC

NOT TO SCALE34-TY-501

2 TYPICAL ACCESS CONTROL DOOR DETAIL FOR SPACES WITH ACCESSIBLE CEILINGS

NOT TO SCALE34-TY-501

3 TYPICAL 48 PORT PATCH PANEL DETAIL

NOT TO SCALE34-TY-501

4 VOICE AND DATA CABLE LABELING DETAIL

NOT TO SCALE34-TY-501

8 CAMERA INSTALLATION DETAIL

NOT TO SCALE34-TY-501

6 BISCUIT BOX

1/8" = 1'-0"34-TY-501

5 TYPICAL ACCESS CONTROL DOOR DETAIL FOR SPACES WITHOUT ACCESSIBLE CEILINGS

1/2" = 1'-0"34-TY-501

7 SECURITY DEVICE ROUGH-IN DETAIL

A

4 3 1

NOTE:

F) CORRIDORS

J) BOILER, CENTRAL HEATING PLANT, OR

HOT WATER SUPPLY ROOM ENCLOSURES.

I) "TYPE OF CONSTUCTION SEPARATION"

H) EXIT PASSAGEWAYS

G) STAIR ENCLOSURES

E) SHAFT ENCLOSURES

D) JANITOR CLOSETS

C) AREA SEPARATIONS

B) EXTERIOR WALLS

A) OCCUPANCY SEPARATIONS

PENETRATIONS OF FIRE RATED ASSEMBLIES MUST BE

PROTECTED BY U.L. SYSTEM WL 1001, 1002 OR 1003.

SUCH PENETRATIONS ARE TYPICALLY FOUND AT:

1A

1.

A.

B.

2.

PIPE OR CONDUIT-NOM 12 IN. DIA. (OR SMALLER) SCHEDULE 10 (OR HEAVIER) STEEL PIPE, NOM.6 IN. DIA. (OR SMALLER) STEEL CONDUIT, NOM. 4 IN. DIA. (OR SMALLER) STEEL ELECTRICAL METALLIC TUBING OR TYPE L (OR HEAVIER) COPPER TUBING OR NOM 1 IN. DIA. (OR SMALLER) FLEXIBLE STEEL CONDUIT. WHEN COPPER PIPE OR FLEXIBLE STEEL CONDUIT IS USED, MAX. F RATING OF FIRESTOP SYSTEM (ITEM 3) IS 2 HR. STEEL PIPES OR CONDUITS LARGER THAN NOM 4 IN. DIA. MAY ONLY BE USED IN WALLS CONSTRUCTED USING STEEL CHANNEL STUDS. A MAX OF ONE PIPE OR CONDUIT IS PERMITTED IN THE FIRESTOP SYSTEM. PIPE OR CONDUIT TO BE INSTALLED NEAR CENTER OF STUD CAVITY WIDTH AND TO BE RIGIDLY SUPPORTED ON BOTH

SIDES OF WALL ASSEMBLY.

WALLBOARD, GYPSUM* -NOM 1/2 OR 5/8 IN. THICK, 4 FT. WIDE WITH SQUARE OR TAPERED EDGES. THE GYPSUM WALLBOARD TYPE, THICKNESS, NUMBER OF LAYERS, FASTENER TYPE AND SHEET ORIENTATION SHALL BE AS SPECIFIED IN THE INDIVIDUAL U300 OR U400 SERIES DESIGN IN THE U.L. FIRE RESISTANCE DIRECTORY. MAXIMUM DIAMETER OF OPENING IS 13-1/2 IN.

STUDS-WALL FRAMING MAY CONSIST OF EITHER WOOD STUDS (MAX. 2 HR. FIRE RATED ASSEMBLIES) OR STEEL CHANNEL STUDS. WOOD STUDS TO CONSIST OF NOMINAL 2 BY 4 IN. LUMBER SPACED 16 IN. OC WITH NOMINAL 2 BY 4 IN. LUMBER END PLATES AND CROSS BRACES. STEEL STUDS TO BE MINIMUM 3-5/8 IN. WIDE BY 1-3/8 IN.

DEEP CHANNELS SPACED MAX. 24 IN. O.C.

WALL ASSEMBLY - THE 1,2,3 OR 4 HR. FIRE-RATED GYPSUM WALLBOARD/STUD WALL ASSEMBLY SHALL BE CONSTRUCTED OF THE MATERIALS AND IN THE MANNER DESCRIBED IN THE INDIVIDUAL U300 OR U400 SERIES WALL OR PARTITION DESIGNS IN THE U.L. FIRE RESISTANCE DIRECTORY AND SHALL INCLUDE THE FOLLOWING

CONSTRUCTION FEATURES:

A

A

T

RATING

HOUR

3 OR 4

F

RATING

HOUR

1 OR 2

1 OR 2

1 OR 2

3 OR 4

3 OR 4

0 TO 1/4

3/16 TO 3/8

1/4 TO 1/2

0 TO 3/16

1/4 TO 1/2

ANNULAR

SPACE, IN.

3.

SYSTEM NO. FA1002

(FORMERLY SYSTEM NO.152)

F RATING-2 HR

T RATING-0 HR

L RATING AT AMBIENT-2 CFM/sq ft (SEE ITEM 4) L RATING AT 400 F- LESS THAN 1 CFM/sq ft (SEE ITEM 4)

FILL, VOID OR CAVITY MATERIAL* - CAULK** - CAULK FILL MATERIAL INSTALLED TO COMPLETELY FILL ANNULAR SPACE BETWEEN PIPE OR CONDUIT AND GYPSUM WALLBOARD AND WITH A MIN. 1/4 IN. DIA. BEAD OF CAULK APPLIED TO PERIMETER OF PIPE OR CONDUIT AT ITS EGRESS FROM THE WALL. CAULK INSTALLED SYMMETRICALLY ON BOTH SIDES OF WALL ASSEMBLY. THE HOURLY F RATING OF THE FIRESTOP SYSTEM IS DEPENDENT UPON THE HOURLY FIRE RATING OF WALL ASSEMBLY IN WHICH IT IS INSTALLED AS SHOWN IN THE FOLLOWING TABLE. THE HOURLY T RATING OF THE FIRE STOP SYSTEM IS DEPENDENT UPON THE TYPE OR SIZE OF THE PIPE OR CONDUIT AND THE HOURLY FIRE RATING OF THE WALL ASSEMBLY IN WHICH IT IS INSTALLED, AS TABULATED

BELOW:

+WHEN COPPER PIPE IS USED, T RATING IS 0 HOUR.

* BEARING THE UL CLASSIFICATION MARKING.

**MING & MFG. CO. - TYPES CP-25 S/L, CP-25 N/S, CP-25 WB, CP-25 WB+.

MAX PIPE

OR CONDUIT

DIAMETER, IN.

1B

*BEARING THE UL CLASSIFICATION MARKING

MINNESOTA MINING & MFG. CO. - TYPES CP-25 WB. CP-25 WB +. (NOTE: L RATINGS

APPLY ONLY WHEN TYPE CP-25 WB+ CAULK IS USED).

4) FILL, VOID, OR CAVITY MATERIALS* - CAULK - APPLIED TO FILL THROUGH OPENING TO A MIN. DEPTH OF 1 IN., FLUSH WITH TOP SURFACE OF FLOOR.

3) PACKING MATERIAL - MIN. 1 IN. THICK MINERAL-WOOL BATT MATERIAL INSULATION FIRMLY PACKED INTO OPENING AS A PERMANENT FORM WITH ITS TOP SURFACE RECESSED MIN. 1 IN. FROM TOP SURFACE OF FLOOR.

2) PIPE - NOM 4 IN. DIAMETER (OR SMALLER) TYPE L (OR HEAVIER) COPPER TUBING SCHEDULE 10 (OR HEAVIER) STEEL PIPE, STEEL CONDUIT OR STEEL EMT TO BE INSTALLED WITH A MIN. CLEARANCE OF 1 IN. AND A MAX.

CLEARANCE OF 2 IN. FROM THE SIDES OF THE THROUGH OPENING. A MIN. SEPARATION OF 1 IN. SHALL BE MAINTAINED BETWEEN ADJACENT PIPES. PIPES TO BE RIGIDLY SUPPORTED ON BOTH SIDES OF FLOOR

ASSEMBLY.

1) FLOOR ASSEMBLY - MIN. 4-1/2 IN. THICK LIGHTWEIGHT OR NORMAL WEIGHT (100-150 PCF) CONCRETE.

MAX. AREA OF OPENING 192 SQ. IN. WITH MAX. LENGTH OF 24 IN. AND MAX WIDTH OF 8 IN.

THROUGH-PENETRATION FIRESTOP SYSTEMS (XHEZ)

FIRESTOP METHOD

SYSTEMS NO. WL1001-CAULK ONLY

(FORMERLY SYSTEM NO. 147A)

F RATINGS--1,2,3 AND 4 HR (SEE ITEMS 2 AND 3)

T RATINGS--0,1,2,3 AND 4 HR (SEE ITEM 3)

SECTION A-A

THROUGH-PENETRATION FIRESTOP SYSTEMS (XHEZ)

0+, 1 OR 2

1/8" = 1'-0"34-TY-502

1 ELECTRICAL CONDUIT PENETRATION DETAIL

FILE:

DRAWN BY:

CHECKED BY:

PROJ. NO:

DRAWING NO:

DRAWING TITLE:

PROJECT NAME:

http://www.ZDSDesign.com

135 Corporate Center Drive Suite 532 Scott Depot, WV 25560

TEL 304/755-0075

FAX 304/755-0076

THIS SQUARE APPEARS 1/2"x1/2"

ON FULL SIZE SHEETS

CLIENT:

XXX

C :\U se rs

\e di so n.

ad ki ns \D oc um en ts

\G

SD

2C

_2

4-

-2 3_

BL

D

G

W

EI

R

TO

N _e di so n.

ad ki ns

.rv t

8/

/2

:4 2:

P

M

34-TY-502

EA

TZ3

GSD-252-C

SECURITY DETAILS

BUILDING 34 SECURITY

SYSTEM UPGRADES

100 Municipal Plaza Weirton, WV 26062

WEST VIRGINIA

GENERAL SERVICES

FILE:

DRAWN BY:

CHECKED BY:

PROJ. NO:

DRAWING NO:

DRAWING TITLE:

PROJECT NAME:

http://www.ZDSDesign.com

135 Corporate Center Drive Suite 532 Scott Depot, WV 25560

TEL 304/755-0075

FAX 304/755-0076

THIS SQUARE APPEARS 1/2"x1/2"

ON FULL SIZE SHEETS

CLIENT:

XXX

C :\U se rs

\e di so n.

ad ki ns \D oc um en ts

\G

SD

2C

_2

4-

-2 3_

BL

D

G

W

EI

R

TO

N _e di so n.

ad ki ns

.rv t

8/

/2

:4 2:

P

M

34-TY-601

EA

TZ3

GSD-252-C

SECURITY SCHEDULES

BUILDING 34 SECURITY

SYSTEM UPGRADES

100 Municipal Plaza Weirton, WV 26062

WEST VIRGINIA

GENERAL SERVICES

Security Device Schedule

Mark Identity Type

Mark Description Model Comments

ACP001 ACCESS CONTROL PANEL UNIFIED POWER SUPPLY ENCLOSURE WITH

ACCESS CONTROL BOARDS

ACP002 ACCESS CONTROL PANEL UNIFIED POWER SUPPLY ENCLOSURE WITH

ACCESS CONTROL BOARDS

ACP003 ACCESS CONTROL PANEL UNIFIED POWER SUPPLY ENCLOSURE WITH

ACCESS CONTROL BOARDS

ADO01 AUTOMATIC DOOR OPERATOR LCN 4630/4640 SERIES

ADO02 AUTOMATIC DOOR OPERATOR LCN 4630/4640 SERIES

ADO03 AUTOMATIC DOOR OPERATOR LCN 4630/4640 SERIES

ADO04 AUTOMATIC DOOR OPERATOR LCN 4630/4640 SERIES

C001 TYPE A 4MP DOME CAMERA, 4.4 - 9.3MM LENS, IR, IN-CEILING MOUNT 4.0C-H6A-D1-IR

C002 TYPE C 12MP FISHEYE CAMERA, IR SURFACE MOUNT 12.0W-H6A-FE-DO1-IR

C003 TYPE H 3 X 5MP MULTI-HEAD CAMERA, IN-CEILING MOUNT 15C-H5A-3MH

C005 TYPE C 12MP FISHEYE CAMERA, IR SURFACE MOUNT 12.0W-H6A-FE-DO1-IR

C006 TYPE B 5MP DUAL HEAD CAMERA, SURFACE MOUNT 10.0C-H6DH-DO1-IR

C007 TYPE B 5MP DUAL HEAD CAMERA, SURFACE MOUNT 10.0C-H6DH-DO1-IR

C008 TYPE B 5MP DUAL HEAD CAMERA, SURFACE MOUNT 10.0C-H6DH-DO1-IR

C011 TYPE C 12MP FISHEYE CAMERA, IR SURFACE MOUNT 12.0W-H6A-FE-DO1-IR

C014 TYPE B 5MP DUAL HEAD CAMERA, SURFACE MOUNT 10.0C-H6DH-DO1-IR

C015 TYPE B 5MP DUAL HEAD CAMERA, SURFACE MOUNT 10.0C-H6DH-DO1-IR

C016 TYPE J 3 X 5MP MULTI-HEAD CAMERA, IR, CORNER MOUNT 15C-H5A-3MH 14' AFF

C020 TYPE J 3 X 5MP MULTI-HEAD CAMERA, IR, CORNER MOUNT 15C-H5A-3MH

C024 TYPE C 12MP FISHEYE CAMERA, IR SURFACE MOUNT 12.0W-H6A-FE-DO1-IR

C025 TYPE J 3 X 5MP MULTI-HEAD CAMERA, IR, CORNER MOUNT 15C-H5A-3MH 14' AFF

CR001 MULTI-TECHNOLOGY CARD READER MTB15

CR002 MULTI-TECHNOLOGY CARD READER MTB15

CR003 MULTI-TECHNOLOGY CARD READER MTB15

CR010 MULTI-TECHNOLOGY CARD READER MTB15

CR011 MULTI-TECHNOLOGY CARD READER MTB15

CR012 MULTI-TECHNOLOGY CARD READER MTB15

CR013 MULTI-TECHNOLOGY CARD READER MTB15

CR014 MULTI-TECHNOLOGY CARD READER MTB15

CR015 MULTI-TECHNOLOGY CARD READER MTB15

CR016 MULTI-TECHNOLOGY CARD READER MTB15

CR017 MULTI-TECHNOLOGY CARD READER MTB15

CR018 MULTI-TECHNOLOGY CARD READER MTB15

CR019 MULTI-TECHNOLOGY CARD READER MTB15

CR020 MULTI-TECHNOLOGY CARD READER MTB15

CR021 MULTI-TECHNOLOGY CARD READER MTB15

CR023 MULTI-TECHNOLOGY CARD READER MTB15

CR024 MULTI-TECHNOLOGY CARD READER MTB15

CR025 MULTI-TECHNOLOGY CARD READER MTB15

CR026 MULTI-TECHNOLOGY CARD READER MTB15

CR027 MULTI-TECHNOLOGY CARD READER MTB15

CR028 MULTI-TECHNOLOGY CARD READER MTB15

CR029 MULTI-TECHNOLOGY CARD READER MTB15

CR030 MULTI-TECHNOLOGY CARD READER MTB15

CR031 MULTI-TECHNOLOGY CARD READER MTB15

CR032 MULTI-TECHNOLOGY CARD READER MTB15

CR033 MULTI-TECHNOLOGY CARD READER MTB15

CR034 MULTI-TECHNOLOGY CARD READER MTB15

CR035 MULTI-TECHNOLOGY CARD READER MTB15

CR036 MULTI-TECHNOLOGY CARD READER MTB15

CR037 MULTI-TECHNOLOGY CARD READER MTB15

CWKS01 CREDENTIALING WORKSTATION COMPUTER WITH MOUSE, KEYBOARD, 24"

MONITOR AND USB ENROLLMENT READER

DB001 DOOR OPERATOR PUSHBUTTON LCN 8310-3856TWF/WS

DB002 DOOR OPERATOR PUSHBUTTON LCN 8310-3856TWF/WS

DB003 DOOR OPERATOR PUSHBUTTON LCN 8310-3856TWF/WS

DB004 DOOR OPERATOR PUSHBUTTON LCN 8310-3856TWF/WS

DB005 DOOR OPERATOR PUSHBUTTON LCN 8310-3856TWF/WS

DB006 DOOR OPERATOR PUSHBUTTON LCN 8310-3856TWF/WS

DB007 DOOR OPERATOR PUSHBUTTON LCN 8310-3856TWF/WS

DB008 DOOR OPERATOR PUSHBUTTON LCN 8310-3856TWF/WS

DC001 DOOR CONTACT GRI MODEL 195-12WG OR 4463

DC002 DOOR CONTACT GRI MODEL 195-12WG OR 4463

DC003 DOOR CONTACT GRI MODEL 195-12WG OR 4463

DC004 DOOR CONTACT GRI MODEL 195-12WG OR 4463

DC005 DOOR CONTACT GRI MODEL 195-12WG OR 4463

DC006 DOOR CONTACT GRI MODEL 195-12WG OR 4463

DC007 DOOR CONTACT GRI MODEL 195-12WG OR 4463

DC008 DOOR CONTACT GRI MODEL 195-12WG OR 4463

DC009 DOOR CONTACT GRI MODEL 195-12WG OR 4463

DC010 DOOR CONTACT GRI MODEL 195-12WG OR 4463

DC011 DOOR CONTACT GRI MODEL 195-12WG OR 4463

DC012 DOOR CONTACT GRI MODEL 195-12WG OR 4463

DC013 DOOR CONTACT GRI MODEL 195-12WG OR 4463

DC014 DOOR CONTACT GRI MODEL 195-12WG OR 4463

DR001 DOOR RELEASE BUTTON ALARM CONTROLS DTC SERIES

ES001 ELECTRIC DOOR STRIKE HESS 8000 SERIES/HESS 9700 SERIES

ES002 ELECTRIC DOOR STRIKE HESS 8000 SERIES/HESS 9700 SERIES

ES003 ELECTRIC DOOR STRIKE HESS 8000 SERIES/HESS 9700 SERIES

ES004 ELECTRIC DOOR STRIKE HESS 8000 SERIES/HESS 9700 SERIES

ES005 ELECTRIC DOOR STRIKE HESS 8000 SERIES/HESS 9700 SERIES

ES006 ELECTRIC DOOR STRIKE HESS 8000 SERIES/HESS 9700 SERIES

ES007 ELECTRIC DOOR STRIKE HESS 8000 SERIES/HESS 9700 SERIES

M001 DESK MOUNT CCTV MONITOR DELL S3425DW

M002 DESK MOUNT CCTV MONITOR DELL S3425DW

M003 DESK MOUNT CCTV MONITOR DELL S3425DW

SNR001 WALL MOUNT EQUIPMENT RACK DWR-16-22

SNR003 WALL MOUNT EQUIPMENT RACK DWR-12-22

SWKS01 SECURITY WORKSTATION COMPUTER WITH MOUSE AND KEYBOARD

34-C-001 - COVER SHEET
34-E-001 - ELECTRICAL TITLE SHEET
34-TD-101 - DEMO PLAN FIRST FLOOR SECURITY
34-TD-102 - DEMO PLAN SECOND FLOOR SECURITY
34-TY-101 - FIRST FLOOR SECURITY PLAN
34-TY-102 - SECOND FLOOR SECURITY PLAN
34-TY-501 - SECURITY DETAILS
34-TY-502 - SECURITY DETAILS
34-TY-601 - SECURITY SCHEDULES