This document provides details for a federal construction contract solicitation issued by the Department of Health and Human Services Indian Health Service. The solicitation seeks proposals for a construction project to provide and install a fire sprinkler system at the Kyle Health Center in South Dakota and replace an existing dry sprinkler system at the Wanblee Health Center. The project magnitude is estimated between $250,000 and $500,000, and proposals are due by the date and time listed in block 13 of the SF1442 solicitation form. The contract type will be firm fixed price with a period of performance of 360 calendar days. Evaluation will be based on lowest price technically acceptable using the total firm fixed price listed in block 17 of the SF1442. The solicitation is set aside for small businesses only under NAICS code 236220 with a size standard of $39.5 million.
View the file
Other files
Show all 25
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
maksch 01/31/2018
X
PROVIDE SLEEVES, ESCUTCHEONS, GROUT, SUPPORTS, AND ALL
ASSOCIATED MATERIALS PER "SPECIFICATION SECTION 21 05 00
COMMON WORK RESULTS FOR FIRE SUPPRESSION."
FIRE SPRINKLER SYSTEM SHALL BE INSTALLED ACCORDING TO
MANUFACTURER'S SPECIFICATIONS AND RECOMMENDATIONS
ALONG WITH AUTHORITY HAVING JURISDICTION AND ALL LOCAL,
STATE, AND FEDERAL CODES. COORDINATE SPRINKLER AND
PIPING INSTALLATION WITH NEW AND EXISTING LIGHTS, RGD'S,
SPEAKERS, AND ALL OTHER CEILING EQUIPMENT TO AVOID ANY
CONFLICTS.
ES-A-C200/C200N
Features
Job Name ________________________________________________ Contractor ______________________________________________
Job Location ______________________________________________ Approval _______________________________________________
Engineer _________________________________________________ Contractor’s P.O. No. ______________________________________
Approval _________________________________________________ Representative ___________________________________________
Ames product specifications in U.S. customary units and metric are ap prox i mate and are provided for reference only. For pre cise mea sure ments, please contact Ames Technical Service. Ames reserves the right to change or mod i fy product design, con struc tion, specifications, or ma te ri als without pri or notice and without incurring any obligation to make such changes and mod i fi ca tions on Ames products pre vi ous ly or sub se quent ly sold.
Specifications
ColtTM Series C200, C200N Double Check Valve Assemblies
1⁄2
C200N BFG
C200 OSY
LEAD FREE*
* The wetted surface of this product contacted by consumable water contains less than 0.25% of lead by weight.
SIZE (DN) DIMENSIONS WEIGHT
A C (OSY) C (NRS) D G H I J P C200NRS C200OSY C200N NRS C200N OSY
in. mm in. mm in. mm in. mm in. mm in. mm in. mm in. mm in. mm in. mm lbs. kgs. lbs. kgs. lbs. kgs. lbs. kgs.
21⁄2 65 31 787 163⁄8 416 93⁄8 238 31⁄2 89 291⁄16 738 211⁄2 546 151⁄2 393 813⁄16 223 93⁄16 234 115 52 125 57 123 56 133 60 3 80 3111⁄16 805 187⁄8 479 101⁄4 260 311⁄16 94 301⁄4 768 221⁄4 565 171⁄8 435 93⁄16 233 101⁄2 267 131 59 145 66 144 65 158 72 4 100 331⁄2 851 223⁄4 578 123⁄16 310 4 102 33 838 231⁄2 597 181⁄2 470 915⁄16 252 113⁄16 284 161 73 161 73 184 83 184 83 6 150 44 1118 301⁄8 765 16 406 51⁄2 140 443⁄4 1137 333⁄4 857 233⁄16 589 131⁄16 332 15 381 273 124 295 134 314 142 336 152 8 200 50 1270 373⁄4 959 1915⁄16 506 611⁄16 170 541⁄8 1375 405⁄8 1032 277⁄16 697 1511⁄16 399 173⁄16 437 438 199 480 218 513 233 555 252 10 250 571⁄2 1461 453⁄4 1162 2313⁄16 605 83⁄16 208 66 1676 50 1270 321⁄2 826 175⁄16 440 20 508 721 327 781 354 891 404 951 431
Dimensions — Weights
Configurations
Materials
SIZE (DN) DIMENSIONS WEIGHT
A C D G H I J P C200BFG C200NBFG
in. mm in. mm in. mm in. mm in. mm in. mm in. mm in. mm in. mm lbs. kgs. lbs. kgs.
21⁄2 65 271⁄2 698 8 203 31⁄2 89 297⁄8 759 211⁄2 546 1415⁄16 379 813⁄16 223 9 229 56 25 64 29 3 80 28 711 85⁄16 211 311⁄16 94 3011⁄16 779 221⁄4 565 157⁄16 392 93⁄16 233 91⁄2 241 54 24 67 30 4 100 283⁄4 730 815⁄16 227 311⁄16 94 3115⁄16 811 231⁄2 597 161⁄4 412 915⁄16 252 10 254 61 28 84 38 6 150 37 940 10 254 5 127 433⁄16 1097 333⁄4 857 1911⁄16 500 131⁄16 332 101⁄2 267 117 53 157 71 8 200 431⁄2 1105 121⁄4 311 61⁄2 165 511⁄16 1297 405⁄8 1032 235⁄16 592 1511⁄16 399 143⁄16 361 261 118 337 153
HA
I J
G P
D
C
A
D
C (open)
G
H
J
I
PC200, C200N
C200BFG, C200NBFG
Available Models
Pressure — Temperature
Approvals
For additional approval information please contact the factory or visit our website at www.amesfirewater.com
Capacity
UL/FM Certified Flow Characteristics Flow characteristics collected using butterfly shutoff valves.
See literatue S-Colt-200/300 for gate valve flow characteristics
Horizontal Vertical N - Pattern
28S6 B64.51015
IMPORTANT: INQUIRE WITH GOVERNING AUTHORITIES
FOR LOCAL IN STAL LA TION RE QUIRE MENTS
kPa psi 96 14 83 12 69 10 55 8 41 6 28 4 14 2 0 0
0 50 100 150 200 250 300 350 gpm 0 190 380 570 760 950 1140 1330 lpm 15 fps
4.6 mps kPa psi 83 12 69 10 55 8 41 6 28 4 14 2 0 0 kPa psi 83 12 69 10 55 8 41 6 28 4 14 2 0 0
0 100 200 300 400 500 gpm 0 380 760 1140 1520 1900 lpm 15 fps
4.6 mps
21⁄2" (65mm)
3" (80mm)
0 300 600 900 1200 1500 gpm 0 1140 2280 3420 4560 5700 lpm 15 fps
4.6 mps
6" (150mm)
0 100 200 300 400 500 600 700 800 gpm 0 380 760 1140 1520 1900 2280 2660 3040 lpm 15 fps
4.6 mps
4" (100mm) kPa psi 83 12 69 10 55 8 41 6 28 4 14 2 0 0
0 500 1000 1500 2000 2500 3000 3500 gpm 0 1900 3800 5700 7600 9500 11400 13300 lpm fps mps
10" (250mm) kPa psi 83 12 69 10 55 8 41 6 28 4 14 2 0 0
0 500 1000 1500 2000 2500 gpm 0 1900 3800 5700 7600 9500 lpm 15 fps
4.6 mps
8" (200mm)
** kPa psi 165 24 138 20 110 16 83 12 55 8 28 4 0 0
N
V H
H
N V
N V H
N V H
N H V
N H V
For additional information, visit our web site at: www.amesfirewater.com
A Watts Water Technologies Company USA: Backflow- Control Valves-
Canada:
The Reliable Automatic Sprinkler Co., Inc., 103 Fairview Park Drive, Elmsford, New York 10523
Model F1FR Series Quick Response Standard Spray
B ulletin 014 R
ev. I Bulletin 014 Rev. I
Model F1FR56 Sprinkler Types Standard Upright Standard Pendent Conventional Vertical Sidewall Horizontal Sidewall
Model F1FR56 Recessed Sprinkler Types Standard Pendent/F1/F2/FP Horizontal Sidewall
Model F1FR56 Concealed Sprinkler Types Standard Pendent
Model F1FR42, F1FRXLH & F1FR28 Sprinkler Types
Standard Upright Standard Pendent
Model F1FR42, F1FRXLH & F1FR28 Recessed Sprinkler Types
Standard Pendent
Listing & Approvals
1. Underwriters Laboratories Inc. and Certified for
Canada (cULus).
2. Factory Mutual Approvals (FM)
3. Loss Prevention Council (LPCB, UK)
4. VdS Schadenverhütung GmbH
UL Listing Category Sprinklers, Automatic & Open (VNIV) Quick Response Sprinkler
Product Description Reliable Models F1FR56, F1FR42, F1FRXLH & F1FR28
Series Sprinklers are quick response sprinklers which combine the durability of a standard sprinkler with the attractive low profile of a decorative sprinkler.
The Models F1FR56, F1FR42, F1FRXLH & F1FR28 Series Recessed automatic sprinklers utilize a 3.0 mm frangible glass bulb. These sprinklers have demonstrat-ed response times in laboratory tests which are five to ten times faster than standard response sprinklers. This quick response enables the Model F1FR56, F1FR42, F1FRXLH & F1FR28 Series sprinklers to apply water to a fire much faster than standard sprinklers of the same temperature rating.
The glass bulb consists of an accurately controlled amount of special fluid hermetically sealed inside a pre-cisely manufactured glass capsule. This glass bulb is specially constructed to provide fast thermal response.
Pendent Conventional
Recessed Pendent/F1/F2
Upright
Vertical Sidewall Horizontal Sidewall
Recessed Horizontal Sidewall
Recessed Pendent/FP
Concealed Pendent
XLH Upright XLH Pendent XLH Recessed Pendent F1/F2
XLH Recessed Pendent FP
At normal temperatures, the glass bulb contains the fluid in both the liquid and vapor phases. The vapor phase can be seen as a small bub-ble. As heat is applied, the liquid expands, forcing the bubble smaller and smaller as the liquid pressure increases. Continued heating forces the liquid to push out against the bulb, causing the glass to shatter, opening the waterway and allowing the deflec-tor to distribute the discharging water.
2.
Technical data:
Models Discharge Coeffi cient Response Thread
Size
Max.
Working Pressure
Min.
Working Pressure
Temperature Rating
Finish
F1FR56 K 5.6
Quick Response
1/2” NPT
(R1/2) 175 PSI 7 PSI
See “Temperature Ratings” Table.
See “Finish Table”
F1FR42
F1FRXLH K 4.2
F1FR28 K 2.8
Material Data:
Frame Defl ector Load Screw Pintle Cup Washer Bulb
DZR Brass QM Brass
CDA Alloy 260, CDA Alloy 220 or CDA Alloy510
CDA Alloy 360 or
CDA Alloy 544
CDA Alloy 360 or
CDA Alloy 544
CDA Alloy 651 or
CDA Alloy 693
Nickel Alloy 440 or Alloy 360 coated with PTFE Adhesive
Tape Glass
Application Quick response sprinklers are used in fixed fire protection systems: Wet, Dry, Deluge or Preaction. Care must be exercised that the orifice size, temperature rating, deflector style and sprinkler type are in accordance with the latest published standards of the National Fire Protection Association or the approving Authority Having Jurisdiction. Quick response sprinklers are intended for installation as specified in NFPA 13. Quick response sprinklers and standard re-sponse sprinklers should not be intermixed.
Model F1FR42, F1FRXLH Upright
Pendent ConventionalUpright
Model F1FR56, F1FRXLH & F1FR28 F1 or F2
Model F1FR56, Upright, Pendent & Conventional Sprinklers Model F1FR42, F1FRXLH & F1FR28 Upright & Pendent Sprinklers Installation Wrench: Model D Sprinkler Wrench Installation Data:
Nominal Orifi ce
Thread Nominal K Factor Sprinkler Approval Sprinkler Identifi cation Number
(SIN)
Size US Metric Height Organization Upright Pendent
Standard-Upright (SSU) and pendent Deflectors Marked to Indicate Position
1/2” (15mm) (1) 1/2” NPT (R1/2) 5.6 80 2.25” (57mm) 1,2,3,4 RA1425(1)(2)(3) RA1414(1)(2)(3)
7/16” (10mm) 1/2” NPT (R1/2) 4.2 60 2.25” (57mm) 1 RA1423(1) RA1413
3/8” (10mm) 1/2” NPT (R1/2) 2.8 40 2.25” (57mm) 1 RA1421(1) RA1411 Conventional-Install in Upright or Pendent Position
15mm (1) 1/2” NPT (R1/2) 5.6 80 57mm 3, 4 RA1475(3)
(1) cULus listed corrosion resistant (Polyester coated) sprinkler.
(2) Polyester coated FM approved sprinkler.
(3) Polyester coated LPCB & VdS approved sprinkler RA1425, RA1414 & RA1475.
Model F1FR56, F1FRXLH & F1FR28 FP
Model F1FR56, F1FR42, F1FRXLH & F1FR28 Quick Response Recessed Pendent Sprinkler(1)
Installation Wrench: Model GFR2 Sprinkler Wrench Installation Data:
Nominal Orifi ce
Thread Size
K Factor Sprinkler Height
Sprinkler Identifi cation Number (SIN)US Metric
1/2” (15mm) 1/2” NPT(R½) 5.6 80 2.25” (57mm) RA1414
7/16” (10mm) 1/2” NPT (R1/2) 4.2 60 2.25” (57mm) RA1413
3/8” (10mm) 1/2” NPT (R1/2) 2.8 40 2.25” (57mm) RA1411
(1) Refer to escutcheon data table for approvals & dimensions
3.
4.
Model F1FR56 Quick Response Vertical Sidewall Sprinkler Installation Wrench: Model D Sprinkler Wrench Installation Position: Upright or Pendent Approval Type: Light Hazard Occupancy Installation Data:
Nominal Orifi ce
Thread Size Nominal K Factor
Sprinkler Height
Approval Organizations
Sprinkler Identifi cation
Numbers (SIN)US Metric
½” (15mm) ½” NPT (R1/2) 5.6 8.0 2.25” (57mm) 1,2,3,4
RA1485(2)
15mm ½” NPT (R1/2) 5.6 8.0 2.25” (57mm) 4(1)
(1) LPC Approval is for pendent position only.
(2) cULus Listed corrosion resistant (Polyester coated) sprinkler.
Sprinkler Type Defl ector to Ceiling Distance (Min. - Max.)
Upright 4” (102mm) - 12” (305mm)
Pendent 4” (102mm) - 12” (305mm)
Model F1FR56 Quick Response Horizontal Sidewall Sprinkler Defl ector: HSW Installation Wrench: Model D Sprinkler Wrench Installation Data: Horizontal Sidewall
Nominal Orifi ce Thread Size Nominal K Factor
Sprinkler Height
Approval Organizations and Type of Approval Sprinkler
Identifi cation Numbers (SIN)US Metric Light Hazard
Ordinary Hazard
½” (15mm) ½” NPT (R1/2) 5.6 80 2.63” (67mm) 1,2 1 RA1435(1)(2)
(1) cULus Listed corrosion resistant (Polyester coated) sprinkler.
(2) Polyester coated FM approved sprinkler.
Horizontal Sidewall
Vertical Sidewall
Note: For Recessed HSW Sprinklers use installation wrench GFR2.
Model F1FR56 Quick Response Concealed Pendent Sprinklers Installation Wrench: Model RC1 Sprinkler Wrench Technical Data:
Nominal Orifi ce
“K” Factor Thread
Size Model
Temp. Rating Max.
Ambient
Temp
Bulb Color
Approvals Sprinkler
Identifi cation Number(SIN)US Metric Sprinkler Cover
½” (15mm) 5.6 80 ½” NPT F1FR 135°F/57°C 135°F/57°C 100°F/38°C Orange 1 RA1414
½” (15mm) 5.6 80 ½” NPT F1FR 155°F/68°C 135°F/57°C 100°F/38°C Red 1, 4(1) RA1414
½” (15mm) 5.6 80 ½” NPT F1FR 175°F/79°C 165°F/74°C 100°F/38°C Yellow 1 RA1414
½” (15mm) 5.6 80 ½” NPT F1FR 200°F/93°C 165°F/74°C 150°F/65°C Green 1 RA1414
(1) For VdS only = 155°F/68°C Norbulb and 1/2” [12,7mm] adjustment.
Figure 1 Figure 2
Installation Aid A protective cap is included for use during installation.
Important: The F1FR56 Sprinkler with Model CCP cover plate is not an FM Approved combination.
Installation
Quick response sprinklers are intended for installation as specified in NFPA 13. Quick response sprinklers and standard response sprinklers should not be intermixed.
The Model F1FR56, F1FR42, F1FRXLH & F1FR28 Recessed Quick Response Sprinklers are to be installed as shown. The Model F1 or F2 Escutcheons illustrated are the only recessed escutcheons to be used with the Model F1FR56, F1FR42, F1FRXLH & F1FR28 Sprinklers. The use of any other recessed escutcheon will void all approvals and negate all warranties.
When installing Model F1FR56, F1FR42, F1FRXLH & F1FR28 Sprinklers, use the Model D Sprinkler Wrench. Use the Mod-el GFR2 Wrench for installing F1FR56, F1FR42, F1FRXLH & F1FR28 Recessed Pendent Sprinklers. Any other type of wrench may damage these sprinklers.
NOTE: A leak tight ½” NPT (R1/2) sprinkler joint can be ob-tained with a torque of 8-18 ft-lbs (10,8 - 24,4 N-m). Do not tighten sprinklers over maximum recommended torque. It may cause leakage or impairment of the sprinklers.
The Model F1FR56/ CCP Concealed Sprinkler uses the ½” ori-fice, ½” NPT (R1/2), 135°F (57°C), 155°F (68°C), 175°F (79°C) or 200°F (93°C) Model F1FR56 Pendent Sprinkler with a threaded Model CCP cup which is factory attached to the sprinkler. The assembly is completed by the installation of the attractive, low profile, 135°F (57°C) or 165°F (74°C) rated Model CCP push on cover plate assembly. The cover plate and sprinkler cup as-semblies are joined using a cover plate skirt with flexible tabs for threaded engagement. A choice of two cover plate assemblies provide either ½” (13mm) or 5/16” (8mm) of cover adjustment.
Do not install these sprinklers in ceiling which have positive pressure in the space above.
After a 25/8” (67mm) diameter hole is cut in the ceiling, the sprinkler is easily installed with the Model RC1 Wrench. A Tef-lon* based thread sealant should be applied to the sprinkler threads only. The Model RC1 Wrench is then used to engage the sprinkler wrenching surfaces and to install the sprinkler in the fitting. When inserting or removing the wrench from the sprin-kler/cup assembly, care should be taken to prevent damage to the sprinkler. DO NOT WRENCH ON ANY OTHER PART OF THE SPRINKLER. The cover plate is then pushed onto the cup.
Final adjustment is made by hand turning the cover plate until the skirt flange makes full contact with the ceiling. Cover plate removal requires turning in the counter clockwise direction.
5.
*DuPont Registered Trade Mark
The Reliable Automatic Sprinkler Co., Inc.
(800) 431-1588 Sales Offices
(800) 848-6051 Sales Fax
(914) 829-2042 Corporate Offices www.reliablesprinkler.com Internet Address
Manufactured by Recycled
Paper
Revision lines indicate updated or new data.
EG. Printed in U.S.A. 07/12 P/N 9999970300
The equipment presented in this bulletin is to be installed in accordance with the latest published Standards of the National Fire Protection Association, Factory Mutual Research Corporation, or other similar organizations and also with the provisions of governmental codes or ordinances whenever applicable.
Products manufactured and distributed by Reliable have been protecting life and property for over 90 years, and are installed and serviced by the most highly qualified and reputable sprinkler contractors located throughout the United States, Canada and foreign countries.
After installation, inspect all sprinklers to ensure that there is a gap between the cover plate and ceiling and that the four cup slots are open and free from any air flow impediment to the space above.
Concealed cover plate/cup assemblies are listed only for use with specific sprinklers. The use of any other concealed cover plate/cup assembly with the Model F1FR56 Pendent Sprinkler or the use of the Model CCP Concealed cover plate assembly on any sprinkler with which it is not specifically listed my prevent good fire protection and will void all guarantees, warranties, listings and approvals.
Glass bulb sprinklers have orange bulb protectors to minimize bulb damage during shipping, handling and installation. REMOVE
THIS PROTECTION AT THE TIME THE SPRINKLER SYSTEM IS
PLACED IN SERVICE FOR FIRE PROTECTION. Removal of the protectors before this time may leave the bulb vulnerable to dam-age. RASCO wrenches are designed to install sprinklers when covers are in place. REMOVE PROTECTORS BY UNDOING THE
CLASP BY HAND. DO NOT USE TOOLS TO REMOVE THE PRO-
TECTORS.
Temperature Ratings
Classifi cation Sprinkler
Temperature Max. Ambient
Temp.
Bulb Color
°C °F Ordinary Ordinary
Intermediate Intermediate
High (1)
100°F (38°C) 100°F (38°C) 150°F (66°C) 150°F (66°C)
225°F (107°C)
Orange Red
Yellow Green Blue
(1) Not available for recessed sprinklers.
Escutcheon Data (1)
(1) SIN RA1435 – cULus permits use with F1, F2 or FP escutcheons for “light hazard” only, while FM limits use for same hazard with F2 escutcheon only.
Maintenance The Model F1FR56, F1FR42, F1FRXLH and Model F1FR56, F1FR42, F1FRXLH & F1FR28 Recessed Sprinklers should be in-spected quarterly and the sprinkler system maintained in accor-dance with NFPA 25. Do not clean sprinklers with soap and water, ammonia or any other cleaning fluids. Remove dust by using a soft brush or gentle vacuuming. Remove any sprinkler which has been painted (other than factory applied) or damaged in any way. A stock of spare sprinklers should be maintained to allow quick replace-ment of damaged or operated sprinklers. Prior to installation, sprin-klers should be maintained in the original cartons and packaging to minimize the potential for damage to sprinklers that would cause improper operation or non-operation.
Sprinkler Types Standard Upright Standard Pendent Conventional Recessed Pendent Vertical Sidewall Horizontal Sidewall Recessed Horizontal sidewall Concealed pendent Maximum Working Pressure 175 psi (12 bar) 100% Factory tested hydrostatically to 500 psi (34.5 bar) Finishes (1)
Standard Finishes Sprinkler Escutcheon Cover plate(1)
Bronze Chrome Plated Polyester Coated (4)(5)(6)
Brass Chrome Plated White Painted
Chrome White
Special Application Finishes Sprinkler Escutcheon Cover plate(1)
Bright Brass (3)
Black Plated Black Paint (2)(6)
Off White (2)(6)
Satin Chrome
Bright Brass Black Plated Black Paint Off White Satin Chrome
Bright Brass Satin Off White Black Paint Black Plated
(1) Other finishes and colors are available on special order. Consult the factory for details. Custom color painted sprinklers may not retain their UL Corrosion resistance listing. Coverplate custom paint is semi-gloss, unless specified otherwise.
(2) cULus Listed only.
(3) 200°F (93°C) maximum.
(4) cULus listed “corrosion resistance” applies to SIN Numbers RA1435 (HSW), RA1485(VSW), RA1425 (Upright) and RA1414 (Pendent) in standard black or white. Corrosion resistance in other polyester colors is available upon request.
(5) FM Approvals finish as “Polyester coated” applies to SIN Number RA1414 (Pendent) in standard black or white.
(6) LPCB and VdS Approved finish applies only to RA1425, RA1414 and RA1475.
Ordering Information Specify:
1. Sprinkler Model
2. Sprinkler Type
3. Orifice Size
4. Deflector Type
5. Temperature Rating
6. Sprinkler Finish
7. Escutcheon Type
8. Escutcheon Finish (where applicable)
9. Cover plate Model
10. Cover plate Thread size
11. Cover plate Temperature
12. Cover plate Adjustment
13. Cover plate Finish
Note: When Model F1FR56 Recessed sprinklers are ordered, the sprinklers and escutcheons are packaged separately.
FORGED STEEL FITTINGS
www.anvilintl.com90
PF-11.13
Standards and Specifications
Dimensions Material Thread Pressure Rating
FORGED STEEL THREADED FITTINGS
Class 2000, 3000, 6000 ASTM Al05, ASTM A182, ASTM A350 ASMEB1.20.1+
Forged Steel Fittings
In accordance with ASME standard B16.11 - “Forged Fittings, Socket-Welding and Threaded” this table shows the schedule of pipe corresponding to each class of fitting for rating purposes.
PRESSURE RATINGS
Class Schedule
N.P.T. S.W.
2000 80 –
3000 160 80
6000 XXS/XXH 160
Materials The steel for Anvil Forged Carbon Steel Fittings consists of forging, bars, seamless pipe or tubes which conform to the requirements for melting process, chemical composition and mechanical properties of ASTM A105.
Design Basis ASME B16.11 - Forged fittings, socket-weld and threaded
Dimensions ASME B16.11, unless otherwise noted
Threads ANSI/ASME B1.20.1 NPT Threads
CROSS
11⁄2 x 3⁄4 x 11⁄4 x 1⁄2
11⁄4
Side
Outlet 1⁄2
3⁄4
11⁄2
Branch
R u n
TEE
11⁄2 x 3⁄4 x 11⁄4
3⁄4
11⁄4
11⁄2
CROSS
38 x 19 x 32 x 13 mm
Side
Outlet
Branch
R u n
TEE
38 x 19 x 32 mm
Reducing Fittings Reducing elbows, tees and crosses are available in both threaded and socket-welding.
On reducing tees and crosses give the size of the largest run opening; then give the opposite opening. On a tee give the branch size last. On a cross give the largest side outlet third and the opposite opening last.
ASME B16.11 provides that the maximum allowable pressure of a fitting be computed in accordance with the applicable piping code or regulation for straight seamless pipe or for material of equivalent composition and mechanical properties to the fitting.
Any corrosion or mechanical allowances and any reduction in allowable stress due to temperature or other service conditions must be applied to the pipe and fitting alike.
Material Specifications:
Fitting:
Ductile iron conforming to ASTM A-536, grade
65-45-12.
Fitting Coating:
Orange enamel
Red enamel in Europe, Middle East, Africa, and
India
Optional: Hot dipped galvanized
Approvals/Listings:
Product Description:
FireLock® products comprise a unique system specifically designed for fire protection services.
FireLock full-flow elbows and tees feature CAD-developed, hydrodynamic design, affording a shorter center-to-end dimension than standard fittings. A noticeable bulge allows the water to make a smoother turn to maintain similar flow characteristics as standard full flow fittings.
FireLock fittings are designed for use exclusively with
Victaulic couplings that have been Listed or Approved for Fire Protection Services. Use of other couplings or flange adapters may result in bolt pad interference.
Refer to the appropriate listing agency or approval body for pressure ratings. Pressure ratings vary by agency.
FireLock® Fittings
10.03 victaulic.com | FireLock® Fittings | Publication 10.03
10.03 1539 Rev M Updated 12/2014 © 2014 Victaulic Company. All rights reserved.
Job/Owner
System No.
Location
Contractor
Submitted By
Date
Engineer
Spec Section
Paragraph
Approved
Date
Dimensions:
NO. 001
C to E
NO. 003 NO. 002 No. 006
Nominal Size
Actual Outside Diameter
No. 001 90° Elbow
No. 003 45° Elbow
No. 002 Straight Tee
No. 006 Cap
C to E
Approx.
Weight Each C to E
Approx.
Weight Each C to E
Approx.
Weight Each C to E
Approx.
Weight Each inches mm inches mm inches mm
Lbs.
kg inches mm
Lbs.
kg inches mm
Lbs.
kg inches mm
Lbs.
kg
1 ¼ 1.660 — — — — — — 0.82 0.3 32 42.4 21 0.1 1 ½ 1.900 — — — — — — 0.82 0.4 40 48.3 — — — — — — 21 0.2 2 2.375 2.75 1.7 2.00 1.8 2.75 2.4 0.88 0.6
50 60.3 70 0.8 51 0.8 70 1.1 22 0.3 2 ½ 2.875 3.00 3.1 2.25 2.2 3.00 3.6 0.88 1.0 65 73.0 76 1.4 57 1.0 76 1.6 22 0.5
76.1 mm 3.000 3.00 3.30 2.25 2.4 3.00 3.8 — —76.1 76 1.5 57 1.1 76.2 1.7 3 3.500 3.38 4.0 2.50 3.1 3.38 5.3 0.88 1.2
80 88.9 86 1.8 64 1.4 86 2.4 22 0.5
108 mm 4.250 4.00 5.7 3.00 5.1 4.00 7.5 — —108.0 102 2.6 76 2.3 102 3.4 4 4.500 4.00 6.7 3.00 5.6 4.00 8.7 1.00 2.4
100 114.3 102 3.0 76 2.5 102 3.9 25 1.1 5 5.563 4.88 12.6 3.25 8.3 4.88 15.7 1.00 4.1
125 141.3 124 5.7 83 3.8 124 7.1 25 1.9
139.7 mm 5.500 4.88 12.4 3.25 8.2 4.88 15.4 — —139.7 124.0 5.6 82.6 3.7 124.0 6.9
159 mm 6.250 5.50 12.6 3.50 9.2 5.50 17.9 — —158.8 140 5.7 89 4.2 140 8.0 6 6.625 5.50 18.3 3.50 11.7 5.50 22.7 1.00 5.9
150 168.3 140 8.3 89 5.3 140 10.3 25 2.7
165.1 mm 6.500 5.43 17.6 3.50 11.4 5.50 22.0 — —165.1 139.7 7.9 88.9 5.2 139.7 9.9 8 8.625 6.81 25.5 4.25 20.4 6.94 38.7 1.13 12.7
200 219.1 173 11.6 108 9.3 176 17.6 29 5.8
C to E
C to E
T
C to E
C to E victaulic.com | FireLock® Fittings | Publication 10.03
10.03 1539 Rev M Updated 12/2014 © 2014 Victaulic Company. All rights reserved.
victaulic.com
DIMENSIONS
Module Body Size Dimensions – Inches/mm Aprx. Weight
Each
Nominal Diameter
Inches/mm
Actual Outside
Diameter Inches/mm
Drain Size Inches/mm A B C D
E (Groove) F G Lbs./kgs
1 1/4
1.660 42.2
33.4
11.45 290.8
7.20 182.9
5.77 146.5
3.50 88.9
10.05 255.3
7.48 190.0
2.54 64.5
15.2 6.9
1 ½
1.900 48.3
33.4
11.45 290.8
7.32 185.9
5.77 146.5
3.50 88.9
10.05 255.3
7.48 190.0
2.54 64.5
15.5 7.0
2.375 60.3
33.4
11.45 290.8
7.55 191.8
5.77 146.5
3.50 88.9
10.05 255.3
7.48 190.0
2.54 64.5
19.9 9.0
2 ½
2.875 73.0
1 1/4
12.00
8.41
6.18
4.25
9.76
11.87
4.25
22.7 10.3
3.500 88.9
1 1/4
12.00
9.42
6.18
4.25
9.76
11.87
4.25
23.2 10.6
4.500 114.3
12.00
9.90
7.25
5.00
10.15
12.62
4.21
30.3 13.8
6.625 168.3
12.00
10.85
8.31
6.00
10.15
13.62
4.24 107.7
36.7 16.7
Nominal Size inches
Orifices
1.25 K5.6
1.5 K5.6
2 K5.6
2.5 K5.6 K6.9 K8.0 K11.2
3 K5.6 K6.9 K8.0 K11.2
4 K5.6 K6.9 K8.0 K11.2 K14.0 K16.8
6 K5.6 K6.9 K8.0 K11.2 K14.0 K16.8
Nominal Size inches Drain Type Drain Size
1.25 NPT 1"
1.5 NPT 1"
2 NPT 1"
2.5 Grooved 1 1/4"
3 Grooved 1 1/4" 4 Grooved 2" 6 Grooved 2"
Designed for NFPA 13 commercial requirements, the Victaulic Series 747M Zone Control Riser Module features a cast body, and is compact and easy to install in zoned wet sprinkler systems.
The integrated module body consists of a shut off valve, test and drain valve combination and different orifice sizes (K factors), a UL Listed and FM Approved Flow Switch, and a Pressure Gauge. The Series 747M FireLock Zone Control Riser Module is available in sizes from 1 ¼ through 6"/32 mm – 150 mm with grooved ends on the main pipe for installation in the horizontal or vertical up-flow positions with UL Listed, FM Approved Victaulic grooved couplings. 1 1/4 - 2" modules have an NPT drain port. 2 ½ - 6" modules have a grooved drain port.
The Series 747M FireLock Zone Control Riser Module is FM Approved and UL and ULC Listed for working pressures up to 365psi/2517 kPa. An optional pressure relief valve kit is available for all sizes. The Pressure Relief Valve is FM Approved and UL and ULC Listed for working pressures up to 175psi/1200kPa.
10.96_1
FireLock® Zone Control Riser Module
SERIES 747M
10.96IPS CARBON STEEL PIPE – FIRE PROTECTION PRODUCTS
STYLE 747M
PATENT PENDING
JOB/OWNER CONTRACTOR ENGINEER
System No. ______________________________ Submitted By ____________________________ Spec Sect _______________ Para ___________
Location ________________________________ Date ___________________________________ Approved _______________________________
Date ___________________________________ www.victaulic.com VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY. © 2010 VICTAULIC COMPANY. ALL RIGHTS RESERVED.
REV_I
SEE VICTAULIC PUBLICATION 10.01 FOR DETAILS
2 1/2 – 6"/65.0 – 150 mm Nominal Sizes
Hose Clamp
Barbed Fitting Pressure Relief Valve
Drain TubingClose Nipple
Elbow
Hose Clamp
Barbed Fitting
Optional Pressure Relief Valve Kit Detail
(Valves shown above in the “test” position.
Shown with optional Pressure Relief Valve Kit installed)
1 ¼ – 2"/32 – 50 mm Nominal Sizes
E
A
D
G
C
B
F
B
C
E
A
D G
F
MATERIAL SPECIFICATIONS Module Body: Cast from ductile iron conforming to ASTM A-536, grade 65-45-12 with integral Victaulic grooved ends. Finish: orange enamel.
Shut-off and Test/Drain Valve: Chrome plated brass ball, S 37700 brass clapper, 416SS or 410SS shafts, Delrin orifice, virgin Teflon*, enhanced Teflon and EPDM rubber seals.
*Teflon is a registered trademark of Dupont
Coupling: Any UL Listed, FM Approved Victaulic IPS-sized coupling may also be used. Note:
Couplings not included with product.
Waterflow Detector: System Sensor Model WFD/WFDTH vane type waterflow detector with sealed retard, visual switch activation, and mechanical delay adjustment. Cover includes tamper resistant security screws and tool. Note: ULC models WFDA /WFDTHA include cover tamper switch.
10.96
FireLock® Zone Control Riser Module
SERIES 747M
10.96FIRE PROTECTION PRODUCTS – DEVICES
For complete contact information, visit www.victaulic.com
10.96 3089 REV I UPDATED 7/2010
VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY. © 2010 VICTAULIC COMPANY. ALL RIGHTS RESERVED.
WARNING
�•� This�product�must�be�installed�by�an�experienced,�trained�installer,� in accordance with the instructions provided with each valve. These instructions contain important information.
Failure�to�follow�these�instructions�may�result�in�serious�personal�injury,� property�damage,�or�valve�leakage.
If you need additional copies of this product literature or the valve installation�instructions,�or�if�you�have�any�questions�about�the�safe� installation�and�use�of�this�device,�contact�Victaulic�Company,�P.O.� Box�31,�Easton,�PA�18044-0031�USA,�Telephone:�001-610-559-3300.
WARNING
WARRANTY Refer to the Warranty section of the current Price List or contact Victaulic for details.
This product shall be manufactured by Victaulic or to Victaulic specifications. All products to be installed in accordance with current Victaulic installation/assembly instructions. Victaulic reserves the right to change product specifications, designs and standard equipment without notice and without incurring obligations.
NOTE
FIRE DEPT. INLET CONN. EXPOSED TYPE 6405-6425 SERIES
Page 6-15
SINGLE CLAPPER TWO-WAY INLETS
4 x 2 1/2 x 2 1/2
An exposed auxiliary inlet connection with 500 G.P.M. inlet capacity to supplement fire protection water supply. Exposed design provides an economical method of satisfying Fire Dept.
inlet requirements.
STANDARD EQUIPMENT: Cast brass two-way inlet body only with single swing clapper and pin lug swivel back or angle outlet connection as selected by figure number.
SPECIFY THREAD.
"Auto Spkr."BRANDING: FINISH: Cast Brass
OPTIONAL FINISHES:
PB - Polished Brass RC - Rough Chrome Plated PC - Polished Chrome Plated
*U/L LISTED
Model C
6 1/2
Outlet Dimensions
Style A B
6405 Back 5 1/4 8 5/64
6407 Angle 6 5/16 7 11/16 4 3/4
DOUBLE CLAPPER TWO-WAY INLETS
An exposed auxiliary inlet connection with 500 G.P.M. Inlet capacity to supplement fire protection water supply. Exposed design provides an economical method of satisfying Fire Department Inlet requirements.
STANDARD EQUIPMENT: Cast brass two-way inlet body only with double drop clappers and pin lug swivels; back or angle outlet connection as selected by figure number. Branding as selected. SPECIFY THREAD AND BRANDING.
BRANDING: "Standpipe", "Auto Spkr."
FINISH: Cast Brass
OPTIONAL FINISHES:
PB - Polished Brass RC - Rough Chrome Plated
PC - Polished Chrome Plated
*U/L LISTED
NY BSA-MEA APPROVED
6407 Angle Outlet
6420 Angle Outlet
Outlet Style Dimensions
Back Angle Size B C DA E
*6410 4 X 2 1/2 X 2 1/2 9 5/8 12 1/4
6420 4 X 2 1/2 X 2 1/2 11 3/4 9 5/8 7 1/4
6412 6 X 2 1/2 X 2 1/2 10 1/4 11 3/4
6422 6 X 2 1/2 X 2 1/2 12 1/2 10 1/8 7 1/2
6413 4 X 3 X 3 10 12 1/2
6423 4 X 3 X 3 12 1/2 10 1/8 7 1/2
6414 5 X 3 X 3 10 1/8 12 1/2
6424 5 X 3 X 3 12 1/4 10 1/2 7 1/2
6415 6 X 3 X 3 10 3/8 12 1/2
6425 6 X 3 X 3 12 1/4 10 7/8 7 1/4
Figure No. 6410-6415
Figure No. 6420-6425
6410 Back Outlet
Figure No. 6405
Figure No. 6407
6405 Back Outlet
Hydraulic Overview Job Number: 1
Report Description: Ordinary Group II (One)
Node Flow(gpm) Hose Flow(gpm) Static(psi) Residual(psi)Name
1 530.60 100.00 52.000 10.000Water Supply
Identifier Pressure(psi) K-Factor(K) Flow(gpm)
Job
System
Supplies Check Point Gauges
1 Mike Moken
Dakota Plains Kyle Clinic Health Ctr
FIRE SPRINKLER PROTECTION LAYOUT
1000 Health Ctr Rd
605-593-4917
Kyle Clinic.1
BIA
2017 Expansion
Job Name:
Address 1
Address 2
Design Engineer
Phone FAX
State Certification/License Number
AHJ
Job Site/Building
Most Demanding Sprinkler Data
Coverage Per Sprinkler
Total Demand
Area of Application
Hose Streams
Number Of Sprinklers Calculated
Pressure Result
Job Number
286.14 @ 30.552
Water Supply at Node 1 (530.60, 0.00, 52.000, 10.000)
0.200gpm/ft²
5.6 K-Factor 18.53 at 10.946
92.64ft²
986.62ft² (Actual 986.62ft²)
100.00
Density
+8.048 (20.9%)
Address 3
Kyle, SD 57752
System Pressure Demand System Flow Demand
30.552 186.14
© M.E.P.CAD, Inc. 12/19/2017 Page 1AutoSPRINK® 12 v12.0.61.0 10:04:40AM
Hydraulic Summary
Job Number: 1
Node Flow(gpm)
Total Hose Streams
100.00
Safety MarginRequiredAvailable
Node
Hose Flow Static Residual Flow Total Demand
(gpm) (psi) (psi) (gpm) (psi) (gpm) (psi) (psi)
Name
1 38.600 30.552 8.048530.60100.00 10.00052.000 286.14Water Supply
Design EngineerJob Number
Total Water Required (Including Hose Allowance)
286.14
Maximum Pressure Unbalance In Loops
0.000
Additional Hose Supplies
100.00
Hose Allowance At Source
Supplies
1871.06gal
Ordinary Group II
0.200gpm/ft²
92.64ft²
986.62ft² (Actual 986.62ft²)
Occupancy
Area of Application
Coverage Per SprinklerNumber Of Sprinklers Calculated
Density
Job Suffix
AutoPeak Results: Pressure For Remote Area(s) Adjacent To Most Remote Area
Left: 30.589
Volume capacity of Dry PipesVolume capacity of Wet Pipes
4.27 between nodes 5 and 638 Maximum Velocity Under Ground
8.00 between nodes 752 and 753 Maximum Velocity Above Ground
5.6 K-Factor 18.53 at 10.946
Most Demanding Sprinkler Data
System
2017 Expansion1000 Health Ctr Rd Job Site/Building
BIAFIRE SPRINKLER PROTECTION LAYOUT
AHJ
Dakota Plains Kyle Clinic Health Ctr
Job
State Certification/License NumberJob Name:
Mike Moken1
Contractor
Contractor Number
RFP
Name of Contractor:
RAPID FIRE PROTECTION
Address 1
1530 SAMCO ROAD
Address 2
RAPID CITY, SD 57702
Contact Name Contact Title
PM
ExtensionPhone
605.348.2342
FAX
Mmoken@rapidfireinc.com
Web-Site www.rapidfireinc.com
Mike Moken
Address 3
Address 1
Address 2
Drawing Name
Kyle Clinic.1
System Flow Demand
186.14
Remote Area(s)
Address 3
Kyle, SD 57752
12/19/2017© M.E.P.CAD, Inc. Page 2AutoSPRINK® 12 v12.0.61.0 10:04:41AM
Hydraulic Graph
Job Number: 1
10.000 @ 530.60
Residual: Pressure
52.000
Static: Pressure
Water Supply at Node 1
Hydraulic Graph
Water Supply at Node 1
30.552 @ 186.14
30.552 @ 286.14
Available Pressure at Time of Test Date of Test Time of Test
12/14/17 9:45
Test Conducted By Test Witnessed By
Rapid Fire Protection MM GG
Southside of Hosp Location
38.600 @ 286.14
System Demand
System Demand (Including Hose Allowance at Source)
© M.E.P.CAD, Inc. 12/19/2017 Page 3AutoSPRINK® 12 v12.0.61.0 10:04:42AM
Device (gpm)
Actual Flow Minimum Flow
(gpm) (K)
K-Factor
(psi)
Pressure
Summary Of Outflowing Devices Report Description: Ordinary Group II (One)
Job Number: 1
Sprinkler 1013 18.71 18.53 5.6 11.161
Sprinkler 1014 18.63 18.53 5.6 11.071
Sprinkler 1015 18.62 18.53 5.6 11.062
Sprinkler 1016 18.63 18.53 5.6 11.071
Sprinkler 1017 18.68 18.53 5.6 11.124
Sprinkler 1026 18.64 18.53 5.6 11.081
Sprinkler 1029 18.53 18.53 5.6 10.949
Sprinkler 1030 18.53 18.53 5.6 10.946
Sprinkler 1031 18.54 18.53 5.6 10.966
Most Demanding Sprinkler Data
© M.E.P.CAD, Inc. 12/19/2017 Page 4AutoSPRINK® 12 v12.0.61.0 10:04:43AM
FittingsNode Elevation(Foot) Pressure(psi) Discharge(gpm)
Node Analysis Report Description: Ordinary Group II (One)
Job Number: 1
1 -4'-0 S 30.552 186.14
1013 13'-0 Spr(-11.161) 11.161 18.71
1014 13'-0 Spr(-11.071) 11.071 18.63
1015 13'-0 Spr(-11.062) 11.062 18.62
1016 13'-0 Spr(-11.071) 11.071 18.63
1017 13'-0 Spr(-11.124) 11.124 18.68
1026 13'-0 Spr(-11.081) 11.081 18.64
1029 13'-0 Spr(-10.949) 10.949 18.53
1030 13'-0 Spr(-10.946) 10.946 18.53
1031 13'-0 Spr(-10.966) 10.966 18.54
1032 13'-0 Spr(-11.059) 11.059 18.62
5 -4'-0 T(33'-5½) 28.638
590 11'-11 PO(10'-0) 16.885
591 13'-0 E(5'-0) 16.158
626 12'-0 PO(10'-0) 11.941
627 13'-0 T(10'-0) 11.762
638 2'-6 BFP(-4.000) 25.140
640 4'-4 fT(20'-0) 20.346
645 5'-9 19.722
647 11'-11 T(20'-0) 16.903
668 11'-11 PO(10'-0) 16.791
669 13'-0 E(5'-0) 16.091
671 12'-0 PO(10'-0) 11.919
672 13'-0 T(10'-0) 11.714
744 12'-0 PO(10'-0) 11.834
745 13'-0 T(10'-0) 11.179
751 13'-0 T(10'-0) 13.273
752 11'-11 PO(10'-0) 16.767
753 13'-0 E(5'-0) 15.571
770 12'-0 PO(10'-0) 11.811
© M.E.P.CAD, Inc. 12/19/2017 Page 5AutoSPRINK® 12 v12.0.61.0 10:04:44AM
Pipe Type Diameter Flow Velocity Friction Loss Length Pressure
Downstream Elevation Discharge K-Factor Pt Pn Fittings Eq. Length Summary
Upstream Total Length
HWC
Hydraulic Analysis Job Number: 1
Report Description: Ordinary Group II (One)
• • • • • Route 1 • • • • •
Pf
Pe
Pv
BL 2.1230 14.04 1.27 0.002182 9'-0 0.020
1030 13'-0 18.53 5.6 10.946
1031 13'-0 10.966 9'-0
Sprinkler
Pf
Pe
Pv
BL 2.1230 32.58 2.95 0.010362 4'-4 0.148
1031 13'-0 18.54 5.6 10.966 10'-0
771 13'-0 11.115 14'-4
Sprinkler, T(10'-0)
Pf
Pe
Pv
RN 2.1230 51.21 4.64 0.023914 1'-0 0.263
771 13'-0 18.62 11.115 10'-0 0.434
770 12'-0 11.811 11'-0
Flow (q) from Route 3
PO(10'-0)
Pf
Pe
Pv
CM 3.3340 51.21 1.88 0.002655 8'-9½ 0.023
770 12'-0 11.811
744 12'-0 11.834 8'-9½
Pf
Pe
Pv
CM 3.3340 97.87 3.60 0.008800 9'-7 0.084
744 12'-0 46.66 11.834
671 12'-0 11.919 9'-7
Flow (q) from Route 5
Pf
Pe
Pv
CM 3.3340 50.38 1.85 0.002576 8'-5½ 0.022
671 12'-0 11.919
626 12'-0 11.941 8'-5½
Pf
Pe
Pv
RN 2.1230 50.38 4.57 0.023206 1'-0 0.255
626 12'-0 11.941 10'-0 -0.434
627 13'-0 11.762 11'-0
PO(10'-0)
Pf
Pe
Pv
BL 2.1230 50.38 4.57 0.023206 154'-5 4.396
627 13'-0 11.762 35'-0
591 13'-0 16.158 189'-5
T(10'-0)
5E(5'-0)
Pf
Pe
Pv
RN 2.1230 50.38 4.57 0.023206 1'-1 0.257
591 13'-0 16.158 10'-0 0.470
590 11'-11 16.885 11'-1
PO(10'-0)
Pf
Pe
Pv
FR 4.3100 50.38 1.11 0.000738 4'-3 0.018
590 11'-11 16.885 20'-0
647 11'-11 16.903 24'-3
T(20'-0)
Pf
Pe
Pv
FR 4.3100 186.14 4.09 0.008279 7'-7 0.145
647 11'-11 135.76 16.903 10'-0 2.674
645 5'-9 19.722 17'-7
Flow (q) from Route 2
E(10'-0)
Pf
Pe
Pv
MS 4.2600 186.14 4.19 0.008763 1'-1 0.009
645 5'-9 19.722 0.614
640 4'-4 20.346 1'-1
2f(-0.000)
Pf
Pe
Pv
DY 4.3100 186.14 4.09 0.008279 0'-0 4.000
640 4'-4 20.346 0.795
638 2'-6 25.140 0'-0
BFP(-4.000)
Pf
Pe
Pv
UG 4.2200 186.14 4.27 0.006898 55'-0 0.679
638 2'-6 25.140 43'-6 2.818
5 -4'-0 28.638 98'-6
LtE(10'-0½), T(33'-5½)
Pf
Pe
Pv
UG 5.3490 186.14 2.66 0.001914 1000'-0 1.914
5 -4'-0 28.638
1 -4'-0 30.552 1000'-0
Water Supply
286.14
100.00 Hose Allowance At Source
• • • • • Route 2 • • • • •
Pf
Pe
Pv
BL 2.1230 4.49 0.41 0.000265 9'-8 0.003
1030 13'-0 18.53 5.6 10.946
1029 13'-0 10.949 9'-8
Sprinkler
Pf
Pe
Pv
BL 2.1230 23.02 2.09 0.005449 14'-2 0.132
1029 13'-0 18.53 5.6 10.949 10'-0
1026 13'-0 11.081 24'-2
Sprinkler, 2E(5'-0)
Pf
Pe
Pv
BL 2.1230 41.66 3.78 0.016327 99'-3½ 2.192
1026 13'-0 18.64 5.6 11.081 35'-0
751 13'-0 13.273 134'-3½
Sprinkler, 5E(5'-0), T(10'-0)
Pf
Pe
Pv
BL 2.1230 88.28 8.00 0.065500 30'-1 2.298
751 13'-0 46.62 13.273 5'-0
753 13'-0 15.571 35'-1
Flow (q) from Route 4
E(5'-0)
Pf
Pe
Pv
RN 2.1230 88.28 8.00 0.065500 1'-1 0.726
753 13'-0 15.571 10'-0 0.470
752 11'-11 16.767 11'-1
PO(10'-0)
Pf
Pe
Pv
FR 4.3100 88.28 1.94 0.002082 11'-10½ 0.025
752 11'-11 16.767
668 11'-11 16.791 11'-10½
Pf
Pe
Pv
FR 4.3100 135.76 2.99 0.004617 4'-2½ 0.112
668 11'-11 47.48 16.791 20'-0
647 11'-11 16.903 24'-2½
Flow (q) from Route 7
T(20'-0)
• • • • • Route 3 • • • • •
© M.E.P.CAD, Inc. 12/19/2017 Page 6AutoSPRINK® 12 v12.0.61.0 10:04:45AM
Upstream Total Length
HWC
Hydraulic Analysis Job Number: 1
Report Description: Ordinary Group II (One)
Pf
Pe
Pv
BL 2.1230 18.62 1.69 0.003681 5'-0 0.055
1032 13'-0 18.62 5.6 11.059 10'-0
771 13'-0 11.115 15'-0
Sprinkler, T(10'-0)
• • • • • Route 4 • • • • •
Pf
Pe
Pv
BL 2.1230 9.28 0.84 0.001014 9'-8 0.010
1015 13'-0 18.62 5.6 11.062
1014 13'-0 11.071 9'-8
Sprinkler
Pf
Pe
Pv
BL 2.1230 27.91 2.53 0.007781 11'-7 0.090
1014 13'-0 18.63 5.6 11.071
1013 13'-0 11.161 11'-7
Sprinkler
Pf
Pe
Pv
BL 2.1230 46.62 4.23 0.020102 90'-0½ 2.111
1013 13'-0 18.71 5.6 11.161 15'-0
751 13'-0 13.273 105'-0½
Sprinkler, E(5'-0), T(10'-0)
• • • • • Route 5 • • • • •
Pf
Pe
Pv
BL 2.1230 9.35 0.85 0.001029 9'-6 0.010
1015 13'-0 18.62 5.6 11.062
1016 13'-0 11.071 9'-6
Sprinkler
Pf
Pe
Pv
BL 2.1230 27.98 2.54 0.007819 3'-10 0.108
1016 13'-0 18.63 5.6 11.071 10'-0
745 13'-0 11.179 13'-10
Sprinkler, T(10'-0)
Pf
Pe
Pv
RN 2.1230 46.66 4.23 0.020135 1'-0 0.221
745 13'-0 18.68 11.179 10'-0 0.434
744 12'-0 11.834 11'-0
Flow (q) from Route 6
PO(10'-0)
• • • • • Route 6 • • • • •
Pf
Pe
Pv
BL 2.1230 18.68 1.69 0.003701 5'-0 0.056
1017 13'-0 18.68 5.6 11.124 10'-0
745 13'-0 11.179 15'-0
Sprinkler, T(10'-0)
• • • • • Route 7 • • • • •
Pf
Pe
Pv
RN 2.1230 47.48 4.30 0.020798 1'-0 0.229
671 12'-0 11.919 10'-0 -0.434
672 13'-0 11.714 11'-0
PO(10'-0)
Pf
Pe
Pv
BL 2.1230 47.48 4.30 0.020798 155'-5½ 4.377
672 13'-0 11.714 55'-0
669 13'-0 16.091 210'-5½
T(10'-0)
9E(5'-0)
Pf
Pe
Pv
RN 2.1230 47.48 4.30 0.020798 1'-1 0.231
669 13'-0 16.091 10'-0 0.470
668 11'-11 16.791 11'-1
PO(10'-0)
1.51
4.87
)( 150
1.33
1.16
0.713
Equivalent Pipe Lengths of Valves and Fittings (C=120 only)
Actual Inside Diameter
Schedule 40 Steel Pipe Inside Diameter = Factor
C Value Multiplier
Value Of C
Multiplying Factor
© M.E.P.CAD, Inc. 12/19/2017 Page 7AutoSPRINK® 12 v12.0.61.0 10:04:45AM
Upstream Total Length
HWC
Hydraulic Analysis Job Number: 1
Report Description: Ordinary Group II (One)
Pipe Type Legend
AO Arm-Over
BL Branch Line
CM Cross Main
DN Drain
DR Drop
DY Dynamic
FM Feed Main
FR Feed Riser
MS Miscellaneous
OR Outrigger
RN Riser Nipple
SP Sprig
ST Stand Pipe
UG Underground
Units Legend
Diameter Inch
Elevation Foot
Flow gpm
Discharge gpm
Velocity fps
Pressure psi
Length Foot
Friction Loss psi/Foot
HWC Hazen-Williams Constant
Pt Total pressure at a point in a pipe
Pn Normal pressure at a point in a pipe
Pf Pressure loss due to friction between points
Pe Pressure due to elevation difference between indicated points
Pv Velocity pressure at a point in a pipe
Fittings Legend
ALV Alarm Valve
AngV Angle Valve b Bushing
BalV Ball Valve
BFP Backflow Preventer
BV Butterfly Valve
C Cross Flow Turn 90° cplg Coupling
Cr Cross Run
CV Check Valve
DelV Deluge Valve
DPV Dry Pipe Valve
E 90° Elbow
EE 45° Elbow
Ee1 11¼° Elbow
Ee2 22½° Elbow f Flow Device fd Flex Drop
FDC Fire Department Connection fE 90° FireLock(TM) Elbow fEE 45° FireLock(TM) Elbow flg Flange
FN Floating Node fT FireLock(TM) Tee g Gauge
GloV Globe Valve
GV Gate Valve
Ho Hose
Hose Hose
HV Hose Valve
Hyd Hydrant
LtE Long Turn Elbow mecT Mechanical Tee
Noz Nozzle
P1 Pump In
P2 Pump Out
PIV Post Indicating Valve
PO Pipe Outlet
PRV Pressure Reducing Valve
PrV Pressure Relief Valve red Reducer/Adapter
S Supply sCV Swing Check Valve
Spr Sprinkler
St Strainer
T Tee Flow Turn 90°
Tr Tee Run
U Union
WirF Wirsbo
WMV Water Meter Valve
Z Cap
© M.E.P.CAD, Inc. 12/19/2017 Page 8AutoSPRINK® 12 v12.0.61.0 10:04:45AM
Flow Diagram (Top View)
Job Number: 1
© M.E.P.CAD, Inc. 12/19/2017 Page 9AutoSPRINK® 12 v12.0.61.0 10:04:47AM
Report Description: Ordinary Group II (two)
Node Flow(gpm) Hose Flow(gpm) Static(psi) Residual(psi)Name
1 530.60 52.000 10.000Water Supply
Identifier Pressure(psi) K-Factor(K) Flow(gpm)
Job
System
Supplies Check Point Gauges
1 Mike Moken
Dakota Plains Kyle Clinic Health Ctr
FIRE SPRINKLER PROTECTION LAYOUT
1000 Health Ctr Rd
605-593-4917
Kyle Clinic.1
BIA
2017 Expansion
Job Name:
Address 1
Address 2
Design Engineer
Phone FAX
State Certification/License Number
AHJ
Job Site/Building
Most Demanding Sprinkler Data
Coverage Per Sprinkler
Total Demand
Area of Application
Hose Streams
Number Of Sprinklers Calculated
Pressure Result
Job Number
197.59 @ 42.500
Water Supply at Node 1 (530.60, 0.00, 52.000, 10.000)
0.200gpm/ft²
5.6 K-Factor 24.08 at 18.495
120.42ft²
963.35ft² (Actual 963.35ft²)
0.00
Density
+2.746 (6.1%)
Address 3
Kyle, SD 57752
System Pressure Demand System Flow Demand
42.500 197.59
© M.E.P.CAD, Inc. 12/19/2017 Page 1AutoSPRINK® 12 v12.0.61.0 10:10:13AM
Job Number: 1
Node Flow(gpm)
Total Hose Streams
0.00
Safety MarginRequiredAvailable
Node
Hose Flow Static Residual Flow Total Demand
(gpm) (psi) (psi) (gpm) (psi) (gpm) (psi) (psi)
Name
1 45.245 42.500 2.746530.6010.00052.000 197.59Water Supply
Design EngineerJob Number
Total Water Required (Including Hose Allowance)
197.59
Maximum Pressure Unbalance In Loops
0.000
Additional Hose Supplies
0.00
Hose Allowance At Source
Supplies
1871.06gal
Ordinary Group II
0.200gpm/ft²
120.42ft²
963.35ft² (Actual 963.35ft²)
Occupancy
Area of Application
Coverage Per SprinklerNumber Of Sprinklers Calculated
Density
Job Suffix
AutoPeak Results: Pressure For Remote Area(s) Adjacent To Most Remote Area
Volume capacity of Dry PipesVolume capacity of Wet Pipes
4.53 between nodes 5 and 638 Maximum Velocity Under Ground
11.01 between nodes 574 and 957 Maximum Velocity Above Ground
5.6 K-Factor 24.08 at 18.495
Most Demanding Sprinkler Data
System
2017 Expansion1000 Health Ctr Rd Job Site/Building
BIAFIRE SPRINKLER PROTECTION LAYOUT
AHJ
Dakota Plains Kyle Clinic Health Ctr
Job
State Certification/License NumberJob Name:
Mike Moken1
Contractor
Contractor Number
RFP
Name of Contractor:
RAPID FIRE PROTECTION
Address 1
1530 SAMCO ROAD
Address 2
RAPID CITY, SD 57702
Contact Name Contact Title
PM
ExtensionPhone
605.348.2342
FAX
Mmoken@rapidfireinc.com
Web-Site www.rapidfireinc.com
Mike Moken
Address 3
Address 1
Address 2
Drawing Name
Kyle Clinic.1
System Flow Demand
197.59
Remote Area(s)
Address 3
12/19/2017© M.E.P.CAD, Inc. Page 2AutoSPRINK® 12 v12.0.61.0 10:10:15AM
Job Number: 1
10.000 @ 530.60
Residual: Pressure
52.000
Static: Pressure
Water Supply at Node 1
Hydraulic Graph
Water Supply at Node 1
42.500 @ 197.59
42.500 @ 197.59
Available Pressure at Time of Test Date of Test Time of Test
12/14/17 9:45
Test Conducted By Test Witnessed By
Rapid Fire Protection MM GG
Southside of Hosp Location
45.245 @ 197.59
System Demand
© M.E.P.CAD, Inc. 12/19/2017 Page 3AutoSPRINK® 12 v12.0.61.0 10:10:16AM
(gpm) (K)
K-Factor
(psi)
Pressure
Summary Of Outflowing Devices Report Description: Ordinary Group II (two)
Job Number: 1
Sprinkler 891 24.09 24.08 5.6 18.513
Sprinkler 892 24.08 24.08 5.6 18.495
Sprinkler 921 24.48 24.08 5.6 19.112
Sprinkler 922 24.47 24.08 5.6 19.094
Sprinkler 957 25.14 24.08 5.6 20.149
Sprinkler 958 25.13 24.08 5.6 20.130
Sprinkler 986 25.11 24.08 5.6 20.098
Sprinkler 987 25.09 24.08 5.6 20.079
© M.E.P.CAD, Inc. 12/19/2017 Page 4AutoSPRINK® 12 v12.0.61.0 10:10:17AM
Report Description: Ordinary Group II (two)
Job Number: 1
1 -4'-0 S 42.500 197.59
891 20'-4 Spr(-18.513) 18.513 24.09
892 20'-4 Spr(-18.495) 18.495 24.08
921 20'-4 Spr(-19.112) 19.112 24.48
922 20'-4 Spr(-19.094) 19.094 24.47
957 20'-4 Spr(-20.149) 20.149 25.14
958 20'-4 Spr(-20.130) 20.130 25.13
986 20'-4 Spr(-20.098) 20.098 25.11
987 20'-4 Spr(-20.079) 20.079 25.09
5 -4'-0 T(33'-5½) 40.363
573 19'-7 PO(10'-0) 23.542
574 20'-4 T(5'-0) 22.349
575 19'-7 PO(10'-0) 23.520
576 20'-4 T(5'-0) 22.328
590 11'-11 PO(10'-0) 28.323
591 13'-0 E(5'-0) 27.863
626 12'-0 PO(10'-0) 28.461
627 13'-0 T(10'-0) 28.018
638 2'-6 BFP(-4.000) 36.786
640 4'-4 fT(20'-0) 31.991
645 5'-9 31.366
647 11'-11 T(20'-0) 28.530
668 11'-11 PO(10'-0) 28.530
669 13'-0 E(5'-0) 28.059
671 12'-0 PO(10'-0) 28.461
672 13'-0 T(10'-0) 28.029
744 12'-0 PO(10'-0) 28.462
745 13'-0 T(10'-0) 28.029
751 13'-0 T(10'-0) 28.045
752 11'-11 PO(10'-0) 28.530
753 13'-0 E(5'-0) 28.057
770 12'-0 PO(10'-0) 28.462
© M.E.P.CAD, Inc. 12/19/2017 Page 5AutoSPRINK® 12 v12.0.61.0 10:10:18AM
Upstream Total Length
HWC
Hydraulic Analysis Job Number: 1
Report Description: Ordinary Group II (two)
• • • • • Route 1 • • • • •
Pf
Pe
Pv
BL 1.4180 24.08 4.89 0.042283 14'-2 0.599
892 20'-4 24.08 5.6 18.495
922 20'-4 19.094 14'-2
Sprinkler
Pf
Pe
Pv
BL 1.6540 48.55 7.25 0.073096 14'-2 1.036
922 20'-4 24.47 5.6 19.094
958 20'-4 20.130 14'-2
Sprinkler
Pf
Pe
Pv
BL 1.6540 73.68 11.00 0.158113 5'-11 2.198
958 20'-4 25.13 5.6 20.130 8'-0
576 20'-4 22.328 13'-11
Sprinkler, T(8'-0)
Pf
Pe
Pv
RN 2.1230 98.77 8.95 0.080627 0'-9 0.867
576 20'-4 25.09 22.328 10'-0 0.326
575 19'-7 23.520 10'-9
Flow (q) from Route 3
PO(10'-0)
Pf
Pe
Pv
FR 4.3100 98.77 2.17 0.002563 8'-6 0.022
575 19'-7 23.520
573 19'-7 23.542 8'-6
Pf
Pe
Pv
FR 4.3100 197.59 4.35 0.009245 107'-8½ 1.458
573 19'-7 98.82 23.542 50'-0 3.323
590 11'-11 28.323 157'-8½
Flow (q) from Route 2
E(10'-0), 2T(20'-0)
Pf
Pe
Pv
FR 4.3100 189.33 4.16 0.008543 4'-3 0.207
590 11'-11 28.323 20'-0
647 11'-11 28.530 24'-3
T(20'-0)
Pf
Pe
Pv
FR 4.3100 197.59 4.35 0.009245 7'-7 0.162
647 11'-11 8.26 28.530 10'-0 2.674
645 5'-9 31.366 17'-7
Flow (q) from Route 5
E(10'-0)
Pf
Pe
Pv
MS 4.2600 197.59 4.45 0.009786 1'-1 0.011
645 5'-9 31.366 0.614
640 4'-4 31.991 1'-1
2f(-0.000)
Pf
Pe
Pv
DY 4.3100 197.59 4.35 0.009245 0'-0 4.000
640 4'-4 31.991 0.795
638 2'-6 36.786 0'-0
BFP(-4.000)
Pf
Pe
Pv
UG 4.2200 197.59 4.53 0.007704 55'-0 0.759
638 2'-6 36.786 43'-6 2.818
5 -4'-0 40.363 98'-6
LtE(10'-0½), T(33'-5½)
Pf
Pe
Pv
UG 5.3490 197.59 2.82 0.002137 1000'-0 2.137
5 -4'-0 40.363
1 -4'-0 42.500 1000'-0
Water Supply
197.59
0.00 Hose Allowance At Source
• • • • • Route 2 • • • • •
Pf
Pe
Pv
BL 1.4180 24.09 4.90 0.042320 14'-2 0.600
891 20'-4 24.09 5.6 18.513
921 20'-4 19.112 14'-2
Sprinkler
Pf
Pe
Pv
BL 1.6540 48.58 7.25 0.073161 14'-2 1.036
921 20'-4 24.48 5.6 19.112
957 20'-4 20.149 14'-2
Sprinkler
Pf
Pe
Pv
BL 1.6540 73.71 11.01 0.158252 5'-11 2.200
957 20'-4 25.14 5.6 20.149 8'-0
574 20'-4 22.349 13'-11
Sprinkler, T(8'-0)
Pf
Pe
Pv
RN 2.1230 98.82 8.96 0.080698 0'-9 0.868
574 20'-4 25.11 22.349 10'-0 0.326
573 19'-7 23.542 10'-9
Flow (q) from Route 4
PO(10'-0)
• • • • • Route 3 • • • • •
Pf
Pe
Pv
BL 1.0830 25.09 8.74 0.169513 8'-3 2.248
987 20'-4 25.09 5.6 20.079 5'-0
576 20'-4 22.328 13'-3
Sprinkler, T(5'-0)
• • • • • Route 4 • • • • •
Pf
Pe
Pv
BL 1.0830 25.11 8.74 0.169662 8'-3 2.250
986 20'-4 25.11 5.6 20.098 5'-0
574 20'-4 22.349 13'-3
Sprinkler, T(5'-0)
• • • • • Route 5 • • • • •
Pf
Pe
Pv
BL 2.1230 5.08 0.46 0.000333 30'-1 0.012
751 13'-0 2.38 + 2.70 28.045 5'-0
753 13'-0 28.057 35'-1
Flow (q) from Route 6 and 7
E(5'-0)
Pf
Pe
Pv
RN 2.1230 5.08 0.46 0.000333 1'-1 0.004
753 13'-0 28.057 10'-0 0.470
752 11'-11 28.530 11'-1
PO(10'-0)
Pf
Pe
Pv
FR 4.3100 5.08 0.11 0.000011 11'-10½ 0.000
752 11'-11 28.530
668 11'-11 28.530 11'-10½
© M.E.P.CAD, Inc. 12/19/2017 Page 6AutoSPRINK® 12 v12.0.61.0 10:10:19AM
Upstream Total Length
HWC
Hydraulic Analysis Job Number: 1
Report Description: Ordinary Group II (two)
Pf
Pe
Pv
FR 4.3100 8.26 0.18 0.000026 4'-2½ 0.001
668 11'-11 3.18 28.530 20'-0
647 11'-11 28.530 24'-2½
Flow (q) from Route 8
T(20'-0)
• • • • • Route 6 • • • • •
Pf
Pe
Pv
RN 2.1230 8.26 0.75 0.000819 1'-0 0.009
627 13'-0 8.26 28.018 10'-0 0.434
626 12'-0 28.461 11'-0
Flow (q) from Route 9
PO(10'-0)
Pf
Pe
Pv
CM 3.3340 8.26 0.30 0.000091 8'-5½ 0.001
626 12'-0 28.461
671 12'-0 28.461 8'-5½
Pf
Pe
Pv
CM 3.3340 5.08 0.19 0.000037 9'-7 0.000
671 12'-0 28.461
744 12'-0 28.462 9'-7
Pf
Pe
Pv
CM 3.3340 2.38 0.09 0.000009 8'-9½ 0.000
744 12'-0 28.462
770 12'-0 28.462 8'-9½
Pf
Pe
Pv
RN 2.1230 2.38 0.22 0.000082 1'-0 0.001
770 12'-0 28.462 10'-0 -0.434
771 13'-0 28.029 11'-0
PO(10'-0)
Pf
Pe
Pv
BL 2.1230 2.38 0.22 0.000082 136'-5½ 0.016
771 13'-0 28.029 55'-0
751 13'-0 28.045 191'-5½
T(10'-0)
7E(5'-0), T(10'-0)
• • • • • Route 7 • • • • •
Pf
Pe
Pv
RN 2.1230 2.70 0.25 0.000104 1'-0 0.001
744 12'-0 28.462 10'-0 -0.434
745 13'-0 28.029 11'-0
PO(10'-0)
Pf
Pe
Pv
BL 2.1230 2.70 0.25 0.000104 124'-7½ 0.016
745 13'-0 28.029 25'-0
751 13'-0 28.045 149'-7½
T(10'-0)
E(5'-0), T(10'-0)
• • • • • Route 8 • • • • •
Pf
Pe
Pv
RN 2.1230 3.18 0.29 0.000140 1'-0 0.002
671 12'-0 28.461 10'-0 -0.434
672 13'-0 28.029 11'-0
PO(10'-0)
Pf
Pe
Pv
BL 2.1230 3.18 0.29 0.000140 155'-5½ 0.029
672 13'-0 28.029 55'-0
669 13'-0 28.059 210'-5½
T(10'-0)
9E(5'-0)
Pf
Pe
Pv
RN 2.1230 3.18 0.29 0.000140 1'-1 0.002
669 13'-0 28.059 10'-0 0.470
668 11'-11 28.530 11'-1