This document provides details for a federal construction contract opportunity with the Department of Veterans Affairs. The solicitation seeks a construction contractor to replace air handling units impacting the pharmacy, lab, imaging suites, and ground floor at the Oklahoma City VA Medical Center. The contractor will provide all labor, materials, equipment, and supervision necessary to complete the replacement work according to provided plans, drawings, and specifications. All work must be done at the Oklahoma City VAMC campus located at 921 NE 13th St in Oklahoma City, Oklahoma. The solicitation number for this opportunity is 36C25922R0009.
View the file
Other files
Show all 15
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
SATELLITE IMAGEAREA OF WORK SHEET INDEX
OKLAHOMA CITY, OK
VAMC PROJECT #: 635-20-102
REPLACE AIR HANDLERS 4,7,14, AND FCU
Plan North
VEG 20.13
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Fi le
P at h
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
321 4 5 6 7 8 9 10
Project Director
Issued: Date:
750 W HAMPDEN AVE
SUITE #300
ENGLEWOOD CO 80110
(720) 550-6307
WWW.VALHALLAENGINEERING.COM
635-20-102
921 NE 13TH ST OKLAHOMA CITY, OK 73104
CONSULTANTS: ARCHITECT/ENGINEERS: STAMP: REPLACE AIR HANDLERS 4, 7, 14,
AND FCU
100% CONSTRUCTION
DOCUMENTS
06/09/2021 DD MR
GI001
COVER SHEET
SHEET NO. SHEET NAME
GI001 COVER SHEET
GI002 GENERAL INFORMATION & ABBREVIATIONS
A-141 FOURTH FLOOR PLAN
M-001 MECHANICAL ABBREVIATIONS AND GENERAL NOTES
M-002 MECHANICAL SYMBOLS
M-501 MECHANICAL DETAILS
M-502 MECHANICAL DETAILS
M-503 MECHANICAL DETAILS
M-504 MECHANICAL DETAILS
M-505 MECHANICAL DETAILS
M-506 MECHANICAL DETAILS
M-507 MECHANICAL DETAILS
M-601 MECHANICAL SCHEDULES
M-602 MECHANICAL SCHEDULES
M-603 MECHANICAL SCHEDULES
M-701 MECHANICAL CONTROLS
M-702 MECHANICAL CONTROLS
M-703 MECHANICAL RISER DIAGRAM
M-704 MECHANICAL RISER DIAGRAM
MD101 GROUND FLOOR HVAC DEMO PLAN 1 (AHU 4)
MD102 GROUND FLOOR HVAC DEMO PLAN 2 (AHU 4)
MD103 GROUND FLOOR HVAC DEMO PLAN 3 (AHU 4)
MD111 FIRST FLOOR HVAC DEMO PLAN 1 (AHU 4)
MD112 FIRST FLOOR HVAC DEMO PLAN 2 (AHU 4)
MD113 FIRST FLOOR HVAC DEMO PLAN 3 (AHU 4)
MD121 SECOND FLOOR HVAC DEMO PLAN 1 (AHU 4)
MD122 SECOND FLOOR HVAC DEMO PLAN 2 (AHU 4)
MD123 SECOND FLOOR HVAC DEMO PLAN C (AHU 7)
MD131 THIRD FLOOR HVAC DEMOLITION PLAN (AHU 7 AND 14)
MD181 EIGHTTH FLOOR HVAC DEMOLITION PLAN (AHU 4)
M-100 GROUND FLOOR AHU 4 ZONES
M-110 FIRST FLOOR AHU 4 ZONES
M-120 SECOND FLOOR AHU 4 AND 7 ZONES
M-140 FOURTH FLOOR AHU 14 ZONES
MH101 GROUND FLOOR HVAC PLAN 1 (AHU 4)
MH102 GROUND FLOOR HVAC PLAN 2 (AHU 4)
MH103 GROUND FLOOR HVAC PLAN 3 (AHU 4)
MH111 FIRST FLOOR HVAC PLAN 1 (AHU 4)
MH112 FIRST FLOOR HVAC PLAN 2 (AHU 4)
MH113 FIRST FLOOR HVAC PLAN 3 (AHU 4)
MH121 SECOND FLOOR HVAC PLAN 1 (AHU 4)
MH122 SECOND FLOOR HVAC PLAN 2 (AHU 4)
MH123 SECOND FLOOR HVAC PLAN 3 (AHU 7)
MH131 THIRD FLOOR HVAC PLAN (AHU 7 AND 14)
MH141 FOURTH FLOOR HVAC PLAN 1 (AHU 14)
MH142 FOURTH FLOOR HVAC PLAN 2 (AHU 14)
MP101 GROUND FLOOR HVAC PLAN 1 (AHU 4)
MP102 GROUND FLOOR HVAC PLAN 2 (AHU 4)
MP103 GROUND FLOOR HVAC PLAN 3 (AHU 4)
MP111 FIRST FLOOR MECHANICAL PIPING PLAN 1 (AHU 4)
MP112 FIRST FLOOR MECHANICAL PIPING PLAN 2 (AHU 4)
MP113 FIRST FLOOR MECHANICAL PIPING PLAN 3 (AHU 4)
MP121 SECOND FLOOR MECHANICAL PIPING PLAN 1 (AHU 4)
MP122 SECOND FLOOR MECHANICAL PIPING PLAN 2 (AHU 4)
MP181 EIGHTH FLOOR MECHANICAL PIPING PLAN (AHU 4)
MP131 THIRD FLOOR MECHANICAL PIPING PLAN (AHU 7 AND 14)
MP132 MECHANICAL PIPING ENLARGEMENT PLAN (AHU 7 AND 14)
MP181 EIGHTH FLOOR MECHANICAL PIPING PLAN (AHU 4)
MP701 MECHANICAL PIPING RISER DIAGRAM
E-001 ELECTRICAL SYMBOLS & ABBREVIATIONS
E-501 ELECTRICAL DETAIL SHEET
EP101 GROUND FLOOR POWER PLAN 1 (AHU 4)
EP102 GROUND FLOOR POWER PLAN 2 (AHU 4)
EP103 GROUND FLOOR POWER PLAN 3 (AHU 4)
EP111 FIRST FLOOR POWER PLAN 1 (AHU 4)
EP112 FIRST FLOOR POWER PLAN 2 (AHU 4)
EP113 FIRST FLOOR POWER PLAN 3 (AHU 4)
EP121 SECOND FLOOR POWER PLAN 1 (AHU 4)
EP122 SECOND FLOOR POWER PLAN 2 (AHU 4)
EP131 THIRD FLOOR POWER PLAN (AHU 7 AND 14)
EP141 FOURTH FLOOR POWER PLAN 1 (AHU 14)
EP181 EIGHTH FLOOR POWER PLAN (AHU 4)
STAMP:
STAMP:
NOT IN SCOPE
06/09/2021
1 View Name 1/8" = 1'-0"
SECTION, DETAIL, OR ELEVATION TITLE EXAMPLE
ELEVATION CALLOUT EXAMPLE
DETAIL CALLOUT EXAMPLE
SECTION CALLOUT EXAMPLE
SECTION, DETAIL, OR ELEVATION
SYMBOL IDENTIFIERS
DETAIL NAME
LETTER OR NUMBER DESIGNATOR
DRAWING SEQUENCE NUMBER
INDICATES WHERE TITLE IS
LOCATED
ONE OR TWO CHARACTER
DISCIPLINE DESIGNATOR (MAY
NOT BE PRESENT IF CALLOUT
AND TITLE ARE ON DRAWINGS
WITHIN THE SAME DISCIPLINE)
A A101
AE101
AE101
AE101
W-3
P2
RB3
DOOR NUMBER TAG
WALL TYPE TAG
WINDOW TYPE TAG
CENTER LINE
WALL FINISH TAG
A COLUMN BUBBLE
ROOM TAG
WALL COLOR
BASE TYPE /
COLOR
MATCH LINE
DETAIL NUMBER
ON SHEET
SHEET NUMBER
DETAIL NUMBER
ON SHEET
SHEET NUMBER
NEW LINE TYPE.
EXISTING LINE TYPE.
DEMO LINE TYPE.
DEMO HATCH TYPE.
FIRE RESISTIVE RATED WALL, 1 HOUR
FIRE RESISTIVE RATED WALL, 2 HOUR
FIRE RESISTIVE RATED WALL, 3 HOUR
FIRE RESISTIVE RATED WALL, 4 HOUR
S
S
S
S
FIRE RATED, SMOKE BARRIER WALL, 1 HOUR
FIRE RATED, SMOKE BARRIER WALL, 1 HOUR
FIRE RATED, SMOKE BARRIER WALL, 1 HOUR
FIRE RATED, SMOKE BARRIER WALL, 1 HOUR
SYMBOLS LEGENDABBREVIATIONS GENERAL NOTES
& AND
@ AT
AB ANCHOR BOLT
ACFL ACCESS FLOOR
ACOUS ACOUSTICAL
AD AREA DRAIN
ADJ ADJUSTABLE
ADJT ADJACENT
ADMIN ADMINISTRATION
AFF ABOVE FINISH FLOOR
AHU AIR HANDLING UNIT
ALT ALTERNATE
ALUM ALUMINUM
AP ACCESS PANEL
APROX APPROXIMATE
ARCH ARCHITECTURAL
AT ACOUSTICAL CEILING TILE
AUTO AUTOMATIC
AWT ACOUSTICAL WALL TREATMENT
BD BOARD
BFE BOTTOM FOOTING ELEVATION
BG BUMPER GUARD
BKT BRACKET
BLDG BUILDING
BM BEAM
BOT BOTTOM
BP BRICK PAVING
BR BRICK
BRG BEARING
BSMT BASEMENT
C CHANNEL
CAB CABINET
CANTL CANTILEVER
CAP CAPACITY
CAT CATEGORY
CCTV CLOSED CIRCUIT TELEVISION
CD COILING DOOR
CG COILING GRILLE
CGD CORNER GUARD
CH COAT HOOK
CJT CONTROL JOINT
CL CENTER LINE
CLS CLASS
CLG CEILING
CLR CLEAR
CM CONSTRUCTION MANAGER
CMU CONCRETE MASONRY UNIT
CO CASED OPENING
COL COLUMN
CONC CONCRETE
CONF CONFERENCE
CONN CONNECT/-ED/-ION
CONST CONSTRUCTION
CONT CONTINUE/CONTINUOUS
CONTR CONTRACTOR
COORD COORDINATE
CORR CORRIDOR
CP CARPET
CPT CARPET MODULE TILE
CR-1 CHAIR RAIL
CR-2 CRASH RAIL
CT CERAMIC TILE
CTR CENTER
CW CURTAIN WALL
CWR COLD WATER
CYL CYLINDER
D DEPTH OR DEEP
DEMO DEMOLITION
DEPR DEPRESSION
DBL DOUBLE
DF DRINKING FOUNTAIN
DIA DIAMETER
DIAG DIAGONAL
DIFF DIFFUSER
DIM DIMENSION
DISP DISPENSER
DIST DISTRIBUTION
DIV DIVISION
DN DOWN
DP DATA PROCESSING
DR DOOR
DS DOWNSPOUT
DWG DRAWING
ELC ELECTRICAL CABINET
EC EPOXY COATING
EF EXHAUST FAN
EFTR EXISTING FINISH TO REMAIN
EJT EXPANSION JOINT
EL ELEVATION
ELEC ELECTRICAL
EMERG EMERGENCY
EO ELECTRICAL OUTLET
EPDM ETHYLENE PROPYLENE DIENE
MONOMER
EQ EQUAL
EQUIP EQUIPMENT
EWC ELECTRIC WATER COOLER
EXH EXHAUST HOOD
EXIST EXISTING
EXP EXPANSION
EXT EXTERIOR
EXT-P EXTERIOR PAINT
EXT-ST EXTERIOR STAIN
FA FIRE ALARM
FAP FIRE ALARM PANEL
FB FIRE BLANKET
FD FLOOR DRAIN
FDN FOUNDATION
FDV FIRE DEPARTMENT VALVE
FE FIRE EXTINGUISHER
FEC FIRE EXTINGUISHER CABINET
FGS FOAM GASKET SEAL
FH FIRE HOSE
FHV FIRE HOSE VALVE
FIN FINISH
FIXT FIXTURE
FLR FLOOR
FL FLOW LINE
FP FIRE PROOFING
H HIGH
HB HOSE BIB
HD HAND DRYER
HDCP HANDICAP
HDR HEADER
HDW HARDWARE
HM HOLLOW METAL
HORIZ HORIZONTAL
HPT HIGH POINT
HR HANDRAIL
HT HEIGHT
HTR HEATER
HVAC HEATING, VENTILATING,
AIR CONDITIONING
HW HOT WATER
HWD HARDWOOD
IC INTERCOM
ID INSIDE DIAMETER
IN INCH
INSUL INSULATION
INT INTERIOR
ISO ISOLATION
JAN JANITOR
JB JUNCTION BOX
JST JOIST
JT JOINT
KO KNOCK OUT
L LAVATORY
LB POUND
LCD LINEAR CEILING DIFFUSER
LF LINE FIGURED
LIN LINEAR
LKR LOCKER
LLH LONG LEG HORIZONTAL
LLV LONG LEG VERTICAL
LMC LINEAR METAL CEILING
LOC LOCATION OR LOCATE
LPT LOW POINT
LS LAWN SPRINKLING
LT LIGHT
LTG LIGHTING
LVR LOUVER
LWC LINEAR WOOD CEILING
MAT MATERIAL
MAX MAXIMUM
MBD MARKER BOARD
MC MEDICINE CABINET
MCU MODULAR COOLING UNIT
MECH MECHANICAL
MEMB MEMBRANE
MET METAL
MRF MANUFACTURER
MH MANHOLE
MIL MILLIMETER
MN MINIMUM
MR MIRROR
MISC MISCELLANEOUS
MO MASONRY OPENING
MONO MONOLITHIC
MPU MULTI- PURPOSE UNIT
MTD MOUNTED
MTL METAL
MTR MOTOR
MULL MULLION
PNL PANEL
PR PAIR
PRELIM PRELIMINARY
PRES PLASTIC RESIN
PRESS PRESSURE
PRIM PRIMARY
PROJ PROJECTION
PRV POWER ROOF VENTILATOR
PTC PAPER TOWEL CABINET
PTR PRINTER
PVC POLYVINYL CHLORIDE
R RADIUS
RI RISER
RA RETURN AIR
RB RESILIENT BASE/RUBBER BASE
RD ROOF DRAIN
REC RECESSED
REF REFERENCE
REFR REFRIGERATOR
REG REGISTER
REIN REINFORCE/-ED/-ING
REM REMOVE
REQD REQUIRED
RET RETAINING
REVS REVERSE
REV REVISE
RF RESILIENT FLOOR
RFI REQUEST FOR INFORMATION
RH ROOF HATCH
RM ROOM
RO ROUGH OPENING
RS ROUGH SLAB
RSF RESILIENT SHEET FLOOR
RWC RAIN WATER CONDUCTOR
SI SINK
SCHED SCHEDULE
SD SHOWER DRAIN
SDR SMOKE DAMPER
SDISP SOAP DISPENSER
SFT STORE FRONT
SF SQUARE FOOT
SH SHOWER
SHT SHEET
SHTG SHEATHING
SIM SIMILAR
SM SURFACE MOUNTED
SNC SANITARY NAPKIN CABINET
SND SANITARY NAPKIN DISPOSER
SP STANDPIPE
SPEC SPECIFICATIONS
SPR SINGLE PLY ROOF
SQ SQUARE
SQ YD SQUARE YARD
SR SERVICE RECEPTOR
SS SERVICE SINK
SST STAINLESS STEEL
STR STREET
ST STONE TILE
STC SOUND TRANSMISSION
STD STANDARD
STL STEEL
STOR STORAGE
STRUC STRUCTURAL
T TOP
TAN TANGENT
TCAB TOWEL CABINET
TDR TRENCH DRAIN
TEL TELEPHONE
TEMP TEMPERATURE
TER TERRAZZO
TG TONGUE & GROVE
THRES THRESHOLD
TOIL TOILET
TPH TOILET PAPER HOLDER
TR TREAD
TRANSF TRANSFORMER
TS TUBE SECTION
TV TELEVISION
TYP TYPICAL
U URINAL
UCT UNDERCUT
UC UNDERCOUNTER
UFD UNDER FLOOR DUCT
UG UNDERGROUND
UH UNIT HEATER
UNFIN UNFINISHED
UNO UNLESS NOTED OTHERWISE
US UTILITY SHELF
UTIL UTILITY
VIF VERIFY IN FIELD
VC VALVE CABINET
VCT VINYL COMPOSITION TILE
VENT VENTILATION
VERT VERTICAL
VEST VESTIBULE
VR VAPOR RETARDER
VTR VENT THROUGH ROOF
WCV WALL COVERING
W WIDTH/WIDE
WF WIDE FLANGE
W/ WITH
W/O WITHOUT
WC WATER CLOSET
WD WOOD
WDW WINDOW
WG WALL GUARD
WH WALL HYDRANT
WHCH WHEELCHAIR
WHTR WATER HEATER
WPL WALL PANEL
WP WATERPROOF
WR WASTE RECEPTACLE
WS WEATHERSTRIP
WSCT WAINSCOT
WSF WELDED SEAM - RESILIENT
SHEET FLOORING
WDT WINDOW TREATMENT
WT WEIGHT
WW WOOD WINDOW
WWF WELD WIRE FABRIC
NA NOT APPLICABLE
NC NURSE CALL
NIC NOT IN CONTRACT
NO NUMBER
NOM NOMINAL
NRC NOISE REDUCTION COEFFICIENT
NT NOTE
NTS NOT TO SCALE
OC ON CENTER
OD OUTSIDE DIAMETER
OFF OFFICE
OH OVERHEAD
OP OPERABLE PARTITION
OPER OPERATOR
OPNG OPENING
OPP OPPOSITE
OFD OVERFLOW ROOF DRAIN
FRMG FRAMING
FSTOP FIRE STOPPING
FT FOOT/FEET
FTG FOOTING
FURR FURRING
GA GAUGE
GAL GALLONS
GALV GALVANIZED
GB GRAB BAR
GBM GRADE BEAM
GC GENERAL CONTRACTOR
GEN GENERAL
GENR GENERATOR
GL GLASS
GR GRADE
GRT GROUT
GWB GYPSUM WALLBOARD
GYP GYPSUM
P PAINT
PART PARTITION
PB PUSH BUTTON
PC PRECAST CONCRETE
PCD PAPER CUP DISPENSER
PED PEDESTAL
PLT PLATE
PROP PROPERTY LINE
PLAM PLASTIC LAMINATE
PLBG PLUMBING
PLS PLASTER
PLW PLYWOOD
VEG 20.13
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Fi le
P at h
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
321 4 5 6 7 8 9 10
Project Director
Issued: Date:
750 W HAMPDEN AVE
SUITE #300
ENGLEWOOD CO 80110
(720) 550-6307
WWW.VALHALLAENGINEERING.COM
635-20-102
921 NE 13TH ST OKLAHOMA CITY, OK 73104
CONSULTANTS: ARCHITECT/ENGINEERS: STAMP: REPLACE AIR HANDLERS 4, 7, 14,
AND FCU
100% CONSTRUCTION
DOCUMENTS
03/26/2021 MR GD
GI002
GENERAL INFORMATION &
ABBREVIATIONS
COR CONTRACTING OFFICER'S
REPRESENTATIVE
A. ALL CONTRACTORS AND THEIR SUPERVISORY PERSONNEL MUST REVIEW THE GENERAL AND
SUPPLEMENTARY CONDITIONS TO THE CONTRACT.
B. ALL WORK MUST CONFORM WITH PROJECT SPECIFICATIONS.
C. CONTRACTOR MUST BECOME FULLY ACQUAINTED WITH CONDITIONS RELATED TO THE WORK. QUESTIONS
WILL BE DIRECTED TO VHA COR.
D. CONTRACTOR WILL BE SOLELY RESPONSIBLE FOR THE MEANS, METHODS AND SEQUENCES OF
CONSTRUCTION AND THE SAFETY OF ALL CONSTRUCTION PERSONNEL AND VISITORS.
E. DRAWINGS CONTAINED IN THIS SET MUST NOT BE REPRODUCED FOR SHOP DRAWINGS. COPIES OF THESE DRAWINGS SUBMITTED AS SHOP DRAWINGS WILL BE REJECTED AND RETURNED TO THE CONTRACTOR.
REFER TO SPECIFICATION SECTION 01 33 23.
F. EACH CONTRACTOR AND SUBCONTRACTOR WILL EXAMINE SUBSTRATE AND/OR CONDITIONS UNDER WHICH THE WORK WILL BE INSTALLED AND REPORT TO THE CONTRACTOR, IN WRITING, ANY CONDITIONS DETRIMENTAL TO THE PROPER AND TIMELY EXECUTION OF THEIR WORK. DO NOT PROCEED UNTIL UNSATISFACTORY CONDITIONS ARE CORRECTED. COMMENCING WITH INSTALLATION WILL CONSTITUTE
ACCEPTANCE OF THE SUBSTRATE AND/OR CONDITIONS.
G. DO NOT SCALE DRAWINGS: FOLLOW WRITTEN DIMENSIONS AND NOTES. CONTACT VHA COR FOR
CLARIFICATIONS, IF REQUIRED.
H. DIMENSIONS SHOWN ON THE FLOOR PLAN ARE TO THE FACE OF GYPSUM WALL BOARD (FOG), FACE OF EXPOSED MASONRY (FOM), FACE OF CONCRETE WALLS (FOC) AND COLUMN GRID LINES, UNLESS
OTHERWISE NOTED OR INDICATED.
I. "TYPICAL", AS USED IN THESE DOCUMENTS, MEANS THAT THE CONDITION OR DIMENSION IS
REPRESENTATIVE OF, OR THE SAME, FOR SIMILAR CONDITIONS THROUGHOUT.
J. IF THERE IS A DISCREPANCY BETWEEN SMALL SCALE AND LARGE SCALE DRAWINGS, (PLAN, SECTION, &
DETAIL DRAWINGS, ETC), CONTACT VHA COR FOR CLARIFICATION.
K. IF THERE IS A DISCREPANCY BETWEEN THE DRAWINGS AND THE SPECIFICATIONS, SPECIFICATIONS GOVERN.
CONTACT VHA COR FOR CLARIFICATION.
L. ANY DISCREPANCIES BETWEEN THE DRAWINGS AND ACTUAL CONDITIONS MUST BE REPORTED TO THE VHA
COR, IN WRITING, FOR RESOLUTION PRIOR TO PROCEEDING WITH THE WORK.
M. ANY AND ALL DISCREPANCIES MUST BE REPORTED TO THE VHA COR IN WRITING FOR RESOLUTION, PRIOR TO PROCEEDING WITH THE WORK. NO CHANGE ORDERS OR EXTENSIONS OF TIME WILL BE ALLOWED OR ACCEPTED FOR PROCEEDING WITH THE WORK WITHOUT THE CONTRACTING OFFICER'S WRITTEN DIRECTION AND APPROVAL. ALSO, CONTRACTOR MUST REPAIR AND/OR REPLACE ANY UNAUTHORIZED WORK, AS
INDICATED BY THE VHA COR, AT NO ADDITIONAL COST TO THE VHA.
N. ALL DISSIMILAR METAL MATERIALS MUST BE ISOLATED WITH AN APPROVED NONMETAL ISOLATION MATERIAL
IN ACCORDANCE WITH SPECIFICATIONS.
O. ALL EXTERIOR EXPOSED STEEL MUST BE PAINTED PER SPECIFICATION SECTION 09 91 00.
P. OPEN EXTERIOR JOINTS AROUND WINDOW AND DOOR FRAMES, BETWEEN WALLS AND FOUNDATIONS, BETWEEN WALL PANELS, AT PENETRATIONS THROUGH THE BUILDING ENVELOPE, ETC, MUST BE SEALED, CAULKED, FLASHED OR WEATHER-STRIPPED AS REQUIRED BY SPECIFICATION SECTION 07 92 00.
Q. PROVIDE SEALANT AND/OR CAULKING BETWEEN DISSIMILAR ADJOINING INTERIOR MATERIALS, IE WINDOW SILLS TO GWB, ACT CEILINGS TO MASONRY WALLS, ETC. REFER TO SPECIFICATION SECTION 07 92 00.
R. CONTRACTOR MUST VERIFY THE LOCATIONS OF ALL EXISTING UNDERGROUND UTILITIES AND THEIR SERVICE CONNECTIONS WITH THE PROPER UTILITY COMPANY, COORDINATE ANY ISSUES WITH VHA COR.
S. CONTRACTOR MUST COORDINATE SIZE, LOCATIONS AND NUMBER OF ALL ROOF OPENINGS AND ROOF ACCESSORIES WITH ALL OTHER TRADES. REFER TO THE ARCHITECTURAL, STRUCTURAL, PLUMBING, MECHANICAL AND ELECTRICAL DRAWINGS FOR REFERENCE AND SPECIFICATIONS FOR REQUIREMENTS.
T. LOCATIONS AND SIZES OF ALL CONCRETE MECHANICAL AND ELECTRICAL EQUIPMENT PADS MUST BE COORDINATED BY THE MECHANICAL AND ELECTRICAL CONTRACTORS WITH THE SELECTED EQUIPMENT MANUFACTURER AND/OR SUPPLIER. LOCATIONS ARE TO BE APPROVED BY THE VHA COR PRIOR TO
PROCEEDING WITH THE WORK.
U. ALL WALL AND COLUMN GYPSUM BOARD FACING MUST BE HELD AT 5/8" BELOW STRUCTURE, EXCEPT AT
FIRE-RATED PARTITIONS, UNLESS DETAILED OR NOTED OTHERWISE.
V. ALL CEILING HEIGHTS AS SHOWN ON PLANS AND DETAILS ARE FROM SLAB OR FINISHED FLOOR TO FINISH
CEILING.
W.PROVIDE INDEPENDENT FRAMING AND ATTACHMENTS TO THE STRUCTURE, ADEQUATE TO SUPPORT THE CEILING SYSTEM, LIGHT FIXTURES, DUCTS, DIFFUSERS, SPRINKLER PIPING AND BUS DUCTS.
X. ALL CLOSETS AND ALCOVES WITHOUT A SPACE IDENTIFICATION NUMBER MUST HAVE THE SAME FINISHES AS
ADJOINING SPACES, UNLESS NOTED OTHERWISE.
Y. CONTRACTOR TO INSTALL WOOD BLOCKING AND PLYWOOD AS REQUIRED FOR THE MOUNTING OF ALL TOILET ACCESSORIES, MILLWORK, CASEWORK, AV EQUIPMENT, MEP ITEMS AND RADIOLOGY EQUIPMENT, ETC. REFER TO SPECIFICATIONS.
Z. ALL PROPRIETARY PRODUCTS DESCRIBED AND/OR DRAWN IN THE DOCUMENTS MUST MEET
SPECIFICATIONS.
AA. REFER TO SPECIFICATION SECTION 01 45 29 FOR ALL REQUIRED TESTING AND INSPECTIONS.VHA VETERAN'S HEATH
ADMINISTRATION
STAMP:
STAMP:
STAMP:
REFRIGERATOR
WALK-IN
DIRTY
STORAGE
CL
EA
N
ST
OR
AG
E
4F115C
4F115C1
OFFICE
SPECIMEN
ACCESSION
OFFICE
MICROBIOLOGY
A.F.B./FUNGUS
ISOLATION
OFFICE
BLOOD BANK
H.A.C.
ELECTRICAL
CLOSET
STORAGE
BREAK ROOM
OFFICE
OFFICE
OFFICEA.F.B./
FUNGUS
STORAGE
SEROLOGY
FILING
TOILET
TOILET
OFFICE
WAITING
PHLEBOTOMY
OFFICE
EMS
STORAGE
TELE/DATA
CLOSET
4F105E4F114
4F115A
4F105D
4F105C
4F115B
4F115B1 4F105B
4F149
4F150
4F151
4F100
4F102A
4F103 4F104
4F101
4F107
4F106
4F148
4F108
4F110
4F109 4F111
4F
24F112A 4F112B
4F113
CLIENT SERVICES
MICRO-
BIOLOGY
4F102
PHLEBOTOMY
506 SF 296 SF
5 S
F
1 S F
8 S
F C4
F
C4F 2
C4 F
C4F 4
C4 F
C4F 12 C4F 13
C4 F
C4F 15
590 SF
3 S
F
315 SF
234 SF
CHEMISTRY HEMATOLOGY
LABORATORY
OFFICE
URINALYSIS
4F105A
4F105
STAIR 8
ELEVATOR
P-9
ELEVATOR
P-10
ELEVATOR
P-7
ELEVATOR
P-8
SEE SHEET MH142
E
F
G
H
I
E
F
G
H
I
E
F
G
H
I
2 3 64 5 7 82 3 64 5 7 82 3 65 7 84
8 9a8a 9
118 9a8a 9
118a
8 9a9 11765432 765432 764 532
9 10 119 10 119 10 11
222 222
03/26/2021 MR GD
A-141
FOURTH FLOOR PLAN
SCALE:
2' 4' 8' 16' 32'
1/8" = 1'-0"
FOURTH FLOOR PLAN
Pl an
N or th Tr ue N or th
KEY NOTES:
A. FIELD VERIFY EXISTING CONDITIONS AND REPORT ANY
DISCREPANCIES TO THE VHA COR BEFORE PROCEEDING WITH WORK.
B. REFER TO GI002 FOR ADDITIONAL GENERAL NOTES AND SYMBOLS.
C. COORDINATE ICRA BARRIER CONSTRUCTION AND LOCATION WITH THE
VHA COR AND VHA INFECTION CONTROL OFFICER.
D. COORDINATE ABOVE CEILING WORK WITH VHA COR AND INFECTION
CONTROL OFFICER; MINIMIZE REMOVAL OF CEILING TILES DURING
WORK AND REINSTALL AT THE END OF SHIFT.
ARCHITECTURAL GENERAL
NOTES:
VEG 20.13
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Fi le
P at h
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
321 4 5 6 7 8 9 10
Project Director
Issued: Date:
750 W HAMPDEN AVE
SUITE #300
ENGLEWOOD CO 80110
(720) 550-6307
WWW.VALHALLAENGINEERING.COM
635-20-102
921 NE 13TH ST OKLAHOMA CITY, OK 73104
CONSULTANTS: ARCHITECT/ENGINEERS: STAMP: REPLACE AIR HANDLERS 4, 7, 14,
AND FCU
KEY PLAN
NO SCALE
B
D
8 G
HW
C
5 18
Tr ue
N or th
E
A
F
100% CONSTRUCTION
DOCUMENTS
A-141
A-141
SCALE: 1/2" = 1'-0"
6" 1' 2' 4' 8'0
4F105 CHEMISTRY HEMATOLOGY LABORATORY
Pl an
N or th Tr ue N or th
SCALE: 1/2" = 1'-0"
6" 1' 2' 4' 8'0
4F115 MICROBIOLOGY PLAN
Pl an
N or th Tr ue N or th
6 1/2"
1'- 1"
1'- 9"
7"
4 1 /4"
2'-6"
1'- 0"
2'- 2 7
/8"
10'-9"
℄ TO ℄
A-141
SCALE: 1" = 1'-0"
3" 6" 1' 2' 4'0
DUCT CHASE SECTION
EXISTING CONC FLOOR SLAB;
VERIFY THICKNESS IN FIELD
EXISTING GYP BD WALL
6"
NEW SUPPLY DUCT; RE: MECH
5/8" TYPE "X" GYP BD OVER 3-5/8"
METAL STUD, TYP
EXISTING CLG TILE AND GRID;
MODIFY AROUND NEW CHASE, TYP
1'-1"
WALL BASE; MATCH EXISTING
1. APPROXIMATE LOCATION OF DUCT ROUTING AND CONNECTION
ABOVE CEILING
2. APPROXIMATE CORE DRILL/ SAW CUT LOCATION; MINIMIZE
PENETRATION SIZE, TYP; VERIFY CONCRETE BEAM LOCATION BELOW,
WHERE APPLICABLE; RE: MECH
3. FIRE STOP TO MEET 2-HOUR FIRE RATING. REFER TO SPECIFICATION
SECTION 07 84 00 FIRESTOPPING.
4. EXTEND NEW CHASE WALL TO 6" ABOVE CEILING;
PAINT FROM INSIDE CORNER TO INSIDE CORNER,
MATCH EXISTING ADJACENT; RE: 4 / A-141
5. ALIGN CHASE WITH EXISTING COLUMN WRAP
6. MODIFY EXISTING CEILING TILE AND GRID TO ACCOMMODATE NEW
CHASES.
7. EXISTING FUME HOOD, TO REMAIN
8. APPROXIMATE EXTENTS OF CEILING WORK ABOVE, TYP
VERIFY SIZE OF EXISTING BEAM IN FIELD
EXISTING COLUMN, BEYOND
5"
MIN
STEEL ANGLE OPENING SUPPORT; RE: 5/A-141
SCALE: 1/2" = 1'-0"
6" 1' 2' 4' 8'0
OPENING SUPPORT DETAILS
A-141
SECTION @ 4F115
TOP VIEW @ 4F115
TOP VIEW @ 4F105
L4x4x5/16, TYP
2'-0"
MIN
2'-0"
MIN
WELDED L4x4x5/16
CROSS ANGLE,
TYP OF (2) PER OPENING
5/8" EPOXY ANCHOR,
TYP OF (4) PER LEG
4"1'-0"4" 1'-0"
5'-4"
MIN
2'-0"
MIN
2'-0"
MIN
WELDED L4x4x5/16
CROSS ANGLE,
TYP OF (2) PER OPENING
5'-4"
MIN
4"1'-0"
5'-6"
MIN
4" 1'-0"
SAW CUT OPENING
HVAC GENERAL NOTESMECHANICAL ABBREVIATIONS
1. CONTRACTOR SHALL PROVIDE AN INFECTION CONTROL RISK ASSESSMENT BARRIER AROUND
THE PROJECT AREA CONSISTENT WITH THE CONTRACTOR'S PHASING PLAN AS APPROVED BY
THE VHA COR AND SPECIFICATION 01 35 26.
MECHANICAL ASCE 7 NONSTRUCTURAL
SEISMIC RESTRAINT AND ANCHORAGE NOTES:
REFERENCE SPECIFICATION: SECTION 13 05 41
SEISMIC RESTRAINT REQUIREMENTS FOR NON-STRUCTURAL COMPONENTS
SEISMIC DESIGN DATA FOR ANALYSIS AND DESIGN
SEISMIC RISK CATEGORY = IV
COMPONENT IMPORTANCE FACTOR IP=1.50
MAPPED SPECTRAL RESPONSE ACCELERATION PARAMETERS:
SS=0.309G S1=0.081G
SITE CLASS D (ASSUMED)
DESIGN SPECTRAL RESPONSE ACCELERATION PARAMETERS:
SDS=0.319G SD1=0.13G
SEISMIC DESIGN CATEGORY C
1. ALL PIPING AND DUCTS IN FINISHED ROOMS OR SPACES SHALL BE CONCEALED IN A
FURRED CHASE OR ABOVE THE HARD OR SUSPENDED CEILING. REFER TO 23 05 11
FOR ADDITIONAL INFORMATION.
2. THE FIRST FIGURE OF DUCT SIZE INDICATES DIMENSION OF FACE SHOWN OR
INDICATED. DUCT SIZES ARE NET INSIDE DIMENSIONS. REFER TO 23 31 00.
3. ACCESS PANELS IN HARD SUSPENDED CEILINGS ARE REQUIRED FOR ALL VALVES,
TRAPS, DAMPERS, CLEANOUTS, CONTROLS, ETC. ACCESS PANELS SHALL BE
FURNISHED AND INSTALLED UNDER THE ARCHITECTURAL SPECIFICATIONS, 08 31 13.
4. TOTAL STATIC PRESSURE NOTED IN THE SCHEDULES INCLUDES DUCT SYSTEM,
TERMINAL UNITS, FILTERS, COILS, ETC. EQUIPMENT PROVIDED SHALL MEET
SPECIFICATION REQUIREMENTS
5. FOR TYPICAL STEAM AND WATER PIPING CONNECTIONS TO EQUIPMENT, SEE
EQUIPMENT DETAILS AND DIVISION 23 SPECIFICATIONS.
6. DIFFUSER, REGISTER AND GRILLE SIZES SHOWN ON FLOOR PLANS ARE NECK SIZES.
7. WATER PIPE CONNECTIONS TO AIR HEATING AND COOLING COILS SHALL BE MADE
TO PROVIDE COUNTER FLOW BETWEEN WATER AND AIR. REFER TO CONNECTION
DETAILS AND DIV 23 SPECIFICATIONS.
8. WALL TYPE EXHAUST REGISTERS NOTED AS "BR" ON DRAWINGS ARE TO BE
INSTALLED WITH BOTTOM ELEVATION OF REGISTER AT 7" ABOVE FINISHED FLOOR.
9. ALL PRESSURES LISTED ARE GAGE PRESSURE UNLESS NOTED OTHERWISE.
10. ALL CONTROL SYSTEM EQUIPMENT SHALL BE COMPATIBLE WITH EXISTING
BUILDING MANAGEMENT SYSTEM CONTROLS. EXTEND EXISTING CONTROL SYSTEM
TO INCLUDE ALL OF THE CONTROLS AND SEQUENCES SHOWN. REFER TO 23 09 23
FOR ADDITIONAL REQUIREMENTS.
11. COORDINATE EXISTING FIRE SPRINKLER HEADS AND LIGHTS WITH DUCTS AND
DIFFUSERS.
13. SUBMIT COMPLETE CONSOLIDATED AND COORDINATED SHOP DRAWINGS FOR ALL
NEW SYSTEMS, AND FOR EXISTING SYSTEMS THAT ARE IN THE SAME AREAS. DO
NOT INSTALL EQUIPMENT FOUNDATIONS, EQUIPMENT, OR PIPING UNTIL
COORDINATION/SHOP DRAWINGS HAVE BEEN APPROVED. REFER TO 01 33 23 AND
23 05 11 FOR ADDITIONAL REQUIREMENTS.
GENERAL NOTES
03/26/2021 DD MR
M-001
MECHANICAL ABBREVIATIONS AND
GENERAL NOTES
SR SUPPLY AIR REGISTER
SS STAINLESS STEEL
SSHX STEAM TO STEAM HEAT EXCHANGER
SSR SOLID SEPARATOR
ST STEAM TRAP
SUH STEAM UNIT HEATER
SV STEAM PRESSURE REDUCING VALVE
SVS STEAM VENT SILENCER
SWHX STEAM TO WATER HEAT EXCHANGER
T&PCV TEMPERATURE AND PRESSURE CONTROL VALVE
TAB TESTING, ADJUSTING, AND BALANCING
TD TEMPERATURE DIFFERENCE
TDH TOTAL DYNAMIC HEAD
TDS TOTAL DISSOLVED SOLIDS
TG TRANSFER GRILLE
TP TRAP
TR TOP REGISTER
TSP TOTAL STATIC PRESSURE
TSTAT THERMOSTAT
TU TERMINAL UNIT
TWU THRU-WALL UNIT
UCT UNDERCUT
UC UNIT COOLER
UH UNIT HEATER
UL UNDERWRITER'S LABORATORY
URV UPBLAST UNIT VENTILATOR
V VALVE
VAF VANE-AXIAL FAN
VAV VARIABLE AIR VOLUME
VD VOLUME DAMPER (MANUAL OPPOSED BLADE)
VFD VARIABLE FREQUENCY DRIVE
VHA VETERANS HEALTH ADMINISTRATION
VI VIBRATION ISOLATOR
VIV VARIABLE INLET VANES
VP VACUUM PUMP
VPS VARIABLE PRIMARY SYSTEM
VR VACUUM (STEAM CONDENSATE) RETURN
VSD VARIABLE SPEED DRIVE
VUH VERTICAL UNIT HEATER
W WASTE
WAG WASTE ANESTHESIA GAS
WB WET BULB
WC WATER COOLED
WCCH WATER COOLED CHILLER
WCCU WATER COOLED CONDENSING UNIT
WCPU WATER COOLED HEAT PUMPS
WEF WATER COOLED PACKAGED UNIT
WF WATER FILTER
WFCV WATER FLOW CONTROL VALVE
WFM WATER FLOWMETER
WFMD WATER FLOW MEASURING DEVICE
WG WATER GAGE
WPD WATER SIDE PRESSURE DROP
YR YEAR
OFM OIL FLOWMETER
OR OPERATING ROOM
P PUMP
PA PASCAL
PC PUMPED CONDENSATE
PCF POUNDS PER CUBIC FOOT
PD PRESSURE DROP
PEF PROPELLER TYPE EXHAUST FAN
PF PRE-FILTER
PG PRESSURE GAUGE
PGW PROPYLENE GLYCOL-WATER SOLUTION
PHC PREHEAT COIL
PPM PARTS PER MILLION
PRS PRESSURE REGULATING VALVE STATION
PRV PRESSURE REGULATING VALVE
PSI POUNDS PER SQUARE INCH
PSIA POUNDS PER SQUARE INCH, ABSOLUTE
PSIG POUNDS PER SQUARE INCH, GAGE
PSS PRIMARY SECONDARY SYSTEM
PSV PRESSURE SAFETY VALVE
PTAC PACKAGED TERMINAL AIR CONDITIONER
R/E RETURN OR EXHAUST
RA RETURN AIR
RAD REFRIGERANT AIR DRYER
RAF RADIO FREQUENCY
RAHX ROTARY AIR HEAT EXCHANGER
RAT RETURN AIR TEMPERATURE
RCCH REMOTE CONDENSER CHILLER
RCU RECIPROCATING CHILLER UNIT
RD REFRIGERANT DISCHARGE
RDS ROOM DATA SHEETS
REA RELIEF AIR
RF RETURN FAN
RG RETURN GRILLE
RH RELATIVE HUMIDITY
RHC REHEAT COIL
RHG REFRIGERANT HOT GAS
RL REFRIGERANT LIQUID LINE
RLA RUN LOAD AMPERE
RO REVERSE OSMOSIS
RPM REVOLUTIONS PER MINUTE
RR RETURN REGISTER
RS REFRIGERANT SUCTION
RTU ROOFTOP UNIT
RV RELIEF VALVE
SA SUPPLY AIR
SAD SOUND ATTENUATING DEVICE
SAT SUPPLY AIR TEMPERATURE
SC SHADING COEFFICIENT
SCFM STANDARD CUBIC FEET PER MINUTE
SCR SILICON CONTROLLED RECTIFIER
SD SMOKE DETECTOR
SD SUPPLY AIR DIFFUSER
SD-1 SCHEMATIC DESIGN SUBMISSION 1
SD-2 SCHEMATIC DESIGN SUBMISSION 2
SDPR SMOKE DAMPER
SDR SMOKE DAMPER (RETURN)
SDS SMOKE DAMPER (SUPPLY)
SEN SENSIBLE HEAT
SF SUPPLY FAN
SG SUPPLY AIR GRILLE
SH STEAM HUMIDIFIER
SHC STEAM HEATING COIL
SI SQUARE INCHES
SP STATIC PRESSURE
SP GR SPECIFIC GRAVITY
SPD SUPPLY PROCESS AND DISTRIBUTION
SPRV STEAM PRESSURE REDUCING VALVE
SPS STATIC PRESSURE SENSOR
SQ FT SQUARE FOOT
IRH INFRARED HEATER
IS INSECT SCREEN
IU INDUCTION UNIT
IV INLET VANES
KG KILOGRAM
KG/H KILOGRAMS PER HOUR
KPA KILOPASCAL
KW KILOWATT
KWH KILOWATT HOURS
L LITER
L/H LITERS PER HOUR
L/M LITERS PER MINUTE
L/S LITERS PER SECOND
LAT LEAVING AIR TEMPERATURE
LB/H POUND PER HOUR
LF LINEAR FOOT (FEET)
LGT LEAVING GLYCOL TEMPERATURE
LH LATENT HEAT
LLHX LIQUID TO LIQUID HEAT EXCHANGER
LPG LIQUID PROPANE GAS
LPR LOW PRESSURE RETURN (STEAM
CONDENSATE)
LPRC LOW PRESSURE STEAM RETURN (CLEAN)
LPS LOW PRESSURE STEAM
LPSC LOW PRESSURE STEAM (CLEAN)
LSD LINEAR SLOT DIFFUSER
LTCP LOCAL TEMPERATURE CONTROL PANEL
LVG LEAVING
LVR LOUVER
LWT LEAVING WATER TEMPERATURE
M METER
M/S METERS PER SECOND
MA MIXED AIR
MAT MIXED AIR TEMPERATURE
MAU MAKE-UP AIR UNIT
MAV MANUAL AIR VENT
MAX MAXIMUM
MB MIXING BOX
MBH 1000 BTUH
MCA MINIMUM BRANCH CIRCUIT AMPACITY
MER MECHANICAL EQUIPMENT ROOM
MERV MINIMUM EFFICIENCY REPORTING VALUE
MH MANHOLE
MHP MOTOR HORSEPOWER
MIN MINIMUM
MM MILLIMETER
MOV MOTOR OPERATED VALVE
MPR MEDIUM PRESSURE RETURN (STEAM
CONDENSATE)
MPS MEDIUM PRESSURE STEAM
MRI MAGNETIC RESONANCE IMAGING UNIT
MTD MEAN TEMPERATURE DIFFERENCE
MVD MANUAL VOLUME DAMPER
MZ MULTI-ZONE
NA NOT APPLICABLE
NC NOISE CRITERIA
NC NORMALLY CLOSED
NG NATURAL GAS
NGFM NATURAL GAS FLOW METER
NO NORMALLY OPEN
NOAA NATIONAL OCEANIC & ATMOSPHERIC
ADMINISTRATION
NOM NOMINAL
NPLV NON-STANDARD PART LOAD VALUE
NPSH NET POSITIVE SUCTION HEAD
NTS NOT TO SCALE
OA OUTSIDE AIR
OAG OUTSIDE AIR GRILLE
OAI OUTSIDE AIR INTAKE
OD OUTER DIAMETER
FF FINAL FILTER
FHX FLUE GAS/FEEDWATER HEAT EXCHANGER
FM FLOW METER
FOHX FUEL OIL HEAT EXCHANGER
FOP FUEL OIL PUMP
FOT FUEL OIL TANK
FPM FEET PER MINUTE
FPS FEET PER SECOND
FPTU FAN POWERED TERMINAL UNIT
FR FLOOR REGISTER
FRP FIBER REINFORCED POLYESTER
FS FLOW SWITCH
FSTAT FREEZESTAT
FT FEET
FT-LB FOOT-POUND
FTR FINNED TUBE RADIATION
FV FACE VELOCITY
GA GAUGE
GAL GALLONS
GH GRAVITY HOOD
GPD GALLONS PER DAY
GPH GALLONS PER HOUR
GPM GALLONS PER MINUTE
GPR GAS PRESSURE REGULATOR
GS GALVANIZED STEEL
H HUMIDIFIER
H&CW HOT & COLD WATER
HAC HOUSEKEEPING AID CLOSET
HB HOSE BIBB
HC HEATING COIL
HD HEAD
HD HOOD
HOA HAND/OFF/AUTOMATIC
HP HEAT PUMP
HP HORSEPOWER
HPDT HIGH PRESSURE DRIP TRAP
HPR HIGH PRESSURE RETURN (STEAM
CONDENSATE)
HPS HIGH PRESSURE SUPPLY (STEAM)
HRC HEAT RECOVERY COIL
HRD HEAT RECOVERY DEVICE
HRP HYDRONIC RADIANT (CEILING) PANEL
HRW HEAT RECOVERY WHEEL
HSTAT HUMIDISTAT
HTM HUMIDIFIER TERMINAL
HUM HUMIDIFIER UNIT MOUNTED
HVD HOISTWAY VENT DAMPER
HVU HEATING AND VENTILATING UNIT
HW HOT WATER
HWC HOT WATER COIL
HWHC HOT WATER HEATING COIL
HWP HEATING WATER PUMP
HWR HEATING WATER RETURN
HWS HEATING WATER SUPPLY
HWUH HOT WATER UNIT HEATER
HX HEAT EXCHANGER
HZ HERTZ
I/O INPUT/OUTPUT
IAQ INDOOR AIR QUALITY
IBT INVERTED BUCKET TRAP
ICF IN-LINE CENTRIFUGAL FAN
ICU INTENSIVE CARE UNIT
ID INSIDE DIAMETER
IFB INTEGRAL FACE AND BYPASS
IN INCHES
IN HG INCHES OF MERCURY
IN WC INCHES OF WATER COLUMN
IN WG INCHES OF WATER, GAUGE
IN-LB INCH-POUND
IPLV INTEGRATED PART LOAD VALUE
CP CONDENSATE PUMP
CR CEILING REGISTER
CS CONDENSATE STORAGE TANK
CSG CLEAN STEAM GENERATOR
CT COOLING TOWER
CU CONDENSING UNIT
CUH CABINET UNIT HEATER
CV CONSTANT VOLUME
CW COLD WATER (POTABLE)
CWCC CHILLED WATER COOLING COIL
CWP CONDENSER WATER PUMP
CWR CONDENSER WATER RETURN (TO COOLING
TOWER)
CWS CONDENSER WATER SUPPLY (FROM COOLING
TOWER)
D DAMPER - AUTOMATIC
D-1 OUTDOOR AIR DAMPER
D-2 RETURN AIR DAMPER
D-3 RELIEF AIR DAMPER
Db DRY BULB TEMPERATURE dB DECIBEL
DD-1 DESIGN DEVELOPMENT SUBMISSION 1
DD-2 DESIGN DEVELOPMENT SUBMISSION 2
DDC DIRECT DIGITAL CONTROLS
DEG DEGREES
DF DIFFUSER
DIA DIAMETER
DIW DEIONIZED WATER
DP DEW POINT TEMPERATURE
DP DIFFUSER PLATE
DPA DIFFERENTIAL PRESSURE ASSEMBLY
DPS DIFFERENTIAL PRESSURE SENSOR
DX DIRECT EXPANSION
DXCC DIRECT EXPANSION COOLING COIL
EA EXHAUST AIR
EAT ENTERING AIR TEMPERATURE
EC EVAPORATIVE COOLER
ECC ENGINEERING CONTROL CENTER
ECU EVAPORATIVE CONDENSER UNIT
EDH ELECTRIC DUCT HEATER
EER ENERGY EFFICIENCY RATIO
EF EXHAUST FAN
EG EXHAUST GRILLE
EGS EMERGENCY GAS SHUTOFF
EGT ENTERING GLYCOL TEMPERATURE
EH EXHAUST HOOD
EJ EXPANSION JOINT
EMD END OF MAIN DRIP (STEAM)
ENT ENTERING
ER EXHAUST REGISTER
ERC ELECTRIC REHEAT COIL
ERP ELECTRIC RADIANT PANEL
ESP EXTERNAL STATIC PRESSURE
ET EXPANSION TANK
ETO ETHYLENE OXIDE
EUH ELECTRIC UNIT HEATER
EWC EVAPORATIVE WATER COOLER
EWT ENTERING WATER TEMPERATURE
EX. EXISTING
F FAHRENHEIT
F&T FLOAT AND THERMOSTATIC
F/SDPR COMBINATION FIRE SMOKE DAMPER
FA FREE AREA
FC FLEXIBLE CONNECTION
FCU FAN COIL UNIT (4 PIPE)
FCUC FAN COIL UNIT COOLING ONLY
FCUH FAN COIL UNIT HEATING ONLY
FCW FORWARD CURVED WHEEL (FAN)
FD FLOOR DRAIN
FD FIRE DAMPER
A/E ARCHITECT / ENGINEER
AAHX AIR TO AIR HEAT EXCHANGER
AAV AUTOMATIC AIR VENT
AB AIR BLENDER
ACC AIR COOLED CONDENSER
ACCH AIR COOLED CHILLER
ACCU AIR-COOLED CONDENSING UNIT
ACD AUTOMATIC CONTROL DAMPER, MODULATING
ACD-TP AUTOMATIC CONTROL DAMPER, TWO POSITION
ACFM ACTUAL CUBIC FEET PER MINUTE
ACU AIR CONDITIONING UNIT
AD ACCESS DOOR
AF AFTER FILTER
AFCV AIR FLOW CONTROL VALVE
AFF ABOVE FINISHED FLOOR
AFMD AIR FLOW MEASURING DEVICE
AFW AIR FOIL WHEEL (FAN)
AHU AIR HANDLING UNIT
AMP AMPERE
AP ACCESS PANEL
APD AIR PRESSURE DROP
ARI AIR CONDITIONING AND REFRIGERATION INSTITUTE
AS AIR SEPARATOR
ASME AMERICAN SOCIETY OF MECHANICAL ENGINEERS
AW AIR WASHER
AXF AXIAL FLOW
B BOILER
BD BUTTERFLY DAMPER
BDD BACKDRAFT DAMPER
BDR BASE BOARD RADIATOR
BFP BACKFLOW PREVENTER
BFT BOILER PLANT FIRE TUBE
BG BOTTOM GRILLE
BHP BRAKE HORSEPOWER
BHW HOT WATER HEATING BOILER
BHX BOILER BLOWDOWN HEAT EXCHANGER
BIW BACKWARD INCLINED WHEEN (FAN)
BR BONE REGISTER
BSC BIOLOGICAL SAFETY CABINETS
BT BLOWOFF TANK
BTC BLOWOFF TANK CONTROL VALVE
BTU BRITISH THERMAL UNIT
BTUH BRITISH THERMAL UNIT PER HOUR
BWT BOILER PLANT WATER TUBE
C CENTIGRADE (CELSIUS)
CC COOLING COIL
CCD COOLING COIL CONDENSATE DRAIN
CD CEILING DIFFUSER
CD-1 CONSTRUCTION DOCUMENTS (SUBMISSION 1)
CD-2 CONSTRUCTION DOCUMENTS (SUBMISSION 2)
CENT CENTRIFUGAL
CFH CUBIC FEET PER HOUR
CFM CUBIC FEET PER MINUTE
CFP CHEMICAL FEED PUMP
CFT CUBIC FEET
CG CEILING GRILLE
CH CHILLER
CHP CHILLED WATER PUMP
CHR CHILLED WATER RETURN
CHS CHILLED WATER SUPPLY
CHW CHILLED WATER
CI CAST IRON
CM CARBON MONOXIDE
CM CUBIC METER
CO2 CARBON DIOXIDE
COMP COMPRESSOR UNIT
COP COEFFICIENT OF PERFORMANCE
BAS BUILDING AUTOMATION SYSTEMS
DO DIGITAL OUTPUT
DI DIGITAL INPUT
AI ANALOG INPUT
AO ANALOG OUTPUT
AV ANALOG VARIABLE
BV BINARY VARIABLE
VEG 20.13
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Fi le
P at h
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
321 4 5 6 7 8 9 10
Project Director
Issued: Date:
750 W HAMPDEN AVE
SUITE #300
ENGLEWOOD CO 80110
(720) 550-6307
WWW.VALHALLAENGINEERING.COM
635-20-102
921 NE 13TH ST OKLAHOMA CITY, OK 73104
CONSULTANTS: ARCHITECT/ENGINEERS: STAMP: REPLACE AIR HANDLERS 4, 7, 14,
AND FCU
100% CONSTRUCTION
DOCUMENTS
PHASING NOTES:
THE FOLLOWING PHASING REQUIREMENTS ARE INTENDED TO DEFINE PERFORMANCE-BASED
PARAMETERS TO ENSURE COMPLETION OF THE PROJECT WITH MINIMAL DISRUPTION TO THE
FACILITY. THE CONTRACTOR SHALL PLAN ITS MEANS AND METHODS AND ALLOCATE TIME AND
RESOURCES AS NECESSARY TO MEET THE MINIMUM REQUIREMENTS HEREIN. THE CONTRACTOR IS
REQUIRED TO DEVELOP A SCHEDULE PER SPECIFICATION REQUIREMENTS THAT COVERS ALL
ASPECTS OF THE SCOPE OF WORK REQUIRED BY THE CONTRACT DOCUMENTS. GC SHALL
COORDINATE WORK WITH VHA COR FOR ACCESS TO SPACES SERVED. SPECIFIC ADDITIONAL
REQUIREMENTS ARE DESCRIBED IN SPECIFICATIONS 01 00 00, 23 05 11 AND THE SPECIFICATION SET
AS A WHOLE.
EACH AHU IN THE PROJECT SHALL BE CONSIDERED A SEPARATE PHASE WITH SEPARATE
SUBSTANTIAL COMPLETION, TAB, CX, PUNCH-LIST, AND CLOSEOUT REQUIREMENTS PER
SPECIFICATIONS. SCOPE IN EACH PHASE MUST BE COMPLETED AND CLOSED OUT BEFORE MOVING
TO THE NEXT PHASE.”
SEQUENCE OF WORK SHALL BE:
1. AHU-7
2. AHU-14
3. AHU-4
UNLESS OTHERWISE NOTED, ALL WORK SHALL BE CONDUCTED DURING NIGHT OR WEEKEND SHIFTS
AND SPACES SHALL BE RETURNED TO THE VHA COR OR REPRESENTATIVE EACH MORNING.
MECHANICAL EQUIPMENT ROOMS ARE EXEMPT FROM THIS REQUIREMENT. PROVIDE TEMPORARY
AHUs AS REQUIRED TO KEEP ALL SPACES SERVED CONDITIONED THROUGHOUT THE COURSE OF
WORK. SEE TEMP AHU SCHEDULES FOR MINIMUM REQUIREMENTS.
AHU-14 AND AHU-7 MAY BE SERVED BY THE SAME TEMPORARY UNIT. CONTRACTOR'S OPTION: IR SUITE SERVED BY AHU-7 CAN BE SHUT DOWN FOR ONE CONTINUOUS WEEK. IF CONTRACTOR CAN COMPLETE WORK PER THE DOCUMENTS WITHIN 1 WEEK INCLUDING WEEKENDS (9 CALENDAR DAYS)
AND RETURN SPACE TO VHA, TEMPORARY UNIT FOR AHU-7 WILL NOT BE REQUIRED. REFER TO
SPECIFICATIONS FOR POTENTIAL VHA ACTIONS IF THERE ARE DELAYS IN RETURNING TO SPACE TO
OPERATION.
REQUIREMENTS FOR AHU-4: FAN COILS AND VAVS REPLACED PER THE DOCUMENTS MUST BE
COMPLETED PRIOR TO START OF AHU-4 WORK AND MAY BE COMPLETED CONCURRENT WITH WORK
SHOWN FOR AHU-7 AND AHU-14. MODIFY EXISTING AHU-4 OUTPUT AS REQUIRED TO MAINTAIN OA
CFM TO SPACES SERVED. COORDINATE FOR ACCESS TO PHARMACY THROUGH VHA COR. SPACES
SHALL BE RETURNED TO THE VHA COR EACH MORNING. VHA WILL PROVIDE TEMPORARY SPOT
COOLING FOR FCU AND VAV REPLACEMENT AREAS. COORDINATE WITH THE VHA COR IN ADVANCE
FOR SCHEDULED WORK AREAS IN ORDER TO ALLOW PRIOR SPOT COOLER MOVEMENT AND SETUP.
NOTE: REMOVE CEILING TILE, GRID. SUSPEND DEVICES AND CEILING MOUNTED EQUIPMENT IN THE
AREAS OF WORK TO ALLOW INSTALLATION OF MECHANICAL DUCTWORK, EQUIPMENT AND AIR
TERMINALS. REINSTALL EXISTING CEILING, TILE, GRID AND ALL DEVICES. REPLACE ANY DAMAGED
TILE GRID OR LIGHT FIXTURES WITH LIKE KIND IF DAMAGED. CONTRACTOR SHALL REPLACE
REMOVED CEILING TILE, GRID, DEVICES AND EQUIPMENT AT THE END OF THE SHIFT. A FIRE WATCH
WILL BE REQUIRED IF CEILING IS OPEN FOR MORE THAN 10 CONSECUTIVE HOURS. REFER TO
SPECIFICATION 01 00 00 FOR ADDITIONAL REQUIREMENTS.
GHR GLYCOL WATER RETURN
GHS GLYCOL WATER SUPPLY
STAMP:
T
TT
M
MT
PT
TT
FT
IT
CT
SPS
SD
PDT
KR
TSL
HS
ZC
LC
LT
PDS
TSH
EPT
AT
CO2
AT
CO
AT
OC
LTCP
HVAC
ECC
TC
VSMC
PC
SC
FC
PSH
FSH
PSL
CONTROLS SYMBOLS
DRAWING SYMBOLS
26-SF 3
26-TU-I-I
DETAIL NUMBER
DRAWING NUMBER WHERE SHOWN
SECTION LETTER
TYPICAL UNIT NO.
BUILDING NO. WHERE EQUIPMENT IS LOCATED.
SUPPLY FAN NO. 3 IN BUILDING NO. 26
EQUIPMENT ABBREVIATION (SUPPLY FAN)
ITEM NUMBER (TERMINAL UNIT NO. 1)
ITEM (TERMINAL UNIT SHOWN)
SERVED BY AIR HANDLER UNIT NO. 1
DRAWING NUMBER WHERE DRAWN
BUILDING NO. WHERE EQUIPMENT IS LOCATED
H4
H7
A
BDD
FD
VD
SUPPLY
RETURN45°
45°
N
1/24
F/S DPR
GENERAL PIPING SYMBOLS
FE
AV
MV
SCH
SH
TH
PS
RC
WB
CSH
SS
* TYPE NUMBERS REFER TO MANUFACTURER'S STANDARDIZATION SOCIETY STANDARD PRACTICE SP-58
VR
CTPS
CTPD
FWPS
FWPD
CF
FWS
BWS
CBD
BO
TC
A
OFL
HW
SW
CW
FOR
FOS
LPG(I)
G(I)
G
HVAC PIPING SYMBOLS
HPS
HPR
MPS
MPR
LPS
LPR
PC
HWS
HWR
GHS
GHR
V
SWS
SWR
CWR
CHR
GCR
RL
RS
RHG
CWS
CHS
GCS
MW
D
GRR
GRS
X
AIR TERMINAL SYMBOLS
MB
KC
FSL
A
M
BAS
HIGH PRESSURE STEAM (60 PSIG AND ABOVE)
HIGH PRESSURE STEAM CONDENSATE RETURN
MEDIUM PRESSURE STEAM (16 PSIG THRU 59 PSIG)
MEDIUM PRESSURE STEAM CONDENSATE RETURN
LOW PRESSURE STEAM (15 PSIG AND BELOW)
LOW PRESSURE STEAM CONDENSATE RETURN
CONDENSATE PUMP DISCHARGE
HEATING WATER SUPPLY
HEATING WATER RETURN
GLYCOL-WATER HEATING SUPPLY
GLYCOL-WATER HEATING RETURN
SOLAR WATER SUPPLY
SOLAR WATER RETURN
REFRIGERANT LIQUID
REFRIGERANT SUCTION
REFRIGERANT HOT GAS
CONDENSER WATER SUPPLY (FROM TOWER)
CONDENSER WATER RETURN (TO TOWER)
CHILLED WATER SUPPLY
CHILLED WATER RETURN
CHILLED GLYCOL-WATER SUPPLY
CHILLED GLYCOL-WATER RETURN
MAKE-UP WATER
DRAIN LINE
VENT LINE
GLYCOL-WATER RUN AROUND SUPPLY
GLYCOL-WATER RUN AROUND RETURN
EXISTING PIPE TO BE REMOVED
FEEDWATER PUMP DISCHARGE
FEEDWATER PUMP SUCTION
CONDENSATE TRANSFER PUMP DISCHARGE
CONDENSATE TRANSFER PUMP SUCTION
VACUUM CONDENSATE RETURN
TUBE CLEANER WATER SUPPLY
BOILER BLOWOFF
CONTINUOUS BLOWDOWN
BOILER WATER SAMPLE
FEEDWATER SAMPLE (FROM DEAERATOR)
CHEMICAL FEED
OVERFLOW
COMPRESSED AIR
NATURAL GAS MAIN FUEL
NATURAL GAS IGNITER FUEL
LIQUEFIED PETROLEUM GAS IGNITER FUEL
FUEL OIL SUPPLY
FUEL OIL RETURN
COLD WATER (CITY WATER)
SOFTENED WATER
HOT WATER
ROLLER-TYPE HANGER
VARIABLE SPRING-TYPE HANGER (TYPE 51)*
SPRING CUSHION-TYPE HANGER (TYPE 48 OR 49)*
CLEVIS-TYPE HANGER
TRAPEZE HANGER (PROVIDE U-BOLT PIPE ATTACHMENT
TO TRAPEZE EXCEPT WHERE RH ARE INDICATED)
FLOOR-SUPPORTED PIPE STAND
RISER CLAMP (TYPE 42)*
WALL BRACKET (TYPE 31, 32, 33)*
CONSTANT SUPPORT HANGER (TYPE 54, 55, 56)*
SLIDING SUPPORTS (TYPE 35)*
RH
DIRECTION OF PIPE PITCH (DOWN)
DIRECTION OF FLOW
ANCHOR
REDUCER OR INCREASER
ECCENTRIC REDUCER
TOP CONNECTION, 45° OR 90°
BOTTOM CONNECTION, 45° OR 90°
SIDE CONNECTION
CAPPED OUTLET
RISE OR DROP IN PIPE
UNION
PIPE UP
PIPE DOWN
INVERTED BUCKET TRAP SET INCLUDING
PIPING ACCESSORIES SEE DETAIL
FLOAT & THERMOSTATIC TRAP SET INCLUDING
PIPING ACCESSORIES SEE DETAIL
THERMOSTATIC TRAP SET INCLUDING
PIPING ACCESSORIES SEE DETAIL
THERMOMETER
PRESSURE GAGE
FLOW ELEMENT
REFRIGERANT SIGHT GLASS
TEST PLUG (PRESSURE/TEMPERATURE)
AUTOMATIC AIR VENT
MANUAL AIR VENT
QUICK-COUPLE HOSE CONNECTOR
CONNECT TO EXISTING
LIMIT OF DEMOLITION
AIR SEPERATOR
TERMINAL UNIT WITH REHEAT COIL
DOUBLE DUCT MIXING BOX.
FAN POWERED VARIABLE VOLUME
TERMINAL UNIT WITH HEATING COIL.
EXISTING DUCT TO BE REMOVED
LOUVER (LOUVER SPECIFIED IN ARCHITECTURAL
SECTION.)
FLEXIBLE DUCTWORK (INSULATED)
DUCT WITH SOUND LINING
MANUAL VOLUME DAMPER
FIRE DAMPER
BACK DRAFT DAMPER
COMBINATION FIRE/SMOKE DAMPER
POINT OF CHANGE IN DUCT CONSTRUCTION BY
STATIC PRESSURE CLASS. THE NUMBER ASSIGNS
PRESSURE CLASS (IN. OF WATER) WHICH WILL
ACCOMMODATE MAXIMUM OPERATING PRESSURE
IN THE DUCT SUBSECTION. THE SYMBOL CONTINUES
THE ASSIGNMENT UNTIL THE DUCT TERMINATES OR
ANOTHER SYMBOL APPEARS. A "N" SUPERSCRIPT
INDICATES NEGATIVE PRESSURE.
AUTOMATIC CONTROL DAMPER MODULATING
AUTOMATIC CONTROL DAMPER TWO POSITION
MANUAL SPLITTER DAMPER
STANDARD BRANCH SUPPLY OR RETURN, NO
SPLITTER (45° TAP)
DUCT MOUNTED COIL (HOT WATER OR STEAM
COIL)
DUCT MOUNTED COIL (ELECTRIC)
LC
M
VALVE SYMBOLS
GATE VALVE - THREADED/FLANGED
GLOBE VALVE - THREADED/FLANGED
GATE VALVE WITH 3/4" HOSE ADAPTER
CHECK VALVE
WYE STRAINER (WITH BALL VALVE & HOSE CONNECTION)
WYE STRAINER WITH VALVED DRAIN AND QUICK-COUPLE
FLEXIBLE CONNECTION
ANGLE GLOBE VALVE
BUTTERFLY VALVE
BALL VALVE
MODULATING CONTROL VALVE
MODULATING CONTROL BUTTERFLY VALVE
TWO POSITION CONTROL VALVE
THREE-WAY MODULATING CONTROL VALVE
THREE-WAY TWO POSITION CONTROL VALVE
PRESSURE REGULATING VALVE
PRESSURE SAFETY VALVE
AUTOMATIC BALANCING CONTROL VALVE
WATER BALANCE DEVICE
CIRCUIT SETTER VALVE
GATE VALVE WITH GLOBE-VALVED BYPASS
PLUG VALVE
CONTROL VALVE (CV) - FLOAT-OPERATED
PRESSURE REDUCING VALVE (PRV)
WATER LEVEL CONTROLLER
FLOW METER
ROOM THERMOSTAT/TRANSMITTER - WALL MOUNT
ROOM HUMIDISTAT (MOISTURE)/TRANSMITTER - WALL
MOUNT
TEMPERATURE TRANSMITTER
TEMPERATURE TRANSMITTER, AVERAGING ELEMENT
MOISTURE (HUMIDITY) TRANSMITTER
PRESSURE TRANSMITTER
STATIC PRESSURE SENSOR
FLOW TRANSMITTER
CURRENT TRANSMITTER
CONDUCTIVITY TRANSMITTER
SMOKE DETECTOR
PRESSURE DIFFERENTIAL TRANSMITTER
PRESSURE DIFFERENTIAL SWITCH
HAND SWITCH (HAND-OFF-AUTO SWITCH)
VALVE OR DAMPER POSITION CONTROLLER
LOCAL RECORDING TIME CLOCK (RUNTIME)
TEMPERATURE SWITCH, LOW (FREEZESTAT)
TEMPERATURE SWITCH, HIGH (FREEZESTAT)
LEVEL CONTROLLER
LEVEL TRANSMITTER
PRESSURE SWITCH HIGH
PRESSURE SWITCH LOW
ELECTRONIC TO PNEUMATIC TRANSDUCER
CARBON DIOXIDE TRANSMITTER
CARBON MONOXIDE TRANSMITTER
OCCUPANCY SENSOR
LOCAL TEMPERATURE CONTROL PANEL
HVAC CONTROL PANEL
VARIABLE SPEED MOTOR CONTROLLER
INTEGRATE CONTROL POINT ON REMOTE
GRAPHICS WORKSTATION AT ENERGY
CONTROL CENTER
TEMPERATURE CONTROLLER. SEE
SEQUENCE OF OPERATION
PRESSURE CONTROLLER. SEE SEQUENCE
OF OPERATION
SPEED CONTROLLER. SEE SEQUENCE OF
OPERATION
FLOW CONTROLLER. SEE SEQUENCE OF
OPERATION
FLOW SWITCH HIGH
FLOW SWITCH LOW
TIME CLOCK CONTROLLING EQUIPMENT ON
A SCHEDULE
TEMPERATURE SENSING ELEMENT FOR
TRANSMITTING TEMPERATURE TO EMCS
(PROVIDE 12 INCHES MINIMUM
LENGTH IN DUCT WHEN SPACE PERMITS.)
SENSOR WITH AVERAGING ELEMENT
TO TRANSMIT TEMPERATURE TO EMCS
MOTOR STARTER
ELECTRIC OPERATED CONTROL
DAMPER/OR VALVE
BUILDING AUTOMATION SYSTEM
03/26/2021 DD MR
M-002
MECHANICAL SYMBOLS
DUCTWORK SYMBOLS
TERMINAL UNIT SYMBOLS
A PTAC
A TWU
A
FCU
FCU
A
PTACA
CONVECTOR OR RADIATOR (RECESSED)
CONVECTOR OR RADIATOR (WALL HUNG)
FLOOR MOUNTED VERTICAL RECESSED FAN COIL UNIT.
LETTER INDICATES UNITSIZE.
FLOOR MOUNTED VERTICAL CABINET FAN
COIL UNIT. LETTER INDICATES UNIT SIZE.
THRU WALL AIR CONDITIONING UNIT.
LETTER INDICATES UNIT SIZE.
WINDOW TYPE AIR CONDITIONING UNIT.
LETTER INDICATES UNIT SIZE.
FLOOR MOUNTED HEAT PUMP. LETTER
INDICATES UNIT SIZE.
AIR CURTAIN
UNIT HEATER (HORIZONTAL)
UNIT HEATER (VERTICAL)
2'x2' RADIANT CEILING PANEL
2'x4' RADIANT CEILING PANEL
SUPPLY DUCT (UP & DOWN)
EXHAUST DUCT (UP & DOWN)
RETURN DUCT (UP & DOWN)
ROUND AND SQUARE 4-WAY CEILING DIFFUSERS
SQUARE 3-WAY CEILING DIFFUSERS
SQUARE 2-WAY CEILING DIFFUSERS
SQUARE 1-WAY CEILING DIFFUSERS
LINEAR SLOT DIFFUSER
SUPPLY TOP REGISTER OR GRILLE (WALL TYPE)
EXHAUST OR RETURN CEILING
REGISTER OR GRILLE
EXHAUST OR RETURN BOTTOM
REGISTER OR GRILLE (WALL TYPE)
EXHAUST OR RETURN REGISTER OR TOP GRILLE
(WALL TYPE)
VANED ELBOW & AIR SPLIT TYPE DUCT TAKE-OFF
CONNECT NEW DUCT TO EXISTING DUCT
INCLINED RISE, IN DIRECTION OF AIR FLOW
INCLINED DROP, IN DIRECTION OF AIR FLOW
LIMIT OF DEMOLITION
FLEXIBLE CONNECTION, EQUIPMENT, VIBRATION,
OR SEISMIC
VANED ELBOW (PROVIDE ALL SQUARE OR
RECTANGULAR ELBOWS WITH VANES EVEN IF
SYMBOL IS MISSING)
VANED ELBOW (SHORT RADIUS)
STANDARD RADIUS ELBOW (LONG RADIUS)
NEW DUCT (INSIDE DIMENSIONS: WIDTH x DEPTH)
EXISTING DUCT TO REMAIN
DN
DN
UP
UP
D
R
DNUP
FC
10x8
VEG 20.13
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Fi le
P at h
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
321 4 5 6 7 8 9 10
Project Director
Issued: Date:
750 W HAMPDEN AVE
SUITE #300
ENGLEWOOD CO 80110
(720) 550-6307
WWW.VALHALLAENGINEERING.COM
635-20-102
921 NE 13TH ST OKLAHOMA CITY, OK 73104
CONSULTANTS: ARCHITECT/ENGINEERS: STAMP: REPLACE AIR HANDLERS 4, 7, 14,
AND FCU
100% CONSTRUCTION
DOCUMENTS
03/26/2021 DD MR
M-501
MECHANICAL DETAILS
VEG 20.13
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Fi le
P at h
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
321 4 5 6 7 8 9 10
Project Director
Issued: Date:
750 W HAMPDEN AVE
SUITE #300
ENGLEWOOD CO 80110
(720) 550-6307
WWW.VALHALLAENGINEERING.COM
635-20-102
921 NE 13TH ST OKLAHOMA CITY, OK 73104
CONSULTANTS: ARCHITECT/ENGINEERS: STAMP: REPLACE AIR HANDLERS 4, 7, 14,
AND FCU
100% CONSTRUCTION
DOCUMENTS
"B" "B"
NOTES:
1. LATCHES SHALL BE OF THE WEDGE TYPE TO CLOSE DOORS TIGHTLY.
2. HINGES ON THE ACCESS DOORS SHALL HAVE NON-CORROSIVE PINS.
3. SEE SPECIFICATIONS FOR TECHNICAL REQUIREMENTS.
ACCESS PANEL
ACCESS DOOR
CASING
GASKET HANDLE INSIDE
FLEXIBLE
WASHER
FACTORY
FABRICATED
LATCH
SECTION "B-B"
INSULATION
DUCT
GASKET
INSULATION
INSULATION
"A"
"A"
SECTION "A-A"
NOTE:
ALL DUCT WORK RISERS WHICH ARE RUN EXPOSED, SUCH AS THRU ATTIC FLOORS AND FAN ROOM
FLOORS SHALL BE PROVIDED WITH A 3" HIGH CONCRETE CURB AROUND OPENING FOR DUCT.
SEAL HOLE WITH FIREPROOFING
MATERIAL AFTER DUCT
INSTALLATION
2"x2"x1/4" ANGLE INSTALL ON
BOTH LONG DIMENSION SIDES
OF DUCT.
DUCT RISER - SEE FLOOR
PLANS FOR DETAILS
SEAL HOLE WITH
FIREPROOFING
MATERIAL AFTER DUCT
INSTALLATION
FLOOR
EXTEND ANGLE 3"
BEYOND DUCT
DUCT RISER - SEE FLOOR
PLANS FOR SIZES
SHEET METAL SCREWS 4" ON
CENTER
1 1/2"x1 1/2"x1/8" ANGLE INSTALL ON
BOTH LONG DIMENSION SIDES OF
DUCT. FOR DUCTS OVER 60" USE
2"x2"x1/8" ANGLE.
HOLE IN STRUCTURAL FLOOR
DUCT RISER
0.5 INCH WG TO 2 INCHES WG DUCT RISER SUPPORT
ARRANGE RISER SO
REINFORCER TRANSVERSE
JOINT IS AT RISER SUPPORT
POINT
FLOOR
2 INCHES WG TO 4 INCHES WG DUCT RISER SUPPORT
HOLE IN STRUCTURAL FLOOR
DUCT RISER
DESIGNER'S NOTES:
1. THE SUPPLY REGISTER TAKE-OFF MAY BE USED FOR UP UP TO 25% OF THE MAIN
DUCT CFM. THE BRANCH DUCT TAKE-OFF MAY BE USED FOR UP TO 15% OF THE MAIN
DUCT CFM ANYTIME AND UP TO 40% WHEN THE MAIN DUCT VELOCITY IS 1000 FPM
OR LESS. THE AIR SPLIT DUCT TAKE-OFF SHALL BE USED IN ALL OTHER CASES AND
MAY BE USED AT ANYTIME.
2. SHOW ALL VOLUME DAMPERS ON FLOOR PLANS.
AIR SPLIT DUCT TAKE-OFF
PLAN VIEW
BRANCH DUCT TAKE-OFF PLAN VIEW
AIR FLOW
AIR FLOW
AI
R
FL
OW
SUPPLY REGISTER
OR BRANCH DUCT
TURNING VANES
MAIN
SUPPLY
DUCT
SEE FLOOR PLAN FOR
SPLIT DIMENSION
PROVIDE VOLUME
DAMPER
PROVIDE VOLUME
DAMPER
1/4 W OR 4" MIN.
AIR
FLOW
MAIN SUPPLY DUCT
W
AI
R
FL
OW
NOTES:
1. DELETE INSULATION STAND-OFF ON DUCTWORK WITHOUT EXTERIOR
INSULATION.
2. DETAIL SHOWS SINGLE BLADE DAMPER. DAMPER INSTALLATION SHALL BE
SIMILAR FOR MULTI-BLADE DAMPERS & ROUND DAMPERS.
INSULATION SEE
SPECIFICATION
DAMPER BLADE
1/8" CLEARANCE
ALL AROUND
OUTSIDE END BEARING
INSIDE END BEARING
HANDLE WITH
LOCKING QUADRANT
INSULATION
STAND-OFF
1/2" ROUND ROD PIN
DUCT
STIFFEN BLADE
AS REQUIRED
SIDE ELEVATION SECTION
NOTES:
1. PROVIDE BRACING TO LIMIT THE AMPLITUDE OF WALL VIBRATION AND WALL
DEFLECTION TO SPECIFIED MAXIMUMS.
2. MINIMUM BRACING REQUIREMENTS:
MAXIMUM DUCT WIDTH MAXIMUM SIZE ANGLE MAXIMUM SPACING
(IN.) (IN.) (IN.)
UP TO 26 NONE
27 TO 40 1-1/2x1-1/2x3/16 72 41 TO 60 2x2x3/16 48 61 TO 72 2x2x3/16 24
3. INSULATION: FOR COLD DUCTS INSULATE BRACES AND PROVIDE VAPOR
BARRIER. REFER TO SPECIFICATION SECTION 23 07 11.
GALVANIZED ANGLE
IRON OR EQUIVALENT
STRENGTH CHANNEL
ALL THREAD ROD.
MINIMUM 3/8" Ø
INSULATION
NOTES:
1. ALL VANE ELBOWS SHALL BE CONSTRUCTED AND INSTALLED AS DETAILED BY
SMACNA.
2. WHEN W1 DOES NOT EQUAL W2, VANE SHALL BE SINGLE THICKNESS VANE
TYPE REGARDLESS OF W DIMENSION.
3. ALL SINGLE THICKNESS VANES SHALL HAVE A 2" RADIUS, 1 1/2" MAXIMUM
SPACE BETWEEN VANES AND A 3/4" TRAILING EDGE.
4. WHEN W1 EQUALS W2 AND W1 IS GREATER THAN 20", VANES SHALL BE DOUBLE
VANE TYPE.
5. ALL 90 DEGREE ELBOWS SHALL HAVE VANES.
6. REFER TO SPECIFICATION 23 31 00 FOR TECHNICAL REQUIREMENTS.
W
W1
HOUSING
WELDED TO
DUCT SECTION
ROUND OR
FLAT OVAL
DUCT
SECTION
COVER WITH HANDLE
AND CHAIN
RETAINER
GASKETED AND
PRESSURE SEALED
NOTES:
1. THE INTERIOR SURFACE OF ALL RADIUS ELBOWS SHALL BE MADE ROUND.
2. ALL STANDARD RADIUS ELBOWS CAN BE SUBSTITUTED WITH SHORT RADIUS
ELBOWS. ALL SHORT RADIUS ELBOWS SHALL HAVE VANES. VANES SHALL BE
CONSTRUCTED, SUPPORTED AND FASTENED AS RECOMMENDED BY SMACNA.
3. REFER TO SPECIFICATION SECTION 23 31 00 FOR ADDITIONAL INFORMATION.
R SHALL
EQUAL OR
BE
GREATER
THAN W.
W
R
STANDARD RADIUS OR
LONG RADIUS ELBOW
MAIN EXHAUST OR RETURN
PLAN VIEW
AIR FLOW
AIR FLOW
W
PROVIDE VOLUME DAMPER
AT EACH BRANCH DUCT
1/4W OR 4" MIN.
BRANCH DUCT
VD
NOTE:
TABULATED DATA FROM SMACNA ALLOWS FOR
DUCT REINFORCING AND INSULATION, BUT NO
EXTERNAL LOAD.
LOAD RATED
FASTENER
BAND OF SAME SIZE
AS HANGER STRAP
HANGER STRAPS OR RODS
MAX. DUCT Ø
(IN.)
QUANTITY/SIZE
(IN.)
MAX. LOAD
(LBS.)
MAX. SPACING
(IN.)
ONE 1 X 22 GA STRAP
ONE 1 X 18 GA STRAP
ONE 1 X 16 GA STRAP
TWO 3/8 Ø RODS
TWO 1/2 Ø RODS
50" Ø &
UNDER
HANGER RODS
BAND
OVER 50" Ø
SCALE: NO SCALE
ACCESS PANEL AND DOOR DETAIL
SCALE: NO SCALE
DUCT RISER SUPPORTS
SCALE: NO SCALE
EXHAUST OR RETURN BRANCH DUCTWORK
SCALE: NO SCALE
SUPPLY DUCTWORK TAKE-OFFS
SCALE: NO SCALE
ROUND DUCT HANGERS
SCALE: NO SCALE
VOLUME DAMPER DETAIL
SCALE: NO SCALE
FLAT OVAL DUCT HANGERS/REINFORCEMENT
SCALE: NO SCALE
DUCTWORK SQUARE VANE ELBOWS
SCALE: NO SCALE
ACCESS SECTION FOR ROUND/OVAL DUCT
SCALE: NO SCALE
DUCTWORK RADIUS ELBOWS
NEW FCU PER PLANS &
SCHEDULES
(E) DUCT (E) DUCT (E) SA DUCT
FROM NEW OA AHU
SCALE: NO SCALE
TYPICAL FCU RETROFIT DUCT REWORK SCOPE
1A
FCU REPLACEMENT TYPES DESCRIPTION
· TYPE A: FCU REPLACING EXISTING FCU. OA REVISED TO
DELIVER DIRECT TO SPACE SEPARATE FROM NEW FCU.
· TYPE B: FCU REPLACING EXISTING VAV. OA REVISED TO
DELIVER DIRECT TO SPACE SEPARATE FROM NEW FCU.
INLET DUCT REVISED TO PROVIDE RETURN AIR TO NEW
FCU.
· TYPE C: FCU REPLACING EXISTING FCU. NO OA OR RA
CHANGES.
· TYPE D: FCU REPLACING EXISTING VAV. OA DELIVERED
TO NEW FCU MIXING PLENUM . INLET DUCT REVISED TO
PROVIDE RETURN AIR TO NEW FCU
DETAIL KEYED NOTE
APPLIES TO FCU
REPLACEMENT
TYPE
1. PROVIDE FLEXIBLE FABRIC DUCT CONNECTIONS, TYP. A, B, C
2. PROVIDE DUCT EXTENSIONS, TRANSITIONS, AND OFFSETS
AS REQUIRED TO RECONNECT TO EXISTING DUCT MAINS. A, B, C
3. PROVIDE NEW RA DUCT AND GRILLE. REF: PLANS FOR
APPROXIMATE LOCATION. VERIFY WITH ABOVE CEILING
CONDITIONS IN THE FIELD.
B, D
4. NEW 'R1' PER AIR DEVICE SCHEDULE WHERE NOTED ON
PLANS. B, D
5. DEMO PIECE OF EXISTING DUCT AND CAP REMAINING
ENDS TO SEPARATE FCU AND OA SYSTEMS. A, B
6. PROVIDE NEW SA BRANCH TAP, DUCT, AND DIFFUSER FOR
OA DELIVERY. REF: PLANS FOR APPROXIMATE LOCATION.
VERIFY WITH ABOVE-CEILING CONDITIONS IN THE FIELD.
A, B
7. NEW 'S1' PER AIR DEVICE SCHEDULE WHERE NOTED ON
PLANS. A, B
7 6
STAMP:
M-502
MECHANICAL DETAILS
VEG 20.13
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Fi le
P at h
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
321 4 5 6 7 8 9 10
Project Director
Issued: Date:
750 W HAMPDEN AVE
SUITE #300
ENGLEWOOD CO 80110
(720) 550-6307
WWW.VALHALLAENGINEERING.COM
635-20-102
921 NE 13TH ST OKLAHOMA CITY, OK 73104
CONSULTANTS: ARCHITECT/ENGINEERS: STAMP: REPLACE AIR HANDLERS 4, 7, 14,
AND FCU
100% CONSTRUCTION
DOCUMENTS
RIGID DUCT TO AIR TERMINAL
UNIT.
ROUND SHEET METAL
DUCT.
MAIN SUPPLY
"D"
45°MAX.
PLAN VIEW
SMACNA FIGURE 4-6 45°
LEED IN RIGID DUCT TO
AIR TERMINAL UNIT.
MAIN SUPPLY
PLAN VIEW
FLOW
FL
OW
SEE SPECIFICATIONS FOR CLAMPS
AND SEALANT (TYP.)
NOTE:
THE USE OF FLEXIBLE AIR DUCT CONNECTORS ARE NOT PERMITTED
FOR THE DEDICATED AHU SERVING THE SURGICAL SUITE.
TYPICAL
DIFFUSER OR
REGISTER IN
LAY-IN CLG.
THERMAL INSULATION
SEE SPECIFICATIONSSUPPORT SADDLE
FROM STRUCTURE
FLEXIBLE DUCT SIZE
SAME AS DIFFUSER
INLET: 5'-0" MAX LENGTH.
USE RIGID ELBOWS
FOR CHANGE OF
DIRECTION GREATER
THAN 45°
CONICAL OUTLET
BRANCH DUCT
VOLUME DAMPER
W/LOCKING QUAD
SHEET METAL
SADDLE
CEILING
12"
SEE NOTE 1
SEE NOTE 2
SEE NOTE 3
SOUND ATTENUATOR SEE
EQUIPMENT SCHEDULE.
FLEXIBLE AIR DUCT
CONNECTOR. SEE DETAIL.
DIFFUSER (TYP.)
SE
E
NO
TE
SEE SPECIFICATIONS FOR
CLAMPS AND SEALANT (TYP.) SEE NOTE 5
AIR TERMINAL
UNIT (CV OR VAV)
NOTES:
1. RIGID STRAIGHT TERMINAL UNIT INLET LENGTH SHALL BE A MINIMUM OF 3 TIMES THE DIAMETER OF INLET
2. A FLEXIBLE AIR DUCT CONNECTOR IS NOT MANDATORY FOR INLET TO THIS BOX, BUT ALLOWED TO ACCOMMODATE
MINOR OFFSETS. MAXIMUM LENGTH 3'-0".
3. A BRANCH DUCT SERVING AN INDIVIDUAL BOX MAY BE THE SAME SIZE AS THE BOX INLET, PROVIDED THE EQUIVALENT LENGTH OF THE BRANCH DUCT, AS SHOWN, DOES NOT EXCEED 10 FEET. FOR LONGER LENGTHS, INCREASE THE DUCT SIZE AND PROVIDE A DUCT TRANSITION TO MAINTAIN THE DUCT STATIC PRESSURE DROP AT OR BELOW 0.2"/100'.
4. FLEXIBLE AIR DUCT CONNECTORS, WHEN USED FROM TERMINAL UNIT SUPPLY AIR DUCT TO DIFFUSER, SHALL NOT
EXCEED 5'-0". USE RIGID ELBOWS FOR CHANGE OF DIRECTION GREATER THAN 45°.
5. COMPONENT ARRANGEMENT MAY VARY BY MANUFACTURER. PROVIDE INSULATION W/VAPOR BARRIER FOR
CONNECTING DUCT SECTIONS.
5. REFER TO DIV 23 SPECIFICATIONS FOR TECHNICAL REQUIREMENTS.
FLANGED
CONNECTION ON FAN
SIDE
WASHER 1-1/2" MIN. TO 3" MAX. INSTALLED. 6"
NOMINAL WITH MATERIAL TAUT
FLEXIBLE
MATERIAL AS
SPECIFIED
1"x1/8" DRAW BAND 1"x1/8" BAND IRON
BOLT ON 4" CENTERS
5/16" FLANGE
DUCT
SHEET METAL
SCREWS ON 12"
CENTERS
RIVET ON 4"
CENTERS
SHEET METAL AS
SPECIFIED FOR
DUCTWORK.
1"x1/8" BAND IRON
BOLT ON 4" CENTERS
1" FLANGE & HEM
ALTERNATE
POSITION
OF…