This document outlines a federal construction contract opportunity and related technical specifications. The Oklahoma City VA Medical Center requires a contractor to replace air handling units impacting the pharmacy, lab, IR suites and ground floor in accordance with provided plans, drawings and specifications. All work will be performed at the Oklahoma City VAMC located at 921 NE 13th St. Oklahoma City, OK. Additionally, the technical specifications call for providing power for a temporary air handler by connecting to a spare breaker at Substation #3, installing approximately 450 feet of 4-inch conduit and conductors to a new 400-amp panel at the temporary unit's discretionary location. The conduit between Substation #4 and the air handler can be above ground and temporary.
View the file
Other files
Show all 15
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Power for Temporary Air Handler – Provide instead of temporary generator
A pathway exists between Substation #3 and Substation #4. Connect to spare breaker and set to 400 amps. Install 4-inch conduit and 4-600 MCM THHN/THWN plus #3 grounding conductor approximately 450 feet from Substation #3 through Substation room #4 to new panel at temporary air handler. Install new 400-amp panel for feed to temporary air handling unit. Specific panel location at discretion of VA.
Conduit between Substation #4 and air handler can be above ground and will be temporary.