36E77619B0003-008.pdf
PDF 12 MB Posted
- Solicitation number
- 36E77619B0003
About this file
36E77619B0003 ATTACHMENT 8 - Drawings 4 of 7.pdf
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 36E77619C0023-000.docx | DOCX document | |
| 36E77619B0003-0003002.pdf | ||
| 36E77619B0003-0003003.pdf | ||
| 36E77619B0003-0003004.pdf | ||
| 36E77619B0003-0003005.pdf | ||
| 36E77619B0003-0003000.docx | DOCX document | |
| 36E77619B0003-0003006.pdf | ||
| 36E77619B0003-0003001.pdf | ||
| 36E77619B0003-0002000.docx | DOCX document | |
| 36E77619B0003-0001001.pdf | ||
| 36E77619B0003-0001000.docx | DOCX document | |
| 36E77619B0003-000.docx | DOCX document | |
| 36E77619B0003-013.docx | DOCX document | |
| 36E77619B0003-005.pdf | ||
| 36E77619B0003-012.pdf | ||
| 36E77619B0003-002.pdf | ||
| 36E77619B0003-006.pdf | ||
| 36E77619B0003-009.pdf | ||
| 36E77619B0003-007.pdf | ||
| 36E77619B0003-011.pdf | ||
| 36E77619B0003-001.pdf | ||
| 36E77619B0003-003.pdf | ||
| 36E77619B0003-010.pdf | ||
| 36E77619B0003-004.pdf | ||
| 36E77619B0003.docx | DOCX document |
Show all 25
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
eric.slaughter Text Box eric.slaughter Text Box
CONSTRUCTION DOCUMENTS
eric.slaughter Text Box 06/21/2017 eric.slaughter
2017.06.21 eric.slaughter Text Box
CONSTRUCTION DOCUMENTS
eric.slaughter Text Box 06/21/2017 eric.slaughter eric.slaughter Text Box
CONSTRUCTION DOCUMENTS
eric.slaughter Text Box 06/21/2017 eric.slaughter eric.slaughter Text Box
CONSTRUCTION DOCUMENTS
eric.slaughter Text Box 06/21/2017 eric.slaughter eric.slaughter Text Box
CONSTRUCTION DOCUMENTS
eric.slaughter Text Box 06/21/2017 eric.slaughter eric.slaughter Text Box
CONSTRUCTION DOCUMENTS
eric.slaughter Text Box 2017.06.21 eric.slaughter
06/21/2017 eric.slaughter Text Box
CONSTRUCTION DOCUMENTS
eric.slaughter Text Box 2017.06.21 eric.slaughter eric.slaughter Text Box 2017.06.21 eric.slaughter Text Box
CONSTRUCTION DOCUMENTS
eric.slaughter eric.slaughter Text Box 2017.06.21 eric.slaughter Text Box
CONSTRUCTION DOCUMENTS
eric.slaughter eric.slaughter Text Box
CONSTRUCTION DOCUMENTS
eric.slaughter Text Box 06/21/2017 eric.slaughter
3/8" POWERS HYDROGUARD SERIES
e480 COMBINATION T/P TEMPERING
VALVE W/ INTEGRAL CHECK STOPS.
SET DISCHARGE TEMPERATURE AT 105F
H&CW TO B.F.
LAVATORY OR SINK
1/2" H&CW
3/8" CP TUBE BEND
W/ TUBING BENDER.
PROVIDE ADEQUATE
CLEARANCE
AROUND TRAP AND
STOP VALVES
ANGLE STOP VALVE
BEHIND WALL
1/2"
1/2"
PROVIDE ACCESS PANEL IN
SOLID CEILINGS FOR EACH
TRAP PRIMER OR GROUP
OF TRAP PRIMERS
TRAP PRIMER
FLOOR
DRAIN
1/2" TYPE "K" SOFT COPPER
OR PEX TUBING, W/ 1/2"
ARMAFLEX INSULATION IN
GROUND OR 1/2" TYPE "L"
HARD COPPER IF ACCESSIBLE
FROM FLOOR BELOW
1/2" TYPE "L" HARD
COPPER. DROP DOWN
IN WALL OR CHASE TO
BELOW FLOOR
1/2"
CW LINE
BALL VALVE
CEILING
FLOOR
WALL LINE12" (300 mm)
PLAN
PIPE SUPPORT
ELEVATION
FINISHED
FLOOR
PIPE TO DRAIN (TYP)
WATER
LINE FROM
METER
AIR GAP
FITTING
COLD WATER
TO SYSTEM
12" [300mm] MIN
TO BOTTOM OF
RELIEF OPENINGS
REDUCED PRESSURE
PRINCIPAL BACKFLOW
PREVENTER WITH GATE VALVES
CONCRETE FILL
TILE FLOOR
CEMENT BED
LOOSE GRAVEL
AT WEEP HOLES
3mm TO 6mm SIZE
NICKEL BRONZE
ADJUSTABLE
STRAINER
CLAMP WATERPROOF
MEMBRANE INSIDE
OF DRAIN BODY
WATERPROOF
MEMBRANE
STRUCTURAL SLAB
FLASHING CLAMP
WITH WEEP HOLES
THREADED,
CAULKED OR NO-
HUB CONNECTION
PROVIDE A METAL
SUPPORT PLAT WHEN
DRAIN IS INSTALLED IN
AN EXISTING FLOOR -
CAULK AROUND DRAIN
PRIOR TO RE-GROUTING
6' -6
[1 m m
T O
C E
N T
E R
LI
N
E O
F O
U T
LE
T
6' -0
[1 m m
5' -4
[1 m m
T O
C E
N T
E R
LI
N
E O
F O
U T
LE
T
3' -4
[1 m m
2' -9
[8 m m
SHOWER
CONTROL
TYPE T/P
WARP ENTIRE FLOOR
(ASSUMES TOPPING SLAB)
DRAIN
GRAB BAR
24"
[600 MM]
SLIDE BAR
2' -9
[8 m m
] 3' -6
[1 m m
5' -6
[1 m m
6' -8
[2 m m
SHOWER HEAD
VACUUM
BREAKER
CURTAIN ROD
6"
[150 mm]
9"
[225 mm]
9"
[225 mm]
6"
[150 mm]
FD
P
BRINE
TANK
P
FD
BRUNER -------
WATER SOFTENER
BACKWASH
PIPE.
DISCHARGE
TO FD
AUTOMATIC
BACKWASH
CONTROL
MANHOLE
RAW WATER BYPASS
DIELECTRIC UNION
WATER
METER
OUTLET
PRESSURE
GAUGE
SOFT WATER
SAMPLING
COCK
RAW CW
SOFT CW
CW
HWR
HW
GG
WH-2WH-1
STRAP-ON
AQUASTAT
CHECK VALVE (TYP)
DOMESTIC HW
RECIRC. PUMP
EXPANSION TANK ET-1
THERMOMETER (TYP)
BALL VALVE (TYP)
INSULATING UNION (TYP)
DRAFT DIVERTER (TYP)
PIPING TO BE EQUAL LENGTHS
TO EACH WATER HEATER
GAS FLUE THRU ROOF (TYP)
TEMPERATURE &
PRESSURE RELIEF
VALVE (TYP)
RELIEF PIPE, SPILL
TO FLOOR DRAIN
(TYP)
LUBRICATED GAS
SHUT OFF COCK
(TYP)
FULL SIZE 6" LONG
DIRT LEG W/ PIPE
END CAP
FINISHED FLOOR
4" CONCRETE PAD
HOSE END DRAIN
VALVE (TYP)
3/4"
190°F 190°F
HOT WATER
RETURN
HOT WATER
SUPPLY
110 DEGREE
HOT WATER
SUPPLY
TEMPERATURE
GAGES
MIXING VALVE
COLD WATER
RETURN
COLD WATER
SUPPLY
COLD WATER
INLET
SINK/LAVATORY
ANGLE STOP VALVE
(TYP.)
FINISH FLOOR
th re e-qu ar te rs in ch o ne fo ot on e-qu ar te r in ch o ne fo ot on e-ei gh th in ch o ne fo ot th re e-ei gh th s in ch o ne fo ot on e-ha lf in ch o ne fo ot on e in ch o ne fo ot on e an d on e-ha lf in ch o ne fo ot
B th re e in ch es o ne fo ot
SCALE
PROJECT PRINCIPAL
PROJECT ARCHITECT
ELECTRICAL ENGINEER
PROJECT MANAGER
MECHANICAL ENGINEER
Use or disclosure of data contained on this sheet is subject to the restriction on the title page of this proposal.
Robinson
Robinson
Fischer
Gobreski
Daller
Danville, IL
Drawing Title
Approved:
Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
Revisions: Date
CONSULTANTS: ARCHITECT/ENGINEERS:
B
A
C
D
E
F
VA FORM 08-6231
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
Department of Veteran Affairs
LANDSCAPE ARCHITECT
CIVIL ENGINEER
STRUCTURAL ENGINEER
Cyr
Meneley
VanderWoude
PLUMBING ENGINEER Daller
CONSTRUCTION DOCUMENTS 06/21/2017
URS PROJECT NO. 25628010
7/
/2
:3 2:
A
M \\U
R S
In di an ap ol is
\ In di an ap ol is
\ P ro je ct s\
\Y dr aw
\Y F ac ili t\P df
\2
5_ 2_
F ire P ro te ct io n R ed lin es \2
0_
V A
_G re en H om es
_2
4_ M
P .r vt
PL722
Plumbing Details
TJBRDS2017.06.21
VA Danville - Construct Two Green HomesOne Indiana Square, Suite 2100
Indianapolis, IN 46204 United States
P: 317 532 5400 F: 317 532 5499 www.URScorp.com
550-316
NOT TO SCALE
SINGLE BARRIER-FREE LAVATORY & SINK
MIXING VALVE DETAIL
NOT TO SCALE
7 TRAP PRIMER PIPING DIAGRAM
NOT TO SCALE
5 BACKFLOW PREVENTER PIPING DETAIL
NOT TO SCALE
4 TYPE "C" FLOOR DRAIN
NOT TO SCALE
3 PATIENT SHOWER DETAIL
NOT TO SCALE
WATER SOFTENER, WATER HEATER / STORAGE
TANK PIPING DETAIL
NOT TO SCALE
GAS FIRED DOMESTIC WATER HEATER PIPING
DIAGRAM
132 & 133
NONE
PL722 PL722 PL722
PL722 PL722 PL722
PL722
PL722
PL722
Scale: NO SCALE
8 TYPICAL SINK CONNECTION
eric.slaughter Text Box 06/21/2017 eric.slaughter Text Box 2017.06.21 eric.slaughter
CONSTRUCTION DOCUMENTS