36C25618B0375-005.pdf
PDF 5 MB Posted
- Solicitation number
- 36C25618B0375
About this file
36C25618B0375 50_PL_VACLC_2018 01 11_IFB 02.pdf
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 36C25618B0375-00004000.docx | DOCX document | |
| 36C25618B0375-00004003.pdf | ||
| 36C25618B0375-00004005.pdf | ||
| 36C25618B0375-00004004.pdf | ||
| 36C25618B0375-00004001.pdf | ||
| 36C25618B0375-00004006.pdf | ||
| 36C25618B0375-00004002.pdf | ||
| 36C25618B0375-00003000.docx | DOCX document | |
| 36C25618B0375-00002000.docx | DOCX document | |
| 36C25618B0375-00002001.pdf | ||
| 36C25618B0375-00001000.docx | DOCX document | |
| 36C25618B0375-001.docx | DOCX document | |
| 36C25618B0375-009.pdf | ||
| 36C25618B0375-010.pdf | ||
| 36C25618B0375-007.pdf | ||
| 36C25618B0375-003.pdf | ||
| 36C25618B0375-004.pdf | ||
| 36C25618B0375-006.pdf | ||
| 36C25618B0375-008.pdf | ||
| 36C25618B0375-002.pdf | ||
| 36C25618B0375-000.docx | DOCX document |
Show all 21
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
A7 PLUMBING ABBREVIATIONS
RD ROOF DRAIN
RDL ROOF DRAIN LEADER
RL ROOF LEADER
RO REVERSE OSMOSIS WATER
RWL RAIN WATER LEADER
SAN SANITARY SEWER
SMACNA SHEET METAL AND AIR CONDITIONING CONTRACTORS
NATIONAL ASSOCIATION
SP SUMP PUMP
SPR SPRINKLER LINE
SQFT SQUARE FEET
SS STAINLESS STEEL
ST STORAGE TANK
SW STORM WATER
TCV TEMPERATURE CONTROL VALVE
TD TEMPEREATURE DIFFERENCE
TD TRENCH DRAIN
TDH TOTAL DYNAMIC HEAD
TEMP TEMPERATURE
TMV THERMOSTATIC MIXING VALVE
TP TRAP PRIMER
T STAT THERMOSTAT
TWR TEMPERED WATER RETURN
TWS TEMPERED WATER SUPPLY
TYP TYPICAL
UPC UNIFORM PLUMBING CODE
V VENT
VAC VACUUM
VB VACUUM BREAKER
VCO VACUUM CLEANER OUTLET
VP VACUUM PUMP
VS VENT STACK
VTR VENT THRU ROOF
W WASTE
WC WATER CLOSET
WCO WALL CLEANOUT
WG WATER GAGE
WH WALL HYDRANT
WH WATER HEATER
WHA WATER HAMMER ARRESTOR
WL WATER LINE
WM WATER METER
WPD WATER PRESSURE DROP
WS WASTE STACK
YCO YARD CLEANOUT
YH YARD HYDRANT
A/E ARCHITECT/ENGINEER
AD AREA DRAIN
AFF ABOVE FINISHED FLOOR
AFG ABOVE FINISHED GRADE
AG AIR GAP
AP ACCESS PANEL
AS AUTOMATIC SPRINKLER
ASD ADJUSTABLE SPEED DRIVES
ASD AUTOMATIC SPRINKLER DRAIN
ASHRAE AMERICAN SOCIETY OF HEATING, REFRIDGERATION
AND AIR CONDITIONING ENGINEERS
ASME AMERICAN SOCIETY OF MECHANICAL ENGINEERS
ASPE AMERICAN SOCIETY OF PLUMBING ENGINEERS
ASR AUTOMATIC SPRINKLER RISER
AV ACID VENT
AW ACID WASTE
BFP REDUCED PRESSURE BACKFLOW PREVENTER
BHP BRAKE HORSEPOWER
BSP BLACK STEEL PIPE
BT BATH TUB
BTU BRITISH THERMAL UNIT
BTUH BRITISH THERMAL UNIT PER HOUR
C CELSIUS
CGA COMPRESSED GAS ASSOCIATION
CI CAST IRON
CO CLEANOUT
CS CLINICAL SINK
CV CONTROL VALVE
DCW DOMESTIC COLD WATER
DHW DOMESTIC HOT WATER
DHWR DOMESTIC HOT WATER RETURN
DHWS DOMESTIC HOT WATER SUPPLY
DI DEIONIZED WATER
DN DOWN
DOE DEPARTMENT OF ENERGY
DS DOWNSPOUT
DW DISHWASHER
DWG DRAWING
DWR DRINKING WATER RETURN
DWS DRINKING WATER SUPPLY
DWV DRAIN WASTE VENT
EL ELEVATION
EMCS ENERGY MONOSERRAT AND CENTRAL SYSTEM
EPA ENVIRONMENTAL PROTECTION AGENCY
EPACT ENERGY POLICY ACT
ESC ESCUTCHEON
ESH EMERGENCY SHOWER
ET EXPANSION TANK
EWC ELECTRIC WATER COOLER
EWH ELECTRIC WATER HEATER
EWS EYE WASH STATION
EX EXISTING
F FAHRENHEIT
FCO FLOOR CLEANOUT
FCW FILTERED COLD WATER
FD FLOOR DRAIN
FDC FIRE DEPARTMENT (HOSE) CONNECTION
FM FLOW METER
FOP PUEL OIL PUMP
FOR FUEL OIL RETURN
FOS FUEL OIL SUPPLY
FOV FUEL OIL VENT
FS FLOOR SINK
FS FLOW SWITCH
FU FIXTURE UNITS
GAL GALLON
GCO GRADE CLEANOUT
GPD GALLONS PER DAY
GPH GALLONS PER HOUR
GPM GALLONS PER MINUTE
GPR GAS PRESSURE REGULATOR
GRS GAS REGULATOR STATION
GT GREASE TRAP
GVTR GAS VENT THROUGH ROOF
GWH GAS FIRED WATER HEATER
H&CW HOT AND COLD WATER
HB HOSE BIBB
HD HUB DRAIN
HEX HEAT EXCHANGER
HP HORSEPOWER
HS HAND SINK
HST HOT WATER STORAGE TANK (DOMESTIC)
HWB HOT WATER BOILER
HWCP HOT WATER CIRCULATING PUMP
HWP HOT WATER PUMP
HYD HYDRANT
ICW INDUSTRIAL COLD WATER
INV INVERT
IPC INTERNATIONAL PLUMBING CODE
IRW IRRIGATION WATER
IW INDIRECT WASTE
IWH INSTANTANEOUS WATER HEATER
IWR INDUSTRIAL WATER RETURN
IWS INDUSTRIAL WATER SUPPLY
KW KILOWATT
KWHR KILOWATT-HOUR
L/S LITER PER SECOND
LA LABORATORY AIR
LAV LAVATORY
LBS/HR POUNDS PER HOUR
LCW LABORATORY COLD WATER
LHW LABORATORY HOT WATER
LNG LIQUID NATURAL GAS
LOX LIQUID OXYGEN
LV LABORATORY VACUUM
LW LOW WATER
M METER
MA MEDICAL AIR
MAV MANUAL AIR VENT
MBH 1,000 BTU
MED MEDICAL
MER MECHANICAL EQUIPMENT ROOM
MH MANHOLE
MOU MEMORANDUM OF UNDERSTANDING
MSB MOP SERVICE BASIN
MV MEDICAL VACUUM
N2 NITROGEN
N2O NITROUS OXIDE
NC NORMALLY CLOSED
NG NATURAL GAS
NIC NOT IN CONTRACT
NO NORMALLY OPEN
NOM. NOMINAL
NPW NON POTABLE WATER
NTS NOT TO SCALE
O2 OXYGEN
OC ON CENTER
OD OUTSIDE DIAMETER
OFD OVERFLOW DRAIN
OR OPERATING ROOM
OVFL OVERFLOW DRAIN
PA PASCAL
PD PRESSURE DROP OR DIFFERENCE
PDI PLUMBING AND DRAINAGE INSTITUTE
PG PRESSURE GAGE
PP PLUMBING PUMP
PPM PARTS PER MILLION
PRS PRESSURE REDUCING STATION
PRV PRESSURE REDUCING VALVE
PSI POUNDS PER SQUARE INCH
PSIA POUNDS PER SQUARE INCH ATMOSPHERE
PSIG POUNDS PER SQUARE INCH GAUGE
PTRV PRESSURE TEMPERATURE RELIEF VALVE
PW POTABLE WATER
A6
PLUMBING PIPING SYMBOLS
LIMIT OF DEMOLITION
ANCHOR
REDUCER OR INCREASER
DIRECTION OF FLOW
SIDE CONNECTION
ECCENTRIC REDUCER
BOTTOM CONNECTION, 45° OR 90°
TOP CONNECTION, 45° OR 90°
DIRECTION OF PIPE PITCH (DOWN)
UNION
RISE OR DROP IN PIPE
CAPPED OUTLET
POINT OF CONNECTION BETWEEN NEW
AND EXISTING WORK
PRESSURE GAGE
THERMOMETER
STRAINER
FLOW ELEMENT
FLOAT & THERMOSTATIC TRAP SET INCLUDING
PIPING ACCESSORIES
INVERTED BUCKET TRAP SET INCLUDING
PIPING ACCESSORIES
PIPE UP
PIPE DOWN
FE
D6 GENERAL PLUMBING SYMBOLS
PL105
A
TYPICAL UNIT NO.
BUILDING NO. WHERE EQUIPMENT IS LOCATED.
PUMP NO.3 IN BUILDING NO.26
EQUIPMENT ABBREVIATION (PUMP)
BALL VALVE
GATE VALVE WITH 3/4 " HOSE ADAPTER
CHECK VALVE
ANGLE GLOBE VALVE
BUTTERFLY VALVE
MODULATING CONTROL VALVE
TWO POSITION CONTROL VALVE
THREE-WAY MODULATING CONTROL VALVE
AUTOMATIC FLOW CONTROL VALVE
PRESSURE RELIEF VALVE
GATE VALVE
MANUAL AIR VENT
TEST PLUG (PRESSURE/TEMPERATURE)
GLOBE VALVE
PRESSURE REGULATING VALVE
THREE-WAY TWO POSITION CONTROL VALVE
AUTOMATIC AIR VENT
B4 PLUMBING VALVE SYMBOLS
AV
A4 DRAWING SYMBOLS
26-P 3
SECTION LETTER
DRAWING NUMBER WHERE SHOWN
PL105
A SECTION LETTER
DRAWING NUMBER WHERE SHOWN
WATER BALANCE DEVICE
DOMESTIC HOT WATER RETURN (DHWR) DEMO
DOMESTIC HOT WATER RETURN (DHWR)
DOMESTIC HOT WATER RETURN (DHWR) EXISTING
DOMESTIC HOT WATER (DHW) EXISTING
DOMESTIC HOT WATER (DHW)
DOMESTIC HOT WATER (DHW) DEMO
DOMESTIC COLD WATER (DCW) DEMO
DOMESTIC COLD WATER (DCW)
DOMESTISC COLD WATER (DCW) EXISTING
VENT (V) DEMO
VENT (V) EXISTING
VENT (V)
STORM WATER (SD)
STORM WATER (SD) EXISTING
STORM WATER (SD) DEMO
WASTE (W)
WASTE (W) EXISTING
WASTE (W) DEMO
MEDICAL VACUUM (MV) DEMO
MEDICAL VACUUM (MV)
MEDICAL VACUUM (MV) EXISTING
OXYGEN (O2) DEMO
OXYGEN (O2)
OXYGEN (O2) EXISTING
MEDICAL AIR (MA) EXISTING
MEDICAL AIR (MA)
MEDICAL AIR (MA) DEMO
NATURAL GAS (NG) DEMO
NATURAL GAS (NG)
NATURAL GAS (NG) EXISTING
MA
MA
MA
O2
O2
O2
MV
MV
MV
NG
NG
NG
SD
SD
SD
W
W
W
B3
GENERAL NOTES
A3
DEMOLITION NOTES
1. DEMOLITION INFORMATION SHOWN ON THE DRAWINGS IS BASED
ON SHOP DRAWINGS AND A REVIEW OF THE EXISTING CONDITIONS.
2. PERFORM ALL WORK OF A DEMOLITION NATURE THAT MAY BE
REQUIRED OR NECESSARY FOR A FULL AND COMPLETE EXECUTION
OF THE WORK, WHETHER OR NOT SHOWN OR SPECIFIED. THE
EXACT EXTENT OF DEMOLITION MAY NOT BE FULLY INDICATED BY
THE DRAWINGS. DETERMINE THE NATURE AND EXTENT OF
DEMOLITION THAT WILL BE NECESSARY BY COMPARING THE
CONTRACT DOCUMENTS WITH THE EXISTING FIELD CONDITIONS
PRIOR TO BIDS.
3. MATERIALS AND EQUIPMENT TO BE SALVAGED OR REUSED SHALL
BE IDENTIFIED BY THE OWNER. THESE ITEMS ARE THE PROPERTY
OF THE OWNER AND SHALL BE RETURNED TO THE OWNERS
DESIGNATED STORAGE AREA. WHERE REMOVAL IS REQUIRED THE
CONTRACTOR SHALL BE RESPONSIBLE FOR CARE TAKEN DURING
THE HANDLING OF THESE ITEMS.
4. DEMOLISHED MATERIALS AND EQUIPMENT NOT BEING SALVAGED
OR REUSED, SHALL BECOME THE PROPERTY OF THE CONTRACTOR
AND REMOVED FROM THE SITE AND LEGALLY DISPOSED OF.
5. WHERE EXISTING FIXTURES ARE INDICATED TO BE DEMOLISHED.
THIS SHALL INCLUDE ALL ASSOCIATED PIPING, CARRIERS, SUPPORTS,
SLEEVES, HANGERS, FITTINGS, AND OTHER ACCESSORIES. PIPING
SHALL BE REMOVED TO A LOCATION ABOVE CEILING OR BEHIND
WALLS AND CAPPED. HOWEVER NO INACTIVE BRANCH OF MORE
THAN 2 FEET IN LENGTH CAN REMAIN ON ANY PIPE. CONTRACTOR
SHALL REMOVE AS REQUIRED.
6. WHERE DEMOLITION OF FIXTURE AND REMOVAL OF PIPING OR
OTHER ACCESSORY LEAVES AN OPENING IN THE FLOOR, WALL, OR
CEILING, SAME SHALL BE PATCHED TO MATCH EXISTING ADJACENT
FINISH.
1. ALL VALVES SHALL BE READILY ACCESSIBLE FROM A SAFE HEIGHT
ON A SIX FOOT LADDER AND TO BE CLEAR OF ALL OBSTRUCTIONS.
OPERATION SHALL NOT BE ENCUMBERED BY ANY DEVICE OR
EQUIPMENT.
2. ALL WATER PIPING SUPPLYING FIXTURES FROM WALLS OR CHASES
SHALL BE ONE PIPE SIZE LARGER THAN THE SIZE INDICATED
UNDER "CONNECTIONS" OF THE FIXTURE SPECIFICATIONS.
SEE PLANS FOR SUPPLY PIPE SIZING TO WALLS OR CHASES.
3. DO NOT SUPPORT PLUMBING PIPING FROM METAL DECK.
4. COORDINATE SCHEDULE FOR HOOK-UPS TO EXISTING SYSTEMS
AND EQUIPMENT REMOVAL OR RELOCATIONS WITH THE OWNER
AND PERFORM THIS WORK AT SUCH TIMES TO ENSURE THAT
PERIODS OF SHUTDOWN WILL BE ACCEPTABLE TO THE OWNER.
5. VERIFY EXACT LOCATION OF CONNECTION POINTS (NEW TO
EXISTING) IN FIELD PRIOR TO CONSTRUCTION.
6. COORDINATE INSTALLATION OF NEW PIPING WITH EXISTING
BUILDING STRUCTURE, DUCTWORK, PIPING, ELECTRICAL CONDUIT,
LIGHTING, ETC.
7. RELOCATE EXISTING PIPING IN EXISTING CEILING SPACES TO
ACCOMMODATE ALL RENOVATIONS AND ADDITIONS.
8. REFER TO ARCHITECTURAL ELEVATION DRAWINGS FOR LOCATION
OF WALL MOUNTED MECHANICAL ITEMS.
9. THIS PLAN IS APPROVED FOR WORK INDICATED PER THE
APPLICABLE DRAWINGS AND SPECIFICATIONS ONLY. ALL OTHER
AREAS SHOWN ARE FOR REFERENCE ONLY AND SHALL NOT BE
CONSIDERED OR APPROVED TO BE IN ACCORDANCE WITH
APPLICABLE CODES OR AUTHORITY HAVING JURISDICTION.
10. NOT ALL PIPING AND PIPE SIZES ARE SHOWN ON THE DRAWINGS
FOR CLARITY. REFER TO STACK DIAGRAMS, WATER RISERS, AND
MEDICAL GAS RISER FOR ADDITIONAL PIPING AND SIZES.
11. CUT, PATCH AND MATCH EXISTING CEILINGS, WALLS AND FLOORS
AS REQUIRED PER INSTALLATION OF PLUMBING PIPING.
12. CAREFULLY REMOVE AND INSTALL EXISTING CEILING TILES AS
REQUIRED PER INSTALLATION OF PLUMBING PIPING. DAMAGED
CEILING TILES TO BE REPLACED BY PLUMBING CONTRACTOR.
13. ALL EXISTING BUILDING UTILITIES HAVE BEEN DOCUMENTED FROM
AVAILABLE DRAWINGS, RECORDS AND FIELD SURVEY AND
THEREFORE, THEIR LOCATIONS MUST BE CONSIDERED
APPROXIMATE ONLY. IT SHALL BE THE CONTRACTOR'S
RESPONSIBILITY TO DETERMINE THE LOCATION AND SIZE OF ALL
EXISTING UTILITIES BEFORE BEGINNING WORK.
14. THIS IS A GENERAL LIST OF ABBREVIATIONS AND SYMBOLS ON THIS
SHEET. SOME ABBREVIATIONS AND SYMBOLS MAY NOT BE
APPLICABLE TO THIS PROJECT.
15. THE SPACE ABOVE THE CEILING IS LIMITED AND THE INSTALLATION
OF WORK WILL BE TIGHT. DUE TO THIS, IT IS IMPORTANT THAT THE
TRADE CONTRACTOR SHALL COORDINATE THE INSTALLATION OF
THEIR WORK WITH THE CEILING SYSTEM HEIGHT AND
CONSTRUCTION, THE STRUCTURAL SYSTEM, THE LIGHTING
FIXTURES, THE SPRINKLER HEADS / MAINS AND THE PLUMBING
PIPES. ROUTE PIPING AS HIGH AS POSSIBLE. MAINTAIN PROPER
SERVICE ACCESS CLEARANCE. ACCURATE SHOP DRAWINGS
SHALL BE SUBMITTED FOR APPROVAL, PRIOR TO FIELD INSTALLATION.
16. DO NOT INSTALL ANY NEW WORK DIRECTLY ABOVE ANY ELECTRICAL
PANELS AND TRANSFORMERS.
17. THESE DRAWINGS ARE DIAGRAMMATIC IN NATURE AND MAY NOT
SHOW EXACT ROUTING OR ALL REQUIRED OFFSETS, ACCESSORIES
OR APPURTENANCES. CONTRACTOR SHALL PROVIDE AS REQUIRED
TO INSTALL A COMPLETE AND COORDINATED JOB, INCLUDING ANY
ADDITIONAL ITEMS REQUIRED TO MEET ACTUAL FIELD CONDITIONS
AND ACTUAL EQUIPMENT SELECTED.
18. FOR EXACT LOCATION OF EQUIPMENT AND FIXTURES, SEE
ARCHITECTURAL DRAWINGS.
19. NO EQUIPMENT OR DEVICE REQUIRING REGULAR ACCESS OR
MAINTENANCE SHALL BE INSTALLED IN AN INACCESSIBLE CEILING
CAVITY. LOCATE SUCH ITEMS ABOVE ACOUSTIC TILE CEILINGS
WHEREVER POSSIBLE. IF ANY SUCH ITEMS ARE REQUIRED TO BE
INSTALLED ABOVE DRYWALL CEILINGS, PROVIDE AN ACCESS PANEL
OR PANELS SIZED AND LOCATED TO PROVIDE SUFFICIENT ACCESS
FOR EQUIPMENT SERVICE. SUBMIT LAYOUT OF ALL REQUIRED ACCESS
PANELS FOR ARCHITECTS REVIEW AND APPROVAL PRIOR TO THE
ONSET OF INSTALLATION.
20. ALL UNLABELED MEDICAL GAS PIPING SECTIONS SHALL BE
INSTALLED AS THE MINIMUM PIPE SIZE LISTED BELOW:
O2 = 1/2"
MV = 3/4"
MA = 1/2"
21. MEDICAL GAS SERVICE OUTLETS FURNISHED AND INSTALLED BY
THE PLUMBING CONTRACTOR. SEE ARCHITECTURAL DRAWINGS
FOR LOCATION, QUANTITY AND ARRANGEMENTS.
22. PVC TYPE PIPING SHALL NOT BE UTILIZED IN PLENUMS.
1100 Clark Avenue St. Louis, Missouri 63102
T: 314.241.6250 F: 314.241.2570
JACKSON, MS
CANNON DESIGN PROJECT NO. 03640.61
© CannonDesign 2017 - All rights reserved. No part of this document may be reproduced or utilized in any form, without prior written authorization by the Cannon Corporation.
JAN 12, 2018
NOT FOR CONSTRUCTION
Drawing Title
Approved: Project Director
Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
Dwg. of 81Revisions: Date
CONSULTANTS: ARCHITECT/ENGINEERS: Office of Construction and Facilities Management o n e e ig h th in c h o n e fo o t 1
B
A
C
D
E
F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t
VA FORM 08-6231
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
Department of Veterans Affairs
COMMUNITY LIVING CENTER
RENOVATION
586-16-106LEGENDS, SYMBOLS &
ABBREVIATIONS
PL0001
JJS RJL
VUTR S W
PONMKJH
FD ECBA
DEMO DCW
DEMO DCW
DEMO DCW
DEMO DCW
DEMO DCW
DEMO DCW
DEMO DCWDEMO DCWDEMO DCWDEMO DCW
DEMO DCW
DEMO DCW DEMO DCW
DEMO DCW
DEMO DCW
UP TO WH
DEMO DCW
UP TO WH
DEMO DCW
UP TO WH
DEMO DCW, W
AND V UP
DEMO DCW, W
AND V UP
DEMO DCW, W
AND V UP
DEMO DCW, W
AND V UP
DEMO DCW, W,
ST AND V UP
DEMO DCW
AND W UP
DEMO DCW
AND W UP
DEMO DCW, W
AND V UP
DEMO DCW, ST
AND W UP
DEMO DCW, W
AND V UP
DEMO DCW, W
AND V UP
DEMO DCW, W
AND V UP DEMO DCW, W
ST AND V UP
DEMO DCW, W
AND V UP
DEMO DCW, W
AND V UP
DEMO DCW, W
AND V UP
DEMO DCW, W
AND V UP
DEMO DCW, W
AND V UP
DEMO DCW, W
AND V UP
DEMO W
DEMO W
DEMO W
DEMO W
DEMO W
DEMO W
10" EX ST
E X
S T
8" EX ST
E X
S T
E X
S T
8" EX ST
E X
S T
8" EX ST8" EX ST8" EX ST
DEMO W UP
DEMO W UP
DEMO W UP
EXISTING WASTE
TO BE CONNECTED
TO NEW WASTE MAIN
DEMO DCW BACK
TO MAIN EXTENDING
UP TO MECHANICAL
ROOM.
EXISTING DCW INTO
BUILDING TO REMAIN
EXISTING FLOOR
DRAIN TO REMAIN.
REPIPE TO NEW
WASTE MAIN
DEMO DCW
UP TO WH
EXISTING WASTE
TO REMAIN
DEMO WASTE
TO THIS POINT
DEMO ST
DEMO ST
DEMO ST
EX 8" ST UP
DEMO DCW, W
AND V UP DEMO DCW, W
AND V UP
DEMO DCW, W
AND V UP
DEMO DCW, W
AND V UP
DEMO DCW, W
AND V UPDEMO DCW, W
AND V UP
DEMO DCW, W UP DEMO DCW, W UP
EX ST 6" EX ST
EX W
EX DCW
EX W EX W
EX DCW
6" EX ST EX DCW
EX WEX W
EX DCW
EX DHWR
EX W
EX DCW
EX DHWR
EX W
EX DCW
EX DHWR
EX W
EX DCW
EX DHWR
E X
D C
W
EX W
EX DCW
EX DHWR
EX W
EX DCW
EX DHWR
E X
D C
W
W
E X
D C
W
E X
D C
W
E X
W
E X
D C
W E
X D
H W
R
EX DHWR
EX DCW
E X
W
E X
D H
W R
E X
W
E X
D H
W R
DEMO DHWR UP
DEMO DHWR
DEMO DHWR
DEMO DHWRE
X
W
DEMO W UP
DEMO W UP
DEMO W UP
DEMO W UP
DEMO STORM
TO THIS POINT
DEMO ST UP
DEMO W UP
DEMO W UP
DEMO W UP
DEMO W UP
DEMO W UP
DEMO DHWR
E X
D H
W R
EX. 3/4" DHWR
TO REMAIN
EX. 3/4" DHWR
TO REMAIN
DEMO DHWR
DEMO DHWR DEMO DHWRDEMO DHWRDEMO DHWRDEMO DHWRDEMO DHWR
DEMO DHWR
1100 Clark Avenue St. Louis, Missouri 63102
T: 314.241.6250 F: 314.241.2570
JACKSON, MS
CANNON DESIGN PROJECT NO. 03640.61
© CannonDesign 2017 - All rights reserved. No part of this document may be reproduced or utilized in any form, without prior written authorization by the Cannon Corporation.
JAN 12, 2018
NOT FOR CONSTRUCTION
Drawing Title
Approved: Project Director
Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
Dwg. of 81Revisions: Date
CONSULTANTS: ARCHITECT/ENGINEERS: Office of Construction and Facilities Management o n e e ig h th in c h o n e fo o t 1
B
A
C
D
E
F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t
VA FORM 08-6231
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
Department of Veterans Affairs
COMMUNITY LIVING CENTER
RENOVATION
586-16-106UNDERFLOOR PLUMBING DEMO PLAN
PD010
JJS RJL
1/8" = 1'-0" 4F
UNDERFLOOR PLUMBING DEMO PLAN
PONMKJH
FD ECBA
NIC
DEMO DHWDEMO DHWDEMO DHWDEMO DHWDEMO DHWDEMO DHWDEMO DHWDEMO DHWDEMO DHWDEMO DHW
EX 2" FD
TO REMAIN
EX 2" FD
TO REMAIN
DEMO DHW
DEMO CW
DEMO DHW
DEMO DHW
DEMO DHW
DEMO DHW
EXISTING WATER HEATER
TO REMAIN
DEMO FLOOR DRAIN
DEMO WC AND
ASSOCIATED PIPING
DEMO WC AND
ASSOCIATED PIPING
DEMO LAVS AND
ASSOCIATED PIPING
E X
S T
4" EX ST
E X
S T
8" EX
ST
EX 8" ST DN
EX 4" ST UP
EX 4" ST UP
EX 4" ST UP
2 2
EXISTING 3/4 DHWR DN
EX 2" FD
TO REMAIN
EX 2" FD
TO REMAIN
EX. 2" V DN
EX. 4" W DN
EX. 2" W DN
EX. 2" W DN
EX. 4" W
EX. 4" W
EX. 3" W
EXISTING 4" W
1.
2.
3.
4.
5.
DEMO EXISTING WH AND DCW PIPING
CUT AND REMOVE WASTE, VENT, DHW AND
DCW PIPING IN CEILING FEEDING
LEVEL 00. PREPARE EXISTING WASTE
VENT, DHW AND DCW PIPING UP TO LEVEL 01
FOR CONNECTION TO NEW WASTE, VENT
AND DOMESTIC SYSTEM. THE DEMOLITION
AND CONNECTION TO NEW SYSTEMS SHALL
OCCUR AT SAME TIME TO KEEP LEVEL 01
IN OPERATION DURING CONSTRUCTION.
ANY SHUT DOWN TO SERVICES OF LEVEL 01
SHALL BE COORDINATED WITH OWNER
ONE WEEK PRIOR TO SHUT DOWN.
DEMOLISH WASTE PIPING TO THIS POINT.
PREPARE FOR NEW CONNECTION.
DEMOLISH DCW, DHW PIPING TO 1'-0" FROM
BOTTOM OF LEVEL 01 SLAB. PREPARE
PIPING FOR NEW CONNECTION.
EXISTING DCW, DHW, W TO REMAIN
1100 Clark Avenue St. Louis, Missouri 63102
T: 314.241.6250 F: 314.241.2570
JACKSON, MS
CANNON DESIGN PROJECT NO. 03640.61
© CannonDesign 2017 - All rights reserved. No part of this document may be reproduced or utilized in any form, without prior written authorization by the Cannon Corporation.
JAN 12, 2018
NOT FOR CONSTRUCTION
Drawing Title
Approved: Project Director
Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
Dwg. of 81Revisions: Date
CONSULTANTS: ARCHITECT/ENGINEERS: Office of Construction and Facilities Management o n e e ig h th in c h o n e fo o t 1
B
A
C
D
E
F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t
VA FORM 08-6231
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
Department of Veterans Affairs
COMMUNITY LIVING CENTER
RENOVATION
586-16-106LEVEL 00 PLUMBING DEMO PLAN
PD100
JJS RJL
1/8" = 1'-0" 4F
LEVEL 00 PLUMBING DEMO PLAN
8A
KEYED NOTES
PONMKJH
FD ECBA
EX.6" WASTE
I.E. 340.40'
EX. 10" ST
TO REMAIN
I.E. 338.16'
EX WW
EX ST
W
W
W
W
4" UP TO FD
2" UP TO FD
4" UP TO CO
4" UP
2" UP TO FD
2" UP TO FD
4" UP TO FD
4" W UP
2" UP TO FD2" UP TO FD
4" W UP2" UP TO FD
4" UP TO FD
4" UP
TO FD
2" UP TO FD4" W UP
4" W UP
2" W UP
2" W UP
2" W UP
3" UP TO MS
4" UP TO FD
4" UP TO FD
2" UP TO FD
CONNECT NEW
2" W TO
EX. 2" W UP TO SH
2" W UP
4" W UP2" W UP
EXISTING 4" DCW
TO REMAIN
W W
W
2" W UP
E X
S T
EX ST
W W
CONNECT 4" W TO
EXISTING WASTE UP
CAP CAP CAP
CAP
CAP
2" W UP
W
3" UP TO FD
2" V UP
2" V UP
4" ST UP
2" V UP 4" ST UP
4" ST UP
2" V UP
2" V UP
2" V UP
2" V UP
4" UP TO CO
EX 8"
ST UP
2" V UP
2" V UP
2" W UP
2" W UP
2" V UP
3" W UP
3" UP TO CO
2" W UP
4" W UP
3" UP
TO CO
E X
S T
EX ST
EX ST
2" V UP
2" UP
TO FD
2" V UP
2" W UP
4" W
4" W
4" W
4" W
4" W
4" W
6" W
4" W
4" W
4" W
4" W
4" W
4" W
10" EX ST
8" EX ST
10" EX ST
10" EX ST
8" EX ST
6" W 6" W
6" EX ST8" EX ST
4" W UP
4" UP
2" V UP
4" UP TO FD
2" V UP
2" W UP
2" W UP
4" W UP
2" V UP
2" V UP
2" V UP
2" W UP
4" W4" W
2" V UP
2" V UP
4" UP TO FD
4" W UP
2" W UP
2" V UP
2" V UP
4" W UP
4" UP TO FD4" UP TO FD
2" UP TO FD
2" UP
TO FD
2" V UP
2" V UP
2" V UP
2" W UP
4" W UP
2" V UP
4" W UP
4" ST UP
2" V UP
4" W UP
4" UP TO FD
4" UP TO FD
2" UP
TO FD
2" UP TO FD
2" V UP
2" V UP
2" W UP
4" W UP
2" V UP
4" W UP
2" V UP
4" W UP
2" V UP
2" V UP
2" UP TO FD 2" V UP
4" W UP TO FD
2" W UP TO FD
2" V UP
2" W UP
4" W UP
2" UP TO FD
2" V UP
2" V UP
4" UP TO FD
2" V UP
2" V UP
2" W UP TO FD
4" W UP TO FD
2" V UP
4" W UP
2" W UP
4" W UP
4" W UP
2" V UP
2" V UP
2" V UP
2" W UP TO FD
2" V UP
4" W UP TO FD
4" W UP TO FD
2" V UP
2" W UP TO FD
4" W UP
2" W UP
2" V UP
4" W UP
2" V UP
2" V UP
4" W UP TO FD
2" V UP
4" UP TO FD
4" W UP
2" V UP
4" W UP
2" W UP
2" V UP
2" V UP
4" W UP TO FD
2" W UP
4" W UP TO CO
4" W UP TO CO
4" W UP TO CO
4" W UP
4" W UP
2" V UP
4" W UP
2" W UP
2" V UP
2" UP TO FD
4" UP TO FD
4" UP TO CO
2" W UP
4" UP TO FD
2" V UP
2" V UP
2" UP TO FD
2" V UP
2" V UP
4" UP
4" W UP
4" UP TO CO
2" V UP
2" W UP
4" UP TO FD
2" V UP
2" UP TO FD
2" UP TO FD
2" V UP
2" UP TO FD
4" W UP
2" V UP
2" V UP
2" V UP
2" UP TO FD
2" W UP
4" UP TO FD
4" UP
4" UP
4" UP
2" V UP
2" W UP
2" V UP
4" UP TO FD
2" V UP
2" W UP
4" W UP
2" V UP4" UP TO CO
4" UP2" V UP
2" UP
2" V UP
4" W UP
4" ST UP
4" UP TO FD
2" V UP
W
CONNECT NEW 2" W TO
EX 2" W UP
CONNECT NEW 4" W TO
EX 4" W UP
CONNECT NEW 4" W TO
EX 4" UP TO EX FD
WV
WV
WV
WV
WV
WV
WV
WV
WV
WV
WV
WV
WV
WV
WV
WV
WV
CONNECT NEW 4" DCW
TO EXISTING 4" DCW
4" DCW UP
2" W UP
CONNECT NEW 4" W TO
EX 4" UP TO EX FD
2" V UP
4" W UP
2" W UP
4" W UP
EX DHWR UP
EX DHWR UP
E X
D H
W R
EX 4" W UP
8" EX ST
4" W UP TO FD
4" W UP TO FD
2" V UP2" V UP
EX 4" W UP
TO HUB DRAIN
2" V UP
2" V UP
4" W UP TO FD
2" V UP
4" W UP
4" ST UP
4" W UP
2" V UP
6" EX ST
WW
W
V
W
W W
E X
S T
W
W
W
W
W
W
W
W
W
W
WW
W
W W
W
EX. 4" W UP
CONNECT NEW 4" W
TO EXISTING 4" W
4" UP
TO CO
4" UP TO CO
4" UP
TO CO
4" W 6" W
4" UP TO CO
4" UP TO CO
4" W
6" W
6" W
6" W 6" W
W W
W W
V W W
W
W S
T
W
WW
W
W
W
V
V
W W
W
W
W
V
W
W
EX W
W
W
EX ST
W
W
W
W
V
W
W
V
WS
T
4" UP
TO CO
4" UP TO CO
4" UP TO CO
2" W UP
4" UP TO CO
1.
2.
3.
ALL WORK ON THIS PLAN TAKES PLACE IN A PIPE BASEMENT.
PROVIDE ALL NECESSARY ATTACHEMENTS, ACHORS AND HANGERS.
ELEVATION OF PIPE BASEMENT IS 4'-0"
ALL CONCRETE CORING THROUGH SLAB SHALL HAVE THE SLAB X-RAY SCANNED AND THE
LOCATION VERIFIED ON A CASE BY CASE BASIS WITH THE STRUCTURAL ENGINEER PRIOR
TO SLAB CORING. IF THE LOCATION IS FOUND TO BE UNACCEPTABLE, THE LOCATION SHALL
BE REVISED.
1100 Clark Avenue St. Louis, Missouri 63102
T: 314.241.6250 F: 314.241.2570
JACKSON, MS
CANNON DESIGN PROJECT NO. 03640.61
© CannonDesign 2017 - All rights reserved. No part of this document may be reproduced or utilized in any form, without prior written authorization by the Cannon Corporation.
JAN 12, 2018
NOT FOR CONSTRUCTION
Drawing Title
Approved: Project Director
Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
Dwg. of 81Revisions: Date
CONSULTANTS: ARCHITECT/ENGINEERS: Office of Construction and Facilities Management o n e e ig h th in c h o n e fo o t 1
B
A
C
D
E
F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t
VA FORM 08-6231
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
Department of Veterans Affairs
COMMUNITY LIVING CENTER
RENOVATION
586-16-106UNDERFLOOR PLUMBING PLAN
PL010
JJS RJL
1/8" = 1'-0" 4F
UNDERFLOOR PLUMBING PLAN
7C
GENERAL NOTES
D W
REF.
T L
T -0
B N
TLT-01
B N
TLT-01
P-101
P-101
P-101 P-418
P-703P-703
P-101
P-414
P-414
4" FD-D
2" FD-D
2" FD-D
4" FD-D
Bedroom
G143
Bedroom
G146
Bedroom, Bariatric
G141
Bath Suite
G154
Bedroom, Bariatric
G161
Office
G123
Family Lounge
G107
Medicine Storage
G106
Telecom Closet
G113
Conference
G131Staff Lounge
G126
Office
G127
Office
G128
Mechanical (E)
G132
Mechanical (E)
G132.1
Concierge Station
G105
Sitting Area
G104
Shared Office
G129
Stairs
G167
Stairs
G147
Stairs
G133
Oxygen Storage- Empty
G121
Elevator
C1-G
Elevator
C2-G
Locker Room
G130
Kitchen
G111
Office
G124
Closet
G114
Multi-Purpose Area
G102
Storage
G140.3
Elec
G120.1
Toilet
G130.2
House Keeping
G122
VUTR S W
PONMKJH
FD ECBA
2" FD-D
4" FD-D
DHWR
DHW
DCW
DCW
DHW
DHWR
D C
W D
H W
D H
W R
DHWR
DHW
DCW
DHWR
DHW
DCW
D C
W D
H W
D H
W R
DHWR
DCW
DHW DHW
DHWR
DCW
D C
W D
H W
D H
W R
DHWR
DHW
DCW
P-528
P-528
P-502
4" FD-D
P-101
P-703
P-414
2" FD-D
4" FD-D
P-703
P-101
P-414
4" FD-D
2" FD-D P-101
P-703
P-414
2" FD-D
4" FD-D
P-703
P-703 P-703
P-101
P-703
2" FD-D
4" FD-DP-414
P-114
P-703
2" FD-D
4" FD-D
P-421
NIC
4" ST
4" S
T
S T
ST
S T
V
V
3" EX V UP
V
V
3" FD-D
FCO
FCO
P-808
P-808
FCO
P-701
P-521
P-101
P-414
P-101
2" DCW
1" DHW
1/2" DHWR
2" V
4" DCW
3" DHW
2" DHWR
3" DCW
2" DHW
1" DHWR
2" DCW
1" DHW
1/2" DHWR
3" DCW
1-1/2" DHW
3/4" DHWR
3" DCW
2" DHW
3/4" DHWR
3" DCW
2" DHW
1" DHWR
3" DCW
2" DHW
3/4" DHWR
2" DCW
1-1/2" DHW
1/2" DHWR
2" DCW
1" DHW
P-502
P-530 P-418
P-418
P-402 P-709
P-402
P-524
4" ST
4" ST DN
1/2" DHW, 1/2" DCW DN TO
OWNER FURNISHED BATHUB
3" DCW
2" DHW
1" DHWR
VALVE AND CAP
3" DCW, 2" DHW
1" DHWR FOR
FUTURE
SET BALANCING
VALVE TO 8 GPM
4" DCW
3" DHW
2" DHWR
2" DCW
1-1/2" DHW
1/2" DHWR
P-505
2-1/2" V
1/2" DHWR
1" DHW
2" DCW
4" W
4" EX ST
E X
S T
8" EX
ST
E X
S T
P801
P801
EX 4" ST UP
EX 4" ST UP
EX 4" ST UP
EX 8" ST DN
DHW
4" FD-D
4" ST DN
4" ST UP
P-801
P-801
P-101
P-703
P-703
P-101
P-414P-414
4" FD-D
2" FD-D
2" FD-D
4" FD-D
P-101
P-703P-703
P-101
P-414
P-414
4" FD-D
2" FD-D
2" FD-D
4" FD-D
P-101
P-703
P-101
P-414
P-414
4" FD-D
2" FD-D
2" FD-D
4" FD-D
P-101
P-703
P-101
P-414P-414
4" FD-D
2" FD-D 2" FD-D
4" FD-D
P-101
P-703
P-703
P-101
P-414P-414
4" FD-D
2" FD-D
2" FD-D
4" FD-D
P-101 P-703
P-101
P-414
P-414
4" FD-D
2" FD-D
2" FD-D
4" FD-D
P-101
P-703
P-703
P-101
P-414P-414
4" FD-D
2" FD-D
2" FD-D
4" FD-D
P-703
P-101
P-414
4" FD-D
2" FD-DP-703
P-114
P-421
4" FD-D
2" FD-D
P-418
P-608
1 4
4 4
4 24
4 2
4" FD-D
PL301
8F
PL301
4F
DOM
DOM
DOM
3 DOM
DOM
DOM
DOM
DOM
DOM
DOM
DOM
DOM
DOM
DOM
DOM
DOM
DOM
4" WCO
WV
WV
WV
WV
WV
WV
3 WV
WV
WV
WV
WV
WV
WV
WV
WV
WV
WV
4" WCO
4" WCO
4" WCO 4" WCO
4" WCO 4" WCO
4" WCO 4" WCO
EX. 1" DHW
Bedroom
G148
Bedroom
G149
Bedroom
G150
Bedroom
G151
Bedroom
G152
Bedroom
G153
Bedroom
G145
Bedroom
G144
Bedroom
G142
26 27 27
27 26
P-418
4" W
EX DHW
EX DCW
E X
W
EX W
EX W
D C
W
DHWR
DCW
DHWR
DHW
DCW
V
V
V
VV
1" DCW
1" DHW
1/2" DHWR
EX 4" W UP
V
D C
W
PL301
1F
4" FCO
FCO
FCO
FCO
4" ST DN
FCO
S T
ST
W
V
W W
V
V
W
W
V
V
4" ST DN
4" ST UP
4" ST UP
FIELD VERIFY EXISTING CONNECTIONS.
EXISTING WASTE, VENT AND DOMESTIC
CONNECTIONS SHALL BE RECONNECTED
TO THE NEW WASTE, VENT AND DOMESTIC
SYSTEM
PL601
1D
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.
14.
15.
16.
17.
18.
19.
20.
21.
22.
23.
24.
25.
26.
27.
28.
29.
30.
31.
32.
33.
34.
35.
36.
37.
38.
39.
40.
41.
42.
43.
1/2" DCW DN, 1/2" DHW DN, 2" W DN, 2" V DN
1/2" DCW DN, 1/2" DHW DN
1-1/4" DCW DN, 4" W DN, 2" V DN
2" V DN
1-1/2" DCW DN, 4" W DN, 2" V DN
1-1/4" DCW DN
CONNECT NEW 4" V TO EX 4" V UP
3/4" DCW DN
3" V DN
1-1/2" DCW DN, 1/2" DHW DN, 4" W DN, 2" V DN
4" W DN, 4" V DN
1/2" DHW DN, CONNECT WASTE TO ADJACENT SINK
3/4" DCW DN, 3/4" DHW DN
3/4" DCW DN, 3/4" DHW DN, 2" W DN, 2" V DN.
CONNECT TO P-808
1/2" DCW DN, 2" W DN, 2" V DN
4" W DN
CONNECT NEW 4" W TO EXISTING 4" W
CONNECT NEW 1-1/4" DCW AND 1-1/4" DHW TO
EXISTING DCW AND DHW
CONNECT NEW 1/2" DHWR TO EXISTING
CONNECT NEW 1/2" DCW TO EXISTING
CONNECT NEW 1-1/2" DCW, 1/2" DHW, 4" W TO EXISTING
CONNECT NEW 3/4" DCW, 3/4" DHW, 1-1/2" W TO EXISTING
CONNECT NEW 1/2" DCW, 1/2" DHW, 1-1/2" W TO EXISTING
CONNECT NEW 2-1/2" DCW, 1" DHW, 4" W, 3" V, 4" ST TO EXISTING
CONNECT NEW 1" DCW, 1/2" DHW, 2" W, 2" V TO EXISTING
CONNECT NEW 2" DCW, 4" W, 2" V TO EXISTING
CONNECT NEW 2-1/2" DCW, 1/2" DHW, 4" W, 2" V TO EXISTING
CONNECT NEW 3" DCW, 3/4" DHW, 4" W, 2" V, 4" ST TO EXISTING
CONNECT NEW 2" DCW, 3/4" DHW, 4" W, 4" V TO EXISTING
CONNECT NEW 1-1/2" DCW, 3/4" DHW, 3" W, 2" V TO EXISTING
CONNECT NEW 3/4" DCW, 3/4" DHW, 1-1/2" W, 2" V TO EXISTING
CONNECT NEW 2" DCW, 3/4" DHW, 2" W, 1-1/2" V TO EXISTING
CONNECT NEW 2-1/2" DCW, 3/4" DHW, 4" W, 2" V TO EXISTING
CONNECT NEW 4" ST TO EXISTING
CONNECT NEW 3" DCW, 3/4" DHW, 4" W, 2" V, 4" ST TO EXISTING
CONNECT NEW 1" DHW TO EXISTING
CONNECT NEW 4" W TO EXISTING
CONNECT NEW 3/4" DCW, 3/4" DHW TO EXISTING
CONNECT NEW 1-1/2" DCW, 3/4" DHW TO EXISTING
3" W DN
EXISTING DCW, DHW, W AND V TO REMAIN
1/2" DCW DN, 2" W DN, 2" V DN, CONNECT TO ICE MAKER BOX
1/2" DCW DN
1. ALL CONCRETE CORING THROUGH SLAB SHALL HAVE THE SLAB X-RAY SCANNED AND THE
LOCATION VERIFIED ON A CASE BY CASE BASIS WITH THE STRUCTURAL ENGINEER PRIOR
TO SLAB CORING. IF THE LOCATION IS FOUND TO BE UNACCEPTABLE, THE LOCATION SHALL
BE REVISED.
1100 Clark Avenue St. Louis, Missouri 63102
T: 314.241.6250 F: 314.241.2570
JACKSON, MS
CANNON DESIGN PROJECT NO. 03640.61
© CannonDesign 2017 - All rights reserved. No part of this document may be reproduced or utilized in any form, without prior written authorization by the Cannon Corporation.
JAN 12, 2018
NOT FOR CONSTRUCTION
Drawing Title
Approved: Project Director
Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
Dwg. of 81Revisions: Date
CONSULTANTS: ARCHITECT/ENGINEERS: Office of Construction and Facilities Management o n e e ig h th in c h o n e fo o t 1
B
A
C
D
E
F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t
VA FORM 08-6231
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
Department of Veterans Affairs
COMMUNITY LIVING CENTER
RENOVATION
586-16-106LEVEL 00 PLUMBING PLAN
PL100
JJS RJL
1/8" = 1'-0" 4F
LEVEL 00 PLUMBING PLAN
8A
KEYED NOTES
B1
GENERAL NOTES
T L
T -0
TLT-01
MK
P-101
P-101
P-418
2" FD-D
4" FD-D
P-703
P-418
1/2" DCW DN
1/2" DHW DN
CONNECT NEW 1" DHW
TO EXISTING 1" DHW
2" V DN
1-1/4" DCW DN
2" V DN
1/2" DCW DN
1/2" DHW DN
2" W DN
2" V DN
1/2" DCW DN
1/2" DHW DN
2" W DN
2" V DN
CONNECT 4" W
TO EXISTING 4" W
4" W DN
EX. 4" W UP
EX. 4" ST UP
2" V
1/2" DHWR
1" DHW
2" DCW
D H
W
D C
W
V
V
/4
D
C W
D H
W
/2
D
H W
R
1 1/4" DCW
2" V
1/2" DHWR
E X
S T
W
EX. 1/2" DHW UP
V
3" V
U
1/2" DCW DN
1/2" DHW DN
2" W DN
2" V DN
1-1/2" DCW DN
4" FD-D
P-101
1-1/2" DCW DN
1/2" DCW DN
1/2" DHW DN
1/2" DCW DN
1/2" DHW DN
2" V DN
2" FD-D 4" FD-D
P-101
4" V DN
4" W DN
D C
W
D H
W
D C
W
D H
W
DHW
DCW
DHW
DCW
NOTE:
LOCATION OF EXISTING WASTE,
VENT, DOMESTIC AND STORM TO
LEVEL 01 ARE IN DIFFERENT
LOCATIONS IN ALL BACK TO BACK
ROOMS. REFER TO PL101 FOR
ACTUAL LOCATION.
2" V DN
2" V DN PIPING CHANGES PER
PLAN LOCATION.
CONTRACTOR TO FIELD
VERIFY EXISTING CONNECTION
SIZES AND RECONNECT TO
NEW SYSTEM
PIPING CHANGES PER
PLAN LOCATION.
CONTRACTOR TO FIELD
VERIFY EXISTING CONNECTION
SIZES AND RECONNECT TO
NEW SYSTEM
2" V DN
ST
S T
4” ST DN
PONMK
EXISTING STEAM
WATER HEATER
TO REMAIN
EX 2" FD
TO REMAIN
EX 2" FD
TO REMAIN
4" DCW
3" DHW
2" DHWR
EXISTING WATER
QUAILTY AND MONITORING
STATION TO REMAIN.
RECONNECT TO NEW PIPING
EX 4" ST UP
EX 4" ST UP
EX. 2" V DN
EX. 4" W DN
EX. 2" V UP
EX. 2" W DN
EX. 2" W DN
EX. 2" FD
TO REMAIN
TMV-1
2" V DN
EX 2" FD
TO REMAIN
EX 2" FD
TO REMAIN
EX 2" FD
TO REMAIN
EX HUB DRAIN
P803
VALVE AND CAP
4" DCW, 3" DHW, 2" DHWR
FOR FUTURE LEVEL 02
RENOVATION
4" DCW
2 1/2" DHW
3" DHW
2 1/2" V2" V
4" EX W
2" EX V
V
/2
V
D H
W
/2
D H
W
/2
V
2" V 2" V
1/2" DCW
E X
S T
2" V DN2" V DN
4" V UP
2" V DN
2" V DN
4" DCW DN
(2) BFP-1
EX. 4" W
EX. 4" WEX. 3" W
PL601
5F
3/4" DCW DN
EX. 4" W DN
EXISTING HWR TO CONNECT
TO NEW HWR
2" DHWR
1" DCW 1" DCW
BFP-3
HANG BFP, ROUTE
WASTE TO DRAIN
TO MECHANICAL
MAKE UP
P708
1/2" DHW
1/2" DHWR
1/2" DHW
1/2" DHWR
2" DHWR
3" DHW
4" DCW
FCO
1100 Clark Avenue St. Louis, Missouri 63102
T: 314.241.6250 F: 314.241.2570
JACKSON, MS
CANNON DESIGN PROJECT NO. 03640.61
© CannonDesign 2017 - All rights reserved. No part of this document may be reproduced or utilized in any form, without prior written authorization by the Cannon Corporation.
JAN 12, 2018
NOT FOR CONSTRUCTION
Drawing Title
Approved: Project Director
Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
Dwg. of 81Revisions: Date
CONSULTANTS: ARCHITECT/ENGINEERS: Office of Construction and Facilities Management o n e e ig h th in c h o n e fo o t 1
B
A
C
D
E
F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t
VA FORM 08-6231
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
Department of Veterans Affairs
COMMUNITY LIVING CENTER
RENOVATION
586-16-106PLUMBING ENLARGED PLANS
PL301
JJS RJL
1/4" = 1'-0" 8F
ENLARGED LOCKER ROOM
1/4" = 1'-0"
4F
TYPICAL BACK TO BACK BEDROOM
1/4" = 1'-0" 1F
P110 - ENLARGED MECHANICAL ROOM
1 1/4" DCW
3/4" DCW
1/2" DCW
1/2" DHW
1/2" DHWR
3/4" DCW
3/4" EX DCW
3/4" DCW
1/2" DCW
1/2" DHW
1/2" DHWR
1/2" DHWR
1" DHW
2" DCW
1 1/2" EX DCW
3/4" EX DHW
P-101
P-414
P-703
"A"
"A"
1" DHW
1 1/2" DCW
"A" "A"
3/4" DHW
3/4" DCW 1/2" DHW
1 1/2" DCW
1/2" DHW
1/2" DCW
1 1/2" DCW
2" DHWR
2" DHW
3" DCW
2" DHWR
1 1/2" DHW
3" DCW
3/4" DHW
1 1/2" DCW
3" DCW
2" DHW
2" DHWR
P-703P-414
P-414
P-101 P-101
"A"
"A" "A"
P-703
"A"
"B"
"A"
"A"
1 1/2" EX DCW
1/2" EX DHW
DCW: 15 WFU
DHW: 3 WSFU
3/4" EX DHW
1 1/2" EX DCW
3/4" DHW
3/4" DCW
1 1/2" DCW
1/2" DHW
1/2" DCW
3/4" DHW
1 1/2" DCW
3" DCW
2" DHW
2" DHWR
1/2" DHW
1/2" DCW
2" DHWR
2" DHW
3" DCW
3" DCW
2" DHW
2" DHWR
1/2" DHWR
1/2" DCW
P-414
P-414 P-101
P-101
"A" "A"
"A"
"A"
"A"
"A"
P-703
P-703
"B"
DCW: 15 WFU
DHW: 3 WSFU
1 1/4" DCW
1 1/4" EX DCW
1/2" EX DCW
1/2" EX DHW
1/2" EX DHW
1/2" EX DHW
1/2" DHW
1/2" DCW
2" DHWR
2" DHW
3" DCW
1 1/4" DCW
1/2" DCW
1/2" DHWR
1/2" DHW
1/2" DHW
1/2" DCW
1" DHWR
2" DHW
3" DCW
1" DHWR
2" DHW
3" DCW
1" DHWR
2" DHW
3" DCW
1 1/4" DCW
3/4" DHW
1 1/4" DCW
3/4" DHW
3/4" DCW
3/4" DCW
3/4" DHW
"A"
"A"
P-418
P-414
P-101
P-703
P-101
P-414
BATHTUB
P-420
"A" "A"
"A"
"A"
"A"
"A"
"A"
"A" "A"
"A"
"A"
"A"
1/2" EX DCW
1/2" EX DHW3/4" EX DCW
3/4" EX DHW
DCW: 7.5 WSFU
DHW: 1.5 WSFU
1/2" DCW
1/2" DHW
1/2" DHW
1/2" EX DCW
1/2" EX DHW
1/2" DHW
1/2" DCW
1/2" DHW
1/2" DCW
1/2" DCW
1/2" DHW
1 1/2" DCW
2" DHWR
1 1/2" DHW
3" DCW
3/4" DCW
3/4" DHW
1/2" DHW
1/2" DHWR
1 1/2" DHW
3" DCW
"A"
"A"
"A"
"A"
"A"
"A"
"A"
P-414
P-414 P-101
P-101 P-703
P-703
1 1/4" EX DCW
1 1/2" EX DHW
1/2" EX DCW
1/2" EX DHW
1 1/2" DHW
1 1/4" DCW
DCW: 15 WFU
DHW: 3 WSFU
1/2" EX DCW
3/4" DCW
3/4" DCW
1/2" DCW
1/2" DHW
1 1/2" DCW
1/2" DHW
2" DHWR
2" DHW
3" DCW
1/2" DCW
2" DHWR
2" DHW
3" DCW
"A"
"A" "A"
"A"
"A"
"A"
1 1/2" DCW
3/4" DHW
P-801
P-414
P-414 P-101
P-101 P-703
P-703
"B"
1/2" EX DHW
1 1/4" EX DCW
1 1/4" DCW
1 1/4" DHW
DCW: 15 WFU
DHW: 3 WSFU
1 1/4" DCW
1/2" DHW
1 1/4" DCW
1/2" DCW
1/2" DHW
1/2" DHWR
2" DHWR
2" DHW
3" DCW
1 1/4" DCW
1/2" DHW
1/2" DHWR
1/2" DHWR
1/2" DHW
1/2" DCW
1 1/4" DCW
1/2" DHW
"A"
"A"
"A"
"A"
P-414
P-101
P-703
P-703
P-414
P-101
"A"
"A"
"A"
"A"
"A" "A"
1/2" DHW
1 1/2" DCW
1/2" EX DHW
1 1/2" EX DCW
1/2" EX DHW
1/2" EX DCW
1 1/4" EX DCW
1 1/2" DCW
DCW: 7.5 WSFU
DHW: 1.5 WSFU
1 1/4" DCW
3/4" DHW
1/2" DHWR
1/2" DCW
1/2" DHW
1/2" DHWR
1/2" DHW
1/2" DCW
1/2" DHW
1/2" DHW
1 1/2" DCW
1/2" DCW
1/2" DHW
1/2" DHWR
1" DHWR
3" DCW
2" DHW
2" DHW
3" DCW
2" DHWR
2" DHWR
3" DCW
2" DHW
3/4" DCW
3/4" DHW
1/2" DHWR
DISHWASHER
P-524
P-428
P-505
"A" "A"
1/2" EX DHW
1 1/2" EX DCW
"A" "A"
"A"
1/2" EX DHW
1/2" EX DCW
3/4" DHW
1/2" DHWR
1/2" DHW
1/2" DCW
1 1/4" DCW
1/2" DHWR
3/4" DHW
1 1/2" DCW
2" DHWR
3" DCW
2" DHW
2" DHWR
3" DCW
2" DHW
P-414
P-101
P-703
P-418
"A"
"A"
"A" "A"
"A"
"A"
"B"
DCW: 6.5
WSFU
DHW: 1.5
WSFU
1/2" EX DCW
1/2" EX DHW
1/2" DCW
1/2" DHW
2" DHWR
3" DCW
2" DHW
3/4" DHW
3/4" DCW
3/4" DHW
1 1/2" DCW
1 1/2" DCW
1/2" DCW
1/2" DHW
2" DCW
3/4" DHW
2" DHW
3" DCW
2" DHWR
2" DHWR
3" DCW
1 1/2" DHW
1 1/2" DCW
1/2" DHW
2" DCW
2" EX DCW
3/4" EX DHW
3/4" DHW
"A"
"A"
P-414
P-414
P-101
P-101 P-703
P-703
"A"
1 1/2" EX DCW1/2" EX DCW
"B"
"A"
"A"
DCW: 15 WSFU
DHW: 3 WSFU
"A"
1/2" DHW
1/2" DCW
1/2" DHW
1 1/2" DCW
2" DHWR
3" DCW
1 1/2" DHW
1 1/2" DCW
1" DHW
1 1/2" DCW
"A" "A"
"A"
"A"
1/2" EX DHW1 1/2" EX DCW
1/2" DHW
1 1/2" DCW
P-414
P-414
P-101
P-101
P-801"B"
"A" "A"
DCW: 21.5
WSFU
DHW: 3.5 WSFU
P-703
3/4" DCW
3/4" DCW
1/2" DCW
1/2" DHW
1/2" DCW
1/2" DHW
P-703
3/4" DHW
1 1/2" DCW
3/4" DHW
1/2" DCW
1/2" DHW
1 1/2" DCW
1/2" DCW
1/2" DHW
2" DHW
3" DCW
2" DHWR
2" DHW
3" DCW
2" DHWR
1 1/4" EX DCW
1 1/4" DCW
1/2" EX DHW
1/2" EX DCW
1/2" DHW
1 1/2" DCW
1/2" EX DHW
1 1/2" EX DCW
1/2" DHW
1/2" DCW
1 1/2" DCW
3/4" DHW
"A" "A"
"A"
"A"
"A"
"A"
"A"
"A"
P-414
P-101
P-703
P-114
P-421
P-703
"A"
"A"
DCW: 7.5 WSFU
DHW: 1.5 WSFU
DCW: 7.5 WSFU
DHW: 1.5 WSFU
1 1/2" DCW
1100 Clark Avenue St. Louis, Missouri 63102
T: 314.241.6250 F: 314.241.2570
JACKSON, MS
CANNON DESIGN PROJECT NO. 03640.61
© CannonDesign 2017 - All rights reserved. No part of this document may be reproduced or utilized in any form, without prior written authorization by the Cannon Corporation.
JAN 12, 2018
NOT FOR CONSTRUCTION
Drawing Title
Approved: Project Director
Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
Dwg. of 81Revisions: Date
CONSULTANTS: ARCHITECT/ENGINEERS: Office of Construction and Facilities Management o n e e ig h th in c h o n e fo o t 1
B
A
C
D
E
F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t
VA FORM 08-6231
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
Department of Veterans Affairs
COMMUNITY LIVING CENTER
RENOVATION
586-16-106PLUMBING RISER DIAGRAMS
PL401
JJS RJL
8F
DOMESTIC WATER RISER - 1
5F
DOMESTIC WATER RISER - 2
3F
DOMESTIC WATER RISER - 3
1F
DOMESTIC WATER RISER - 4
8D
DOMESTIC WATER RISER - 5
5D
DOMESTIC WATER RISER - 6
3D
DOMESTIC WATER RISER - 7
1D
DOMESTIC WATER RISER - 8
8B
DOMESTIC WATER RISER - 9
5B
DOMESTIC WATER RISER - 10
3B
DOMESTIC WATER RISER - 11
1B
DOMESTIC WATER RISER - 12
1 1/2" DCW
3/4" DCW
1/2" DCW
1/2" DHW
2" DHW
3" DCW
2" DHWR
1 1/2" DHW
3" DCW
2" DHWR
"A"
"A"
"A"
"A"
1 1/2" DHW
3" DCW
2" DHWR
2" DHWR
3" DCW
2" DHW
P-414
P-414
P-101
P-101 P-703
"B"
P-801
DCW: 15 WSFU
DHW: 3 WSFU
1/2" EX DCW
1/2" EX DHW
1 1/4" EX DCW
1/2" DCW
1/2" DHW
1 1/4" DCW
1/2" DHWR
"A" "A"
1/2" DCW
1/2" DHW
3/4" DHW
3/4" DCW
1/2" DCW
1/2" DHW
1/2" DHW
1/2" DCW
3/4" DCW
1/2" DCW
1/2" DCW
1/2" DHW
1 1/2" DCW
1 1/2" DCW
3/4" DHW
2" DHWR
3" DCW
1 1/2" DHW
"A" "A"
"B"
"A"
"A"
"A"
"A"
P-414
P-414
P-101
P-101 P-703
P-703
1 1/2" DCW
1/2" EX DCW
1/2" EX DHW
1 1/4" EX DCW
1 1/4" DCW
1/2" DCW
1/2" DHW
DCW: 15 WSFU
DHW: 1.5 WSFU
1/2" DHW
1/2" DCW
1/2" DHW
1/2" DHWR
1/2" DCW
1/2" DHW
1/2" DCW
1/2" DHW
1/2" DHWR
3/4" DHW
1 1/2" DCW
1 1/4" DCW
1/2" DHW
1/2" DCW
3/4" DCW
3/4" DHW
1/2" DHWR
1" DHW
1" DCW
1/2" DHWR
1/2" DCW
P-808
P-808
P-808
P-808
P-502
P-808
4" DCW
3" DHW
2" DHWR
P-418
P-521
P-608
"A"
"A"
"A"
"A"
"A"
"A"
"A"
"A"
"A"
"A"
DCW: 10.5 WSFU
DHW: 10 WSFU
DCW: 9 WSFU
DHW: 3 WSFU
3/4" DHW
3/4" DCW
3/4" DHW
3/4" DCW
3/4" DCW
3/4" DHW
3/4" DCW
3/4" DHW
4" DCW
3" DHW
2" DHWR
2" DCW
1 1/4" DHW
1/2" DHWR
1/2" DCW
1/2" DHW
1/2" DCW 1/2" DHW
2" DCW
1 1/4" DHW
1/2" DHWR
4" DCW
3" DHW
2" DHWR
4" DCW
3" DHW
2" DHWR
P-420P-528
"A"
"A""A"
"A"
"A"
"A"
DCW: 3 WSFU
DHW: 3 WSFU
3/4" EX DCW
3/4" EX DHW
3/4" DCW
3/4" DHW
1/2" DHWR
3/4" EX DCW
3/4" EX DHW
P-502
1/2" DHWR
3/4" DHW
3/4" DCW
2" DCW
1 1/2" DHW
1/2" DHWR
1/2" DHWR
1" DHW
2" DCW
2" DCW
1" DHW
1 1/4" DCW
1/2" DHW
1/2" DCW
"A"
"A"
1/2" DCW
1/2" DHW
1 1/4" DCW
1/2" DCW
1/2" DHW
P-528
P-418
P-101
P-418
P-101
P-701
"A"
"A"
"A""A"
"A"
"A"
DCW: 13.5 WSFU
DHW: 1.5 WSFU
"A"
"A"
1/2" DHW
1/2" DCW
1 1/4" DCW
1 1/4" DHW
1100 Clark Avenue St. Louis, Missouri 63102
T: 314.241.6250 F: 314.241.2570
JACKSON, MS
CANNON DESIGN PROJECT NO. 03640.61
© CannonDesign 2017 - All rights reserved. No part of this document may be reproduced or utilized in any form, without prior written authorization by the Cannon Corporation.
JAN 12, 2018
NOT FOR CONSTRUCTION
Drawing Title
Approved: Project Director
Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
Dwg. of 81Revisions: Date
CONSULTANTS: ARCHITECT/ENGINEERS: Office of Construction and Facilities Management o n e e ig h th in c h o n e fo o t 1
B
A
C
D
E
F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t
VA FORM 08-6231
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
Department of Veterans Affairs
COMMUNITY LIVING CENTER
RENOVATION
586-16-106PLUMBING RISER DIAGRAMS
PL402
JJS RJL
7F
DOMESTIC WATER RISER - 13
5F
DOMESTIC WATER RISER - 14
3F
DOMESTIC WATER RISER - 15
1F
DOMESTIC WATER RISER - 16
7C
DOMESTIC WATER RISER - 17
4" W
4" W
2" V
2" V
4" W
4" W
4" V
2" V
2" V
4" V
4" W
P-414
P-101
4" FD-D
2" FD-D
2" W
4" EX W
2" V
2" V
4" V
4" W
2" V
WCO
4" W
4" W 2" W
4" W
2" V
2" W
4" W
2" W
4" V
4" V
4" FD-D
4" FD-D
2" FD-D
2" FD-D
2" V4" W4" V
2" V
P-101
P-101
4" W
2" V
2" VP-414
4" EX W
4" EX W
4" EX V
2" V
2" V
2" V
2" V
4" W
4" W
4" W
2" V
2" V
4" W
2" V
2" V
4" W
2" W
4" W
2" W
4" W
4" W
2" V
4" V
4" V
P-414
P-101
P-101
4" FD-D
2" FD-D
2" W
2" FD-D
2" FD-D
4" EX W
4" EX W
4" EX V
2" V
2" V
4" W
6" W
4" W
4" W
4" W
4" W
2" V
2" V
2" V
4" W
2" W
4" W
4" W
4" W
2" V
2" V
4" W
2" V 4" V
2" V
4" W
4" W
4" W
2" W
2" W
2" V
4" W
2" W
4" W
4" V
4" V
4" V
P-414
4" FD-D
4" FD-D
2" FD-D
P-101
2" V
P-420
P-101
P-414
P-414
4" EX V
4" EX W
4" EX W
4" V
4" EX W
4" EX W
4" EX W
4" W
4" EX W
2" V
2" V 2" V
4" W
2" V 4" W
2" W
2" V
2" V
2" V
2" V
4" W
4" W
4" W
4" W
4" W
2" W
4" W
2" V
4" W
4" W
2" W
4" FD-D
4" FD-D
2" FD-D
2" FD-D
P-414
P-101
P-101
4" EX W
4" EX V
4" EX W
4" EX W
4" V
2" V
2" V
2" V
4" V
4" W
2" V
2" V
2" V
2" V
2" V
2" V
4" W
2" W
4" V
2" W 4" W
4" W
4" W
4" W
2" FD-D
4" FD-D
2" FD-D
4" FD-D
P-414
P-101
P-101
4" W
2" W
2" V
4" EX W
4" EX W
4" EX V
4" EX W
4" W
4" V
4" V
2" V
4" W
2" V
2" V 2" V
4" W
4" W
4" W
2" V 2" V
4" W
4" W
2" W
4" W
4" W 4" V
4" W
4" W
2" W
4" W
2" V
2" V
4" V
2" V
4" FD-D
4" FD-D
2" FD-D
P-101
P-101
2" FD-D
P-414
P-414
4" EX W
4" EX W
4" EX V
4" EX W
4" EX W
4" EX W
4" V
4" W 4" W
4" W
4" W
4" W
2" V
2" V 2" V
2" V
2" W
4" W
6" W
6" W
6" W
2" W
2" W
2" W
2" V
4" V
4" W
4" W P-418
P-524
4" EX W
4" EX W
4" EX W
4" EX W
4" EX V
4" EX V
4" W
2" EX W
2" W
4" V
4" V
2" V
4" V
4" W
2" V
2" V
2" V
2" V
2" W
4" W
4" W
6" W
6" W
6" W
4" W
4" W
2" V
2" W
4" W
2" FD-D
4" FD-D
P-414
4" W
4" W
2" V
2" V
6" W
4" W
4" W
4" W
P-418
4" W
2" EX W
2" W
1100 Clark Avenue St. Louis, Missouri 63102
T: 314.241.6250 F: 314.241.2570
JACKSON, MS
CANNON DESIGN PROJECT NO. 03640.61
© CannonDesign 2017 - All rights reserved. No part of this document may be reproduced or utilized in any form, without prior written authorization by the Cannon Corporation.
JAN 12, 2018
NOT FOR CONSTRUCTION
Drawing Title
Approved: Project Director
Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
Dwg. of 81Revisions: Date
CONSULTANTS: ARCHITECT/ENGINEERS: Office of Construction and Facilities Management o n e e ig h th in c h o n e fo o t 1
B
A
C
D
E
F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t
VA FORM 08-6231
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
Department of Veterans Affairs
COMMUNITY LIVING CENTER
RENOVATION
586-16-106PLUMBING RISER DIAGRAMS
PL403
JJS RJL
8F
WASTE AND VENT RISER - 1
6F
WASTE AND VENT RISER - 2
4F
WASTE AND VENT RISER - 3
1F
WASTE AND VENT RISER - 4
8D
WASTE AND VENT RISER - 5
6D
WASTE AND VENT RISER - 6
4D
WASTE AND VENT RISER - 7
1D
WASTE AND VENT RISER - 8
8B
WASTE AND VENT RISER - 9
2" V
2" V
2" V
2" V
2" V
2" W
6" W
6" W
6" W
4" W
4" W
4" W
4" W
4" V
2" V
2" V
2" V 2" V
2" V 4" V
4" W
4" W
4" W
2" FD-D
4" FD-D
2" FD-D
4" FD-D
P-414
P-101
P-101
4" EX W
4" EX W
4" EX V
CO
4" V
2" V
2" V
2" V
4" W
2" V
4" W
4" W
4" W
6" W
6" W
4" W
6" W
2" V
4" W
2" V
4" V
4" W
4" W
4" W
4" W
4" W
6" W
2" V
2" V
2" FD-D
2" FD-D
4" FD-D
4" FD-DP-414
P-101
P-101
4" EX W
4" EX W
4" EX V
4" V
2" V
2" V
2" FD-D
4" FD-D
P-421
P-114
2" FD-D
4" FD-D
P-414P-101
2" V 2" V
4" V
4" W
2" V
3" V
2" W
4" W
6" W
4" W
4" W
4" W
4" W
4" W
4" W
2" V
2" W
4" W
4" W
6" W
6" W
4" V
4" W
4" V
4" V
4" EX V
4" EX W
4" EX V
4" EX W
4" EX W
4" EX V
4" W
4" W
4" W
4" W
2" V
2" W
2" V
4" V
4" W
2" W2" V
2" V
2" V
2" V
2" W
4" W
6" W
6" W
2" V
4" W
4" W
4" W
4" V
2" V
2" V
4" W
4" W
4" W
2" V
4" V
4" FD-D
4" FD-D
2" FD-D
2" V
2" V
2" FD-D
P-414
P-101
P-101
4" EX V
4" EX W
2" V
2" V
2" V2" V
2" V
2" V
6" W
2" V
2" V
2" V
2" V
2" V
4" W
4" W
4" W 4" W
6" W
6" W
6" W
2" V
2" V
4" V
4" W
2" V
2" V
2" W
4" FD-D
4" FD-D
2" FD-D
2" FD-D
P-414
P-101
P-101
4" V
4" EX V
4" V
4" W
2" V
2" V
2" V
4" W
4" W
2" V
4" W
3" W
4" W
4" W
4" W
4" W
4" W
4" W
2" V
2" W
2" V
2" V
2" V
2" V 2" V
2" V
2" V
2" V
2" V
2" V
2" V
4" W
3" W 3" W
2" W
4" W
4" FD-D
P-101
P-418
4" FCO
3" FD-D
P-808
P-808
P-502
3" FCO
2" W
2" V
2" W
P-521
P-608
3" W
4" W
2" V
2" V
2" V
4" W
3" V
4" W
2" V
2" V
2" W 2" W
4" W
4" W
4" W
P-528 P-420
4" FD-D
P-502
4" EX W
4" EX W
4" W
EXISTING
FD
EXISTING
FD
2" V
2" V
2" V
4" W
4" W
4" W
2" V
4" W
2" V
2" V
EXISTING
FD
P-418
4" FCO
2" FD-D
P-101
P-418
P-528
2" V
2" V
3" V
2" V
2" V
2" V
2" W
4" W 4" W
4" W
2" V
4" V
2" V
2" V 4" W
2" W
4" W
4" W
2" W
4" FD-D
4" W
4" EX W
4" EX W
4" EX W
4" EX W
4" W
4" W
2" V
1100 Clark Avenue St. Louis, Missouri 63102
T: 314.241.6250 F: 314.241.2570
JACKSON, MS
CANNON DESIGN PROJECT NO. 03640.61
© CannonDesign 2017 - All rights reserved. No part of this document may be reproduced or utilized in any form, without prior written authorization by the Cannon Corporation.
JAN 12, 2018
NOT FOR CONSTRUCTION
Drawing Title
Approved: Project Director
Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
Dwg. of 81Revisions: Date
CONSULTANTS: ARCHITECT/ENGINEERS: Office of Construction and Facilities Management o n e e ig h th in c h o n e fo o t 1
B
A
C
D
E
F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t
VA FORM 08-6231
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
Department of Veterans Affairs
COMMUNITY LIVING CENTER
RENOVATION
586-16-106PLUMBING RISER DIAGRAMS
PL404
JJS RJL
8F
WASTE AND VENT RISER - 10
6F
WASTE AND VENT RISER - 11
3F
WASTE AND VENT RISER - 12
1F
WASTE AND VENT RISER - 13
8C
WASTE AND VENT RISER - 14
6C
WASTE AND VENT RISER - 15
3C
WASTE AND VENT RISER - 16
1C
WASTE AND VENT RISER - 17
SHOCK ARRESTOR SCHEDULE
ABBREV. CONNECTION
SIZE
1-11
FIXTURE
UNIT
CAPACITY
NOM.
PIPE SIZE
1/2" --
REMARKS
“A”
12-32 3/4”“B”
33-60 1"“C”
61-113 1-1/4"“D”
114-154 1-1/2"“E”
1/2"
3/4”
1"
1-1/4"
1-1/2"
PLUMBING FIXTURE SCHEDULE
DESCRIPTION
WASTE PIPE
WATER CLOSET, FLOOR MOUNT [100] 2 [50] 1.25 [31]
1.5 [38] 0.5 [13]
[50] 0.75 [19] 0.75
0.5
[50]
[75]
LAVATORY, WALL HUNG
SINK SERVICE, FLOOR
MARK
P402
P502
P101 --
[13]
[19] 3
WASTE
FIXTURE
UNITS
NO
NO
ELECTRIC
SENSOR
WATER
FIXTURE
UNITS
4 --
REMARKS
[50] 0.5 [13] 0.52[50]2SINK, COUNTERP528 [13] 2 NO2 --
1.5 [38] 0.5 [13]
[38] 0.5 [13] 0.5
1.5
[50]
[50]
ELECTRIC WATER COOLER
SHOWER
P608
P703
[13] 2
NO
NO1
120 V, 1 PH
VENT PIPE COLD WATER HOT WATER
[mm]IN [mm]IN [mm]IN [mm]IN
FLOOR DRAINFD-D VARIES VARIES 2 [50] VARIES VARIES N/A -------- --
P808 WASHING MACHINE SUPPLY & DRAIN [50]2 [38]1.5 0.5 [13] 1 1
TP-1 TRAP PRIMER -------- ----[19]0.75 ------ --
1.5 [38] 0.5 [13] 0.5[50]2LAVATORY, INTEGRAL BOWLP414 [13] 2 2 --
P803 HOSE BIBB (CONCEALED PIPING) ---- ---- 0.75 [19] ---- -- 4
P114 WATER CLOSET, BARIATRIC FLOOR MOUNT -- -- NO
[50] 0.5
[13]
0.52
[50]2LAUNDRY TUBP521 [13] 2 NO2
P801 WALL HYDRANT ---- ---- 0.75 [19] ---- -- 4 -- --
NOTE: PERFORMANCE AND ADDITIONAL APPURTENANCES IN THE SPECIFICATION.
[100] 2 [50] 1.25 [31]4 6 10
1.5 [38] 0.5 [13] 0.5[50]2LAVATORY, BARIATRIC FLOOR MOUNTP421 [13] 2 2
[50] 0.52
[13][50]2KITCHEN SINKP524 [13] 2 NO2
0.5
0.5 [13]
YES
NO
NO
[50] 1.5 [38] 0.52[100]4CLINICAL SERVICE SINKP505 [19] 6 NO10 --
1.5 [38] 0.5 [13] 0.5[50]2LAVATORY, WALL HUNGP418 [13] 2 2 YES
[38] 0.5 [13] 0.51.5[50]2SHOWER W/ BASEP701 [13] 2 NO2
DUAL FLUSH
FLOW
RATE
2.2 GPM
2.2 GPM
0.5 GPM
2.2 GPM
[50] 0.5 [13] 0.52[50]2SINK, SALONP530 [13] 2 NO2 ---
-- 0.5 [13] 0.5----TO SINKEYE WASH, DECK MOUNTP709 [13] 2 NO2 ---
DUAL FLUSH
1.5 [38] 0.5 [13] 0.5[50]2EYE WASH, WALL MOUNTP708 [13] 2 2 NO -
ZONE VALVE BOX SCHEDULE
DESCRIPTION
ZONE VALVE BOX #1
ABBREV.
MEDICAL
AIR
1/2" 1-1/4"
MEDICAL
VAC
O2
1/2" --
REMARKS
ZVB-1
EQUIPMENT CONNECTION SCHEDULE
DESCRIPTION
WALL OUTLETS
ABBREV.
MEDICAL
AIR
1/2" 3/4"
MEDICAL
VAC
O2
1/2" --
REMARKS
MGO-1
PUMP SCHEDULE
MANUFACTURER
BELL & GOSSETT
ABBREV. MODEL NO.
PL-55BCP-1
FLOW (GPM)
TOTAL DISCHARGE HEAD
HORSEPOWER
(HP)
2/5
ELECTRICAL
V/PH
115/1
COMMENTS
EXISTING TO BE REPIPED
BELL & GOSSETT PL-55BCP-2 26 30 2/5 115/1 EXISTING TO BE REPIPED, PUMP IS REDUDANT
AREA ALARM PANEL SCHEDULE
DESCRIPTION
AREA ALARM PANEL
ABBREV.
MEDICAL
AIR
1/2" 1-1/4"
MEDICAL
VAC
O2
1/2" --
REMARKS
AAP-1
1100 Clark Avenue St. Louis, Missouri 63102
T: 314.241.6250 F: 314.241.2570
JACKSON, MS
CANNON DESIGN PROJECT NO. 03640.61
© CannonDesign 2017 - All rights reserved. No part of this document may be reproduced or utilized in any form, without prior written authorization by the Cannon Corporation.
JAN 12, 2018
NOT FOR CONSTRUCTION
Drawing Title
Approved: Project Director
Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
Dwg. of 81Revisions: Date
CONSULTANTS: ARCHITECT/ENGINEERS: Office of Construction and Facilities Management o n e e ig h th in c h o n e fo o t 1
B
A
C
D
E
F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t
VA FORM 08-6231
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
Department of Veterans Affairs
COMMUNITY LIVING CENTER
RENOVATION
586-16-106PLUMBING SCHEDULES
PL501
JJS RJL
BACKFLOW PREVENTER SCHEDULE
ABBREV DESCRIPTION LOCATION SERVING SIZE REMARKS
BFP-1 BACKFLOW PREVENTER MECHANICAL ROOM DOMESTIC 4" REDUCED PRESSURE TYPE
BFP-2 BACKFLOW PREVENTER PIPE BASEMENT DOMESTIC MATCH EXISTING DOUBLE CHECK DETECTOR TYPE
BFP-3 BACKFLOW PREVENTER MECHANICAL ROOM MECHANICAL MAKEUP 1" REDUCED PRESSURE TYPE
2F
P-103 WATER CLOSET DETAIL - SENSOR OPERATED
NTS
FINISHED FLOOR
FINISHED WALL
SOLENOID
OPERATED FLUSH
VALVE
BACK CHECK
ANGLE STOP
F O
R F
IX
T
U R
E H
E
IG
H T
S
S E
E A
R C
H
IT
E C
T U
R A
L
D R
A W
IN
G
S
[4 m m
[1 m m
[8 m m
GRAB BAR, SEE
ARCH.
DRAWINGS
SOLENOID
TRANSFORMER
IN JUNCTION
BOX
MOUNT ELECTRONIC
SENSOR IN 12"x16"
[300x400mm] PANEL
1F
TYPE "D" FLOOR DRAIN DETAIL
NTS
COMPOSITION
FLOORING
NOTE:
PROVIDE FLASHING WHEN DRAIN IS INSTALLED IN A NON MEMBRANE FLOOR
CAULKED, NO-HUB OR
THREADED CONNECTION
ADJUSTABLE NICKEL BRONZE
STRAINER WITH 4" [100mm]
FLANGE
INVERTIBLE
FLASHING
COLLAR
LOOSE GRAVEL AT
WEEP HOLES
3mm TO 6mm
GRAVEL SIZE
WEEP HOLES
FLASHING, MIN. 24" [600mm]
SQUARE 2 1/2 LB. [1.1kg] TO 4 LB.
[1.8kg] LEAD OR 16 OZ. [0.45kg]
COPPER
8D
TYPICAL WHEELCHAIR LAVATORY DETAIL
NTS
F O
R F
IX
T
U R
E H
E
IG
H T
S S
E E
A R
C H
IT
E
C T
U R
A L D
R A
W
IN
G S
LOOSE KEY
STOP
[8 m m
ESCUTCHEON
FINISHED FLOOR
FAUCET SEE
SPECIFICATIONS
LAMINAR FLOW
CONTROL DEVICE
[200mm]
OFFSET
WASTE
TRAP
PARALLEL TO
WALL
[2 m m
/4
8"
EXPOSED, UNDER SINK
ASSE 1070
THERMOSTATIC
MIXING VALVE
DCW
SUPPLY
DHW
SUPPLY
6D
P-505 CLINIC SERVICE SINK ROUGH-IN DETAIL
NTS
P E
R M
A N
U F
A C
T U
R E
R S
R E
C O
M M
E N
D A
T
IO
N S
F R
O M
F
IN
IS
H
E D
F L O
O R
[150mm]
[1 m m
[1 m m
[1 m m
[1 m m
[7 m m
[5 m m
[300mm]
[225mm]
P E
R M
A N
U F
A C
T U
R E
R S
R E
C O
M M
E N
D A
T
IO
N S
3/8" [11mm] H
& CW
CARRIER LEG
FINISHED FLOOR
3/8" [11mm]
TW FROM PEDAL
VALVE
7/8" [22mm]∅ HOLE
1/2" [13mm]
[300mm]
NOTE:
PROVIDE AN ADDITIONAL 16 GAGE GALVANIZED STEEL
PLATE 12"x16" [300x400mm] SECURED TO A MINIMUM
OF 2 STUDS FOR A FOOT PEDAL.
1/2" [13mm] H&CW
[100mm]
[3 m m
C E
N T
E R
L
IN
E O
F
S P
O U
T B
R A
C E
[2 m m
[500mm]
1/2" [13mm] FROM VACUUM BREAKER
1/2" [13mm] TO VACUUM BREAKER
F R
O M
F
IN
IS
H
E D
F L O
O R
1/2" [13mm] TO
SPRAY NOZZLE
[1 m m
9"
20"
12"
6"
" 6
/4
/4
R O
U G
H -I
N R
O U
G H
-I N
12"
[1 m m T
O
4"
[1 m m
2D
P-703 PATIENT SHOWER
NTS
8"x8"x3"
[200x200x75mm]
ACCESS BOX
W/S.S. LOCKING
DOOR ON OPP.
WALL. SEE DETAIL
AT LEFT
[7 m m
SECTION A
ACCESS BOX W/VALVE
S.S. DOOR W/VANDALPROOF
LOCK (KEYED)
SUPPLY PIPE
ELEVATION
[2 m m
[7 m m
[1 m m
[375mm]
FINISHED
FLOOR
COMBINATION
CHECK-STOP VALVES
SHOWER
CONTROL VALVE
TYPE T/P
BALL TYPE
SHUTOFF VALVE
IN BOX
A
ALT HANDLE
POSITION (CLOSED)
SHUTOFF VALVE
TILE WALL
[2 m m
A
[8 m m
[600mm]
EDGE OF SHOWER
INSTITUTIONAL
SHOWER HEAD
/2
15"
2'-0"
THERMOSTATIC
MIXING VALVE
DCW
SUPPLY
DHW
SUPPLY
P P
TP
TP
PP
DHW 140
CW
STEAM HEADER
FINISHED FLOOR
CDCD
EXPANSION TANK
SHUT-OFF VALVE
(TYPICAL)
THERMOMETER
(WITH VALVE)
(TYPICAL)
UNION (TYPICAL)
PROVIDE NEW
TEMPERATURE
& PRESSURE
RELIEF VALVE
(TYPICAL)
TO FLOOR
DRAIN
(TYPICAL)
DRAIN
(FULL SIZE)
TO FLOOR
DRAIN
(TYPICAL)
ORIFICE UNION
(TYPICAL)
PRESSURE
GAGE (TYPICAL)
STEAM FIRED
DOMESTIC WATER
HEATER (TYPICAL)
CONTROL VALVE
(TYPICAL)
STRAINER
(TYPICAL)
TRAP
(TYPICAL)
CHECK VALVE
(TYPICAL)
DIRT LEG
(TYPICAL)
TO CONDENSATE
RETURN UNIT
NOTE:
STEAM AND
CONDENSATE BY
MECHANICAL
NOTE:
ONLY ONE PUMP TO RUN
AT A TIME. PUMPS SHALL
BE CONNECTED TO BAS.
EXISTING
STEAM
WATER
HEATER
TO REMAIN
EXISTING
STEAM
WATER
HEATER
TO REMAIN
DHW 140
DHW 130 DHW 130
DHWR 125
P
BALL VAVE (TYP.)
UNION (TYP.)
TH
TH
140°
140°
140°
THERMOMETER
(0-210ºF) TYP.
PIPE ARRANGEMENT SHALL
COMPLY WITH THE MANUFACTURERS
RECOMMEDATIONS
THERMOSTATIC
MIXING VALVE
PRESSURE GAUGETH
EXISTING
CIRCULATING PUMP
CP-1 (TYP)
CHECK VALVE (TYP)
DHWR 125DHWR 125
DCW
DHW 130
SEE FLOOR PLAN
FOR CONTINUATION
AND PIPE SIZES
EXISTING
CIRCULATING PUMP
CP-2 (TYP)
DCW
EXISTING
WATER
QUALITY AND
MONITORING
STATION
TO DRAIN
SHUT OFF VALVE (TYP.)
BALANCING VALVE
BALANCE TO 0.5 GPM
UNLESS NOTED ON DRAWING
THERMOMETER
CHECK VALVE
1100 Clark Avenue St. Louis, Missouri 63102
T: 314.241.6250 F: 314.241.2570
JACKSON, MS
CANNON DESIGN PROJECT NO. 03640.61
© CannonDesign 2017 - All rights reserved. No part of this document may be reproduced or utilized in any form, without prior written authorization by the Cannon Corporation.
JAN 12, 2018
NOT FOR CONSTRUCTION
Drawing Title
Approved: Project Director
Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
Dwg. of 81Revisions: Date
CONSULTANTS: ARCHITECT/ENGINEERS:…