36C25618B0375-00004004.pdf
PDF 140 KB Posted
- Solicitation number
- 36C25618B0375
About this file
36C25618B0375 00004 102600.pdf
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 36C25618B0375-00004000.docx | DOCX document | |
| 36C25618B0375-00004003.pdf | ||
| 36C25618B0375-00004005.pdf | ||
| 36C25618B0375-00004001.pdf | ||
| 36C25618B0375-00004006.pdf | ||
| 36C25618B0375-00004002.pdf | ||
| 36C25618B0375-00003000.docx | DOCX document | |
| 36C25618B0375-00002000.docx | DOCX document | |
| 36C25618B0375-00002001.pdf | ||
| 36C25618B0375-00001000.docx | DOCX document | |
| 36C25618B0375-001.docx | DOCX document | |
| 36C25618B0375-009.pdf | ||
| 36C25618B0375-010.pdf | ||
| 36C25618B0375-007.pdf | ||
| 36C25618B0375-003.pdf | ||
| 36C25618B0375-004.pdf | ||
| 36C25618B0375-006.pdf | ||
| 36C25618B0375-008.pdf | ||
| 36C25618B0375-005.pdf | ||
| 36C25618B0375-002.pdf | ||
| 36C25618B0375-000.docx | DOCX document |
Show all 21
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
10-01-15
Jackson, MS VA Medical Center Addendum No.1, May 17, 2018
Renovate Ground Floor Community Living Center
VA Project No. 586-16-106
CannonDesign Project No. 003640.61
10 26 00 - 1
SECTION 10 26 00
WALL AND DOOR PROTECTION
PART 1 - GENERAL
1.1 DESCRIPTION:
A. This section specifies wall guards, handrail/wall guard combinations, corner guards and door/door frame protectors and high impact wall covering.
1.2 RELATED WORK:
A. Structural Steel Corner Guards: Section 05 50 00, METAL FABRICATIONS.
B. Armor plates and kick plates not specified in this section: Section 08
71 00, DOOR HARDWARE.
1.3 QUALITY ASSURANCE:
A. Manufacturer’s Qualifications: Manufacturer with a minimum of three (3) years’ experience in providing items of type specified.
1. Obtain wall and door protection from single manufacturer.
B. Installer’s Qualifications: Installers are to have a minimum of three
(3) years’ experience in the installation of units required for this project.
1.4 SUBMITTALS:
A. Submit in accordance with Section 01 33 23, SHOP DRAWINGS, PRODUCT
DATA, AND SAMPLES.
B. Shop Drawings: Show design and installation details.
C. Manufacturer's Literature and Data:
1. Wall Guards.
2. Corner Guards.
3. High Impact Wall covering.
D. Test Report: Showing that resilient material complies with specified fire and safety code requirements.
E. Manufacturer’s qualifications.
F. Installer’s qualifications.
G. Manufacturer’s warranty.
1.5 DELIVERY AND STORAGE:
A. Deliver materials to the site in original sealed packages or containers marked with the name and brand, or trademark of the manufacturer.
B. Protect from damage from handling and construction operations before, during and after installation.
Renovate Ground Floor Community Living Center
10 26 00 - 2
C. Store in a dry environment of approximately 21 degrees C (70 degrees F) for at least 48 hours prior to installation.
1.6 WARRANTY:
A. Construction Warranty: Comply with FAR clause 52.246-21 “Warranty of
Construction”.
B. Manufacturer Warranty: Manufacturer shall warranty their wall and door protection for a minimum of five (5) // // years from date of installation and final acceptance by the Government. Submit manufacturer warranty.
1.7 APPLICABLE PUBLICATIONS:
A. Publications listed below form a part of this specification to extent referenced. Publications are referenced in text by basic designation only.
B. ASTM International (ASTM):
A240/A240M-14...........Chromium and Chromium-Nickel Stainless Steel
Plate, Sheet, and Strip for Pressure Vessels and For General Applications
B221-14.................Aluminum and Aluminum-Alloy Extruded Bars, Rods, Wire, Shapes, and Tubes
B221M-13................Aluminum and Aluminum-Alloy Extruded Bars, Rods, Wire, Shapes, and Tubes (Metric)
D256-10.................Impact Resistance of Plastics
D635-10.................Rate of Burning and/or Extent and Time of
Burning of Self-Supporting Plastics in a
Horizontal Position
E84-14..................Surface Burning Characteristics of Building
Materials
C. Aluminum Association (AA):
DAF 45-09...............Designation System for Aluminum Finishes
D. American Architectural Manufacturers Association (AAMA):
611-14..................Anodized Architectural Aluminum
E. Code of Federal Regulation (CFR):
40 CFR 59...............Determination of Volatile Matter Content, Water
Content, Density Volume Solids, and Weight
Solids of Surface Coating
F. The National Association of Architectural Metal Manufacturers (NAAMM):
Renovate Ground Floor Community Living Center
10 26 00 - 3
AMP 500-06..............Metal Finishes Manual
G. National Fire Protection Association (NFPA):
80-13...................Standard for Fire Doors and Windows
H. SAE International (SAE):
J 1545-05(R2014)........Instrumental Color Difference Measurement for
Exterior Finishes.
I. Underwriters Laboratories Inc. (UL):
Annual Issue............Building Materials Directory
PART 2 - PRODUCTS
2.1 MATERIALS:
A. Stainless Steel: A240/A240M, Type 304.
B. Resilient Material:
1. Provide resilient material consisting of high impact resistant extruded acrylic vinyl, polyvinyl chloride, or injection molded thermal plastic conforming to the following:
a. Minimum impact resistance of 960.8 N-m/m (18 ft.-lbs./sq. inch) when tested in accordance with ASTM D256 (Izod impact, ft.-lbs.
per inch notched).
b. Class 1 fire rating when tested in accordance with ASTM E84, having a maximum flame spread of 25 and a smoke developed rating of 450 or less.
c. Rated self-extinguishing when tested in accordance with
ASTM D635.
d. Provide material labeled and tested by Underwriters Laboratories or other approved independent testing laboratory.
e. Provide resilient material for protection on fire rated doors and frames assemblies that is listed by the testing laboratory performing the tests.
f. Provide resilient material installed on fire rated wood/steel door and frame assemblies that have been tested on similar type assemblies. Test results of material tested on any other combination of door and frame assembly are not acceptable.
g. Provide integral color with colored components matched in accordance with SAE J 1545 to within plus or minus 1.0 on the
CIE-LCH scales.
Renovate Ground Floor Community Living Center
10 26 00 - 4
2.2 CORNER GUARDS:
A. Resilient, Shock-Absorbing Corner Guards: Surface mounted type.
1. Profile: Minimum 76 mm (3 inch) long leg and 6 mm (1/4 inch) corner radius.
2. Height: 2.43 m (8 feet).
3. Provide factory fabricated end closure caps at top and bottom of surface mounted corner guards.
B. Fabricate stainless steel corner guards of 1.27 mm (.05 inch) thick material conforming to ASTM A240/A240M, Type 304. Install corner guards as indicated on construction documents. Form corner guard to dimensions shown on construction documents.
2.3 HIGH IMPACT WALL COVERING:
A. Provide wall covering/panels consisting of high impact rigid acrylic vinyl or polyvinyl chloride resilient material.
B. Panel sizes to be 0.61 x 1.21 m (2 x 4 ft.).
C. Submit fire rating and extinguishing test results for resilient material.
D. Submit statements attesting that the items comply with specified fire and safety code requirements.
E. Rigid Vinyl Acrylic Wall Covering: Wall covering thickness to be 0.71 mm (0.028 inch).
F. Provide adhesive as recommended by the wall covering manufacturer.
2.4 FASTENERS AND ANCHORS:
A. Provide fasteners and anchors as required for each specific type of installation.
B. Where type, size, spacing or method of fastening is not shown or specified in construction documents, submit shop drawings showing proposed installation details.
2.5 FINISH:
A. Stainless Steel: In accordance with NAAMM AMP 500 finish Number 4.
B. Resilient Material: Embossed textures and color in accordance with
SAE J1545.
PART 3 - INSTALLATION
3.1 RESILIENT CORNER GUARDS:
A. Install corner guards on walls in accordance with manufacturer's instructions.
Renovate Ground Floor Community Living Center
10 26 00 - 5
3.2 STAINLESS STEEL CORNER GUARDS:
A. Mount guards on external corners of interior walls, partitions and columns as shown on construction documents.
B. Where corner guards are installed on gypsum board, clean surface and anchor guards with a neoprene solvent-type contact adhesive specifically manufactured for use on gypsum board construction. Remove excess adhesive from around edge of guard and allow curing undisturbed for 24 hours.
3.3 RESILIENT WALL GUARDS
A. Secure guards to walls with brackets and fasteners in accordance with manufacturer's details and instructions.
3.4 ALUMINUM WALL GUARDS
A. Secure brackets to walls with fasteners, spaced in accordance with manufacturer's installation instructions.
3.5 STAINLESS STEEL WALL GUARDS
A. Space brackets at not more than 914 mm (3 feet) on centers and anchor to the wall in accordance with manufacturer's installation instructions.
3.6 HIGH IMPACT WALL COVERING
A. Surfaces to receive protection to be clean, smooth and free of obstructions.
B. Install protectors after frames are in place but preceding installation of doors in accordance with approved shop drawings and manufacturer’s specific instructions.
C. Apply with adhesive in controlled environment according to manufacturer’s recommendations.
D. Protection installed on fire rated doors and frames to be installed according to NFPA 80 and installation procedures listed in UL Building
Materials Directory; or, equal listing by other approved independent testing laboratory establishing the procedures.
- - - E N D - - -