36C25618B0375-00002000.docx
DOCX document 938 KB Posted
- Solicitation number
- 36C25618B0375
About this file
36C25618B0375 00002 36C25618B0375 00002.docx
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 36C25618B0375-00004000.docx | DOCX document | |
| 36C25618B0375-00004003.pdf | ||
| 36C25618B0375-00004005.pdf | ||
| 36C25618B0375-00004004.pdf | ||
| 36C25618B0375-00004001.pdf | ||
| 36C25618B0375-00004006.pdf | ||
| 36C25618B0375-00004002.pdf | ||
| 36C25618B0375-00003000.docx | DOCX document | |
| 36C25618B0375-00002001.pdf | ||
| 36C25618B0375-00001000.docx | DOCX document | |
| 36C25618B0375-001.docx | DOCX document | |
| 36C25618B0375-009.pdf | ||
| 36C25618B0375-010.pdf | ||
| 36C25618B0375-007.pdf | ||
| 36C25618B0375-003.pdf | ||
| 36C25618B0375-004.pdf | ||
| 36C25618B0375-006.pdf | ||
| 36C25618B0375-008.pdf | ||
| 36C25618B0375-005.pdf | ||
| 36C25618B0375-002.pdf | ||
| 36C25618B0375-000.docx | DOCX document |
Show all 21
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
5. PROJECT NUMBER (if applicable)
CODE
7. ADMINISTERED BY
2. AMENDMENT/MODIFICATION NUMBER
CODE
6. ISSUED BY
8. NAME AND ADDRESS OF CONTRACTOR
4. REQUISITION/PURCHASE REQ. NUMBER
3. EFFECTIVE DATE
9A. AMENDMENT OF SOLICITATION NUMBER
9B. DATED
PAGE
OF PAGES
10A. MODIFICATION OF CONTRACT/ORDER NUMBER
10B. DATED
BPA NO.
1. CONTRACT ID CODE
FACILITY CODE
CODE
Offers must acknowledge receipt of this amendment prior to the hour and date specified in the solicitation or as amended, by one of the following methods:
The above numbered solicitation is amended as set forth in Item 14. The hour and date specified for receipt of Offers
E. IMPORTANT:
is extended,
(a) By completing Items 8 and 15, and returning __________ copies of the amendment; (b) By acknowledging receipt of this amendment on each copy of the offer submitted; or (c) By separate letter or electronic communication which includes a reference to the solicitation and amendment numbers. FAILURE OF YOUR ACKNOWLEDGMENT TO BE RECEIVED AT THE PLACE DESIGNATED FOR THE RECEIPT OF OFFERS PRIOR TO THE HOUR AND DATE SPECIFIED MAY is not extended.
12. ACCOUNTING AND APPROPRIATION DATA
(REV. 11/2016)
is required to sign this document and return ___________ copies to the issuing office.
is not, A. THIS CHANGE ORDER IS ISSUED PURSUANT TO: (Specify authority) THE CHANGES SET FORTH IN ITEM 14 ARE MADE IN THE CONTRACT ORDER NO. IN ITEM 10A.
15C. DATE SIGNED
B. THE ABOVE NUMBERED CONTRACT/ORDER IS MODIFIED TO REFLECT THE ADMINISTRATIVE CHANGES SET FORTH IN ITEM 14, PURSUANT TO THE AUTHORITY OF FAR 43.103(b).
RESULT IN REJECTION OF YOUR OFFER. If by virtue of this amendment you desire to change an offer already submitted, such change may be made by letter or electronic communication, provided each letter or electronic communication makes reference to the solicitation and this amendment, and is received prior to the opening hour and date specified.
C. THIS SUPPLEMENTAL AGREEMENT IS ENTERED INTO PURSUANT TO AUTHORITY OF:
D. OTHER
BY
Contractor
16C. DATE SIGNED
14. DESCRIPTION OF AMENDMENT/MODIFICATION
16B. UNITED STATES OF AMERICA
Except as provided herein, all terms and conditions of the document referenced in Item 9A or 10A, as heretofore changed, remains unchanged and in full force and effect.
15A. NAME AND TITLE OF SIGNER
16A. NAME AND TITLE OF CONTRACTING OFFICER
15B. CONTRACTOR/OFFEROR
STANDARD FORM 30
PREVIOUS EDITION NOT USABLE
Prescribed by GSA - FAR (48 CFR) 53.243 (Type or print) (Type or print) (Organized by UCF section headings, including solicitation/contract subject matter where feasible.)
(Number, street, county, State and ZIP Code) (If other than Item 6) (Specify type of modification and authority) (such as changes in paying office, appropriation date, etc.)
(If required)
(SEE ITEM 11)
(SEE ITEM 13)
(X)
CHECK
ONE
13. THIS ITEM APPLIES ONLY TO MODIFICATIONS OF CONTRACTS/ORDERS,
IT MODIFIES THE CONTRACT/ORDER NO. AS DESCRIBED IN ITEM 14.
11. THIS ITEM ONLY APPLIES TO AMENDMENTS OF SOLICITATIONS
AMENDMENT OF SOLICITATION/MODIFICATION OF CONTRACT
(Signature of person authorized to sign) (Signature of Contracting Officer) 00002 586-16-106 00586 Department of Veterans Affairs G.V. (Sonny) Montgomery VAMC 1500 E. Woodrow Wilson Dr.
Jackson
MS
39216 10N16 Department of Veterans Affairs G.V. (Sonny) Montgomery VAMC A&MM Service (90C) 715 South Pear Orchard Road Ridgeland
MS
39157 To all Offerors/Bidders
36C25618B0375 05-16-2018
X x x Reference Solicitation 36C25618B0375, Amendment A00002 is issued as follows:
1. RFI's and corresponding answers are attached.
2. No other changes are made at this time.
Ashlei Donerson Contractiing Officer
A.1 RFIS
| Date |
| May 14, 2018 |
| To |
| Jason Steed |
| From |
| Amy Phillips |
| Project |
| VA Jackson: CLC Renovation 586-16-106 |
| Project No. |
| 003640.61 |
Page 1 of
| Bidders Questions – Received 05.10.2018 |
| CannonDesign Response 05.14.2018 |
1. Please confirm that the work will be allowed to be completed in two phases as shown on sheet G0301.
The entire basement level will be vacated and available to Contractor. With that said, if chosen, there is no issue in doing the asbestos abatement in two phases but it must be remembered that a separate mobilization, air clearance, and 10 day advance notification would be required for each phase. Also, building the containment adds considerable cost to the abatement and two phases would necessitate two containments.
| 2. Are there any work restriction (off hours) that we need to be aware of? |
| Major utility shutdowns or temporary tie-ins may require off hours. Please see specification requirements as related to disruptions to functioning of medical center. |
| 3. Some Gypsum Board Framed Walls extend from finish floor to the underside of the deck above. What is the dimension or height from finish floor to the underside of the deck? |
| Existing drawings indicate 14’ deck to deck. Contractor will need to verify in field. |
| 4. The Architectural Equipment Schedule on plan sheet A0002 indicates a med gas wall box but we cannot locate any specifications or basis of design. Please provide specifics on how this headwall is to be configured. |
| AR-03 indicated on the equipment schedule shall be Amico Corporation; Reflection Series Artwall. |
| 5. Specification Section 02 82 11 part 1.1.2 Extent of Work states that 25,000 square feet of asbestos containing floor time and mastic is to be abated. No abatement investigative survey has been supplied. Please confirm that we are to utilize this quantity or is there a survey that can be provided? |
| As illustrated on dwg. No. G0201, the total building floor area only equals 22,500 sq.ft., with only 21,978 sq.ft. being renovated. Not sure why a greater number was stated. See attached asbestos survey. |
| 6. Specification Section 02 83 33.13 Lead Based Paint Removal and Disposal states under Part 1.1 that this section includes removing and disposal of lead-based paint at interior locations indicated in existing conditions report. We cannot locate an existing conditions report. Please advise. |
| No lead is known to be present. |
| 7. The demolition drawings indicate walls and floor finishes to be demolished but do not delineate what types of walls or type of flooring is to be removed. Can as-built drawings be provided or another form identifying this missing information. |
| VA established a day / time for prebid site visits. Questions such as these should have been addressed at that time. |
| 8. Window shades are indicated to be installed on the existing exterior windows but no dimensions are provided. Please advise. |
| Window sizes vary. Typical resident room full window unit size is 4’-2 ¼”W x 9’2 ½”. Contractor to verify all window sizes prior to ordering and indicate on shop drawings. |
| 9. The corner guard locations are indicted on A1301 but the designation CG-1 cannot be located. Vinyl and Stainless Steel corner guards are detailed on sheet A0810. Please advise on the CG designations. |
| There are only vinyl corner guards. CG-1 is vinyl. Reference to stainless steel corner guards in the specification will be removed. The stainless-steel corner guard details on A0810 will also be removed per addendum. |
| 10. Vinyl Coated Fabric Wall Coverings are specified but locations and sizes cannot be located. Please advise. |
| WC-1 (writable wall covering) is located in nursing alcoves (A0601) and in north wall of the conference room. Will add to finish plan with addendum. |
| 11. We cannot locate on the drawings the Marker Boards specified in 10 11 13 Chalkboards and Marker Boards. Please advise. |
| Will add to equipment list and will locate on typical patient room plan with addendum. This is an 8.5x11 wall mount board. |
| 12. No signage details or locations can be located on the drawings. Please advise. |
| Typical room signage, code required signage, and ADA details are located on sheet A0002. Final names and numbers to be coordinated with the VA. |
| 13. Specification Section 11 26 00 indicates that there is a nourishment unit consisting of a stainless steel cabinet with sink and fixture and a refrigerator, ice maker and dispenser. We cannot locate this unit on the drawings. Please advise. |
| There is no nourishment unit. However, the other components listed are used. |
| 14. Specification Section 12 31 00 Manufactured Metal Casework indicates that there is metal casework within the project. No metal casework can be located on the drawings. Please advise. |
| Section 123100 will be removed by Addendum. |
| 15. Specification Section 13 05 41 indicates to install seismic restraints. Please advise if seismic constraints are required. |
| Yes, Site class D and seismic design category D. Clarifications will be issued with Addendum. |
| 16. Can the existing fire alarm system vendor and/or manufacturer be identified? |
| Design coordinated with Siemens. |
| 17. Can the existing nurse call system vendor and/or manufacturer be identified? |
| Design based on Rauland nurse call system. |
| 18. Can the existing Access Control system vendor and/or manufacturer be identified? |
| Design coordinated with Siemens. |
| 19. Can the existing intrusion detection system vendor and/or manufacturer be identified? |
| Intrusion detection system is not part of this design scope. |
20. Is this project sales tax exempt? If the project is sales tax exempt can the government provide a sales tax exemption certificate?
Mississippi Prime Contractors Tax is required. Please verify state laws as it pertains to construction.
| 21. Will the Government provide comprehensive written badging requirements for the project if badging is required? |
| To be handled after award. Not all subs will require |
| 22. Where will the designated parking area be for workers accessing the construction site |
| A designated staging area will be provided as discussed in the prebid walkthru. Other than that, Contractors are allowed in employee lots ONLY. |
23. Will the government accept the use of the industry leading Procore Project Management software as the primary submittal and data tracking tool for this project? The software is compatible with the VA’s networks and is currently in use at many VA locations.
Yes; CannonDesign also uses Procore.
24. During construction in an area where the ceilings or fire suppression system will be disrupted, will NFPA 241 apply? Will the government require additional security measures beyond NFPA code such as fire watch, temporary fire alarms, adjustments to sprinkler heads, etc.
Refer to specification Section 013526 – Safety Requirements.
25. Does the Government have a fire alarm servicer that they currently work with? What is the name and contact information of the person or persons that will need to be coordinated with for security and fire alarm and suppression systems work and/or disruptions?
Siemens Fire Finder is our fire alarm system.
26. Has the work area been checked for asbestos?
Please see question #5
27. What is the Governments’ policy if asbestos products are encountered during construction?
Please see question #5 as well as attached Asbestos Survey.
28. Does the Government currently have a 3rd party testing service for those items requiring testing or is the contractor free to locate and hire applicable testing firms?
Please clarify question to specific testing.
29. Who is responsible for the utility locations?
Please clarify question.
30. Due to current potentially significant tariffs being placed on the importation of building materials such as wood or steel by the current Presidential Executive Branch, if a tariff is placed after bid time and before award will the government consider a price escalation on a contract value for products such as steel or wood should the executive branch levee tariffs effecting such materials? Most of these materials would still have been Buy American compliant as the tariffs would increase pricing on all steel or wood materials, regardless of origin.
This is a firm fixed price. We are not going to prematurely set the Government up for Change Orders.
| 31. Describe any and all tasks that may be required for this project as it relates to infectious control |
| Please refer to sheet G0301. |
| 32. What is the level of infectious disease control rating for this site? |
| Please refer to Note 18 in general notes on sheet G0301. |
33. Will the contractor employees be required to take the Flu Shot? Who is responsible for the cost? Same questions for TB shot.
Yes. Requirement of contract.
34. Please provide a schedule for phasing of plumbing.
Contractor is responsible for scheduling phasing and coordination of shutdowns with the VA.
35. The photography specifications mention to have a commercial photographer or subcontractor used for documentation. Does this have to be separate entity?
Please adhere to specification requirement.
36. Will there be an independent set of drawings per division for seismic restraint requirements? Will an engineer be needed to cover every division that calls for seismic restraint?
See question 15.
37. Is it possible since the engineer is from different location that they are blanketing the seismic restraint requirements throughout the specifications?
Please clarify question.
38. For demolition purposes, what materials were previous walls built out of?
Requests for existing conditions documents would need to be made to the VA.
39. In Metal Fabrications Division 05 5000, there are metal gas racks on specifications but not anywhere plans. Is that something that will be added for fabrication or will not be necessary for project?
Please refer to floor plan for oxygen storage room on sheet A0101 for location.
40. No specification on the temporary fencing, can you specify what type?
Chain link fencing will be added to Section 010000 by addendum.
41. On Detail 9 / A0901 what type of wood for the beadboard wainscot?
Refer to Section 062000, 2.1C.
42. Millwork suppliers are not able to get the two vinyl and pvc wall coverings. They do not supply as casework finishes. Is there an alternative material the architect can use as an alternative (i.e. PLAM)?
Please clarify question, or refer to specifications. The product is not a new product and is used in conjunction with the casework. It is up to the contractor to determine the means and methods for which it is applied, whether that be through the casework vendor, or after installation and applied by others.
43. Will the old nurse call devices be reused or are we to pull old devices and replace with new?
All nurse call devices will be new.
44. What are the camera specifications and requirements? They are not listed.
Emerald Resource is the manufacturer. Please refer to spec 282300 section 2.6A for contact information.
| 45. During the fire sprinkler installation, we will need to schedule a shut down, will the COR of the VA coordinate with this? Our aim is to limit the number of shutdown times and durations as much as possible. |
| Yes, all shutdowns are to be requested and coordinated through the COR. |