36C25219B0038-0003003.pdf
PDF 675 KB Posted
- Attached to
- 556-305, Construct New Parking Garage Federal contract opportunity
- Solicitation number
- 36C25219B0038
About this file
36C25219B0038 0003 A00002 - Structural Dwgs.pdf
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| 36C25219B0038-0007001.pdf | ||
| 36C25219B0038-0007000.docx | DOCX document | |
| 36C25219B0038-0006000.docx | DOCX document | |
| 36C25219B0038-0005000.docx | DOCX document | |
| 36C25219B0038-0005001.pdf | ||
| 36C25219B0038-0005002.pdf | ||
| 36C25219B0038-0004000.docx | DOCX document | |
| 36C25219B0038-0003004.pdf | ||
| 36C25219B0038-0003006.pdf | ||
| 36C25219B0038-0003005.pdf | ||
| 36C25219B0038-0003008.pdf | ||
| 36C25219B0038-0003002.pdf | ||
| 36C25219B0038-0003001.pdf | ||
| 36C25219B0038-0003009.pdf | ||
| 36C25219B0038-0003010.pdf | ||
| 36C25219B0038-0003000.docx | DOCX document | |
| 36C25219B0038-0003007.pdf | ||
| 36C25219B0038-0002000.docx | DOCX document | |
| 36C25219B0038-0001001.pdf | ||
| 36C25219B0038-0001000.docx | DOCX document | |
| 36C25219B0038-006.pdf | ||
| 36C25219B0038-003.pdf | ||
| 36C25219B0038-005.pdf | ||
| 36C25219B0038-004.pdf | ||
| 36C25219B0038-001.docx | DOCX document | |
| 36C25219B0038-002.pdf | ||
| 36C25219B0038-000.docx | DOCX document |
Show all 27
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
A
2 3 4 5 6 7 8
B
C
UP
UP
DN
DN
SF301
SF301
FD
250'-8"
45'-4" 32'-0" 32'-0" 32'-0" 32'-0" 32'-0" 45'-4"
6'
-8
'-4
'-4
727.42' 728.08' 728.75'
727.08' 726.25'
727.08' 726.25'
726.92' 727.58' 728.25'
729.42' 730.08' 730.75 730.92'
730.42'729.58'728.92'
729.58'731.18'732.78'
731.18'732.78' 724.65' 723.05'
724.65' 723.05'
SF521
SF521
SF521
SF521
SB502
SF301
SF301
SF521
SF521
SF521
SF521
SF521
B.7
A.1
1.2 1.4 1.7
A.A
7.8
'-5
8'
-4
'-0
'-9
'-7
10'-8" 9'-8" 10'-8" 14'-4" 35'-0" 10'-4"
SF401
SF411
SF522
SF522
SB502
727.51'
727.46'
727.33'
730.22'
730.22' 730.42'
730.42'
727.67'
FD
FD
16'-0" 34'-0"
'-8
TO WASH EL 730.00'
SF522
SF522
SF522
SF522
12'-10"
(3) #4 CONT
CHORD
REINF
(3) #4 CONT
CHORD
REINF
(3) #4 CONT
CHORD
REINF
(3) #4 CONT
CHORD
REINF
(3) #4 CONT
CHORD
REINF
(3) #4 CONT
CHORD
REINF
(3) #4 CONT
CHORD
REINF
(3) #4 CONT
CHORD
REINF
(3) #4 CONT
CHORD
REINF
(3) #4 CONT
CHORD
REINF
(3) #4 CONT
CHORD
REINF
(3) #4 CONT
CHORD
REINF
(3) #4 CONT
CHORD
REINF
(3) #4 CONT
CHORD
REINF
(3) #4 CONT
CHORD
REINF
3" CIP CONCRETE TOPPING
REINFORCE WITH 6X6 W4X4 WWR
3" CIP CONCRETE TOPPING
REINFORCE WITH 6X6 W4X4 WWR
FDFD
FD
SHEET NOTES:
NO SYMB NOTE
1 COORDINATE ALL DIMENSIONS, DETAILS, FINISHES,
AND TIE HOLE LOCATIONS WITH ARCHITECTURAL
DRAWINGS.2 INDICATES PLAN MATCH LINE.
3 FOR GENERAL NOTES, REFER TO SHEETS SI001 AND
SI002
4 FOR EXPLANATION OF NOTATIONS AND
ABBREVIATIONS, REFER TO GENERAL NOTES, SHEET
SI002.5 DATUM: XXX.XX' = ELEVATION ABOVE MEAN SEA
LEVEL, REFER TO CIVIL
6 FLOOR ELEVATIONS AS INDICATED DESIGNATE TOP
OF CONCRETE SLAB AT COLUMN CENTER LINES.
ELEVATIONS DO NOT INCLUDE CONCRETE WASHES,
BEAMS, CURBS, ETC. FOR PLAN ELEVATION KEYS,
REFER TO DETAILS 1-3/SF551.
7 FOR FLOOR ELEVATIONS BETWEEN POINTS
INDICATED, USE STRAIGHT LINE INTERPOLATION AND
SLOPE SLAB TO DRAIN.
8 FOR COLUMN DETAILS, REFER TO SHEETS SF511. ALL
COLUMNS ARE CENTERED ON GRID LINES UNLESS
NOTED.
9 FOR TYPICAL SLAB ON GRADE DETAILS REFER TO
SHEET SB501.
10 FOR PRECAST FRAMING DETAILS AND NOTES, REFER
TO SHEETS SF521, SF531, AND SF532.
11 FOR TYPICAL DOUBLE TEE PROFILE, REFER TO
DETAIL 1/SF531.
12 CAST-IN-PLACE TOPPING THICKNESS ON SUPPORTED
LEVELS SHALL BE 3 INCHES TYPICAL UNLESS NOTED
OTHERWISE.
13 FOR SEALANT, DECK COATING, AND EXPANSION JOINT
DETAILS, REFER TO SHEET SF541.
14 INDICATES FLOOR DRAIN. FOR ADDITIONAL INFO,
REFER TO DETAIL 4/SB501, 5/SF531 AND PLUMBING
DRAWINGS.15 FOR ADDITIONAL FLOOR DRAIN INFORMATION, REFER
TO MECHANICAL/PLUMBING DRAWINGS.
16 ALL PIPING FLOOR PENETRATIONS SHALL HAVE PVC
COLLARS TO ELIMINATE FLOODING FROM FLOOR TO
FLOOR, REFER TO DETAIL 4/SF551.
17 REFER TO MECHANICAL/PLUMBING DRAWINGS FOR
DRAIN AND PIPE SIZES. NO PIPING SHALL BE INSTALLED
WITH LESS THAN 8'-4" CLEARANCE UNLESS IT IS
IMMEDIATELY ADJACENT TO A WALL OR COLUMN LINE
WHERE IT COULD NOT BE HIT BY A VEHICLE OR
PEDESTRIAN.
18 ALL VERTICAL RISERS FOR PLUMBING, ELECTRICAL AND
MECHANICAL SYSTEMS SHALL BE PROTECTED BY
STEEL PIPE GUARDS, REFER TO DETAILS 4, 5, & 6/SF551.
19 SLAB-ON-GRADE SHALL BE A MINIMUM OF 5" THICK
CONCRETE OVER 24" OF COMPACTED STRUCTURAL
FILL. SLAB-ON-GRADE IS REINFORCED WITH #4 @ 12"
OC EACH WAY.
20 ALL CONTROL AND CONSTRUCTION JOINTS SHALL BE
HAND TOOLED, REFER TO 4 AND 5/SF541.
21 ALL CRACKS THAT APPEAR IN SOG AND CIP SLAB
SHALL BE ROUTED & SEALED, REFER TO DETAIL 11
AND 2/SF541.
22 FOR LIGHT POLE LOCATIONS AND LIGHT POLE BASE
DETAILS REFER TO ELECTRICAL AND DETAIL 7/SF511
23 INDICATES DECK COATING, REFER TO DETAILS
17-20/SF541 FOR ADDITIONAL INFORMATION.
24 PROVIDE CONCRETE SEALER ON ALL SLAB
SURFACES AS INDICATED IN GENERAL NOTE 7.1.
25 WORK SHALL INCLUDE ALL NECESSARY
ACOMMODATIONS FOR HOT AND COLD WEATHER
CONCRETE INSTALLATIONS INCLUDING, BUT NOT
LIMITED TO: CHILLED MIXING WATER, NIGHT
PLACEMENTS, EVAPORATION REDUCING MEASURES,
HEATING, BLANKETS, ADMIXTURES, ETC. REFER TO
SPEC SECTION 033000.
26 FOR MASONRY DETAILS, REFER TO DETAILS 8, 9, AND
10/SF551.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
Architect / Civil Engineer:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
M/E/P Engineers: Structural Engineer:
Apogee Consulting Group, PA
1511 Kildaire Farm Road, Suite 120
Cary, NC 27511
(919) 858-7420
Carl Walker, a Division of WGI
8910 Purdue Road, Suite 400
Indianapolis, IN 46828
(317) 735-3349
Guidon Design, Inc.
905 North Capitol Avenue, Suite 100
Indianapolis, IN 46204
(317) 800-6388
BID DOCUMENT
NOT SPRINKLERED
NEW PARKING GARAGE AT THE
CAPTAIN JAMES A. LOVELL
FEDERAL HEALTH CARE
CENTER
NORTH CHICAGO, IL
556-305
DPG DEB
D R e v it U s e r F ile s \P
-2
-0
-C
W I-
V d a n .b ro w n L
D P
W Z
.r v t
/1
/2
:1
:2
A
M
SF102
LEVEL 2 PLAN - STRUCTURAL
1/9/2019 28 OF 80
ISOMETRIC VIEW
LEVEL 2
EL 727'-8"
LEVEL 3
EL 739'-0"
LEVEL 1
EL 716'-4"
LEVEL 2
EL 730'-5"
LEVEL 1
EL 719'-1"
NORTH
1/8" = 1'-0"
LEVEL 2 PLAN - STRUCTURAL
Revisions: Date:
1 AMENDMENT A00002 4/17/2019
A
2 3 4 5 6 7 8
B
C
SF301
SF301
250'-8"
45'-4" 32'-0" 32'-0" 32'-0" 32'-0" 32'-0" 45'-4"
6'
-8
'-4
'-4
737.58''
737.58''
735.98'' 734.38''
735.98'' 734.38''
SF521
SF301
SF301
B.7
A.1
1.2 1.4 1.7
A.A
7.8
'-5
8'
-4
'-0
'-9
'-7
10'-8" 9'-8" 10'-8" 14'-4" 35'-0" 10'-4"
SF401
SF411
741.75'
SF522
(3) #4 CONT
CHORD
REINF
(4) #5 CONT
CHORD
REINF
(3) #4 CONT
CHORD
REINF
TO COL EL 746.17' TO COL EL 744.56' TO COL EL 743.00' TO COL EL 743.00' TO COL EL 739.75'
TO COL EL 738.17'
TO COL
EL 739.50'
TO COL EL 739.50'TO COL EL 739.50'TO COL EL 738.83'TO COL EL 737.95'TO COL EL 737.27'TO COL EL 748.00'TO COL EL 747.33'
TO COL
EL 747.00'
TO COL
EL 747.00'
TO COL EL 742.00'
TO COL EL 735.00'
3" CIP CONCRETE TOPPING
REINFORCE WITH 6X6 W4X4 WWR
PROVIDE NOTCH IN SPANDREL
TO TOP OF WASH FOR SNOW
GATE. REFER TO ARCH FOR
GATE INFO.
CONC FILLED STEEL BOLLARDS
WELDED TO EMBED PLATE,
REFER TO DET 13/SF551, SIM.
PCC MFR TO PROVIDE EMBED
PLATE W/ LOAD CAPACITY FOR
VEHICLE IMPACT LEADING PER
SI001.
2' -0
4'
-0
2' -0
8' -0
(3) #4 CONT
CHORD
REINF
(3) #4 CONT
CHORD
REINF
(3) #4 CONT
CHORD
REINF
(3) #4 CONT
CHORD
REINF
(3) #4 CONT
CHORD
REINF
(3) #4 CONT
CHORD
REINF
SF521
SF521
SF522
SF522
SF522
739.00'
738.75' 739.42'
738.42'
738.42'
738.25'
738.83'
738.79'
738.67'
FD
3" CIP CONCRETE TOPPING
REINFORCE WITH 6X6 W4X4 WWR
SF401
UP
DN
'-4
9'-8"
FD
SHEET NOTES:
NO SYMB NOTE
1 COORDINATE ALL DIMENSIONS, DETAILS, FINISHES,
AND TIE HOLE LOCATIONS WITH ARCHITECTURAL
DRAWINGS.2 INDICATES PLAN MATCH LINE.
3 FOR GENERAL NOTES, REFER TO SHEETS SI001 AND
SI002
4 FOR EXPLANATION OF NOTATIONS AND
ABBREVIATIONS, REFER TO GENERAL NOTES, SHEET
SI002.5 DATUM: XXX.XX' = ELEVATION ABOVE MEAN SEA
LEVEL, REFER TO CIVIL
6 FLOOR ELEVATIONS AS INDICATED DESIGNATE TOP
OF CONCRETE SLAB AT COLUMN CENTER LINES.
ELEVATIONS DO NOT INCLUDE CONCRETE WASHES,
BEAMS, CURBS, ETC. FOR PLAN ELEVATION KEYS,
REFER TO DETAILS 1-3/SF551.
7 FOR FLOOR ELEVATIONS BETWEEN POINTS
INDICATED, USE STRAIGHT LINE INTERPOLATION AND
SLOPE SLAB TO DRAIN.
8 FOR COLUMN DETAILS, REFER TO SHEETS SF511. ALL
COLUMNS ARE CENTERED ON GRID LINES UNLESS
NOTED.
9 FOR TYPICAL SLAB ON GRADE DETAILS REFER TO
SHEET SB501.
10 FOR PRECAST FRAMING DETAILS AND NOTES, REFER
TO SHEETS SF521, SF531, AND SF532.
11 FOR TYPICAL DOUBLE TEE PROFILE, REFER TO
DETAIL 1/SF531.
12 CAST-IN-PLACE TOPPING THICKNESS ON SUPPORTED
LEVELS SHALL BE 3 INCHES TYPICAL UNLESS NOTED
OTHERWISE.
13 FOR SEALANT, DECK COATING, AND EXPANSION JOINT
DETAILS, REFER TO SHEET SF541.
14 INDICATES FLOOR DRAIN. FOR ADDITIONAL INFO,
REFER TO DETAIL 4/SB501, 5/SF531 AND PLUMBING
DRAWINGS.15 FOR ADDITIONAL FLOOR DRAIN INFORMATION, REFER
TO MECHANICAL/PLUMBING DRAWINGS.
16 ALL PIPING FLOOR PENETRATIONS SHALL HAVE PVC
COLLARS TO ELIMINATE FLOODING FROM FLOOR TO
FLOOR, REFER TO DETAIL 4/SF551.
17 REFER TO MECHANICAL/PLUMBING DRAWINGS FOR
DRAIN AND PIPE SIZES. NO PIPING SHALL BE INSTALLED
WITH LESS THAN 8'-4" CLEARANCE UNLESS IT IS
IMMEDIATELY ADJACENT TO A WALL OR COLUMN LINE
WHERE IT COULD NOT BE HIT BY A VEHICLE OR
PEDESTRIAN.
18 ALL VERTICAL RISERS FOR PLUMBING, ELECTRICAL AND
MECHANICAL SYSTEMS SHALL BE PROTECTED BY
STEEL PIPE GUARDS, REFER TO DETAILS 4, 5, & 6/SF551.
19 SLAB-ON-GRADE SHALL BE A MINIMUM OF 5" THICK
CONCRETE OVER 24" OF COMPACTED STRUCTURAL
FILL. SLAB-ON-GRADE IS REINFORCED WITH #4 @ 12"
OC EACH WAY.
20 ALL CONTROL AND CONSTRUCTION JOINTS SHALL BE
HAND TOOLED, REFER TO 4 AND 5/SF541.
21 ALL CRACKS THAT APPEAR IN SOG AND CIP SLAB
SHALL BE ROUTED & SEALED, REFER TO DETAIL 11
AND 2/SF541.
22 FOR LIGHT POLE LOCATIONS AND LIGHT POLE BASE
DETAILS REFER TO ELECTRICAL AND DETAIL 7/SF511
23 INDICATES DECK COATING, REFER TO DETAILS
17-20/SF541 FOR ADDITIONAL INFORMATION.
24 PROVIDE CONCRETE SEALER ON ALL SLAB
SURFACES AS INDICATED IN GENERAL NOTE 7.1.
25 WORK SHALL INCLUDE ALL NECESSARY
ACOMMODATIONS FOR HOT AND COLD WEATHER
CONCRETE INSTALLATIONS INCLUDING, BUT NOT
LIMITED TO: CHILLED MIXING WATER, NIGHT
PLACEMENTS, EVAPORATION REDUCING MEASURES,
HEATING, BLANKETS, ADMIXTURES, ETC. REFER TO
SPEC SECTION 033000.
26 FOR MASONRY DETAILS, REFER TO DETAILS 8, 9, AND
10/SF551.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
Architect / Civil Engineer:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
M/E/P Engineers: Structural Engineer:
Apogee Consulting Group, PA
1511 Kildaire Farm Road, Suite 120
Cary, NC 27511
(919) 858-7420
Carl Walker, a Division of WGI
8910 Purdue Road, Suite 400
Indianapolis, IN 46828
(317) 735-3349
Guidon Design, Inc.
905 North Capitol Avenue, Suite 100
Indianapolis, IN 46204
(317) 800-6388
BID DOCUMENT
NOT SPRINKLERED
NEW PARKING GARAGE AT THE
CAPTAIN JAMES A. LOVELL
FEDERAL HEALTH CARE
CENTER
NORTH CHICAGO, IL
556-305
DPG DEB
D R e v it U s e r F ile s \P
-2
-0
-C
W I-
V d a n .b ro w n L
D P
W Z
.r v t
/1
/2
:1
:3
A
M
SF103
LEVEL 3 PLAN - STRUCTURAL
1/9/2019 29 OF 80
NORTH
1/8" = 1'-0"
LEVEL 3 PLAN - STRUCTURAL
ISOMETRIC VIEW
LEVEL 2
EL 727'-8"
LEVEL 3
EL 739'-0"
LEVEL 1
EL 716'-4"
LEVEL 2
EL 730'-5"
LEVEL 1
EL 719'-1"
±15'-6" ±15'-6"
3'-0" 6'-0" 3'-0"
SIDE ELEVATION
END ELEVATION A-A
A
A
6" WIDE X 4" HIGH
BLOCKOUT, ALIGN IN
TOP OF TEE STEM, TYP
TEE
DAPPED BRG
REFER TO DET
3/SF531
UNDAPPED BRG
REFER TO DET
2/SF531
CG PRESTRESSING
STRANDS
ADDITIONAL LAYER
OF WWF
ADDITIONAL LAYER
OF WWF
WWF
2' -7
3" F
IE
LD
T O
P P
IN
G
CIP TOPPING W/ WWF
2"
.0
AshERECTION DAP AS
REQUIRED BY PCC
BEARING PLATE
Acv
Av
Avf
ERECTION DAP AS
REQUIRED BY PCC
BEARING PLATE
Acv
Av
Avf
Avh
Ash 2"
SEALANT, REFER TO DET 4 AND 5/SF541
CIP CONC TOPPING
PC TEE FLANGE
SMOOTH BAR (STAINLESS STEEL)
NOTE:
BARS OF VARIOUS SIZES MAY BE REQD DEPENDING UPON FIELD CONDITIONS. PRE CASTER SHALL KEEP
ADEQUATE SUPPLY OF SIZES ON SITE TO FACILITATE ERECTION.
BACKER ROD
STAINLESS STEEL
SHEAR CONNECTIONS
BY PCC MFR
1/2".
1"
N O
M
3"
DRAIN
1'-0" WASH
AROUND
W A
S H
1/ 2"
PC TEE FLANGE
CONC TOPPING
(2) #4, REFER
TO DET 5/SB501
FLOOR DRAIN SYSTEM,
REFER TO MECH. SEALANT, REFER
TO DET 8 OR 9/SF541
REMOVE BACKER ROD
AFTER STRIPPING FORM
AFTER ERECTION,
REMOVE ALL WATER
FROM CAVITY & FILL
ENTIRE VOID W/
SILICONE SEALANT
TOP OF SPANDREL,
LIGHT WALL OR
COLUMN
PCC EMBEDDED
LIFTING INSERT
AFTER ERECTION,
REMOVE ALL WATER
FROM CAVITY & FILL
ENTIRE VOID W/
SILICONE SEALANT.
SET PLUG INTO
SEALANT AND
REMOVE EXCESS.
TOP OF SPANDREL,
LIGHT WALL OR
COLUMN
PCC EMBEDDED
LIFTING INSERT
AT TOP
SPANDRELS OR
LIGHT WALLS,
6" Ø MAX AT
TOP OF COL
PCC PLUG TO MATCH
SURROUNDING
EXTERIOR
FACE OF
PCC SPANDREL
2" 3/4"
3/ 4"
3/ 4"
3/4"
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
Architect / Civil Engineer:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
M/E/P Engineers: Structural Engineer:
Apogee Consulting Group, PA
1511 Kildaire Farm Road, Suite 120
Cary, NC 27511
(919) 858-7420
Carl Walker, a Division of WGI
8910 Purdue Road, Suite 400
Indianapolis, IN 46828
(317) 735-3349
Guidon Design, Inc.
905 North Capitol Avenue, Suite 100
Indianapolis, IN 46204
(317) 800-6388
BID DOCUMENT
NOT SPRINKLERED
NEW PARKING GARAGE AT THE
CAPTAIN JAMES A. LOVELL
FEDERAL HEALTH CARE
CENTER
NORTH CHICAGO, IL
556-305
DPG DEB
D R e v it U s e r F ile s \P
-2
-0
-C
W I-
V d a n .b ro w n L
D P
W Z
.r v t
/1
/2
:1
:3
A
M
SF531
TYPICAL PCC BEAM DETAILS -
STRUCTURAL
1/9/2019 37 OF 80
12" = 1'-0"
PCC DOUBLE TEE (FIELD TOPPED) PROFILE
3/4" = 1'-0"
PCC UNDAPPED TEE DETAIL
3/4" = 1'-0"
PCC DAPPED TEE DETAIL
3" = 1'-0"
PCC TEE JOINT DETAIL
1" = 1'-0"
FLOOR DRAIN DETAIL
3" = 1'-0"
LIFTING INSERT DETAIL
3" = 1'-0"
LIFTING INSERT DETAIL
6" = 1'-0"
DRIP DETAIL
| Sheets |