260583-RIB-Wiring Connections-12-24-2025.pdf
PDF 58 KB Posted
- Attached to
- CBI GJ HVAC/Lighting Upgrade Project
- Solicitation number
- IFB1 REAA 2027000043 1
- Issued by
- Denver County, Denver City, Colorado
About this file
This is a specification document for Section 260583 – Wiring Connections, part of project 25-388 CBI HVAC and Lighting Upgrade. The specification outlines electrical connection requirements and standards for equipment installations under this upgrade project. The scope includes electrical connections to equipment, wiring devices, conduit systems, disconnect switches, and related electrical components. The specification mandates compliance with NFPA 70 (National Electrical Code), NEMA WD 1 and WD 6 standards, and requires coordination with related sections including low-voltage electrical power conductors, conduit systems, boxes for electrical systems, wiring devices, enclosed switches, and enclosed controllers. Contractors must obtain and review shop drawings, product data, and manufacturer's wiring diagrams to determine connection locations and requirements.
The specification requires specific product standards including NEMA WD 6 cords and caps with proper color compliance per NEMA WD 1, flexible cord construction per NFPA 70 Type SO suitable for damp locations, and disconnect switches as detailed in related sections. Electrical connections must be made using flexible conduit with liquidtight connections in damp or wet locations, cord and plug connections with NEMA 6-20R configuration, and field-installed disconnect switches. Installation requirements include compliance with manufacturer's instructions, proper strain-relief clamps and fittings, terminal block jumpers, and interconnecting conduit and wiring to complete all equipment requirements. All materials, connections, and installations must meet applicable electrical codes and manufacturer specifications.
View the file
Other files
Show all 41
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
25-388 CBI HVAC and Lighting Upgrade 260583 - 1 Wiring Connections
SECTION 260583
WIRING CONNECTIONS
PART 1 GENERAL
1.01 SECTION INCLUDES
A. Electrical connections to equipment.
1.02 RELATED REQUIREMENTS
A. Section 260519 - Low-Voltage Electrical Power Conductors and Cables.
B. Section 260533.13 - Conduit for Electrical Systems.
C. Section 260533.16 - Boxes for Electrical Systems.
D. Section 262726 - Wiring Devices.
E. Section 262816.16 - Enclosed Switches.
F. Section 262913 - Enclosed Controllers.
1.03 REFERENCE STANDARDS
A. NEMA WD 1 - General Color Requirements for Wiring Devices; 1999 (Reaffirmed 2020).
B. NEMA WD 6 - Wiring Devices - Dimensional Specifications; 2021.
C. NFPA 70 - National Electrical Code; Most Recent Edition Adopted by Authority Having
Jurisdiction, Including All Applicable Amendments and Supplements.
1.04 ADMINISTRATIVE REQUIREMENTS
A. Coordination:
1. Obtain and review shop drawings, product data, manufacturer's wiring diagrams, and manufacturer's instructions for equipment furnished under other sections.
2. Determine connection locations and requirements.
1.05 SUBMITTALS
A. See Section 013000 - Administrative Requirements, for submittal procedures.
B. Product Data: Provide wiring device manufacturer’s catalog information showing dimensions, configurations, and construction.
1.06 QUALITY ASSURANCE
A. Comply with requirements of NFPA 70.
PART 2 PRODUCTS
2.01 MATERIALS
A. Cords and Caps: NEMA WD 6; match receptacle configuration at outlet provided for equipment.
1. Colors: Comply with NEMA WD 1.
2. Cord Construction: NFPA 70, Type SO, multiconductor flexible cord with identified equipment grounding conductor, suitable for use in damp locations.
3. Size: Suitable for connected load of equipment, length of cord, and rating of branch circuit overcurrent protection.
B. Disconnect Switches: As specified in Section 262816.16 and in individual equipment sections.
C. Wiring Devices: As specified in Section 262726.
D. Flexible Conduit: As specified in Section 260533.13.
E. Wire and Cable: As specified in Section 260519.
F. Boxes: As specified in Section 260533.16.
2.02 EQUIPMENT CONNECTIONS
A.
25-388 CBI HVAC and Lighting Upgrade 260583 - 2 Wiring Connections
1. Electrical Connection: Flexible conduit.
2. Electrical Connection: Cord and plug (NEMA 6-20R).
3. Provide field-installed disconnect switch.
PART 3 EXECUTION
3.01 EXAMINATION
A. Verify that equipment is ready for electrical connection, wiring, and energization.
3.02 ELECTRICAL CONNECTIONS
A. Make electrical connections in accordance with equipment manufacturer's instructions.
B. Make conduit connections to equipment using flexible conduit. Use liquidtight flexible conduit with watertight connectors in damp or wet locations.
C. Connect heat producing equipment using wire and cable with insulation suitable for temperatures encountered.
D. Provide receptacle outlet to accommodate connection with attachment plug.
E. Provide cord and cap where field-supplied attachment plug is required.
F. Install suitable strain-relief clamps and fittings for cord connections at outlet boxes and equipment connection boxes.
G. Install disconnect switches, controllers, control stations, and control devices to complete equipment wiring requirements.
H. Install terminal block jumpers to complete equipment wiring requirements.
I. Install interconnecting conduit and wiring between devices and equipment to complete equipment wiring requirements.
END OF SECTION
260583 - Wiring Connections