2026.07.23_-_DRAWINGS.pdf

PDF 13 MB Posted

Attached to
Beaufort County Detention Center Gymnasium Conversion Project
Solicitation number
090126
Issued by
Barnwell County, South Carolina

About this file

This is a construction drawing set for the Beaufort County Detention Center Gymnasium Conversion Project located at 106 Ribauto Road, Beaufort, South Carolina 29902. The project, assigned number 644482, involves the renovation and conversion of an existing gymnasium into a dormitory-style inmate housing unit with associated support facilities. The work area encompasses 2,260 square feet within a larger 99,455 square foot facility classified as I-3 Institutional occupancy. The construction documents, prepared by Moseley Architects (Charleston, SC) and dated July 23, 2026, include comprehensive architectural, structural, plumbing, fire protection, mechanical, and electrical plans. Key architectural elements include the conversion of the gymnasium (Dorm 101) into a housing unit with capacity for quad-bunk beds with middle dividers, a new shower room (Shower 102), detention-grade fixtures and hardware, security features including fixed windows above existing openings and 12-foot tall steel surrounds at roof level, detention-grade mirrors and safety equipment, activity tables, and a relocated commissary and video visitation station. The project requires demolition of existing interior elements including walls, plumbing fixtures, ceiling systems, and mechanical equipment, followed by new construction including security cladding, detention-grade doors and frames, resin epoxy flooring, and architectural finishes throughout the converted space.

The drawings specify detention-grade materials and security-focused construction methodologies throughout, including security caulking at penetrations, tamper-proof fasteners, and specialized detention equipment such as anti-ligature grab bars and recessed toilet paper holders. Mechanical work includes new exhaust fans with smoke control capabilities, duct routing with security bars, and fire damper installations. Fire protection plans indicate the addition and relocation of sprinklers to accommodate the renovated walls and ceilings in accordance with 2021 South Carolina Building Code and 2019 NFPA 13 standards. Electrical and plumbing systems require significant rework, including relocation of devices, installation of new fire alarm devices and smoke detectors, and coordination of utility systems throughout the space. The finish schedule specifies materials including composite textile flooring, resin epoxy finishes, acoustical ceiling panels, and Sherwin Williams paint products (Toque White for walls and High Reflective White for ceilings). All contract documents are noted as complementary, with conflicts requiring provision of better quality and greater quantity of work.

View the file

Other files

File Type Posted
Beaufort_County_Detention_Center_Gymnasium_Conversion_Project.pdf PDF
2026.07.23_-_PROJECT_MANUAL.pdf PDF
Hydrant_0321_parking_lot_magistrate_court_Ribaut_road.pdf PDF
Hydrant_0332_Marsh_Road.pdf PDF
Hydrant_0336_Duke_Street..pdf PDF
E2-1_-_FLOOR_PLAN_AND_DETAILS.dwg DWG drawing
M0-1_-_LEGENDS,_ABBREVIATIONS_AND_GENERAL_NOTES.dwg DWG drawing
P2-1_-_FLOOR_PLANS_-_PLUMBING.dwg DWG drawing
26-2574_-_Beaufort_County_-_106_Ribaut_Rd_Gymnasium_-_Lim_ACM.pdf PDF
P5-1_-_DETAILS.dwg DWG drawing
S1-1-1_-_SECOND_FLOOR_&_ROOF_FRAMING_PLAN_&_DETAILS.dwg DWG drawing
M2-1_-_MECHANICAL_CONSTRUCTION_PLANS.dwg DWG drawing
P0-1_-_LEGENDS,_ABBREVIATIONS_AND_GENERAL_NOTES.dwg DWG drawing
S0-0-1_-_GENERAL_NOTES_AND_LEGENDS.dwg DWG drawing
M0-2_-_SCHEDULES_AND_DETAILS.dwg DWG drawing
FP0-1_-_LEGENDS,_ABBREVIATIONS_AND_GENERAL_NOTES.dwg DWG drawing
M1-1_-_MECHANICAL_DEMOLITION_PLANS.dwg DWG drawing
FP1-0_-_FLOOR_PLAN.dwg DWG drawing
A1-3_-_MULTI-PURPOSE_TOILET_PLANS_&_DETAILS.dwg DWG drawing
A1-0_-_OVERALL_PLANS.dwg DWG drawing
COVER.dwg DWG drawing
A1-2_-_MULTI-PURPOSE_ELEVATIONS,_FRAME_TYPES_&_DETAILS.dwg DWG drawing
A1-1_-_MULTI-PURPOSE_PLANS.dwg DWG drawing
E0-1_-_LEGENDS,_ABBREVIATIONS_AND_GENERAL_NOTES.dwg DWG drawing
Detention_Center_Multi-Purpose_Renovation_Plans_Review.pdf PDF
A3-1_-_FINISH_SCHEDULE.dwg DWG drawing
Exhibit_4_-_Monthly_Compliance_Status_Report.pdf PDF
Show all 27

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

BEAUFORT AIRPORT

B U

S

T R

A S

K P

K W

Y

ROBERT SMALLS PKWY

R

IB

A U

T R

O A

D

CREDIT: GOOGLE MAPS

BOUNDARY STREET

R

IB

A U

T R

O A

D

CREDIT: GOOGLE MAPS

NN

M O

S E

L E

Y A

R C

H

IT

E C

T S

.C O

M

MOSELEYARCHITECTS.COM

THE CONTRACT DOCUMENTS ARE COMPLEMENTARY, AND WHAT IS REQUIRED BY ONE SHALL BE AS BINDING AS IF REQUIRED BY ALL.

IN CASE OF A CONFLICT, DISAGREEMENT, OR AMBIGUITY, PROVIDE THE BETTER QUALITY. IN CASE OF A CONFLICT, DISAGREEMENT, OR AMBIGUITY, PROVIDE THE GREATER QUANTITY OF WORK.

VICINITY MAP LOCATION MAP

DRAWING INDEX CODE INFORMATION

PROJECT NO:

DATE:

M O

R R

IS

O

N D

R

IV

E S

U

IT

E

C

H A

R L E

S T

O N

S

C

P H

O N

E

-5

997 MORRISON DRIVE, SUITE 601 CHARLESTON, SC 29403

PHONE (843) 577-5063

/2

/2

:1 :2

P

M

COVER

B E

A U

F O

R T

C O

U N

T Y

R

IB

A U

T R

O A

D

B E

A U

F O

R T

S

C

P R

O

JE

C T

BEAUFORT COUNTY DETENTION CENTER

GYM CONVERSION

BEAUFORT COUNTY

BEAUFORT, SC

PROJECT #644482

CONSTRUCTION DOCUMENTS

644482

JULY 23, 2026

B E

A U

F O

R T

C O

U N

T Y

D E

T E

N T

IO

N

C E

N T

E R

G Y

M C

O N

V E

R S

IO

N

G0.1

GENERAL

G0.1 COVER

ARCHITECTURAL

A1.0 OVERALL PLANS

A1.1 FLOOR PLANS

A1.2 ELEVATIONS, FRAME TYPES & DETAILS

A1.3 TOILET PLANS & DETAILS

A3.1 FINISH SCHEDULE

STRUCTURAL

S0.0.1 GENERAL NOTES AND LEGENDS

S1.1.1 SECOND FLOOR & ROOF FRAMING PLAN & DETAILS

PLUMBING

P0.1 LEGENDS, ABBREVIATIONS AND GENERAL NOTES

P2.1 FLOOR PLANS - PLUMBING

P5.1 DETAILS

FIRE PROTECTION

FP0.1 LEGENDS, ABBREVIATIONS AND GENERAL NOTES

FP1.0 FLOOR PLAN

MECHANICAL

M0.1 LEGENDS, ABBREVIATIONS AND GENERAL NOTES

M0.2 SCHEDULES AND DETAILS

M1.1 MECHANICAL DEMOLITION PLANS

M2.1 MECHANICAL CONSTRUCTION PLANS

ELECTRICAL

E0.1 LEGENDS, ABBREVIATIONS AND GENERAL NOTES

E2.1 FLOOR PLAN AND DETAILS

PROJECT: BEAUFORT COUNTY DETENTION CENTER GYM CONVERSION & INTERIOR FINISHES

PROJECT NUMBER: #644482 BEAUFORT COUNTY DETENTION CENTER - GYM CONVERSION

OWNER: BEAUFORT COUNTY

ATTN: ROBERT GECY

INTERIM DIRECTOR

Robert.Gecy@bcgov.net

REFERENCE REQUIREMENTS (DATE OF ANALYSIS - JULY 23, 2025):

FLOOR AREA EXISTING OCCUPANCY PROPOSED OCCUPANCY

FIRST 62,616 SQFT I-3 INSTITUTIONAL I-3 INSTITUTIONAL

SECOND 36,839 SQFT I-3 INSTITUTIONAL I-3 INSTITUTIONAL

TOTAL BUILDING AREA: 99,455 SQFT

WORK AREA: 2,260 SQFT

REVISIONS

DATE DESCRIPTION

CAROLIN

A

HTU

O S

MOSELEY

ARCHITECTS

No. 3983

C E R T

IF

IC

A

T E

OF AUT

H

O R

IZ

A T

IO

N

03/20/2026

MOSELEY INC

CHARLESTON, SC

02025

OU

E T

S

R E

G

IS

T E R E A

C

T

S O

A

F

TH CAR

O L

IN

A

D R H

I T E

C T

S

A1.1

SURROUNDING PLAN SHOWN FOR REFERENCE ONLY AND IS NOT IN SCOPE EXCEPT WHERE NOTED

DORM

FLOOR PLAN GENERAL NOTES

A. ALL DIMENSIONS SHOWN ARE APPROXIMATE AND NEED TO BE VERIFIED IN FIELD BY

CONTRACTOR.

B. PAINT ALL DOORS AND JAMBS IN AREAS WITHIN AREA OF WORK.

M O

S E

L E

Y A

R C

H

IT

E C

T S

.C O

M

PROJECT NO:

DATE:

A

B

C

D

E

1 2 4 53 6 7 8 9 10

F

G

H

I

J

M O

R R

IS

O

N D

R

IV

E S

U

IT

E

C

H A

R L E

S T

O N

S

C

P H

O N

E

-5

/2

/2

:1 :1

P

M

OVERALL PLANS

B E

A U

F O

R T

C O

U N

T Y

B

EA

U

FO

R T

C O

U N

TY

D

ET

EN

TI

O

N C

EN

TE

R G

YM

C

O N

VE

R

SI

O

N

R

IB

A U

T R

O A

D

B E

A U

F O

R T

S

C

A1.0

P R

O

JE

C T

644482

JULY 23, 2026

3/64" = 1'-0"

OVERALL 1ST FLOOR PLAN

REVISIONS

DATE DESCRIPTION

CAROLIN

A

HTU

O S

MOSELEY

ARCHITECTS

No. 3983

C E R T

IF

IC

A

T E

OF AUT

H

O R

IZ

A T

IO

N

03/20/2026

MOSELEY INC

CHARLESTON, SC

02025

OU

E T

S

R E

G

IS

T E R E A

C

T

S O

A

F

TH CAR

O L

IN

A

D R H

I T E

C

S S S

S

S

S

SS

SD

SD

FLOOR PLAN GENERAL NOTES

A. ALL DIMENSIONS SHOWN ARE APPROXIMATE AND NEED TO BE VERIFIED IN FIELD BY

CONTRACTOR.

B. PAINT ALL DOORS AND JAMBS IN AREAS WITHIN AREA OF WORK.

DORM

4' - 0"

CORRIDOR

CORRIDOR

CORRIDOR

4' - 0" 4' - 0"

4' - 0"

3' - 0"

4' - 0" 4' - 0"

CONTROL

ROOM

EXTERIOR

HC

HC

SHOWER

CORRIDOR

DHM

DHM

DHM

DHM

D2

14 14 14 15

141414

A1.3

40 BED UNIT

A1.2

A1.23

4' - 0"

D1

D11

D12

TYP

DORM

SHOWER

CORRIDOR

EXTERIOR

NOTE:

CEILING HEIGHTS TO MATCH EXISTING

REFLECTED CEILING PLAN LEGEND

APPLIES TO DRAWINGS A9.1.n - A9.1.n

REFER TO M, E & FP DRAWINGS FOR REFLECTED CEILING PLAN SYMBOLS NOT INDICATED BELOW

A101 nn'-nn"

SPACE NUMBER

CEILING HEIGHT, AFF UNO

2'-0" x 2'-0" LAY-IN ACOUSTICAL CEILING PANELS

IN SUSPENDED GRID

AP ACCESS PANEL

REFLECTED CEILING PLAN/DETAIL GENERAL NOTES

A. DRAWINGS INDICATE GRID LAYOUT DIAGRAMMATICALLY. REFER TO SPECIFICATIONS FOR

SPECIFIC GRID LAYOUT CRITERIA AT PERIMETER CONDITIONS THAT MAY DIFFER FROM GRID

LAYOUT INDICATED ON DRAWINGS.

B. CENTER CEILING MOUNTED ITEMS WITHIN CEILING PANELS, UNLESS INDICATED OTHERWISE.

C. IF ADDITIONAL SPRINKLER HEADS ARE REQUIRED TO SATISFY CODE OR COVERAGE DENSITIES

(OTHER THAN THOSE THAT MAY BE INDICATED), PROVIDE ADDITIONAL SPRINKLER HEADS AT

NO ADDITIONAL COST AND OBTAIN APPROVAL OF ARCHITECT FOR LOCATION OF SUCH HEADS,

IF ANY.

INTERIOR WALL/PARTITION TO CAP ABOVE OR

TERMINATES ADJACENT TO A RATED

HORIZONTAL ASSEMBLY

WITH OPENING

INTERIOR WALL/PARTITION TO UNDERSIDE OF DECK

WITH OPENING

EXTERIOR WALL

WITH OPENING

INTERIOR WALL/PARTITION 4" MIN ABOVE HIGHEST

ADJACENT CEILING. IF NECESSARY TO ACHIEVE

RESULTS DESIRED, EXTEND WALL HEIGHT SO WALL

BRACING IS NOT EXPOSED TO VIEW IN FINISHED

SPACES

WITH OPENING

INTERIOR WALL/PARTITION TO UNDERSIDE OF

CEILING

EXISTING TO REMAIN, VERIFY VERTICAL EXTENTS

WHERE THE HEIGHT IMPACTS THE WORK

4'-0" x 4'-0" STAINLESS STEEL DETENTION

GRADE ACOUSTIC CEILING SYSTEM

CORRIDOR

CORRIDOR

EXTERIOR

CORRIDOR

CORRIDOR

D1

D2

D2

D2

D2

D3

D4

D5

D6

D8D7

SHOWER

DORM

D9

D10

D11

D12

D13

D14

D13

D13

D15

DEMOLITION PLAN LEGEND

APPLIES TO DRAWINGS A1.2.1 - A1.2.n

EXISTING PARTITION/ WALL/ ITEM TO REMAIN

REMOVE EXISTING PARTITION/WALL/ITEM

REMOVE EXISTING WINDOW ASSEMBLY AND

FRAMING, INCLUDING ANCHORS

REMOVE EXISTING DOOR AND FRAME ASSEMBLY

INCLUDING DOOR HARDWARE, ANCHORS, AND

THRESHOLD (WHERE OCCURS).

REMOVE EXISTING PLUMBING FIXTURE. REFER TO

PLUMBING DEMOLITION PLAN FOR ADDITIONAL

INFORMATION.

DEMOLITION PLAN GENERAL NOTES

DA. REMOVE EXISTING AIR SUPPLY GRILLS.

DB. REMOVE LOOSE & CHIPPED CEILING PAINT.

DC. REMOVE CEILING PANELS WITHIN AREA OF SCOPE BOUNDAIRES.

CEILING GRID TO REMAIN. CONTRACTOR TO NOTIFY ARCHITECT OF ANY

ISSUES UNCOVERED THAT REQUIRE SPECIAL ATTENTION, INCLUDING

BUT NOT LIMITED TO LEAKS OR ANY ISSUES THAT AFFECT SECURITY.

DD. EXISTING TILE TO BE FULLY ADHERED TO SUBSTRATE BEFORE RESIN

MATERIAL CAN BE INSTALLED OVER TILE. REVIEW RESIN

MANUFACTURERS REQUIREMENTS FOR SURFACE PREPARATION.

DE. REMOVE EXSITING COUNTERTOP SOAP DISPENSERS.

DF. REMOVE EXISTING ACCESS CEILING PANEL

REMOVE ALL EXISTING FINISH FLOORING AND

CEILING PANELS IN AREA

FLOOR PATTERN LEGEND

NEUTRAL FIELD

CARPET WITH VINYL

TRANSITION &

SECURITY CAULK

RESIN EPOXY

FLOORING

SHOWER

DORM

2' - 9 1/4"

STORAGE ABOVE

SHOWER ROOM

MASONRY UNIT WALL/PARTITION TYPES

REPRESENTED BY Xnn

INFORMATIONMARK REMARKS

FIRE RATED

ASSEMBLY

(REFER TO

LS 1.1 FOR

LEGEND)

M1 ----

M2 ----

6" CMU

8" CMU

M O

S E

L E

Y A

R C

H

IT

E C

T S

.C O

M

PROJECT NO:

DATE:

A

B

C

D

E

1 2 4 53 6 7 8 9 10

F

G

H

I

J

M O

R R

IS

O

N D

R

IV

E S

U

IT

E

C

H A

R L E

S T

O N

S

C

P H

O N

E

-5

/2

:1 :1

P

M

FLOOR PLANS

B E

A U

F O

R T

C O

U N

T Y

B

EA

U

FO

R T

C O

U N

TY

D

ET

EN

TI

O

N C

EN

TE

R G

YM

C

O N

VE

R

SI

O

N

R

IB

A U

T R

O A

D

B E

A U

F O

R T

S

C

A1.1

P R

O

JE

C T

644482

JULY 23, 2026

APPLIES TO DRAWINGS A2.1 - A2.nn

7 QUAD-BUNK BED WITH MIDDLE DIVIDER (O.F.O.I).

11 FIXED SECURITY WINDOW ABOVE (TYP X4). MOUNT AT SAME ELEVATIOON AS

EXISTING CORRIDOR WINDOWS.

12 12 FOOT TALL, 12-GAUGE STEEL SURROUND @ ROOF DS SECURED TO WALL WITH

FASTENERS SPACED 12" O.C. AND TAMPER PROOF SEALANT.

14 4-PERSON DETENTION GRADE FLOOR MOUNTED ACTIVITY TABLE.

15 4-PERSON ACCESSIBLE DETENTION GRADE FLOOR MOUNTED ACTIVITY TABLE.

20 SEAL ALL PENETRATIONS / DAMAGE TO WALL AND CONFIRM WALL IS CONTINUOUS

TO UNDERSIDE OF ROOF DECK ABOVE.

22 INSTALL 8" CMU CHASE TO UNDERSIDE OF ROOF DECK ABOVE. CORE THROUGH

FLOOR SLAB FOR INSTALLATION OF WORK PER PLUMBING DRAWINGS. ALL

PENETRATIONS TO BE FIRE SEALED.

24 FIELD CARPET - PROVIDE VINYL TRANSITION STRIP AND SECURITY CAULK AT BREAK

BETWEEN CARPET & RES-A FLOORING

25 EXTENT OF SMOKE COMPARTMENT. SEE FIRE PROTECTION DRAWINGS FOR MORE

INFORMATION.

1/8" = 1'-0"

FIRST FLOOR PLAN

1/8" = 1'-0"

FIRST FLOOR REFLECTED CEILING PLAN

1/8" = 1'-0"

FIRST FLOOR DEMOLITION PLAN

APPLIES TO DRAWINGS A1.2.1 - A1.2.nn

D1 EXISTING LIGHT SWITCHES TO BE RELOCATED TO CORRIDOR SIDE OF WALL.

D2 REMOVE PORTION OF EXTERIOR WALL COMPLETE TO FIT NEW WINDOW PER PLAN

(TYP).

D3 REMOVE DOOR CEILING AND WALL/FLOOR TILE COMPLETE. PLUMBING FIXTURES

SHALL BE REMOVED AND ALL PLUMBING LINES SHALL BE CAPPED BEHIND WALL OR

IN FLOOR.

D4 REMOVE TV AND WALL MOUNT. TERMINATE ELECTRICAL IN JUNCTION BOX WITH

SECURE COVER PLATE. STORE UNTIL RELOCATED PER NEW PLAN.

D5 REMOVE WALL MOUNTED TELEPHONE AND PREPARE FOR REINSTALLATION WITH

NEW WORK. PATCH AND REPAIR WALL IN PREVIOUS LOCATION.

D6 REMOVE DOUBLE DOORS COMPLETE.

D7 REMOVE WALLS AND PLUMBING FIXTURES COMPLETE. ALL PLUMBING LINES SHALL

BE CAPPED BEHIND WALL OR IN FLOOR.

D8 SAWCUT SLAB ON GRADE TO ACCESS BELOW GRADE PLUMBING AS REQUIRED.

D9 REMOVE BASKETBALL GOAL, FRAME, AND LIFT SYSTEM COMPLETE.

D10 DEMOLISH GYPSUM BOARD CEILING AND SUPPORT STRUCTURE COMPLETE.

D11 PARTITION SHALL BE REMOVED COMPLETE AND EXISTING WALL PATCHED AND

FINISHED TO MATCH.

D12 DEMOLISH ACCESS HATCH AND END OF CMU WALL SUFFICIENT TO INSTALL

EXTENSION IN NEW WORK.

D13 REMOVE EXISTING DOOR/WINDOW, FRAME, AND HARDWARE COMPLETE. PREPARE

ROUGH OPENING FOR INSTALLATION OF NEW WORK WHERE SHOWN.

D14 REMOVE WALL MOUNTED COMMISSARY AND PREPARE FOR REINSTALLATION PER

A-2.2.

D15 DEMO CEILING GRID AND TILES COMPLETE.

1/8" = 1'-0"

FIRST FLOOR FINISH PLAN

1/4" = 1'-0"A1.1

ENLARGED CHASE PLAN6

DETENTION DOOR SCHEDULE

NUMBER

HDWR

SET

NO.

DOOR

SIZE (NOMINAL)

DOOR FRAME FRAME FRAME FRAME FRAME FRAME KEYING KEYING

FIRE

RATING NOTESTYPE MATL

SECURITY

GLAZING

TYPE TYPE NUMBER

HEAD

DETAIL

JAMB

DETAIL

JAMB

DETAIL

SILL

DETAIL SECURITY MASTER

D1 SH2A DG 3' - 0" x 7' - 0" x 2" DHM SG-14F DMH 1 11 11 11 M2 MA -- See sheet A1.2, details # 11,14,15

D2 SH2A DG 3' - 0" x 7' - 0" x 2" DHM SG-14F DMH 1 11 11 11 M2 MA -- See sheet A1.2, details # 11,14,15

REVISIONS

DATE DESCRIPTION

CAROLIN

A

HTU

O S

MOSELEY

ARCHITECTS

No. 3983

C E R T

IF

IC

A

T E

OF AUT

H

O R

IZ

A T

IO

N

03/20/2026

MOSELEY INC

CHARLESTON, SC

02025

OU

E T

S

R E

G

IS

T E R E A

C

T

S O

A

F

TH CAR

O L

IN

A

D R H

I T E

C

A .F

.F

4' - 0"

D

D

NOTE:

WINDOW DIMENSIONS, PROFILE,

AND FINISH TO MATCH EXISTING

HEAD AND SILL TO ALIGN

WITH EXISTING ADJACENT

WINDOW HEAD AND SILL

INSG-1

OPEN TO

SHOWER

ROOM

C L E

A R

SG-14F= 1 1/8" THICK MULTI-PLY GLASS CLAD POLYCARBONATE GLAZING; ASTM F1915 GRADE 1, UL FIRE 45 MIN.

INSG-1= 1 11/16" THICK MULTI-PLY GLASS CLAD POLYCARBONATE INSULATED GLASS UNIT;

OUTER LITE 1/4" GLASS, 1/2" AIR SPACE, & INNER LITE SG-11, CLEAR

DETENTION GLAZING TYPES

REPRESENTED BY n

NOTES:

1. GLAZE ALL OPENINGS IN FRAMES UNLESS SPECIFICALLY INDICATED OTHERWISE

2. ALL GLAZING SHALL BE SAFETY GLASS UNLESS INDICATED OTHERWISE

6" x 11" x 1/4"

STL PLATE TYP.

3" x 3" x 3/16"

STL TUBE

4' - 8"

8"

16 GA SS SEATS TYP.

2'-6" x 2'-6" x 3/8"

STL PLATE

6" x 6" x 1/4" STEEL BASE PLATE W/ (4) 7/16" DIA HOLES W/ 3/8" DIA

SECURITY-TYPE WEDGE ANCHORS TO FLOOR, (1) BASE PLATE PER

TABLE LEG. PLACE BASE PLATES ON LEVELING GROUT

16 GA SS TABLE TOP W/ 1 1/2"

FLANGE. PROVIDE GAME

BOARD ON THE TABLE TOP.

VERIFY W/ OWNER THE EXACT

GAME BOARD TO BE APPLIED.

3" x 3" x 3/16" STL TUBE

/2

3' - 6"

FINISHED FLOOR

1"

1' - 0"

6" x 11" x 1/4" STL

PLATE TYP.

3" x 3" x 3/16" STL TUBE TYP.;

APPLY FINISH PAINT AFTER

INSTALLATION

8"

16 GA SS

SEATS TYP.

2'-6" x 2'-6" x 3/8"

STL PLATE

6" x 6" x 1/4" STEEL BASE PLATE W/ (4) 7/16" DIA. HOLES, TYP W/ 3/8" DIA. SECURITY-TYPE WEDGE ANCHORS TO FLOOR, BOLT & NUT TO BE TACK WELDED, CUT TOP OF BOLT FLUSH WITH NUT, (1) BASE PLATE PER

TABLE LEG. PLACE BASE PLATES ON LEVELING GROUT. FINISH PAINT AFTER INSTALLATION.

16 GA SS TABLE TOP W/ 1 1/2" FLANGE

AND HEMMED EDGES

3" x 3" x 3/16" STL TUBE

TYP. ; FINISH PAINT

AFTER INSTALLATION,

REFER TO SPEC 099000

/2

FINISHED FLOOR

1"

1' - 0"

3' - 6"

6" INVERTED BOND BEAM, FILL

WITH LOW SLUMP MORTAR PRIOR

TO PLACEMENT. GRIND SMOOTH

CORNERS TO MATCH STANDARD

BULLNOSE RADIUS AT TOPS &

EXPOSED ENDS OF WALLS

#4 REINFORCING STEEL

@ 8" O.C.

6" CMU GROUTED SOLID

3" EMBEDMENT INTO FLOOR AND

WALL - REFER TO STRUCTURAL FOR

ADHESIVE DOWEL REQUIREMENTS

H E

IG

H

T V

A R

IE

S

R

E F

E R

T O

P L A

N S

A B C

/4

V A

R

IE

S

3/4" C = 8"

A = 2" B = 4"

/2

D E

1 1/4" G = 8"

/2

/2

D = 2" E = 4" F = 6"

GLAZING AS

SCHEDULED

" 2

/4

V A

R

IE

S

/4

L = 1' - 4"1 1/4"

1 1/4"

GLAZING AS

SCHEDULED

Q = 1'-4"

P = 8" 1 1/4"

M = 2" N = 6"

JM G

H = 2" J = 4" K = 8"

H

L

3/4"

KN P FR S T

R = 2" S = 4"

/2

/2

T = 6"

UU = 8"

U = 4"1 1/4"

UDD

DD = 2"

/4

UU

DETENTION DOOR, FRAME

AND GLAZING TYPE GENERAL NOTES

REFER TO DWG A1.2

FOR DETAILS

n nREFER TO A1.2 FOR

GLAZING TYPE

LEGEND AND NOTES

A .F

.F

3 3

24 24

LEVEL 1

0"

LEVEL 2

14' - 0"

DHM

DHM

DHM

DHM

QUAD-BUNK BED WITH MIDDLE DIVIDER (O.F.O.I) TYP

12 GAUGE PAINTED

STEEL SHEET (12'-0"

TOTAL HEIGHT)

SECURITY SCREWS @ 12"

O.C. WITH TAMPER PROOF

SEALANT ALONG FULL

LENGTH OF CONNECTION

EXISTING ROOF DRAIN

EXISTING CMU WALL

C L R

MINIMUM 2" OVERLAP @ JOINTS

WITH SECURITY SCREWS AND

TAMPER PROOF SEALANT

PROVIDE 12 GAUGE TOP CAP TO

OVERLAP AND BE CONNECTED WITH

SECURITY SCREWS AND TAMPER

PROOF SEALANT

A C

B

SG-14F

PROVIDE GROUT

OPENINGS WHEN

FRAME IS WELDED

TO ADJACENT STL

DOOR POSITION

SWITCH OR

DPS/ CLOSER

DHM FRAME MFR SHALL

PROVIDE & INSTALL CONDUIT

JUNCTION BOXES LOCATED

WITHIN FRAME. COORDINATE

SUPPLIED BOX & CONDUIT

SIZES & LOCATION WITH

RESPECTIVE TRADES FOR

TOP OR BOTTOM FEED

CONDUIT STUB-UP BY

ELECTRICAL CONTRACTOR

JUNCTION BOX & CONDUIT

FOR JAMB MOUNTED LOCK

CONDUIT STUB-UP BY

ELECTRICAL CONTRACTOR

8"

8"

M O

S E

L E

Y A

R C

H

IT

E C

T S

.C O

M

PROJECT NO:

DATE:

A

B

C

D

E

1 2 4 53 6 7 8 9 10

F

G

H

I

J

M O

R R

IS

O

N D

R

IV

E S

U

IT

E

C

H A

R L E

S T

O N

S

C

P H

O N

E

-5

/2

:1 :1

P

M

ELEVATIONS, FRAME

TYPES & DETAILS

B E

A U

F O

R T

C O

U N

T Y

B

EA

U

FO

R T

C O

U N

TY

D

ET

EN

TI

O

N C

EN

TE

R G

YM

C

O N

VE

R

SI

O

N

R

IB

A U

T R

O A

D

B E

A U

F O

R T

S

C

A1.2

P R

O

JE

C T

644482

JULY 23, 2026

1/4" = 1'-0"A1.2

DHM1 ELEVATION4

1/2" = 1'-0"A1.3 A1.2

VIDEO VISITATION1

APPLIES TO DRAWINGS A3.2.1 - A3.2.n

1 ANCHORAGES, REINFORCING, SPECIFIC PARTITION CONSTRUCTION AND/OR LINTELS ARE NOT SHOWN

FOR CLARITY.

2 REFER TO FRAME SECTION IN DOOR SCHEDULE FOR TYPE.

3 SEALANT, ALL SIDES - TOOL TO 90°.

4 BACKBEND RETURN @ GB LOCATIONS ONLY.

5 9/16" @ MAS; 1/2" @ GB.

6 1/4" @ JAMBS, UNO; DIMENSION @ HEAD & SILL VARIES.

7 BULLNOSE @ CMU JAMBS & SILLS.

8 0" @ GB LOCATIONS; 1/16" @ MAS LOCATIONS.

1" = 1'-0"A1.2

DETENTION 4-MAN TABLE8

1" = 1'-0"A1.2

DETENTION 4-MAN ACCESSIBLE TABLE9

APPLIES TO DRAWINGS A2.1 - A2.nn

1 RELOCATED COMMISSARY. COORDINATE WITH OWNERS 3RD PARTY VENDOR.

3 VIDEO VISITATION STATION WITH 56" H DIVIDER WALL & FIXED STOOL (SWING STOOL FOR ADA ACCESS).

4 TV MOUNTED TO WALL ABOVE.

12 12 FOOT TALL, 12-GAUGE STEEL SURROUND @ ROOF DS SECURED TO WALL WITH FASTENERS SPACED

12" O.C. AND TAMPER PROOF SEALANT.

18 RELOCATED WALL MOUNTED TELEPHONE.

19 CONFIRM EXISTING DRINKING FOUNTAIN IS IN WORKING CONDITION AND FULLY SECURED TO WALL.

23 INSTALL STAINLESS STEEL SHEET WITH SECURITY CAULKING BEHIND TELEPHONE BOOTHS TO HEIGH OF

DIVIDER WALLS. REFER TO SPECIFICATION SECTION 055000 METAL FABRICATIONS.

24 FIELD CARPET - PROVIDE VINYL TRANSITION STRIP AND SECURITY CAULK AT BREAK BETWEEN CARPET &

RES-A FLOORING

1 1/2" = 1'-0"A1.2

TYPICAL WING WALL5

3" = 1'-0"A1.2

DETENTION FRAME SECTIONS10

1/2" = 1'-0"A1.3 A1.2

OFFICER STATION 12

1 1/2" = 1'-0"A1.1 A1.2

ROOF DRAIN SURROUND7

A1.2

ROOF DRAIN AXON6

1/4" = 1'-0"A1.1 A1.2

INTERIOR WEST ELEVATION3

1/2" = 1'-0"A1.2

DOOR TYPE DG15

1/2" = 1'-0"A1.2

FRAME ELEVATION DETAIL14

REVISIONS

DATE DESCRIPTION

CAROLIN

A

HTU

O S

MOSELEY

ARCHITECTS

No. 3983

C E R T

IF

IC

A

T E

OF AUT

H

O R

IZ

A T

IO

N

03/20/2026

MOSELEY INC

CHARLESTON, SC

02025

OU

E T

S

R E

G

IS

T E R E A

C

T

S O

A

F

TH CAR

O L

IN

A

D R H

I T E

C

F

3K

3K

'-1

C H

IL

D

'-1

T O

T O

P O

F G

R A

B B

A R

1' - 0"

3' - 4"

F A

C E

O F

F

IN

IS

H

E D

W A

L L

'-6

C H

IL

D

'-4

T

O B

O T

T O

M O

F G

R A

B B

A R

TOP OF WATER

CLOSET SEAT

F R

O N

T R

IM

O

W A

T E

R

C L

O S

E T

8"

B O

T T

O M

O F

G R

A B

B A

R

/2

C L E

A R

1' - 0"

A

C E

O F

F

IN

IS

H

E D

W A

L L

O R

T O

IL

E

T P

A R

T

IT

IO

N

T O

P O

F S

E A

T

T

O OF WATER

CLOSET

4"

'-2

C H

IL

D

'-6

M

IN

T

O D

IS

P

E N

S E

R O

U T

L E

T

AB

C

E D

A. PLAN DIMENSIONS ARE TO FACE OF WALL OR PARTITION. WHERE APPLIED FINISHES OCCUR-SUCH AS CERAMIC TILE-DIMENSIONS ARE TO FACE OF APPLIED FINISH. FOR WAINSCOTS, FLOOR PLAN DIMENSIONS ARE TO FACE OF WAINSCOT MATERIAL. APPLIED FINISHES ARE NOT ALLOWED TO REDUCE CLEAR DIMENSIONS. “APPLIED FINISHES” IN THIS CASE DO NOT INCLUDE TRIM, BASE, AND ACOUSTIC WALL PANELS.

B. CLEAR DIMENSIONS ARE TO FACE OF APPLIED WALL AND PARTITION FINISHES.

TOILET ASSEMBLIES, SCHEDULE AND ENLARGED PLAN GENERAL NOTES

D18D10 D18

4" MAX

1' - 3" MAX

T O

T O

P O

F G

R A

B B

A R

T O

B O

T T

O M

O F

G R

A B

B A

R

D4

D4

M

IN

M A

X

F A

C E

O F

F

IN

IS

H

E D

C O

N T

R O

L W

A L

L

O P

E N

S

ID

E

COORDINATE

BLOCKING WITH

MANUFACTURERS

RECOMMENDATIONS

F A

C E

O F

F

IN

IS

H

E D

W A

L L

F A

C E

O F

F

IN

IS

H

E D

W A

L L

CONTROL

AREA

CONTROL END WALL

SHOWER

C L E

A R

T Y

P

3'

2"

3' - 1 1/4"

A1.2

M2

M2

M1

M1

M1

M2

/4

/4

/4

E Q

E Q

E Q

E Q

M1

/4

EXISTING

M2

10 16

6' - 8"

ALIGN

M1

2' - 9 1/4"

2' - 8"

CLEAR

4' - 0"

3'

6"

CLEAR

4' - 0"

4'

8"

3'

6"

18B

18A

M1

M1

M1

D3 D4

D1

D5

D5

D47

D5

D5

D1

D2

D1

D6

D6

D6

D6

D6

D10

D10

D10

D10

D10

D18

D8

D8A

D19

DORM

D1

SLOPE TO DRAIN

HALF THE WIDTH

OF CMU WALL

/4

/4

E M

B E

D P

L A

T E

H E

IG

H

T

SECTION 'C'

@CMU

A

F F

/2

/4

/2

/4

A

F F

C

± 1' - 0 1/2"

1/4" 1/4"

EMBED PLATE WIDTH

MIRROR

SHOWN

DASHED

FOR

CLARITY

OUTLINE

OF

MIRROR

16 HOLES DRILLED AND TAPPED FOR 1/4" #20 FLAT HEAD SECURITY

SCREWS. LOCATIONS AS PER MIRROR MFR'S RECOMMENDATIONS

POLISHED SHEET SS

MIRROR. REFER TO

SECTION 111900

/2

8 HOLES FOR

1/4" #20 FLAT

HEAD SECURITY

SCREWS

18 GA CHROME

PLATE. 1 1/4"

WIDE FRAME

± 1' - 0 1/2"

M

IN

A

F F

SECURITY SEALANT AT

WALL (ENTIRE

PERIMETER)

1/4" GALVANIZED STL EMBED PLATE w/ 11 GA x 2" BENT STL ANCHORS w/ MINIMUM 2" BEND

M

IN

/2

PROVIDE BOTTOM OF MIRROR

REFLECTIVE SURFACE AT MAX

3'-4" (40") AFF

CL

A

HALF THE WIDTH

OF CMU WALL

MIRROR SHOWN

DASHED FOR

CLARITY

MIRROR

/2

/4

/4

E

M B

E D

P L A

T E

H E

IG

H

T

8 HOLES DRILLED AND TAPPED FOR

1/4" #20 FLAT HEAD SECURITY

SCREWS. LOCATIONS AS PER MIRROR

MFG'S RECOMMENDATIONS

SECTION 'B' @CMU

OUTLINE

OF MIRROR

POLISHED SHEET SS

MIRROR. REFER TO

SECTION 111900

/2

8 HOLES FOR

1/4" #20 FLAT

HEAD SECURITY

SCREWS.

18 GA CHROME

PLATE. 1 1/4"

WIDE FRAME

± 1' - 0 1/2"

± 1' - 0 1/2"

EMBED PLATE WIDTH1/4" 1/4"

B

M

IN

A

F F

A

F F

SECURITY SEALANT AT WALL

(ENTIRE PERIMETER)

1/4" GALVANIZED STL EMBED

PLATE w/ 11 GA x 2" BENT STL ANCHORS w/ MINIMUM 2" BEND

A F

F

/2

S Q

5 1/4"

CL

7-9" TO FRONT

OF TOILET

14 GA WITH

SS FINISH

CL

D

SECTION 'D'

4 1/2"

/2

ELEVATION

1/4"

1"

1" WIDE x 1" x 2-1/2" x 1/4"

ANGLE TABS AT 4

SIDES - WELD TO

HOLDER CASING

SECURITY

SEALANT ALL

SIDES

A

F F

T

Y P

SECTION 'A'

A

ELEVATION

14 GA SS SLOPE TOP HOUSING

WITH COLLAPSIBLE STAINLESS

STL BALL JOINT AND SPRING

FRICTION TYPE HOOK

A

F

A C

C E

S S

IB

L

E L

O C

A T

IO

N

S

1 HOOK

5"

/2

1/4" STAINLESS STL

EMBED PLATE WITH

11 GA X 2" WIDE BENT

STL ANCHORS

HALF THE WIDTH

OF CMU WALL

M

IN

DRILL & TAP EMBED

PLATE FOR 1/4" #20

SECURITY SCREWS

ON HOUSING

SECURITY SEALANT

AT WALL (ENTIRE

PERIMETER)

M O

S E

L E

Y A

R C

H

IT

E C

T S

.C O

M

PROJECT NO:

DATE:

A

B

C

D

E

1 2 4 53 6 7 8 9 10

F

G

H

I

J

M O

R R

IS

O

N D

R

IV

E S

U

IT

E

C

H A

R L E

S T

O N

S

C

P H

O N

E

-5

/2

:1 :2

P

M

TOILET PLANS &

DETAILS

B E

A U

F O

R T

C O

U N

T Y

B

EA

U

FO

R T

C O

U N

TY

D

ET

EN

TI

O

N C

EN

TE

R G

YM

C

O N

VE

R

SI

O

N

R

IB

A U

T R

O A

D

B E

A U

F O

R T

S

C

A1.3

P R

O

JE

C T

644482

JULY 23, 2026

3/4" = 1'-0"

WATER CLOSET ELEVATIONS

3/4" = 1'-0"

TRANSFER-TYPE SHOWER ELEVATIONS

1/2" = 1'-0"A1.1 A1.3

ENLARGED TOILET PLAN7

APPLIES TO DRAWINGS A2.1 - A2.nn

1 RELOCATED COMMISSARY. COORDINATE WITH OWNERS 3RD PARTY VENDOR.

2 FIXED OFFICER STATION.

3 VIDEO VISITATION STATION WITH 56" H DIVIDER WALL & FIXED STOOL (SWING STOOL FOR ADA ACCESS).

4 TV MOUNTED TO WALL ABOVE.

5 FLUSH FLOOR DRAIN @ OPENING.

6 EXTENSION OF EXIST 72" HIGH PLUMBING CHASE. USE SIMILAR MATERIALS MATCHING DIMENSION, PROFILE, AND FINISH.

8 40" H CMU PARTITION (TYP).

9 56" H CMU PARTITION (TYP).

10 PLUMBING CHASE.

16 DETENTION GRADE, 18" X 36" ACCESS DOOR.

17 DETENTION GRADE ACCESS DOOR. GC TO VERIFY EXISTING OPENING.

18A EXISTING WALL MOUNTED TELEPHONE. CONFIRM IN WORKING ORDER. COORDINATE WITH OWNERS 3RD PARTY VENDOR.

18B RELOCATED WALL MOUNTED TELEPHONE. CONFIRM IN WORKING ORDER. COORDINATE WITH OWNERS 3RD PARTY VENDOR.

19 CONFIRM EXISTING DRINKING FOUNTAIN IS IN WORKING CONDITION AND FULLY SECURED TO WALL.

20 SEAL ALL PENETRATIONS / DAMAGE TO WALL AND CONFIRM WALL IS CONTINUOUS TO UNDERSIDE OF ROOF DECK ABOVE.

21 INSTALL ADJUSTABLE SWEEPS AND SEALS COMPLETE.

22 INSTALL 8" CMU CHASE TO UNDERSIDE OF ROOF DECK ABOVE. CORE THROUGH FLOOR SLAB FOR INSTALLATION OF WORK PER PLUMBING DRAWINGS. ALL

PENETRATIONS TO BE FIRE SEALED.

23 INSTALL STAINLESS STEEL SHEET WITH SECURITY CAULKING BEHIND TELEPHONE BOOTHS TO HEIGH OF DIVIDER WALLS. REFER TO SPECIFICATION SECTION

055000 METAL FABRICATIONS.

25 EXTENT OF SMOKE COMPARTMENT. SEE FIRE PROTECTION DRAWINGS FOR MORE INFORMATION.

REVISIONS

DATE DESCRIPTION

DETENTION EQUIPMENT SCHEDULE

NO DESCRIPTION MOUNTING HEIGHT DETAIL NOTES

D1 DETENTION MIRROR - SINGLE 3/A7.2.1

D2 DETENTION MIRROR - DOUBLE REFER TO DETAIL 4/A7.2.1

D3 GRAB BAR, ANTI-LIGATURE, 42" REFER TO WATER CLOSET ACCESSORY ELEVS 1/A7.2.1

D4 18" VERTICAL GRAB BAR, ANTI-LIGATURE REFER TO WATER CLOSET ACCESSORY ELEVS 1/A7.2.1

D5 RECESSED TOILET PAPER HOLDER REFER TO DETAIL 6/A7.2.1

D6 SINGLE DETENTION HOOK - ANTI-LIGATURE REFER TO DETAIL 7/A7.2.1

D8 DETENTION STOOL - FLOOR MOUNTED

D8A DETENTION SWING STOOL - WALL MOUNTED

D10 DETENTION SHOWER CURTAIN

D11 4-SEAT TABLE FLOOR MOUNTED 8/A1.2

D12 3-SEAT TABLE (ADA ACCESSIBLE) FLOOR MOUNTED 9/A1.2

D18 18"x36" CORNER GRAB BAR ASSEMBLY REFER TO SHOWER ELEVATIONS

D19 L-SHAPED FOLDING SHOWER SEAT REFER TO SHOWER ELEVATIONS

D47 PENAL COMBINATION FIXTURE

1 1/2" = 1'-0"

DETENTION MIRROR - DOUBLE

1 1/2" = 1'-0"

DETENTION MIRROR - SINGLE

3" = 1'-0"

RECESSED TOILET PAPER ROLL HOLDER

3" = 1'-0"

SAFETY CLOTHES HOOK

CAROLIN

A

HTU

O S

MOSELEY

ARCHITECTS

No. 3983

C E R T

IF

IC

A

T E

OF AUT

H

O R

IZ

A T

IO

N

03/20/2026

MOSELEY INC

CHARLESTON, SC

02025

OU

E T

S

R E

G

IS

T E R E A

C

T

S O

A

F

TH CAR

O L

IN

A

D R H

I T E

C

A. FINISH SCHEDULE DESCRIBES ONLY THE BASIC OR PREDOMINANT SURFACE FINISH.

B. PROVIDE SAME FINISHES AS THE ADJACENT SPACE IN ALCOVES AND CONTINUOUS

SPACES WITHOUT DESIGNATED SPACE NUMBERS.

C. CASEWORK FINISHES ARE NOT NOTED IN THE FINISH SCHEDULE. REFER TO CASEWORK

ELEVATIONS AND SPECIFICATIONS FOR MATERIALS AND FINISHES.

D. DIRECTIONAL WALL FINISH INDICATORS (NORTH, EAST, SOUTH, WEST) REFER TO THE

"PLAN" NORTH ORIENTATION.

E. BULKHEADS AND SOFFITS MAY NOT BE INDICATED IN FINISH SCHEDULES. REFER TO RCP

DETAILS, AND OTHER DOCUMENTS FOR EXTENT.

F. PROVIDE CONTINUOUS SEALANT BETWEEN INTERIOR SLAB-ON-GRADE AND VERTICAL

ELEMENT WHERE JOINT IS NOT CONCEALED BY FINISH BASE OR OTHER CONSTRUCTION

G. REFER TO SPECIFICATIONS FOR INFORMATION ON FINISH FIRE CLASSIFICATION RATING..

FINISH SCHEDULE GENERAL NOTES

M O

S E

L E

Y A

R C

H

IT

E C

T S

.C O

M

PROJECT NO:

DATE:

A

B

C

D

E

1 2 4 53 6 7 8 9 10

F

G

H

I

J

M O

R R

IS

O

N D

R

IV

E S

U

IT

E

C

H A

R L E

S T

O N

S

C

P H

O N

E

-5

/2

:1 :2

P

M

FINISH SCHEDULE

B E

A U

F O

R T

C O

U N

T Y

B

EA

U

FO

R T

C O

U N

TY

D

ET

EN

TI

O

N C

EN

TE

R G

YM

C

O N

VE

R

SI

O

N

R

IB

A U

T R

O A

D

B E

A U

F O

R T

S

C

A3.1

P R

O

JE

C T

644482

JULY 23, 2026

FINISH SCHEDULE

NUMBER NAME FLOOR BASE

WALLS

WAINSCOT CEILING NOTESNORTH EAST SOUTH WEST

101 DORM TCF-A1; RES-A RES-A EPX PT EPX PT EPX PT EPX PT HNRC-ACP

102 SHOWER SSM SSM EPX PT EPX PT EPX PT EPX PT MATCH CURRENT

201 STORAGE

INTERIOR FINISH LEGEND

SPECIFICATION DESCRIPTION MANUFACTURER PRODUCT - COLOR

SOLID SURFACE MATERIALS

10000 SSM CORIAN EVEREST

ACOUSTICAL CEILINGS

95100 ACP ARMSTRONG 1756; WHITE; 15/16 ANGLED TEGULAR

FLUID-APPLIED FLOORING

96700 RES-A SHERWIN WILLIAMS ANVIL

TEXTILE COMPOSITE FLOORING

96817 TCF-A1 JJ FLOORING Z FACTOR 1844 - TRIAL 2864

PAINT

99100 EPX PT A1 SHERWIN WILLIAMS TOQUE WHITE; FIELD PAINT

99100 EPX PT A3 SHERWIN WILLIAMS HIGH REFLECTIVE WHITE, CEILING

99100 EPX PT A4 SHERWIN WILLIAMS DOMINO, TRIM

REVISIONS

DATE DESCRIPTION

CAROLIN

A

HTU

O S

MOSELEY

ARCHITECTS

No. 3983

C E R T

IF

IC

A

T E

OF AUT

H

O R

IZ

A T

IO

N

03/20/2026

MOSELEY INC

CHARLESTON, SC

02025

OU

E T

S

R E

G

IS

T E R E A

C

T

S O

A

F

TH CAR

O L

IN

A

D R H

I T E

C

A. THE CONTRACT DOCUMENTS ARE COMPLEMENTARY AND WHAT IS REQUIRED BY ONE SHALL BE AS BINDING AS IF REQUIRED BY ALL. IN THE CASE OF A CONFLICT, DISAGREEMENT, OR AMBIGUITY, PROVIDE THE BETTER QUALITY. IN THE CASE OF A CONFLICT, DISAGREEMENT, OR AMBIGUITY, PROVIDE THE GREATER QUANTITY

OF WORK.

B. FOLLOW MOUNTING HEIGHTS INDICATED IN THE ELECTRICAL LEGEND UNLESS OTHERWISE INDICATED.

MEASURE ALL MOUNTING HEIGHTS FROM THE DEVICE CENTER LINE UNLESS OTHERWISE INDICATED.

C. FIELD VERIFY EXACT FEEDER LOCATIONS FOR MECHANICAL EQUIPMENT PRIOR TO ROUGH-IN.

D. EQUIPMENT CONNECTIONS ARE INDICATED IN THEIR APPROXIMATE LOCATIONS. VERIFY EXACT LOCATIONS OF ALL CONNECTIONS WITH OTHER TRADES SUPPLYING EQUIPMENT TO AVOID CONFLICTS AT INSTALLATION.

E. LOCATED ALL SWITCHES FOR LOCAL CONTROL OF LIGHTING ON STRIKE SIDE OF SINGLE DOORS UNLESS

OTHERWISE INDICATED.

F. PROVIDE SPECIFIC BREAKER ARRANGEMENT FOR THE PANEL BOARDS WHEREVER PHYSICALLY POSSIBLE.

PROVIDE AS-BUILT DRAWINGS INDICATING ACTUAL BRANCH CIRCUIT ARRANGEMENT. PROVIDE TYPE

WRITTEN PANELBOARD DIRECTORIES INDICATING ACTUAL BRANCH CIRCUIT ARRANGEMENT.

G. PROVIDE AS-BUILT DRAWINGS INDICATING ACTUAL BRANCH CIRCUIT ARRANGEMENT. PROVIDE TYPEWRITTEN PANELBOARD DIRECTORIES INDICATING ACTUAL BRANCH CIRCUIT ARRANGEMENT. HAND

WRITTEN SCHEDULES ARE NOT ACCEPTABLE.

H. ALL CONDUIT RUNS INDICATED ARE DIAGRAMMATIC, COORDINATE ROUTING IN ALL SPACES WITH OTHER

TRADES.

I. ALL PANELBOARDS INDICATED ARE HOUSED IN A SINGLE WIDTH ENCLOSURE, UNO. THE CONTRACTOR SHALL FIELD VERIFY ROOM LAYOUT AND ADJUST ACCORDINGLY, AT NO COST TO THE OWNER, IF PROVIDING ANY

PANELBOARD ENCLOSURES.

J. WHERE POWER AND COMMUNICATION OUTLETS ARE INDICATED IN CLOSE PROXIMITY ON THE DRAWINGS, FIELD COORDINATE THE LOCATIONS TO PLACE THE OUTLETS ADJACENT TO EACH OTHER.

K. ALL EXTERIOR RECEPTACLES SHALL BE LABELED "WR" - WEATHER RESISTANT.

L. WHEN GROUPING MULTIPLE LINE TO NEUTRAL BRANCH CIRCUITS IN A CONDUIT, PROVIDE DEDICATED COLOR CODED NEUTRAL CONDUCTORS FOR EACH CIRCUIT. DO NOT USE BREAKER TIES AND SHARED

NEUTRALS EVEN THOUGH PERMITTED BY NEC.

M. PROVIDE A 2” WIDE YELLOW LINE PAINTED ON THE FLOOR INDICATING THE ELECTRICAL WORKING SPACE. IN FRONT OF ALL ELECTRICAL PANELS IN ELECTRICAL ROOMS. REFER TO PLANS FOR ELECTRICAL WORKING SPACE DETAILS. STENCIL “NO STORAGE” IN 2” HIGH, YELLOW LETTERS CENTERED IN THE OUTLINED AREA.

GENERAL NOTES

NOTE: REFER TO 'TYPICAL COMMUNICATION OUTLET DETAIL' FOR BOX & CONDUIT REQUIREMENTS. REFER TO

TELECOMMUNICATION DEVICE DETAILS FOR CABLING AND TERMINAL JACK REQUIREMENTS.

SYMBOL DESCRIPTION

COMMUNICATIONS LEGEND

TELECOMMUNICATIONS OUTLET, MOUNT AT +3'-10"AFF.

TELECOMMUNICATIONS OUTLET, . MOUNT AT +1'-6"AFF.

VIDEO VISIT STATION WITH PUSHBUTTON, REFER TO ARCH DRAWING FOR MOUNTING HEIGHTS

CATV OUTLET, REFER TO ARCH DRAWING FOR MOUNTING HEIGHTS

SOUND SYSTEM SPEAKER, RECESS CEILING MOUNT. 'WG' WHERE PRESENT INDICATES PROVIDE

PROTECTIVE WIRE GUARD.

S

MONITOR OUTLET, REFER TO ARCH DRAWING FOR MOUNTING HEIGHTS

SMOKE DAMPERS. REFER TO DETAILS MATRIX M

INMATE PHONE OUTLET, MOUNT AT +3'-10"AFF.

WALL MOUNT CAMERA. REFER TO PLANS FOR DETAILS. ADDITIONAL EQUIPMENT AND WIRING

SHALL BE PROVIDED BY THE OWNER.

INTERCOM. REFER TO PLANS FOR DETAILS. ADDITIONAL EQUIPMENT AND WIRING SHALL BE

PROVIDED BY THE OWNER.

SYMBOL DESCRIPTION

DEMOLITION LEGEND

REMOVE DEVICES, EQUIPMENT, IN ACCORDANCE

WITH THE GENERAL DEMOLITION NOTES.

DEVICES ARE EXISTING TO REMAIN.

WITHIN HATCHED AREAS, DISCONNECT AND REMOVE ALL ELECTRICAL MATERIALS

INCLUDING BUT NOT LIMITED TO LIGHTS, DEVICES, EQUIPMENT, SPEAKERS, FIRE ALARM,

COMMUNICATIONS, AND CIRCUITRY.

A. PROVIDE ALL ELECTRICAL DEMOLITION WORK REQUIRED TO INSTALL THE WORK INDICATED. REMOVE, REROUTE, AND RECONNECT ALL BRANCH CIRCUITS THAT WILL REMAIN IN USE BUT INTERFERES WITH THE

WORK.

B. REMOVE ALL EXISTING CONDUITS THAT WILL NOT BE REUSED AND WHERE THEY WILL BE EXPOSED AFTER COMPLETION. ABANDON ALL OTHERS IN THE WALLS ONLY. DISCONNECT ALL WIRING INDICATED AND/OR

REQUIRED TO BE REMOVED FROM ALL POWER SOURCES. REMOVE ALL WIRING FROM ABANDONED

CONDUITS AND PROVIDE BLANK COVER PLATES FOR BOXES NOT UTILIZED FOR THE WORK.

C. MAINTAIN CONTINUITY OF ALL EXISTING CIRCUITS TO REMAIN OR PORTIONS THEREOF AFFECTED BY THE

WORK.

D. BEFORE DEMOLITION, VERIFY WITH THE OWNER ALL EQUIPMENT TO BE SALVAGED TO OWNER AND NOT REMOVED FROM THE SITE. FOR ALL REMAINING EQUIPMENT INDICATED FOR REMOVAL (AND NOT

RELOCATED), REMOVE AND DISPOSE IN A LEGAL MANNER.

E. EXERCISE CARE IN REMOVING DEMOLITION ITEMS. REPAIR OR REPLACE ALL DAMAGE CAUSED TO EXISTING

CONSTRUCTION AND EQUIPMENT TO REMAIN.

F. DRAWINGS ARE BASED UPON EXISTING PLANS AND FIELD INVESTIGATION WITHOUT DEMOLITION. VISIT THE EXISTING BUILDING AND BECOME FAMILIAR WITH ALL EXISTING CONDITIONS AND EXAMINE ALL DRAWINGS

TO AVOID CONFLICTS.

G. WHERE DEMOLITION OF TELECOMMUNICATIONS DEVICES OCCUR, REMOVE CABLING NOT INDICATED TO

REMAIN BACK TO POINT OF ORIGIN.

H. DEMOLITION FLOOR PLANS ARE PROVIDED FOR REFERENCE ONLY TO AID IN DEFINING THE SCOPE OF

DEMOLITION WORK.

GENERAL DEMOLITION NOTES

SYMBOL DESCRIPTION

FIRE ALARM LEGEND

FIRE ALARM AUDIO/VISUAL NOTIFICATION DEVICE, MOUNT AT 80” AFF AND NOT MORE THAN 96”.

SUBSCRIPT NUMBER INDICATES STROBE CANDELA RATING.

FIRE ALARM VISUAL STROBE NOTIFICATION DEVICE, 80” AFF AND NOT MORE THAN 96”. SUBSCRIPT

NUMBER INDICATES STROBE CANDELA RATING.

FIRE ALARM MANUAL PULL STATION, MOUNT AT +3'-10"AFF.

FIRE ALARM KEY OPERATED MANUAL PULL STATION, MOUNT AT +3'-10"AFF.

F

FK

FIRE ALARM DUCT SMOKE DETECTOR, FURNISH AND CONNECT UNDER DIVISION 28. INSTALL UNDER DIVISION 23. VERIFY LOCATION WITH DIVISION 23 PRIOR TO ROUGH-IN. PROVIDE ACCESSIBLE KEY

OPERATED REMOTE TEST SWITCH FOR EACH DETECTOR.

SMOKE DETECTOR, CEILING MOUNT. SUBSCRIPT 'G' WHEN PRESENT INDICATES PROVIDE DEVICE GUARD.

HEAT DETECTOR, CEILING MOUNT. SUBSCRIPT 'G' WHEN PRESENT INDICATES PROVIDE DEVICE GUARD.

S

H

FIRE ALARM TAMPER SWITCHTS

FS FIRE ALARM FLOW SWITCH

FIRE ALARM/POWER CONNECTION TO DIVISION 23 SMOKE OR FIRE/SMOKE DAMPER. COORDINATE

WITH DIVISION 23. REFER TO TYPICAL FIRE/SMOKE DAMPER DIAGRAM.

SD

FIRE ALARM AUDIO/VISUAL NOTIFICATION DEVICE WITH DEVICE GUARD, 80” AFF AND NOT MORE THAN 96”. SUBSCRIPT NUMBER INDICATES STROBE CANDELA RATING. # / # INDICATES STROBE SETTING AND

REDUCED EFFECTIVE OUTPUT WHEN DEVICE GUARD IS PRESENT.

FIRE ALARM VISUAL STROBE NOTIFICATION DEVICE, 80” AFF AND NOT MORE THAN 96”. SUBSCRIPT NUMBER INDICATES STROBE CANDELA RATING. # / # INDICATES STROVE SETTING AND REDUCED

EFFECTIVE OUTPUT WHEN DEVICE GUARD IS PRESENT.

xx xx xx xx

SYMBOL DESCRIPTION

LIGHTING LEGEND

LIGHT SWITCH, RATED 120/277 VOLTS, 20-AMPS, MOUNT AT +3'-10"AFF. SUBSCRIPT/SUPERSCRIPT

LETTERS, NUMBERS, AND SYMBOLS INDICATES SWITCH TYPE AS FOLLOWS:

3 INDICATES 3-WAY LIGHT SWITCH

4 INDICATES 4-WAY LIGHT SWITCH

D INDICATES DIMMER SWITCH

P INDICATES PILOT LIGHT, ON WHEN SWITCH IS ON

K INDICATES KEY OPERATED LIGHT SWITCH

OS INDICATES SWITCH WITH INTEGRAL OCCUPANCY SENSOR

OD INDICATES DIMMER SWITCH WITH INTEGRAL OCCUPANCY SENSOR

LOWER CASE LETTER INDICATES LIGHT FIXTURE CONTROL DESIGNATION

OMNI-DIRECTIONAL LIGHTING CONTROL OCCUPANCY DETECTOR, CEILING MOUNT.

LIGHT FIXTURE, CEILING MOUNT.

LIGHT FIXTURE ON EMERGENCY POWER, CEILING MOUNT.

LIGHTING FIXTURE.

LIGHTING FIXTURE ON EMERGENCY POWER.

LIGHT FIXTURE, WALL MOUNT, HEIGHT AS INDICATED.

EMERGENCY EGRESS LIGHTING FIXTURE, WITH BATTERY PACK, WALL MOUNT AT +8'-0"AFF.

EXIT SIGN, CEILING MOUNT. DIRECTIONAL ARROWS AS INDICATED. SHADING INDICATES FACE(S) OF SIGN.

EXIT SIGN, WALL MOUNT. DIRECTIONAL ARROWS AS INDICATED. SHADING INDICATES FACE(S) OF SIGN.

SYMBOL DESCRIPTION

POWER LEGEND

APPLIANCE RECEPTACLE, MOUNT AT +1'-6" AFF. PROVIDE NEMA CONFIGURATION TO MATCH PLUG FOR

EQUIPMENT SERVED.

DUPLEX RECEPTACLE, NEMA 5-20R, MOUNT AT +1'-6"AFF.

DUPLEX RECEPTACLE, NEMA 5-20R, MOUNT AT +3'-10"AFF.

DUPLEX RECEPTACLE, NEMA 5-20R, MOUNT AT +7'-6"AFF.

GFCI DUPLEX RECEPTACLE, NEMA 5-20R, MOUNT AT +1'-6"AFF.

GFCI DUPLEX RECEPTACLE, NEMA 5-20R, MOUNT AT +3'-10"AFF.

DOUBLE DUPLEX RECEPTACLE, NEMA 5-20R, MOUNT AT +1'-6"AFF.

DOUBLE DUPLEX RECEPTACLE, NEMA 5-20R, MOUNT AT +3'-10"AFF.

DOUBLE DUPLEX RECEPTACLE, NEMA 5-20R, RECESS FLOOR MOUNT.

JUNCTION BOX, CONCEALED ABOVE CEILING, UNO.

EQUIPMENT POWER CONNECTION.

MOTOR CONNECTION.

CONNECTION TO DIV 23 MOTORIZED DAMPER, VERIFY LOCATION.

PANELBOARD.

J

E

M

FEEDER TAG. REFER TO FEEDER SCHEDULE XXX

POWER FOR VIDEO VISIT STATION ADJACENT TO COMM OUTLET.

POWER FOR CATV OUTLET ADJACENT TO COMM OUTLET.

POWER FOR MONITOR OUTLET ADJACENT TO COMM OUTLET.

FEEDER

ID

# OF

SETS

BUILDING WIRE

QUANTITY & SIZE TYPE

THHN - DRY

TYPE THWN - WET

MINIMUM

CONDUIT

SIZE

COPPER FEEDER SCHEDULE

30 1 3#10,#10 G 3/4"

35 1 3#8,#10 G 3/4"

40 1 3#8,#10 G 3/4"

45 1 3#6,#10 G 1"

50 1 3#6,#10 G 1"

60 1 3#4,#10 G 1"

70 1 3#4,#8 G 1 1/4"

80 1 3#3,#8 G

90 1 3#2,#8 G

100 1 3#2,#8 G

1 1/4"

1 1/4"

1 1/4"

NOTES:

1. ELECTRICAL CONTRACTOR TO VERIFY CONDUIT SIZE REQUIRED IF WIRE TYPES OTHER THAN THOSE LISTED ABOVE ARE USED.

2. FEEDER SIZES BASED ON TABLE 310.15(B)(16), 75º C.

3. SIZES ADJUSTED PER NEC 110.14.

FEEDER

ID

# OF

SETS

BUILDING WIRE

QUANTITY & SIZE TYPE

THHN - DRY

TYPE THWN - WET

MINIMUM

CONDUIT

SIZE

30Y 1 4#10,#10 G 3/4"

35Y 1 4#8,#10 G 3/4"

40Y 1 4#8,#10 G 3/4"

45Y 1 4#6,#10 G 1"

50Y 1 4#6,#10 G 1"

60Y 1 4#4,#10 G 1"

70Y 1 4#4,#8 G 1 1/4"

80Y 1 4#3,#8 G

90Y 1 4#2,#8 G

100Y 1 4#2,#8 G

1 1/4"

1 1/4"

1 1/4"

FEEDER

ID

# OF

SETS

BUILDING WIRE

QUANTITY & SIZE TYPE

THHN - DRY

TYPE THWN - WET

30S 1 2#10,#10 G 3/4"

35S 1 2#8,#10 G 3/4"

40S 1 2#8,#10 G 3/4"

45S 1 2#6,#10 G 1"

50S 1 2#6,#10 G 1"

60S 1 2#4,#10 G 1"

70S 1 2#4,#8 G 1 1/4"

80S 1 2#3,#8 G

90S 1 2#2,#8 G

100S 1 2#2,#8 G

1 1/4"

1 1/4"

1 1/4"

MINIMUM

CONDUIT

SIZE

20 1 3#12,#12 G 3/4" 20Y 1 4#12,#12 G 3/4"20S 1 2#12,#12 G 3/4"

BAS

C

COIL

SYSTEMS WITH MULTIPLE MOTORS REQUIRE ONE SHUTDOWN RELAY FOR EACH STARTER OR VFD. THERE MAY BE MORE THAN ONE DUCT SMOKE DETECTOR PER SYSTEM, BUT ONLY ONE CONTROL MODULE IS REQUIRED PER MOTOR. SHUTDOWN IS VIA

CONTROL MODULE, NOT VIA DUCT DETECTOR AUX CONTACTS. COORDINATE W/ DIV 23.

UNDER NORMAL CONDITIONS, FA SYSTEM POWERS THE NORMALLY OPEN FA CONTROL MODULE CONTACT TO THE CLOSED

POSITION TO ALLOW NORMAL UNIT CONTROL BY BAS.

UPON ALARM SIGNAL FROM THE FIRE ALARM SYSTEM, THE CONTACTS IN THE FA SYSTEM RELEASES CONTROL MODULE TO OPEN POSITION, CAUSING SHUTDOWN OF ASSOCIATED HVAC EQUIPMENT. HVAC EQUIPMENT SHALL NOT BE OPERABLE UNTIL FA

CONTROL MODULE IS RESET TO NORMAL CLOSED POSITION.

DIVISION 23 SHALL PROVIDE WIRING BETWEEN FA AND BAS CONTROL MODULES AND HVAC EQUIPMENT CONTROLLER (STARTER, VFD, OR INTEGRAL CONTROL PANEL).

FIRE ALARM ADDRESSABLE CONTROL

MODULE INSTALLATION AND FA

CONTROL WIRING BY DIV 28.

LINE/24 VOLT TRANSFORMER

INTEGRAL WITH HVAC UNIT,

STARTER, OR VFD (VARIES

BY UNIT).

H

N

UNIT

LINE

VOLTAGE

MECHANICAL CONTROL RELAY FURNISHED AND

INTERLOCK WIRING WITH MECH EQUIPMENT BY DIV

23. INSTALLATION AND POWER WIRING BY DIV 26.

STARTER CONTROL COIL (OR

EQUIVALENT CONTROLLER

FOR EQUIPMENT)

MECHANICAL EQUIPMENT

24V

SD

SD

FIRE ALARM DUCT SMOKE DETECTOR

PROVIDED BY DIV 23 AND WIRING BY DIV 28.

NOTES:

1. UNDER NORMAL CONDITIONS, DAMPER SHALL OPEN OR CLOSE UPON DIV 23 SIGNAL FROM THE

BAS MECHANICAL CONTROL RELAY.

2. DUCT SMOKE DETECTOR INTEGRAL WITH DAMPER SHALL CLOSE DAMPER AND CLOSE OUTPUT

ALARM RELAY UPON DETECTION OF SMOKE IN SYSTEM.

3. DIV 28 FIRE ALARM MONITOR MODULE SHALL CAUSE FIRE ALARM SYSTEM "TROUBLE" IF

DAMPER DUCT SMOKE DETECTOR GOES TO "ALARM" STATUS.

4. VERIFY DAMPER LOCATIONS AND QUANTITY WITH DIV 23.

120V

H

N

D A

M P

E R

DIV 26 PROVIDE 120V TOGGLE

SWITCH WITH PILOT LIGHT.

LIGHT ON WHEN SWITCH IS ON.

MOUNT ADJACENT TO

DAMPER.

MOTORIZED SMOKE DAMPER

POWER OPEN. SPRING

CLOSED WITH INTEGRAL DUCT

SMOKE DETECTOR.

PROVIDED BY DIV 23, POWER

WIRING BY DIV 26.

OUTPUT

INPUT

DIV 28 PROVIDE AND WIRE FIRE

ALARM ADDRESSABLE MONITOR

MODULE FOR DAMPER DUCT

SMOKE DETECTOR "ALARM"

CONDITION. MOUNT WITHIN 36"

OF SMOKE DAMPER.M

SD

DUCT SMOKE DETECTOR

INTEGRAL WITH DIV 23 DAMPER

SHALL CLOSE DAMPER AND

CLOSE OUTPUT ALARM RELAY

UPON DETECTION OF SMOKE IN

SYSTEM.

C

FA CONTROL RELAY PROVIDED

AND WIRED BY DIV 28 TO OPEN

AND CLOSE DAMPER AS

REQUIRED BY THE FIRE

ALARM/SMOKE MATRIX.

CONTROL COIL

PRESSURE DIFFERENTIAL SWITCH CLOSES ON AIR FLOW

PROVIDE FIRE ALARM

MONITOR FOR DAMPER

POSITION SWITCH

SMOKE FAN PROVIDED BY

DIV 23 AND WIRED BY DIV

PROVIDE FIRE ALARM

MONITOR FOR "VOLTAGE

PRESENT AT DAMPER"

PROVIDE 120V VOLTAGE

SENSING RELAY

A

B

NOTES:

THIS DIAGRAM DOES NOT INDICATE ALL ELEMENT OF THE FAN CONTROLLER, COORDINATE ACTUAL INSTALLATION WIRING WITH

EQUIPMENT PROVIDER

UNDER NORMAL OPERATION, FA SYSTEM HOLDS CONTROL MODULE CONTACT CLOSED TO KEEP FAN OFF.

UNDER NORMAL FAN IS OFF AND OPEN PDS MONITOR SHALL INDICATE "NORMAL". A CLOSED PDS MONITOR SHALL INDICATE "FAULT" CONDITION ON THE SMOKE CONTROL PANEL AS WELL AS "TROUBLE" ON THE FIRE ALARM PANEL

AT ANY TIME, IF FAN POWER IS LOST AS DETERMINED BY FA MONITOR OF VOLTAGE SENSING RELAY, THE SMOKE CONTROL SYSTEM SHALL INDICATE "FAULT" CONDITION FOR THE ASSOCIATED ACU LED AT THE SMOKE CONTROL PANEL, AS WELL AS "TROUBLE" AT THE

FIRE ALARM CONTROL PANEL.

UPON SMOKE CONTROL SYSTEM ACTIVATION SIGNAL FROM THE FIRE ALARM SYSTEM, THE CONTACTS IN THE FA CONTROL MODULE

SHALL CLOSE AND START THE FAN.

VSR

C

PS M

C

PROVIDE FIRE ALARM ADDRESSABLE

CONTROL MODULE FOR FAN

AUTOMATIC START/STOP

M

C

INTEGRAL STARTER/CONTROL

FINISHED FLOOR

WALL/PARTITION CAVITY

2.5" DEEP 2-GANG OUTLET BOX

WITH SINGLE GANG PLASTER RING

WALL/PARTITION FACE

1.25" CONDUIT MINIMUM

SIZE OR AS INDICATED

CONCEALED 6" ABOVE CEILING WITH NYLON

BUSHING AT CABLE TRAY TERMINATION. PROVIDE

FOUR CAT 6a DATA CABLES (2V/2D) AND FOUR

GANG FACEPLATE ON PER OUTLET.

FINISHED CEILING

TO CABLE TRAY

REFER TO LEGEND

FOR CABLING

REQUIREMENTS

FINISHED FLOOR

WALL/PARTITION CAVITY

WALL/PARTITION FACE

1.25" CONDUIT MINIMUM

SIZE OR AS INDICATED

CONCEALED 6" ABOVE CEILING WITH NYLON

BUSHING AT CABLE TRAY TERMINATION.

FINISHED CEILING

TO CABLE TRAY

2.5" DEEP 2-GANG OUTLET BOX

WITH SINGLE GANG PLASTER RING, MOUNTING

HEIGHT PER THE ARCH PLANS AND WITH TWO

CAT 6a DATA CABLES. PROVIDE A DUPLEX

POWER OUTLET ADJACENT

STEEL ENCLOSURE WITH POWDER COAT

FINISH AND SCREW OR HINGED, LOCKABLE)

COVER. (HOFFMAN OR EQUAL). FIELD

VERIFY SIZE (12"x12"x4" SUGGESTED.)

OPERATOR INSTRUCTIONS

NORMAL OPERATION:

KEEP ALL SWITCHES ON "AUTO" POSITION.

SMOKE SYSTEM TEST or MANUAL CONTROL:

TURN ANY SMOKE ZONE CONTROL TO "ON" POSITION. THIS

OPENS SMOKE FAN DAMPERS, ACTIVATES SMOKE FANS AND

SHUTS DOWN ASSOCIATED HVAC UNITS FOR THE ZONE. TURN

CONTROL BACK TO "AUTO" TO RESET.

ROOF TOP MANUAL CONTROL:

TURN ANY CONTROL TO "OFF" POSITION TO SHUT DOWN HVAC

UNIT. TURN CONTROL BACK TO "AUTO" TO RESET.

SMOKE

CONTROL

PANEL

ZONE

CONTROL

ROOF TOP

EQUIPMENT

STATUS

ZONE

CONTROL

ON AUTO OFF

NORM

ON

OFF

FAULT

W

G

R

A

WHITE LED - NORMAL OPERATION

RED LED - SYSTEM IS OFF

WHETHER IN MANUAL OR AUTOMATIC

GREEN LED - SYSTEM IS RUNNING

WHETHER IN MANUAL OR AUTOMATIC

YELLOW/AMBER LED -

EQUIPMENT FAULT

ROOF TOP

EQUIPMENT

AUTO OFF

AUTO

OFF

G

R

RED LED - UNIT IS OFF

GREEN LED - UNIT IS RUNNING

CONTROLLED BY THE BAS

STATUS

ABNORMAL

SWITCH

POSITION

POWER

ON

Y

R

GREEN LED - SYSTEM ON

NORMAL POWER

YELLOW/AMBER LED -

ANY SWITCH NOT IN

"AUTO" POSITION

CAROLINA

HTU

O S

MOSELEY

ARCHITECTS

No. 3983

C E

R T

IF

IC

ATE

OF AUTHO

R

IZ

A T

IO

N

CAROLINA

HTU

O S

PR

OFESSIONAL

E N

G

IN

E E

RLI

C

E N

S E

D

W

ILLIAM

J . CARY ,

JR

.05/01/2605/01/2605/01/2605/01/26

No. 34883

PROJECT NO:

DATE:

A

B

C

D

E

1 2 4 53 6 7 8 9 10

F

G

H

I

J

M O

R R

IS

O

N D

R

IV

E S

U

IT

E

C

H A

R L E

S T

O N

S

C

P H

O N

E

-5

M

S E

L E

Y D

E S

IG

N

S .C

O M

/2

/2

:5

:3

P

M LEGENDS,

ABBREVIATIONS AND

GENERAL NOTES

B E

A U

F O

R T

C O

U N

T Y

B

EA

U

FO

R T

C O

U N

TY

D

ET

EN

TI

O

N C

EN

TE

R G

YM

C

O N

VE

R

SI

O

N

R

IB

A U

T R

O A

D , B

E A

U F

O R

T , S

C

E0.1

P R

O

JE

C T

644482 May 1, 2026

ABBREVIATIONS

1P SINGLE PHASE

3P THREE PHASE

3R WEATHERPROOF (NEMA 3R)

A AMPS

AFF ABOVE FINISHED FLOOR

AL ALUMINUM

ATS AUTOMATIC TRANSFER SWITCH

BFC BELOW FINISHED CEILING

BFG BELOW FINISHED GRADE

BKR BREAKER

C CONDUIT

CATV COMMUNITY ANTENNA TELEVISION (CABLE)

CB CIRCUIT BREAKER

CBL CABLE

CCTV CLOSED CIRCUIT TELEVISION

CKT CIRCUIT

CLG CEILING

CLR CLEAR

CO. COMPANY

COMB COMBINATION

COMM COMMUNICATIONS

CU COPPER

DIA DIAMETER

DISC DISCONNECT

DIV DIVISION

DWG DRAWING

EBH ELECTRIC BASEBOARD HEATER

EC EMPTY CONDUIT

ECS EMERGENCY COMMUNICATIONS STATION

ELEC ELECTRICAL

ELEV ELEVATOR

EPO EMERGENCY POWER OFF

EQ EQUIPMENT

ETR EXISTING TO REMAIN

EWC ELECTRIC WATER COOLER

EX EXISTING

EXT EXTERIOR

FA FIRE ALARM

FAAP FIRE ALARM ANNUNCIATOR PANEL

FACP FIRE ALARM CONTROL PANEL

FAGP FIRE ALARM GRAPHIC PANEL

FAXP FIRE ALARM EXTENDER PANEL

FFSCP FIRE FIGHTER'S SMOKE CONTROL PANEL

FLA FULL LOAD AMPS

FPMR FUSE PER MANUFACTURERS REQUIREMENTS/RECOMMENDATIONS

FPND FUSE PER NAMEPLATE DATA

G GROUND

GE GROUND FAULT PROTECTION FOR EQUIPMENT, 6-50mA PER NEC 427.22 (PROVIDE ACCESSORY FOR

INDICATED BREAKER)

GFCI GROUND FAULT CIRCUIT INTERRUPT

GFP GROUND FAULT PROTECTION FOR PERSONNEL, 4-6mA (PROVIDE ACCESSORY FOR INDICATED

BREAKER)

HKP HOUSEKEEPING PAD

HP HORSEPOWER

HPS HIGH PRESSURE SODIUM

Hz HERTZ

IAW IN ACCORDANCE WITH

IG ISOLATED GROUND

J-BOX JUNCTION BOX

KHFSS KITCHEN HOOD FIRE SUPPRESSION SYSTEM

KHz KILOHERTZ

KVA KILOVOLT AMPS

KW KILOWATTS

KWH KILOWATT HOURS

L LOCKOUT TO PREVENT UNAUTHORIZED SWITCHING (PROVIDE ACCESSORY FOR INDICATED BREAKER)

LC ROUTE CIRCUIT TO LOAD VIA LIGHTING CONTACTOR, REFER TO LC SCHEDULE

LED LIGHT EMITTING DIODE

LTG LIGHTING

LTS LIGHTS

MAX MAXIMUM

MCA MINIMUM CIRCUIT AMPACITY

MCB MAIN CIRCUIT BREAKER

MCC MOTOR CONTROL CENTER

MH METAL HALIDE

MHz MEGAHERTZ

MIN MINIMUM

ML MAINTENANCE LOCK (PROVIDE ACCESSORY FOR INDICATED BREAKER)

MLO MAIN LUG ONLY

MNS MASS NOTIFICATION SYSTEM

MOCP MAXIMUM OVER CURRENT PROTECTION.

MTD MOUNTED

N NEUTRAL

N/C NORMALLY CLOSED

N/O NORMALLY OPEN

NO. NUMBER

OFCI OWNER FURNISHED CONTRACTOR INSTALLED

P PILOT LIGHT (AT THE SWITCH HANDLE)

PBD PANELBOARD

PD PROTECTIVE DEVICE

RCPT RECEPTACLE

REC RECEPTACLE

SEC SECURITY

SPD SURGE PROTECTIVE DEVICE

SPEC. SPECIFICATION(S)

ST SHUNT TRIP, 120V COIL (PROVIDE ACCESSORY FOR INDICATED BREAKER)

SW SWITCH

SWBD SWITCHBOARD

TBB TELECOMMUNICATIONS BONDING BACKBONE

TC TELECOMMUNICATIONS CLOSET

TELECOM TELECOMMUNICATIONS

TGB TELECOMMUNICATIONS GROUNDING BUS BAR

TMGB TELECOMMUNICATIONS MAIN GROUNDING BUS BAR

TYP TYPICAL

UNO UNLESS NOTED (INDICATED) OTHERWISE

V VOLTS

VFD VARIABLE FREQUENCY DRIVE

VIF VERIFY IN FIELD

W WATTS

W/ WITH

WG WIRE GUARD

WP WEATHERPROOF

XFER TRANSFER

XFMR TRANSFORMER

NO SCALE

TELECOMMUNICATIONS OUTLET CONDUIT DETAIL

NO SCALE

FIRE/SMOKE DAMPER & SMOKE DAMPER WIRING DIAGRAM

NO SCALE

FIRE ALARM HVAC UNIT SHUTDOWN WIRING DIAGRAM

NO SCALE

SMOKE CONTROL FAN WIRING DIAGRAM

NO SCALE

TELEVISION OUTLET CONDUIT DETAIL

NO SCALE

SMOKE CONTROL PANEL (SCP)

NO SCALE

ENLARGED CONTROL SWITCHES/INDICATORS

FIRE ALARM / SMOKE CONTROL MATRIX

ACTIVATION DEVICES DAMPER EQUIPMENT

SMOKE DETECTORS DUCT SMOKE DETECTOR SYSTEM ID TAG(S) FLOW SWITCH SYSTEM ID TAG(S) FAN DAMPERS OPEN SMOKE DAMPERS CLOSE ON OFF

SMOKE ZONE D REFER TO PLANS DSD-D1 FS-D1 D-SSF-D1, D-SEF-D1 FSD-D1, FSD-D2, FSD-D3, FSD-D4

SSF-D1, SEF-D1 EX-RTU-2

GENERAL NOTES:

A. DIV 28 SHALL PROVIDE EACH SMOKE SYSTEM FAN WITH FIRE ALARM CONTROL MODULE(S) TO ALLOW 'ON' AND 'OFF' CONTROL.

B. DIV 28 SHALL PROVIDE A MONITOR MODULE FOR THE DIFFERENTIAL PRESSURE SWITCH TO CONFIRM OPERATION. FAILURE SHALL CAUSE SUPERVISE CONDITION FOR DEVICE AND ZONE WHEN IN SMOKE MANAGEMENT MODE.

C. PROVIDE EACH SMOKE SYSTEM FAN AND SMOKE CONTROL DAMPER WITH POWER DISCONNECTING MEANS (DIV 26), VOLTAGE SENSING RELAY (DIV 26), AND TO CONFIRM POWER AVAILABLE. LOSS OF POWER SHALL CAUSE SUPERVISE

CONDITION FOR DEVICE/EQUIPMENT AND SUPERVISE CONDITION FOR DEVICE AND ZONE AT ANY TIME.

D. DIV 28 SHALL PROVIDE EACH CONTROL DAMPER WITH FIRE ALARM CONTROL MODULE, FAIL TO INDICATED POSITION.

E. DIV 23 SHALL PROVIDE EACH CONTROL DAMPER WITH LIMIT SWITCH. DIV 28 SHALL PROVIDE MONITOR MODULE TO CONFIRM POSITION. FAILURE SHALL CAUSE SUPERVISE CONDITION FOR DEVICE AND ZONE WHEN IN SMOKE MANAGEMENT

MODE.

F. DIV 28 SHALL PROVIDE MECH EQUIPMENT IN THE "OFF" COLUMN WITH FIRE ALARM CONTROL MODULE TO SHUT DOWN EQUIPMENT.

G. DIV 26 SHALL PROVIDE MECH EQUIPMENT IN THE "OFF" COLUMN WITH CURRENT SENSING RELAY AT LAST DISCONNECT MEANS, AND FIRE ALARM MONITOR MODULE TO CONFIRM CURRENT IS NOT FLOWING TO EQUIPMENT. PRESENCE OF

CURRENT SHALL CAUSE TROUBLE CONDITION FOR EQUIPMENT AND ZONE DURING SMOKE CONTROL MODE.

H. DIV 28 SHAL PROVIDE A MANUAL OVERRIDE SWITCH IN CENTRAL CONTROL THAT SHALL CAUSE SMOKE CONTROL SYSTEM OPERATION AS INDICATED FOR A SMOKE DETECTOR IN THE AFFECTED ZONE, BUT SHALL NOT CAUSE ALARM

CONDITION TO OCCUR (SUPERVISORY CONDITION SHALL OCCUR IN MANUAL OR OFF MODES).

I. DIV 23 SHALL MEASURE AND RECORD THE PRESSURE DIFFERENCE ACROSS EACH DOOR THAT SEPARATES THE SMOKE ZONE FROM ADJACENT ZONES. ADJUST SMOKE CONTROL FANS AS NECESSARY TO ACHIEVE THE FOLLOWING

PRESSURE DIFFERENTIAL ACROSS THE BOUNDARIES: MIN PRESSURE DIFFERENTIAL: +0.05 IN. W.C. MAX PRESSURE DIFFERENTIAL: +0.08 IN. W.C.

J. DURING SMOKE CONTROL MODE, SMOKE FANS SHALL BE DELAYED 15 SECONDS SO THAT SMOKE CONTROL DAMPERS ARE SUFFICIENTLY OPEN TO PREVENT DEADHEADING OF FANS, TEST THIS OPERATION AND ADJUST DELAY AS

REQUIRED.

K. MOTORIZED SMOKE CONTROL FAN DAMPERS ARE 120V, 2-POSITION.

L. PROVIDE ALL NECESSARY INTERFACE DEVICES AND CONTROLS ON EXISTING EQUIPMENT INDICATED IN THIS MATRIX TO PERFORM FUNCTIONS AS INDICATED.

REVISIONS

DATE DESCRIPTION

PROJECT NO:

DATE:

644482

JULY 16, 2026

REVISIONS

DATE DESCRIPTION

PROJECT NO:

DATE:

644482

JULY 23, 2026

REVISIONS

DATE DESCRIPTION

S

S

S

SS

S B

S B

M

SB

S B

FS TS

M

SD

3K

3K

3K3K

S

S S S

S S S

S

S S S

S S S 3

F

DORM

SHOWER

EC

HC

C

C2

HEC

EX FACP

FSD-D3

FSD-D1

D-SSF-D1

FSD-D2

D-SSF-D4

SSF-D1

SEF-D1

EF-D1

CENTRAL

CONTROL

SMOKE CONTROL

PANEL (SCP). FIELD

LOCATE PER

OWNER DIRECTION.

REFER TO FP DRAWINGS

FOR LOCATION

D-SEF-D1

A1

HC- 11

A1

HC- 11

A3

HEC- 7

A1

HC- 11

A1

HC- 11

A1

HC- 11

A3

HEC- 7

A1

HC- 11

A1

HC- 11

A1

HC- 11

A1

HC- 11

A1

HC- 11

A1

HC- 11

A1

HC- 11

A3

HEC- 7

A1

HC- 11

A1

HC- 11

A1

HC- 11

A1

HC- 11

A3

HEC- 7

A1

HC- 11

D1

HC- 11

D3

HEC- 7

D1

HC- 11

DORM

SHOWER

FIELD LOCATE

PER OWNER

DIRECTION.

CENTRAL

CONTROL

REPRESENTED BY n

GENERAL NOTES

APPLIES TO THIS DRAWING

KEYNOTES

1. DISCONNECT AND REMOVE EXISTING POWER OUTLET AND ENSURE THE CONTINUITY OF

THE EXISTING CIRCUIT. PROVIDE BLANK DETENTION GRADE COVER PLATE, ATTACHED

WITH TAMPER RESISTANT HARDWARE, OVER THE BOX.

2. REMOVE EXISTING ELECTRICAL DEVICE AND REWORK TO LOCATION INDICATED. ENSURE

THE CONTINUITY OF THE EXISTING CIRCUIT (CCT C-17 PER AS-BUILT DRAWINGS).

3. RELOCATE EXISTING ELECTRICAL DEVICE AS INDICATED.

4. RELOCATE EXISTING TV COMM OUTLET AS INDICATED. REWORK POWER TO LOCAL

RECEPTACLE CIRCUIT (CCT C-17 PER AS-BUILT DRAWINGS).

5. POWER THE VIDEO VISIT STATION FROM THE EXISTING 120V CIRCUIT IN THE AREA FREED

BY DEMOLITION (CCT C-19 PER AS-BUILT DRAWINGS) . PROVIDE A CAT 6 A DATA CABLE IN

1" CONDUIT TO CENTRAL CONTROL AND TERMINATE PER OWNER DIRECTION.

6. PROVIDE SMOKE DETECTORS IN THIS SPACE AND CONNECT TO THE EXISTING FIRE ALARM

SYSTEM. ZONE THE DETECTORS TOGETHER FOR CONTROL OF THE SMOKE CONTROL

EQUIPMENT.

7. DISCONNECT AND REMOVE EXISTING LIGHTING FIXTURES IN THIS AREA AND REPLACE

WITH TYPES INDICATED ON THE RENOVATION PLANS. UNO, REWORK TO EXISTING CIRCUIT

AND CONTROLS

8. REMOVE EXISTING LIGHTING CONTROLS. PROVIDE CONTROLS INDICATED AND REWORK

TO LOCATION INDICATED ON THE RENOVATION PLANS.

9. PROVIDE CONDUIT AND BOX TO RELOCATE EXISTING INTERCOM AS INDICATED. MATCH

MOUNTING HEIGHT OF EXISTING. PROVIDE DETECTION GRADE BLANK PLATE OVER ANY

EXISTING TO REMAIN BOX.

10. REWORK CONDUIT AND BOX INTO NEW WALL FOR EXISTING DOOR LOCKS

11. PROVIDE 3/4" CONDUIT AND BOX TO CONTROL ROOM FOR FUTURE CAMERA. MATCH

MOUNTING HEIGHT OF EXISTING CAMERA.

A. REPLACE ALL COMMERCIAL GRADE WALL PLATES WITH DETENTION GRADE PLATES

ATTACHED WITH TAMPER RESISTANT HARDWARE.

B. PROVIDE ADDITIONAL 2-HOLE STRAPPING (DOUBLE THE AMOUNT REQUIRED BY NEC) FOR

ANY EXISTING EXPOSED CONDUIT WITHIN 12' OF THE FLOOR.

C. PROVIDE PROTECTION LOCK COVER OVER EXISTING LIGHTING CONTROLS AND FIRE

ALARM DEVICES.

D. REWORK EXISTING CEILING MOUNTED DEVICES TO REPLACEMENT CEILING AND

RECONNECT.

E. PROVIDE TESTING FOR ANY DEVICE DISCONNECTED AND RECONNECTED

F. REFER TO THE MECHANICAL DRAWINGS FOR THE OPERATIONAL AND SHUT DOWN

SEQUENCE OF THE HVAC EQUIPMENT THAT INTERFACES TO THE FIRE ALARM SYSTEM AND

DEVICES.

G. UPDATE ALL PANEL SCHEDULES

H. ALL INFORMATION PERTAINING TO EXISTING DEVICE AND CIRCUITS IS OBTAINED FROM AS-

BUILT DRAWINGS AND LIMITED FILED INVESTIGATION. FILED VERIFY THE INFORMATION AND

ADJUST AS NEEDED

DORM

SHOWER

1 1 1

CAROLINA

HTU

O S

MOSELEY

ARCHITECTS

No. 3983

C E

R T

IF

IC

ATE

OF AUTHO

R

IZ

A T

IO

N

CAROLINA

HTU

O S

PR

OFESSIONAL

E N

G

IN

E E

RLI

C

E N

S E

D

W

ILLIAM

J . CARY ,

JR

.05/01/2605/01/2605/01/2605/01/26

No. 34883

PROJECT NO:

DATE:

A

B

C

D

E

1 2 4 53 6 7 8 9 10

F

G

H

I

J

M O

R R

IS

O

N D

R

IV

E S

U

IT

E

C

H A

R L E

S T

O N

S

C

P H

O N

E

-5

S E

L E

Y D

E S

IG

N

S .C

O M

/2

/2

:5

:3

P

M FLOOR PLAN AND

DETAILS

B E

A U

F O

R T

C O

U N

T Y

B

EA

U

FO

R T

C O

U N

TY

D

ET

EN

TI

O

N C

EN

TE

R G

YM

C

O N

VE

R

SI

O

N

R

IB

A U

T R

O A

D , B

E A

U F

O R

T , S

C

E2.1

P R

O

JE

C T

644482 May 1, 2026

1/8" = 1'-0"

FLOOR PLAN - ELECTRICAL

1/8" = 1'-0"

FLOOR PLAN -LIGHTING

1/8" = 1'-0"

FLOOR PLAN - ELECTRICAL DEMOLITION

DIV 23 ELECTRICAL CONNECTION SCHEDULE

TAG VOLTAGE

POLES PANEL WIRE DISCONNECTING MEANS REMARKS

D-SEF-D1 120 V 1 C 2#12,#12G,3/4"C. MOTOR RATED SWITCH PROVIDE 20A/1P BREAKER IN SPACE OF PANEL INDICATED FOR ALL DAMPERS

D-SSF-D1 120 V 1 C 2#12,#12G,3/4"C. MOTOR RATED SWITCH PROVIDE 20A/1P BREAKER IN SPACE OF PANEL INDICATED FOR ALL DAMPERS

D-SSF-D4 120 V 1 C 2#12,#12G,3/4"C. MOTOR RATED SWITCH PROVIDE 20A/1P BREAKER IN SPACE OF PANEL INDICATED FOR ALL DAMPERS

EF-D1 120 V 1 C 2#12,#12G,3/4"C. MOTOR RATED SWITCH PROVIDE 20A13P BREAKER IN SPACE OF PANEL INDICATED

FSD-D1 120 V 1 C 2#12,#12G,3/4"C. MOTOR RATED SWITCH PROVIDE 20A/1P BREAKER IN SPACE OF PANEL INDICATED FOR ALL DAMPERS

FSD-D2 120 V 1 C 2#12,#12G,3/4"C. MOTOR RATED SWITCH PROVIDE 20A/1P BREAKER IN SPACE OF PANEL INDICATED FOR ALL DAMPERS

FSD-D3 120 V 1 C 2#12,#12G,3/4"C. MOTOR RATED SWITCH PROVIDE 20A/1P BREAKER IN SPACE OF PANEL INDICATED FOR ALL DAMPERS

SEF-D1 460 V 3 HEC 3#10,#10G,3/4"C 480V.30A,3P,NEMA 3R STARTER PROVIDE 30A/3P BREAKER IN SPACE OF PANEL INDICATED

SSF-D1 460 V 3 HEC 3#12,#12G,3/4"C. 480V.30A,3P,NEMA 3R STARTER PROVIDE 20A/3P BREAKER IN SPACE OF PANEL INDICATED

LIGHT FIXTURE SCHEDULE

TYPE DESCRIPTION MANUFACTURER SERIES NO. VOLTAGE WATTAGE LUMENS TYPE COLOR TEMP. MOUNTING OPTIONS COMMENTS

A1 2X4 VANDAL RESIST LENS LITHONIA 2VRTL ICW AP250FL 277 V 50 5000 lm LED 4000 K RECESSED PROVIDE FLANGE KIT WHEN MOUNTED IN DRYWALL CEILING

A3 2X4 VANDAL RESIST LENS - EM LITHONIA 2VRTL ICW AP250FL 277 V 50 5000 lm LED 4000 K RECESSED HIGH OUTPUT BATTERY PROVIDE FLANGE KIT WHEN MOUNTED IN DRYWALL CEILING

D1 4' MAX SECURITY KENALL SDSA 4 0/0 2/J 1 277 V 45 4500 lm LED 4000 K SURFACE MOUNT WITH TAMPER PROOF HARDWARE

D3 4' MAX SECURITY KENALL SDSA 4 0/0 2/J 1 277 V 45 4500 lm LED 4000 K SURFACE HIGH OUTPUT BATTERY MOUNT WITH TAMPER PROOF HARDWARE

REVISIONS

DATE DESCRIPTION

PROJECT NO:

DATE:

644482

JULY 16, 2026

REVISIONS

DATE DESCRIPTION

PROJECT NO:

DATE:

644482

JULY 23, 2026

GENERAL NOTES

THE CONTRACT DOCUMENTS ARE COMPLEMENTARY AND WHAT IS REQUIRED BY ONE SHALL BE AS BINDING AS IF REQUIRED BY ALL. IN THE CASE OF A CONFLICT, DISAGREEMENT, OR AMBIGUITY, PROVIDE THE BETTER QUALITY. IN THE CASE OF A CONFLICT, DISAGREEMENT, OR AMBIGUITY, PROVIDE THE GREATER QUANTITY

OF WORK.

COORDINATE THE LOCATION OF ALL SPRINKLER PIPING WITH THE WORK OF OTHER TRADES. SPRINKLER PIPING SHALL NOT BE INSTALLED WHERE ITS LOCATION INHIBITS ACCESS TO EQUIPMENT ABOVE THE CEILING, FILTER ACCESS OR INFRINGES UPON CLEARANCES DICTATED BY THE NATIONAL ELECTRIC CODE.

VERIFY DIMENSIONS AND ROUTING IN FIELD BEFORE FABRICATION OF PIPING AND FIXTURES.

REFER TO THE LIFE SAFETY PLAN FOR LOCATIONS OF FIRE AND SMOKE SEPARATIONS ASSEMBLIES AND SMOKE COMPARTMENTS.

REFER TO STRUCTURAL DRAWINGS FOR DETAILS AND MAXIMUM SPACING REQUIREMENTS REGARDING HANGER ATTACHMENTS TO STEEL BAR JOISTS.

ADD/ RELOCATE FIRE SPRINKLERS THROUGHOUT SPACE TO ACCOMMODATE RENOVATED WALLS AND CEILING IN ACCORDANCE WITH 2021…