2025-10-30 Addendum 1~1.pdf
PDF 12 MB Posted
- Attached to
- ITB - Elementary Schools Cooling Project
- Solicitation number
- S-P20052-00015216
- Issued by
- Lane County, Oregon
About this file
This is an Addendum 1 to the Invitation to Bid (ITB) issued by Bethel School District #52 in Lane County, Oregon, for the Irving and Danebo Elementary Schools Cooling Project. The project involves installing new split system direct expansion heat pump systems at two elementary schools, including all necessary refrigerant piping, control/signal wiring, condensate drainage systems, and electrical upgrades with wiring and circuit installation to support the new systems. Testing and commissioning of the new HVAC systems are required as part of the scope. A mandatory pre-bid job walk was scheduled for Wednesday, October 29, 2025, at 1:30 PM, beginning at Irving Elementary School and continuing to Danebo Elementary School. Sealed bids were due by 2:00 PM PST on Tuesday, November 18, 2025, at the Bethel School District Administration Building, with bid documents available beginning Wednesday, October 22, 2025. Bidders must submit a bid bond or certified check equal to 10% of the total bid amount, along with bidder responsibility information, nondiscrimination certifications, and first-tier subcontractor disclosures.
Contractors are restricted to those registered with the Construction Contractors Board or licensed by the State Landscape Contractors Board, with contractors bidding $100,000 or more required to have a $30,000 public works bond filed with the Construction Contractors' Board. The addendum modifies the original ITB terms; specific details regarding pricing adjustments, timeline modifications, or scope changes should be referenced within the addendum document itself. No set-aside designations or disadvantaged enterprise requirements are specified. The district reserves the right to reject any or all bids, waive informalities, or postpone contract award for up to 60 days from the bid opening date. No specific budget range is disclosed in the procurement materials.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Notice of Intent to Award-cooling.pdf | ||
| Addendum 2 IrvingDanebo Cooling Project.pdf | ||
| Attachment J Proposer Checklist.xlsx | XLSX spreadsheet | |
| ITB Irving and Danebo Elementary Cooling Project.pdf | ||
| Bid Opening Minutes.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Proudly serving clients from Springfield, West Linn, and Bend.
HQ: 725 A Street, Springfield OR 97477
SystemsWestEngineers.com
(541) 342-7210
Addendum No. 1, 250051.01 1
Addendum No. 1
Date: October 30, 2025 250051.01
To: Prospective Bidders
From: Systems West Engineers, Inc.
725 A Street Springfield, OR 97477
Project: Bethel School District, Irving ES, and Danebo ES Cooling
Designs
This addendum forms a part of the Contract Documents and modifies the original Bidding Documents dated October 15, 2025, as noted below. Acknowledge receipt of this addendum in the space provided on the Bid Form. Failure to do so may subject the Bidder to disqualification.
General
Pre-bid conference attendance list for meeting attendees on site is attached.
Pre-purchased Danebo ES equipment product submittals and SWE review comments are attached .
PROJECT MANUAL
Section 00 1113 Invitation to Bid: Bidding documents are available at the following link:
https://bethel.k12.or.us/rfp.
Replace section 001113.01 Exhibits to Contract, Exhibit B with that attached to this addendum with revision to Project Name and signing year.
Replace section 001113.01 Exhibits to Contract, Exhibit H with that attached to this addendum with revision to Project Name.
Replace Section 00 4100 Bid Form with that attached to this addendum, revising bid deadline to November 18, 2025.
Drawings
Irving - A101 – Overall Roof Plan: Add sheet A601 to Architectural Sheet Index.
Irving - A601 – Interior Details: Add sheet to project.
Danebo - E101 – Demolition Plan – Admin Building: Add existing electrical gear.
Danebo - E121 – Floor Plan – Admin Building: Add Sheet Note.
Danebo - E122 – Floor Plan – Admin Building: Add Sheet Note.
Danebo - E123 – Floor Plan – Admin Building: Add Sheet Note.
Addendum No. 1, 250051.01 2
Danebo - E611 – Diagrams: Revise reference notes.
Irving - E121 – Floor Plan – Building A: Add Sheet Note.
Irving - E122 – Floor Plan – Building B: Add Sheet Note.
Irving - E123 – Floor Plan – Building C & D: Add Sheet Note.
Irving - E124 – Floor Plan – Building E: Add Sheet Note.
End of Addendum No. 1
Paul E. Fooks, PE
PEF/ejp
Attachments:
Pre-purchase equipment submittal review E00R1 - SWE Submittal Review_2523 Danebo ES Cooling_Submittal #262413-REV 1.1-Switchboards_100625
Pre-bid conference listing of attendees.
Section 001113.01 Exhibits to Contract, Exhibit B section 001113.01 Exhibits to Contract, Exhibit H
Section 00 4100 Bid Form Irving – A101 – Overall Roof Plan
Irving – A601 – Interior Details
Danebo – E101 – Demolition Plan – Admin Building
Danebo – E121 – Floor Plan – Admin Building
Danebo – E122 – Floor Plan – Admin Building
Danebo – E123 – Floor Plan – Admin Building
Danebo – E611 – Diagrams
Irving - E121 – Floor Plan
Irving - E122 – Floor Plan
Irving - E123 – Floor Plan
Irving - E124 – Floor Plan
E
X
P
I
R
E
S : 12
J
A
N
1, RE
GI
STERED PROFESSIONALENGINEER# 59,544
OREGONP
A
U L
E . F O O
K S
725 A Street Springfield, OR 97477 | 550 NW Franklin Blvd., Suite 448 Bend, OR 97703
SystemsWestEngineers.com (541) 342-7210
Submittal Review, <Project #> 1
SUBMITTAL REVIEW
REVIEW IS ONLY FOR GENERAL CONFORMANCE WITH THE DESIGN CONCEPT OF THE PROJECT AND GENERAL COMPLIANCE WITH THE INFORMATION GIVEN IN THE CONTRACT DOCUMENTS. ANY ACTION SHOWN IS SUBJECT TO THE REQUIREMENTS OF THE CONTRACT. CONTRACTOR IS RESPONSIBLE FOR
DIMENSIONS, QUANTITIES, AND COORDINATION.
Project Name: BSD Irving ES and Danebo ES Cooling Addition Design
SWE Project No.: 250051.01
Review Date: 10/9/2025
Reviewed By: JMS
SWE Submittal No.: E00 R1
Contractor Submittal No.: 262413-1.0
Bold Items – Reviewed in this submittal
Gray Items – Previous reviewed submittals
I tem
No.
Act ion
Code
Last
Submitta l
Spec
Sect ion I tem Name Comments
1.
B 26 2413 Switchboard
2N-SWB-S1A
Revise 1000A main breaker to 800A main.
Revise (1) 100A breaker to 150A
-Previous comments have Addressed
Add (4) 100A/3P breakers
2.
A Surge Protection Device
TPS4C0520x2
3.
A Power Meter
PAC3220
ACTION CODES
A No Exceptions Taken
B Make Corrections Noted*
C Revise and Resubmit
D Submittal Not Received
E Incomplete, Not Reviewed
F Rejected
*No exceptions taken and a resubmittal is not required if correction notes are applied.
https://www.systemswestengineers.com/
Project: 2523 Danebo ES Cooling – Early Procurement 1265 Candlelight Drive Eugene, Oregon 97402
Submittal #262413-1.1 - Switchboards 262413 - Switchboards
Revision 1 Submittal Manager
Status Open Date Created Sep 25, 2025
Issue Date Oct 6, 2025 Spec Section 262413 - Switchboards
Responsible Contractor
Received From
Received Date Oct 6, 2025 Submit By Oct 6, 2025
Final Due Date Oct 13, 2025 Lead Time 182 day(s)
Cost Code 30-3000.000 - Service Gear/Panel/Circuit Breakers/Fuses
Location Type Product Information
Submittal Package
Approvers
Ball in Court
Distribution
Description Siemens LOT BOM
1. Switchboard - 2N-SWB-S1A / SB1 208Y/120 1000A
2. SPD - TPS4C0520X2
3. Power Meter - PAC3220
Submittal Workflow
Name Sent Date Due Date Returned Date Response Attachments
General Information Attachments
2523 Danebo ES Cooling_Submittal
#262413-REV 1.1-
Switchboards_092525.pdf
Oct 13, 2025 Pending
Page 1 of 1 Printed On: Oct 6, 2025 08:12 AM PDT
JMS10/9/2025
This review is for general conformance with the design concept for the project and general compliance with the information given in the Contract Documents. Corrections or comments made on the shop drawings during this review do not relieve the contractor from compliance with the requirements of the plans and specifications. Approval of a specific item shall not include approval of an assembly of which the item is a component.
Contractor is responsible for: dimensions to be confirmed and correlated at the jobsite; information that pertains solely to the fabrication processes or the means, methods, techniques, sequences and procedures of construction; coordination of the work of all trades; and for performing all work in a safe and satisfactory manner.
No Exceptions Taken Incomplete, not Reviewed
Make Corrections Noted
Submittal not Received
By:Date:
Revise and Resubmit Rejected
See Attached Comments
Make Corrections Noted
725 A Street Springfield, OR 97477 550 NW Franklin Blvd, Suite 448, Bend, OR 97701
(541) 342-7210 https://app.procore.com/3313927/project/submittal_logs/document_downloader?attachment_id=5735216982&item_id=66390812&item_type=SubmittalLog&project_id=3313927&source=coversheet https://app.procore.com/3313927/project/submittal_logs/document_downloader?attachment_id=5735216982&item_id=66390812&item_type=SubmittalLog&project_id=3313927&source=coversheet https://app.procore.com/3313927/project/submittal_logs/document_downloader?attachment_id=5735216982&item_id=66390812&item_type=SubmittalLog&project_id=3313927&source=coversheet
TABLE OF CONTENTS
DANEBO ES
TYPE CAT# MANUFACTURER
SWITCHBOARD
2N-SWB-S1A SB1 208Y/120 800A SIEMENS
SPD
TPS4C0520X2 SIEMENS
POWER METER
PAC3220 SIEMENS
Siemens Industry, Inc. SPEEDFAX™ 2011 Product Catalog13-2
SW
IT
CH
BO
AR
DS
Distribution Switchboards Type SB1, SB2 and SB3 General
Product Description Siemens modular front connected switchboard design provides a broad range of features and capabilities for a wide range of applications.
Every aspect of design of Siemens switchboards has been aimed at improving layout convenience, reducing installation costs and minimizing the impact and cost of changes to the system.
Siemens switchboards provide a rugged design and the flexibility necessary in electrical systems for all types of applications, some examples are:
▪ Commercial buildings
▪ Industrial plants
▪ Retail chain stores
▪ Health care facilities
▪ Hi-rise complexes
Features & Benefits Features
▪ Up to 6000 ampere main bus rating
▪ Up to 600 volts AC
▪ Bus bracing up to 200KAIC
▪ Tin plated aluminum bus, silver plated copper bus or tin plated copper bus
▪ Bussing can be temperature or density rated
▪ Type 1 and Type 3R enclosures
▪ Main and branch circuit breakers and fusible switches
▪ Thermal magnetic and solid state circuit breakers
▪ Surge protective devices
▪ Customer metering
▪ Utility metering provisions
▪ Ground fault protection on mains and distribution devices
▪ Busway and transformer connections
▪ ACCESS power monitoring on mains and branches
Service Sections
Typical switchboards require one or more service main disconnects that feed one or more distribution sections.
Service sections can be fed from overhead or underground, occasionally underground applications require that a pull section to be added to the switchboard lineup.
Distribution Sections
All switchboard distribution sections can accommodate any combination of panel mounted or individually mounted circuit breakers or fusible switches. This modularity allows future system modifications to be made without adding switchboard sections.
Front Accessibility
All Siemens switchboards are rear aligned and front accessible, enabling switchboards to be placed against a wall, while minimizing floor space requirements. Switchboards are standard rear aligned to minimize floor space requirements but can be front and rear aligned as an option.
Rear Accessibility
Rear access is available as an option for when bus maintenance and cable entry and exit require access to the rear of the switchboard.
Front Connected Distribution Switchboard (Type SB2)
Siemens Industry, Inc. SPEEDFAX™ 2011 Product Catalog 13-3
SW
ITCHBOARDS
Distribution Switchboards Type SB1, SB2 and SB3 General
Front Connected Distribution Switchboard (Type SB2)
Features & Benefits (continued) Protective Devices
Thermal magnetic molded case circuit breakers can be supplied from 15 to 2000 amperes. Solid state (electronic) molded case circuit breakers are available from 30 to 1600 amperes. The solid state trip units provide finite trip setting adjustment, Modbus and Profibus communication along with many other features.
WL insulated case UL489 circuit breakers can be provided from 200 to 5000 amperes with solid state trip units.
For fusible applications, bolted pressure switches, high contact pressure switches and Vacu-Break fusible switches can be supplied.
Power Monitoring
Power monitoring can be accomplished in both service and distribution sections with a wide array of ACCESS power monitoring products. Digital and analog meters can be applied as well as branch circuit monitoring devices for tenant sub-billing or cost allocation applications. See section 9 of the Speedfax for further information on power monitoring devices.
Surge Protective Devices
Siemens surge protective devices can be applied in switchboards to improve the electrical system’s protection, safety and reliability. These devices can be applied in customer metering compartments in main service sections or can be panel mounted in auxiliary compartments in distribution sections. See section 10 of the Speedfax for further information on surge protection devices.
Arc Flash Mitigation
Many arc flash mitigating features can be incorporated into switchboards. The WL breaker can be provided with Dynamic Arc Flash Sentry to allow for safer device settings when personnel are working near the switchboard. Also, breaker shutters, remote racking devices and infrared scanning windows can be supplied to further protect personnel from potential arc flash hazards.
Busway and Transformer Connections
Busway and transformer incoming and outgoing connections can be provided in switchboards. For busway connections to the switchboard, bussing is provided up to where the busway enters the switchboard. Also, a cutout for the busway is provided to allow for quick connection of the switchboard to the busway. For transformer connections, flex connectors are supplied for close coupling the switchboard to the secondary side of the unit substation.
Standards and Certifications
▪ UL891
▪ NEMA PB-2
▪ Seismically qualified
▪ Other equipment is UL listed as applicable
Additional Information For complete application and pricing information contact your local Siemens sales office.
For further information on the product, visit our website at www.usa.siemens.com/switchboards
For detailed configuration information consult the selection and application guide on the website.
Siemens Industry, Inc. SPEEDFAX™ 2011 Product Catalog13-4
SW
IT
CH
BO
AR
DS
Distribution Switchboards Type SB1, SB2 and SB3 General
Individual Product lines SB1 Switchboards
Siemens SB1 switchboards have been specifically designed for the shortest lead times and for applications where floor space is at a premium. The rear of all sections align so the switchboard can be installed against a wall. SB1 switchboards can contain main and branch protective devices and through bus ratings up to 2000 amperes and 600 Volts AC.
SB2 Switchboards
Siemens SB2 switchboards have been designed to be able to incorporate additional features. SB2 switchboards can have extra depth behind the bussing in each distribution section, can be front and rear aligned and can handle up to 4000 amperes and 600 Volts AC. These switchboards may also include insulated case circuit breakers, solid state molded case circuit breakers and density rated bussing.
SB3 Switchboards
Siemens SB3 switchboards are designed for custom options. SB3 switchboards can incorporate custom busway & transformer connections, rear access, all types of utility metering provisions and many other options. No matter your need, Siemens SB3 switchboards can provide a solution.
SB1 Switchboards
Available Features Device Usage Device Type
Ampere Rating Mounting
• Individual or panel mounted mains
• Individual or panel mounted branches
• Thermal magnetic MCCBs
• 2000A maximum main bus
• Front accessible
• Standard utility metering
• Customer metering: digital & analog meters
• 65KAIC interruption rating
• 65C Copper and Aluminum bussing
• Type 1 and 3R enclosures
• Integrated lighting panelboards
Main Molded Case Circuit Breakers (MCCB) Molded Case Circuit Breakers (MCCB) Vacu-Break Switches (VBS) Vacu-Break Switches (VBS) High Contact Pressure Switches (HCP) Bolted Pressure Switches (BPS)
400 - 1200 400 - 2000 400 - 600 800 - 1200 800 - 1200 800 - 2000
Panel Individual Panel Individual Individual Individual
Branch Molded Case Circuit Breakers (MCCB) Molded Case Circuit Breakers (MCCB) Vacu-Break Switches (VBS) Vacu-Break Switches (VBS) High Contact Pressure Switches (HCP) Bolted Pressure Switches (BPS)
400 - 1200 400 - 2000 400 - 600 800 - 1200 800 - 1200 800 - 2000
Panel Individual Panel Individual Individual Individual
SB2 Switchboards
Available Features Device Usage Device Type
Ampere Rating Mounting
• All SB1 options
• 4000A maximum main bus
• Electronic trip unit (solid state) MCCBs
• Density rated copper and aluminum bussing
• 100KAIC interruption rating
• Front and rear aligned
Main All SB1 main devices Bolted Pressure Switches (BPS) WL Insulated Case Circuit Breakers (WL)
Up to 4000 Up to 4000
Individual Individual
Branch All SB1 branch devices Bolted Pressure Switches (BPS)
Up to 4000 Up to 4000
Individual
SB3 Switchboards
Available Features Device Usage Device Type
Ampere Rating Mounting
• All SB1 & SB2 options
• 6000A maximum main bus
• 200KAIC interruption rating
• Rear accessible
• Custom busway connections
• Custom transformer connections
• Custom utility metering
• Additional special options and configurations
Main All SB1 & SB2 main devices Bolted Pressure Switches (BPS)
Up to 6000 Up to 5000
Individual
Branch All SB1 & SB2 branch devices Bolted Pressure Switches (BPS)
Up to 6000 Up to 5000
Individual
Siemens Industry, Inc. SPEEDFAX™ 2011 Product Catalog 13-5
SW
ITCHBOARDS
Integrated Power Systems Switchboards Type IPS General
Product Description Siemens integrated power systems (IPS) switchboards integrate multiple pieces of electrical distribution equipment into a single assembly. The design results in reduced installation time, a reduced footprint and reduced labor risk for installation.
The modular design of the IPS switchboard allows it to be combined with standard service entrance or distribution switchboards if needed. Also, the IPS switchboard can be added to an existing switchboard lineup.
IPS switchboards have a wide range of applications and are commonly used in retail stores, offices, health care facilities and retrofits.
Features & Benefits Features
▪ All standard SB1, SB2 & SB3 switchboard features
▪ Lighting panelboards
▪ Distribution transformers
▪ Half high distribution switchboard chassis
▪ i-3 lighting control
▪ Individually mounted breakers (cable in & cable out)
▪ Auxiliary sections for surge devices, ACCESS power monitoring, contactors, relays, time clocks, motor starters, customer equipment, etc.
Integrated Power Systems Switchboard Commonly Mounted Equipment
Distribution sections
| ▪ | Up to 3000A (full height) |
| ▪ | Up to 1200A (half height) |
Transformers
| ▪ | Up to 300KVA (full height) |
| ▪ | Up to 150KVA (half height) |
Panelboards
| ▪ | Up to 800A (full height) |
| ▪ | Up to 600A (half height) |
Siemens Industry, Inc. SPEEDFAX™ 2011 Product Catalog13-6
SW
IT
CH
BO
AR
DS
Integrated Power Systems Switchboards Type IPS General
Features & Benefits (continued) Reduced Installation Time
IPS switchboards arrive at a jobsite with the components factory installed and wired. The result is significantly reduced installation time. The realized savings on installation result in lower labor costs which drops directly to the bottom line.
Reduced Space Requirements
By integrating components that are typically individually mounted, the IPS switchboard can reduce the space requirements for typical electrical equipment installation by up to 40%. This smaller footprint frees up valuable square footage that can be utilized by the building owner for other profitable uses.
Reduced Installation Risk
IPS switchboards are assembled at Siemens manufacturing plants with meticulous attention to details reinforced with strict testing procedures. This focus on quality ensures that problems encountered with traditional installations such as misinterpretation of drawings or field installation errors are eliminated. Utilizing IPS switchboards eliminates risks, enabling projects to come in on time and on budget.
Standards and Certifications
▪ UL891
▪ NEMA PB-2
▪ Seismically qualified
▪ Mounted panelboards built to UL67 and NEMA PB-1
▪ Other equipment is UL listed as applicable
Additional Information For complete application and pricing information contact your local Siemens sales office.
For further information on the product, visit our website at www.usa.siemens.com/switchboards
For detailed configuration information consult the selection and application guide on the website.
Integrated Power Systems Switchboard Optimized electrical room layout
Panelboard
Transformer Panelboards
Panelboards
Traditional layout
Panelboard Panelboard
Transformer & 2-Panelboards 4-Panelboards
▪ � 50% reduction in required floor space
▪ � 90% reduction in installation time
Integrated power systems layout
Siemens Industry, Inc. SPEEDFAX™ 2011 Product Catalog 13-7
SW
ITCHBOARDS
Commercial Multi-Metering Switchboards Type SMM & MMS General
Product Description Siemens commercial multi-metering switchboards provide utility metering for multiple tenants. The sockets and protective devices are cable connected at the factory making the sockets ready for the installation of the meters.
With the modular design of Siemens switchboards all multi-metering sections can be combined with standard main service or distribution sections.
Multi metering switchboards can be used in many applications, some of the most common are:
▪ Shopping centers
▪ Office buildings
▪ Retail chain stores
Features & Benefits Features
▪ Up to 4000 ampere main bus rating
▪ Up to 600 volts AC
▪ Bus bracing up to 200KAIC
▪ Type 1 and Type 3R enclosures
▪ Standard hot sequence metering with optional cold sequence metering
▪ 100, 200 or 320 ampere meter sockets
▪ Sockets include lever type manual bypass
▪ Ring-less type meter cover design
▪ Type 1 and Type 3R ratings
▪ All other SB1, SB2 & SB3 switchboard features
Individual Product Lines Type SMM
Type SMM switchboards are specifically designed for the west coast and meet all EUSERC requirements.
Type MMS
Type MMS switchboards are designed for non-EUSERC territories and are designed to meet the specific requirements of any local utility.
Standards and Certifications
▪ UL891
▪ NEMA PB-2
▪ Seismically qualified
▪ Other equipment is UL listed as applicable
Additional Information For complete application and pricing information contact your local Siemens sales office.
For further information on the product, visit our website at www.usa.siemens.com/switchboards
For detailed configuration information consult the selection and application guide on the website.
SMM Commercial Multi-Metering Switchboard
Siemens Industry, Inc. SPEEDFAX™ 2011 Product Catalog13-8
SW
IT
CH
BO
AR
DS
Generator Ready Switchboards Type Generator Ready
Product Description
Siemens Generator Ready quick connect switchboards meet the market need for quick connection of a generator for temporary back-up power.
The most common application of these switchboards are retail stores with perishable items, nursing homes & hospitals.
However, these types of switchboards should be applied in any application that is sensitive to power outages.
Features & Benefits
Features
▪ All standard SB1, SB2 & SB3 switchboard features
▪ Crouse-Hinds quick-connect Cam-Loks for a quick primary connection method
▪ Standard mechanical lugs suitable for use with Type W welding cable for a secondary connection method
▪ NEMA 1 and NEMA 3R enclosures
▪ Trap door on NEMA 3R enclosure to maintain rating with cables connected
▪ Labeled phases and ground connections
▪ Bus connection between generator breaker and plug-in quick connects
▪ Mechanical interlocking with normal breaker
▪ Removable screw cover for covering quick-connects when not in use
▪ Stand alone or hard bussed in standard switchboard lineup
Generator Breaker Compartment
The generator breaker can be connected to the normal main switchboard by cable or bus. The generator breaker should be key-interlocked with the main breaker in the normal switchboard lineup. The switchboard can rated Suitable for Service Entrance (SUSE).
Quick-Connect Compartment
The Crouse-Hinds quick-connect Cam-Loks are provided in a compartment with a removable screw cover covering the quick-connects for when they are not in use. In addition to the quick-connects, standard mechanical lugs are provided as a secondary method of connection. The mechanical lugs are rated for Type W welding cable which is common in these generator connection applications.
Outgoing Connection
The outgoing load connection of the generator breaker can be accomplished through either cable connection or can be hard bussed to an existing or new switchboard lineup.
Standards and Certifications
▪ UL891
▪ NEMA PB-2
▪ NEC702
▪ Florida Building Code section 420.4.2.9.7
▪ Seismically qualified
▪ Other equipment is UL listed as applicable
4/0 Crouse-Hinds quick connect Cam-Lok
Generator Ready Switchboard in NEMA 3R Enclosure
Siemens Industry, Inc. SPEEDFAX™ 2011 Product Catalog 13-9
SW
ITCHBOARDS
Generator Ready Switchboards Type Generator Ready
Product Features
2000A main WL generator breaker key interlocked with normal main breaker
2000A of Crouse-Hinds Cam-Loks for a three phase four wire system with ground connections
Hinged NEMA 3R door to maintain NEMA 3R rating with cables connected
Standard mechanical lugs suitable for use with Type W welding cable as a secondary method of connection
Common Application
1 2
Job Name:
Quote #:
Danebo ES SB
Danebo ES SB Rev #4 turnpx00c_08272500_00_04_M00
Quote Name:
Bid Date: 08/27/2025
Siemens Industry, Inc. (Company) agrees to sell to Purchaser and Purchaser agrees to purchase from the Company the goods described below. Written quotations are valid for 30 calendar days from price approval date unless otherwise stated in the quotation. Quotations are subject to change by Siemens Industry, Inc. at any time upon written notice to Purchaser. Estimated Lead times refer to the manufacturing cycles, in working days, at time of quotation and are subject to change.
To: NORTH COAST ELECTRIC COMPANY From:
130 GARFIELD ST
Attention:
Tel. No.:
USA USA
EUGENE, OR 97402-7605
Quote Notes:
Line #: Qty Description
27000 1 2N-SWB-S1A--SB1 SWITCHBOARD - 2 SECTIONS
SB1, Material group 3: VD4, Incoming Location: Bottom, Incoming Position: Left, Service Entrance: Yes, System: 208Y/120 3Ø4W WYE AC, 42,000 A, Bus Bracing:
65,000 A, Bus Material: 65°C Copper, Bus Rating: Non-Tapered, Incoming Bus Amperage: 800 A, Enclosure Rating: 1 - Indoor (Standard).
SECT.1-MAIN
Section Type: Panel Mounted Main Section.
Seismic Qualification1 -
Standard Frame1 -
Section Barrier1 -
Master Nameplate1 -
800 Copper Section Bus1 -
800 Amp Top Thru Bus1 -
500 Kcmil Al/Cu 400-800A Mechanical Lugs1 -
Copper Ground Bus1 -
(1)#6-300MCM Ground Lug1 -
INCOMING LUGS: (3) 500 KCMIL AL/CU MECH1 -
Wire Marker Labels1 -
1 800 A/3P 3VA65-MMAE Main-
Catalog #: 3VA65805HN320AA01 -
800 A 3VA651 -
800 A Sensors1 -
800 A Trip Setting1 -
Model ETU350 Trip Unit LSI1 -
Short Time Trip1 -
Proposal
10/6/2025turnpx00c_08272500_00_04_M00 1
1 AUXILIARY COMPARTMENT-
SPD Surge Counter1 -
Surge Protective Device - 200kA Distribution SPD1 -
US2:TPS4C0520X21 -
1 AUXILIARY COMPARTMENT-
(3) Current Transformers 8001 -
Catalog #: 7KM32200BA011DA01 -
PAC3220 Digital Meter1 -
CT Shorting Block1 -
2 200 A/3P HQR2 Branch Breaker-
Catalog #: HQR23B2001 -
200 A/3P HQR21 -
MCCB Breaker1 -
1 150 A/3P HQR2 Branch Breaker-
Catalog #: HQR23B1501 -
150 A/3P HQR21 -
MCCB Breaker1 -
13 100 A/3P HBL Branch Breaker-
Catalog #: B3100HH1 -
100 A/3P HBL1 -
MCCB Breaker1 -
SECT.2-DISTRIBUTION
Section Type: Distribution Panel.
Seismic Qualification1 -
800 Future Connection (Outgoing)1 -
Standard Frame1 -
600 Copper Section Bus1 -
800 Amp Bottom Thru Bus1 -
Copper Ground Bus1 -
800 Amp Interconnection Components1 -
Proposal
NORTH COAST ELECTRIC COMPANY
turnpx00c turnpx00c_08272500_00_04_M00-27000-1
1 2
Danebo ES SB
2N-SWB-S1A
NORTH COAST ELECTRIC COMPANY
turnpx00c turnpx00c_08272500_00_04_M00-27000-1
1 2
Danebo ES SB
2N-SWB-S1A
HBL 100 A/3
800 A CU
PER Ø & N
BRANCH
N LUGS
PER Ø & N
600 A CU
HBL 100 A/3 HBL100 A/3
HBL 100 A/3 HBL100 A/3
800 A/3 3VA65 LSI
(3)500
HBL 100 A/3 HBL100 A/3
HBL 100 A/3 HBL100 A/3
200 A/3 HQR2 200 A/3 HQR2
HBL 100 A/3 HBL100 A/3
150 A/3 HQR2
HBL 100 A/3 HBL100 A/3
( )#6-300 MCM
GRD LUG(s)
800 A CU
PER Ø & N
BRANCH
N LUGS
PER Ø & N
800 A CU
SECTION
BARRIER
1.25
UNIT
SPACE
UNIT
SPACE
UNIT
SPACE
UNIT
SPACE
UNIT
SPACE
UNIT
SPACE
10.0
10.0
10.0
10.0
10.0
10.0
3.75 K
IT
21#
NEUTRAL5.0
2.5
2.575.0
7.5
7.5
UL
Supply =800 Section =600 Neutral =600
32.00
SECTION# 2
EST. WEIGHT:585.0
1.25
M
10.0 4#
SPD
10.0 3#
3.75 K
IT
8# 9#
3.75 K
IT
10# 11#
8.75
2#
3.75 K
IT
12# 13#
3.75 K
IT
14# 15#
5.0 K
IT
5# 6#
3.75 K
IT
16# 17#
5.0 K
IT
7#
3.75 K
IT
18# 19#
NEUTRAL
7.5
2.5
2.575.0
7.5
7.5
SIEMENS
0.00
10.00"
20.00"
30.00"
40.00"
50.00"
60.00"
70.00"
80.00"
90.00"
SUSE UL
Supply =800 Section =800 Neutral =800
38.00
SECTION# 1
EST. WEIGHT:925.0
RESTRICTED
AREA
17.00
12.00
3.
3.
0026.00
TOP & BOTTOM
CONDUIT
20.00
2.50
2.50
15.00
RESTRICTED
AREA
17.00
12.00
3.
3.
0032.00
TOP & BOTTOM
CONDUIT
20.00
2.50
2.50
15.00
ABBREVIATIONS
'UL' INDICATES THAT THE MARKED SWITCHBOARD SECTION COMPLIES WITH ALL APPLICABLE
UNDERWRITERS LABORATORIES STANDARDS AND IS IDENTIFIED WITH A UL LABEL.
'SUSE' INDICATES THAT THE MARKED SWITCHBOARD SECTION IS SUITABLE ONLY FOR USE
AS SERVICE ENTRANCE EQUIPMENT.
'UNIT SPACE' INDICATES UNOCCUPIED AREA INTENDED FOR FUTURE USE.
'SPD' INDICATES SURGE PROTECTIVE DEVICE
'KIT' INDICATES A BREAKER MOUNTING KIT
'DAS' INDICATES DYNAMIC ARC FLASH SENTRY OR ARC ENERGY REDUCTION MODE WHICH
COMPLIES WITH NEC 240.87
BONDING STRAP
CONCEALED
HINGES
INCOMING
LUGS
LOAD LUGS
BARRIER
NEUTRAL
DISCONNECT
LINK
2.19
4.56
0.50 DIA.
TYPICAL BOLTDOWN
HOLE PROVISION FOR
CUBICLE BOTTOM EACH
SECTION
BARREL LOCK
PROVISION
SEALING DEVICE
STANDARD ACCURACY
HIGH ACCURACY
SEM3 METER w/ PULSE
PROVISION
DEVICE
STANDARD ACCURACY
SEM3 METERS
HIGH ACCURACY
SEM3 METERH
SEM3 METER w/ PULSEPS
PH
NOTES
CONSTRUCTION :SWITCHBOARD IS BUILT AND LABELED PER UL 891 IN EFFECT.
INCOMING :AMPERES: 800
SERVICE :SYSTEM VOLTAGE: 208Y/120 3Ø4W Wye AC
INTERRUPTING :THE SHORT CIRCUIT INTERRUPTING CAPABILITY IS 42,000
RATING :RMS SYMMETRICAL AMPERES AT 208 VOLTS BASED ON THE LOWEST SHORT CIRCUIT
CURRENT RATING OF THE INDIVIDUAL OR SERIES RATED COMBINATION DEVICES INSTALLED
AT TIME OF MANUFACTURE OF BUSSING STRUCTURE. THE BUSSING STRUCTURE IS
CONSTRUCTED TO WITHSTAND FAULTS OF 65,000 RMS SYMMETRICAL AMPERES.
ENCLOSURE :ENCLOSURE IS TYPE NEMA 1 FOR INDOOR APPLICATION.
SEISMIC :ENCLOSURE SHALL BE CONSTRUCTED TO MEET SEISMIC REQUIREMENTS.
EXTERIOR :ANSI 61 LIGHT GREY PAINT.
TERMINATIONS :TERMINATIONS ARE ACCESSIBLE FROM THE FRONT.
BUS BARS :SILVER PLATED COPPER BUS BARS SIZED ON BASIS OF 65°C MAXIMUM
TEMPERATURE RISE.
BUS BARS :THE SWITCHBOARD THROUGH BUS SHALL BE EXTENDED ON THE LAST LOAD SIDE
SECTION TO ALLOW FUTURE SECTION ADDITIONS.
ENCLOSURE :THIS SWITCHBOARD IS PROVIDED WITH SECTION BARRIERS.
NAMEPLATE :NAMEPLATES ATTACHED WITH ADHESIVE.
BUS BARS :THE GROUND BUS IN THIS SWITCHBOARD IS COPPER SIZED PER UL 891 OR
GREATER.
NO. REVISIONS DRAWN DATE
BY:
01 turnpx00c0926259-26-2025
JOB
P.O.
TIE
S.O.
CUST.
ENG. LOC.BY
DATE
APP.
APP.
MFG. LOC.
DWG. FILE
DESIGNATION
DWG. NO.
REV.
SHEETNorcross, Georgia
Siemens Industry, Inc.
9-26-2025
1OF
CONSLTCONTR
JOB
P.O.
TIE
S.O.
CUST.
ENG. LOC.BY
DATE
APP.
APP.
MFG. LOC.
DWG. FILE
DESIGNATION
DWG. NO.
REV.
SHEETNorcross, Georgia
Siemens Industry, Inc.
9-26-2025
1OF
CONSLTCONTR
NORTH COAST ELECTRIC COMPANY
turnpx00c turnpx00c_08272500_00_04_M00-27000-2
2 2
Danebo ES SB
2N-SWB-S1A
NORTH COAST ELECTRIC COMPANY
turnpx00c turnpx00c_08272500_00_04_M00-27000-2
2 2
Danebo ES SB
2N-SWB-S1A
CIRCUIT SCHEDULE
DEVICE TRIP INTERRUPT POLES LOAD LUG SIZE PER PHASE
DESCRIPTION AMPERAGE (A) RATING (AIC)
NUMBER METER
ACC
CT
RATING
_ _ _ _ _1 __
3VA65-MMAE 800 100000 3 _2 __
3VA _ _ _ _3 __
3VA _ _ _ _4 __
HQR2 200 65000 3 (1)#3-300 KCMIL AL/CU MECH5 __
HQR2 200 65000 3 (1)#3-300 KCMIL AL/CU MECH6 __
HQR2 150 65000 3 (1)#3-300 KCMIL AL/CU MECH7 __
HBL 100 65000 3 (1)#2-#1/0AL/(1)#4-#1/0CU MECH8 __
HBL 100 65000 3 (1)#2-#1/0AL/(1)#4-#1/0CU MECH9 __
HBL 100 65000 3 (1)#2-#1/0AL/(1)#4-#1/0CU MECH10 __
HBL 100 65000 3 (1)#2-#1/0AL/(1)#4-#1/0CU MECH11 __
HBL 100 65000 3 (1)#2-#1/0AL/(1)#4-#1/0CU MECH12 __
HBL 100 65000 3 (1)#2-#1/0AL/(1)#4-#1/0CU MECH13 __
HBL 100 65000 3 (1)#2-#1/0AL/(1)#4-#1/0CU MECH14 __
HBL 100 65000 3 (1)#2-#1/0AL/(1)#4-#1/0CU MECH15 __
HBL 100 65000 3 (1)#2-#1/0AL/(1)#4-#1/0CU MECH16 __
HBL 100 65000 3 (1)#2-#1/0AL/(1)#4-#1/0CU MECH17 __
HBL 100 65000 3 (1)#2-#1/0AL/(1)#4-#1/0CU MECH18 __
HBL 100 65000 3 (1)#2-#1/0AL/(1)#4-#1/0CU MECH19 __
_ _ _ _ _20 __
HBL 100 65000 3 (1)#2-#1/0AL/(1)#4-#1/0CU MECH21 __
_ _ _ _ _22 __
JOB
P.O.
TIE
S.O.
CUST.
ENG. LOC.BY
DATE
APP.
APP.
MFG. LOC.
DWG. FILE
DESIGNATION
DWG. NO.
REV.
SHEETNorcross, Georgia
Siemens Industry, Inc.
9-26-2025
1OF
CONSLTCONTR
JOB
P.O.
TIE
S.O.
CUST.
ENG. LOC.BY
DATE
APP.
APP.
MFG. LOC.
DWG. FILE
DESIGNATION
DWG. NO.
REV.
SHEETNorcross, Georgia
Siemens Industry, Inc.
9-26-2025
1OF
CONSLTCONTR
usa.siemens.com/surge
TPS Surge Protection Device Comparison
Voltage Code
| A | = | 120/240 V, 1Ø, 3W |
| B | = | 120/240 V, 3Ø, 4W |
| C | = | 120/208 V, 3Ø, 4W |
| D | = | 240 V, 3Ø, 3W |
| E | = | 277/480 V, 3Ø, 4W |
| F | = | 480 V, 3Ø, 3W |
| G | = | 600 V, 3Ø, 3Wa |
| K | = | 380/220 V, 3Ø, 4W |
| L | = | 600/347 V, 3Ø, 4W |
| S | = | 400/230 V, 3Ø, 4W |
a Available in 100 kA & 150 kA only
Surge Current (kA)
10 = 100 kA per phase 15 = 150 kA per phase 20 = 200 kA per phase 25 = 250 kA per phase 30 = 300 kA per phase
Catalog Number TPS3 05
Example: TPS3C0530X2 =
| Type 2 SPD (Default) for a 208/120V power panel with a surge |
| current capacity of 300 kA per phase and a surge counter. |
When an option is not selected, include a zero (0) in the field.
Options
X = Surge counter (Standard)
| 2 | = | Type 2 SPD (Default) |
| Includes UL 1283 EMI/RFI Filters |
0 = Type 1 SPD (Consult Factory Prior to Ordering)
Catalog Number TPS4 05 X
TPS4 Surge Protection Device
TPS3 Surge Protection Device
Voltage Code Surge Current Rating Options (1 Alpha numeric Character)
A = 240/120V ,1Ø, 3W (Figure 1) 10 = 100kA per phase X = Surge Counter (Standard)
| B = 240/120V, 3Ø, 4W (Figure 3) | 15 = 150kA per phase | |
| C = 208/120V, 3Ø, 4W (Figure 2) | 20 = 200kA per phase | 2 = Type 2 SPD |
| W = 220/127V, 3Ø, 4W (Figure 2) | 25 = 250kA per phase | (Default) Includes UL 1283 EMI/RFI Filter |
| D = 240V, 3Ø, 3W (Figure 4) | 30 = 300kA per phase | 0 = Type 1 SPD |
| E = 480/277V, 3Ø, 4W (Figure 2) | 40 = 400kA per phase | |
| F = 480V, 3Ø, 3W (Figure 4) | 50 = 500kA per phase |
G = 600V, 3Ø, 3W (Figure 4)* K = 380/220V, 3Ø, 4W (Figure 2) L = 600/347V, 3Ø, 4W (Figure 2) S = 400/230V, 3Ø, 4W (Figure 2) T = 415/240V, 3Ø, 4W (Figure 2)
*Not avilable in 300, 400 or 500kA versions
Example: TPS4C0520X2 =
| SPD for a 208/120V panelboard with a surge current capacity of |
| 200kA per phase and Type 2 SPD. |
Voltage Protection Rating
TPS3 TPS4
Voltage Code System Voltage L-N L-G L-L N-G
Voltage Code System Voltage L-N L-G L-L N-G
A 120/240V, 1Ø, 3W 700 700 1200 700 A 120/240V, 1Ø, 3W 700 600 1000 600
B 240/120V, 3Ø, 4W 700/1500 700/1200 1800 700 B 240/120V, 3Ø, 4W 700/900 600/800 1200/1200 600
C 208Y/120V, 3Ø, 4W 700 700 1200 700 C 208Y/120V, 3Ø, 4W 600 500 900 500
W 220/127V, 3Ø, 4W - - - - W 220/127V, 3Ø, 4W 700 600 1000 600
D 240V, 3Ø, 3W - 1200 1500 - D 240V, 3Ø, 3W 900 900
E 480Y/277V, 3Ø, 4W 1200 1200 2000 1200 E 480Y/277V, 3Ø, 4W 1200 1000 1800 1000
F 480V, 3Ø, 3W - 1800 1800 - F 480V, 3Ø, 3W 1800 1800
G 600V, 3Ø, 3W - 2500 2500 - G 600V, 3Ø, 3W 1800 1800
K 380Y/220V, 3Ø, 4W 1500 1200 2500 1200 K 380Y/220V, 3Ø, 4W 1000 900 1800 900
L 600Y/347V, 3Ø, 4W 1500 1500 2500 1500 L 600Y/347V, 3Ø, 4W 1500 1500 2500 1200
S 400Y/230V, 3Ø, 4W 1500 1200 2500 1200 S 400Y/230V, 3Ø, 4W 1000 900 1800 900
T 415Y/240V, 3Ø, 4W - - - - T 415Y/240V, 3Ø, 4W 1000 900 1800 900
Features/Specifications TPS3 TPS4
SCCR 200kA 200kA
I-nominal 20kA 20kA
UL 1449/1283 1449/1283
Modes of Protection (Standard)
L-N, L-G, N-G, L-L L-N, L-G, N-G, L-L
7 discrete modes of protection (L-N x3, L-G x3, N-G) and 3 indirect modes (L-L through N or G)
7 discrete modes of protection (L-N x3, L-G x3, N-G) and 3 indirect modes (L-L through N or G)
Modes of Protection (10 Mode)
L-N, L-G, N-G, L-L L-N, L-G, N-G, L-L
Directly connected discrete protection elements between all possible modes providing true 10 mode protection.
Directly connected discrete protection elements between all possible modes providing true 10 mode protection.
EMI/RFI Filtering Yes Yes
SPD Type 1 & 2 1 & 2
Alarms Yes Yes
Visual Alerts Lights Lights and LCD Screen
Warranty 10 Years 10 Years
Surge Current Rating Standard - 100kA – 300kA Standard - 100kA – 500kA
10 mode – 150kA – 300kA 10 mode – 150kA – 750kA
TPS Family 05 - Power Panels (P4, P5), Switchboard Distribution 05 - Power Panels (P4, P5), Switchboard Distribution
System Voltage
120/240V, 1Ø, 3W 120/240V, 1Ø, 3W
240/120V, 3Ø, 4W 240/120V, 3Ø, 4W
208Y/120V, 3Ø, 4W 208Y/120V, 3Ø, 4W
220/127V, 3Ø, 4W
240V, 3Ø, 3W 240V, 3Ø, 3W
480Y/277V, 3Ø, 4W 480Y/277V, 3Ø, 4W
480V, 3Ø, 3W 480V, 3Ø, 3W
600V, 3Ø, 3W 600V, 3Ø, 3W
380Y/220V, 3Ø, 4W 380Y/220V, 3Ø, 4W
600Y/347V, 3Ø, 4W 600Y/347V, 3Ø, 4W
400Y/230V, 3Ø, 4W 400Y/230V, 3Ø, 4W
415Y/240V, 3Ø, 4W
Siemens Industry, Inc. SPEEDFAX™ Product Catalog 9-1
PO
W
ER
M O
N
ITO
RIN
G
Siemens recognizes that high performance facilities make for high performance business. Energy is the lifeline of your business, and better efficiency and sustainability can have a large positive impact on your bottom line.
Energy Management and Control Systems from Siemens are complete enterprise solutions that help you manage the energy costs and availability of your business.
With our advanced meters and controls, you can be sure to use only the energy you need, when you need it.
Siemens Power Distribution Solutions contribute toward achieving LEED® certification and provides the needed energy metering data for federal/local government energy reductions programs.
Features and Benefits of Siemens Power Distribution Solutions:
n Power Quality Reliability & Analysis n Utilities Cost Allocation & Billing n Utilities Usage Aggregation n Load Preservation n Equipment Monitoring n Facility Monitoring & Automation n Sequence of Event Recording n Preventative Maintenance n Electrical Asset Management
Additional Products/Services n Branch Circuit Monitoring n Sub-Billing and Cost Allocation n Application Engineering n Services Agreements n Network/Communication Components n Integration with Existing n SCADA/BAS Systems n Incorporation of Third Party Devices
For Technical Assistance Contact: 1-800-333-7421
Create Support Ticket Online:
https://support.industry.siemens.com/my/WW/en/requests#createRequest
PDS Request for Information / Request for Quote:
www.usa.siemens.com/pds-request
SEM3T ™ Thermal Monitoring System Selection and Application Guide
New! Thermal Monitoring System – SEM3T
Electrical Power Monitoring Software
Power Meters
Assembled Meter Enclosure
Digital Power & Thermal Monitoring Products SPEEDFAXTM Section� c o n t e n t s Power Distributions Solutions Introduction
| Power Monitoring Systems Overview | 9-2 |
| Intelligent Metering and Control Devices | 9-3 |
Power Meters
| PAC2200 | 9-4 |
| PAC3120 | 9-5 |
| PAC3200T | 9-6 |
| PAC3220 | 9-7 |
| PAC4200 | 9-8 |
| 9410 | 9-9 |
| 9810 | 9-10 – 9-11 |
| Enclosed Meters | 9-12 |
| Branch Circuit Monitoring /SEM3 Embedded Metering | 9-13 – 9-20 |
| Enclosures for External Applications | 9-21 – 9-22 |
| MD Meter – BACnet MSTP/IP standalone meter | 9-23 |
| Low-voltage Current Transformers | 9-24 – 9-25 |
Thermal Monitoring Solution
SEM3T 9-26 – 9-33
Energy Management Software
| Powermanager Software | 9-34 |
| WinPM.Net Software | 9-35 |
Application Engineering
| Digitalization for Smart Infrastructure | 9-36 |
| Services | 9-37 |
Scan to connect online to the most up-to-date version of this Section of
SPEEDFAX.
(Section was last modified on 04/21/21)
Siemens Industry, Inc. SPEEDFAX™ Product Catalog9-2
PO
W
ER
M
O N
IT
O
RI
N
G
Siemens / Speedfax Previous folio: 8-2
1. �Power Meters Siemens power monitors combine the best of new technologies and proven practices. Monitor critical loads, power quality, and demand via the web directly from the meters.
2. �Power Monitoring Software WinPM.Net and Powermanager web-enabled software facilitates easy, enterprise-wide connection to power monitoring equipment, circuit breakers, and other devices from Siemens and third parties.
Access information via the web with unlimited no-cost clients using built-in Web Client via your web browser.
3. �Communications Networks Utilize existing Ethernet or RS-485 communications networks to extract the information you need and get it where it needs to go.
4. �Components Current Transformers (CTs), Voltage/Potential Transformers (PTs), Power Supplies, Ethernet Switches, Protocol Converters. Siemens can provide everything required for your system.
5. �Intelligent I/O Our S7 I/O enables plug-n-play communications with Modbus devices and expands digital and analog input and output functionality of Siemens Systems.
6. �Billing and Load Allocation Software Powermanager is the simplified solution for cost allocation, billing & load/demand analysis using your web browser.
7. �Engineering Services PDS Application Engineers can help from design through commissioning of even the most demanding power quality and monitoring systems.
8. �Motor Control Centers Monitor mains and feeders for critical or power-intensive loads.
Communicate with WL, VL and 3VA breakers, SIMOCODE, I/O and devices from other manufacturers. Use Siemens power meters to web-enable new as well as existing MCCs.
9. �Low- & Medium-Voltage Switchgear Web-enable switchgear by having Siemens power monitoring as well as breaker status and upload the information to a corporate Intranet or to the Internet. Use MeterMailTM directly from meters for alarm conditions or simple reporting.
10. ��Facility Management Systems Tie into building automation systems to provide the required power and energy information. Many communications options are available ranging from legacy protocols to XML directly from the power monitors.
11. �Distributed Control Systems, Automation, and SCADA/Human Machine Interface Siemens power monitors and/or software can talk to all major vendors’ systems.
Totally Integrated Power System Overview General�
Siemens Industry, Inc. SPEEDFAX™ Product Catalog 9-3
PO
W
ER
M O
N
ITO
RIN
G
PAC2200 PAC3120 MD Meter SEM3 PAC3200T PAC3220 PAC4200 9410 9810 Power, Energy and Demand Voltage/current: per phase, average n n n n n n n n n Voltage/current: unbalance n n n n n n n n Power: real(kW), reactive(kVAR), apparent(kVA), power factor, frequency n n n n n n n n n
Energy: bi-directional, import, export n n n n n n n n Energy kWh: total, net n n n n n n n n n Demand: block, sliding window n n n n n n n n n
Demand: thermal predicted n n
Power Quality Analysis Sag(Dip)/Swell disturbances monitoring n n Voltage disturbance direction detection n n High speed transient capture 10MHz Harmonics (individual, even, odd, total) up to THD only THD only THD only 63rd 63rd 63rd Sampling rate, maximum samples/cycle 135k 135k 60 135k 135k 204 256 1024 Flicker, harmonics to EN50160, IEC 6100-4-7 / 4-15 n n Configurable for IEEE 519-2014, SEMI/ITIC n
Data and Waveform Logs Triggered by setpoint, schedule, or external signal n n Sequence-of-event logs or alarm logs, variable log depth n n n n Minimum/maximum logs n n n n n n Onboard Historical logging Memory c c 8GB (6 mos.) c c d 320MB 2GB Email data and event logs n Waveform recording n n Waveform in COMTRADE format with FTP n n GPS time synchronization NTP/SNTP NTP NTP/SNTP NTP/SNTP SNTP NTP/SNTP NTP/SNTP Time-stamps, resolution in seconds ±1 sec 1 min ±1 sec ±1 sec ±0.1 sec. ±0.1 msec. ±0.1 msec.
Time synchronization - IEEE1588/IEC615888/PTP n n
Communication Ports, Protocols and I/O ( ) = Optional USB ports 1 2 (not activated) RS-485-only ports (1) 1 1 1 (1) (1) 1 2 Ethernet ports (1) (1) 1 1 2 1 2 (UTP) 2 (UTP) PROFIBUS ports (1) (1) PROFINET ports (2) (2) Modbus RTU Slave on serial (n) n n n (n) (n) n n Modbus RTU Master on serial ports n n Modbus/TCP on Ethernet ports (n) n n n n n n n Modbus TCP Master over Ethernet n n BACnet MS/TP n BACnet IP on Ethernet ports n n SNMP n n n DNP 3 n n IEC 61850 n n DHCP (n) n n n n n (IP v4/IP v6) n (IP v4/IP v6) RSTP n n Secure protocols (HTTPS, SFTP, SSH, Secure Modbus) HTTPS HTTPS Ethernet Gateway: 31 other meters accessible via RS-485 (n) n n Multiple masters over Ethernet 3 2 4 3 3 3 8 8 On-board web server - Realtime, Trending (n) n (CSV output) n n n n n On-board web server - Waveform display n n Analog inputs (1) (1) (16) (16) Analog outputs (8) (8) Digital status/counter inputs (standard/optional add-ons) 1 2 2/(44) 1 2 / (8) 2 / (8) 3 / (24) 8 / (24) Digital relay outputs (control/pulse) 1 2 1 1 1 2 / (4) 2 / (4) 1 / (8) 4 FA/2RO (8RO)a
Integrated display B/W B/W B/W Opt. Color B/W B/W Color Color
Setpoints, Alarming and Control Setpoints, minimum response time n n n n n n ½ cycle ½ cycle Math, logic, trig, log, linearization formulas and/or, > < Grouping and/or, > < and/or, > < and/or, > < n n Multi-condition alarms n n n n n n Email on alarm n n
Revenue metering ANSI C12.1 accuracy compliant 1.0 n n ANSI C12.20 0.5 0.2 0.2 0.5 0.5 0.2 0.2b 0.2 EN50160 Compliance Reporting n n (Ed4) IEC 61000-4-30 Class A/S n(Class S Meter) n(Class A Ed3) IEC 61577-12 accuracy compliant 1.0 0.5 0.5 0.5 IEC 62053-22 replaces IEC 60687 0.2S compliant n n n n n n n (0.1S) IEC 62053-23, 24 compliant for Reactive Energy accuracy n n n n n (0.25) IEC 62586-1 (new Power Quality standard) n IEC 60687 accuracy class compliant n (1.0) n (0.5) n (0.2) n (0.5) n (0.5) n (0.2) n (0.2) n (0.2) ANSI class 10, IEC 1/10 (1A nominal, 10A max) n n ANSI class 20, IEC 5/20 (5A nominal, 20A max) n n Time-of-use n n n n n n n
Power Distribution Solutions Intelligent Metering and Control Devices
Revised on 04/30/21
| FA - Form A contact output, RO - Relay output. | |
| b | This meter is 0.2S compliant at 5A nominal CT, and 0.5S compliant at 1A nominal CT. |
Some Features are optional, Refer to datasheets for allowable port configurations. Products meet or exceed the accuracy requirements of the standards listed; due to form factors, not all ANSI/IEC compliance tests may apply. Some products certified by third party laboratory.
| c | Load profile kWh/day for 63 days. kWh/month for 24 months. |
| d | Load profile kWh/15min values for 40 days. |
Siemens Industry, Inc. SPEEDFAX™ Product Catalog9-6
PO
W
ER
M
O N
IT
O
RI
N
G
The PAC3200T is a powerful compact din rail mounted power monitoring device that is suitable for use in industrial, government and commercial applications where basic metering and energy monitoring is required. The meter may be used as a standalone device monitoring over 100+ parameters or as part of an industrial control, building automation or global power monitoring system.
Metering and monitoring applications range from simple analog volt and amp meter replacements to stand-alone sub billing or cost allocation installations with multiple tariffs.
The PAC3200T provides open communications using Modbus TCP protocol for easy integration into any local or remote monitoring system. With a built-in web server viewing your data has never been easier. Simple configuration of the meter can be done by using a PC with SENTRON powerconfig setup free software available for download from SIEMENS website.
Reliable and Precise Monitoring of Electrical Power Systems
Precision
| n | ANSI C12.20 Class 0.5s | |
| n | Energy Measurement | |
| • | Voltage +/- 0.5% | |
| • | Current +/- 0.5% | |
| • | Power Factor +/- .5% | |
| • | Sampling Rate 135K/per cycle | |
| • | Total Harmonic Distortion (THD) |
| n | Revenue Accurate | |
| • | Sub Billing | |
| • | Cost Allocation |
n Cost Effective
Energy Management n Serves three masters via the
TCP connection
| n | Energy Consumption |
| n | Automation Integration |
| n | Solution for LEED® credit |
| n | Monitors Critical Equipment |
| n | Modbus TCP/RTU |
Reliability
| n | Economical Measurement | |
| • | Commercial |
• Industrial
• Residential
| n | Degree of Protection | |
| • | Front – IP40 |
• Rear – IP20
| n | 400V Connected Voltage |
| n | Simple Retrofit Installation |
| n | Integration with Existing Systems |
Order information Product Catalog Number
PAC3200T DIN Rail Mount Power Meter without DISPLAY, AC/DC, Modbus TCP, L-L: 400 V, L-N: 230 V, 5 A, wide-range pwr sup. unit AC/DC, screw terminals 7KM32000CA011AA0
Languages included as standard in the meter are English, German, French, Spanish, Italian, Portuguese, Turkish, Russian and Chinese.
Power Distribution Solutions PAC3200T Power Meter
Revised on 04/30/21
| • | DIN rail mount |
| • | Modbus TCP/Ethernet Port available on the |
top right slot
• No Integrated display
Current and Voltage Input wiring screw terminals
Digital Input and Digital Output wiring screw terminals m m
.8 in
71 mm [2.8 in]
108 mm [4.2 in]
Siemens Industry, Inc. SPEEDFAX™ Product Catalog 9-7
PO
W
ER
M O
N
ITO
RIN
G
Siemens / Speedfax Previous folio: 8-5
The PAC3220 is a powerful compact power monitoring device that is suitable for use in industrial, government and commercial applications where basic metering and energy monitoring is required. The meter may be used as a stand alone device monitoring over 100+ parameters or as part of an industrial control, building automation or global power monitoring system. Metering and monitoring applications range from simple analog volt and amp meter replacements to stand-alone sub billing or cost allocation installations with multiple tariffs.
The PAC3220 provides open communications using Modbus RTU/TCP, PROFIBUS-DP, and PROFINET protocols for easy integration into any local or remote monitoring system. With a built-in web server viewing your data has never been easier. Simple configuration of the meter can be done from the front display or by using a PC with SENTRON powerconfig setup free software available for download from SIEMENS website.
Reliable and Precise Monitoring of Electrical Power Systems
Precision
| n | ANSI C12.20 Class 0.5s | |
| n | Energy Measurement | |
| • | Voltage +/- 0.2% | |
| • | Current +/- .2% | |
| • | Power Factor +/- .5% | |
| • | Sampling Rate 135K/per cycle | |
| • | Total Harmonic Distortion (THD) |
| n | Revenue Accurate | |
| • | Sub Billing | |
| • | Cost Allocation |
n Cost Effective
Energy Management n Serves three masters via the
TCP connection
| n | Energy Consumption | |
| n | Automation Integration | |
| n | Solution for LEED® credit | |
| n | Monitors Critical Equipment | |
| n | Modbus TCP/RTU | |
| n | Industrial Systems | |
| • | PROFIBUS |
• PROFINET
Reliability
| n | Economical Measurement | |
| • | Commercial |
• Industrial
• Residential
| n | Degree of Protection | |
| • | Front – IP65 |
• Rear – IP20
| n | 600V Connected Voltage |
| n | Simple Retrofit Installation |
| n | Integration with Existing Systems |
Order information Product Catalog Number
PAC3220 compression terminals (not suitable for use with ring tongue terminals), AC/DC 7KM32200BA011DA0
PAC3220 compression terminals (not suitable for use with ring tongue terminals), DC only 7KM32201BA011EA0
Expansion Module - PAC PROFIBUS DP 7KM93000AB010AA0
Expansion Module - PAC PROFINET 7KM93000AE020AA0
Expansion Module - PAC MODBUS RTU 7KM99000XA000AA0
Expansion Module - I(N), I(Diff), Analog for PAC 3220 or 4200 7KM92000AD000AA0
PAC3220/4200 Meter DIN Rail adapter – Meter display will not be seen 7KM99000YA000AA0
PAC3220/4200 Meter DIN Rail 2-Tier adapter – Meter display will not be seen 7KM99000XA000AA0
Power Supply. Input: 120-230V AC / 110-300V DC Output: 24 V DC 4 Amps. DIN Rail mounted. US2:PWRSP4A
Adapter Plate for 4700/4720 meter cutout 93-47ADAPTER
Languages included as standard in the meter are English, German, French, Spanish, Italian, Portuguese, Turkish, Russian and Chinese.
Power Distribution Solutions PAC3220 Power Meter
Product Category: PDS
Revised on 03/31/20
Full Graphic LCD Display to indicate:
• Display title or designation of the displayed measurements
| • | Phase |
| • | Measured value |
| • | Unit |
| • | Labeling of function keys |
Example of operating menu:
The texts can be displayed in several languages, which can be selected directly on the device. The large graphic LCD display facilitates reading even from a distance. For opti-mum visability even in poor light conditions the PAC3220 comes with a gradually adjustable background illumination.
96 mm [3.78 in.]
Example of Optional Expansion Module install m m
.7 in
SWE#250051.01 001113.01 - 1 Exhibits to Contract Exhibit B
EXHIBIT B
BID BOND
(Here insert full name and address or legal title of Contractor) as Principal, hereinafter called the Principal, and
(Here insert full name and address or legal title of Surety) a Corporation duly organized under the laws of the State of Oregon as Surety, hereinafter called the Surety, are held and firmly bound unto Bethel School District, as Obligee, hereinafter called the Obligee, in the sum of ten percent (10%) of the total amount of the Bid for work herein described, for the payment of which sum well and truly to be made, as agreed and liquidated damages, the said Principal and the said Surety, bind ourselves, our heirs, executors, administrators, successors and assigns, jointly and severally,…