17268 Plans.pdf
PDF 5 MB Posted
- Solicitation number
- S-29100-00017268
- Issued by
- Oregon
About this file
This file comprises architectural and engineering construction plans and specifications for a medical unit renovation project at the Oregon State Correctional Institution located at 3405 Deer Park Road SE in Salem, Oregon. The project, prepared by AC + CO Architecture with consulting engineers from MSC Engineers Inc., Colebreit Engineers, and Axiom Engineers, details a comprehensive remodel of the correctional institution's medical unit including mechanical, electrical, plumbing, and structural work. The scope encompasses demolition and new construction across multiple rooms including exam rooms, offices, a dental area, vestibule, corridor, and stair areas totaling approximately 182,605 square feet of existing building space. The project is classified as Type II-B construction, unsprinkled, with I-3 occupancy for a prison medical unit. Key architectural work includes new floor plans, reflected ceiling plans, door and frame specifications, window installations, and finishes. The mechanical scope includes new HVAC equipment including heat pumps and fan coils, new ductwork and piping systems, and equipment connections. Electrical work comprises new lighting with LED fixtures, power distribution panels, branch circuits, receptacles, occupancy sensors, exit signs with emergency lighting, and fire alarm system integration. A $10,000 contingency allowance is included for detention door, frame, and hardware changes beyond what is shown and specified.
The project documents establish construction standards requiring compliance with the 2025 Oregon Structural Specialty Code, 2025 Oregon Mechanical Specialty Code, 2023 Oregon Plumbing Specialty Code, 2025 Oregon Energy Efficiency Specialty Code, 2025 Oregon Electrical Specialty Code, and 2022 Oregon Fire Code. Specific design details address fire-rated wall and ceiling construction, asbestos abatement coordination, seismic restraint requirements for mechanical equipment, testing and balancing of HVAC systems, and commissioning requirements. The project owner is the Oregon State Correctional Institution with Terry Bergamo identified as the contact. The design team contact is Blake Bural, AIA at AC + CO Architecture. The plans are dated June 16, 2026 with revision notation of March 20, 2026 for electrical and mechanical sheets. All materials and equipment are specified as new unless otherwise noted, with substitution requests requiring engineer approval after contract award. The contractor is responsible for field verification of existing dimensions, disconnection and reconnection of all necessary systems, and coordination with multiple mechanical, electrical, fire alarm, security, and telecom systems serving the facility.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Med Basement enterance.jpeg | JPEG file | |
| Med Dental hall.jpeg | JPEG file | |
| Med Dental.jpeg | JPEG file | |
| Med Corridor.jpeg | JPEG file | |
| Med Dental Door.jpeg | JPEG file | |
| Med Basement Panel.jpeg | JPEG file | |
| Med Basement Panel Wall.jpeg | JPEG file | |
| 17268 ITB TCs.pdf | ||
| Med Basement Door.jpeg | JPEG file | |
| Med Basement enterance1.jpeg | JPEG file | |
| Med North Office area.jpeg | JPEG file | |
| Med Basement Stair up.jpeg | JPEG file | |
| Med Corridor1.jpeg | JPEG file | |
| Med Basement Panel area 2.jpeg | JPEG file | |
| Med Office1.jpeg | JPEG file | |
| Med Basement Panel area.jpeg | JPEG file | |
| 17268 Scope Specs.pdf | ||
| Med Basement Panel area1.jpeg | JPEG file | |
| Med Enterance.jpeg | JPEG file | |
| Med Basement Panel Floor.jpeg | JPEG file | |
| Med Enterance1.jpeg | JPEG file | |
| Med Door.jpeg | JPEG file | |
| 17268 Plan Holder List.pdf | ||
| Med Office.jpeg | JPEG file | |
| Med Office2.jpeg | JPEG file | |
| Med Basement south of Panel.jpeg | JPEG file | |
| 17268 ADDENDA 1.pdf |
Show all 27
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
A0.0
CJA
SHEET INDEXVICINITY MAPDESIGN TEAM
2025.0018
JUNE 16, 2026
3405 DEER PARK DR SE
SALEM, OREGON 97310
OREGON STATE
CORRECTIONAL
INSTITUTION
MEDICAL UNIT RENOVATION
3405 DEER PARK ROAD SE
SALEM, OREGON
A0.0 COVER SHEET
A2.1 FLOOR PLAN - DEMOLITION AND NEW
A6.1 REFLECTED CEILING PLAN - DEMOLITION AND NEW
A8.1 DOOR, FRAME & WINDOW TYPES AND DETAILS
A9.1 SCHEDULES AND SAFETY ZONE PLAN
ARCHITECTURAL
TYPES OF CONSTRUCTION (CHAPTER 6)
USE AND OCCUPANCY CLASSIFICATION (CHAPTER 3)
I-3 OCCUPANCY, CONDITION 5: PRISON
MEDICAL UNITB OCCUPANCY:
CODE ANALYSIS
SYMBOL LEGEND
OCCUPANCY CLASSIFICATION
OCCUPANTS
SQUARE FOOTAGE OF AREA
OCCUPANT LOAD FACTOR
REQUIRED EXIT
EXIT
ROOM
B
MECHANICAL
OREGON STATE
bbural@accoac.com
ATTN: BLAKE BURAL, AIA
FAX 503-581-3655
PH. 503-581-4114
SALEM, OREGON 97302
1100 LIBERTY STREET SE
AC + CO ARCHITECTURE | COMMUNITY
ARCHITECT
SUITE 200
OWNER
OREGON STATE CORRECTIONAL INSTITUTION
3405 DEER PARK RD SE
SALEM, OREGON 97310
ATTN: TERRY BERGAMO
Terry.J.BERGAMO@doc.oregon.gov
CORRECTIONAL INSTITUTION
PROJECT
MEDICAL UNIT RENOVATION
ELECTRICAL AND MECHANICAL
PROJECT
AERIAL VIEW
M001 LEGEND
M002 GENERAL NOTES AND SPECIFICATIONS
M003 SCHEDULES AND DETAILS
M201 MECHANICAL PLAN - DEMOLITION AND NEW
SECT. 308.4.5
SECT. 304.1
CONSTRUCTION TYPE: II-B, UNSPRINKLED TABLE 601
BUILDING ELEMENTS:
STRUCTURAL FRAME: 0-HR TABLE 601
EXTERIOR BEARING WALL: 0-HR (NON-COMBUSTIBLE) TABLE 601
INTERIOR BEARING WALL: 0-HR TABLE 601
EXTERIOR NON-BEARING WALL: 0-HR (NON-COMBUSTIBLE) TABLE 601
x < 5'-0" = 1-HR TABLE 705.5 5 ≤ x < 10'-0" = 1-HR TABLE 705.5 10'-0" ≤ x < 30'-0" = 0-HR TABLE 705.5 x ≥ 30'-0" 0-HR (ALL SIDES) TABLE 705.5
INTERIOR NON-BEARING WALL 0-HR TABLE 601
FLOOR, INCLUDING BEAMS 0-HR TABLE 601
ROOF, INCLUDING BEAMS 0-HR TABLE 601
ALLOWABLE MATERIALS TYPE I & II CONSTRUCTION: SECT. 603.1
INTERIOR WOOD: FIRE RETARDANT SHEATHING
REQUIRED AND NOTED
AREA NOT
IN SCOPE
AREA
B
DENTAL
OFFICE
B
OFFICE
B
OFFICE
B
OFFICE
B
EXITEXIT
EXIT D
ISTAN
C E = 45'-5" < 100', C O
M
PLIES FO
R
SIN
G
LE EXIT
DN
UP
VESTIBULE
B
CORRIDOR
EXTERIOR
SCALE:1
FLOOR PLAN - CODE ANALYSIS
1/8" = 1'-0"
SCALE:
KEY PLAN
FIRE-RESISTANCE-RATED CONSTRUCTION (CHAPTER 7)
OCCUPANT LOAD: 10 OCCUPANTS
EGRESS WIDTH (DOOR):
REQUIRED: 10 OCC x (0.2) = 2" SECT. 1005.3.2
EXISTING: 78" > 2" REQ., COMPLIES
SPACES WITH ONE EXIT B OCC, 49 OCC MAX TABLE 1006.2.1
I-3 OCC, 10 OCC MAX
COMMON PATH B OCC 100 FT MAX TABLE 1006.2.1
I-3 OCC 100 FT MAX
EGRESS ILLUMINATION: REQUIRED SECT. 1008.1
EXIT TRAVEL DISTANCE TABLE 1017.2
B OCC, SPRINKLED 300 FT MAX, COMPILES
I-3 OCC, SPRINKLED 200 FT MAX, COMPILES
CORRIDOR: 1-HR RATED, COMPLIES TABLE 1020.2
AUTOMATIC SPRINKLER SYSTEMS:
GROUP I REQUIRED THROUGHOUT BUILDINGS SECT. 903.2.6
WITH A GROUP I FIRE AREA, COMPLIES
FIRE ALARM AND SMOKE DETECTION SYSTEMS: GROUP I-3 REQUIRED TO HAVE MANUAL SECT. 907.2.6.3
FIRE ALARM SYSTEM AND AUTOMATIC SMOKE
DETECTION SYSTEM TO ALERT STAFF
FIRE PROTECTION AND LIFE SAFETY SYSTEMS (CHAPTER 9)
EXTERIOR WALLS, PROJECTIONS: TABLE 705.2
0-2 FT NOT PERMITTED
2-3 FT 24 INCHES
3-5 FT 2
3 OF FSD
5 FT + 40 INCHES
FIRE RATING: GREATER THAN 10 FEET, RATED ONLY FROM INTERIOR SECT. 705.5
MEANS OF EGRESS (CHAPTER 10)
PH. 503-399-1399
SALEM, OREGON 97301
3470 PIPEBEND PL NE
MSC ENGINEERS INC.
STRUCTURAL
SUITE 120
ATTN: CAM CARROLL
camc@mscengineersinc.com
ELECTRICAL
E001 LEGEND AND GENERAL NOTES
E001.2 SPECIFICATIONS
E002 SCHEDULES
E201 LIGHTING PLAN - DEMOLITION AND NEW
E301 POWER PLAN - DEMOLITION AND NEW
E801 DETAILS
STRUCTURAL
S0.1 GENERAL NOTES
S1.1 FLOOR PLAN - DEMOLITION
S2.1 FLOOR PLAN - NEW
S5.1 DETAILS
COLEBREIT ENGINEERS+AXIOM ENGINEERS
1220 NW KINGS BOULEVARD
CORVALLIS, OREGON 97330
PH: 541.728.3293
CONTACT: ROB JAMES, PE
Rob.James@colebreit.com
ADA
ADA
AREA OF WORK
GENERAL BUILDING HEIGHTS AND AREAS (CHAPTER 5)
EXISTING BUILDING AREA: 182,605 SF (PER MARION COUNTY ASSESSOR)
II-B, UNSPRINKLED CONSTRUCTION TYPE:
FIRE-RESISTANCE-RATED CONSTRUCTION CONT. (CHAPTER 7)
WALL OPENINGS: TABLE 705.8
0-3 FT UP, S - NOT PERMITTED
3-5 FT UP, S - 15%
5-10 FT UP, S - 25%
10-15 FT UP, S - 45%
15-20 FT UP, S - 75%
20-25 FT UP, S - NO LIMIT
25-30 FT UP, S - NO LIMIT
30 FT + UP, S - NO LIMIT (ALL SIDES)
FIRE PARTITIONS: 1-HR RATED, SEE CHAPTER 10 ANALYSIS SECT. 708.1(3)
DOOR OPENINGS: 20 MIN TABLE 716.1(2)
1-HOUR RATED CORRIDOR
ALLOWANCE:
CONTINGENCY ALLOWANCE: INCLUDE THE STIPULATED SUM/PRICE OF $10,000 FOR USE UPON OWNERS INSTRUCTIONS INTENDED USE IS TO COVER CHANGES TO DETENTION DOOR, FRAME, AND HARDWARE BEYOND WHAT HAS BEEN SHOWN AND SPECIFIED. SEE DRAWINGS FOR DOOR SCHEDULE AND SECTION 083460 - DETENTION CENTER DOORS AND FRAMES. ALLOWANCE TO BE CARRIED AND
INCLUDED IN BASE BID AMOUNT
AutoCAD SHX Text
SHEET
AutoCAD SHX Text
DRAWN
AutoCAD SHX Text
REVISIONS
AutoCAD SHX Text
JOB NO.
AutoCAD SHX Text
DATE
AutoCAD SHX Text In the event conflicts are discovered between the original signed and sealed documents prepared by the Architects and/or their Consultants, and any copy of the documents transmitted by mail, fax, electronically or otherwise, the original signed and sealed documents shall govern.
AutoCAD SHX Text
ARCHITECTURERCHITECTURECHITECTUREHITECTUREITECTURETECTUREECTURECTURETUREUREREE
AutoCAD SHX Text
COMMUNITYOMMUNITYMMUNITYMUNITYUNITYNITYITYTYY
AutoCAD SHX Text 1100 Liberty St, SE, Suite 200 Salem, OR 97302 P: 503.581.4114 www.accoac.com
AutoCAD SHX Text O
AutoCAD SHX Text
SALEM, OREGON
AutoCAD SHX Text T
AutoCAD SHX Text A
AutoCAD SHX Text S
AutoCAD SHX Text T
AutoCAD SHX Text E
AutoCAD SHX Text R
AutoCAD SHX Text E
AutoCAD SHX Text F
AutoCAD SHX Text O
AutoCAD SHX Text G
AutoCAD SHX Text O
AutoCAD SHX Text N
AutoCAD SHX Text E
AutoCAD SHX Text C
AutoCAD SHX Text T
AutoCAD SHX Text D
AutoCAD SHX Text T
AutoCAD SHX Text E
AutoCAD SHX Text R
AutoCAD SHX Text E
AutoCAD SHX Text S
AutoCAD SHX Text R
AutoCAD SHX Text E
AutoCAD SHX Text G
AutoCAD SHX Text I
AutoCAD SHX Text A
AutoCAD SHX Text R
AutoCAD SHX Text C
AutoCAD SHX Text H
AutoCAD SHX Text I
AutoCAD SHX Text T
AutoCAD SHX Text
BLAKE BURAL
AutoCAD SHX Text kirtleyr Cross-Out
2025.0018
JUNE 16, 2026
3405 DEER PARK DR SE
SALEM, OREGON 97310
OREGON STATE
CORRECTIONAL
INSTITUTION
MEDICAL UNIT RENOVATION
CJA
A2.1
SCALE:1
FLOOR PLAN - DEMOLITION
1/8" = 1'-0"
80'-0"
'-8
80'-0"
25'-8"
'-8
26'-5" 27'-11"
4'-0" 2'-8" 2'-8"
1'-2"
3'-4"21'-2"
5' -5
26'-5"
8'-9"
1'-3"
9'-0"
2'-9"
4'-8"
27'-11"25'-8"
GENERAL NOTES:
1. GENERAL NOTES APPLY TO ALL DRAWINGS.
2. DIMENSIONS ARE TO EXISTING FACE OF WALL, FACE OF NEW FRAMING, AND FACE OF
EXISTING CONCRETE UNLESS NOTED OTHERWISE.
3. DIMENSIONS OF EXISTING CONDITIONS ARE APPROXIMATE AND INTENDED FOR
ESTIMATING PURPOSES ONLY. CONTRACTOR SHALL BE RESPONSIBLE TO FIELD
VERIFY ALL DIMENSIONS PRIOR TO ACTUAL CONSTRUCTION. NOTIFY OWNER
IMMEDIATELY OF ANY DISCREPANCIES OR QUESTIONABLE DIMENSIONS PRIOR TO
PROCEEDING WITH AREA OF WORK IN QUESTION.
4. DRAWINGS ARE DIAGRAMMATIC ONLY AND SHOULD NOT BE SCALED.
5. IN CASE OF ANY CONFLICTS IN THE REQUIREMENTS OF THE CONTRACT DOCUMENTS,
THE CONTRACTOR IS REQUIRED TO INCLUDE THE BETTER QUALITY AND LARGER
QUANTITY OF THE WORK.
6. CONTRACTOR AND BIDDERS SHALL USE COMPLETE SETS OF CONTRACT DOCUMENTS;
NEITHER THE OWNER NOR ARCHITECT ASSUMES RESPONSIBILITY FOR ERRORS OR
MISINTERPRETATIONS RESULTING FROM THE USE OF INCOMPLETE SETS OF
CONTRACT DOCUMENTS.
REFERENCE NOTES:
1 NO WORK THIS ROOM / AREA
EXISTING WINDOW TO BE REMOVED
A. ~3'-6"x~4'-0" STEEL WINDOW B. ~3'-6"x~5'-0" WOOD WINDOW
EXISTING WINDOW TO REMAIN, PROTECT AT ALL TIMES, PREP AND PAINT
EXISTING CASEWORK AND SHELVING TO BE REMOVED THIS ROOM/AREA
EXISTING FLOORING AND BASE TO BE REMOVED THIS ROOM/AREA, PREP FOR NEW FINISH
A. VCT TILE
NOTE: ASBESTOS PRESENT IN TILE AND MASTIC ON CONCRETE, REFER
TO ASBESTOS REPORT
B. CARPET OVER VCT TILE
NOTE: ASBESTOS PRESENT IN TILE AND MASTIC ON CONCRETE, REFER
TO ASBESTOS REPORT
EXISTING DRINKING FOUNTAIN TO BE REMOVED, REFER TO PLUMBING DESIGN/BUILD
DRAWINGS
EXISTING STEEL BENCHES TO BE REMOVED
EXISTING DOOR AND HARDWARE TO BE REMOVED, EXISTING FRAME TO REMAIN
NOT USED
NEW POLISHED CONCRETE FLOOR AND RUBBER BASE THIS ROOM/AREA
NEW MECHANICAL EQUIPMENT ON AT-GRADE CONCRETE PAD, ALL PIPING
EXPOSED ON EXTERIOR TO BE COVERED WITH STAINLESS STEEL SHROUD,
REFER TO MECHANICAL DRAWINGS
EXISTING MECHANICAL EQUIPMENT TO BE REMOVED. AT SIM CONDITION
PROVIDE NEW SHEET METAL COVER IN AREA OF EQUIPMENT REMOVAL ~12"x36"
NEW DOOR INFILL ~3'-4"x7'-2"
EXISTING SWINGING STEEL SECURITY GRILLE TO BE REMOVED
A8.1
A8.1
A8.1
SYMBOL LEGEND:
EXISTING WALL TO REMAIN
EXISTING DOOR, FRAME AND HARDWARE TO REMAIN
NEW 6" METAL STUDS AT 16" o.c. WITH ACOUSTICAL BATT
INSULATION, 12" FIRE RETARDANT PLYWOOD, AND TYPE 'X'
GYPSUM WALLBOARD EACH SIDE
EXISTING FRAMED WALL TO BE REMOVED, PATCH AND REPAIR
EXISTING ADJACENT FINISHES AS REQUIRED
(E)
NEW CMU INFILL WALL. PROVIDE FLUSH AND SMOOTH
TRANSITION, ANCHOR PER STRUCTURAL
X NEW WINDOW, REFER TO
A8.1
0 NEW DOOR, FRAME AND/OR HARDWARE, REFER TO DOOR
SCHEDULE
EXISTING DOOR, FRAME AND HARDWARE TO BE REMOVED(D)
EXISTING CONCRETE WALL TO BE REMOVED, PATCH AND REPAIR
EXISTING ADJACENT FINISHES AS REQUIRED, REFER TO
STRUCTURAL DRAWINGS
A2.1
1 1
(E)
(D)
(D)
(E)(E)
(E)
SCALE:2
FLOOR PLAN
1/8" = 1'-0"
80'-0"
'-8
80'-0"
25'-8"
'-8
26'-5" 27'-11"
26'-5" 27'-11"25'-8"
17'-8" 8'-9"
8'-9"17'-8"
7' -1
DN
UP
(E)
(E)
(E)(E)
(E)
CL
7' -7
EXAM
ROOM
OFFICE
OFFICE
DENTAL
AREA
OFFICE
OFFICE
VESTIBULE
103-A
103-B 103-C
A
A
1 1
3' -7
3'
-7
CL
SCALE:
KEY PLAN
3' -8
9'
-0
3' -7
EXTEND WALL TO UNDERSIDE OF FLOOR
STRUCTURE
SCALE:
WALL SECTION
3 1 1/2" = 1'-0" 25018-A2.1-03
NEW DEFLECTION CLIP
1 2"
LINE OF EXISTING FLOOR TO REMAIN
NEW RUBBER BASE, TYP.
NEW 5 8" TYPE 'X' GYPSUM BOARD
EACH SIDE
NEW 3" ACOUSTICAL BATT INSULATION
CONTINUOUS SEALANT, TYP
NEW METAL STUD WALL PER PLAN
NEW 12" FIRE RETARDANT PLYWOOD
SHEATHING ONE SIDE
2B
2B
2B
2A
5B
3 3 12 3 3
4 7 7
5A
5A
A2.1
HALL
CORRIDOR
SCALE:4
INTERIOR ELEVATION - DEMOLITION
1/4" = 1'-0"
F.F.E.
0'-0"
7'-2"
B.O. CEILING
EXST
NOTE: ASBESTOS PRESENT IN HIGHLIGHTED
AREA, REFER TO ASBESTOS REPORT
EXISTING WALL FINISH TO REMAIN
3 3 3 3
3 3
13'-11"
A8.1
A2.1
2'-8"
ITEM ITEM BRAND NOTES
1 SIX DRAWER MEDSTATION WITH 5
SECURE DRAWERS BD PYXIS OFCI
EQUIPMENT SCHEDULE - PROJECT NO. 2025.0018
BD PYXIS
BD PYXIS
SEVEN DRAWER AUXILIARY WITH 6
SECURE DRAWERS
ES REFRIGERATOR - 13 CU FT
SCALE:5
INTERIOR ELEVATION
1/4" = 1'-0"
F.F.E.
0'-0"
B.O. CEILING
EXST
1 1
DN
UP
6"
SIM
SIM
123 3 3 3
33333
3 3
EXISTING
STAIR
EXISTING WALL TO REMAIN, PREP AND PAINT
NOTE: ASBESTOS PRESENT IN HIGHLIGHTED AREA,
REFER TO ASBESTOS REPORT, PREP AND PAINT
NOTE: ASBESTOS PRESENT ON OPPOSITE
SIDE OF WALL
A8.1
(E)
OFCI
OFCI
AutoCAD SHX Text
SHEET
AutoCAD SHX Text
DRAWN
AutoCAD SHX Text
REVISIONS
AutoCAD SHX Text
JOB NO.
AutoCAD SHX Text
DATE
AutoCAD SHX Text In the event conflicts are discovered between the original signed and sealed documents prepared by the Architects and/or their Consultants, and any copy of the documents transmitted by mail, fax, electronically or otherwise, the original signed and sealed documents shall govern.
AutoCAD SHX Text
ARCHITECTURERCHITECTURECHITECTUREHITECTUREITECTURETECTUREECTURECTURETUREUREREE
AutoCAD SHX Text
COMMUNITYOMMUNITYMMUNITYMUNITYUNITYNITYITYTYY
AutoCAD SHX Text 1100 Liberty St, SE, Suite 200 Salem, OR 97302 P: 503.581.4114 www.accoac.com
AutoCAD SHX Text O
AutoCAD SHX Text
SALEM, OREGON
AutoCAD SHX Text T
AutoCAD SHX Text A
AutoCAD SHX Text S
AutoCAD SHX Text T
AutoCAD SHX Text E
AutoCAD SHX Text R
AutoCAD SHX Text E
AutoCAD SHX Text F
AutoCAD SHX Text O
AutoCAD SHX Text G
AutoCAD SHX Text O
AutoCAD SHX Text N
AutoCAD SHX Text E
AutoCAD SHX Text C
AutoCAD SHX Text T
AutoCAD SHX Text D
AutoCAD SHX Text T
AutoCAD SHX Text E
AutoCAD SHX Text R
AutoCAD SHX Text E
AutoCAD SHX Text S
AutoCAD SHX Text R
AutoCAD SHX Text E
AutoCAD SHX Text G
AutoCAD SHX Text I
AutoCAD SHX Text A
AutoCAD SHX Text R
AutoCAD SHX Text C
AutoCAD SHX Text H
AutoCAD SHX Text I
AutoCAD SHX Text T
AutoCAD SHX Text
BLAKE BURAL
AutoCAD SHX Text
2025.0018
JUNE 16, 2026
3405 DEER PARK DR SE
SALEM, OREGON 97310
OREGON STATE
CORRECTIONAL
INSTITUTION
MEDICAL UNIT RENOVATION
CJA
A6.1
SCALE:1
REFLECTED CEILING PLAN - DEMOLITION
1/8" = 1'-0"
80'-0"
'-8
80'-0"
25'-8"
'-8
26'-5" 27'-11"
26'-5" 27'-11"25'-8"
GENERAL NOTES:
1. GENERAL NOTES APPLY TO ALL DRAWINGS.
2. DIMENSIONS ARE TO EXISTING FACE OF WALL, FACE OF NEW FRAMING, AND FACE OF
EXISTING CONCRETE UNLESS NOTED OTHERWISE.
3. DIMENSIONS OF EXISTING CONDITIONS ARE APPROXIMATE AND INTENDED FOR
ESTIMATING PURPOSES ONLY. CONTRACTOR SHALL BE RESPONSIBLE TO FIELD
VERIFY ALL DIMENSIONS PRIOR TO ACTUAL CONSTRUCTION. NOTIFY OWNER
IMMEDIATELY OF ANY DISCREPANCIES OR QUESTIONABLE DIMENSIONS PRIOR TO
PROCEEDING WITH AREA OF WORK IN QUESTION.
4. DRAWINGS ARE DIAGRAMMATIC ONLY AND SHOULD NOT BE SCALED.
5. IN CASE OF ANY CONFLICTS IN THE REQUIREMENTS OF THE CONTRACT DOCUMENTS,
THE CONTRACTOR IS REQUIRED TO INCLUDE THE BETTER QUALITY AND LARGER
QUANTITY OF THE WORK.
6. CONTRACTOR AND BIDDERS SHALL USE COMPLETE SETS OF CONTRACT DOCUMENTS;
NEITHER THE OWNER NOR ARCHITECT ASSUMES RESPONSIBILITY FOR ERRORS OR
MISINTERPRETATIONS RESULTING FROM THE USE OF INCOMPLETE SETS OF
CONTRACT DOCUMENTS.
SCALE:2
REFLECTED CEILING PLAN
1/8" = 1'-0"
80'-0"
'-8
80'-0"
25'-8"
'-8
26'-5" 27'-11"
26'-5" 27'-11"25'-8"
17'-8" 8'-9"
8'-9"17'-8"
'-1
EXAM
ROOM
OFFICE
OFFICE
DENTAL
AREA
OFFICE
OFFICE
OFFICE
'-7
SCALE:
KEY PLAN
SYMBOL LEGEND:
NEW SURFACE MOUNTED LED LIGHT FIXTURES, REFER TO
ELECTRICAL DRAWINGS
NEW EXIT SIGN WITH BATTERY BACK-UP EMERGENCY EGRESS
LIGHTING, (E) DENOTES EXISTING TO REMAIN, REFER TO ELECTRICAL
DRAWINGS
NEW 5/8" GYPSUM WALLBOARD OVER 7 8" HAT CHANNEL FURRING. U.O.N.
EXISTING CEILING TO BE REMOVED, ABETMENT BY G.C.
EXISTING SURFACE MOUNTED LED LIGHT FIXTURES TO BE
REMOVED, REFER TO ELECTRICAL DRAWINGS
EXISTING SURFACE MOUNTED LED LIGHT FIXTURES TO REMAIN
CD
CONTRACTOR TO PROVIDE DRILLING IN EXISTING CONCRETE WALL
FOR EQUIPMENT LINE ROUTING, REFER TO MECHANICAL DRAWINGS
FOR REQUIRED SIZING
REFERENCE NOTES:
1 NO WORK THIS ROOM / AREA
EXISTING WINDOW BLINDS TO BE REMOVED
EXISTING CONCRETE BEAM TO REMAIN
EXISTING MINI SPLIT TO BE REMOVED, REFER TO MECHANICAL DRAWINGS
NEW MECHANICAL EQUIPMENT, REFER TO MECHANICAL EQUIPMENT
EXISTING CONCRETE WALL TO BE SAWCUT AS REQUIRED TO TAP INTO EXISTING
DUCT WORK ABOVE, REFER TO MECHANICAL DRAWINGS
NEW SUPPLY GRILLE AND ASSOCIATED DUCT WORK, REFER TO MECHANICAL
DRAWINGS.
NEW SUSPENDED GYPSUM WALLBOARD CEILING THIS ROOM/AREA, CEILING HEIGHT
TO MATCH EXISTING
HALL
2 4
32 2
(N)(N)
(N)7
CD
CD
CD
AutoCAD SHX Text
SHEET
AutoCAD SHX Text
DRAWN
AutoCAD SHX Text
REVISIONS
AutoCAD SHX Text
JOB NO.
AutoCAD SHX Text
DATE
AutoCAD SHX Text In the event conflicts are discovered between the original signed and sealed documents prepared by the Architects and/or their Consultants, and any copy of the documents transmitted by mail, fax, electronically or otherwise, the original signed and sealed documents shall govern.
AutoCAD SHX Text
ARCHITECTURERCHITECTURECHITECTUREHITECTUREITECTURETECTUREECTURECTURETUREUREREE
AutoCAD SHX Text
COMMUNITYOMMUNITYMMUNITYMUNITYUNITYNITYITYTYY
AutoCAD SHX Text 1100 Liberty St, SE, Suite 200 Salem, OR 97302 P: 503.581.4114 www.accoac.com
AutoCAD SHX Text O
AutoCAD SHX Text
SALEM, OREGON
AutoCAD SHX Text T
AutoCAD SHX Text A
AutoCAD SHX Text S
AutoCAD SHX Text T
AutoCAD SHX Text E
AutoCAD SHX Text R
AutoCAD SHX Text E
AutoCAD SHX Text F
AutoCAD SHX Text O
AutoCAD SHX Text G
AutoCAD SHX Text O
AutoCAD SHX Text N
AutoCAD SHX Text E
AutoCAD SHX Text C
AutoCAD SHX Text T
AutoCAD SHX Text D
AutoCAD SHX Text T
AutoCAD SHX Text E
AutoCAD SHX Text R
AutoCAD SHX Text E
AutoCAD SHX Text S
AutoCAD SHX Text R
AutoCAD SHX Text E
AutoCAD SHX Text G
AutoCAD SHX Text I
AutoCAD SHX Text A
AutoCAD SHX Text R
AutoCAD SHX Text C
AutoCAD SHX Text H
AutoCAD SHX Text I
AutoCAD SHX Text T
AutoCAD SHX Text
BLAKE BURAL
A8.1
2025.0018
JUNE 16, 2026
3405 DEER PARK DR SE
SALEM, OREGON 97310
OREGON STATE
CORRECTIONAL
INSTITUTION
MEDICAL UNIT RENOVATION
SCALE:1
DOOR TYPES
1/4" = 1'-0" SCALE:2
FRAME TYPES
1/4" = 1'-0"
PE
R
D O
O R
S C
H
ED
U
LE
2"
2"
PER
DOOR
SCHEDULE
2"
1CA
2"
PER
DOOR
SCHEDULE
2"
PE
R
D O
O R
SC
H
ED
U
LE
2"
2' -1
0"
2HOLLOW
METAL
METAL STUDS WITH 12" FIRE RETARDANT
PLYWOOD SHEATHING AND 5 8" TYPE 'X'
GYPSUM BOARD EACH SIDE
HM FRAME (GROUT FULL), PAINT
DOOR AS PER SCHEDULE
2" 1
2"
HEADER - SEE STRUCTURAL
SCALE:
TYP HOLLOW METAL HEAD
4 3" = 1'-0" 25018-A8.1-04
4"
4"
NEW FRAME BY CONTRACTOR, PAINT
NEW DOOR BY CONTRACTOR
SCALE:
TYP HOLLOW METAL HEAD - CONCRETE
6 3" = 1'-0" 25018-A8.1-06
NEW CONTINUOUS BACKER ROD AND SEALANT
EXISTING CONCRETE WALL TO REMAIN
8"
2"
8"
NEW CONT. 16 GA CLIP AT H.M. RETURN TO
PROVIDE BACKING FOR SEALANT SYSTEM,
TYP EACH SIDE
HM FRAME (GROUT FULL), PAINT
DOOR AS PER SCHEDULE
1 2"
1 2"
2"
8"
4"
SCALE:
TYPICAL HOLLOW METAL JAMB
5 3" = 1'-0" 25018-A8.1-05
METAL STUDS WITH 12" FIRE RETARDANT
PLYWOOD SHEATHING AND 5 8" TYPE 'X'
GYPSUM BOARD EACH SIDE
4"
NEW FRAME BY CONTRACTOR, PAINT
NEW DOOR BY CONTRACTOR
SCALE:
TYP HOLLOW METAL JAMB - CONCRETE
7 3" = 1'-0" 25018-A8.1-07
NEW CONTINUOUS BACKER ROD AND SEALANT
EXISTING CONCRETE WALL TO REMAIN
2"
8"
8"
NEW CONT. 16 GA CLIP AT H.M. RETURN TO
PROVIDE BACKING FOR SEALANT SYSTEM,
TYP EACH SIDE
SCALE:
COILING DOOR HEAD - CONCRETE
8 1-1/2" = 1'-0" 25018-A8.1-08
2"
F.V.
8" F.
V.
COILING COUNTER GUIDE RAILS
NEW COILING COUNTER DOOR AND
HOUSING
EXISTING CONCRETE WALL TO
REMAIN. CONTRACTOR TO
PROTECT ASBESTOS WALL
MATERIAL AT ALL TIMES
NEW HM FRAME (GROUT FULL), PAINT
NEW CONT. 16 GA CLIP AT H.M.
RETURN TO PROVIDE BACKING FOR
SEALANT SYSTEM, TYP EACH SIDE
NEW CONTINUOUS BACKER ROD AND
SEALANT
T.O. OPENING
7'-2"
NEW COILING COUNTER DOOR
2"
EXISTING CONCRETE WALL TO REMAIN.
CONTRACTOR TO PROTECT ASBESTOS
WALL MATERIAL AT ALL TIMES
NEW COILING COUNTER DOOR VERTICAL
GUIDE RAIL WITH UL LISTED GUIDE SEAL
SCALE:
COILING DOOR JAMB - CONCRETE
9 1 1/2" = 1'-0" 25018-A8.1-09
NEW HM FRAME (GROUT FULL), PAINT
NEW CONT. 16 GA CLIP AT H.M.
RETURN TO PROVIDE BACKING FOR
SEALANT SYSTEM, TYP EACH SIDE
NEW CONTINUOUS BACKER ROD AND
SEALANT
CORRIDOR
OFFICE
SCALE:
COILING DOOR SILL - CONCRETE
10 1-1/2" = 1'-0" 25018-A8.1-10
NEW COILING COUNTER GUIDE
RAILS
NEW 16 GA. STAINLESS STEEL
COUNTERTOP OVER PT (2) LAYERS 3 4"
FIRE RETARDANT PLYWOOD SUBSTRATE
NEW COILING COUNTER DOOR
NEW COILING COUNTER
BOTTOM BAR
EXISTING CONCRETE WALL TO REMAIN.
CONTRACTOR TO PROTECT ASBESTOS
WALL MATERIAL AT ALL TIMES
B.O. OPENING
2'-10"
NEW CONTINUOUS SEALANT
8" 8"
CORRIDOR
OFFICE
SCALE:3
WINDOW TYPES
1/4" = 1'-0"
TYPE 1: SINGLE PANE, TEMPERED
GLASS TYPES:
2' -1
0"
A
2'-3"
2'-0"
2' -1
0"
2"
2"2"
ALUM
(LOCKABLE)
SCALE:
ALUM WINDOW HEAD - JAMB SIM
11 3" = 1'-0" 25018-A8.1-11
SEALANT, BOTH SIDES
NEW ALUMINUM FRAME
HEADER - SEE STRUCTURAL
NEW WINDOW PER PLAN
METAL STUDS WITH 12" FIRE RETARDANT
PLYWOOD SHEATHING AND 5 8" TYPE 'X'
GYPSUM BOARD EACH SIDE
SCALE:
ALUM WINDOW SILL
12 3" = 1'-0" 25018-A8.1-12
NEW ALUMINUM FRAME
METAL STUDS WITH 12" FIRE
RETARDANT PLYWOOD
SHEATHING AND 5 8" TYPE 'X'
GYPSUM BOARD EACH SIDE
12"
24" AT SIM CONDITION
T.O. COUNTER
2'-10"
4" FIRE RETARDANT
PLYWOOD COUNTERTOP,
PLASTIC LAMINATE AT ALL
EXPOSED TO VIEW
SURFACES
NEW WINDOW PER PLAN
SEALANT, BOTH SIDES
HOLLOW
METAL
PADLOCK STYLE
(OFFICE SIDE)
SCALE:13
CASEWORK ELEVATION
1/4" = 1'-0"
REFERENCE NOTES:
1 DOOR AND/OR WINDOW PER PLAN
2 WALL PER PLAN TO BE PAINTED
3 NEW FLOOR BASE
24" DEEP BASE CABINET, DOORS, DRAWERS AS SHOWN, PLASTIC LAMINATE AT ALL EXPOSED
TO VIEW SURFACES
25" DEEP COUNTERTOP, U.O.N., PLASTIC LAMINATE AT ALL EXPOSED TO VIEW SURFACES
4" BACKPLASH AT ALL WALL SURFACES, PLASTIC LAMINATE AT ALL EXPOSED TO VIEW
SURFACES
2' -1
0"
4"
PE
R
R C
P
5'-6"
1'-4"4'-2"
SUPPORT BRACE, PAINT
A8.1
SCALE:
SUPPORT BRACE - HIDDEN
14 N.T.S. 25018-A8.1-14
2"x2"x3
16" T.S. W/ (4) 3 8"DIA. MB
TO 20 GA STUDS EACH SIDE
PLAN
2' -8
3'
-6
NOTE:
SPACING AS REQUIRED FOR
LENGTH OF COUNTERTOP
2"
1 6
B
1.
TYPE 1: SINGLE PANE, TEMPERED
TYPE 2: FIRE RATED, SINGLE PANE, TEMPERED
GLASS TYPES:
A8.1SIM
SCALE:17
EXISTING EQUIPMENT REMOVAL
N.T.SSCALE:
EQUIPMENT SHROUD
16 3" = 1'-0" 25018-A8.1-16
NEW STAINLESS STEEL SHROUD
FACE OF EXISTING WALL
NEW HVAC LINES AS OCCURS, REFER TO
MECHANICAL DRAWINGS FOR SIZE AND
QUANTITY
SCALE:
EXTERIOR EQUPMENT SLAB
15 3/4" = 1'-0" 25018-A8.1-15
NEW 4" CONCRETE SLAB AT GRADE
OVER 6" COMPACTED CRUSHED
ROCK. SIZE TO MEET MINIMUM
CLEARANCES PER MECHANICAL
EQUIPMENT MANUFACTURER
NEW MECHANICAL EQUIPMENT,
REFER TO MECHANICAL DRAWINGS
FACE OF EXISTING BUILDING
NEW SHEET METAL OVER AND SEALANT
EXISTING MECHANICAL UNIT TO BE
REMOVED, REFER TO MECHANICAL
DRAWINGS
~36" F.V.
~1 2"
F .V
1. 1.
4" 11 2"
2' -4
1 2"
D
2.
AutoCAD SHX Text
SHEET
AutoCAD SHX Text
DRAWN
AutoCAD SHX Text
REVISIONS
AutoCAD SHX Text
JOB NO.
AutoCAD SHX Text
DATE
AutoCAD SHX Text In the event conflicts are discovered between the original signed and sealed documents prepared by the Architects and/or their Consultants, and any copy of the documents transmitted by mail, fax, electronically or otherwise, the original signed and sealed documents shall govern.
AutoCAD SHX Text
ARCHITECTURERCHITECTURECHITECTUREHITECTUREITECTURETECTUREECTURECTURETUREUREREE
AutoCAD SHX Text
COMMUNITYOMMUNITYMMUNITYMUNITYUNITYNITYITYTYY
AutoCAD SHX Text 1100 Liberty St, SE, Suite 200 Salem, OR 97302 P: 503.581.4114 www.accoac.com
AutoCAD SHX Text O
AutoCAD SHX Text
SALEM, OREGON
AutoCAD SHX Text T
AutoCAD SHX Text A
AutoCAD SHX Text S
AutoCAD SHX Text T
AutoCAD SHX Text E
AutoCAD SHX Text R
AutoCAD SHX Text E
AutoCAD SHX Text F
AutoCAD SHX Text O
AutoCAD SHX Text G
AutoCAD SHX Text O
AutoCAD SHX Text N
AutoCAD SHX Text E
AutoCAD SHX Text C
AutoCAD SHX Text T
AutoCAD SHX Text D
AutoCAD SHX Text T
AutoCAD SHX Text E
AutoCAD SHX Text R
AutoCAD SHX Text E
AutoCAD SHX Text S
AutoCAD SHX Text R
AutoCAD SHX Text E
AutoCAD SHX Text G
AutoCAD SHX Text I
AutoCAD SHX Text A
AutoCAD SHX Text R
AutoCAD SHX Text C
AutoCAD SHX Text H
AutoCAD SHX Text I
AutoCAD SHX Text T
AutoCAD SHX Text
BLAKE BURAL
A9.1
2025.0018
JUNE 16, 2026
3405 DEER PARK DR SE
SALEM, OREGON 97310
OREGON STATE
CORRECTIONAL
INSTITUTION
MEDICAL UNIT RENOVATION
DOOR FRAME DETAILS
NOMINAL
SIZENO. TYPE MAT'L GLASS TYPE MAT'L GLASS H J S
HDWR.
GROUP LABEL REMARKS
DOOR SCHEDULE - PROJECT NO. 2025.0018
103-A 3'-0"x7'-0" B HM 1 1 HM - - NO. 1 - -
ALL DOORS 13
4" THICK UNLESS OTHERWISE NOTED
103-B 2'-4"x4'-2" C ALUM - 2 HM - - 20 MIN COILING COUNTER DOOR
4/A8.1 5/A8.1
105 3'-0"x7'-0" D STL 1 1 HM - - NO. 2 20 MIN DETENTION GRADE DOOR, SEE SPECS6/A8.1 7/A8.1
8/A8.1 9/A8.1 10/A8.1
8/A8.1 9/A8.1 10/A8.1
102 3'-0"x7'-0" B HM 1 1 HM - - NO. 1 - -4/A8.1 5/A8.1
103-C 2'-4"x4'-2" C ALUM - 2 HM - - 20 MIN COILING COUNTER DOOR
DESCRIPTION CATALOG NUMBER FINISH MANUFACTURERQUANTITY
HARDWARE GROUP NO. 1
HINGE 652 IV3 EACH 5BB1 4 1/2 x 4 1/2
LOCKSET 626 SC1 EACH ND53P6 RHO K510-066
CLOSER AL LC1 EACH 4011 REGARM WMS
WALL STOP1 EACH WS406/407CCV US32D IVE
DOOR SILENCER GRY IV3 EACH SR64
FLOOR BASE WALL
FINISH KEY - PROJECT NO. 2025.0018
CEILING
1 EXISTING TO REMAIN A EXISTING TO REMAIN 1 EXISTING TO REMAIN A EXISTING TO REMAIN
2 POLISHED CONCRETE B 6" RUBBER BASE 2 GYPSUM WALLBOARD, PAINT B GYPSUM WALLBOARD, PAINT
3 EXISTING CONCRETE, PAINT C EXISTING CONCRETE, PAINT
4 NEW CONCRETE, PAINT
FLOOR WALLS CEILING
ROOMNO. MAT'L BASE
N.
WALL
MAT'L
E.
WALL
MAT'L
S.
WALL
MAT'L
W.
WALL
MAT'L
MAT'L HEIGHT REMARKS
ROOM FINISH SCHEDULE - PROJECT NO. 2025.0018
100 EXAM ROOM 1 A 1 1 1 1 A EXST
101 HALL 2 B 3 3 3 2 C EXST
102 OFFICE 2 B 3 2 2 3 B,C EXST
103 OFFICE 2 B 2 2 3 3,4 B,C EXST
104 DENTAL AREA 1 A,B 1 3,4 1 1 A EXST NEW BASE ON EAST WALL
105 VESTIBULE 1 A 3 3,4 3 3 B ~8'-0"
106 OFFICE 1 A 1 1 1 1 A EXST
107 OFFICE 1 A 1 1 1 1 A EXST
108 CORRIDOR 1 A 1 1 1 1 A EXST
109 STAIR 1 A 1 1 1 1 A EXST
REFERENCE NOTES:
NEW TEMPORARY WALL SURROUNDING CONSTRUCTION AREA. 2x4 STUDS AT 16" OC
WITH 12" PLYWOOD AT OUTSIDE FACE, FRAME UP TO 8'-0" A.F.F. CONTRACTOR TO
PROVIDE CONSTRUCTION ZONE SIGNAGE.
TO BE REMOVED AFTER PHASE 1
WORK IN DENTAL AREA IS COMPLETE
SCALE:1
SAFETY ZONE PLAN
1/4" = 1'-0"
EXAM
ROOM
OFFICE
OFFICE
DENTAL
AREA
OFFICE
OFFICE
VESTIBULE
HALL
CORRIDOR
EXISTING
STAIR
DESCRIPTION CATALOG NUMBER FINISH MANUFACTURERQUANTITY
HARDWARE GROUP NO. 2
HINGE USP FOLGER ADAMS3 EACH 205 HINGE
LOCKSET1 EACH 80 DEADLOCK
DOOR PULL 26D1 EACH RAISED DOOR PULL
PLATE1 EACH PUSH PLATE -
USP
FOLGER ADAMS
FOLGER ADAMS
AutoCAD SHX Text
SHEET
AutoCAD SHX Text
DRAWN
AutoCAD SHX Text
REVISIONS
AutoCAD SHX Text
JOB NO.
AutoCAD SHX Text
DATE
AutoCAD SHX Text In the event conflicts are discovered between the original signed and sealed documents prepared by the Architects and/or their Consultants, and any copy of the documents transmitted by mail, fax, electronically or otherwise, the original signed and sealed documents shall govern.
AutoCAD SHX Text
ARCHITECTURERCHITECTURECHITECTUREHITECTUREITECTURETECTUREECTURECTURETUREUREREE
AutoCAD SHX Text
COMMUNITYOMMUNITYMMUNITYMUNITYUNITYNITYITYTYY
AutoCAD SHX Text 1100 Liberty St, SE, Suite 200 Salem, OR 97302 P: 503.581.4114 www.accoac.com
AutoCAD SHX Text O
AutoCAD SHX Text
SALEM, OREGON
AutoCAD SHX Text T
AutoCAD SHX Text A
AutoCAD SHX Text S
AutoCAD SHX Text T
AutoCAD SHX Text E
AutoCAD SHX Text R
AutoCAD SHX Text E
AutoCAD SHX Text F
AutoCAD SHX Text O
AutoCAD SHX Text G
AutoCAD SHX Text O
AutoCAD SHX Text N
AutoCAD SHX Text E
AutoCAD SHX Text C
AutoCAD SHX Text T
AutoCAD SHX Text D
AutoCAD SHX Text T
AutoCAD SHX Text E
AutoCAD SHX Text R
AutoCAD SHX Text E
AutoCAD SHX Text S
AutoCAD SHX Text R
AutoCAD SHX Text E
AutoCAD SHX Text G
AutoCAD SHX Text I
AutoCAD SHX Text A
AutoCAD SHX Text R
AutoCAD SHX Text C
AutoCAD SHX Text H
AutoCAD SHX Text I
AutoCAD SHX Text T
AutoCAD SHX Text
BLAKE BURAL
ABBREVIATIONS
ABBRV.
POWER SYMBOLS
SYMBOL IDENTIFICATION IDENTIFICATION
AC ALTERNATING CURRENT
AFF ABOVE FINISH FLOOR
AT TRIP RATING IN AMPERES
FRAME RATING IN AMPERES
AS SWITCH RATING IN AMPERES
ATS AUTOMATIC TRANSFER SWITCH
AV AUDIO VISUAL
C CONDUIT
CL CENTERLINE
DC DIRECT CURRENT
(E) EXISTING TO REMAIN
ELEV ELEVATOR
EMT ELECTRO METALLIC TUBING
G GROUND
GFCI GROUND FAULT CIRCUIT INTERRUPTER
HID HIGH INTENSITY DISCHARGE
IG ISOLATED GROUND
LCP LIGHTING CONTROL PANEL
NC NORMALLY CLOSED
NEMA NATIONAL ELECTRICAL
MANUFACTURER'S ASSOCIATION
NO NORMALLY OPEN
NTS NOT TO SCALE
PVC POLYVINYL CHLORIDE CONDUIT
RSC RIGID STEEL CONDUIT
TTB TERMINAL BACKBOARD
TC TERMINAL CABINET
TEL TELEPHONE
UON UNLESS OTHERWISE NOTED
VFD VARIABLE FREQUENCY DRIVE
W WEATHERPROOF
WAP WIRELESS ACCESS POINT
W/ WITH
XFMR TRANSFORMER
XP EXPLOSION PROOF
NEC NATIONAL ELECTRIC CODE
(X) REMOVE EXISTING
(R) RELOCATE EXISTING
20A, 125V, DUPLEX RECEPTACLE OUTLET +18" AFF TO
CENTERLINE OF BOX UNLESS OTHERWISE NOTED
20A, 125V, DOUBLE DUPLEX RECEPTACLE OUTLET +18" AFF
TO CENTERLINE OF BOX UNLESS OTHERWISE NOTED
CONN CONNECTED
SPECIAL PURPOSE RECEPTACLE OUTLET; NEMA
CONFIGURATIONS AS SHOWN ON DRAWINGS; 18" AFF
TO CENTERLINE OF BOX UNLESS OTHERWISE NOTED
20A, 125V, SINGLE RECEPTACLE OUTLET; +18" AFF
TO CENTERLINE OF BOX UNLESS OTHERWISE NOTED
A = ABOVE COUNTER
C = CEILING MOUNTED
G = GFCI
S = SWITCHED RECEPTACLE
U = WITH (2) USB PORTS
W = WEATHERPROOF COVER AND GFCI
X
20A, 125V, DUPLEX RECEPTACLE OUTLET;
FLOOR RECESSED
20A, 125V, DOUBLE DUPLEX RECEPTACLE OUTLET;
FLOOR RECESSED
2-COMPARTMENT FLOOR BOX W/ (2) GANG POWER /
(2) GANG DATA; PROVIDE 1"C. FROM EACH DATA
OUTLET TO ACCESSIBLE CEILING SPACE.
SINGLE POLE SWITCH
3 = THREE WAY SWITCH
4 = FOUR-WAY SWITCH
D = DIMMER SWITCH
K = KEY OPERATED SWITCH
M = MOTOR RATED SWITCH
T = INTERVAL TIMER
V = VACANCY SENSOR SWITCH
W = WEATHERPROOF SWITCH
X
PUSH BUTTON
OCCUPANCY LIGHT CONTROL SWITCH; CEILING MOUNTED
OCCUPANCY LIGHT CONTROL SWITCH; WALL MOUNTED
PHOTOSENSOR; CEILING MOUNTED
C = CORRIDOR PATTERN
X
DIMMING PHOTOSENSOR
D
ELECTRIC VEHICLE CHARGING STATION
LUMINAIRE; CEILING OR SURFACE MOUNTED
LUMINAIRE; WALL MOUNTED
AREA POLE WITH MOUNTED LUMINAIRE ON RAISED POLE BASE
LUMINAIRE ON EMERGENCY POWER
EXIT SIGN; CEILING MOUNTED; ARROWS AND FACES
AS SHOWN ON PLANS
EXIT SIGN; WALL MOUNTED; ARROWS AND FACES AS
SHOWN ON PLANS
SPD SURGE PROTECTION DEVICE
PH PHASE
GND GROUND
CONTRACTOR FURNISHED,
CONTRACTOR INSTALLEDCFCI
CONTRACTOR FURNISHED,
OWNER INSTALLEDCFOI
OFCI OWNER FURNISHED,
CONTRACTOR INSTALLED
MOTOR CONNECTION
FUSED DISCONNECT
SWITCH XX/XX/XX = AMP SWITCH/POLES/AMP FUSE
NON-FUSED DISCONNECT
SWITCH XX/XX = AMP SWITCH/POLES
JUNCTION BOX; FLOOR/GRADE MOUNTED
JUNCTION BOX; CEILING MOUNTEDC
JUNCTION BOX WITH WHIP-STYLE CONNECTION TO
POWERED FURNITURE; POWER AND/OR DATA
JUNCTION BOX; WALL MOUNTED
GENERATOR CONNECTION
TRANSFORMER; BOTTOM OF T DESIGNATES FRONT SIDE
PANELBOARD OR TERMINAL CABINET; SURFACE MOUNTED
PANELBOARD OR TERMINAL CABINET; FLUSH MOUNTED
AUTOMATIC TRANSFER SWITCH
DRAWOUT CIRCUIT BREAKER; RATING AS SHOWN ON PLANS
STATIONARY - CIRCUIT BREAKER; RATING AS SHOWN ON PLANS
FUSED DISCONNECT; RATING AS SHOWN ON PLANS
NON-FUSED DISCONNECT; RATING AS SHOWN ON PLANS
TRANSFORMER
INVERTER
GROUNDING POINT
UTILITY METER
GROUND BUS BAR
M
G
F
J
J
J
OS
O S
OS
PS
S = OCCUPANCY SENSOR SWITCH
T = TAMPER PROOF
+#" = INCHES ABOVE FINISH FLOOR TO CENTERLINE OF BOX
COMMERCIAL CORD REEL RECEPTACLE; CEILING MOUNTED
H = HIGH BAY SENSOR
V = VACANCY SENSOR MODE
EV
J
EMERGENCY FIXTURE; DUAL LAMP HEAD
J C
M
PB
LIGHTING SYMBOLS
SYMBOL IDENTIFICATION
WIRING DEVICE SYMBOLS
SYMBOL IDENTIFICATION
CONDUIT INSTALLED BELOW FINISHED FLOOR OR
BELOW GRADE
CONDUIT INSTALLED ABOVE FINISHED FLOOR OR GRADE
INDICATES CONDUIT TURNING UP
CONDUIT HOMERUN; ROUTE TO PANELBOARD, CABINET, OR
TERMINAL BOARD INDICATED, AND TERMINATE CONDUCTORS
TO CIRCUIT OVER CURRENT PROTECTIVE DEVICE
CONDUIT SYMBOLS
SYMBOL IDENTIFICATION
FEEDER DESIGNATION TAG
SHEET KEYNOTE TAG
MECHANICAL EQUIPMENT TAG
CONTRACTOR EQUIPMENT TAG
LETTER INDICATES FIXTURES CONTROL (WHERE SHOWN)
NUMBER INDICATES CIRCUIT NUMBER (WHERE SHOWN)
REVISION DELTA WITH REVISION NUMBER#
a.$
XX-#
XX-#
DESIGNATION SYMBOLS
SYMBOL IDENTIFICATION
MANUAL TRANSFER SWITCH
CUSTOMER METERCM
T
INDICATES CONDUIT TURNING DOWN
CONDUIT STUBBED AND CAPPED
CONDUIT AND WIRE. HATCH LINES INDICATE QUANTITY OF
UNGROUNDED #12 CONDUCTORS, OR CONDUCTOR SIZE AS
NOTED ADJACENT TO HATCH LINES. GROUND CONDUCTOR TO
BE PROVIDED SIZED IN ACCORDANCE WITH NEC TABLE
250-122. IF NO HATCH LINES ARE SHOWN, 2#12 & 1#12G
CONDUCTORS ARE ASSUMED.
TERMINAL CABINET OR CONTROL PANEL; FLUSH MOUNTED
TERMINAL CABINET OR CONTROL PANEL; FLUSH MOUNTED
EXIT SIGN WITH DUAL LAMP HEAD
LUMINAIRE; STRIP LIGHT
EPO PUSH BUTTON
OS
PS COMBINATION OCCUPANCY SENSOR/PHOTOSENSOR
PS
AIC AMPS INTERRUPTING CURRENT
A AMPERES
AWG AMERICAN WIRE GAUGE
AFCI ARC FAULT CIRCUIT INTERRUPTER
AFG ABOVE FINISHED GRADE
CATV CABLE TELEVISION
CB CIRCUIT BREAKER
CCTV CLOSED CIRCUIT TELEVISION
CU COPPER
EM EMERGENCY / STANDBY POWER
FA FIRE ALARM
FACP FIRE ALARM CONTROL PANEL
HP HORSEPOWER
HZ HERTZ
IDF INTERMEDIATE DISTRIBUTION FRAME
KV KILOVOLT
KVA KILOVOLT AMPERE
KW KILOWATT
LED LIGHT EMITTING DIODE
MCB MAIN CIRCUIT BREAKER
MCC MOTOR CONTROL CENTER
MDF MAIN DISTRIBUTION FRAME
MTS MANUAL TRANSFER SWITCH
NIC NOT INCLUDED IN CONTRACT
PV PHOTOVOLTAIC
TYP TYPICAL
(RR) REMOVE AND REPLACE WITH NEW
EV ELECTRICAL VEHICLE
MLO MAIN LUGS ONLY
CONDUIT ONLYCO
CURRENT TRANSFORMERCT
UL UNDERWRITER LABORATORIES
V VOLTAGE
W/O WITHOUT
AF
LEGEND NOTES
A. ALL SYMBOLS MAY NOT BE USED IN THIS PROJECT
B. SYMBOLS DO NOT ALWAYS REPRESENT REAL LIFE DIMENSIONS
C. SEE SPECIFICATIONS FOR ADDITIONAL INFORMATION
D. MOUNTING HEIGHTS OF DEVICES SHALL BE AS NOTED IN THE LEGEND FOR THE
RESPECTIVE SYMBOL, UON ON FLOOR PLANS OR AS REQUIRED PER ADA REQUIREMENTS.
ABBRV. IDENTIFICATION
CD
M F
CD
CD
S W
H F
W
CD
VISIBLE ONLY (STROBE)
WALL MOUNTED
VISIBLE ONLY (STROBE)
CEILING MOUNTED
SPEAKER ONLY
WALL MOUNTED
HORN/STROBE VISUAL & AUDIBLE APPLIANCE
SOUNDER TO USE TEMPORAL 3 PATTERN.
WALL MOUNTED
HORN ONLY AUDIBLE APPLIANCE
SOUNDER TO USE TEMPORAL 3 PATTERN
WALL MOUNTED
MINI-HORN AUDIBLE APPLIANCE
SOUNDER TO USE LOW FREQUENCY OF 520HZ
WALL MOUNTED
SPEAKER/STROBE VISUAL & AUDIBLE APPLIANCE
WALL MOUNTED
NOTIFICATION APPLIANCES
PRI PRIMARY
SEC SECONDARY
P POLE
RECPT RECEPTACLE
LGT LIGHTING
NEU NEUTRAL
LUMINAIRE; PENDANT
AREA POLE WITH MOUNTED LUMINAIRE
LUMINAIRE; UNDERCABINET OR TAPE
DP DISTRIBUTION PANEL
S SWITCHBOARD
SWITCHBOARD OR DISTRIBUTION PANEL
LV = LOW VOLTAGE SWITCH
INV INVERTER
GEN GENERATOR
DIA DIAMETER REFR REFRIGERATOR
UC UNDER COUNTER
MICRO MICROWAVE
20A, 125V, DUPLEX RECEPTACLE OUTLET;
COUNTERTOP POP-UP TYPE.
TELEPHONE/DATA OUTLET; PROVIDE 1"C. W/
PULL-STRING TO ACCESSIBLE CEILING SPACE
UNLESS OTHERWISE NOTED
TELECOM SYMBOLS
SYMBOL IDENTIFICATION
SECURITY CAMERA
X C = CEILING MOUNTED; BACK BOX ONLY FOR
FUTURE WAP UNLESS OTHERWISE NOTED
4 = 4 PORT OUTLET
TELEPHONE OUTLET; PROVIDE 1"C. W/ PULL-
STRING TO ACCESSIBLE CEILING SPACE UNLESS
OTHERWISE NOTED
TV
RG-6 COAX OUTLET; PROVIDE 1"C. W/ PULL-
STRING TO ACCESSIBLE CEILING SPACE UNLESS
OTHERWISE NOTED
1. SCOPE OF WORK:
A. THIS PROJECT IS A REMODEL. THE PLANS AND SPECIFICATIONS INDICATE THE GENERAL
EXTENT OF THE WORK BASED ON OWNER-PROVIDED INFORMATION AND LIMITED
FIELD VERIFICATION. CONTRACTOR SHALL VISIT SITE, VERIFY EXISTING CONDITIONS,
AND REPORT ANY DISCREPANCIES NOTED TO THE ARCHITECT PRIOR TO SUBMITTING A
BID. CONTRACTOR SHALL BE RESPONSIBLE FOR THE DISCONNECTION AND
RECONNECTION OF MECHANICAL, PLUMBING, AND ELECTRICAL SYSTEMS NECESSARY
TO ACCOMPLISH THE WORK WHETHER OR NOT SPECIFIED AND/OR INDICATED.
2. REFER TO ARCHITECTURAL PLANS FOR LOCATIONS OF FIRE RATED WALLS, FLOORS, CEILINGS, ETC. PROVIDE FIRE RATED PENETRATIONS AT THESE LOCATIONS.
3. REFER TO MECHANICAL DRAWINGS FOR EXACT LOCATIONS OF EQUIPMENT AND ADDITIONAL
CONTROL REQUIREMENTS. CONNECTION REQUIREMENTS TO ALL EQUIPMENT TO BE VERIFIED
WITH APPROVED SUBMITTALS / SHOP DRAWINGS.
4. FLOOR MOUNTED ELECTRICAL EQUIPMENT SHALL BE INSTALLED ON A 3" HIGH CONCRETE
HOUSEKEEPING PAD.
5. VERIFY DEVICE MOUNTING HEIGHT AND ORIENTATION (VERTICAL OR HORIZONTAL) WITH
ARCHITECTURAL AND INTERIOR DESIGN DRAWINGS AND ELEVATIONS.
6. DISCONNECT SWITCHES TO BE SIZED AT MINIMUM TO MATCH THE BREAKER SIZE OF THE
RESPECTIVE BRANCH CIRCUIT BEING FED.
7. RACEWAY SYSTEMS AND CONDUIT ROUTING SHOWN ON ELECTRICAL DRAWINGS IS
DIAGRAMMATIC IN NATURE AND TO SHOW THE DESIGN INTENT OF CONDUIT INFRASTRUCTURE
REQUIREMENTS. ACTUAL LOCATION AND ROUTING OF ALL CONDUIT RACEWAYS SHALL BE
DETERMINED BY CONTRACTOR TO SUIT FIELD CONDITIONS.
8. CONTRACTOR TO PROVIDE PULL STRINGS IN ALL LOW VOLTAGE SYSTEM CONDUITS AND ALL
SPARE CONDUITS.
9. PROVIDE DEDICATED NEUTRAL FOR EACH NEW CIRCUIT. HOME RUN CONDUCTORS MAY BE
COMBINED INTO ONE CONDUIT. NO RACEWAY OR CABLE SHALL CONTAIN MORE THAN NINE (9)
CURRENT CARRYING CONDUCTORS.
10. BRANCH CIRCUITS TO BE SIZED FOR MAXIMUM 3% VOLTAGE DROP. PROVIDE #10 AWG
CONDUCTORS FOR 20 AMPERE, 120V BRANCH CIRCUITS LONGER THAN 75' AND #8 AWG
CONDUCTORS FOR 20 AMPERE, 120V BRANCH CIRCUITS LONGER THAN 120'. PROVIDE #10
AWG CONDUCTORS FOR 20 AMPERE, 277V BRANCH CIRCUITS LONGER THAN 200'.
11. PROVIDE DEDICATED NEUTRAL TO EACH BRANCH CIRCUIT PER NEC 210.4.
12. SUBSTITUTION REQUESTS TO SPECIFIED MATERIALS AND EQUIPMENT WILL NOT BE
CONSIDERED BY THE ENGINEER UNTIL THE PROJECT HAS BEEN AWARDED TO A CONTRACTOR.
BRAND NAMES AND MODEL NUMBERS ARE USED IN THE CONTRACT DOCUMENTS TO
ESTABLISH A LEVEL OF QUALITY AND REQUIRED FUNCTIONALITY. THE ENGINEER SHALL BE THE
SOLE JUDGE AS TO WHETHER PROPOSED SUBSTITUTIONS ARE EQUIVALENT TO SPECIFIED
ITEMS. THE PROPOSER OF A SUBSTITUTE MATERIAL OR ITEM OF EQUIPMENT SHALL VERIFY FIT
AND FUNCTIONALITY PRIOR TO SUBMISSION FOR APPROVAL AND FURNISH ALL NECESSARY
DOCUMENTATION FOR THE ENGINEER’S EVALUATION. THE PROPOSER OF AN APPROVED
SUBSTITUTION SHALL BEAR ALL COSTS ASSOCIATED WITH INCORPORATING AN APPROVED
SUBSTITUTION INTO THE PROJECT.
THIS WORK SHALL CONFORM TO ALL CURRENT AND ADOPTED LOCAL CODES
• 2025 OREGON STRUCTURAL SPECIALTY CODE (OSSC)
• 2025 OREGON MECHANICAL SPECIALTY CODE (OMSC)
• 2023 OREGON PLUMBING SPECIALTY CODE (OPSC)
• 2025 OREGON ENERGY EFFICIENCY SPECIALTY CODE (OEESC)
• 2025 OREGON ELECTRICAL SPECIALTY CODE (OESC)
• 2022 OREGON FIRE CODE (OFC)
• 2023 ASHRAE 90.1
REVISIONS
JOB NO.
TH
E
U
SE
O F
TH
ES
E
PL
AN
S
AN
D
S
PE
CI
FI
CA
TI
O N
S
SH
AL
L
BE
R
ES
TR
IC
TE
D T
O T
H E
O
RI
G
IN
AL
S
IT
E
FO
R
W H
IC
H
T H
EY
W
ER
E
PR
EP
AR
ED
A N
D P
U
BL
IC
AT
IO
N
T H
ER
EO
F
IS
E
XP
RE
SS
LY
L
IM
IT
ED
T
O S
U
CH
U
SE
. R E-
U
SE
, R
EP
RO
D
U
CT
IO
N
, O R
PU
BL
IC
AT
IO
N
B Y
AN
Y
M
ET
H O
D , I
N W
H O
LE
O
R
IN
P
AR
T, IS
P
RO
H
IB
IT
ED
. T
IT
LE
T
O T
H E
PL
AN
S
AN
D S
PE
CI
FI
CA
TI
O
N S
RE
M
AI
N
S W
IT
H
T H
E
EN
G
IN
EE
R
W
IT
H O
U T
PR
EJ
U D
IC
E.
V
IS
U
AL
C O
N
TA
CT
W
IT
H
T H
ES
E
PL
AN
S
AN
D S
PE
CI
FI
CA
TI
O
N S
SH
AL
L
CO
N
ST
IT
U
TE
P
RI
M
A
FA
CI
E
EV
ID
EN
CE
O F
TH
E
AC
CE
PT
AN
CE
O
F
TH
ES
E
RE
ST
RI
CT
IO
N
S.
C
O
LE
BR
EI
T
EN
G
IN
EE
RI
N G
, L
LC
DRAWN
ARCHITECTURE
COMMUNITY
363 State Street Salem, OR 97301-3533 P: 503.581.4114 www.accoac.com
In the event conflicts are discovered between the original signed and sealed documents prepared by the Architects and/or their Consultants, and any copy of the documents transmitted by mail, fax, electronically or otherwise, the original signed and sealed documents shall govern.
DATE MARCH 20, 2026
SHEET
3/
/2
3:
:1
PM
E001
OREGON STATE
CORRECTIONAL
INSTITUTION
LEGEND AND
GENERAL NOTES
2026009
3405 DEER PARK DR SE
SALEM, OREGON 97310
MEDICAL UNIT RENOVATION
ELECTRICAL SHEET KEY
SHEET NUMBER DESCRIPTION
E001 LEGEND AND GENERAL NOTES
E001.2 SPECIFICATIONS
E002 SCHEDULES
E201 LIGHTING PLANS
E301 POWER PLANS
E801 DETAILS
GENERAL ELECTRICAL NOTES
LIST OF GOVERNING CODES
BASIC ELECTRICAL REQUIREMENTS
A. CODES AND STANDARDS
1. Equipment, materials and installation is to conform to the codes, standards, tests, guidance or recommended methods of trade effective as of the date of the Contract Documents as published by the following bodies:
2. Americans with Disabilities Act (ADA)
3. Authority Having Jurisdiction (AHJ)
4. American National Standards Institute (ANSI)
5. American Society of Testing and Materials (ASTM)
6. Oregon Electrical Specialty Code (OESC)
7. Oregon State Fire Marshal (OSFM)
8. Electrical Testing Laboratories (ETL)
9. Electric Utility Service Equipment Requirements Committee (EUSERC)
10. Institute of Electrical and Electronics Engineers (IEEE)
11. National Electrical Manufacturer’s Association (NEMA)
12. National Fire Protection Association (NFPA)
13. Occupational Safety and Health Act (OSHA)
14. Underwriter’s Laboratories (UL)
15. Local Building Department, where applicable.
16. Local Fire Department, where applicable.
17. Local power, telephone and cable television utilities, where applicable.
B. SUBMITTALS
1. Provide electronic format via zip file via e-mail. no more than one pdf per specification section. Highlight products being submitted; unmarked cutsheets will be returned as rejected.
C. CONNECTIONS TO EQUIPMENT
1. Make final connections to equipment furnished under this Division, other Divisions or by the Owner. Verify the electrical requirements of the equipment nameplates with the information specified on the applicable drawings or submittal, and the designed electrical connection.
D. EXCAVATION AND BACKFILL
1. Provide excavation for underground electrical utilities and substructures. Backfill and patch excavated areas to the original condition and as shown on the
Drawings.
2. Locate all existing underground utilities prior to trenching. Hand-dig in locations of known utilities. Damage caused to utilities by the Contractor is to be repaired at the Contractor’s expense.
BASIC ELECTRICAL MATERIALS
A. METALLIC CONDUIT
1. Exposed conduit in corrosive and high humidity areas including cold: Rigid aluminum conduit with watertight threaded aluminum fittings.
2. Conduit across concrete expansion joints: appropriate metallic conduit as specified above with watertight threaded fittings and expansion couplings, bonding jumpers and corrosion protection as specified above.
3. Interior concealed conduit, exposed conduit in interior unfinished spaces, and exposed conduit in other interior spaces where approved: electrical metallic tubing (EMT) with steel compression fittings in damp areas and steel set-screw fittings in dry areas.
4. Interior concealed connections for lay-in lighting fixtures in ceiling grids: Galvanized flexible steel conduit not exceeding six-foot lengths with approved grounding bushings.
5. Flexible connections damp areas, kitchens, exterior areas, to transformers, motors and other vibrating equipment, and connections across seismic or expansion joints: Liquid-tight flexible galvanized steel conduit not exceeding six-foot lengths with approved grounding bushings.
6. Provide plastic conduit bushings except where metallic grounding bushings are required.
7. Conduit bodies shall be OZ Gedney type EW or equivalent, unless otherwise noted.
B. NON-METALLIC CONDUIT
1. Underground, underslab, in slab, and in concrete and CMU walls: Schedule 40 PVC with cemented fittings. Conduit shall be listed for direct burial and use with 90-degree Celsius wiring. Restrictions: see metallic conduit requirements above for risers and conduit less than 18” below grade.
2. Provide non-metallic underground conduit for utility cables that comply with the requirements of the respective utility.
3. Provide materials as manufactured by Carlon or equivalent.
C. JUNCTION AND OUTLET BOXES
1. Provide galvanized steel boxes with tapped ears approved for the purpose and location of each installation. Boxes shall be flush-mounted unless they are located in unfinished areas. Where boxes are approved by the Architect and Engineer to be surface-mounted in finished areas, provide surface-mounted boxes as specified in this or other Sections.
2. Surface-mounted junction and outlet boxes in process, damp or wet locations shall be Crouse-Hinds cast aluminum type FS or FD with proper quantity and size hubs, device plates, covers, adapters and accessories.
3. Metallic boxes shall be Code-sized at not less than 4” square by 2-1/8” deep. Provide proper galvanized trim rings for flush boxes and flat steel cover plates for surface boxes, color to match neighboring cover plates. The trim ring shall provide a minimum ¼” clearance between any device and the back of the box. All boxes shall have connectors with integral insulated throats.
4. Boxes shall be rigidly supported with prefabricated brackets and/or blocking.
5. Provide materials as manufactured by Raco or equivalent, unless otherwise noted.
D. FLOORBOXES
1. Concrete floors: Thomas & Betts/Steel City: #663-SC two gang multi-service concealed floor box for power, communications and data with no exposed service fitting. Provide a completely flush installation with no raised beveled coverplate.
2. Multi-service cast-iron box with closed cover when in use, wood floors and carpet only: Walker #RFB4-C1 with #RAKMII carpet trim plate receptacle and telcom brackets as required.
3. All receptacles in floor boxes shall include ground-fault interrupters (GFI) unless otherwise noted.
E. CONCRETE UNDERGROUND PULLBOXES
1. Provide Christy, Brooks or Quikset precast concrete underground pullboxes for power and signal systems in sizes and quantities as shown on the Drawings and as required by Code.
2. In areas not subject to vehicular traffic, provide Christy N-series boxes with extensions as required and concrete lids.
3. In areas subject to vehicular traffic, provide Christy B-series boxes with extensions as required and bolt-down galvanized steel checkered lids.
4. Lids shall be properly labeled with the following acceptable captions for the separate systems: “POWER” or “ELECTRICAL”, “TELCOM” or “SIGNAL” or
“COMMUNICATIONS”, or as specially noted on the Drawings.
5. Provide precast utility pullboxes and vaults for utility systems that comply with the requirements of the respective utility.
F. ABOVE-GRADE PULLBOXES AND TERMINAL CABINETS
1. Provide pullboxes and terminal cabinets as shown on the Drawings and where required. Boxes shall be 14 gauge galvanized steel (exterior) or 16 gauge
(interior) and shall have continuous welded seams and stainless steel hardware (hinges, screws, etc.).
2. Pullboxes shall have non-hinged covers attached with machine screws; terminal cabinets shall have hinged pad-lockable covers with stainless-steel hinge pin.
3. Weatherproof boxes shall be fully gasketed. Penetrations into weatherproof boxes shall be made with interchangeable hubs, gaskets and adapter nuts.
G. 600 VOLT CONDUCTORS, SPLICES AND CONNECTORS
1. Conductors shall be copper with THHN/THWN insulation. #10 AWG conductors and smaller shall have color-coded insulation and shall be stranded with compression spade connectors at all device terminations, or may be solid without compression connectors. Conductors #8 AWG and larger shall be stranded. Provide materials as manufactured by General Wire and Cable or equivalent.
2. Prefabricated wiring and raceway assemblies, including types AC (armored cable), MC (metal-clad cable), are permitted in framed areas where the wiring can be concealed in walls and ceilings. Type AC and MC are not permitted for feeders and exterior circuits. NM (non-metallic sheathed “Romex”), is not permitted in this project.
3. Branch-circuit conductor connectors for #10 AWG and smaller: 3M Scotchlok connectors or equivalent.
4. Conductor connectors for #8 AWG and larger: T & B Lock-Tite connectors or equivalent.
5. Feeder splices above-grade in dry locations: Lug connectors with half-lapped Scotch #23 rubber tape covered with an equal number of turns of half-lapped
Scotch #50 PVC tape, or equivalent.
H. WIRING DEVICES
1. Provide wiring devices that are Specification Grade or better as specified below, colors shall be white unless otherwise directed by the Architect.
2. Light switches, 20A 120V/277V, paddle type, back and side wired.
3. 125V 2P 3W convenience receptacles; 15A for multi-outlet branch-circuits, 20A for dedicated 20 amp branch circuits, nylon face, back and side wired, heavy duty specification grade at front of house spaces, and heavy duty at ‘back of house’ locations including equipment rooms, janitor closets, storage rooms and other unfinished spaces.
4. 125V 2P 3W GFCI receptacles, 15 amp for multi-outlet branch-circuits, 20A for dedicated 20 amp branch circuits, nylon face, back and side wired, specification grade.
5. 125V 2P 3W controlled duplex receptacles, 15 amp for multi-outlet branch-circuits, 20A for dedicated 20 amp branch circuits, with permanent marking that identifies the receptacle(s) that are controlled.
6. Cover plates: color to match the respective device. Single and multigang plates
7. Decora, screwless, snap-on cover plates for front of house areas, including public spaces, and offices
A. DISCONNECT SWITCHES
1. Electric loads greater than 30amps: Heavy-duty, padlockable, 600-volt or 250-volt and number of poles as required, quick-make, quick-break operating mechanism, dual cover interlock, Lock-out/Tagout ability, as manufactured by Square D Class 3100 or equivalent.
2. Electric loads 30amps or less: Switched disconnects suitable for motor disconnects with 600-volt or 250-volt and number of poles as required, handle interlock preventing cover removal when switch is in the ON position, as manufactured by Square D #MD3304X, Hubbell #HBL78XXX series or equivalent.
B. GROUNDING AND BONDING
1. Ground clamps, fittings and connectors:
2. Non-utility locations: Bronze pressure clamps.
3. Provide grounding and bonding per the OESC. Permanently ground non-current-carrying metallic parts: raceway systems, supports, cabinets, switchboards, panel boards, transformers, lighting fixtures, and metal equipment housings.
4. Provide an insulated equipment grounding conductor sized per Article 250 of the OESC in all branch-circuit runs. Where isolated ground receptacles or connections are shown, install and terminate an isolated ground conductor along with the circuit conductors and equipment ground conductor.
5. Measure the resistance of the grounding electrode system to true ground using approved testing methods. Where the resistance exceeds 25 ohms, install additional properly spaced ground rods until the resistance is measured to be below 25 ohms.
6. Install bond conductors and provide bonding to the following items:
7. All distribution equipment enclosures including switchboards, distribution boards, panel boards, motor control centers and motor control panels
8. Structural steel columns
9. Metallic cold water and fire protection mains and entrances of each system into each building
10. All bonding and grounding connections shall accessible for testing, unless otherwise noted.
PROJECT SPECIFICATIONS ELECTRICAL DISTRIBUTION
A. PANELBOARDS
1. Panelboards shall be minimum 20” wide with 5” gutter space all around, constructed of Code-gauge galvanized steel and shall be flush or surface mounted as shown on the Drawings.
2. Provide factory-installed copper bus bars with amps rating and withstand (AIC) bracing as shown on the Drawings. Bus bars shall be factory-tapped for future devices. Provide separate full-size factory-tapped copper ground and insulated 100% rated neutral buses inside the panelboard enclosure.
B. CIRCUIT BREAKERS
1. Typical feeder and branch circuit breakers shall be molded-case, status-indicating, quick-make, quick-break, bolt-on, with voltage, amperage and
AIC ratings as noted on the Drawings.
2. Unless otherwise noted, all circuit breakers are to be new. Where required by existing conditions, the use of reconditioned circuit breakers is to be reviewed by the Engineer, and provided with report of certification and testing from a recognized testing agency, that verifies the recondition breaker has been tested in accordance with and meets manufacturer trip curve and breaker characteristic requirements.
3. Breaker trip mechanisms below 600 amps shall be thermal-magnetic, except for motor-circuit protector (MCP) breakers, which shall be adjustable magnetic trip.
4. Breakers 600 amps and above shall be electronic trip equal to Square D Micrologic Standard Function with adjustable long, short and instantaneous trip settings.
5. Breakers noted to be 100% rated and/or ground-fault shall be electronic trip equal to Square D Micrologic Full Function with adjustable long, short and instantaneous trip settings.
6. Multiple-pole breakers shall be single-handle type which interrupt all poles upon trip.
7. Provide circuit breaker with red hand and “Fire Alarm Circuit” marking per the requirements of NFPA 72, for each fire alarm system control and extender panel circuit disconnecting means.
8. Provide HACR Heating, Air Conditioning and Refrigeration rated breakers where mechanical equipment is UL-listed with such breakers and fuses are not provided for the equipment.
9. Provide labeled SWD switching duty breakers for night-light circuits and other circuits to be used as switching devices.
10. Provide GFCI breakers with “push-to-test” buttons for wet location circuits without integral GFCI protection or where shown on the Drawings.
C. FUSES
1. Provide fuses at motor and equipment disconnect switches where required and at control circuits.
2. Fuses rated for maximum 600V and 600A or less shall be equivalent to Bussman FRN or FRS dual-element Class RK-1 rejection type.
LIGHTING AND CONTROLS
A. LIGHT FIXTURES
1. All lighting fixtures to be provided in compliance with ASHRAE 90.1 requirements.
2. Furnish light fixtures as specified on construction documents. Substitutions to specified light fixtures shall be submitted for Engineer approval.
B. EXIT SIGNS AND EMERGENCY LIGHTS
1. Exit signs and emergency lights to be provided with integral 90 minute ni-cad battery backup and integral test switch.
2. Locate emergency lights as noted on plans to provide egress lighting coverage for average 1 footcandle.
3. Provide UL924 emergency lighting relays as…