J-07_Electrical.pdf

PDF 6 MB Posted

Attached to
Wellpinit Service Unit Modernization Project Federal contract opportunity
Solicitation number
16-102-SOL-00031
Issued by
Department of Health and Human Services Indian Health Service

About this file

J-07 Electrical

View the file

Other files for this federal contract opportunity

Other files attached to Wellpinit Service Unit Modernization Project, newest first.
File Type Posted
Amendment_0008_SF30.pdf PDF
Construction_Wage_Determination_MOD_07.pdf PDF
Amendment_0007_SF30.pdf PDF
J-_12_Wellpinit_Service_Unit_Clinic_RBM_Report_Sept_2014.pdf PDF
Amendment_0006_SF30.pdf PDF
Site_Walk_Attendance_Sheet.pdf PDF
Amendment_0005_SF30.pdf PDF
Amendment_0004_SF30.pdf PDF
J-11__Amendment_on_Sheet_No__E-101.pdf PDF
J-10_Construction_Wage_Determination..pdf PDF
Amendment_0003_SF30.pdf PDF
Amendment_0002_SF30.pdf PDF
J-04_Architectural_2_of_2_Rev_1.pdf PDF
Amendment_0001_SF30.pdf PDF
J-02_Specifications.pdf PDF
Solicitation_16-102-SOL-00031.pdf PDF
J-06_Mechanical_2_of_2.pdf PDF
J-03_Architectural_1_of_2.pdf PDF
J-04_Architectural_2_of_2.pdf PDF
J-_05_Mechanical_1_of_2.pdf PDF
J-_01_Contract_Requirements.pdf PDF
J-09_PPI.doc DOC document
Show all 22

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

U. S. DEPARTMENT

OF HEALTH AND

HUMAN SERVICES

a,b,c

DE

NNIS J. ZIMMER ST

ATE OF WASHINGTON

REGISTER ED

PR

O

FESSIONAL ENGIN

EE

R

44924

AutoCAD SHX Text

DRAWING LIST

AutoCAD SHX Text ELECTRICAL E001 GENERAL NOTES AND LEGEND E002 OVERALL LIGHTING & POWER PLAN - DEMO E003 OVERALL LIGHTING & POWER PLAN - NEW - NEW E101 IT PHASE 0 OVERALL COMMUNICATIONS PLAN IT PHASE 0 OVERALL COMMUNICATIONS PLAN E102 IT PHASE 0 COMMUNICATIONS ENLARGED PLANS & DETAILS IT PHASE 0 COMMUNICATIONS ENLARGED PLANS & DETAILS E103 PHASE 1 RECORDS/RECEPTION AREA LIGHTING & POWER PLAN PHASE 1 RECORDS/RECEPTION AREA LIGHTING & POWER PLAN PHASE 1 RECORDS/RECEPTION AREA LIGHTING & POWER PLAN E104 PHASE 2A WORKSTATIONS AND BREAKROOM LTG & POWER PLANS PHASE 2A WORKSTATIONS AND BREAKROOM LTG & POWER PLANS E105 PHASE 2B MEDICAL TEAMING AREA LTG & POWER PLANS PHASE 2B MEDICAL TEAMING AREA LTG & POWER PLANS E106 PHASE 3 PHARMACY/IMAGING LTG & POWER PLANS PHASE 3 PHARMACY/IMAGING LTG & POWER PLANS E107 NOT USED NOT USED E108 PHASE 2B MAIN FLOOR POWER PLAN PHASE 2B MAIN FLOOR POWER PLAN E109 PHASE 4 LABORATORY LIGHTING & POWER PLANPHASE 4 LABORATORY LIGHTING & POWER PLAN

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text A

AutoCAD SHX Text B

AutoCAD SHX Text C

AutoCAD SHX Text A

AutoCAD SHX Text B

AutoCAD SHX Text C

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

REV

AutoCAD SHX Text

ISSUE:

AutoCAD SHX Text

PROJECT NO:

AutoCAD SHX Text

CAD DWG FILE:

AutoCAD SHX Text

DRAWN BY:

AutoCAD SHX Text

CHECKED BY:

AutoCAD SHX Text

SHEET TITLE

AutoCAD SHX Text

DATE

AutoCAD SHX Text

DESCRIPTION

AutoCAD SHX Text

CONSULTANTS

AutoCAD SHX Text

INDIAN HEALTH SERVICE

AutoCAD SHX Text

DIVISION OF ENGINEERING SERVICES

AutoCAD SHX Text E

AutoCAD SHX Text H

AutoCAD SHX Text N

AutoCAD SHX Text M

AutoCAD SHX Text E

AutoCAD SHX Text A

AutoCAD SHX Text R

AutoCAD SHX Text P

AutoCAD SHX Text T

AutoCAD SHX Text O

AutoCAD SHX Text F

AutoCAD SHX Text T

AutoCAD SHX Text C

AutoCAD SHX Text D

AutoCAD SHX Text S

AutoCAD SHX Text U

AutoCAD SHX Text S

AutoCAD SHX Text A

AutoCAD SHX Text E

AutoCAD SHX Text T

AutoCAD SHX Text A

AutoCAD SHX Text E

AutoCAD SHX Text L

AutoCAD SHX Text

AutoCAD SHX Text H

AutoCAD SHX Text N

AutoCAD SHX Text V

AutoCAD SHX Text I

AutoCAD SHX Text S

AutoCAD SHX Text E

AutoCAD SHX Text R

AutoCAD SHX Text U

AutoCAD SHX Text M

AutoCAD SHX Text A

AutoCAD SHX Text H

AutoCAD SHX Text

SEATTLE / DALLAS

AutoCAD SHX Text

DES BRANCH CHIEF

AutoCAD SHX Text

DES PROJECT MANAGER

AutoCAD SHX Text

AGENCY REPRESENTATIVE

AutoCAD SHX Text

APPROVED:

AutoCAD SHX Text

CONCURRENCE

AutoCAD SHX Text

TITLE

AutoCAD SHX Text

REVIEWED:

AutoCAD SHX Text

DES ARCHITECT / ENGINEER

AutoCAD SHX Text

DATE

AutoCAD SHX Text

DATE

AutoCAD SHX Text

DATE

AutoCAD SHX Text

DATE

AutoCAD SHX Text

SHEET ______ OF ______

AutoCAD SHX Text 12 W. Kennewick Ave

AutoCAD SHX Text Kennewick, WA 99336

AutoCAD SHX Text P: 509.735.1589

AutoCAD SHX Text F: 509.783.5075

AutoCAD SHX Text www.meierinc.com

AutoCAD SHX Text

PROJECT NO: 16-7936

AutoCAD SHX Text WELLPINIT SERVICE UNIT MODERNIZATION 6203 AGENCY LOOP ROAD WELLPINIT, WASHINGTON 99040 PROJECT NUMBER PO4WE626C0PO4WE626C0

AutoCAD SHX Text

PO4WE648C0

AutoCAD SHX Text

1. THIS INSTALLATION SHALL COMPLY WITH THE REQUIREMENTS OF THE NATIONAL THIS INSTALLATION SHALL COMPLY WITH THE REQUIREMENTS OF THE NATIONAL ELECTRICAL CODE (NFPA-70, '08 EDITION) AS AMENDED BY WAC (OESC) 296-46B (918-305). CONTRACTOR SHALL BE FAMILIAR WITH, LICENSED TO PERFORM AND EXPERIENCED WITH SUCH WORK INDICATED HEREIN, AND BE QUALIFIED TO MEET MOST RECENT OSHA CERTIFICATION TO WORK ON ENERGIZED EQUIPMENT. CONTRACTOR IS RESPONSIBLE FOR DETERMINING SAFETY REQUIREMENTS; REFER TO AND COMPLY WITH OSHA 29CFR.1910 AND 1926 ELECTRICAL SAFETY PORTIONS AS AMENDED BY WISHA PER WAC 296-800-100. CONTRACTOR RESPONSIBLE FOR DETERMINING CONSTRUCTION METHOD AND MEANS REQUIREMENTS. 2. CONTRACTOR SHALL OBTAIN AND PAY FOR ALL PERMITS AND FEES REQUIRED CONTRACTOR SHALL OBTAIN AND PAY FOR ALL PERMITS AND FEES REQUIRED BY ANY GOVERNMENT AGENCY HAVING JURISDICTION OVER THE WORK AND SHALL BE IN COMPLIANCE WITH SAID AGENCY STANDARDS AND SHALL ARRANGE ALL INSPECTIONS REQUIRED BY THESE AGENCIES. 3. ALL WORK SHALL BE PERFORMED IN A NEAT AND WORKMANLIKE MANNER ALL WORK SHALL BE PERFORMED IN A NEAT AND WORKMANLIKE MANNER WITHIN STANDARD OF CARE FOR PROFESSION PER NEC 110.12 AND NECA-1. ALL LABOR, MATERIAL, TOOLS, PERMITS, ETC. REQUIRED FOR A COMPLETE AND SATISFACTORY INSTALLATION TO DESIGN INTENT SHALL BE FURNISHED BY THIS CONTRACTOR. PROVIDE, AT NO ADDITIONAL COST, INCIDENTAL ITEMS NOT SHOWN WHEN REQUIRED FOR COMPLETION OF WORK. SPECIFICATIONS AND PLAN DRAWINGS ARE TO BE TAKEN TOGETHER AND UNDERSTOOD AS ONE. 4. ANY/ALL ELECTRICAL SHUTDOWNS REQUIRED TO COMPLETE THE WORK ANY/ALL ELECTRICAL SHUTDOWNS REQUIRED TO COMPLETE THE WORK OUTLINED ON THESE DRAWINGS SHALL BE THE RESPONSIBILITY OF THE ELECTRICAL CONTRACTOR. SHUTDOWNS SHALL BE KEPT TO A MINIMUM AND COORDINATED THROUGH THE OWNER'S REPRESENTATIVE. 5. PROVIDE UPDATED TYPE WRITTEN CIRCUIT DIRECTORIES AT ALL PANELS PROVIDE UPDATED TYPE WRITTEN CIRCUIT DIRECTORIES AT ALL PANELS AFFECTED UPON PROJECT COMPLETION. 6. BY THE ACT OF SUBMITTING A BID THE CONTRACTOR SHALL BE DEEMED TO BY THE ACT OF SUBMITTING A BID THE CONTRACTOR SHALL BE DEEMED TO HAVE EXAMINED THE SITE AND ALL STRUCTURAL, ARCHITECTURAL, MECHANICAL AND ELECTRICAL DRAWINGS AND TO HAVE ACCEPTED EXISTING CONDITIONS AND INCLUDED ALLOWANCES FOR THEM IN THE BID. ANY CONTRADICTIONS, DISCREPANCIES OR DESIGN WORK WHICH DOES NOT MEET CODE OR WILL NOT FUNCTION AS INTENDED SHALL BE REPORTED TO THE ENGINEER IN WRITING PRIOR TO THE BID. IF CONTRACTOR DOES NOT REPORT ANY DISCREPANCIES THEN CONTRACTOR WILL BE HELD RESPONSIBLE FOR COMPLETE ELECTRICAL SYSTEM AND MAKE ANY REQUIRED CHANGES AT NO ADDITIONAL COST. 7. THE GENERAL ARRANGEMENT OF OUTLETS AND OTHER EQUIPMENT AS SHOWN THE GENERAL ARRANGEMENT OF OUTLETS AND OTHER EQUIPMENT AS SHOWN ON THE PLANS IS DIAGRAMMATIC AND APPROXIMATELY CORRECT AS TO LOCATIONS. WHERE MINOR CHANGES ARE REQUIRED BECAUSE OF STRUCTURAL CONDITIONS OR FOR THE CONVENIENCE OF THE OWNER, SUCH CHANGES SHALL BE MADE AT THE CONTRACTORS EXPENSE. THE CONTRACTOR SHALL BE RESPONSIBLE FOR THE ACCURATE LOCATION OF ALL LIGHTING FIXTURES, OUTLETS, ETC. WITH RESPECT TO EQUIPMENT, DOORS, PARTITIONS, CABINETS, ETC. 8. ALL MOUNTING HEIGHTS ARE FROM FINISH FLOOR TO CENTER OF DEVICE OR ALL MOUNTING HEIGHTS ARE FROM FINISH FLOOR TO CENTER OF DEVICE OR LIGHTING FIXTURE, UNLESS NOTED OTHERWISE. METAL FRAMING MEMBERS PRESENT: COMPLY WITH NEC 300.4 & 330.30 FOR CONDUIT & BOX ATTACHMENTS AND SUPPORT. PROVIDE ERICO CADDY STUD WALL FAMILY OF PRODUCTS (OR EQUAL) FOR BETWEEN STUD APPLICATIONS. FOR MULTI-GANG INSTALLATIONS USE RIGID STUD-TO-STUD BOX BRACKET. MOUNTING HEIGHTS SHALL BE AS FOLLOWS, UNLESS NOTED OTHERWISE: SWITCHES +48", RECEPTACLES +18", PHONE/DATA/TV 18" AND THERMOSTATS +54" 9. INSULATED COPPER CONDUCTOR TYPES (THWN/THHN/XHHW ) SHALL BE UL INSULATED COPPER CONDUCTOR TYPES (THWN/THHN/XHHW ) SHALL BE UL LISTED, 600V RATED, AND CONSTRUCTED TO NEMA/ICEA STANDARDS; GROUNDED (N) CONDUCTORS IDENTIFIED PER NEC 200.6 WHITE/GREY; EQUIPMENT GROUNDING CONDUCTORS (GND) IDENTIFIED PER NEC 250.119 GREEN/YELLOW OR BARE; UNGROUNDED CONDUCTORS IDENTIFIED PER NEC 210.5(C)-BRANCH CIRCUITS AND 215.12-FEEDERS IN ACCORDANCE WITH NEC 200.7, COLOR CODE PER PHASE-BLACK, RED FOR 240V BLACK, RED AND BLUE FOR 208Y/120V, BROWN, PURPLE, YELLOW FOR 480Y/277V. ALL INSULATED CONDUCTORS SHALL BE SURFACE MARKED PER NEC 310.11(B)(1). BARE GROUNDS SHALL BE SUITABLY PROTECTED PER NEC 250.64(B). IDENTIFY SWITCH LEGS OR TRAVELERS READILY DISTINGUISHABLE FROM OTHER CONDUCTORS. CONDUCTORS OF EACH MULTIWIRE BRANCH CIRCUIT SHALL BE GROUPED BY COLORED WIRE TIE WITHIN PANEL. 10. UNLESS NOTED OTHERWISE, EQUIPMENT WITH CIRCUIT AND PANEL UNLESS NOTED OTHERWISE, EQUIPMENT WITH CIRCUIT AND PANEL IDENTIFICATION ARE 3-12AWG FOR 20A; 120V CIRCUITS GREATER THAN 100' IN LENGTH TO BE 10 AWG. SWITCH AND OUTLET TERMINATIONS MADE WITH SCREW TERMINALS (NO STAB-INS); WHERE MANUFACTURER'S TORQUE REQUIREMENTS ARE NOT INDICATED, AT A MINIMUM, TIGHTEN CONNECTORS AND TERMINALS TO COMPLY WITH TIGHTENING TORQUES SPECIFIED IN UL STANDARDS 486A AND B, AND NEC ARTICLE 110.14 TABLES 1.3 TO 1.6. 11. ALL CONDUCTORS TO HAVE TYPE THWN/THHN INSULATION AND ARE 12 AWG ALL CONDUCTORS TO HAVE TYPE THWN/THHN INSULATION AND ARE 12 AWG UNLESS NOTED OTHERWISE. ALL RACEWAYS, TUBING OR CONDUITS SHALL HAVE SEPARATE CONTINUOUS “GREEN” INSULATED EQUIPMENT GROUNDING CONDUCTOR GREEN” INSULATED EQUIPMENT GROUNDING CONDUCTOR INSULATED EQUIPMENT GROUNDING CONDUCTOR (EGC) OF APPROVED COPPER TYPE PER 250.118(1), IDENTIFIED PER 250.119, INSTALLED PER NEC 250.120, MINIMALLY SIZED PER 250.122 (UNLESS UPSIZED FOR PARALLEL OR ADJUSTMENT APPLICATIONS), TERMINATED AS APPLICABLE PER 250.86, .96, .110, AND .112 AND FOR FEEDERS OR THROUGH OTHER BUILDINGS PER 250.134 OR 250.32(B) ESTABLISHING AN EFFECTIVE GROUND-FAULT CURRENT PATH THROUGH THE NORMALLY NON-CURRENT-CARRYING EQUIPMENT GROUNDING CONDUCTORS (EGC). CONTACTOR SHALL, IN ADDITION, INTENTIONALLY CONSTRUCT CONTINUOUS LISTED METALLIC RACEWAY SYSTEMS IN A MANNER THAT ESTABLISHES AN EFFECTIVE GROUND-FAULT CURRENT PATH ALONG THE ENTIRE RACEWAY ACTING AS ANOTHER REDUNDANT EGC OF APPROVED TYPE PER 250.118(2 THROUGH 14), INSTALLED PER NEC 250.96, AND TERMINATED PER 300.10. 12. MINIMUM CONDUIT SIZE SHALL BE 1/2" UNLESS NOTED OTHERWISE ON THE MINIMUM CONDUIT SIZE SHALL BE 1/2" UNLESS NOTED OTHERWISE ON THE DRAWINGS AND INSTALLED PER NECA-101. RACEWAYS SHALL BE RUN CONCEALED IN OFFICE AND FINISHED AREAS OF NEW CONSTRUCTION. WHERE CONDITIONS DICTATE (EXISTING MASONRY WALLS), EXPOSED SURFACE RACEWAY SHALL BE RIGID RGS RUN PARALLEL OR PERPENDICULAR TO BUILDING LINES. WIREMOLD SHALL BE USED ONLY WITH WRITTEN PERMISSION OF OWNER OR ENGINEER. 13. INTERIOR CONDUITS RUN CONCEALED TO BE ELECTRICAL METALLIC TUBING, INTERIOR CONDUITS RUN CONCEALED TO BE ELECTRICAL METALLIC TUBING, FINAL RACEWAY CONNECTIONS TO EQUIPMENT TO BE FLEXIBLE METALLIC CONDUIT, OR AS ALLOWED BY THE NEC. EXTERIOR UNDERGROUND CONDUITS TO BE RIGID PVC OR PVC-COATED RIGID METALLIC CONDUIT. EXPOSED CONDUITS SHALL BE MOUNTED SECURELY BY SUITABLE HANGERS OR STRAPS WITH MINIMUM SPACING PER NEC 352.30. EXPOSED EXTERIOR CONDUITS WHERE TEMPERATURE CHANGE LARGER THAN 15°C (25°F) IS FEASIBLE; PROVIDE LISTED EXPANSION FITTINGS PER NEC 300.7(B) (PROTECT 1/4” OF STEEL OF STEEL EXPANSION FOR EVERY 200' LENGTH AT 15°C CHANGE) OR 352.44 (PROTECT 1/4” OF PVC EXPANSION FOR EVERY 40' LENGTH AT 15°C CHANGE). OF PVC EXPANSION FOR EVERY 40' LENGTH AT 15°C CHANGE). 14. ALL PULL, JUNCTION, AND SPLICE BOXES SHALL BE SIZED, FURNISHED AND ALL PULL, JUNCTION, AND SPLICE BOXES SHALL BE SIZED, FURNISHED AND INSTALLED PER THE NATIONAL ELECTRICAL CODE WHETHER INDICATED OR NOT. LABEL EACH INTERMEDIATE J-BOX COVER FACE WITH PANEL AND BRANCH CIRCUITS PRESENT; LEGIBLY WRITTEN WITH PERMANENT BLACK MARKER. 15. SEAL ALL BUILDING PENETRATIONS WITH SILICONE SEALANT PER NEC 300.7(A). SEAL ALL BUILDING PENETRATIONS WITH SILICONE SEALANT PER NEC 300.7(A). WHERE CONDUITS PENETRATE A FIRE-RATED WALL, FLOOR OR CEILING, THE OPENING AROUND THE CONDUIT SHALL BE SEALED PER NEC 300.21 WITH CAULK CP 25 OR PUTTY 303 AS MANUFACTURED BY 3M OR EQUAL. ALL GFCI RECEPTACLE DEVICES IN EITHER WET OR DAMP LOCATIONS SHALL BE WR RATED AND HAVE LISTED "IN-USE" WP-COVER PER NEC.406.8. 16. ALL COMPONENTS, DEVICES, MATERIALS AND EQUIPMENT FURNISHED OR ALL COMPONENTS, DEVICES, MATERIALS AND EQUIPMENT FURNISHED OR PROVIDED UNDER THIS SECTION SHALL BE NEW AND ORIGINAL, MANUFACTURED WITHIN THE LAST TWO YEARS, LISTED AND LABELED PER NEC 90.7 AND 110.3 TO U.L. OR EQUIVALENT FOR ITS INTENDED PURPOSE, SUITABLE FOR ITS USE AND SHALL COMPLY WITH SPECIFICATIONS, DRAWINGS AND GENERAL CONDITIONS AND SHALL BE INSTALLED PER MANUFACTURER'S WRITTEN INSTRUCTIONS, OPERATE PER DESIGN INTENT, BE UNDAMAGED AND HAVE MANUFACTURER'S FULL WARRANTY IN EFFECT AT THE DATE OF FINAL ACCEPTANCE OF THIS WORK. 17. LIGHTING FIXTURES SHALL BE INSTALLED IN ACCORDANCE WITH U.L. FIRE LIGHTING FIXTURES SHALL BE INSTALLED IN ACCORDANCE WITH U.L. FIRE RESISTANCE DIRECTORY GUIDELINES FOR RECESSED LIGHTING FIXTURES. PROVIDE I.C. RATED LIGHT FIXTURES WHERE INSTALLED IN DIRECT CONTACT WITH INSULATION PER NEC 410.116. 18. RE-USE EXISTING CONDUITS AND CIRCUITS WHERE APPLICABLE. ANY RE-USE EXISTING CONDUITS AND CIRCUITS WHERE APPLICABLE. ANY COMPONENT TO REMAIN THAT IS DAMAGED DURING CONSTRUCTION SHALL BE REPLACED. 19. NEW TELEPHONE/DATA OUTLETS TO BE 4" SQUARE, 2 1/2" DEEP BOX WITH NEW TELEPHONE/DATA OUTLETS TO BE 4" SQUARE, 2 1/2" DEEP BOX WITH SINGLE GANG MUD RING. STUB ONE(1) 1" CONDUIT WITH PULLWIRE FROM BOX INTO ACCESSIBLE CEILING SPACE, WITH 90° BEND AND PLASTIC BUSHING. WITHIN EXISTING WALL SPACES WITH LIMITED ACCESS, SUCH AS BELOW WINDOWS, LIMITED USE OF ENT WITH FITTINGS LISTED FOR THE PURPOSE IS AN ACCEPTABLE ALTERNATIVE TO EMT WHERE NEC 362 ALLOWS. 20. ELECTRICAL CONTRACTOR SHALL NOT PERFORM ANY ADDITIONAL WORK RELATED ELECTRICAL CONTRACTOR SHALL NOT PERFORM ANY ADDITIONAL WORK RELATED CHANGES” IMPLIED, SUGGESTED OR DIRECTED BY ANY INSPECTOR NOTED IMPLIED, SUGGESTED OR DIRECTED BY ANY INSPECTOR NOTED FAILURE WITHOUT FIRST DOCUMENTING THE INSPECTOR’S SPECIFIC S SPECIFIC CODE-RELATED ISSUE, CITING THE EXACT GOVERNING CODE SECTION, INSPECTOR’S CONTACT INFORMATION, ASSOCIATED LOCATION AND DRAWING, AND S CONTACT INFORMATION, ASSOCIATED LOCATION AND DRAWING, AND NOTIFYING PROJECT COR VIA IMMEDIATE RFI PROCESS, ON A CASE-BY-CASE BASIS; NO CHANGES OR ADDITIONAL COSTS ARE AUTHORIZED UNLESS COR IS PROPERLY NOTIFIED AND APPROVES SUCH IN ADVANCE. 21. PROJECT INVOLVES RE-USE OF EXISTING FEEDERS, PANELS AND ELECTRICAL PROJECT INVOLVES RE-USE OF EXISTING FEEDERS, PANELS AND ELECTRICAL DEVICES; CONTRACTOR SHALL VISUALLY INSPECT ALL SUCH OCCURRENCES TO ASSURE GOOD CONDITIONS ARE PRESENT AND SUCH ARRANGEMENTS MEETS CURRENT NEC AND WA WAC PARAMETERS; REPORT ANY DISCOVERED ELECTRICAL DISCREPANCY IN WRITING TO GENERAL CONTRACTOR IN TIMELY MANNER FOR DISPOSITION. ADDITIONAL WORK SHALL PROCEED ONLY WITH WRITTEN APPROVAL FROM GENERAL CONTRACTOR. 22. BRANCH CIRCUITRY IN PATIENT CARE AREAS SHALL COMPLY WITH NATIONAL BRANCH CIRCUITRY IN PATIENT CARE AREAS SHALL COMPLY WITH NATIONAL ELECTRICAL CODE ARTICLES 517.13 AND 517.61(C)(2). 23. TAMPER RESISTANT RECEPTACLES TO BE INSTALLED WHERE REQUIRED PER NEC TAMPER RESISTANT RECEPTACLES TO BE INSTALLED WHERE REQUIRED PER NEC ARTICLE 517.18(C). TAMPER RESISTANT (TR) RECEPTACLE, TYPICAL EXAM ROOM LAYOUT. TR RECEPTACLES TO BE PROVIDED IN ALL AREAS WHERE YOUNG PATIENTS MAY HAVE ACCESS (I.E. EXAM AND PROCEDURE ROOMS, PLAYROOMS, CORRIDORS, RESTROOMS). 24. WIRING METHOD; LIMITED USE OF TYPE MC OR AC CABLE, WHERE NEC ALLOWS WIRING METHOD; LIMITED USE OF TYPE MC OR AC CABLE, WHERE NEC ALLOWS (TYPE MC CABLE PER ARTICLE 330, TYPE AC CABLE PER ARTICLE 320), IS PERMISSIBLE ON THIS PROJECT WHERE NOT BURIED OR SUBJECT TO PHYSICAL DAMAGE BUT IS FURTHER RESTRICTED IN USE TO DOWNSTREAM OF INDIVIDUAL BRANCH CIRCUIT HOME-RUN; 120 VOLT 20 AMP OR LESS AND MUST CONTAIN SEPARATE EGC WIRE OR ITS APPROVED EQUIVALENT. 25. MEDICAL TREATMENT AREA HAS AN EXISTING SOUND MASKING SYSTEM WITH 34 MEDICAL TREATMENT AREA HAS AN EXISTING SOUND MASKING SYSTEM WITH 34 HARDWIRED SPEAKERS AND SOUND GENERATOR. RESTORE TO WORKING ORDER IF DISTURBED DURING CONSTRUCTION.

AutoCAD SHX Text

GENERAL NOTES

AutoCAD SHX Text

LEGEND

AutoCAD SHX Text

1. ELECTRICAL CONTRACTOR SHALL NOT PERFORM ANY ADDITIONAL WORK RELATED ELECTRICAL CONTRACTOR SHALL NOT PERFORM ANY ADDITIONAL WORK RELATED "CHANGES" IMPLIED, SUGGESTED OR DIRECTED BY ANY INSPECTOR NOTED FAILURE IMPLIED, SUGGESTED OR DIRECTED BY ANY INSPECTOR NOTED FAILURE WITHOUT FIRST DOCUMENTING THE INSPECTOR'S SPECIFIC CODE-RELATED ISSUE, CITING THE EXACT GOVERNING CODE SECTION, INSPECTOR'S CONTACT INFORMATION, ASSOCIATED LOCATION & DRAWING, AND NOTIFYING PROJECT COR VIA IMMEDIATE RFI PROCESS, ON A CASE-BY-CASE BASIS; NO CHANGES OR ADDITIONAL COSTS ARE AUTHORIZED UNLESS COR IS PROPERLY NOTIFIED & APPROVES SUCH IN ADVANCE.

AutoCAD SHX Text

INSPECTION NOTE

AutoCAD SHX Text

1. WHERE APPLICABLE, LIGHTING CONTROLS COMMISSIONING SHALL BE PERFORMED PER THE WHERE APPLICABLE, LIGHTING CONTROLS COMMISSIONING SHALL BE PERFORMED PER THE MOST RECENTLY APPROVED VERSION OF WASHINGTON STATE ENERGY CODE SECTION 1513.7. CONTROLS SHALL BE TESTED TO ENSURE THE SENSORS AND DEVICES ARE CALIBRATED, ADJUSTED AND OPERATE SATISFACTORILY WITHIN APPROVED SEQUENCE OF OPERATION IN ACCORDANCE WITH THE PLANS AND SPECIFICATIONS. A SATISFACTORY COMPLETED REPORT OF TEST PROCEDURES AND DATED/SIGNED RESULTS SHALL BE PREPARED AND FILED WITH THE OWNER PRIOR TO CLOSEOUT BY THIS CONTRACTOR.

AutoCAD SHX Text

NREC NOTES

AutoCAD SHX Text LIGHTING: LIGHTING FIXTURE (GRID/RECESSED) (LETTER INDICATES FIXTURE TYPE) LIGHTING FIXTURE (SURFACE) (LETTER INDICATES FIXTURE TYPE) LIGHTING FIXTURE (CAN TYPE) (LETTER INDICATED FIXTURE TYPE) 1-POLE SWITCH, 120-277VAC, 20-AMP (D=DIMMER, 3=3-WAY, 3D=3-WAY DIMMER, 4=4-WAY, C=CLOSET, K=KEYED, OC=OCCUPANCY SENSOR, M=MOTOR, AND T=TWIST-TYPE TIMER) LOWER CASE LETTERS INDICATE SWITCHING CONFIGURATION. CEILING MOUNTED OCCUPANCY SENSOR POWER: DUPLEX RECEPTACLE FLOOR RECEPTACLE QUADRUPLE RECEPTACLE DENOTES PANEL & CIRCUIT DESIGNATION ELECTRICAL PANEL (120/240V OR 120/208) COMMUNICATIONS OUTLET FLOOR COMMUNICATIONS OUTLET TELEPHONE OUTLET TELEVISION OUTLET CONDUIT/WIRE RUN UNDERGROUND/BELOW FLOOR CONDUIT RUN SPECIAL SYSTEMS: FIRE ALARM PULLSTATION FIRE ALARM COMBINATION HORN/STROBE FIRE ALARM STROBE PHOTO ELECTRIC SMOKE DETECTOR SPEAKER (ABOVE CEILING) (SOUND MASK) SPEAKER TRANSFORMER (ABOVE CEILING) SECURITY KEYPAD/BUTTON NURSE CALL CORRIDOR LIGHT NURSE CALL PULL CORD (WP = GASKETED FACEPLATE) SPEAKER (CEILING MOUNT) (INTERCOM) INTERCOM WALL MOUNT INTERCOM HUB ABBREVIATIONS: WEATHER PROOF (NEMA-3R ENCLOSURE OR BOX) ABOVE FINISH FLOOR UNLESS NOTED OTHERWISE WIREMOLD OR PLUGMOLD EXISTING TO REMAIN EXISTING TO BE REMOVED, INCLUDING ALL ASSOCIATED CONDUIT AND WIRING BACK TO POINT OF FEED EXISTING TO BE RELOCATED EXISTING AS RELOCATED, EXTEND EXISTING CONDUIT AND WIRING TO NEW LOCATION AND RECONNECT EXTEND BRANCH CIRCUIT WIRING TO NEW LOCATION AS INDICATED ABANDON IN PLACE PREVIOUSLY ABANDONED IN PLACE

AutoCAD SHX Text A

AutoCAD SHX Text A

AutoCAD SHX Text A

AutoCAD SHX Text D.1

AutoCAD SHX Text S

AutoCAD SHX Text D

AutoCAD SHX Text S

AutoCAD SHX Text F

AutoCAD SHX Text F

AutoCAD SHX Text F

AutoCAD SHX Text

OC

AutoCAD SHX Text (R)

AutoCAD SHX Text (E)

AutoCAD SHX Text

(TBR)

AutoCAD SHX Text

(ER)

AutoCAD SHX Text

(EX)

AutoCAD SHX Text

WP

AutoCAD SHX Text

AFF

AutoCAD SHX Text U.N.O.

AutoCAD SHX Text

(AP)

AutoCAD SHX Text

(AB)

AutoCAD SHX Text X

AutoCAD SHX Text E-O01

AutoCAD SHX Text 793600E001

AutoCAD SHX Text

GENERAL NOTES & LEGEND

AutoCAD SHX Text

RWS

AutoCAD SHX Text

DJZ

AutoCAD SHX Text

WM

AutoCAD SHX Text C

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text

PO4WE626C0

AutoCAD SHX Text MATCH EXISTING STAINLESS FACE PLATES FOR RECEPTACLES, LIGHT SWITCHES, NURSE CALL AND DATA, TYP

AutoCAD SHX Text I

AutoCAD SHX Text H

AutoCAD SHX Text 32 4242

AutoCAD SHX Text 07/22/2016

AutoCAD SHX Text 07/22/16

HUMAN SERVICES

DE

NNIS J. ZIMMER ST

ATE OF WASHINGTON

R EGISTER ED

PR

O

FESSIONAL ENGIN

EE

R

44924

AutoCAD SHX Text

HWH

AutoCAD SHX Text

AHU-5

AutoCAD SHX Text

AHU-1

AutoCAD SHX Text

AHU-4

AutoCAD SHX Text

AHU-3

AutoCAD SHX Text

REF

AutoCAD SHX Text

AHU-2

AutoCAD SHX Text

REF

AutoCAD SHX Text

REF

AutoCAD SHX Text

REF

AutoCAD SHX Text

DRYER

AutoCAD SHX Text

WASHER

AutoCAD SHX Text

WH

AutoCAD SHX Text

LINENS

AutoCAD SHX Text

ADMINISTRATION BASEMENT

AutoCAD SHX Text

FIRE RISER

AutoCAD SHX Text

DN

AutoCAD SHX Text

DN

AutoCAD SHX Text

DN

AutoCAD SHX Text

UP

AutoCAD SHX Text

UP

AutoCAD SHX Text

DN

AutoCAD SHX Text

(E)PANEL/IMAPANEL/IMA

AutoCAD SHX Text

(E)PANEL/IMB PANEL/IMB (CUTLER-HAMER PRL) SEE NOTE-1

AutoCAD SHX Text

(E)PANEL/IMC PANEL/IMC SEE NOTE-1

AutoCAD SHX Text

(E)PANEL/IPPANEL/IP

AutoCAD SHX Text

(E)FA J-BOX

AutoCAD SHX Text

(E)ACCESS TO CRAWL SPACE BELOW

AutoCAD SHX Text

(E)SECURITY J-BOX

AutoCAD SHX Text

(AB)TMB

AutoCAD SHX Text

(E)PANEL/IDPANEL/ID

AutoCAD SHX Text

(E)PANEL/A2 PANEL/A2 SEE NOTE-1

AutoCAD SHX Text

(E)PANEL/A3PANEL/A3

AutoCAD SHX Text

SCP

AutoCAD SHX Text

FACP (SILENT KNIGHT 5208)

AutoCAD SHX Text

LTG CP

AutoCAD SHX Text

(E)PANEL/MDPPANEL/MDP

AutoCAD SHX Text

(E)CONDUIT CHASE

AutoCAD SHX Text

(E)PANEL/B5 PANEL/B5 (SIEMENS P1) SEE NOTE-1

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text

OC

AutoCAD SHX Text

(TBR)SECURITY SECURITY SUB-PANEL

AutoCAD SHX Text

(AB)PHONE J-BOX

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text 204C

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text 183A

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

(E)PANEL/IR PANEL/IR (CUTLER-HAMMER PRL)

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

(ER) SECURITY KEYPAD

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text 124A

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text 208A

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

(E)THERMOSTAT

AutoCAD SHX Text

(E)IDF (CRAWLSPACE BELOW)

AutoCAD SHX Text

AutoCAD SHX Text

1. ELECTRICAL DEMOLITION DRAWINGS ARE DIAGRAMMATIC AND INDICATE THE GENERAL INTENT ELECTRICAL DEMOLITION DRAWINGS ARE DIAGRAMMATIC AND INDICATE THE GENERAL INTENT AND SCOPE. DURING FIELD INVESTIGATION, SOME EXISTING ELECTRICAL DEVICES MAY NOT HAVE BEEN LOCATED DUE TO UNMOVABLE FURNITURE AND EQUIPMENT LOCATED AGAINST WALLS. THE ELECTRICAL CONTRACTOR SHALL VERIFY QUANTITIES AND SCOPE OF DEMOLITION WORK IN THE FIELD AND SHALL PROVIDE LABOR AND EQUIPMENT TO COMPLETE THE WORK AS REQUIRED. 2. REFERENCE ARCHITECTURAL AND MECHANICAL DEMOLITION PLANS FOR ADDITIONAL REFERENCE ARCHITECTURAL AND MECHANICAL DEMOLITION PLANS FOR ADDITIONAL ELECTRICAL DEMOLITION WORK REQUIRED THAT MAY NOT BE SPECIFICALLY INDICATED ON ELECTRICAL DEMOLITION. 3. ALL DEMOLISHED MATERIAL SHALL BE REMOVED FROM SITE IN ITS ENTIRETY AND ALL DEMOLISHED MATERIAL SHALL BE REMOVED FROM SITE IN ITS ENTIRETY AND DISPOSED OF BY THE ELECTRICAL CONTRACTOR IN ACCORDANCE WITH ALL APPLICABLE LAWS. CONSULT WITH OWNER ON ANY ITEMS THAT MAY HAVE SIGNIFICANT SALVAGE VALUE. 4. ALL WORK TO BE COORDINATED WITH A BUILDING REPRESENTATIVE. ELECTRICAL OUTAGES ALL WORK TO BE COORDINATED WITH A BUILDING REPRESENTATIVE. ELECTRICAL OUTAGES OF EXISTING CIRCUITS SHALL BE SCHEDULED TO ALLOW FOR PLANNED SHUTDOWN OF EXISTING EQUIPMENT. 5. ANY/ALL ELECTRICAL SHUTDOWNS REQUIRED TO COMPLETE THE DEMOLITION WORK ANY/ALL ELECTRICAL SHUTDOWNS REQUIRED TO COMPLETE THE DEMOLITION WORK OUTLINED ON THESE DRAWINGS SHALL BE THE RESPONSIBILITY OF THE ELECTRICAL CONTRACTOR. SHUTDOWNS SHALL BE COORDINATED THROUGH THE OWNER'S REPRESENTATIVE. 6. BEFORE COMMENCING WITH WORK, ELECTRICAL CONTRACTOR SHALL INSPECT THE PROJECT BEFORE COMMENCING WITH WORK, ELECTRICAL CONTRACTOR SHALL INSPECT THE PROJECT SITE AND DETERMINE THE CONDITIONS UNDER WHICH DEMOLITION IS TO BE ACCOMPLISHED ALONG WITH KIND AND THE AMOUNT OF MATERIALS TO BE REMOVED. 7. TEMPORARILY RELOCATE ELECTRICAL EQUIPMENT AS REQUIRED TO ACCOMMODATE THE TEMPORARILY RELOCATE ELECTRICAL EQUIPMENT AS REQUIRED TO ACCOMMODATE THE CONSTRUCTION SCHEDULE. ALL AREAS NOT UNDER CONSTRUCTION MUST BE KEPT OPERATIONAL DURING CONSTRUCTION AT THE DISCRETION OF THE OWNER. TO ACCOMPLISH THIS, PROVIDE THE NECESSARY TEMPORARY ELECTRICAL SERVICES. REMOVE TEMPORARY DEVICES UPON THE COMPLETION OF CONSTRUCTION. 8. ELECTRICAL CONTRACTOR SHALL PROVIDE TEMPORARY POWER AND LIGHTING AS REQUIRED ELECTRICAL CONTRACTOR SHALL PROVIDE TEMPORARY POWER AND LIGHTING AS REQUIRED DURING THE ENTIRE DURATION OF CONSTRUCTION. THE ELECTRICAL CONTRACTOR SHALL REMOVE ALL TEMPORARY POWER AND LIGHTING UPON COMPLETION OF THE PROJECT. 9. RELOCATE OR REMOVE ALL ELECTRICAL DEVICES IN ACCORDANCE WITH THE NATIONAL RELOCATE OR REMOVE ALL ELECTRICAL DEVICES IN ACCORDANCE WITH THE NATIONAL ELCTRICAL CODE (NEC). WHEN RELOCATION OR REMOVAL OF AN ELECTRICAL DEVICE INTERRUPTS THE CONTINUITY OF A CIRCUIT, REROUTE/MODIFY CIRCUITRY AS REQUIRED TO MAINTAIN CONTINUITY. WHERE CIRCUITS ARE INTERRUPTED BY REMOVAL OF A PANELBOARD THE ELECTRICAL CONTRACTOR SHALL RECONNECT DEVICES TO THE NEAREST PANELBOARD OF THE SAME VOLTAGE REQUIREMENTS WITH AVAILABLE SPACE. FURNISH AND INSTALL NEW CIRCUIT BREAKERS OR UTILIZE SPARE CIRCUIT BREAKERS AS REQUIRED. 10. FURNISH AND INSTALL KNOCKOUT COVERS OR PLUGS ON ALL EXISTING PANELS, FURNISH AND INSTALL KNOCKOUT COVERS OR PLUGS ON ALL EXISTING PANELS, EQUIPMENT AND OUTLET BOX OPENINGS CREATED BY THE REMOVAL OR RELOCATION OF EXISTING RACEWAYS. 11. DISCONNECT AND REMOVE ALL BALLASTS FROM FLUORESCENT LIGHT FIXTURES THAT DO DISCONNECT AND REMOVE ALL BALLASTS FROM FLUORESCENT LIGHT FIXTURES THAT DO NOT HAVE LABELS STATING THE FOLLOWING; "BALLAST DOES NOT CONTAIN PCBS" OR SIMILAR LABEL (BALLAST MAY HAVE PCBS). PLACE PCB BALLASTS IN D.O.T. APPROVED CONTAINERS. PROPERLY DISPOSE OF CONTAINERS WITH A FEDERALLY APPROVED DISPOSAL CONTRACTOR. DISPOSAL SHALL INVOLVE SEGREGATION OF COMPONENTS FOR RECYCLING AND INCINERATION OF PCB CONTENTS. ALL DISPOSAL DOCUMENTATION SHALL BE PROVIDED TO OWNER UPON COMPLETION OF THE PROJECT. CONTRACTOR SHALL MAINTAIN AN OWNER APPROVED LOG SHEET FOR EACH DRUM. 12. REMOVE ALL MERCURY CONTAINING LAMPS. DO NOT BREAK OR CRUSH. RETAIN SERVICES REMOVE ALL MERCURY CONTAINING LAMPS. DO NOT BREAK OR CRUSH. RETAIN SERVICES OF A STATE-APPROVED LAMP RECYCLING FACILITY ABLE TO ACCEPT WASTE D009. COORDINATE PACKAGING REQUIRED AND PACKAGE, SECURE, AND DELIVER LAMPS AS REQUIRED BY THE SELECTED RECYCLING FACILITY TO ENSURE MINIMUM LAMP BREAKAGE. MINIMUM OF 95% OF LAMP MATERIAL MUST BE SHIPPED INTACT. ELECTRICAL CONTRACTOR MUST COMPLY WITH ANY REPORTING AND PAPERWORK REQUIREMENTS OF STATE LAWS REGARDING THE HANDLING, TRANSPORTATION, AND DISPOSITION OF HAZARDOUS WASTE, INCLUDING BUT NOT LIMITED TO FILING THE REQUIRED PAPERWORK AND MANIFEST WITH THE STATE AND OWNERS AS REQUIRED BY LAW. ALL DISPOSAL DOCUMENTATION SHALL BE PROVIDED TO OWNER UPON COMPLETION OF THIS PROJECT. 13. RE-USE EXISTING CONDUITS AND CIRCUITS WHERE APPLICABLE. ANY COMPONENT TO REMAIN THAT IS DAMAGED DURING CONSTRUCTION SHALL BE REPLACED. 14. PROVIDE BOX EXTENSIONS AS REQUIRED FOR OUTLETS, SWITCHES, DEVICES, ETC. THAT ARE TO REMAIN IN WALLS RECEIVING NEW FURRING OR APPLICATION. (EX) DESIGNATION, NOT ALL LOCATIONS MAY BE INDICATED ON PLANS. 15. SEE SHEET E001 FOR ADDITIONAL GENERAL NOTES AND LEGEND.E001 FOR ADDITIONAL GENERAL NOTES AND LEGEND. FOR ADDITIONAL GENERAL NOTES AND LEGEND.

AutoCAD SHX Text

DEMO NOTES

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text A

AutoCAD SHX Text B

AutoCAD SHX Text C

AutoCAD SHX Text A

AutoCAD SHX Text B

AutoCAD SHX Text C

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

REV

AutoCAD SHX Text

ISSUE:

AutoCAD SHX Text

PROJECT NO:

AutoCAD SHX Text

CAD DWG FILE:

AutoCAD SHX Text

DRAWN BY:

AutoCAD SHX Text

CHECKED BY:

AutoCAD SHX Text

SHEET TITLE

AutoCAD SHX Text

DATE

AutoCAD SHX Text

DESCRIPTION

AutoCAD SHX Text

CONSULTANTS

AutoCAD SHX Text

INDIAN HEALTH SERVICE

AutoCAD SHX Text

DIVISION OF ENGINEERING SERVICES

AutoCAD SHX Text E

AutoCAD SHX Text H

AutoCAD SHX Text N

AutoCAD SHX Text M

AutoCAD SHX Text E

AutoCAD SHX Text A

AutoCAD SHX Text R

AutoCAD SHX Text P

AutoCAD SHX Text T

AutoCAD SHX Text O

AutoCAD SHX Text F

AutoCAD SHX Text T

AutoCAD SHX Text C

AutoCAD SHX Text D

AutoCAD SHX Text S

AutoCAD SHX Text U

AutoCAD SHX Text S

AutoCAD SHX Text A

AutoCAD SHX Text E

AutoCAD SHX Text T

AutoCAD SHX Text A

AutoCAD SHX Text E

AutoCAD SHX Text L

AutoCAD SHX Text

AutoCAD SHX Text H

AutoCAD SHX Text N

AutoCAD SHX Text V

AutoCAD SHX Text I

AutoCAD SHX Text S

AutoCAD SHX Text E

AutoCAD SHX Text R

AutoCAD SHX Text U

AutoCAD SHX Text M

AutoCAD SHX Text A

AutoCAD SHX Text H

AutoCAD SHX Text

SEATTLE / DALLAS

AutoCAD SHX Text

DES BRANCH CHIEF

AutoCAD SHX Text

DES PROJECT MANAGER

AutoCAD SHX Text

AGENCY REPRESENTATIVE

AutoCAD SHX Text

APPROVED:

AutoCAD SHX Text

CONCURRENCE

AutoCAD SHX Text

TITLE

AutoCAD SHX Text

REVIEWED:

AutoCAD SHX Text

DES ARCHITECT / ENGINEER

AutoCAD SHX Text

DATE

AutoCAD SHX Text

DATE

AutoCAD SHX Text

DATE

AutoCAD SHX Text

DATE

AutoCAD SHX Text

SHEET ______ OF ______

AutoCAD SHX Text 12 W. Kennewick Ave

AutoCAD SHX Text Kennewick, WA 99336

AutoCAD SHX Text P: 509.735.1589

AutoCAD SHX Text F: 509.783.5075

AutoCAD SHX Text www.meierinc.com

AutoCAD SHX Text

PROJECT NO: 16-7936

AutoCAD SHX Text WELLPINIT SERVICE UNIT MODERNIZATION 6203 AGENCY LOOP ROAD WELLPINIT, WASHINGTON 99040 PROJECT NUMBER PO4WE626C0PO4WE626C0

AutoCAD SHX Text

PO4WE648C0

AutoCAD SHX Text

OVERALL LIGHTING & POWER PLAN - DEMO

AutoCAD SHX Text 3/32" = 1'-0"

AutoCAD SHX Text

NOTES

AutoCAD SHX Text

1. POSITIONS AVAILABLE IN THE SPECIFIED PANELS ARE POSITIONS AVAILABLE IN THE SPECIFIED PANELS ARE AS FOLLOWS: PANEL/A2-12,13,14,15,16,17,18,19,20,21,22,23,24 -12,13,14,15,16,17,18,19,20,21,22,23,24 PANEL/B5-29,30,31,32,33,34,35,36,37,38,39,40,41,42 -29,30,31,32,33,34,35,36,37,38,39,40,41,42 PANEL/IMB-13,15,17 -13,15,17 PANEL/IMC-38,40,42 -38,40,42 PANEL/IR-7,9,11,34,36 -7,9,11,34,36 2. FOR GENERAL NOTES & LEGEND SEE SHEET E001. FOR GENERAL NOTES & LEGEND SEE SHEET E001. E001. . 3. FOR LIGHT FIXTURE SCHEDULE SEE SHEET E109.FOR LIGHT FIXTURE SCHEDULE SEE SHEET E109.E109..

AutoCAD SHX Text north

AutoCAD SHX Text E-002

AutoCAD SHX Text 793600E102-10

AutoCAD SHX Text

OVERALL LIGHTING & POWER PLAN - DEMO

AutoCAD SHX Text

RWS

AutoCAD SHX Text

DJZ

AutoCAD SHX Text

AutoCAD SHX Text

PO4WE626C0

AutoCAD SHX Text 33 4242

AutoCAD SHX Text 07/22/2016

HUMAN SERVICES

DE

NNIS J. ZIMMER ST

ATE OF WASHINGTON

R EGISTER ED

PR

O

FESSIONAL ENGIN

EE

R

44924

AutoCAD SHX Text

HWH

AutoCAD SHX Text

AHU-5

AutoCAD SHX Text

AHU-1

AutoCAD SHX Text

AHU-4

AutoCAD SHX Text

AHU-3

AutoCAD SHX Text

REF

AutoCAD SHX Text

AHU-2

AutoCAD SHX Text

REF

AutoCAD SHX Text

REF

AutoCAD SHX Text

REF

AutoCAD SHX Text

DRYER

AutoCAD SHX Text

WASHER

AutoCAD SHX Text

WH

AutoCAD SHX Text

LINENS

AutoCAD SHX Text

(FUTURE GROUP WORK OR MTG RM)

AutoCAD SHX Text

ADMINISTRATION BASEMENT

AutoCAD SHX Text

FIRE RISER

AutoCAD SHX Text

DN

AutoCAD SHX Text

DN

AutoCAD SHX Text

DN

AutoCAD SHX Text

UP

AutoCAD SHX Text

UP

AutoCAD SHX Text

DN

AutoCAD SHX Text

(E)PANEL/IMAPANEL/IMA

AutoCAD SHX Text

(E)PANEL/IMB PANEL/IMB (CUTLER-HAMER PRL) SEE NOTE-1

AutoCAD SHX Text

(E)PANEL/IMC PANEL/IMC SEE NOTE-1

AutoCAD SHX Text

(E)PANEL/IPPANEL/IP

AutoCAD SHX Text

(E)FA J-BOX

AutoCAD SHX Text

(E)ACCESS TO CRAWL SPACE BELOW

AutoCAD SHX Text

(E)SECURITY J-BOX

AutoCAD SHX Text

(AB)TMB

AutoCAD SHX Text

(E)PANEL/IDPANEL/ID

AutoCAD SHX Text

(E)PANEL/A2 PANEL/A2 SEE NOTE-1

AutoCAD SHX Text

(E)PANEL/A3PANEL/A3

AutoCAD SHX Text

SCP

AutoCAD SHX Text

FACP (SILENT KNIGHT 5208)

AutoCAD SHX Text

LTG CP

AutoCAD SHX Text

(E)PANEL/MDPPANEL/MDP

AutoCAD SHX Text

(E)CONDUIT CHASE

AutoCAD SHX Text

(E)PANEL/B5 PANEL/B5 (SIEMENS P1) SEE NOTE-1

AutoCAD SHX Text 204B

AutoCAD SHX Text C

AutoCAD SHX Text C

AutoCAD SHX Text C

AutoCAD SHX Text C

AutoCAD SHX Text C

AutoCAD SHX Text C

AutoCAD SHX Text C

AutoCAD SHX Text C

AutoCAD SHX Text

WP

AutoCAD SHX Text C

AutoCAD SHX Text C

AutoCAD SHX Text

WP

AutoCAD SHX Text

WP

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text C

AutoCAD SHX Text C

AutoCAD SHX Text C

AutoCAD SHX Text C

AutoCAD SHX Text C

AutoCAD SHX Text C

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text

OC

AutoCAD SHX Text

(AB)PHONE J-BOX

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text 204C

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text 183A

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text 180A

AutoCAD SHX Text

(E)PANEL/IR PANEL/IR (CUTLER-HAMMER PRL)

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

(ER) SECURITY KEYPAD

AutoCAD SHX Text

NURSE CALL MASTER STATION & POWER SUPPLY

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text 124A

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text 208A

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text T

AutoCAD SHX Text

(E)THERMOSTAT

AutoCAD SHX Text

(E)IDF (CRAWLSPACE BELOW)

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text A

AutoCAD SHX Text B

AutoCAD SHX Text C

AutoCAD SHX Text A

AutoCAD SHX Text B

AutoCAD SHX Text C

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

REV

AutoCAD SHX Text

ISSUE:

AutoCAD SHX Text

PROJECT NO:

AutoCAD SHX Text

CAD DWG FILE:

AutoCAD SHX Text

DRAWN BY:

AutoCAD SHX Text

CHECKED BY:

AutoCAD SHX Text

SHEET TITLE

AutoCAD SHX Text

DATE

AutoCAD SHX Text

DESCRIPTION

AutoCAD SHX Text

CONSULTANTS

AutoCAD SHX Text

INDIAN HEALTH SERVICE

AutoCAD SHX Text

DIVISION OF ENGINEERING SERVICES

AutoCAD SHX Text E

AutoCAD SHX Text H

AutoCAD SHX Text N

AutoCAD SHX Text M

AutoCAD SHX Text E

AutoCAD SHX Text A

AutoCAD SHX Text R

AutoCAD SHX Text P

AutoCAD SHX Text T

AutoCAD SHX Text O

AutoCAD SHX Text F

AutoCAD SHX Text T

AutoCAD SHX Text C

AutoCAD SHX Text D

AutoCAD SHX Text S

AutoCAD SHX Text U

AutoCAD SHX Text S

AutoCAD SHX Text A

AutoCAD SHX Text E

AutoCAD SHX Text T

AutoCAD SHX Text A

AutoCAD SHX Text E

AutoCAD SHX Text L

AutoCAD SHX Text

AutoCAD SHX Text H

AutoCAD SHX Text N

AutoCAD SHX Text V

AutoCAD SHX Text I

AutoCAD SHX Text S

AutoCAD SHX Text E

AutoCAD SHX Text R

AutoCAD SHX Text U

AutoCAD SHX Text M

AutoCAD SHX Text A

AutoCAD SHX Text H

AutoCAD SHX Text

SEATTLE / DALLAS

AutoCAD SHX Text

DES BRANCH CHIEF

AutoCAD SHX Text

DES PROJECT MANAGER

AutoCAD SHX Text

AGENCY REPRESENTATIVE

AutoCAD SHX Text

APPROVED:

AutoCAD SHX Text

CONCURRENCE

AutoCAD SHX Text

TITLE

AutoCAD SHX Text

REVIEWED:

AutoCAD SHX Text

DES ARCHITECT / ENGINEER

AutoCAD SHX Text

DATE

AutoCAD SHX Text

DATE

AutoCAD SHX Text

DATE

AutoCAD SHX Text

DATE

AutoCAD SHX Text

SHEET ______ OF ______

AutoCAD SHX Text 12 W. Kennewick Ave

AutoCAD SHX Text Kennewick, WA 99336

AutoCAD SHX Text P: 509.735.1589

AutoCAD SHX Text F: 509.783.5075

AutoCAD SHX Text www.meierinc.com

AutoCAD SHX Text

PROJECT NO: 16-7936

AutoCAD SHX Text WELLPINIT SERVICE UNIT MODERNIZATION 6203 AGENCY LOOP ROAD WELLPINIT, WASHINGTON 99040 PROJECT NUMBER PO4WE626C0PO4WE626C0

AutoCAD SHX Text

PO4WE648C0

AutoCAD SHX Text

OVERALL LIGHTING & POWER PLAN - NEW

AutoCAD SHX Text 3/32" = 1'-0"

AutoCAD SHX Text

NOTES

AutoCAD SHX Text

1. POSITIONS AVAILABLE IN THE SPECIFIED PANELS ARE POSITIONS AVAILABLE IN THE SPECIFIED PANELS ARE AS FOLLOWS: PANEL/A2-12,13,14,15,16,17,18,19,20,21,22,23,24 -12,13,14,15,16,17,18,19,20,21,22,23,24 PANEL/B5-29,30,31,32,33,34,35,36,37,38,39,40,41,42 -29,30,31,32,33,34,35,36,37,38,39,40,41,42 PANEL/IMB-13,15,17 -13,15,17 PANEL/IMC-38,40,42 -38,40,42 PANEL/IR-7,9,11,34,36 -7,9,11,34,36 2. FOR GENERAL NOTES & LEGEND SEE SHEET E001. FOR GENERAL NOTES & LEGEND SEE SHEET E001. E001. . 3. FOR LIGHT FIXTURE SCHEDULE SEE SHEET E109.FOR LIGHT FIXTURE SCHEDULE SEE SHEET E109.E109..

AutoCAD SHX Text north

AutoCAD SHX Text

ALL NURSE CALL WORK TO BE PERFORMED DURING PHASE 3.

AutoCAD SHX Text

AutoCAD SHX Text

FLAG NOTES

AutoCAD SHX Text E-003

AutoCAD SHX Text 793600E102-10

AutoCAD SHX Text

OVERALL LIGHTING & POWER PLAN - NEW

AutoCAD SHX Text

RWS

AutoCAD SHX Text

DJZ

AutoCAD SHX Text

AutoCAD SHX Text

TYP

AutoCAD SHX Text

AutoCAD SHX Text

PO4WE626C0

AutoCAD SHX Text 34 4242

AutoCAD SHX Text

MDF (E)MAIN SERVER RACK

AutoCAD SHX Text 07/22/2016

HUMAN SERVICES

DE

NNIS J. ZIMMER ST

ATE OF WASHINGTON

R EGISTER ED

PR

O

FESSIONAL ENGIN

EE

R

44924

AutoCAD SHX Text

HWH

AutoCAD SHX Text

AHU-5

AutoCAD SHX Text

AHU-1

AutoCAD SHX Text

AHU-4

AutoCAD SHX Text

AHU-3

AutoCAD SHX Text

REF

AutoCAD SHX Text

AHU-2

AutoCAD SHX Text

REF

AutoCAD SHX Text

REF

AutoCAD SHX Text

REF

AutoCAD SHX Text

DRYER

AutoCAD SHX Text

WASHER

AutoCAD SHX Text

WH

AutoCAD SHX Text

LINENS

AutoCAD SHX Text

(FUTURE GROUP WORK OR MTG RM)

AutoCAD SHX Text

ADMINISTRATION BASEMENT

AutoCAD SHX Text

FIRE RISER

AutoCAD SHX Text

DN

AutoCAD SHX Text

DN

AutoCAD SHX Text

DN

AutoCAD SHX Text

UP

AutoCAD SHX Text

UP

AutoCAD SHX Text

DN

AutoCAD SHX Text 204B

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text

OC

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text 204C

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text 183A

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text 180A

AutoCAD SHX Text

(E)MAIN SERVER RACKMAIN SERVER RACK

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

12"W CABLE TRAY, (CRAWL SPACE BELOW)

AutoCAD SHX Text

12"W CABLE TRAY, (CRAWL SPACE BELOW)

AutoCAD SHX Text

18"W CABLE TRAY, (CRAWL SPACE BELOW)

AutoCAD SHX Text

18"W CABLE TRAY, (CRAWL SPACE BELOW)

AutoCAD SHX Text

18"W CABLE TRAY, (CRAWL SPACE BELOW)

AutoCAD SHX Text A2,E2

AutoCAD SHX Text A4

AutoCAD SHX Text E4

AutoCAD SHX Text E2

AutoCAD SHX Text E2

AutoCAD SHX Text E2

AutoCAD SHX Text E2

AutoCAD SHX Text E2

AutoCAD SHX Text A2

AutoCAD SHX Text A4

AutoCAD SHX Text A4

AutoCAD SHX Text A4

AutoCAD SHX Text A1,E1

AutoCAD SHX Text E4

AutoCAD SHX Text E4

AutoCAD SHX Text E4

AutoCAD SHX Text A2,E2

AutoCAD SHX Text A1,E1

AutoCAD SHX Text E4

AutoCAD SHX Text E2

AutoCAD SHX Text E2

AutoCAD SHX Text E2

AutoCAD SHX Text A4

AutoCAD SHX Text E2

AutoCAD SHX Text E4

AutoCAD SHX Text A2,E2

AutoCAD SHX Text E4

AutoCAD SHX Text A2

AutoCAD SHX Text E2

AutoCAD SHX Text E2

AutoCAD SHX Text E2

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text A2

AutoCAD SHX Text E2

AutoCAD SHX Text E2

AutoCAD SHX Text A2,E2

AutoCAD SHX Text A2,E2

AutoCAD SHX Text E2

AutoCAD SHX Text A2

AutoCAD SHX Text

BROKEN FOR CLARITY

AutoCAD SHX Text

BROKEN FOR CLARITY

AutoCAD SHX Text A2,E2

AutoCAD SHX Text E3

AutoCAD SHX Text A3

AutoCAD SHX Text A2

AutoCAD SHX Text A2

AutoCAD SHX Text A2

AutoCAD SHX Text A2

AutoCAD SHX Text E2

AutoCAD SHX Text E2

AutoCAD SHX Text E2

AutoCAD SHX Text E2

AutoCAD SHX Text A2

AutoCAD SHX Text A2

AutoCAD SHX Text A2

AutoCAD SHX Text A2,E2

AutoCAD SHX Text E4

AutoCAD SHX Text A1,E3

AutoCAD SHX Text E2

AutoCAD SHX Text A2,E2

AutoCAD SHX Text A2,E2

AutoCAD SHX Text A4

AutoCAD SHX Text E4

AutoCAD SHX Text A4

AutoCAD SHX Text E2

AutoCAD SHX Text E4

AutoCAD SHX Text E2

AutoCAD SHX Text E2

AutoCAD SHX Text A2

AutoCAD SHX Text E2

AutoCAD SHX Text E2

AutoCAD SHX Text E2

AutoCAD SHX Text E2

AutoCAD SHX Text A3,E1

AutoCAD SHX Text A2,E2

AutoCAD SHX Text A1,E3

AutoCAD SHX Text A2,E2

AutoCAD SHX Text E4

AutoCAD SHX Text E4

AutoCAD SHX Text A2

AutoCAD SHX Text A2

AutoCAD SHX Text A4

AutoCAD SHX Text A2,E2

AutoCAD SHX Text A2

AutoCAD SHX Text A2

AutoCAD SHX Text A4

AutoCAD SHX Text A4

AutoCAD SHX Text A4

AutoCAD SHX Text A2

AutoCAD SHX Text A2

AutoCAD SHX Text A2,E2

AutoCAD SHX Text A1,E1

AutoCAD SHX Text A2

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text A4

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text 124A

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text 208A

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text A1,E1

AutoCAD SHX Text A1,E1

AutoCAD SHX Text A1,E1

AutoCAD SHX Text A1,E1

AutoCAD SHX Text A1,E1

AutoCAD SHX Text A1,E1

AutoCAD SHX Text E2

AutoCAD SHX Text +48"

AutoCAD SHX Text +48"

AutoCAD SHX Text E2

AutoCAD SHX Text +48"

AutoCAD SHX Text +48"

AutoCAD SHX Text +48"

AutoCAD SHX Text +48"

AutoCAD SHX Text +48"

AutoCAD SHX Text +48"

AutoCAD SHX Text A2,E2

AutoCAD SHX Text A2,E2

AutoCAD SHX Text A2,E2

AutoCAD SHX Text +48"

AutoCAD SHX Text +48"

AutoCAD SHX Text A2

AutoCAD SHX Text +48"

AutoCAD SHX Text +48"

AutoCAD SHX Text +48"

AutoCAD SHX Text A1,E1

AutoCAD SHX Text A1,E1

AutoCAD SHX Text +54"

AutoCAD SHX Text

CATV+76"

AutoCAD SHX Text A1,E1

AutoCAD SHX Text A1,E1

AutoCAD SHX Text A2,E2

AutoCAD SHX Text A2,E2

AutoCAD SHX Text A2,E2

AutoCAD SHX Text A1,E1

AutoCAD SHX Text A2,E2

AutoCAD SHX Text A2,E2

AutoCAD SHX Text A2,E2

AutoCAD SHX Text A1,E3

AutoCAD SHX Text A1,E3

AutoCAD SHX Text A1,E1

AutoCAD SHX Text A2

AutoCAD SHX Text +54"

AutoCAD SHX Text +48"

AutoCAD SHX Text +48"

AutoCAD SHX Text +48"

AutoCAD SHX Text +48"

AutoCAD SHX Text +48"

AutoCAD SHX Text +48"

AutoCAD SHX Text +48"

AutoCAD SHX Text +48"

AutoCAD SHX Text +48"

AutoCAD SHX Text +48"

AutoCAD SHX Text +48"

AutoCAD SHX Text A4

AutoCAD SHX Text A4

AutoCAD SHX Text E2

AutoCAD SHX Text A2

AutoCAD SHX Text

(E)PANEL/IDPANEL/ID

AutoCAD SHX Text +48"

AutoCAD SHX Text +48"

AutoCAD SHX Text +48"

AutoCAD SHX Text +48"

AutoCAD SHX Text +48"

AutoCAD SHX Text +48"

AutoCAD SHX Text A2

AutoCAD SHX Text A2

AutoCAD SHX Text +48"

AutoCAD SHX Text +48"

AutoCAD SHX Text +48"

AutoCAD SHX Text +48"

AutoCAD SHX Text +48"

AutoCAD SHX Text A2

AutoCAD SHX Text +48"

AutoCAD SHX Text

(N)CU-1 CU-1 1 D.49-51

AutoCAD SHX Text

WP-GFI

AutoCAD SHX Text

ID.53

AutoCAD SHX Text

(R)INTERMEDIATE IDF INTERMEDIATE IDF (CRAWSPACE BELOW)

AutoCAD SHX Text COMMUNICATION OUTLETS SHOWN AS 'STAND ALONE' ADD (NO EXISTING) REQUIRE NEW J-BOX, MUD RING AND CONDUIT TO BELOW, TYP

AutoCAD SHX Text

ROUTE RG-6 TO RM-160

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

CKT

AutoCAD SHX Text

CKT

AutoCAD SHX Text

CKT

AutoCAD SHX Text

CKT

AutoCAD SHX Text

CKT

AutoCAD SHX Text

'CKT' INDICATES RECEPTACLE ADDED DURING 'IT PHASE 0', TYP

AutoCAD SHX Text A3,E1

AutoCAD SHX Text

CKT

AutoCAD SHX Text A3,E1

AutoCAD SHX Text A3,E1

AutoCAD SHX Text

CKT

AutoCAD SHX Text

CKT

AutoCAD SHX Text +48"

AutoCAD SHX Text

(E)MDP MDP (225A FEEDS (E)PANEL/ID)

AutoCAD SHX Text

ORIGINAL 1974 CONSTRUCTION

AutoCAD SHX Text

ORIGINAL 2000 CONSTRUCTION

AutoCAD SHX Text NOTE: NINE(9) ADDITIONAL COMMUNICATIONS OUTLETS SHOWN ON SUBSEQUENT PHASED WORK PLANS

AutoCAD SHX Text

COMMUNICATION OUTLETS SHOWN AS (EXISTING) REUSE (E)J-BOX, TYP

AutoCAD SHX Text

A1,E3 MEANS RUN(4) NEW CAT-6 CABLES RE-USE(E) JBOX,TYP

AutoCAD SHX Text

(E)MODULAR BUILDING SCHEDULED FOR DEMOLITION (BY OTHERS) NOT IN SCOPE.

AutoCAD SHX Text

(2)48 PORT PATCH PANELS SEE E101E101

AutoCAD SHX Text

CU

AutoCAD SHX Text

AutoCAD SHX Text

FC

AutoCAD SHX Text

AutoCAD SHX Text

18"W CABLE TRAY

AutoCAD SHX Text

CU-1 SEE M-100 & M-601M-100 & M-601 & M-601M-601

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text A

AutoCAD SHX Text B

AutoCAD SHX Text C

AutoCAD SHX Text A

AutoCAD SHX Text B

AutoCAD SHX Text C

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

REV

AutoCAD SHX Text

ISSUE:

AutoCAD SHX Text

PROJECT NO:

AutoCAD SHX Text

CAD DWG FILE:

AutoCAD SHX Text

DRAWN BY:

AutoCAD SHX Text

CHECKED BY:

AutoCAD SHX Text

SHEET TITLE

AutoCAD SHX Text

DATE

AutoCAD SHX Text

DESCRIPTION

AutoCAD SHX Text

CONSULTANTS

AutoCAD SHX Text

INDIAN HEALTH SERVICE

AutoCAD SHX Text

DIVISION OF ENGINEERING SERVICES

AutoCAD SHX Text E

AutoCAD SHX Text H

AutoCAD SHX Text N

AutoCAD SHX Text M

AutoCAD SHX Text E

AutoCAD SHX Text A

AutoCAD SHX Text R

AutoCAD SHX Text P

AutoCAD SHX Text T

AutoCAD SHX Text O

AutoCAD SHX Text F

AutoCAD SHX Text T

AutoCAD SHX Text C

AutoCAD SHX Text D

AutoCAD SHX Text S

AutoCAD SHX Text U

AutoCAD SHX Text S

AutoCAD SHX Text A

AutoCAD SHX Text E

AutoCAD SHX Text T

AutoCAD SHX Text A

AutoCAD SHX Text E

AutoCAD SHX Text L

AutoCAD SHX Text

AutoCAD SHX Text H

AutoCAD SHX Text N

AutoCAD SHX Text V

AutoCAD SHX Text I

AutoCAD SHX Text S

AutoCAD SHX Text E

AutoCAD SHX Text R

AutoCAD SHX Text U

AutoCAD SHX Text M

AutoCAD SHX Text A

AutoCAD SHX Text H

AutoCAD SHX Text

SEATTLE / DALLAS

AutoCAD SHX Text

DES BRANCH CHIEF

AutoCAD SHX Text

DES PROJECT MANAGER

AutoCAD SHX Text

AGENCY REPRESENTATIVE

AutoCAD SHX Text

APPROVED:

AutoCAD SHX Text

CONCURRENCE

AutoCAD SHX Text

TITLE

AutoCAD SHX Text

REVIEWED:

AutoCAD SHX Text

DES ARCHITECT / ENGINEER

AutoCAD SHX Text

DATE

AutoCAD SHX Text

DATE

AutoCAD SHX Text

DATE

AutoCAD SHX Text

DATE

AutoCAD SHX Text

SHEET ______ OF ______

AutoCAD SHX Text 12 W. Kennewick Ave

AutoCAD SHX Text Kennewick, WA 99336

AutoCAD SHX Text P: 509.735.1589

AutoCAD SHX Text F: 509.783.5075

AutoCAD SHX Text www.meierinc.com

AutoCAD SHX Text

PROJECT NO: 16-7936

AutoCAD SHX Text WELLPINIT SERVICE UNIT MODERNIZATION 6203 AGENCY LOOP ROAD WELLPINIT, WASHINGTON 99040 PROJECT NUMBER PO4WE626C0PO4WE626C0

AutoCAD SHX Text

PO4WE648C0

AutoCAD SHX Text

IT PHASE/OVERALL COMMUNICATIONS PLAN - NEW PHASE 0

AutoCAD SHX Text 3/32" = 1'-0"

AutoCAD SHX Text

NOTES

AutoCAD SHX Text

1. CONTRACTOR SHALL MAKE ALL ATTEMPTS TO MINIMIZE DOWN-TIME BY PRE-ARRANGING TRAYS, RACEWAYS, CONTRACTOR SHALL MAKE ALL ATTEMPTS TO MINIMIZE DOWN-TIME BY PRE-ARRANGING TRAYS, RACEWAYS, J-BOXES AND CABLING AS MUCH AS FEASIBLE PRIOR TO TRANSITION INTO "LIVE" NEW I.T. RACK ROOM 160. THIS MAY REQUIRE WEEKEND OR OFF-HOURS WORK; ADDITIONAL PERSONNEL AND/OR PRE-TEAM-STAGING ACTIVITIES AS REQUIRED. 2. NOTICE: THE I.T. NETWORK, PERIPHERALS AND ASSOCIATED INFRASTRUCTURE WITHIN FACILITY WILL CONTAIN NOTICE: THE I.T. NETWORK, PERIPHERALS AND ASSOCIATED INFRASTRUCTURE WITHIN FACILITY WILL CONTAIN PERSONAL DATA WHICH LIMITS ACCESS OR USE BY THIRD PARTIES AND MAY BE COVERED UNDER SECURITY AND PRIVACY RULES AS ADMINISTERED BY FACILITY OFFICIAL OR AHJ. PARTIES ACCESSING OR HANDLING DATA OF COVERED ENTITIES TO COMPLY WITH SECURITY AND PRIVACY MEASURES AND SIGN & RECORD RELEVANT NON-DISCLOSURE AND PROTECTIVE MEASURES DOCUMENTS AS DIRECTED AND PROVIDED BY FACILITY OFFICIAL OR AHJ PRIOR TO ANY WORK WHICH ACCESSES OR HANDLES DATA OF COVERED ENTITIES. 3. EXPOSED WIRING PHONE, DATA AND FIBER CABLING SHALL BE INSTALLED IN A NEAT AND WORKMANLIKE EXPOSED WIRING PHONE, DATA AND FIBER CABLING SHALL BE INSTALLED IN A NEAT AND WORKMANLIKE MANNER PER ANSI/TIA 569 AND NECA-1. CABLES INSTALLED EXPOSED ABOVE THE SURFACE OF CEILINGS AND SIDEWALLS SHALL BE SUPPORTED BY THE BUILDING STRUCTURE IN SUCH A MANNER THAT THE CABLE WILL NOT BE DAMAGED BY NORMAL BUILDING USE. SUCH CABLES SHALL BE UNIFORMLY SUPPORTED BY STRAPS, STAPLES, HANGERS, CABLE TIES, OR SIMILAR FITTINGS, TRANSITIONING TO TRAY ASSEMBLIES WHERE SHOWN PER PLANS AND PER NEC 300.4 AND 300.11. NON-CONTINUOUS SUPPORT INTERVALS SHALL BE SPACED AT 5 FT NOMINAL. SUCH CABLE SUPPORT TYPE SHALL BE ABLE TO ACCEPT MODIFICATIONS AND ADDITIONAL WIRING/CABLING. SUCH CABLE AND WIRING SHALL BE GENERALLY ARRANGED WITH ADEQUATE SEPARATION FROM LIGHTS (1 FOOT MIN), MOTORS (4 FEET MIN @5HP), TRANSFORMERS (4 FEET MIN @25KVA), AND OTHER EMI SOURCES INCLUDING RACEWAYS (1 FOOT MIN). SUCH CABLES SHALL BE BUNDLED, COLOR-CODED OR GROUPED TOGETHER AND IDENTIFIED WITH PERMANENT MARKING ALONG INTERMEDIATE AND END POINTS. 4. FOR THE I.T. UPGRADE PHASE; MINOR PATCHING IS REQUIRED PER SPECIFICATION SECTION 024119 PARA FOR THE I.T. UPGRADE PHASE; MINOR PATCHING IS REQUIRED PER SPECIFICATION SECTION 024119 PARA 3.4; MATCH ALL EXISTING CONDITIONS & FINISHES U.O.N. 5. FOR GENERAL NOTES & LEGEND SEE E001.FOR GENERAL NOTES & LEGEND SEE E001.E001..

AutoCAD SHX Text north

AutoCAD SHX Text EXISTING MDF (BASEMENT ROOM 223) IHS PERSONNEL SHALL SCHEDULE, PLAN AND COORDINATE PLANNED CABLE UPGRADE ACTIVITIES AS REQUIRED WITHIN FRAMEWORK OF GC SCHEDULED WORK. INCLUDING SHUT DOWN, INSTALLATIONS AND RESTART WORK. CAREFUL CONSIDERATION & COORDINATION IS REQUIRED FOR CORRECT PLANNING AND EXECUTION BETWEEN ALL PARTIES. MAKE PRE-ARRANGEMENTS FOR ALL BACK-UP DATA STORAGE AND PASSWORD ACCESS PRIOR TO WORK. IHS PERSONNEL RESPONSIBLE FOR VENDER NOTIFICATIONS. IHS PERSONNEL SHALL PROVIDE ANY ADDITIONAL EQUIPMENT LABELING ON EXISTING SERVER RACK AS REQUIRED.

This is the start of the file's text. The full file is on GovTribe.