J-06_Mechanical_2_of_2.pdf
PDF 3 MB Posted
- Attached to
- Wellpinit Service Unit Modernization Project Federal contract opportunity
- Solicitation number
- 16-102-SOL-00031
About this file
J-06 Mechanical 2 of 2
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| Amendment_0008_SF30.pdf | ||
| Construction_Wage_Determination_MOD_07.pdf | ||
| Amendment_0007_SF30.pdf | ||
| J-_12_Wellpinit_Service_Unit_Clinic_RBM_Report_Sept_2014.pdf | ||
| Amendment_0006_SF30.pdf | ||
| Site_Walk_Attendance_Sheet.pdf | ||
| Amendment_0005_SF30.pdf | ||
| Amendment_0004_SF30.pdf | ||
| J-11__Amendment_on_Sheet_No__E-101.pdf | ||
| J-10_Construction_Wage_Determination..pdf | ||
| Amendment_0003_SF30.pdf | ||
| Amendment_0002_SF30.pdf | ||
| J-04_Architectural_2_of_2_Rev_1.pdf | ||
| Amendment_0001_SF30.pdf | ||
| J-02_Specifications.pdf | ||
| Solicitation_16-102-SOL-00031.pdf | ||
| J-07_Electrical.pdf | ||
| J-03_Architectural_1_of_2.pdf | ||
| J-04_Architectural_2_of_2.pdf | ||
| J-_05_Mechanical_1_of_2.pdf | ||
| J-_01_Contract_Requirements.pdf | ||
| J-09_PPI.doc | DOC document |
Show all 22
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
U. S. DEPARTMENT
OF HEALTH AND
HUMAN SERVICES
AutoCAD SHX Text
NO SCALE
AutoCAD SHX Text AFF ABOVE FINISHED FLOOR ABOVE FINISHED FLOOR APD AIR PRESSURE DROP AIR PRESSURE DROP APPROX APPROXIMATELY APPROXIMATELY BCP BOILER CIRCULATION PUMP BOILER CIRCULATION PUMP BDD BACK DRAFT DAMPER BACK DRAFT DAMPER BTUH BRITISH THERMAL UNITS PER HOUR BRITISH THERMAL UNITS PER HOUR CC COOLING COIL COOLING COIL CFM CUBIC FEET PER MINUTE CUBIC FEET PER MINUTE CO CLEANOUT CLEANOUT COND CONDENS(ER,-ING,-ATE) CONDENS(ER,-ING,-ATE) COR CONTRACTING OFFICER'S CONTRACTING OFFICER'S REPRESENTATIVE COTG CLEANOUT TO GRADE CLEANOUT TO GRADE CU CONDENSING UNIT CONDENSING UNIT CW COLD WATER COLD WATER DB DRY BULB DRY BULB DCVA DOUBLE CHECK VALVE ASSEMBLY DOUBLE CHECK VALVE ASSEMBLY DH DUCT HEATER DUCT HEATER DN DOWN DOWN DWH DOMESTIC WATER HEATER DOMESTIC WATER HEATER (E) EXISTING EXISTING EA EXHAUST AIR EXHAUST AIR EAT ENTERING AIR TEMPERATURE ENTERING AIR TEMPERATURE EF EXHAUST FAN EXHAUST FAN EFF EFFICIENCY EFFICIENCY EL ELEVATION ELEVATION ET EXPANSION TANK EXPANSION TANK EUH ELECTRIC UNIT HEATER ELECTRIC UNIT HEATER EVAP EVAPORATOR EVAPORATOR EW EYEWASH EYEWASH EWC ELECTRIC WATER COOLER ELECTRIC WATER COOLER EWH ELECTRIC WALL HEATER ELECTRIC WALL HEATER EWT ENTERING WATER TEMPERATURE ENTERING WATER TEMPERATURE EXT EXTERNAL EXTERNAL FC FAN COIL UNIT FAN COIL UNIT FCO FLOOR CLEANOUT FLOOR CLEANOUT FD FLOOR DRAIN FLOOR DRAIN FFE FINISHED FLOOR ELEVATION FINISHED FLOOR ELEVATION FLA FULL LOAD AMPS FULL LOAD AMPS FLR FLOOR FLOOR FS FLOOR SINK FLOOR SINK FT FEET FEET G (NATURAL) GAS (NATURAL) GAS GA GAUGE GAUGE GAL GALLON(S) GALLON(S) GPH GALLONS PER HOUR GALLONS PER HOUR GPM GALLONS PER MINUTE GALLONS PER MINUTE GSM GALVANIZED SHEET METAL GALVANIZED SHEET METAL GUH GAS UNIT HEATER GAS UNIT HEATER HB HOSE BIBB HOSE BIBB HP HEAT PUMP HEAT PUMP HP HORSEPOWER HORSEPOWER HW HOT WATER HOT WATER IE INVERT ELEVATION INVERT ELEVATION IN INCHES INCHES LAT LEAVING AIR TEMPERATURE LEAVING AIR TEMPERATURE LAV LAVATORY LAVATORY LV LOUVER LOUVER LRA LOCKED ROTOR AMPS LOCKED ROTOR AMPS LWT LEAVING WATER TEMPERATURE LEAVING WATER TEMPERATURE MAX MAXIMUM MAXIMUM MBH BRITISH THERMAL UNITS BRITISH THERMAL UNITS PER HOUR (THOUSAND) MCA MINIMUM CIRCUIT AMPACITY MINIMUM CIRCUIT AMPACITY MIN MINIMUM MINIMUM MOCP MAXIMUM OVERCURRENT PROTECTION MAXIMUM OVERCURRENT PROTECTION MS MOTOR STARTER MOTOR STARTER MVD MANUAL VOLUME DAMPER MANUAL VOLUME DAMPER NC NOISE CRITERIA NOISE CRITERIA NIC NOT IN CONTRACT NOT IN CONTRACT NTS NOT TO SCALE NOT TO SCALE OA OUTSIDE AIR OUTSIDE AIR OB OUTLET BOX OUTLET BOX OPER OPERATING OPERATING PD PRESSURE DROP PRESSURE DROP PH PHASE PHASE PRV PRESSURE REDUCING VALVE PRESSURE REDUCING VALVE PSIG POUNDS PER SQUARE INCH (GAGE) POUNDS PER SQUARE INCH (GAGE) RA RETURN AIR RETURN AIR RLA RATED LOAD AMPS RATED LOAD AMPS RPBA REDUCED PRESSURE REDUCED PRESSURE BACKFLOW PREVENTION ASSEMBLY RPM REVOLUTIONS PER MINUTE REVOLUTIONS PER MINUTE RTU ROOFTOP UNIT ROOFTOP UNIT RV ROOF VENT ROOF VENT SA SUPPLY AIR SUPPLY AIR SF SQUARE FEET SQUARE FEET SK SINK SINK SNS SANITARY SEWER SANITARY SEWER SP STATIC PRESSURE STATIC PRESSURE S/S START/STOP START/STOP SST STAINLESS STEEL STAINLESS STEEL SUM SUMMER SUMMER TA TRANSFER AIR TRANSFER AIR TD TRENCH DRAIN TRENCH DRAIN TEMP TEMPERATURE TEMPERATURE TMV THERMOSTATIC MIXING VALVE THERMOSTATIC MIXING VALVE TP TRAP PRIMER TRAP PRIMER UH UNIT HEATER UNIT HEATER UNO UNLESS NOTED OTHERWISE UNLESS NOTED OTHERWISE V VENT VENT VTR VENT THROUGH ROOF VENT THROUGH ROOF W WASTE WASTE WB WET BULB WET BULB WC WATER CLOSET WATER CLOSET WCO WALL CLEANOUT WALL CLEANOUT WG WATER GAUGE WATER GAUGE WH WALL HYDRANT WALL HYDRANT WHA WATER HAMMER ARRESTOR WATER HAMMER ARRESTOR WIN WINTER WINTER WT WEIGHTWEIGHT
AutoCAD SHX Text
ABBREVIATIONS
AutoCAD SHX Text
1. ALL NEW DUCT SHALL HAVE A MINIMUM OF 1-1/2" EXTERNAL DUCT ALL NEW DUCT SHALL HAVE A MINIMUM OF 1-1/2" EXTERNAL DUCT WRAP INSULATION COMPLYING WITH THE 2012 WASHINGTON STATE ENERGY CODE UNLESS NOTED OTHERWISE. UNLESS OTHERWISE NOTED, RECTANGULAR DUCTWORK SHALL HAVE MINIMUM 1" THICK ACOUSTIC LINER. DUCT WRAP INSULATION MAY BE OMITTED IF DUCT LINER PROVIDES MINIMUM INSULATION VALUES REQUIRED BY ENERGY CODE. ALL DUCT DIMENSIONS SHOWN ON DRAWINGS ARE NET INSIDE DIMENSIONS UNLESS NOTED OTHERWISE. 2. ALL JOINTS AND SEAMS ON NEW SUPPLY, RETURN, AND EXHAUST AIR ALL JOINTS AND SEAMS ON NEW SUPPLY, RETURN, AND EXHAUST AIR DUCTS SHALL BE SEALED PER LOCAL ENERGY CODE WITH DUCT SEALING COMPOUND. 3. PROVIDE AND INSTALL TURNING VANES IN ALL NEW RECTANGULAR 90° PROVIDE AND INSTALL TURNING VANES IN ALL NEW RECTANGULAR 90° ELBOWS AND TEES. 4. INSTALL NEW THERMOSTATS AT SAME HEIGHTS AS (E) THERMOSTATS. INSTALL NEW THERMOSTATS AT SAME HEIGHTS AS (E) THERMOSTATS. 5. ALL NEW DUCTS SHALL BE CONSTRUCTED PER SMACNA 15D 2” WC ALL NEW DUCTS SHALL BE CONSTRUCTED PER SMACNA 15D 2” WC WC MINIMUM PRESSURE CLASS UNLESS NOTED OTHERWISE. 6. ALL EQUIPMENT SHALL BE INSTALLED LEVEL. ADJUSTMENTS SHALL BE ALL EQUIPMENT SHALL BE INSTALLED LEVEL. ADJUSTMENTS SHALL BE MADE IN THE CURBS/EQUIPMENT SUPPORTS OR BY USING SHIMS. 7. CONTRACTOR SHALL ENSURE MECHANICAL SYSTEMS PERFORM AS CONTRACTOR SHALL ENSURE MECHANICAL SYSTEMS PERFORM AS DESCRIBED IN THE SEQUENCE OF OPERATION. 8. INSTALL TAMPER-RESISTANT REFRIGERANT SERVICE PORT CAPS AT ALL INSTALL TAMPER-RESISTANT REFRIGERANT SERVICE PORT CAPS AT ALL EXTERIOR REFRIGERATION EQUIPMENT THAT IS ACCESSIBLE FROM THE GROUND AND NOT WITHIN A SECURE ENCLOSURE. 9. SPECIFICATIONS FOR THIS PROJECT ARE INCORPORATED INTO IHS SPECIFICATIONS FOR THIS PROJECT ARE INCORPORATED INTO IHS PROJECT NO. PO4WE626C0. REFER TO THIS PROJECT'S DOCUMENTS FOR SPECIFICATIONS. 10. FOR TITLE SHEET AND OTHER GENERAL PROJECT NOTES WHICH ARE FOR TITLE SHEET AND OTHER GENERAL PROJECT NOTES WHICH ARE APPLICABLE TO THIS PROJECT, REFER TO DOCUMENTS FOR IHS PROJECT NO. PO4WE626C0. SHEET T101 AND M001. 11. THE SCOPE OF THE HVAC REPLACEMENT INCLUDES ANTICIPATED THE SCOPE OF THE HVAC REPLACEMENT INCLUDES ANTICIPATED RE-USE OF ALL EXISTING ELECTRICAL CIRCUITS SERVING EXISTING HVAC EQUIPMENT. CONTRACTOR SHALL VERIFY THAT SUFFICIENT AMPACITY EXISTS AT EACH CIRCUIT CONNECTION TO NEW EQUIPMENT. IF A CIRCUIT IS DETERMINED TO HAVE INSUFFICIENT CAPACITY, NOTIFY CONTRACTING OFFICER'S REPRESENTATIVE (COR). MODIFICATIONS TO EXISTING ELECTRICAL CIRCUITS SHALL NOT BE MADE WITHOUT APPROVAL OF COR. ALL ELECTRICAL WORK, INCLUDING VERIFICATIONS OF EXISTING CIRCUITS AND DESIGN AND EXECUTION OF MODIFICATIONS REQUIRED TO ACCOMODATE NEW EQUIPMENT SHALL BE DESIGN-BUILD BY CONTRACTOR.
AutoCAD SHX Text
HVAC GENERAL NOTES
AutoCAD SHX Text
HVAC LEGEND
AutoCAD SHX Text
FIRE DAMPER
AutoCAD SHX Text
SMOKE DETECTOR
AutoCAD SHX Text
CARBON DIOXIDE SENSOR
AutoCAD SHX Text
RETURN DIFFUSER
AutoCAD SHX Text
SUPPLY DIFFUSER
AutoCAD SHX Text
BACK DRAFT DAMPER
AutoCAD SHX Text
TEMPERATURE SENSOR
AutoCAD SHX Text
MANUAL VOLUME DAMPER
AutoCAD SHX Text
MOTOR OPERATED DAMPER
AutoCAD SHX Text
RETURN/EXHAUST DUCT RISER
AutoCAD SHX Text
EQUIPMENT TAG (SEE SCHEDULE)
AutoCAD SHX Text
SPIN-IN FITTING WITH DAMPER
AutoCAD SHX Text
DIFFUSER TYPE (SEE SCHEDULE)
AutoCAD SHX Text
SUPPLY DUCT RISER
AutoCAD SHX Text
FLEXIBLE DUCTWORK
AutoCAD SHX Text
RIGID ROUND DUCTWORK
AutoCAD SHX Text
LINED DUCTWORK
AutoCAD SHX Text
AIR OUTLET SIZE
AutoCAD SHX Text
THERMOSTAT MOUNT 5'-0" AFF
AutoCAD SHX Text
AIRFLOW (CFM)
AutoCAD SHX Text
FIRE SMOKE DAMPER
AutoCAD SHX Text
SUPPLY AIR FLOW
AutoCAD SHX Text
RETURN/EXHAUST AIR FLOW
AutoCAD SHX Text
DUCT ELEVATION CALL OUT
AutoCAD SHX Text
TS
AutoCAD SHX Text
CO2
AutoCAD SHX Text
SD
AutoCAD SHX Text T
AutoCAD SHX Text M
AutoCAD SHX Text
BDD
AutoCAD SHX Text
FD
AutoCAD SHX Text F/S
AutoCAD SHX Text
HVAC/PLUMBING DEMOLITION HATCH
AutoCAD SHX Text
HVAC/PLUMBING DEMOLITION LINE
AutoCAD SHX Text 24x24
AutoCAD SHX Text A
AutoCAD SHX Text
AutoCAD SHX Text X
AutoCAD SHX Text
XX
AutoCAD SHX Text
X-XX
AutoCAD SHX Text T+
AutoCAD SHX Text B+
AutoCAD SHX Text
MECHANICAL DRAWING LIST
AutoCAD SHX Text M-001 GENERAL NOTES AND LEGENDS GENERAL NOTES AND LEGENDS M-101 MECHANICAL DEMOLITION FLOOR PLAN MECHANICAL DEMOLITION FLOOR PLAN M-201 MECHANICAL OVERALL FLOOR PLAN MECHANICAL OVERALL FLOOR PLAN M-401 MECHANICAL ENLARGED PLANS MECHANICAL ENLARGED PLANS M-501 MECHANICAL DIAGRAMS AND DETAILS MECHANICAL DIAGRAMS AND DETAILS M-601 MECHANICAL SCHEDULESMECHANICAL SCHEDULES
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text A
AutoCAD SHX Text B
AutoCAD SHX Text C
AutoCAD SHX Text A
AutoCAD SHX Text B
AutoCAD SHX Text C
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
REV
AutoCAD SHX Text
ISSUE:
AutoCAD SHX Text
PROJECT NO:
AutoCAD SHX Text
CAD DWG FILE:
AutoCAD SHX Text
DRAWN BY:
AutoCAD SHX Text
CHECKED BY:
AutoCAD SHX Text
SHEET TITLE
AutoCAD SHX Text
DATE
AutoCAD SHX Text
DESCRIPTION
AutoCAD SHX Text
CONSULTANTS
AutoCAD SHX Text
INDIAN HEALTH SERVICE
AutoCAD SHX Text
DIVISION OF ENGINEERING SERVICES
AutoCAD SHX Text E
AutoCAD SHX Text H
AutoCAD SHX Text N
AutoCAD SHX Text M
AutoCAD SHX Text E
AutoCAD SHX Text A
AutoCAD SHX Text R
AutoCAD SHX Text P
AutoCAD SHX Text T
AutoCAD SHX Text O
AutoCAD SHX Text F
AutoCAD SHX Text T
AutoCAD SHX Text C
AutoCAD SHX Text D
AutoCAD SHX Text S
AutoCAD SHX Text U
AutoCAD SHX Text S
AutoCAD SHX Text A
AutoCAD SHX Text E
AutoCAD SHX Text T
AutoCAD SHX Text A
AutoCAD SHX Text E
AutoCAD SHX Text L
AutoCAD SHX Text
AutoCAD SHX Text H
AutoCAD SHX Text N
AutoCAD SHX Text V
AutoCAD SHX Text I
AutoCAD SHX Text S
AutoCAD SHX Text E
AutoCAD SHX Text R
AutoCAD SHX Text U
AutoCAD SHX Text M
AutoCAD SHX Text A
AutoCAD SHX Text H
AutoCAD SHX Text
SEATTLE / DALLAS
AutoCAD SHX Text
DES BRANCH CHIEF
AutoCAD SHX Text
DES PROJECT MANAGER
AutoCAD SHX Text
AGENCY REPRESENTATIVE
AutoCAD SHX Text
APPROVED:
AutoCAD SHX Text
CONCURRENCE
AutoCAD SHX Text
TITLE
AutoCAD SHX Text
REVIEWED:
AutoCAD SHX Text
DES ARCHITECT / ENGINEER
AutoCAD SHX Text
DATE
AutoCAD SHX Text
DATE
AutoCAD SHX Text
DATE
AutoCAD SHX Text
DATE
AutoCAD SHX Text
SHEET ______ OF ______
AutoCAD SHX Text 12 W. Kennewick Ave.
AutoCAD SHX Text Kennewick, WA 99336
AutoCAD SHX Text P: 509.735.1589
AutoCAD SHX Text F: 509.783.5075
AutoCAD SHX Text www.meierinc.com
AutoCAD SHX Text
PROJECT NO: 15-7640
AutoCAD SHX Text WELLPINIT SERVICE UNIT HVAC REPLACEMENT 6203 AGENCY LOOP ROAD WELLPINIT, WASHINGTON 99040 PROJECT NUMBER PO4WE626C0PO4WE626C0
AutoCAD SHX Text 764000M001
AutoCAD SHX Text M-001
AutoCAD SHX Text
GENERAL NOTES AND LEGENDS
AutoCAD SHX Text
PO4WE648C0
AutoCAD SHX Text 1 66
AutoCAD SHX Text 2012 WASHINGTON STATE ENERGY CODE: COMMERCIAL PROVISIONS (WAC 51-11C) REQUIREMENTS: NOTE: THE FOLLOWING ITEMS ARE GENERAL REQUIREMENTS ONLY. CONTRACTOR IS RESPONSIBLE FOR COMPLYING WITH ALL APPLICABLE PROVISIONS OF THE STATE ENERGY CODE REGARDLESS OF WHETHER OR NOT THE REQUIREMENTS ARE LISTED BELOW OR IN THE DRAWINGS OR SPECIFICATIONS. 1. THERMOSTATS AND ROOM TEMPERATURE SENSORS WHICH CONTROL BOTH HEATING AND COOLING THERMOSTATS AND ROOM TEMPERATURE SENSORS WHICH CONTROL BOTH HEATING AND COOLING EQUIPMENT SHALL HAVE A MINIMUM 5 DEGREE DEADBAND PER SECTION C403.2.4.2. 2. THERMOSTATS OR CENTRAL CONTROLS SHALL HAVE AUTOMATIC SETBACK CONTROLS AND HAVE A THERMOSTATS OR CENTRAL CONTROLS SHALL HAVE AUTOMATIC SETBACK CONTROLS AND HAVE A MINIMUM SEVEN DAY CLOCK CAPABLE OF BEING SET FOR SEVEN DIFFERENT DAYS OF THE WEEK, PER SECTION C403.2.4.3.2. 3. OUTSIDE AIR INTAKES AND EXHAUST OUTLETS, SHALL BE EQUIPPED WITH MOTORIZED DAMPERS OUTSIDE AIR INTAKES AND EXHAUST OUTLETS, SHALL BE EQUIPPED WITH MOTORIZED DAMPERS WHICH CLOSE AUTOMATICALLY WHEN THE SYSTEM IS OFF, DURING BUILDING WARM-UP, COOL DOWN, OR UPON POWER FAILURE, PER SECTION C403.2.4.4. a. EXCEPTIONS: GRAVITY OPERATED RELIEF DAMPERS ARE PERMITTED IN EQUIPMENT WITH LESS EXCEPTIONS: GRAVITY OPERATED RELIEF DAMPERS ARE PERMITTED IN EQUIPMENT WITH LESS THAN 5,000 CFM TOTAL SUPPLY FLOW IN BUILDINGS LESS THAN 3 STORIES IN HEIGHT. RETURN AIR DUCTS SHALL BE EQUIPPED WITH MOTORIZED DAMPERS PER SECTION C402.4.5.2. b. SYSTEMS SERVING AREAS WHICH REQUIRE CONTINUOUS OPERATION. SYSTEMS SERVING AREAS WHICH REQUIRE CONTINUOUS OPERATION. c. OPERATION OF DAMPERS SHALL BE ALLOWED DURING VENTILATION PRE-PURGE ONE HOUR OPERATION OF DAMPERS SHALL BE ALLOWED DURING VENTILATION PRE-PURGE ONE HOUR BEFORE OCCUPANCY AND FOR UNOCCUPIED PERIOD PRE-COOLING DURING COOLING SEASON. d. WHERE PROHIBITED BY LOCAL MECHANICAL CODE. WHERE PROHIBITED BY LOCAL MECHANICAL CODE. 4. MOTORIZED AND NONMOTORIZED DAMPERS SHALL HAVE A MAXIMUM LEAKAGE RATE WHEN MOTORIZED AND NONMOTORIZED DAMPERS SHALL HAVE A MAXIMUM LEAKAGE RATE WHEN TESTED IN ACCORDANCE WITH AMCA STANDARD 500D OF: MOTORIZED DAMPER 4 CFM/SF OF DAMPER AREA AT 1.0 IN W.G., NON MOTORIZED DAMPER 20 CFM/SF OF DAMPER AREA AT 1.0 IN W.G, (FOR RELIEF DAMPERS IN BUILDINGS LESS THAN 3 STORIES IN HEIGHT AND SYSTEMS LESS THAN 5000 CFM SUPPLY AIR) NON MOTORIZED DAMPERS SMALLER THAN 24” IN EITHER IN EITHER DIMENSION: 40CFM/SF OF DAMPER AREA AT 1.0 IN W.G. PER SECTION C402.4.5.2. 5. ALL SYSTEMS SHALL BE EQUIPPED WITH OPTIMUM START CONTROLS PER SECTION C403.2.4.3.3. ALL SYSTEMS SHALL BE EQUIPPED WITH OPTIMUM START CONTROLS PER SECTION C403.2.4.3.3. 6. HEAT PUMP SYSTEMS WITH AUXILIARY HEAT SYSTEMS SHALL HAVE CONTROLS WHICH LOCKOUT HEAT PUMP SYSTEMS WITH AUXILIARY HEAT SYSTEMS SHALL HAVE CONTROLS WHICH LOCKOUT AUXILIARY HEAT ABOVE 40°F OUTDOOR AIR TEMPERATURE PER SECTION C403.2.4.1.1. 7. AIR ECONOMIZERS SHALL BE CAPABLE OF INTEGRATED OPERATION (REFRIGERATION SYSTEM MAY AIR ECONOMIZERS SHALL BE CAPABLE OF INTEGRATED OPERATION (REFRIGERATION SYSTEM MAY OPERATE TO SUPPLEMENT ECONOMIZER OPERATION.) PER SECTION C403.4.1.3. 8. DUCTS SHALL BE CONSTRUCTED, SEALED AND TESTED IN ACCORDANCE WITH SECTION DUCTS SHALL BE CONSTRUCTED, SEALED AND TESTED IN ACCORDANCE WITH SECTION C403.2.7.3. 9. SUPPLY AIR DUCTS WITHIN BUILDING ENVELOPE SHALL BE INSULATED WITH MINIMUM OF R-3.3 SUPPLY AIR DUCTS WITHIN BUILDING ENVELOPE SHALL BE INSULATED WITH MINIMUM OF R-3.3 INSULATION, PER SECTION C403.2.7.2. 10. HVAC PIPING (INCLUDING REFRIGERANT, CHILLED WATER, AND HEATING WATER) SHALL BE HVAC PIPING (INCLUDING REFRIGERANT, CHILLED WATER, AND HEATING WATER) SHALL BE INSULATED TO THE MINIMUM IN SECTION C403.2.8. 11. PROVIDE SYSTEMS COMMISSIONING PLAN, SYSTEMS TESTING AND BALANCING, OWNER TRAINING PROVIDE SYSTEMS COMMISSIONING PLAN, SYSTEMS TESTING AND BALANCING, OWNER TRAINING AND OTHER REQUIRED ITEMS IN ACCORDANCE WITH SECTION C408. 12. SUBMIT COMMISSIONING COMPLETION CHECKLIST TO THE OWNER UPON SUBSTANTIAL COMPLETION SUBMIT COMMISSIONING COMPLETION CHECKLIST TO THE OWNER UPON SUBSTANTIAL COMPLETION PER SECTION C408.1.3.4. 13. WITHIN 90 DAYS OF PROJECT COMPLETION DELIVER MECHANICAL RECORD DRAWINGS TO THE WITHIN 90 DAYS OF PROJECT COMPLETION DELIVER MECHANICAL RECORD DRAWINGS TO THE BUILDING OWNER, PER SECTION C408.1.3.1. 14. WITHIN 90 DAYS OF PROJECT COMPLETION DELIVER HVAC OPERATIONS AND MAINTENANCE WITHIN 90 DAYS OF PROJECT COMPLETION DELIVER HVAC OPERATIONS AND MAINTENANCE MANUAL TO THE BUILDING OWNER, PER SECTION C408.1.3.2. 15. PROVIDE COMMISSIONING AND TEST AND BALANCE REPORT TO OWNER, PER SECTION C408.1.3.3.PROVIDE COMMISSIONING AND TEST AND BALANCE REPORT TO OWNER, PER SECTION C408.1.3.3.
AutoCAD SHX Text
WA STATE ECCP NOTES
AutoCAD SHX Text
BID ALTERNATES DESCRIPTION
AutoCAD SHX Text THE FOLLOWING DESCRIPTIONS ARE FOR INFORMATION ONLY. REFER TO BIDDING DOCUMENTS AND BID FORMS FOR ADDITIONAL INFORMATION ON ALL ALTERNATES AND BIDDING PROCEDURES FOR EACH. DEDUCTIVE ALTERNATE 1: CLEAN, PRESSURE-TEST, AND RE-USE EXISTING REFRIGERANT PIPING FOR CONNECTION BETWEEN NEW HEAT PUMP AND AIR HANDLING UNITS. BASE BID SHALL INCLUDE REPLACEMENT OF BURIED LINES, INCLUDING ALL TRENCHING, BACKFILL, PROTECTIVE CONDUIT REPLACEMENT, AND ALL OTHER ANCILLARY ITEMS REQUIRED. UNDER THIS ALTERNATE, THE EXISTING LINES FOR REFRIGERANT R-22 USE SHALL BE PROPERLY CLEANED IN ACCORDANCE WITH INDUSTRY PRACTICE AND PREPARED FOR R-410A USE. PRICING SHALL BE INCLUDED AS A DEDUCT/CREDIT FROM THE BASE BID.
AutoCAD SHX Text SPLIT AIR CONDITIONING UNITS WITH ECONOMIZERS 1. THE UNITS SHALL BE CONTROLLED BY A 7-DAY PROGRAMMABLE THERMOSTAT. THE UNITS SHALL BE CONTROLLED BY A 7-DAY PROGRAMMABLE THERMOSTAT. 2. DURING OCCUPIED HOURS: DURING OCCUPIED HOURS: 2.1. SUPPLY FAN SHALL BE ON. SUPPLY FAN SHALL BE ON. 2.2. OUTDOOR AIR DAMPER SHALL BE OPEN TO THE MINIMUM POSITION, UNLESS OVERRIDDEN BY ECONOMIZER COOLING DEMAND. OUTDOOR AIR DAMPER SHALL BE OPEN TO THE MINIMUM POSITION, UNLESS OVERRIDDEN BY ECONOMIZER COOLING DEMAND. 2.3. ON A CALL FOR COOLING, THE OUTDOOR AIR, RETURN, AND RELIEF DAMPERS SHALL OPERATE COORDINATELY IN ECONOMIZER MODE TO MAINTAIN SPACE ON A CALL FOR COOLING, THE OUTDOOR AIR, RETURN, AND RELIEF DAMPERS SHALL OPERATE COORDINATELY IN ECONOMIZER MODE TO MAINTAIN SPACE TEMPERATURE AT SETPOINT. WHEN ECONOMIZER OPERATION ALONE CANNOT MAINTAIN SETPOINT CONDITIONS, MECHANICAL COOLING SHALL BE ACTIVATED AS NECESSARY TO MAINTAIN THE SPACE TEMPERATURE SETPOINT CONDITIONS. WHEN THE OUTSIDE AIR TEMPERATURE RISES ABOVE THE RETURN AIR TEMPERATURE, OR AS OTHERWISE SET, THE OUTSIDE AIR DAMPERS SHALL RETURN TO MINIMUM POSITION, THE RETURN AND RELIEF AIR DAMPERS SHALL OPERATE COORDINATELY, AND MECHANICAL COOLING SHALL OPERATE ALONE TO MAINTAIN SETPOINT CONDITIONS. 2.4. ON A CALL FOR HEATING, THE OUTSIDE AIR DAMPER SHALL MODULATE TO MINIMUM POSITION, RETURN AND RELIEF AIR DAMPERS SHALL OPERATE ON A CALL FOR HEATING, THE OUTSIDE AIR DAMPER SHALL MODULATE TO MINIMUM POSITION, RETURN AND RELIEF AIR DAMPERS SHALL OPERATE COORDINATELY, AND COMPRESSION HEATING (HEAT PUMP) SHALL CYCLE AS NECESSARY TO MAINTAIN THE SPACE TEMPERATURE AT SETPOINT CONDITIONS. IF COMPRESSION HEATING ALONE CANNOT MAINTAIN SETPOINT CONDITIONS, AUXILIARY ELECTRIC RESISTANCE HEAT SHALL BE ACTIVATED AS NECESSARY TO MAINTAIN SETPOINT CONDITIONS. IN ADDITION, THE AUXILIARY HEAT SHALL ALSO OPERATE WHEN THE HEAT PUMP SYSTEM IS IN DEFROST CYCLE. AUXILIARY HEAT SHALL BE LOCKED OUT WHEN OUTSIDE AIR TEMPERATURE IS ABOVE 40 DEG F. 3. DURING UNOCCUPIED HOURS: DURING UNOCCUPIED HOURS: 3.1. SUPPLY FAN SHALL CYCLE ON AND OFF WITH HEATING AND COOLING DEMANDS. SUPPLY FAN SHALL CYCLE ON AND OFF WITH HEATING AND COOLING DEMANDS. 3.2. OUTDOOR AIR DAMPER SHALL BE CLOSED UNLESS OVERRIDDEN BY ECONOMIZER COOLING DEMAND. OUTDOOR AIR DAMPER SHALL BE CLOSED UNLESS OVERRIDDEN BY ECONOMIZER COOLING DEMAND. 3.3. CALLS FOR COOLING SHALL BE SATISFIED AS IN THE OCCUPIED MODE. CALLS FOR COOLING SHALL BE SATISFIED AS IN THE OCCUPIED MODE. 3.4. CALLS FOR HEATING SHALL BE SATISFIED AS IN THE OCCUPIED MODE. CALLS FOR HEATING SHALL BE SATISFIED AS IN THE OCCUPIED MODE. 4. FOR ALL UNITS EQUIPPED WITH DUCT SMOKE DETECTORS, COORDINATE SMOKE DETECTION ALARM AND SHUT DOWN WITH THE FIRE ALARM CONTROL PANEL ON FOR ALL UNITS EQUIPPED WITH DUCT SMOKE DETECTORS, COORDINATE SMOKE DETECTION ALARM AND SHUT DOWN WITH THE FIRE ALARM CONTROL PANEL ON ALL APPLICABLE UNITS. UPON SMOKE DETECTION, AIR CONDITIONING UNIT SHALL BE COMMANDED OFF, AND OUTSIDE AIR AND RELIEF DAMPERS CLOSED.
AutoCAD SHX Text
HVAC SEQUENCE OF OPERATION
AutoCAD SHX Text
LOW TEMP SWITCH
AutoCAD SHX Text
LT
AutoCAD SHX Text
ENTHALPY SENSOR
AutoCAD SHX Text
ES
AutoCAD SHX Text
WM
AutoCAD SHX Text
DLA
AutoCAD SHX Text
1. ALL DUCT AND PIPE ROUTING AND CONSTRUCTION SHOWN ON THE DRAWINGS IS DIAGRAMMATIC IN ALL DUCT AND PIPE ROUTING AND CONSTRUCTION SHOWN ON THE DRAWINGS IS DIAGRAMMATIC IN NATURE AND MAY NOT BE SHOWN IN EXACT LOCATIONS OR WITH ALL ANCILLARY ITEMS REQUIRED FOR A COMPLETE AND OPERATING SYSTEM. CONTRACTOR SHALL COORDINATE ROUTING OF ALL DUCTWORK AND PIPING PER TYPICAL CONSTRUCTION PRACTICE IN THE MOST EFFICIENT WAY POSSIBLE WHILE ADHERING AS CLOSELY TO THE DRAWINGS AS POSSIBLE. CONTRACTOR IS RESPONSIBLE FOR COORDINATING ALL INSTALLATION WITH THE WORK OF OTHER TRADES. IN THE EVENT A CONFLICT ARISES WHICH CANNOT BE RESOLVED IN THE FIELD, A REQUEST FOR INFORMATION (RFI) SHALL BE SUBMITTED TO THE COR FOR REVIEW. INCLUDE PROPOSED SOLUTION AND COST/TIME IMPACT. 2. ALL WORK SHALL BE PERFORMED IN A NEAT AND WORKMANLIKE MANNER WITHIN STANDARD OF ALL WORK SHALL BE PERFORMED IN A NEAT AND WORKMANLIKE MANNER WITHIN STANDARD OF CARE FOR PROFESSION. ALL LABOR, MATERIAL, TOOLS, PERMITS, INSPECTIONS, TESTING, CERTIFICATION, ETC. REQUIRED FOR A COMPLETE AND SATISFACTORY INSTALLATION TO DESIGN INTENT SHALL BE FURNISHED BY CONTRACTOR. PROVIDE, AT NO ADDITIONAL COST, INCLUDING INCIDENTAL ITEMS NOT SHOWN WHEN REQUIRED FOR TYPICAL COMPLETION OF WORK. 3. SPECIFICATIONS AND DRAWINGS ARE COMPLEMENTARY AND SHALL BE UNDERSTOOD AS ONE. IN SPECIFICATIONS AND DRAWINGS ARE COMPLEMENTARY AND SHALL BE UNDERSTOOD AS ONE. IN THE EVENT OF A CONFLICT BETWEEN THE PLANS AND SPECIFICATIONS, THE MORE STRINGENT REQUIREMENT SHALL APPLY. IF A CONFLICT CANNOT BE RESOLVED IN THIS MANNER, IT SHALL BE REFERRED TO THE ENGINEER FOR RESOLUTION. 4. CONTRACTOR IS RESPONSIBLE FOR VERIFICATION OF SITE CONDITIONS, INSTALLATION STANDARDS CONTRACTOR IS RESPONSIBLE FOR VERIFICATION OF SITE CONDITIONS, INSTALLATION STANDARDS AND CONSTRUCTION CONDITIONS AND PROCEDURES. FIELD VERIFY ALL DIMENSIONS PRIOR TO SHOP FABRICATION AND/OR FIELD ERECTION. DISCREPANCIES BETWEEN SITE CONDITIONS AND THE CONSTRUCTION DOCUMENTS SHALL BE CALLED TO THE ATTENTION OF THE ENGINEER. WORK DONE WITHOUT THE ENGINEER'S APPROVAL IS THE SOLE RESPONSIBILITY OF THE CONTRACTOR. 5. DRAWINGS NOT BEARING THE STAMP OR SEAL AND SIGNATURE OF A REGISTERED PROFESSIONAL DRAWINGS NOT BEARING THE STAMP OR SEAL AND SIGNATURE OF A REGISTERED PROFESSIONAL ENGINEER SHALL NOT BE USED FOR BIDDING OR CONSTRUCTION PURPOSES. THE CONTRACTOR SHALL BE RESPONSIBLE FOR ENSURING THAT ALL DRAWINGS AND SPECIFICATIONS BEING USED FOR BIDDING AND CONSTRUCTION PURPOSES ARE OF THE LATEST REVISION AVAILABLE AND ALL ADDENDUM DOCUMENTS HAVE BEEN INCORPORATED EITHER BY REVISION RELEASE OF DRAWINGS/SPECIFICATIONS OR ATTACHMENT OF SKETCHES OR OTHER ADDENDUM INFORMATION. 6. NOT ALL SYMBOLS OR ABBREVIATIONS INDICATED MAY BE USED ON PROJECT DRAWINGS. NOT ALL SYMBOLS OR ABBREVIATIONS INDICATED MAY BE USED ON PROJECT DRAWINGS. 7. DRAWINGS MAY BE REDUCED. VERIFY SCALE.DRAWINGS MAY BE REDUCED. VERIFY SCALE.
AutoCAD SHX Text
MECHANICAL GENERAL NOTES
AutoCAD SHX Text 7/22/16
OF HEALTH AND
HUMAN SERVICES
AutoCAD SHX Text
WOMEN
AutoCAD SHX Text
MEN
AutoCAD SHX Text
VESTIBULE
AutoCAD SHX Text
& REGISTRATION
AutoCAD SHX Text
LAB
AutoCAD SHX Text
PROCEDURE/CONTROL
AutoCAD SHX Text
PHARMACY
AutoCAD SHX Text
MECHANICAL
AutoCAD SHX Text
DENTAL
AutoCAD SHX Text
STORAGE
AutoCAD SHX Text
STOR
AutoCAD SHX Text
BUSINESS
AutoCAD SHX Text
MANAGER
AutoCAD SHX Text
PROCEDURE/
AutoCAD SHX Text
BLOOD
AutoCAD SHX Text
DRAW
AutoCAD SHX Text
EXAM 3
AutoCAD SHX Text
EXAM 2
AutoCAD SHX Text
EXAM 1
AutoCAD SHX Text
NURSE STATIONS
AutoCAD SHX Text
& CONTROL CTR
AutoCAD SHX Text
EXAM
AutoCAD SHX Text
BREAK ROOM
AutoCAD SHX Text
TOILET
AutoCAD SHX Text
VESTIBULE
AutoCAD SHX Text
EXIT
AutoCAD SHX Text
AMBULANCE
AutoCAD SHX Text
ENTRANCE
AutoCAD SHX Text
EXIT
AutoCAD SHX Text
VESTIBULE
AutoCAD SHX Text
WAITING
AutoCAD SHX Text
WAITING
AutoCAD SHX Text
OP 1
AutoCAD SHX Text
OP 3
AutoCAD SHX Text
OP 5
AutoCAD SHX Text
LAB
AutoCAD SHX Text
STORAGE
AutoCAD SHX Text
DARK
AutoCAD SHX Text
ROOM
AutoCAD SHX Text
OFFICE
AutoCAD SHX Text
PAN
AutoCAD SHX Text
CLEAN
AutoCAD SHX Text
UP
AutoCAD SHX Text
OP 2
AutoCAD SHX Text
OP 4
AutoCAD SHX Text
JAN
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
TOILET
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
TOILET
AutoCAD SHX Text
AutoCAD SHX Text
EXAM 4
AutoCAD SHX Text
AutoCAD SHX Text
ISOLATION
AutoCAD SHX Text
AutoCAD SHX Text
CASTING
AutoCAD SHX Text
COORDINATOR
AutoCAD SHX Text
AutoCAD SHX Text
TRIAGE
AutoCAD SHX Text
AutoCAD SHX Text
PEDIATRIC
AutoCAD SHX Text
AutoCAD SHX Text
EXAM
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
EYE
AutoCAD SHX Text
DIABETIC
AutoCAD SHX Text
EXAM
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
EXAM
AutoCAD SHX Text
MAIN RECEPTION
AutoCAD SHX Text
SUB-
AutoCAD SHX Text
WAITING
AutoCAD SHX Text
AutoCAD SHX Text
TOILET
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
MEDICAL RECORDS
AutoCAD SHX Text
OFFICE
AutoCAD SHX Text
UTILITY
AutoCAD SHX Text
AutoCAD SHX Text
CLEAN
AutoCAD SHX Text
DIRTY
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
X-RAY
AutoCAD SHX Text
DISPENSING
AutoCAD SHX Text
MEDICAL CODING
AutoCAD SHX Text
AutoCAD SHX Text
UTILITY 2
AutoCAD SHX Text
AutoCAD SHX Text
JAN./
AutoCAD SHX Text
OFFICE 2
AutoCAD SHX Text
SUB-W
AutoCAD SHX Text
AutoCAD SHX Text
COPY CENTER
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
HALL
AutoCAD SHX Text
AutoCAD SHX Text
HALL
AutoCAD SHX Text
AutoCAD SHX Text
HALLWAY
AutoCAD SHX Text
AutoCAD SHX Text
HALLWAY
AutoCAD SHX Text
AutoCAD SHX Text
HALLWAY
AutoCAD SHX Text
AutoCAD SHX Text
HALLWAY
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
WAY
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
HALLWAY
AutoCAD SHX Text
HALL
AutoCAD SHX Text
DISPENSING
AutoCAD SHX Text
DISPENSING
AutoCAD SHX Text
VESTIBULE
AutoCAD SHX Text
AutoCAD SHX Text
HALLWAY
AutoCAD SHX Text
AutoCAD SHX Text
HALL
AutoCAD SHX Text
WAY
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
MECH.
AutoCAD SHX Text 124A
AutoCAD SHX Text
HWH
AutoCAD SHX Text
HALLWAY
AutoCAD SHX Text
AutoCAD SHX Text
REF
AutoCAD SHX Text
REF
AutoCAD SHX Text
WOMEN'S
AutoCAD SHX Text
EXAM
AutoCAD SHX Text
DIABETIC
AutoCAD SHX Text
RECEIVING
AutoCAD SHX Text
BUSINESS
AutoCAD SHX Text
OFFICE
AutoCAD SHX Text
CONFERENCE
AutoCAD SHX Text
IT DIRECTOR
AutoCAD SHX Text
CHS FILES
AutoCAD SHX Text
JANITORS
AutoCAD SHX Text
CLOSET
AutoCAD SHX Text
SERVICES (CHS)
AutoCAD SHX Text
(TWO STAFF)
AutoCAD SHX Text
CONTRACT HEALTH
AutoCAD SHX Text
RESTROOM
AutoCAD SHX Text
PAPER GOODS STG
AutoCAD SHX Text
BREAK ROOM
AutoCAD SHX Text
CEO OFFICE
AutoCAD SHX Text
STORAGE
AutoCAD SHX Text
MAIL ROOM
AutoCAD SHX Text
URGENT CARE
AutoCAD SHX Text
BENEFITS
AutoCAD SHX Text
AutoCAD SHX Text
(6 STAFF)
AutoCAD SHX Text
HALL &
AutoCAD SHX Text
RESOURCES
AutoCAD SHX Text
EDUCATIONAL
AutoCAD SHX Text
REF
AutoCAD SHX Text
REF
AutoCAD SHX Text
DENTAL RECEPT
AutoCAD SHX Text
AutoCAD SHX Text
TRIAGE
AutoCAD SHX Text
AutoCAD SHX Text
ADA
AutoCAD SHX Text
TRIAGE
AutoCAD SHX Text
AutoCAD SHX Text
REGISTRATION
AutoCAD SHX Text 180A
AutoCAD SHX Text
PATIENT
AutoCAD SHX Text
PROVIDERS
AutoCAD SHX Text
OFFICE
AutoCAD SHX Text
AutoCAD SHX Text
PROVIDERS
AutoCAD SHX Text
OFFICE
AutoCAD SHX Text
AutoCAD SHX Text
PROVIDERS
AutoCAD SHX Text
OFFICE
AutoCAD SHX Text
AutoCAD SHX Text
SUPPLY
AutoCAD SHX Text
MED GAS
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 204C
AutoCAD SHX Text
STAIRS
AutoCAD SHX Text
AutoCAD SHX Text
ELECT
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 208A
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
HALLWAY
AutoCAD SHX Text
AutoCAD SHX Text
EKG
AutoCAD SHX Text
AutoCAD SHX Text
SUPPLY
AutoCAD SHX Text
STORAGE
AutoCAD SHX Text 204B
AutoCAD SHX Text
STAIR
AutoCAD SHX Text 220A
AutoCAD SHX Text
DN
AutoCAD SHX Text
DN
AutoCAD SHX Text
DN
AutoCAD SHX Text
DN
AutoCAD SHX Text
DRESSING
AutoCAD SHX Text
AutoCAD SHX Text
SUPPLY
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
PROVIDER
AutoCAD SHX Text
VISITING
AutoCAD SHX Text
WEST WING
AutoCAD SHX Text
EAST WING
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
(E)AHU
AutoCAD SHX Text
AutoCAD SHX Text
(E)HP
AutoCAD SHX Text
AutoCAD SHX Text
(E)HP
AutoCAD SHX Text
AutoCAD SHX Text
(E)HP
AutoCAD SHX Text
AutoCAD SHX Text
(E)HP
AutoCAD SHX Text
AutoCAD SHX Text
(E)HP
AutoCAD SHX Text
AutoCAD SHX Text
(TO REMAIN)
AutoCAD SHX Text
(E)AHU
AutoCAD SHX Text
AutoCAD SHX Text
(E)AHU
AutoCAD SHX Text
AutoCAD SHX Text
(E)AHU
AutoCAD SHX Text
AutoCAD SHX Text
(E)AHU
AutoCAD SHX Text
AutoCAD SHX Text
(E)HP
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
(E)HP
AutoCAD SHX Text
AutoCAD SHX Text
(E) FENCING FENCING TO REMAIN
AutoCAD SHX Text T
AutoCAD SHX Text
AHU-1
AutoCAD SHX Text
AutoCAD SHX Text T
AutoCAD SHX Text
AHU-5
AutoCAD SHX Text
AutoCAD SHX Text T
AutoCAD SHX Text
AHU-2
AutoCAD SHX Text
AutoCAD SHX Text T
AutoCAD SHX Text
AHU-3
AutoCAD SHX Text
AutoCAD SHX Text T
AutoCAD SHX Text
AHU-4
AutoCAD SHX Text
AutoCAD SHX Text
ADMINISTRATION
AutoCAD SHX Text
AutoCAD SHX Text T
AutoCAD SHX Text
AHU-2
AutoCAD SHX Text
AutoCAD SHX Text
(E) FENCING TO REMAINFENCING TO REMAIN
AutoCAD SHX Text
(TO REMAIN)
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
FITNESS ROOM
AutoCAD SHX Text
LAUNDRY &
AutoCAD SHX Text
JAN
AutoCAD SHX Text
STORAGE
AutoCAD SHX Text
STORAGE
AutoCAD SHX Text
SERVER ROOM
AutoCAD SHX Text
FURNACE ROOM
AutoCAD SHX Text
MECHANICAL
AutoCAD SHX Text
ELEC
AutoCAD SHX Text
FIRE RISER
AutoCAD SHX Text
DRYER
AutoCAD SHX Text
WASHER
AutoCAD SHX Text
WH
AutoCAD SHX Text
LINENS
AutoCAD SHX Text
(FUTURE GROUP WORK OR MTG RM)
AutoCAD SHX Text
STORAGE
AutoCAD SHX Text
LINEN
AutoCAD SHX Text
HALLWAY
AutoCAD SHX Text
STORAGE
AutoCAD SHX Text
FIRE RISER
AutoCAD SHX Text
RR
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 223A
AutoCAD SHX Text
IT
AutoCAD SHX Text 223B
AutoCAD SHX Text
UP
AutoCAD SHX Text
UP
AutoCAD SHX Text
(E)AHU
AutoCAD SHX Text
AutoCAD SHX Text
(E)AHU
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text T
AutoCAD SHX Text
AHU-1
AutoCAD SHX Text
AutoCAD SHX Text
NOTED
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text A
AutoCAD SHX Text B
AutoCAD SHX Text C
AutoCAD SHX Text A
AutoCAD SHX Text B
AutoCAD SHX Text C
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
REV
AutoCAD SHX Text
ISSUE:
AutoCAD SHX Text
PROJECT NO:
AutoCAD SHX Text
CAD DWG FILE:
AutoCAD SHX Text
DRAWN BY:
AutoCAD SHX Text
CHECKED BY:
AutoCAD SHX Text
SHEET TITLE
AutoCAD SHX Text
DATE
AutoCAD SHX Text
DESCRIPTION
AutoCAD SHX Text
CONSULTANTS
AutoCAD SHX Text
INDIAN HEALTH SERVICE
AutoCAD SHX Text
DIVISION OF ENGINEERING SERVICES
AutoCAD SHX Text E
AutoCAD SHX Text H
AutoCAD SHX Text N
AutoCAD SHX Text M
AutoCAD SHX Text E
AutoCAD SHX Text A
AutoCAD SHX Text R
AutoCAD SHX Text P
AutoCAD SHX Text T
AutoCAD SHX Text O
AutoCAD SHX Text F
AutoCAD SHX Text T
AutoCAD SHX Text C
AutoCAD SHX Text D
AutoCAD SHX Text S
AutoCAD SHX Text U
AutoCAD SHX Text S
AutoCAD SHX Text A
AutoCAD SHX Text E
AutoCAD SHX Text T
AutoCAD SHX Text A
AutoCAD SHX Text E
AutoCAD SHX Text L
AutoCAD SHX Text
AutoCAD SHX Text H
AutoCAD SHX Text N
AutoCAD SHX Text V
AutoCAD SHX Text I
AutoCAD SHX Text S
AutoCAD SHX Text E
AutoCAD SHX Text R
AutoCAD SHX Text U
AutoCAD SHX Text M
AutoCAD SHX Text A
AutoCAD SHX Text H
AutoCAD SHX Text
SEATTLE / DALLAS
AutoCAD SHX Text
DES BRANCH CHIEF
AutoCAD SHX Text
DES PROJECT MANAGER
AutoCAD SHX Text
AGENCY REPRESENTATIVE
AutoCAD SHX Text
APPROVED:
AutoCAD SHX Text
CONCURRENCE
AutoCAD SHX Text
TITLE
AutoCAD SHX Text
REVIEWED:
AutoCAD SHX Text
DES ARCHITECT / ENGINEER
AutoCAD SHX Text
DATE
AutoCAD SHX Text
DATE
AutoCAD SHX Text
DATE
AutoCAD SHX Text
DATE
AutoCAD SHX Text
SHEET ______ OF ______
AutoCAD SHX Text 12 W. Kennewick Ave.
AutoCAD SHX Text Kennewick, WA 99336
AutoCAD SHX Text P: 509.735.1589
AutoCAD SHX Text F: 509.783.5075
AutoCAD SHX Text www.meierinc.com
AutoCAD SHX Text
PROJECT NO: 15-7640
AutoCAD SHX Text WELLPINIT SERVICE UNIT HVAC REPLACEMENT 6203 AGENCY LOOP ROAD WELLPINIT, WASHINGTON 99040 PROJECT NUMBER PO4WE626C0PO4WE626C0
AutoCAD SHX Text 764000M101
AutoCAD SHX Text M-101
AutoCAD SHX Text
MECHANICAL DEMOLITION FLOOR PLAN
AutoCAD SHX Text
PO4WE648C0
AutoCAD SHX Text
WM
AutoCAD SHX Text
DLA
AutoCAD SHX Text 2 66
AutoCAD SHX Text
MECHANICAL DEMOLITION FLOOR PLAN
AutoCAD SHX Text 3/32" = 1'-0"
AutoCAD SHX Text
NOTES
AutoCAD SHX Text
1. FOR GENERAL NOTES AND LEGEND SEE M-001. FOR GENERAL NOTES AND LEGEND SEE M-001. M-001. . 2. AREAS OF WORK INDICATED FOR REFERENCE. ANCILLARY AREAS OF WORK INDICATED FOR REFERENCE. ANCILLARY TASKS RELATED TO THE WORK MAY TAKE PLACE OUTSIDE THESE AREAS. 3. WEST AND EAST WING NOTATIONS USED THROUGHOUT THESE WEST AND EAST WING NOTATIONS USED THROUGHOUT THESE DRAWINGS ARE FOR CONVENIENCE DUE TO REPEATING EQUIPMENT DESIGNATIONS WITHIN FACILITY. 4. FOR ADDITIONAL INFORMATION ON EQUIPMENT TO BE FOR ADDITIONAL INFORMATION ON EQUIPMENT TO BE REMOVED OR TO REMAIN, SEE SHEET M501. M501. . 5. EXISTING INFORMATION IS DERIVED FROM AVAILABLE EXISTING INFORMATION IS DERIVED FROM AVAILABLE DOCUMENTS, FIELD OBSERVATIONS AND ASSUPTIONS. CONTRACTOR TO VERIFY CONDITIONS PRIOR TO PERFORMING WORK. 6. DO NOT INTERRUPT HVAC SERVICE TO OCCUPIED AREAS OF DO NOT INTERRUPT HVAC SERVICE TO OCCUPIED AREAS OF FACILITY WITHOUT WRITTEN PERMISSION OF COR. LIMIT SERVICE INTERRUPTIONS TO THE MINIMUM EXTENT POSSIBLE WHILE MAINTAINING FACILITY OPERATIONS DURING CONSTRUCTION.
AutoCAD SHX Text
FLAG NOTES
AutoCAD SHX Text REMOVE (E) HEAT PUMP UNIT. POWER FEEDS TO REMAIN FOR NEW UNIT. PIPING TO REMAIN FOR NEW UNIT IF BID ALTERNATE 1 IS SELECTED. REMOVE (E) AIR HANDLING UNIT AND CONTROLS. DUCT CONNECTIONS, AND POWER FEEDS TO REMAIN FOR NEW UNIT. PIPING TO REMAIN FOR NEW UNIT IF BID ALTERNATE 1 IS SELECTED. DEMOLISH (E) CONCRETE PADS AT REMOVED EQUIPMENT. NEW PAD TO BE PROVIDED. SEE M201. M201. . (E) THERMOSTAT TO BE REPLACED. RE-USE WIRING FOR NEW THERMOSTAT. SEE M201 AND M601. M201 AND M601. AND M601. M601. . (E) THERMOSTAT TO REMAIN. IN THE EVENT OF BASE BID CONSTRUCTION, REFRIGERANT PIPING TO BE REMOVED FROM (E) UNIT. PREPARE UNIT FOR INSTALLATION OF NEW REFRIGERANT PIPING.
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AREA OF WORK
AutoCAD SHX Text
ADMINISTRATION BASEMENT PLAN
AutoCAD SHX Text 3/32" = 1'-0"
AutoCAD SHX Text
AREA OF WORK
AutoCAD SHX Text
AREA OF WORK
AutoCAD SHX Text north
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
HUMAN SERVICES
AutoCAD SHX Text
WOMEN
AutoCAD SHX Text
MEN
AutoCAD SHX Text
VESTIBULE
AutoCAD SHX Text
& REGISTRATION
AutoCAD SHX Text
LAB
AutoCAD SHX Text
PROCEDURE/CONTROL
AutoCAD SHX Text
PHARMACY
AutoCAD SHX Text
MECHANICAL
AutoCAD SHX Text
DENTAL
AutoCAD SHX Text
STORAGE
AutoCAD SHX Text
STOR
AutoCAD SHX Text
BUSINESS
AutoCAD SHX Text
MANAGER
AutoCAD SHX Text
PROCEDURE/
AutoCAD SHX Text
BLOOD
AutoCAD SHX Text
DRAW
AutoCAD SHX Text
EXAM 3
AutoCAD SHX Text
EXAM 2
AutoCAD SHX Text
EXAM 1
AutoCAD SHX Text
NURSE STATIONS
AutoCAD SHX Text
& CONTROL CTR
AutoCAD SHX Text
EXAM
AutoCAD SHX Text
BREAK ROOM
AutoCAD SHX Text
TOILET
AutoCAD SHX Text
VESTIBULE
AutoCAD SHX Text
EXIT
AutoCAD SHX Text
AMBULANCE
AutoCAD SHX Text
ENTRANCE
AutoCAD SHX Text
EXIT
AutoCAD SHX Text
VESTIBULE
AutoCAD SHX Text
WAITING
AutoCAD SHX Text
WAITING
AutoCAD SHX Text
OP 1
AutoCAD SHX Text
OP 3
AutoCAD SHX Text
OP 5
AutoCAD SHX Text
LAB
AutoCAD SHX Text
STORAGE
AutoCAD SHX Text
DARK
AutoCAD SHX Text
ROOM
AutoCAD SHX Text
OFFICE
AutoCAD SHX Text
PAN
AutoCAD SHX Text
CLEAN
AutoCAD SHX Text
UP
AutoCAD SHX Text
OP 2
AutoCAD SHX Text
OP 4
AutoCAD SHX Text
JAN
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
TOILET
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
TOILET
AutoCAD SHX Text
AutoCAD SHX Text
EXAM 4
AutoCAD SHX Text
AutoCAD SHX Text
ISOLATION
AutoCAD SHX Text
AutoCAD SHX Text
CASTING
AutoCAD SHX Text
COORDINATOR
AutoCAD SHX Text
AutoCAD SHX Text
TRIAGE
AutoCAD SHX Text
AutoCAD SHX Text
PEDIATRIC
AutoCAD SHX Text
AutoCAD SHX Text
EXAM
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
EYE
AutoCAD SHX Text
DIABETIC
AutoCAD SHX Text
EXAM
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
EXAM
AutoCAD SHX Text
MAIN RECEPTION
AutoCAD SHX Text
SUB-
AutoCAD SHX Text
WAITING
AutoCAD SHX Text
AutoCAD SHX Text
TOILET
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
MEDICAL RECORDS
AutoCAD SHX Text
OFFICE
AutoCAD SHX Text
UTILITY
AutoCAD SHX Text
AutoCAD SHX Text
CLEAN
AutoCAD SHX Text
DIRTY
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
X-RAY
AutoCAD SHX Text
DISPENSING
AutoCAD SHX Text
MEDICAL CODING
AutoCAD SHX Text
AutoCAD SHX Text
UTILITY 2
AutoCAD SHX Text
AutoCAD SHX Text
JAN./
AutoCAD SHX Text
OFFICE 2
AutoCAD SHX Text
SUB-W
AutoCAD SHX Text
AutoCAD SHX Text
COPY CENTER
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
HALL
AutoCAD SHX Text
AutoCAD SHX Text
HALL
AutoCAD SHX Text
AutoCAD SHX Text
HALLWAY
AutoCAD SHX Text
AutoCAD SHX Text
HALLWAY
AutoCAD SHX Text
AutoCAD SHX Text
HALLWAY
AutoCAD SHX Text
AutoCAD SHX Text
HALLWAY
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
WAY
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
HALLWAY
AutoCAD SHX Text
HALL
AutoCAD SHX Text
DISPENSING
AutoCAD SHX Text
DISPENSING
AutoCAD SHX Text
VESTIBULE
AutoCAD SHX Text
AutoCAD SHX Text
HALLWAY
AutoCAD SHX Text
AutoCAD SHX Text
HALL
AutoCAD SHX Text
WAY
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
MECH.
AutoCAD SHX Text 124A
AutoCAD SHX Text
HWH
AutoCAD SHX Text
HALLWAY
AutoCAD SHX Text
AutoCAD SHX Text
REF
AutoCAD SHX Text
REF
AutoCAD SHX Text
WOMEN'S
AutoCAD SHX Text
EXAM
AutoCAD SHX Text
DIABETIC
AutoCAD SHX Text
RECEIVING
AutoCAD SHX Text
BUSINESS
AutoCAD SHX Text
OFFICE
AutoCAD SHX Text
CONFERENCE
AutoCAD SHX Text
IT DIRECTOR
AutoCAD SHX Text
CHS FILES
AutoCAD SHX Text
JANITORS
AutoCAD SHX Text
CLOSET
AutoCAD SHX Text
SERVICES (CHS)
AutoCAD SHX Text
(TWO STAFF)
AutoCAD SHX Text
CONTRACT HEALTH
AutoCAD SHX Text
RESTROOM
AutoCAD SHX Text
PAPER GOODS STG
AutoCAD SHX Text
BREAK ROOM
AutoCAD SHX Text
CEO OFFICE
AutoCAD SHX Text
STORAGE
AutoCAD SHX Text
MAIL ROOM
AutoCAD SHX Text
URGENT CARE
AutoCAD SHX Text
BENEFITS
AutoCAD SHX Text
AutoCAD SHX Text
(6 STAFF)
AutoCAD SHX Text
HALL &
AutoCAD SHX Text
RESOURCES
AutoCAD SHX Text
EDUCATIONAL
AutoCAD SHX Text
REF
AutoCAD SHX Text
REF
AutoCAD SHX Text
DENTAL RECEPT
AutoCAD SHX Text
AutoCAD SHX Text
TRIAGE
AutoCAD SHX Text
AutoCAD SHX Text
ADA
AutoCAD SHX Text
TRIAGE
AutoCAD SHX Text
AutoCAD SHX Text
REGISTRATION
AutoCAD SHX Text 180A
AutoCAD SHX Text
PATIENT
AutoCAD SHX Text
PROVIDERS
AutoCAD SHX Text
OFFICE
AutoCAD SHX Text
AutoCAD SHX Text
PROVIDERS
AutoCAD SHX Text
OFFICE
AutoCAD SHX Text
AutoCAD SHX Text
PROVIDERS
AutoCAD SHX Text
OFFICE
AutoCAD SHX Text
AutoCAD SHX Text
SUPPLY
AutoCAD SHX Text
MED GAS
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 204C
AutoCAD SHX Text
STAIRS
AutoCAD SHX Text
AutoCAD SHX Text
ELECT
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 208A
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
HALLWAY
AutoCAD SHX Text
AutoCAD SHX Text
EKG
AutoCAD SHX Text
AutoCAD SHX Text
SUPPLY
AutoCAD SHX Text
STORAGE
AutoCAD SHX Text 204B
AutoCAD SHX Text
STAIR
AutoCAD SHX Text 220A
AutoCAD SHX Text
DN
AutoCAD SHX Text
DN
AutoCAD SHX Text
DN
AutoCAD SHX Text
DN
AutoCAD SHX Text
DRESSING
AutoCAD SHX Text
AutoCAD SHX Text
SUPPLY
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
PROVIDER
AutoCAD SHX Text
VISITING
AutoCAD SHX Text
WEST WING
AutoCAD SHX Text
EAST WING
AutoCAD SHX Text
ADMINISTRATION
AutoCAD SHX Text T
AutoCAD SHX Text
AHU-1
AutoCAD SHX Text
AutoCAD SHX Text T
AutoCAD SHX Text
AHU-5
AutoCAD SHX Text
AutoCAD SHX Text T
AutoCAD SHX Text
AHU-2
AutoCAD SHX Text
AutoCAD SHX Text T
AutoCAD SHX Text
AHU-3
AutoCAD SHX Text
AutoCAD SHX Text T
AutoCAD SHX Text
AHU-4
AutoCAD SHX Text
AutoCAD SHX Text T
AutoCAD SHX Text
AHU-2
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
FITNESS ROOM
AutoCAD SHX Text
LAUNDRY &
AutoCAD SHX Text
JAN
AutoCAD SHX Text
STORAGE
AutoCAD SHX Text
STORAGE
AutoCAD SHX Text
SERVER ROOM
AutoCAD SHX Text
FURNACE ROOM
AutoCAD SHX Text
MECHANICAL
AutoCAD SHX Text
ELEC
AutoCAD SHX Text
FIRE RISER
AutoCAD SHX Text
DRYER
AutoCAD SHX Text
WASHER
AutoCAD SHX Text
WH
AutoCAD SHX Text
LINENS
AutoCAD SHX Text
(FUTURE GROUP WORK OR MTG RM)
AutoCAD SHX Text
STORAGE
AutoCAD SHX Text
LINEN
AutoCAD SHX Text
HALLWAY
AutoCAD SHX Text
STORAGE
AutoCAD SHX Text
FIRE RISER
AutoCAD SHX Text
RR
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 223A
AutoCAD SHX Text
IT
AutoCAD SHX Text 223B
AutoCAD SHX Text
UP
AutoCAD SHX Text
UP
AutoCAD SHX Text T
AutoCAD SHX Text
AHU-1
AutoCAD SHX Text
AutoCAD SHX Text
NOTED
AutoCAD SHX Text 764000M201
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text A
AutoCAD SHX Text B
AutoCAD SHX Text C
AutoCAD SHX Text A
AutoCAD SHX Text B
AutoCAD SHX Text C
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
REV
AutoCAD SHX Text
ISSUE:
AutoCAD SHX Text
PROJECT NO:
AutoCAD SHX Text
CAD DWG FILE:
AutoCAD SHX Text
DRAWN BY:
AutoCAD SHX Text
CHECKED BY:
AutoCAD SHX Text
SHEET TITLE
AutoCAD SHX Text
DATE
AutoCAD SHX Text
DESCRIPTION
AutoCAD SHX Text
CONSULTANTS
AutoCAD SHX Text
INDIAN HEALTH SERVICE
AutoCAD SHX Text
DIVISION OF ENGINEERING SERVICES
AutoCAD SHX Text E
AutoCAD SHX Text H
AutoCAD SHX Text N
AutoCAD SHX Text M
AutoCAD SHX Text E
AutoCAD SHX Text A
AutoCAD SHX Text R
AutoCAD SHX Text P
AutoCAD SHX Text T
AutoCAD SHX Text O
AutoCAD SHX Text F
AutoCAD SHX Text T
AutoCAD SHX Text C
AutoCAD SHX Text D
AutoCAD SHX Text S
AutoCAD SHX Text U
AutoCAD SHX Text S
AutoCAD SHX Text A
AutoCAD SHX Text E
AutoCAD SHX Text T
AutoCAD SHX Text A
AutoCAD SHX Text E
AutoCAD SHX Text L
AutoCAD SHX Text
AutoCAD SHX Text H
AutoCAD SHX Text N
AutoCAD SHX Text V
AutoCAD SHX Text I
AutoCAD SHX Text S
AutoCAD SHX Text E
AutoCAD SHX Text R
AutoCAD SHX Text U
AutoCAD SHX Text M
AutoCAD SHX Text A
AutoCAD SHX Text H
AutoCAD SHX Text
SEATTLE / DALLAS
AutoCAD SHX Text
DES BRANCH CHIEF
AutoCAD SHX Text
DES PROJECT MANAGER
AutoCAD SHX Text
AGENCY REPRESENTATIVE
AutoCAD SHX Text
APPROVED:
AutoCAD SHX Text
CONCURRENCE
AutoCAD SHX Text
TITLE
AutoCAD SHX Text
REVIEWED:
AutoCAD SHX Text
DES ARCHITECT / ENGINEER
AutoCAD SHX Text
DATE
AutoCAD SHX Text
DATE
AutoCAD SHX Text
DATE
AutoCAD SHX Text
DATE
AutoCAD SHX Text
SHEET ______ OF ______
AutoCAD SHX Text 12 W. Kennewick Ave.
AutoCAD SHX Text Kennewick, WA 99336
AutoCAD SHX Text P: 509.735.1589
AutoCAD SHX Text F: 509.783.5075
AutoCAD SHX Text www.meierinc.com
AutoCAD SHX Text
PROJECT NO: 15-7640
AutoCAD SHX Text WELLPINIT SERVICE UNIT HVAC REPLACEMENT 6203 AGENCY LOOP ROAD WELLPINIT, WASHINGTON 99040 PROJECT NUMBER PO4WE626C0PO4WE626C0
AutoCAD SHX Text
MECHANICAL OVERALL FLOOR PLAN
AutoCAD SHX Text 3/32" = 1'-0"
AutoCAD SHX Text M-201
AutoCAD SHX Text
MECHANICAL OVERALL FLOOR PLAN
AutoCAD SHX Text
PO4WE648C0
AutoCAD SHX Text
WM
AutoCAD SHX Text
DLA
AutoCAD SHX Text 3 66
AutoCAD SHX Text
SEE MECHANICAL ROOM PLAN ON SHEET M-401M-401
AutoCAD SHX Text
SEE MECHANICAL FURNACE ROOM ON SHEET M-401M-401
AutoCAD SHX Text
SEE ENLARGED PLAN (EAST MECHANICAL YARD) ON SHEET M-401M-401
AutoCAD SHX Text
NOTES
AutoCAD SHX Text
1. FOR GENERAL NOTES AND LEGEND SEE M-001. FOR GENERAL NOTES AND LEGEND SEE M-001. M-001. . 2. SEE M501 AND M601 FOR ADDITIONAL CONTROLS SEE M501 AND M601 FOR ADDITIONAL CONTROLS M501 AND M601 FOR ADDITIONAL CONTROLS AND M601 FOR ADDITIONAL CONTROLS M601 FOR ADDITIONAL CONTROLS FOR ADDITIONAL CONTROLS INFORMATION. 3. FLOOR PLAN ON THIS SHEET DOES NOT INCLUDE FLOOR PLAN ON THIS SHEET DOES NOT INCLUDE MODIFICATIONS MADE BY IHS PROJECT NO. P04WE626C0. SEE THESE DOCUMENTS FOR FLOOR PLAN MODIFICATIONS. 4. EXISTING INFORMATION IS DERIVED FROM AVAILABLE EXISTING INFORMATION IS DERIVED FROM AVAILABLE DOCUMENTS, FIELD OBSERVATIONS AND ASSUPTIONS. CONTRACTOR TO VERIFY CONDITIONS PRIOR TO PERFORMING WORK. 5. DO NOT INTERRUPT HVAC SERVICE TO OCCUPIED AREAS OF DO NOT INTERRUPT HVAC SERVICE TO OCCUPIED AREAS OF FACILITY WITHOUT WRITTEN PERMISSION OF COR. LIMIT SERVICE INTERRUPTIONS TO THE MINIMUM EXTENT POSSIBLE WHILE MAINTAINING FACILITY OPERATIONS DURING CONSTRUCTION.
AutoCAD SHX Text
FLAG NOTES
AutoCAD SHX Text REPLACE (E) THERMOSTAT WITH NEW UNIT. SEE M601 M601 FOR ADDITIONAL CONTROLS INFORMATION. (E) THERMOSTAT TO REMAIN. ROUTE NEW REFRIGERANT LINES ON RACK ON EXISTING ABOVE GRADE IF BID ALTERNATE 1 IS NOT SELECTED.
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
ADMINISTRATION BASEMENT PLAN
AutoCAD SHX Text 3/32" = 1'-0"
AutoCAD SHX Text north
AutoCAD SHX Text
AutoCAD SHX Text
HUMAN SERVICES
AutoCAD SHX Text
MECHANICAL
AutoCAD SHX Text
OP 1
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
DISPENSING
AutoCAD SHX Text
SUB-W
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
MECH.
AutoCAD SHX Text 124A
AutoCAD SHX Text
HWH
AutoCAD SHX Text
DENTAL RECEPT
AutoCAD SHX Text
AutoCAD SHX Text
(E)AHU
AutoCAD SHX Text
AutoCAD SHX Text
HP
AutoCAD SHX Text
AutoCAD SHX Text
HP
AutoCAD SHX Text
AutoCAD SHX Text
HP
AutoCAD SHX Text
AutoCAD SHX Text
HP
AutoCAD SHX Text
AutoCAD SHX Text
(E)HP
AutoCAD SHX Text
AutoCAD SHX Text
AHU
AutoCAD SHX Text
AutoCAD SHX Text
AHU
AutoCAD SHX Text
AutoCAD SHX Text
AHU
AutoCAD SHX Text
AutoCAD SHX Text
AHU
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
(NOT IN SCOPE)
AutoCAD SHX Text M
AutoCAD SHX Text M
AutoCAD SHX Text M
AutoCAD SHX Text
(E) RETURN AIR FAN RETURN AIR FAN MOTOR STARTERS RAF-1, 2, 5 ON WALL. INTERLOCK WITH NEW UNITS, SEE M501.M501..
AutoCAD SHX Text
(NOT IN SCOPE)
AutoCAD SHX Text
AutoCAD SHX Text
(E) FLOOR HATCHFLOOR HATCH
AutoCAD SHX Text M
AutoCAD SHX Text
(E) RAF-3 MOTOR STARTER RAF-3 MOTOR STARTER (ON CEILING)
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
REFRIGERANT PIPING STACKED ON ADJACENT WALL
AutoCAD SHX Text
SERVER ROOM
AutoCAD SHX Text
FURNACE ROOM
AutoCAD SHX Text
MECHANICAL
AutoCAD SHX Text
ELEC
AutoCAD SHX Text
HALLWAY
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 223A
AutoCAD SHX Text
IT
AutoCAD SHX Text 223B
AutoCAD SHX Text
AHU
AutoCAD SHX Text
AutoCAD SHX Text
AHU
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
HP
AutoCAD SHX Text
AutoCAD SHX Text
HP
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
(E) FENCINGFENCING
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
NO SCALE
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text A
AutoCAD SHX Text B
AutoCAD SHX Text C
AutoCAD SHX Text A
AutoCAD SHX Text B
AutoCAD SHX Text C
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
REV
AutoCAD SHX Text
ISSUE:
AutoCAD SHX Text
PROJECT NO:
AutoCAD SHX Text
CAD DWG FILE:
AutoCAD SHX Text
DRAWN BY:
AutoCAD SHX Text
CHECKED BY:
AutoCAD SHX Text
SHEET TITLE
AutoCAD SHX Text
DATE
AutoCAD SHX Text
DESCRIPTION
AutoCAD SHX Text
CONSULTANTS
AutoCAD SHX Text
INDIAN HEALTH SERVICE
AutoCAD SHX Text
DIVISION OF ENGINEERING SERVICES
AutoCAD SHX Text E
AutoCAD SHX Text H
AutoCAD SHX Text N
AutoCAD SHX Text M
AutoCAD SHX Text E
AutoCAD SHX Text A
AutoCAD SHX Text R
AutoCAD SHX Text P
AutoCAD SHX Text T
AutoCAD SHX Text O
AutoCAD SHX Text F
AutoCAD SHX Text T
AutoCAD SHX Text C
AutoCAD SHX Text D
AutoCAD SHX Text S
AutoCAD SHX Text U
AutoCAD SHX Text S
AutoCAD SHX Text A
AutoCAD SHX Text E
AutoCAD SHX Text T
AutoCAD SHX Text A
AutoCAD SHX Text E
AutoCAD SHX Text L
AutoCAD SHX Text
AutoCAD SHX Text H
AutoCAD SHX Text N
AutoCAD SHX Text V
AutoCAD SHX Text I
AutoCAD SHX Text S
AutoCAD SHX Text E
AutoCAD SHX Text R
AutoCAD SHX Text U
AutoCAD SHX Text M
AutoCAD SHX Text A
AutoCAD SHX Text H
AutoCAD SHX Text
SEATTLE / DALLAS
AutoCAD SHX Text
DES BRANCH CHIEF
AutoCAD SHX Text
DES PROJECT MANAGER
AutoCAD SHX Text
AGENCY REPRESENTATIVE
AutoCAD SHX Text
APPROVED:
AutoCAD SHX Text
CONCURRENCE
AutoCAD SHX Text
TITLE
AutoCAD SHX Text
REVIEWED:
AutoCAD SHX Text
DES ARCHITECT / ENGINEER
AutoCAD SHX Text
DATE
AutoCAD SHX Text
DATE
AutoCAD SHX Text
DATE
AutoCAD SHX Text
DATE
AutoCAD SHX Text
SHEET ______ OF ______
AutoCAD SHX Text 12 W. Kennewick Ave.
AutoCAD SHX Text Kennewick, WA 99336
AutoCAD SHX Text P: 509.735.1589
AutoCAD SHX Text F: 509.783.5075
AutoCAD SHX Text www.meierinc.com
AutoCAD SHX Text
PROJECT NO: 15-7640
AutoCAD SHX Text WELLPINIT SERVICE UNIT HVAC REPLACEMENT 6203 AGENCY LOOP ROAD WELLPINIT, WASHINGTON 99040 PROJECT NUMBER PO4WE626C0PO4WE626C0
AutoCAD SHX Text 764000M401
AutoCAD SHX Text M-401
AutoCAD SHX Text
MECHANICAL ENLARGED PLANS
AutoCAD SHX Text
PO4WE648C0
AutoCAD SHX Text
WM
AutoCAD SHX Text
DLA
AutoCAD SHX Text 4 66
AutoCAD SHX Text
WEST WING MECH RM & YARD PLAN
AutoCAD SHX Text 1/4" = 1'-0"
AutoCAD SHX Text
EAST WING MECH RM
AutoCAD SHX Text 1/4" = 1'-0"
AutoCAD SHX Text
EAST MECH YARD
AutoCAD SHX Text 1/4" = 1'-0"
AutoCAD SHX Text
NOTES
AutoCAD SHX Text
1. FOR GENERAL NOTES AND LEGEND SEE M-001. FOR GENERAL NOTES AND LEGEND SEE M-001. M-001. . 2. FOR ADDITIONAL INFORMATION ON EQUIPMENT TO BE FOR ADDITIONAL INFORMATION ON EQUIPMENT TO BE INSTALLED AT HVAC UNITS, SEE M501. M501. . 3. SEE M501 AND M601 FOR CONTROLS INFORMATION. SEE M501 AND M601 FOR CONTROLS INFORMATION. M501 AND M601 FOR CONTROLS INFORMATION. AND M601 FOR CONTROLS INFORMATION. M601 FOR CONTROLS INFORMATION. FOR CONTROLS INFORMATION. 4. EXISTING INFORMATION IS DERIVED FROM AVAILABLE EXISTING INFORMATION IS DERIVED FROM AVAILABLE DOCUMENTS, FIELD OBSERVATIONS AND ASSUMPTIONS. CONTRACTOR TO VERIFY CONDITIONS PRIOR TO PERFORMING WORK. 5. FLOOR PLAN ON THIS SHEET DOES NOT INCLUDE FLOOR PLAN ON THIS SHEET DOES NOT INCLUDE MODIFICATIONS MADE BY IHS PROJECT NO. P04WE626C0. SEE THESE DOCUMENTS FOR FLOOR PLAN MODIFICATIONS. 6. DO NOT INTERRUPT HVAC SERVICE TO OCCUPIED AREAS OF DO NOT INTERRUPT HVAC SERVICE TO OCCUPIED AREAS OF FACILITY WITHOUT WRITTEN PERMISSION OF COR. LIMIT SERVICE INTERRUPTIONS TO THE MINIMUM EXTENT POSSIBLE WHILE MAINTAINING FACILITY OPERATIONS DURING CONSTRUCTION.
AutoCAD SHX Text
FLAG NOTES
AutoCAD SHX Text INSTALL NEW HEAT PUMP ON (E) CONCRETE PAD. COORDINATE ORIENTATION WITH MANUFACTURER'S CLEARANCES AND (E) FENCING. CONNECT POWER TO UNITS. INSTALL NEW AIR HANDLING UNIT. CONNECT (E) OR (N) REFRIGERANT PIPING AND POWER TO UNITS.
This is the start of the file's text. The full file is on GovTribe.
File details come from the government source that posted it. Updated .