Amendment_0004_SF30.pdf

PDF 52 KB Posted

Attached to
Wellpinit Service Unit Modernization Project Federal contract opportunity
Solicitation number
16-102-SOL-00031
Issued by
Department of Health and Human Services Indian Health Service

About this file

Amendment 0004

View the file

Other files for this federal contract opportunity

Other files attached to Wellpinit Service Unit Modernization Project, newest first.
File Type Posted
Amendment_0008_SF30.pdf PDF
Construction_Wage_Determination_MOD_07.pdf PDF
Amendment_0007_SF30.pdf PDF
J-_12_Wellpinit_Service_Unit_Clinic_RBM_Report_Sept_2014.pdf PDF
Amendment_0006_SF30.pdf PDF
Site_Walk_Attendance_Sheet.pdf PDF
Amendment_0005_SF30.pdf PDF
J-11__Amendment_on_Sheet_No__E-101.pdf PDF
J-10_Construction_Wage_Determination..pdf PDF
Amendment_0003_SF30.pdf PDF
J-04_Architectural_2_of_2_Rev_1.pdf PDF
Amendment_0002_SF30.pdf PDF
Amendment_0001_SF30.pdf PDF
J-02_Specifications.pdf PDF
Solicitation_16-102-SOL-00031.pdf PDF
J-07_Electrical.pdf PDF
J-04_Architectural_2_of_2.pdf PDF
J-_05_Mechanical_1_of_2.pdf PDF
J-06_Mechanical_2_of_2.pdf PDF
J-03_Architectural_1_of_2.pdf PDF
J-_01_Contract_Requirements.pdf PDF
J-09_PPI.doc DOC document
Show all 22

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

NSN 7540-01-152-8070 30-105 STANDARD FORM 30 (REV. 10-83)

PREVIOUS EDITIONS UNUSABLE Prescribed by GSA FAR (48 CFR) 53.243

AMENDMENT OF SOLICITATION/MODIFICATION OF CONTRACT

1. Contract ID Code Page of Pages

2. Amendment/Modification No.

3. Effective Date

26 November 16

4. Requisition/Purchase Req. No. 5. Project No. (if applicable)

6. Issued By Code

Indian Health Service DES 701 Fifth Ave, Suite 1600 M/S-24 Seattle, WA 98104

7. Administered By (If other than Item 6) Code

Same as block 6

8. Name and Address of Contractor (No., Street, County, and Zip Code) (X) 9A. Amendment of Solicitation No.

16-102-SOL-00031

X 9B. Date (See Item 11)

8 November 2016 10A. Modification of Contract/Order No.

10B. Date (See Item 13)

Code Facility Code

11. THIS ITEM ONLY APPLIES TO AMENDMENTS OF SOLICITATIONS

X The above numbered solicitation is amended as set forth in item 14. The hour and date specified for receipt of Offers is extended X is not extended.

Offers must acknowledge receipt of this amendment prior to the hour and date specified in the solicitation or as amended, by one of the following methods:

(a) By completing items 8 and 15, and returning 1 copies of the amendment; (b) By acknowledging receipt of this amendment on each copy of the offer submitted; or (c) By separate letter or telegram which includes a reference to the solicitation and amendment numbers. FAILURE OF YOUR ACKNOWLEDG- MENT TO BE RECEIVED AT THE PLACE DESIGNATED FOR THE RECEIPT OF OFFERS PRIOR TO THE HOUR AND DATE SPECIFIED MAY RESULT

IN REJECTION OF YOUR OFFER. If by virtue of this amendment you desire to change an offer already submitted, such change may be made by telegram or letter, provided each telegram or letter makes reference to the solicitation and this amendment, and is received prior to the opening hour and date specified.

12. Accounting and Appropriation Data (if required)

13. THIS ITEM APPLIES ONLY TO MODIFICATIONS OF CONTRACT/ORDERS.

IT MODIFIES THE CONTRACT/ORDER NO. AS DESCRIBED IN ITEM 14.

A. This change order is issued pursuant to: (Specify authority) The changes set forth in item 14 are made in the Contract Order No. in item 10A.

B. The above numbered Contract/Order is modified to reflect the administrative changes (such as changes in paying office, appropriation date, etc.)

Set fourth item 14, pursuant to the authority of FAR 43.103 (b)

C. This supplemental agreement is entered into pursuant to authority of:

D. Other (Specify type of modification and authority)

E. IMPORTANT: Contractor is not, is required to sign this document and return copies to the issuing office.

14. Description of Amendment/Modification (Organized by UCF section headings, including solicitation/contract subject matter where feasible.)

Wellpinit Service Unit Modernization Prepared by: Fannon, John W.

16-102-SOL-00031

************************Description of this amendment begins on page 2****************

Except as provided herein, all terms and conditions of the document referenced in item 9A or 10A, as heretofore changed, remains unchanged and in full force and effect.

15A. Name and Title of Signer (Type or Print) 16A. Name and title of Contracting Officer (Type or Print)

15B. Contractor/Offeror

(Signature of person authorized to sign)

15C. Date Signed 16B. United States of America

(Signature of Contracting Officer)

16C. Date Signed

SF30 Continuation of Block Narrative Page of

SUMMARY OF CHANGES

The solicitation is hereby amended to address the following:

1. Provide an amended Sheet No E-101 as attachment J-11.

2. Respond to Pre-Proposal Inquiries (PPI) received in addressing the solicitation package.

PPI RESPONSE:

Section J is hereby amended as follows:

SECTION J – LIST OF ATTACHMENTS

SECTION J

DOCUMENTS, EXHIBITS, AND OTHER ATTACHMENTS

TABLE OF CONTENTS

ATTACHMENT

NUMBER ATTACHMENT TITLE

J-01 Contract Requirement J-02 Design and Specifications J-03 Architectural 1 of 2 J-04 Architectural 2 of 2 REV 1 J-05 Mechanical 1 of 2 J-06 Mechanical 2 of 2 J-07 Electrical J-08 Past Performance Questioner J-09 Pre Proposal Inquiry (PPI) J-10 Construction Wage Determination J-11 Amendment on Sheet No E-101

INQUIRY 0008:

Solicitation 16-102-SOL-0003, Plan Sheet A-103 Keynote 13 calls out for installing new overhead coiling windows, 2 ea. The Specification for these units 08 33 13 Coiling Counter Doors notes in Paragraph 2.3 HOODS

A. General: Form sheet metal hood to entirely enclose coiled curtain and operating mechanism at opening head. Contour to fit end brackets to which hood is attached. Roll and reinforce top and bottom edges for stiffness. Form closed ends for surface-mounted hoods and fascia for any portion of between-jamb mounting that projects beyond wall face. Equip hood with intermediate support brackets as required to prevent sagging.

1. Include automatic drop baffle on fire-rated doors to guard against passage of smoke or flame.

Q: The plan set does not include the coiling counter doors on the Door and Window Schedule, Plan Sheet A-601 to note any special requirements of the doors; nor is there any clear detail in the specifications. Are the two coiling counter doors per Keynote 13 Sheet A-103 to be fire rated? If so, what rating: 20 minute, 45 minute …? If these are to be rated doors then the countertop assembly, per 2009 NFPA 13 must also meet the same rating threshold in construction and require additional design clarification.

2 5

RESPONSE PROVIDED:

The wall where the coiling door units in question are located is not fire-rated. Therefore, automatic drop baffle and fire rating are not required for these units. Comply with all other requirements of the plans and specifications. –Response by Derek L. Archer, PE, Meier Architecture-Engineering.

INQUIRY 0009:

Plan Sheet A102 Phase 0 on the overall floor plan shows a 4-0 wide X 4-0 long X 6-0 high fence with gate around a new compressor pad. Detail 2 on A102 notes concrete pad per Mechanical.

Q-1): Detail 1 corresponds to the overall floor plan showing a 4-0 square enclosure. Detail 2 shows a 6-0 wide gate. Is the chain link enclosure 4-0 foot square or 4-0 x 6-0?

Q-2): The overall floor plans references the concrete pad to the Mechanical. M100 shows the new condensing unit CU-1 and FC-1 and reference M601 for details, but no details on the size of the unit or the exterior housekeeping pad could be found in the Mechanical plans. The specifications only state to install the CU on a cast-in-place concrete pad and there are no concrete specifications for this project.

What is the size and thickness of the CU-1 cast-in-place concrete pad and the performance specification for the concrete mix; 6-Sack 3,500 PSI; 6-Sack 4,000 PSI or ?

RESPONSE PROVIDED:

Fenced enclosure for CU-1 is intended to be approximately 4 feet wide by 4 feet long by 6 feet tall at a minimum. Fence enclosure size shall be coordinated with actual CU-1 equipment provided to ensure that manufacturer's recommended installation clearances are maintained. Basis of design unit is approximately 26 inches long by 12 inches wide and is shown at its approximate size on M100. Clearances in this case are approximately 5 inches on the wall side of the enclosure, 12 inches on the gate side of the enclosure, 2 inches on the east side, and sufficient space on the west side to install refrigerant piping and allow for service. Centering the unit inside the enclosure as shown on M100 provides all of these clearances within a 4 foot square enclosure.

Concrete housekeeping pad size shall be coordinated with size of actual CU-1 equipment provided. Pad size shall be a minimum of 6 inches beyond anchor points of CU-1. The approximate pad size shown on M100 of 27 inches by 34 inches allows for this clearance on the basis of design unit.

Concrete mix shall be 2,500 psi. Thickness shall be minimum of 6 inches. 4 inches above grade, 2 inches below grade. – Response by Derek L. Archer, PE, Meier Architecture- Engineering

INQUIRY 0010:

Solicitation 16-102-SOL-00031, Plan Sheet A 202, General Note 2 states to build all ceiling heights to 9’-0” UNO. Plan Sheet A-601 shows the ceiling height for Room 180A Records/Reception to be 9-0. Typically soffits are constructed to provide a visual break in

3 5 the ceiling plane, however there is no elevation provided on Plan Sheet A-203 for the soffit.

Q) - What is the elevation, AFF of the new soffit planned for room 180A?

RESPONSE PROVIDED:

Existing soffit is 8-0" AFF and existing adjacent ceiling is 8'-6" AFF. New soffit shall be aligned with existing soffit. Field verify actual height and match existing. – Response by Derek L. Archer, PE, Meier Architecture-Engineering.

INQUIRY 0011:

Solicitation 16-102-SOL-00031 Plan Sheet Detail A/A108 Kiosk Elevation shows the basis of design BEST sign panel and components that are detailed in the project specifications.

However, there are no cross sections or details regarding the Kiosk structure.

Q.- What is the construction of the Kiosk, is it to be design-build, is it to be constructed per one of the design wall types, is it to be detailed within the cabinet and casework design with 2x framing and sub-countertop sheathing with plastic laminate to match the new countertops?

RESPONSE PROVIDED:

See the Plan view on Sheet A-108 and Specification section 101400, including submittal requirements.

INQUIRY 0012:

Solicitation 16-102-SOL-00031 Phase 2B, Plan Sheet A-105, Demolition Detail, Room 165 does not have a keynote on the countertop that is shown in a dashed line indicating removal.

Q. – Is the countertop in room 165 on the Demo Detail of sheet A-105 to be demolished per Keynote 3 or Salvaged per Keynote 4?

RESPONSE PROVIDED:

The countertops in Rooms 165 and 166 are to be salvaged as necessary in order to successfully accomplish Keynote 14. Remainder to be demolished.

Add Alternate #1” on Sheet A-105 to be ignored. Those items will all be included in CLIN

INQUIRY 0013:

Solicitation 16-102-SOL-00031, contract document Plan Sheet A106 is Titled Phase 3- Pharmacy/Imaging while the two details on the plan sheet are titled Phase 4 Pharmacy/Imaging. Plant Sheet A107 is Titled Phase 4- Laboratory while the two details on the plan sheet are Titled Phase 5 – Laboratory.

4 5

Q.- Please clarify which Phase is correct on each plan sheet, the sheet title or the detail title?

RESPONSE PROVIDED:

Sheet A-106 is Phase 3, Pharmacy/Imaging.

Sheet A-107 is Phase 4, Laboratory.

The detail title phase numbers are incorrect on each sheet. Sheet A-106 should say Phase 3, and Sheet A-107 should say Phase 4.

END OF THE AMENDMENT. All other terms and conditions remain unchanged.

The proposal due date IS NOT EXTENDED as a result of this Amendment.