072100 thermal insulation.pdf

PDF 12 KB Posted

Attached to
CONSTRUCT USPFO WAREHOUSE
Solicitation number
W91364-09-B-0003
Issued by

About this file

072100 thermal insulation.pdf

View the file

Other files

File Type Posted
ADDENDUM NO 02 CSMS PH II Narrative SENT.pdf PDF
USPFO_M001W.pdf PDF
019313 operation and maintenance manuals.pdf PDF
001 Binder Cover Specs Vol 1.pdf PDF
USPFO_S301W.pdf PDF
083613 sectional doors.pdf PDF
E001.pdf PDF
321313 concrete pavement surfacing.pdf PDF
USPFO_F601W.pdf PDF
260548 vibration and seismic controls for elec systems.pdf PDF
OHARNG-USPFO-A-254W .pdf PDF
C607.pdf PDF
051200 structural steel framing.pdf PDF
USPFO_S253W.pdf PDF
053100 steel decking.pdf PDF
344116 traffic control.pdf PDF
013300c attachment substitution request.pdf PDF
105626.13 mobile aisle storage shelving.pdf PDF
C700.pdf PDF
054000 cold-formed metal framing.pdf PDF
260553 electrical identification.pdf PDF
OHARNG-USPFO-A-001W .pdf PDF
E804.pdf PDF
USPFO_M204W.pdf PDF
221116 domestic water piping.pdf PDF
260529 hangers and supports for electrical systems.pdf PDF
274133 cable antenna television system.pdf PDF
264113 lightning protection for structures.pdf PDF
011000 summary —
OHARNG_USPFO_Q601W.pdf PDF
OHARNG-USPFO-G-001W .pdf PDF
C100.pdf PDF
211313 wet-pipe sprinkler systems.pdf PDF
231123 facility natural gas piping.pdf PDF
OHARNG-USPFO-G-110W .pdf PDF
013233 photographic documentation.pdf PDF
260923 lighting control devices .pdf PDF
C605.pdf PDF
087113 automatic door operators.pdf PDF
087100 door hardware.pdf PDF
USPFO_S001W.pdf PDF
312000 earthwork.pdf PDF
220500 common work results for plumbing.pdf PDF
USPFO_M202W.pdf PDF
OHARNG-USPFO-A-720W .pdf PDF
USPFO_M303W.pdf PDF
USPFO_P302W.pdf PDF
USPFO_S254W.pdf PDF
OHARNG-USPFO-G-116W .pdf PDF
010001 affirmative procurement.pdf PDF
Show 40 more

50 files listed here. See the rest on GovTribe.

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

F5W61608 USPFO Warehouse Ohio Army National Guard Rev. 0 Defense Supply Center Columbus, Ohio 30 January 2009 Bid Final

THERMAL INSULATION 072100 - 1

SECTION 072100 - THERMAL INSULATION

PART 1 - GENERAL

1.1 SUMMARY

A. This Section includes the following:

1. Perimeter insulation under slabs-on-grade.

2. Concealed building insulation.

3. Vapor retarders.

4. Sound attenuation insulation.

1.2 PERFORMANCE REQUIREMENTS

A. Plenum Rating: Provide glass-fiber insulation where indicated in ceiling plenums whose test performance is rated as follows for use in plenums as determined by testing identical products per "Erosion Test" and "Mold Growth and Humidity Test" described in UL 181, or on comparable tests from another standard acceptable to authorities having jurisdiction.

1. Erosion Test Results: Insulation shows no visible evidence of cracking, flaking, peeling, or delamination of interior surface of duct assembly, after testing for 4 hours at 2500-fpm air velocity.

2. Mold Growth and Humidity Test Results: Insulation shows no evidence of mold growth, delamination, or other deterioration due to the effects of high humidity, after inoculation with Chaetomium globosium on all surfaces and storing for 60 days at 100 percent relative humidity in the dark.

1.3 SUBMITTALS

A. Product Data: For each type of product indicated.

B. Samples for Verification: Full-size units for each type of exposed insulation indicated.

C. LEED Submittals:

1. Product Data for Credit MR 4.1: For products having recycled content, documentation indicating percentages by weight of postconsumer and preconsumer recycled content.

a. Include statement indicating costs for each product having recycled content.

Defense Supply Center Columbus, Ohio 30 January 2009 Bid Final

THERMAL INSULATION 072100 - 2

D. Product test reports.

E. Research/Evaluation Reports: For foam-plastic insulation.

1.4 QUALITY ASSURANCE

A. Fire-Test-Response Characteristics: Provide insulation and related materials with the fire-test-response characteristics indicated, as determined by testing identical products per ASTM E 84 for surface-burning characteristics, by UL or another testing and inspecting agency acceptable to authorities having jurisdiction. Identify materials with appropriate markings of applicable testing and inspecting agency.

B. Recycled Content: Provide glass-fiber insulation with recycled content so postconsumer recycled content plus one-half of preconsumer recycled content constitutes a minimum of 10 percent by weight.

PART 2 - PRODUCTS

2.1 FOAM-PLASTIC BOARD INSULATION

A. Extruded-Polystyrene Board Insulation: ASTM C 578, Type IV, 1.60 lb/cu. ft., with maximum flame-spread and smoke-developed indexes of 75 and 450, respectively:

1. Manufacturers:

a. DiversiFoam Products.

b. Dow Chemical Company.

c. Owens Corning.

d. Pactiv Building Products Division.

2.2 GLASS-FIBER BLANKET INSULATION (BATT)

A. Manufacturers:

1. CertainTeed Corporation.

2. Johns Manville.

3. Knauf Fiber Glass.

4. Owens Corning.

B. Unfaced, Glass-Fiber Blanket Insulation: ASTM C 665, Type I (blankets without membrane facing); consisting of fibers; with maximum flame-spread and smoke-developed indexes of 25 and 50, respectively; passing ASTM E 136 for combustion characteristics.

Defense Supply Center Columbus, Ohio 30 January 2009 Bid Final

THERMAL INSULATION 072100 - 3

C. Where glass-fiber blanket insulation is indicated by the following thicknesses, provide blankets in batt or roll form with thermal resistances indicated:

1. 6-1/2 inches thick with a thermal resistance of21 deg F x h x sq. ft./Btu at 75 deg F.

2.3 SOUND ATTENUATION INSULATION

A. Sound Attenuation Blankets: ASTM C 665, Type I (blankets without membrane facing) produced by combining thermosetting resins with mineral fibers manufactured from glass, slag wool, or rock wool

2.4 VAPOR RETARDERS

A. Vapor Barrier: Provide a vapor barrier that meets ASTM E 96 requirements for permeability and as follows:

1. Mixed Climates: Class III, 10 perms or less, installed on the warm winter side of all assemblies.

PART 3 - EXECUTION

3.1 INSTALLATION, GENERAL

A. Comply with insulation manufacturer's written instructions applicable to products and application indicated.

B. Install insulation that is undamaged, dry, and unsoiled and that has not been left exposed at any time to ice, rain, and snow.

C. Extend insulation in thickness indicated to envelop entire area to be insulated. Cut and fit tightly around obstructions and fill voids with insulation. Remove projections that interfere with placement.

D. Water-Piping Coordination: If water piping is located within insulated exterior walls, coordinate location of piping to ensure that it is placed on warm side of insulation and insulation encapsulates piping.

3.2 INSTALLATION OF UNDER-SLAB INSULATION

A. On vertical surfaces, set insulation units in adhesive applied according to manufacturer's written instructions. Use adhesive recommended by insulation manufacturer.

Defense Supply Center Columbus, Ohio 30 January 2009 Bid Final

THERMAL INSULATION 072100 - 4

1. If not otherwise indicated, extend insulation a minimum of 24 inches below exterior grade line.

B. On horizontal surfaces, loosely lay insulation units according to manufacturer's written instructions. Stagger end joints and tightly abut insulation units.

C. Protect top surface of horizontal insulation from damage during concrete work by applying protection course with joints butted.

3.3 INSTALLATION OF GENERAL BUILDING INSULATION

A. Apply insulation units to substrates by method indicated, complying with manufacturer's written instructions. If no specific method is indicated, bond units to substrate with adhesive or use mechanical anchorage to provide permanent placement and support of units.

B. Install mineral-fiber insulation in cavities formed by framing members according to the following requirements:

1. Use insulation widths and lengths that fill the cavities formed by framing members. If more than one length is required to fill cavity, provide lengths that will produce a snug fit between ends.

2. Place insulation in cavities formed by framing members to produce a friction fit between edges of insulation and adjoining framing members.

3. Maintain 3-inch clearance of insulation around recessed lighting fixtures.

4. For metal-framed wall cavities where cavity heights exceed 96 inches, support unfaced blankets mechanically and support faced blankets by taping flanges of insulation to flanges of metal studs.

3.4 INSTALLATION OF INSULATION IN CEILINGS FOR SOUND ATTENUATION

A. Install 3 1/2-inch- thick, unfaced glass-fiber blanket insulation over suspended ceilings at partitions in a width that extends insulation 48 inches on either side of partition.

END OF SECTION 072100