BDG Table of Contents SWF2 – REV2 1

BASE DEFENSE GROUP BEDDOWN

SECURITY FORCES – BUILDING 106

PROJECT NUMBER WHAY089079

105th AIRLIFT WING

NEW YORK AIR NATIONAL GUARD

STEWART INTERNATIONAL AIRPORT

NEWBURGH, NY

TABLE OF CONTENTS

DIVISION 01 – GENERAL REQUIREMENTS

011100 Summary of Work 011900 References 012300 Options 012500 Substitutions 012600 Change Orders / Modifications to Contract 013100 Project Coordination and Meetings 013200 Construction Progress Schedules and Reports 013233 Construction Photographs 013300 Submittals 014000 Quality Requirements 014100 Environmental Protection 014200 Definitions and Standards 015100 Temporary Utilities and Facilities 015200 Field Offices and Sheds 015700 Temporary Barriers and Controls 015800 Project Identification and Signs 016000 Equipment and Materials 017329 Cutting and Patching 017419 Construction Waste Management and Disposal 017500 Manufacturer’s Field Services 017800 Contract Closeout 017836 Warranties 018113 Sustainable Design Requirements Supplement – Sustainable Design Analysis Score Sheet 018150 Recycled / Recovered Materials 019113 Commissioning Requirements

DIVISION 02 – SITE WORK

024100 Demolition

DIVISION 03 – CONCRETE

031000 Concrete Formwork 031550 Vapor Retarder 032000 Concrete Reinforcement

2 BDG Table of Contents SWF2-REV2

DIVISION 03 – CONCRETE (continued)

033000 Concrete

DIVISION 04 – MASONRY

042000 Unit Masonry

DIVISION 05 – METALS

051200 Steel 052100 Steel Joists 053113 Steel Floor Deck 053123 Steel Roof Deck 054000 Cold-Formed Steel Framing 055000 Metal Fabrications 055100 Metal Stairs

DIVISION 06 – WOOD AND PLASTICS

061000 Rough Carpentry

061000.01 Anchors and Fasteners

061600 Sheathing 064023 Interior Architectural Woodwork

DIVISION 07 – THERMAL AND MOISTURE PROTECTION

071113 Bituminous Dampproofing 072100 Thermal Insulation 074113 Metal Roof Panels 074213 Metal Wall Panels 074216 Insulated-Core Metal Wall Panels 075323 Ethylene-Propylene-Diene-Monomer (EPDM) Roofing 076200 Sheet Metal Flashing and Trim 077200 Roof Accessories 078413 Penetration Firestopping 079200 Joint Sealants 079500 Expansion Control

DIVISION 08 – DOORS AND WINDOWS

081113 Hollow Metal Doors and Frames 081416 Flush Wood Doors 083113 Access Doors and Frames 083323 Overhead Coiling Doors 083459 Vault Doors and Day Gates 084413 Glazed Aluminum Curtain Walls 085113 Aluminum Windows 087000 Finish Hardware 088000 Glazing 089000 Louvers and Vents

BDG Table of Contents SWF2-REV2 3

DIVISION 09 – FINISHES

092216 Non-Structural Metal Framing 092900 Gypsum Board 093000 Tiling 095123 Acoustic Tile Ceilings 096513 Resilient Base And Accessories 096519 Resilient Tile Flooring 096813 Tile Carpeting 097200 Wall Coverings 099000 Protective Coatings

DIVISION 10 – SPECIALITIES

101100 Visual Display Surfaces 101400 Signage 102113 Toilet Compartments 102219 Demountable Partitions 102226 Operable Partitions 102800 Toilet And Bath Accessories 104413 Fire Extinguisher Cabinets 105113 Metal Lockers

105626.10 Mobile Storage Shelving – Secured Weapons Cabinets

105626.23 Mobile Storage Shelving – Storage Lockers

107500 Flagpoles

DIVISION 11 – EQUIPMENT

115213 Projection Screens

DIVISION 12 – FURNISHINGS

122113 Horizontal Louver Blinds 124813 Entrance Floor Mats and Frames 129300 Site Furnishings

DIVISION 14 – CONVEYING SYSTEMS

142400 Hydraulic Elevator

DIVISION 21 – FIRE SUPPRESSION

210500 Common Work Results for Fire Suppression 211000 Fire-Suppression Piping

DIVISION 22 – PLUMBING

220500 Common Work Results for Plumbing 220513 Common Motor Requirements for Plumbing Equipment 220516 Expansion Fittings and Loops for Plumbing Piping

4 BDG Table of Contents SWF2-REV2

DIVISION 22 – PLUMBING (continued)

220519 Meters and Gauges for Plumbing Piping 220523 General-Duty Valves for Plumbing Piping 220529 Hangers and Supports for Plumbing Piping and Equipment 220548 Vibration and Seismic Controls for Plumbing Piping and Equipment 220553 Identification for Plumbing Piping and Equipment 221116 Domestic Water Piping 221119 Domestic Water Piping Specialties 221123 Domestic Water Pumps 221316 Sanitary Waste and Vent Piping 221319 Sanitary Waste Piping Specialties 221413 Facility Storm Drainage Piping 221423 Storm Drainage Piping Specialties 221429 Sump Pumps 223400 Fuel-Fired Water Heaters 224000 Plumbing Fixtures 224700 Drinking Fountains and Water Coolers

DIVISION 23 – HEATING, VENTILATING AND AIR CONDITIONING

230500 Common Work Results for HVAC 230513 Common Motor Requirements for HVAC Equipment 230516 Expansion Fittings and Loops for HVAC Piping 230519 Meters and Gauges for HVAC Piping 230523 General-Duty Valves for HVAC Piping 230529 Hangers and Supports for HVAC Piping and Equipment 230548 Vibration and Seismic Controls for HVAC Piping and Equipment 230553 Identification for HVAC Piping and Equipment 230593 Testing, Adjusting and Balancing 230700 Mechanical Insulation 230933 Direct Digital Control (DDC) Systems (Electric Actuation) 231123 Facility Natural Gas Piping 232113 Hydronic Piping 232123 Hydronic Pumps 232300 Refrigerant Piping 233113 Metal Ducts 233300 Duct Accessories 233423 Power Ventilators 233700 Air Terminal Units 233713 Diffusers, Registers and Grilles 233725 Intake and Relief Ventilators 233813 Commercial Kitchen Hoods 235216 Condensing Boilers 236423 Scroll Water Chillers 237200 Air-to-Air Energy Recovery Equipment 237313 Modular Central-Station Air-Handling Units 238123 Computer-Room Air-Conditioners 238126 Split-System Air-Conditioning Units 238153 Rooftop Kitchen Replacement-Air Units 238219 Fan-Coil Units

BDG Table of Contents SWF2-REV2 5

DIVISION 23 – HEATING, VENTILATING AND AIR CONDITIONING (continued)

238239 Cabinet Unit Heaters 238240 Propeller Unit Heaters

DIVISION 26 - ELECTRICAL

260000 Basic Electrical Requirements 260516 Wires and Cables 260526 Grounding 260529 Supporting Devices and Seals 260533 Raceways 260534 Electrical Boxes and Fittings 260536 Cable Tray 260553 Electrical Identification 260800 Field Testing 260923 Lighting Control Equipment 262213 Transformers and Medium Voltage Pad-mounted Sectionalizer Switch 262416 Panelboards 262713 Service Entrance 262726 Wiring Devices 262730 Electrical Connections and Equipment 262813 Fuses 262816 Circuit and Motor Disconnect Switches 262900 Motor Controllers, Contactors, Push Buttons, Selector Switches, Indicating Lights, and

Relays 263213 Diesel Generator Set (Option #1) 263600 Transfer Switch (Base Bid: Manual Transfer Switch; Option #1: Automatic Transfer

Switch) 264100 Lightning Protection Systems 264300 Surge Protective Device (SPD) formerly known as Transient Voltage

Surge Suppression (TVSS) 265000 Interior Lighting Fixtures 265200 Emergency Lighting 265610 Exterior Lighting Fixtures

DIVISION 27 – COMMUNICATIONS

275116 Public Address System 276000 Communication, Premises Distribution System

DIVISION 28 – ELECTRONIC SAFETY AND SECURITY

283100 Fire Alarm Systems 283150 Mass Notification System 283200 Intrusion Detection System

6 BDG Table of Contents SWF2-REV2

DIVISION 31 – EARTHWORK

312000 Site Preparation and Earthwork 312313 Subgrade Preparation

DIVISION 32 – EXTERIOR IMPROVEMENTS

321100 Crushed Rock Base Course 321214 Bituminous Prime Coat 321215 Bituminous Tack Coat 321217 Hot-Mix Asphaltic-Concrete Pavement 321600 Curbs, Gutters, and Sidewalks 321723 Pavement Marking 323113 Chain-Link Fences and Gates 329200 Lawns

DIVISION 33 – UTILITIES

331100 Pressure Pipe 331123 Natural Gas Distribution 331216 Utility Valves and Accessories 333100 Gravity Pipe 333150 Pipe Installation 333900 Utility Structures

BDG238126.SWF2.DOC 238126-1

SECTION 238126 - SPLIT-SYSTEM AIR-CONDITIONING UNITS

PART 1 - GENERAL

1.01 SUMMARY:

A. This Section includes split-system air-conditioning and heat pump units consisting of separate evaporator-fan and compressor-condenser components. Units are designed for exposed or concealed mounting, and may be connected to ducts.

1.02 REFERENCES:

A. Applicable Standards (Latest Edition):

1. Air-Conditioning and Refrigeration Institute (ARI):

a. 210/240 - Unitary Air-Conditioning and Air-Source Heat Pump Equipment.

2. National Fire Protection Association (NFPA):

a. 70 - National Electrical Code.

1.03 SUBMITTALS:

A. General: Submit each item in this Article in accordance with SECTION 220500 - BASIC

MECHANICAL MATERIALS AND METHODS.

B. Product Data: Include rated capacities, furnished specialties, and accessories for each type of product indicated. Include performance data in terms of capacities, outlet velocities, static pressures, sound power characteristics, motor requirements, and electrical characteristics.

C. Shop Drawings: Diagram power, signal, and control wiring.

D. Samples for Initial Selection: For units with factory-applied color finishes.

E. Field quality-control test reports.

F. Operation and Maintenance Data: For split-system air-conditioning units to include in emergency, operation, and maintenance manuals.

G. Warranty: Special warranty specified in this Section.

H. LEED Submittals:

1. Credit EA 4: Manufacturers' product data for refrigerants, including printed statement that refrigerants are free of HCFCs.

1.04 QUALITY ASSURANCE:

A. Product Options: Drawings indicate size, profiles, and dimensional requirements of split-system units and are based on the specific system indicated. Refer to DIVISION 1.

B. Electrical Components, Devices, and Accessories: Listed and labeled as defined in NFPA 70, Article 100, by a testing agency acceptable to authorities having jurisdiction, and marked for intended use.

C. Energy-Efficiency Ratio: Equal to or greater than prescribed by ASHRAE 90.1.

D. Coefficient of Performance: Equal to or greater than prescribed by ASHRAE 90.1.

E. Units shall be designed to operate with HCFC-free refrigerants.

1.05 COORDINATION:

A. Coordinate size and location of concrete bases for units. Cast anchor-bolt inserts into bases.

Concrete, reinforcement, and formwork are specified in DIVISION 3.

B. Coordinate size, location, and connection details with roof curbs, equipment supports, and roof penetrations specified in DIVISION 7.

1.06 WARRANTY:

SECTION 238126 - SPLIT-SYSTEM AIR-CONDITIONING UNITS: continued

238126-2 BDG238126.SWF2.DOC

A. Special Warranty: Manufacturer's standard form in which manufacturer agrees to repair or replace components of split-system air-conditioning units that fail in materials or workmanship within specified warranty period.

1. Warranty Period: Five years from Date of Substantial Completion.

1.07 EXTRA MATERIALS:

A. Furnish extra materials described below that match products installed and that are packaged with protective covering for storage and identified with labels describing contents.

1. Filters: One set of filters for each unit.

2. Fan Belts: One set of belts for each unit.

PART 2 - PRODUCTS

2.01 MANUFACTURERS:

A. Manufacturers: Subject to compliance with requirements, provide products by one of those listed below.

1. Carrier Air Conditioning; Div. of Carrier Corporation.

2. Daikin Industries, Ltd.

3. Lennox Industries Inc.

4. Trane Company (The); Unitary Products Group.

5. York International Corp.

2.02 CEILING-MOUNTING, EVAPORATOR-FAN COMPONENTS:

A. Cabinet: Enameled steel with removable panels on front and ends in color selected by

Engineer, and discharge drain pans with drain connection.

B. Refrigerant Coil: Copper tube, with mechanically bonded aluminum fins, complying with

ARI 210/240, and with thermal-expansion valve.

C. Fan: Direct drive, centrifugal fan, with power-induced outside air, and integral condensate pump.

D. Fan Motors: Comply with requirements in SECTION 230513 - COMMON MOTOR

REQUIREMENTS FOR HVAC EQUIPMENT.

1. Special Motor Features: Multitapped, multispeed with internal thermal protection and permanent lubrication.

E. Filters: Permanent, cleanable.

2.03 AIR-COOLED, COMPRESSOR-CONDENSER COMPONENTS:

A. Casing: Steel, finished with baked enamel in color selected by Engineer, with removable panels for access to controls, weep holes for water drainage, and mounting holes in base.

Provide brass service valves, fittings, and gauge ports on exterior of casing.

B. Compressor: Hermetically sealed with crankcase heater and mounted on vibration isolation.

Compressor motor shall have thermal- and current-sensitive overload devices, start capacitor, relay, and contactor.

1. Compressor Type: Scroll.

2. Two-speed compressor motor with manual-reset high-pressure switch and automatic-reset low-pressure switch.

3. Refrigerant Type: R-410A.

C. Refrigerant Coil: Copper tube, with mechanically bonded aluminum fins, complying with ARI 210/240, and with liquid subcooler.

D. Heat Pump Components: Reversing valve and low-temperature air cut-off thermostat.

BDG238126.SWF2.DOC 238126-3

E. Fan: Aluminum-propeller type, directly connected to motor.

F. Motor: Permanently lubricated, with integral thermal-overload protection.

G. Low Ambient Kit: Permits operation down to 0F.

H. Mounting Base: Polyethylene.

2.04 ACCESSORIES:

A. Control equipment are specified in SECTION 230933 – DIRECT DIGITIAL CONTROL

(DDC) SYSTEMS (ELECTRIC ACTUATION).

B. Thermostat: Low voltage with subbase to control compressor and evaporator fan.

C. Automatic-reset timer to prevent rapid cycling of compressor.

D. Refrigerant Line Kits: Soft-annealed copper suction and liquid lines factory cleaned, dried, pressurized, and sealed; factory-insulated suction line with flared fittings at both ends.

E. Additional Monitoring:

1. Monitor constant variable motor loads.

2. Monitor cooling load.

3. Monitor air distribution static pressure and ventilation air volumes.

PART 3 - EXECUTION

3.01 INSTALLATION:

A. Install units level and plumb.

B. Install evaporator-fan components using manufacturer's standard mounting devices securely fastened to building structure.

C. Install ground-mounting, compressor-condenser components on 4-inch- (100-mm-) thick, reinforced concrete base; 4 inches (100 mm) larger on each side than unit. Concrete, reinforcement, and formwork are specified in DIVISION 3. Coordinate anchor installation with concrete base.

D. Install seismic restraints.

E. Install and connect precharged refrigerant tubing to component's quick-connect fittings. Install tubing to allow access to unit.

3.02 CONNECTIONS:

A. Piping installation requirements are specified in other DIVISION 23 Sections. Drawings indicate general arrangement of piping, fittings, and specialties.

B. Install piping adjacent to unit to allow service and maintenance.

C. Duct Connections: Duct installation requirements are specified in SECTION 233113 -

METAL DUCTS. Drawings indicate the general arrangement of ducts. Connect supply ducts to split-system air-conditioning units with flexible duct connectors. Flexible duct connectors are specified in SECTION 233300 - DUCT ACCESSORIES.

D. Ground equipment according to DIVISION 26.

E. Electrical Connections: Comply with requirements in DIVISION 26 for power wiring, switches, and motor controls.

3.03 FIELD QUALITY CONTROL:

A. Manufacturer's Field Service: Engage a factory-authorized service representative to inspect, test, and adjust field-assembled components and equipment installation, including connections, and to assist in field testing. Report results in writing.

B. Perform the following field tests and inspections and prepare test reports:

238126-4 BDG238126.SWF2.DOC

1. Leak Test: After installation, charge system and test for leaks. Repair leaks and retest until no leaks exist.

2. Operational Test: After electrical circuitry has been energized, start units to confirm proper motor rotation and unit operation.

3. Test and adjust controls and safeties. Replace damaged and malfunctioning controls and equipment.

C. Remove and replace malfunctioning units and retest as specified above.

3.04 STARTUP SERVICE:

A. Engage a factory-authorized service representative to perform startup service.

1. Complete installation and startup checks according to manufacturer's written instructions.

3.05 DEMONSTRATION:

A. Engage a factory-authorized service representative to train Owner's maintenance personnel to adjust, operate, and maintain units. Refer to DIVISION 1.

END OF SECTION 238126

BDGBDG238219.SWF2.DOC 238219-1

PART 1 -

SECTION 238219 - FAN-COIL UNITS

1.01

GENERAL

SUMMARY

A. This Section includes fan-coil units and accessories.

B. Direct Expansion (DX) units are specified under Section 238125 - Split System Air-

Conditioning Units.

1.02 REFERENCES

A. Applicable Standards:

1. Air-Conditioning and Refrigeration Institute (ARI):

a. 210/240 - Unitary Air Conditioning & Air-Source Heat Pump Equipment.

b. 440 - Room Fan Coils and Unit Ventilators.

2. American Society of Heating, Refrigerating and Air-Conditioning Engineers (ASHRAE):

a. 33 - Methods of Testing Forced Circulation Air Cooling and Heating Coils (ANSI).

b. 52.1 - Gravimetric and Dust-Spot Procedures for Testing Air-Cleaning Devices

Used in General Ventilation for Removing Particulate Matter (ANSI).

c. 52.2 - Gravimetric and Dust-Spot Procedures for Testing Air-Cleaning Devices for

Removal Efficiency by Particle Size (ANSI).

d. 62 - Ventilation for Acceptable Indoor Air Quality (ANSI).

3. ASME International (ASME):

a. B16.22 - Wrought Copper and Copper Alloy Solder Joint Pressure Fittings.

4. ASTM International (ASTM):

a. A126 - Gray Iron Castings for Valves, Flanges, and Pipe Fittings.

b. B88 - Seamless Copper Water Tube.

c. B88M - Seamless Copper Water Tube (Metric).

d. B743 - Seamless Copper Tube in Coils.

e. C916 - Adhesives for Duct Thermal Insulation.

f. C1071 - Fibrous Glass Duct Lining Insulation (Thermal and Sound Absorbing

Material).

g. E84 - Test Method for Surface Burning Characteristics of Building Materials.

5. NFPA International (NFPA):

a. 70 - National Electrical Code.

SECTION 238219 - FAN-COIL UNITS: continued

238219-2 BDGBDG238219.SWF2.DOC

b. 90A - Installation of Air Conditioning and Ventilating Systems.

6. Underwriters Laboratories Inc. (UL):

a. 1995 - Heating and Cooling Equipment.

1.03

A. BAS: Building automation system.

DEFINITIONS:

1.04 SUBMITTALS

A. General: Submit the following as specified in SECTION 230500 - COMMON WORK

RESULTS FOR HVAC.

B. Product Data: Include rated capacities, operating characteristics, furnished specialties, and accessories for each unit type and configuration.

C. Shop Drawings: Detail equipment assemblies and indicate dimensions, weights, loads, required clearances, method of field assembly, components, and location and size of each field connection.

1. Wiring Diagrams: Power, signal, and control wiring. Differentiate between manufacturer-installed and field-installed wiring.

D. Coordination Drawings: Floor plans, reflected ceiling plans, and other details, drawn to scale, on which the following items are shown and coordinated with each other, based on input from installers of the items involved:

1. Ceiling suspension components.

2. Structural members to which fan-coil units will be attached.

3. Method of attaching hangers to building structure.

4. Size and location of initial access modules for acoustical tile.

5. Items penetrating finished ceiling, including the following:

a. Lighting fixtures.

b. Air outlets and inlets.

c. Speakers.

d. Sprinklers.

e. Access panels.

6. Perimeter moldings for exposed or partially exposed cabinets.

E. Samples for Initial Selection: For units with factory-applied color finishes.

F. Samples for Verification: For each type of fan-coil unit indicated.

BDGBDG238219.SWF2.DOC 238219-3

091007

G. Manufacturer Seismic Qualification Certification: Submit certification that fan-coil units, accessories, and components will withstand seismic forces defined in SECTION 230548 -

VIBRATION AND SEISMIC CONTROLS FOR HVAC PIPING AND EQUIPMENT.

Include the following:

1. Basis for Certification: Indicate whether withstand certification is based on actual test of assembled components or on calculation.

a. The term "withstand" means "the unit will remain in place without separation of any parts from the device when subjected to the seismic forces specified and the unit will be fully operational after the seismic event."

2. Dimensioned Outline Drawings of Equipment Unit: Identify center of gravity and locate and describe mounting and anchorage provisions.

3. Detailed description of equipment anchorage devices on which the certification is based and their installation requirements.

H. Field quality-control test reports.

I. Operation and Maintenance Data: For fan-coil units to include in emergency, operation, and maintenance manuals. In addition to items specified in SECTION 230500 - COMMON

WORK RESULTS FOR HVAC, include the following:

1. Maintenance schedules and repair part lists for motors, coils, integral controls, and filters.

J. Warranty: Special warranty specified in this Section.

1.05 QUALITY ASSURANCE

A. Electrical Components, Devices, and Accessories: Listed and labeled as defined in NFPA 70, Article 100, by a testing agency acceptable to authorities having jurisdiction, and marked for intended use.

1.06 COORDINATION

A. Coordinate layout and installation of fan-coil units and suspension system components with other construction that penetrates or is supported by ceilings, including light fixtures, HVAC equipment, fire-suppression-system components, and partition assemblies.

PART 2 -

2.01

PRODUCTS

FAN-COIL UNITS:

238219-4 BDGBDG238219.SWF2.DOC

A. Manufacturers: Subject to compliance with requirements, provide products by one of the following:

1. McQuay International.

2. Trane.

3. YORK International Corporation.

B. Description: Factory-packaged and -tested units rated according to ARI 440, ASHRAE 33, and UL 1995.

C. Coil Section Insulation: 1-inch (25-mm) thick, foil-covered, closed-cell foam complying with

ASTM C1071 and attached with adhesive complying with ASTM C916.

1. Fire-Hazard Classification: Insulation and adhesive shall have a combined maximum flame-spread index of 25 and smoke-developed index of 50 when tested according to

ASTM E84.

D. Main and Auxiliary Drain Pans: Stainless steel formed to slope from all directions to the drain connection as required by ASHRAE 62.

E. Chassis: Galvanized steel where exposed to moisture.

F. Cabinet: Steel with baked-enamel finish in manufacturer's standard paint color as selected by

Engineer.

1. Horizontal Unit Bottom Panels: Fastened to unit with cam fasteners and hinge and attached with safety chain; with integral stamped discharge grilles.

2. Steel recessing flanges for recessing fan-coil units into ceiling or wall.

G. Filters: Minimum arrestance according to ASHRAE 52.1, and a minimum efficiency reporting value (MERV) according to ASHRAE 52.2.

1. Pleated Cotton-Polyester Media: 90% arrestance and 8 MERV.

H. Hydronic Coils: Copper tube, with mechanically bonded aluminum fins spaced no closer than

0.1 inch (2.5 mm), rated for a minimum working pressure of 200 psig (1378 kPa) and a maximum entering-water temperature of 220oF (104o

I. Fan and Motor Board: Removable.

C). Include manual air vent and drain valve.

1. Fan: Forward curved, double width, centrifugal; directly connected to motor.

Thermoplastic or painted-steel wheels, and aluminum, painted-steel, or galvanized-steel fan scrolls.

BDGBDG238219.SWF2.DOC 238219-5

2. Motor: Permanently lubricated, multispeed; resiliently mounted on motor board.

Comply with requirements in SECTION 230513 - COMMON MOTOR

REQUIREMENTS FOR HVAC EQUIPMENT.

3. Wiring Termination: Connect motor to chassis wiring with plug connection.

J. Factory, Hydronic Piping Package: ASTM B88, Type L (ASTM B88M, Type B) copper tube with wrought-copper fittings and brazed joints. Label piping to indicate service, inlet, and outlet.

1. Two-way, modulating control valve for chilled-water coil.

2. Two-Piece Ball Valves: Bronze body with full-port, chrome-plated bronze ball; PTFE or

TFE seats; and 600-psig (4140-kPa) minimum CWP rating and blowout-proof stem.

3. Automatic Flow-Control Valve: Brass or ferrous-metal body; 300-psig (2070-kPa) working pressure at 250oF (121o

4. Y-Pattern Hydronic Strainers: Cast-bronze body (85-5-5-5); 125-psig (860-kPa) working pressure; with threaded connections, bolted cover, perforated stainless-steel basket, and bottom drain connection. Include minimum NPS 1/2 (DN 15) hose-end, full-port, ball-type blowdown valve in drain connection.

C), with removable, corrosion-resistant, tamperproof, self-cleaning piston spring; factory set to maintain constant indicated flow with plus or minus 10% over differential pressure range of 2 to 80 psig (13.8 to 552 kPa).

5. Wrought-Copper Unions: ASME B16.22.

K. Control devices are specified in SECTION 230933 – Direct Digital Control (DDC) Systems

(Electric Actuation), sequences of operations are indicated in drawings.

L. BAS Interface Requirements:

1. Interface relay for scheduled operation.

2. Interface relay to provide indication of fault at the central workstation.

3. Provide BACnet or LonWorks interface for central BAS workstation for the following functions:

a. Adjust set points.

b. Fan-coil-unit start, stop, and operating status.

c. Data inquiry, including [outdoor-air damper position, ]supply- and room-air temperature[ and humidity].

d. Occupied and unoccupied schedules.

M. Electrical Connection: Factory wire motors and controls for a single electrical connection.

N. Capacities and Characteristics:

238219-6 BDGBDG238219.SWF2.DOC

1. Capacities and Characteristics are scheduled on drawings

2.02 DUCTED FAN-COIL UNITS

A. Manufacturers: Subject to compliance with requirements, provide products by one of the following:

1. McQuay International.

2. Trane.

3. YORK International Corporation.

B. Description: Factory-packaged and -tested units rated according to ARI 440, ASHRAE 33, and UL 1995.

C. Coil Section Insulation: 1-inch (25-mm) thick, foil-covered, closed-cell foam complying with

ASTM C1071 and attached with adhesive complying with ASTM C916.

1. Fire-Hazard Classification: Insulation and adhesive shall have a combined maximum flame-spread index of 25 and smoke-developed index of 50 when tested according to

ASTM E84.

D. Drain Pans: Stainless steel formed to slope from all directions to the drain connection as required by ASHRAE 62.

E. Chassis: Galvanized steel where exposed to moisture, with baked-enamel finish and removable access panels.

F. Cabinets: Steel with baked-enamel finish in manufacturer's standard paint color.

1. Supply-Air Plenum: Sheet metal plenum finished and insulated to match the chassis.

2. Return-Air Plenum: Sheet metal plenum finished to match the chassis.

G. Filters: Minimum arrestance according to ASHRAE 52.1, and a minimum efficiency reporting value (MERV) according to ASHRAE 52.2.

1. Pleated Media 2-inches thick and with: 8 MERV or 13 MERV according to schedules on drawings..

H. Hydronic Coils: Copper tube, with mechanically bonded aluminum fins spaced no closer than

0.1 inch (2.5 mm), rated for a minimum working pressure of 200 psig (1378 kPa) and a maximum entering-water temperature of 220oF (104o

I. Direct-Driven Fans: Double width, forward curved, centrifugal; with permanently lubricated, multispeed motor resiliently mounted in the fan inlet. Aluminum or painted-steel wheels, and painted-steel or galvanized-steel fan scrolls.

C). Include manual air vent and drain.

BDGBDG238219.SWF2.DOC 238219-7

J. Factory, Hydronic Piping Package: ASTM B88, Type L (ASTM B88M, Type B) copper tube with wrought-copper fittings and brazed joints. Label piping to indicate service, inlet, and outlet.

1. Two-way, modulating control valve for chilled-water coil.

2. Two-way, modulating control valve for heating coil.

3. Two-Piece Ball Valves: Bronze body with full-port, chrome-plated bronze ball; PTFE or

TFE seats; and 600-psig (4140-kPa) minimum CWP rating and blowout-proof stem.

4. Automatic Flow-Control Valve: Brass or ferrous-metal body; 300-psig (2070-kPa) working pressure at 250oF (121o

5. Y-Pattern Hydronic Strainers: Cast-Bronze body (85-5-5-5); 125-psig (860-kPa) working pressure, with threaded connections, bolted cover, perforated stainless-steel basket, and bottom drain connection. Include minimum NPS 1/2 (DN 15) hose-end, full-port, ball-type blowdown valve in drain connection.

C); with removable, corrosion-resistant, tamperproof, self-cleaning piston spring; factory set to maintain constant indicated flow with plus or minus 10% over differential pressure range of 2 to 80 psig (13.8 to 552 kPa).

6. Wrought-Copper Unions: ASME B16.22.

K. Control devices are specified in DIVISION 230933 – Direct Digital Control (DDC) Systems

(Electric Actuation), sequences of operations are indicated on drawings.

L. Electrical Connection: Factory wire motors and controls for a single electrical connection.

M. Capacities and Characteristics:

1. Capacities and Characteristics are scheduled on drawings

PART 3 -

3.01

EXECUTION

EXAMINATION

A. Examine areas to receive fan-coil units for compliance with requirements for installation tolerances and other conditions affecting performance.

B. Examine roughing-in for piping and electrical connections to verify actual locations before fan-coil-unit installation.

C. Proceed with installation only after unsatisfactory conditions have been corrected.

3.02 INSTALLATION

A. Install fan-coil units level and plumb.

B. Install fan-coil units to comply with NFPA 90A.

238219-8 BDGBDG238219.SWF2.DOC

C. Suspend fan-coil units from structure with elastomeric hangers. Vibration isolators are specified in SECTION 230548 - VIBRATION AND SEISMIC CONTROLS FOR HVAC

PIPING AND EQUIPMENT.

D. Verify locations of thermostats, humidistats, and other exposed control sensors with Drawings and room details before installation. Install devices 60 inches (1525 mm) above finished floor.

E. Install new filters in each fan-coil unit within two weeks after Substantial Completion.

3.03

A. Piping installation requirements are specified in other Sections. Drawings indicate general arrangement of piping, fittings, and specialties. Specific connection requirements are as follows:

CONNECTIONS:

1. Install piping adjacent to machine to allow service and maintenance.

2. Connect piping to fan-coil-unit factory hydronic piping package. Install piping package if shipped loose.

3. Connect condensate drain to indirect waste.

a. Install condensate trap of adequate depth to seal against the pressure of fan. Install cleanouts in piping at changes of direction. Provide condensate pumps where indicated.

B. Connect supply and return ducts to fan-coil units with flexible duct connectors specified in

SECTION 233300 - DUCT ACCESSORIES. Comply with safety requirements in UL 1995 for duct connections.

C. Ground equipment according to DIVISION 26.

D. Connect wiring according to DIVISION 26.

3.04 FIELD QUALITY CONTROL

A. Manufacturer's Field Service: Engage a factory-authorized service representative to inspect field-assembled components and equipment installation, including connections. Report results in writing.

B. Perform the following field tests and inspections and prepare test reports:

1. Operational Test: After electrical circuitry has been energized, start units to confirm proper motor rotation and unit operation.

2. Test and adjust controls and safety devices. Replace damaged and malfunctioning controls and equipment.

BDGBDG238219.SWF2.DOC 238219-9

C. Remove and replace malfunctioning units and retest as specified above.

3.05 ADJUSTING

A. Adjust initial temperature and humidity set points.

B. Occupancy Adjustments: When requested within 12 months of date of Substantial

Completion, provide on-site assistance in adjusting system to suit actual occupied conditions.

Provide up to two visits to Project during other than normal occupancy hours for this purpose.

3.06 DEMONSTRATION

A. Engage a factory-authorized service representative to train Owner's maintenance personnel to adjust, operate, and maintain fan-coil units. Refer to DIVISION 1.

END OF SECTION 238219