W912P5-17-R-0002_Reference_Drawings.pdf
PDF 22 MB Posted
- Attached to
- Wolf Creek Station Service Upgrade
- Solicitation number
- W912P5-17-R-0002
About this file
Contract Reference Drawings
View the file
Other files
Show all 37
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
N
NO. 6
NO. 3
NO. 1
NO. 4
NO. 8 NO. 8 NO. 8
111 112
A
12"0 5' 10' 15'
1'-10…"
17'-7" 3'-0"
11" 3'-6" 11'-3" 3'-2" 3'-0" 14'-7" 7'-0"
1'
1'
1'
2'-6"
1'
2'-8"
1'-5"
1'-7"
1'
1'-7" 1'-5"
21'-8" 22'-0" 23'-9" 4'-0" 27'-0" 27'-0" 4'-0" 27'-0" 27'-0" 4'-0" 27'-0" 27'-0" 4'-0"
1'-0"
1†"
2'-10"
1'
13'-6ƒ" 1'-4•" 8'-9ƒ"
OPNG.
2'-0"
6"
12'-3"9'-6"
1'
1'-0"
1'-4•"
1'-0"
0ƒ"
8" 7'-7•" 8" 9'-6ƒ" 8"
1'-3"
5'-10†"
3'-10…" 12'-5…" 8'-9†" 15'-8†" 5'-6…"
1' ƒ
12'-0•" 3'-9"
6'-1†
1'-3"
4' -1 0…
3' -9 ƒ
2'-6"
8"
2'-9" 24'-3" 2'-0" 2'-0" 27'-0" 27'-0" 2'-0" 2'-0" 27'-0" 9'-0‚" 17'-11ƒ" 2'-0"
5'-10†" 5'-10†"
15'-6" 12'-5…"
1†"
8'-9†" 15'-8†" 5'-6…" 15'-6" 12'-5…"
1†"
8'-9†" 15'-8†" 5'-6…" 13'-7†"
15'-1…" 3'-0"
1'-0"
9"
1'
439'-5" TO
ƒ
0ƒ"
8" 7'-7•" 8"
20'-0" I.D. (TYP.)
58'-0" (TYP.)
1'
3' -3
2'-4"
1'
1'
SEPARATION JOINT
NOT IN THIS CONTRACT
STORAGE BINS
DRAIN
OVEN
DRYING
OIL PUMP
FIRE DAMPER
16"x24" GRILLE &
PURIFIER
DRAIN
STORE ROOM
S T
O R
A G
E
T A
N K
L U
B R
IC
A T
IN
O
IL
S T
O R
A
N K
L U
B R
IC
A T
IL
PURIFIER
DRAIN
PUMPS
SEE Q2/729-H
FIRE DAMPER
16x32" GRILLE &
R
U P
R
D N
DRAIN
SEPTIC TANK EJECTOR
SEWAGE
16"x24" GRILLE
STRAINER
8" TWIN
ELEV.
NOT IN POWERHOUSE CONTRACT
FACE OF DAM STEP
DRAIN
DRAIN
WATER TREATMENT PLANT
DRAIN DRAIN
U-7
SEPARATION JOINT
DRAINDRAIN
DRAIN
FACE OF DAM
U P
C O
N T
R A
C T
IO
N
J
O
IN
T
U-3SUMP
AND
PUMP
TRENCH
TANK
PRESSURE
METAL FRAME AND COVER
U P
UP DOWN UP
U P
EL. 567.0
D N
GRATING
TRENCH
TRENCH
D N
UNIT NO. 2 UNIT NO. 3
U-2SUMP
AND
PUMP
TANK
PRESSURE
TRENCH
TURBINE ROOM EL. 567.0
CEMENT MORTAR FIN. FLOOR
U-1
SUMP
AND
PUMP
TANK
PRESSURE
U P
DOWNUP
UNIT NO. 1
MANUFACTURER
TURBINE
METAL STAIRS BY
RAMP
N O
N S
L
IP
S
R F
A C
E
R A
M P
H
V E
E L .0
S T
A T
IO
R V
IC
B
Y
C E
M E
M
R T
F
O
IS
H
F
IL
L
DRAIN
S W
IT
C H
B O
A R
D DOWN
T A
N K
SD
R A
IN
R E T
A
IN
W
L L
N
O
W E
R H
O U
C
N T
R A
C T
A C
F
E
E
D
C
D
B
C O
N T
R A
C T
IO
N
J
O
IN
T
7 8 8•
C
1 17
9 10•105 6 6•
SEE DWG. Q2/717-A AND Q2/717-B.
FOR DETAILS OF MONOLITH #54
NOTE:
B
4•4
LADDER
DRAFT TUBE GATE
DRAFT TUBE
LADDER TO
A
A
B
C
D
D
E
F
E
S T
O R
A G
E
D R
A
IN
F
IR
M P
E R
"x
G R
IL
IL
D R
A
IN
T R
A N
S
IL
GRILLE
8"x16"
Co2 STORAGE
16 R
DN.
PIPE
UP 26 R
VALVES
GENERATOR
GRATING
5 R
UP
C O
N T
R A
C T
IO
N
J
O
IN
T
C O
N T
R A
C T
IO
N
J
O
IN
T
GRATINGGOVERNOR
GRATING
COVER
PUMPS
D N
METAL FRAME AND COVER
TRENCH
C O
N T
R A
C T
IO
N
J
O
IN
T
DRAFT TUBE
ACCESS TO
LADDER
GRATING
C O
N T
R A
C T
IO
N
J
O
IN
T
B
GENERAL NOTES
FOR SECTION "A-A" & "B-B" SEE DRAWING Q2/736.
FOR SECTION "C-C" SEE DWG. Q2/735.
FOR SECTION "D-D" SEE DWG. Q2/737.
FOR SECTION "E-E" SEE DWG. Q2/738.
FOR STAIRS NO. 3 SEE DWG. Q2/729-E.
FOR PIPE TRENCH DETAILS SEE DWG. Q2/750-G.
FOR STAIRS NO. 6 SEE DWG. Q2/729-B.
FOR STAIRS NO. 8 SEE DWG. Q2/730-B.
FOR TYPICAL WALL SECTIONS SEE DWG. Q2/733-B.
FOR CIRCULAR STAIRS SEE DWG. Q2/729-B.
FOR STAIRS NO. 1 & NO. 4 ON DWG. Q2/729-D.
FOR AREAS MARKED "NOT IN POWERHOUSE CONTRACT" SEE DWG. Q2/717.
12345
B
C
D
A
B
C
D
A
Drawn By:
Date:
Drawing
Number
U.S. ARMY ENGINEER DISTRICT
CORPS OF ENGINEERS
NASHVILLE, TENNESSEE
Checked By:
US Army Corps of Engineers Nashville District
Record Drawing as constructed dated
Approved By:
REV. DESCRIPTION DATE CHECKED
REVISIONS
BY
ATLANTA, GA
CADD CONSULTANT
CARPENTER DUNLAP ASSOCIATES, INC.
Scale:
Sheet
CUMBERLAND RIVER WATERSHED
WOLF CREEK RESERVOIR PROJECT
CUMBERLAND RIVER, KENTUCKY
POWERHOUSE
„" = 1'-0" of
ZGA1:[110,20]Q2E729.DGN
TURBINE ROOM FLOOR PLAN - EL. 567.0
F.M.G.
A.R.K.
W. M. HALL
T. M. CONE
MADICY WILDING
CHAS. T. MAIN, INC.
HEAD ENGINEER
COL., C.O.E. DIST. ENG.
Q-2/729.5
FLOOR PLAN - ELEVATION 567.0
UNITS NO. 1-2-3
Scale: „" = 1'-0-"
1 12-27-48 H.G.W. T.H.P.STORE RM., DOOR 102 & WALL BETWEEN 3B & 4B REV.
2 7-17-50 C.W.B.
3 7-28-50 T.H.P.
4 T.H.P.
5 11-29-50 T.H.P.
CHANGE COL. LOCATION BETWEEN 2 & 3 LINES ON D
CORRECT COLUMN LOCATION D-LINE 2 TO 3
RELOCATE S.S. GEN. BUS DUCT OPENING
REVISE WALL AT S.S. GEN. BUS DUCT OPENING
9-7-50
NO. 9
NO. 8
NO. 8
NO. 8NO. 8
NO. 4
NO. 8
12"0 5' 10' 15' ƒ
8" 7'-7•"
8"
3'-1"
3'-9"
27'-0"2'-0"
27'-0" 2'-0"
9'-0" 11'-9"
27'-0"
58'-0" (TYP.)
20'-0" I.D. (TYP.)
27'-0"27'-0" 2'-0" 2'-0" 27'-0"
1'
1' ƒ
1'-8"
2'-0"
17'-4…" 3'-9"3' -9
1'-3"
6'-1†
3' -3 5' -4
1†"
1'-10…" 12'-5…" 8'-9†" 15'-8†"
4'-0" 27'-0" 27'-0" 4'-0"
15'-0" 3'-9"
1'
3'-0" 3'-0"
3'-0"
3'-0"
1'
15'-0" 3'-9"
27'-0" 27'-0" 4'-0"
1'
439'-5" TO
27'-0" 27'-0"
4'-0" 27'-0" 27'-0" 24'-0"
5'-10†" 5
5'-6…"
5'-6…" 15'-6"
1†"
5'-10†"
12'-5…" 8'-9†" 15'-8†"
5'-6…" 15'-6" 12'-5…" 8'-9†"
1†"
5'-10†"
15'-8†" 5'-6…" 11'-7†"
21'-3"
17'-6"3'-9"
U-7
DRAIN
SEPARATION JOINT
U P
DRAIN
TRENCH
TANK
PRESSURE
SUMP
AND
PUMP
FIN. FL. EL. 567.0
U-3
C O
N T
R A
C T
IO
N
J
O
IN
T
NOT IN POWERHOUSE CONTRACT
FACE OF DAM
DRAIN
113 CFM COMPRESSOR
330 CFM COMPRESSOR
34 CF RECEIVER
96 CF RECEIVER
275 CF RECEIVER DRAIN
SEPARATION JOINT
10.8 CFM COMPRESSOR
DRAIN
DRAIN
7'-9•"
CEILING
CONTRACT
NOT IN POWER HOUSE
E L .0
F
IN
F L
P
SEPARATION JOINT
7'-11"
CEILING
DN. 42 R
NO. 10
TANK
PRESSURE
SUMP
AND
PUMP
U-6
TURBINE ROOM EL. 567.0
(CEMENT MORTAR FINISH)
TRENCH
TANK
PRESSURE
METAL FRAME AND COVER
SUMP
AND
PUMP
U-5
UNIT NO. 6
TANK
PRESSURE
AND SUMP
OIL PUMP
GOVERNOR
U-4
U P
UP
U P
DN.
MANUFACTURER
TURBINE
METAL STAIRS BY
UP DN.
GRATING
D N
METAL FRAME AND COVER
TRENCH
UP
U P
DN. UP
U P
EL. 567.0
FIN. FL.
B O
A R
D
S W
D N
15 R
DN.
NO. 11
G
E
D
AND COVER
METAL FRAME
SUMP PUMPS
F
IN
F L
E L .0
D N
STAIRS
METAL CIRCULAR
C O
N T
R A
C T
IO
N
J
O
IN
T
TRENCH
TRENCH
GRATING
G
D N
GRATING
D N
DN.
14 R
DN.
EL. 553.0
LANDING
15 R
UPNO. 11
14 R
UP
EL. 544.33
G
PLATFORM
G
EL. 553.67
FIN. FL.
C O
N T
R A
C T
IO
N
J
O
IN
T
D N
F
C O
N T
R A
C T
IO
N
J
O
IN
T
D
F
PLANS OF PUMP SUMP
8 8• 9
10•10
A
11 12 12• 13
1 17
1615 17
A
B
C
D
F
E
17161514 14•11 12 12• 1310•1098 8•
F
D
E
B
C
UNIT NO. 3 UNIT NO. 4 UNIT NO. 5
C O
N T
R A
C T
IO
N
J
O
IN
T
E
14 14•
AT ELEVATION 544.33
B B
AT ELEVATION 553.67
GENERAL NOTES
FOR SECTION "D-D" SEE DRAWING Q2/737-A.
FOR SECTION "E-E" SEE DRAWING Q2/738-A.
FOR SECTION "F-F" AND "G-G" SEE DRAWING Q2/735-A.
FOR CIRCULAR STAIRS SEE DWG. Q2/729-B.
FOR STAIRS NO. 9-10-11 SEE DWG. Q2/729-F.
FOR TRENCHES SEE DWGS. Q2/750-A AND Q2/750-G.
FOR AREAS MARKED "NOT IN POWERHOUSE CONTRACT"
SEE DWG. Q2/717.
12345
B
C
D
A
B
C
D
A
Drawn By:
Date:
Drawing
Number
U.S. ARMY ENGINEER DISTRICT
CORPS OF ENGINEERS
NASHVILLE, TENNESSEE
Checked By:
US Army Corps of Engineers Nashville District
Record Drawing as constructed dated
Approved By:
REV. DESCRIPTION DATE APPROVED
REVISIONS
BY
CARPENTER DUNLAP ASSOCIATES, INC.
CADD CONSULTANT
ATLANTA, GA
Scale:
Sheet
CUMBERLAND RIVER WATERSHED
WOLF CREEK RESERVOIR PROJECT
CUMBERLAND RIVER, KENTUCKY
POWERHOUSE
„" = 1'-0" of
Q-2/729A
TURBINE ROOM FLOOR PLAN - ELEVATION 567.0
F.M.G.-A.R.K.
J.R.B.
W. M. HALL
T. M. CONE
MADICEY WILDING
CHAS. T. MAIN, INC.
HEAD ENGINEER
COL., C.O.E. DIST. ENG.
ZGA1:[110,20]Q2X729A.DGN
FLOOR PLAN - ELEVATION 567.0
UNITS. NO. 4-5-6
Scale: „" = 1'-0"
T-3
12"0 5' 10' 15'
Scale: „" = 1'-0"F
GENERATOR ROOM FLOOR PLAN - EL. 580.0
D
E
F
E
D
8'-6"
6"
11'-2•" 6'-6"
10'-7" 7'-9"
2'-2"
1'-4"
8" 7'-9" 8"
6'-9‚"
1"
1'
2'-0"
2'-0"
3'-6"
3"
1'-4"
16'-2"
1'-2"
3'-0"
24'-0"27'-0"27'-0"4'-0"27'-0"27'-0"4'-0"27'-0"27'-0"4'-0"
439'-5" TO
1'
1"
2'-0"
2'-0"
3'-0"
8"
2'-0"
2'-0"
1'
ARCHITECTURAL TRIM SCHEDULE
GENERATOR ROOM
FIBRE BOARD ABOVE EL. 624.23 - CEILING SIMILAR
CONCRETE WALLS ABOVE TO EL. 624.23
PAVER TILE FLOOR AND BASE - GLAZED UNIT DADO-
STAIR NO. 9
CONCRETE STAIRS & SOFFITS - CEMENT PLASTER WALLS.
L E G E N D
INDICATES TERRA COTTA TILE
INDICATES BRICK
INDICATES CONCRETE IN POWER HOUSE CONTRACT
INDICATES CONCRETE NOT IN POWER HOUSE CONTRACT
INDICATES GLAZED TILE
GENERAL NOTES
FOR SECTION "D-D" SEE DRAWING Q2/737-A.
FOR SECTION "E-E" SEE DRAWING Q2/738-A.
FOR STAIR NO. 9 SEE DRAWING Q2/729-F.
FOR TUNNEL LAYOUT SEE DRAWING Q2/760 & Q2/760-A.
DRAWING Q2/717.
FOR AREAS MARKED NOT IN POWERHOUSE CONTRACT SEE
FOR SECTION "F-F" SEE DRAWING Q2/735-A.
G4
RELAY CABINET
DRAIN
UP
DRAIN
CYLINDER RACKS
Co2 SYSTEM
ROUTING VALVES
Co2 SYSTEM
SWITCHGEAR "F4""A4"
ACTUATOR
N
N
GLAZED TILE DADO
"A5"
ACTUATOR
SWITCHGEAR "F5"
DRAIN
G5
BUS DUCT OPENING
CYLINDER RACKS
Co2 SYSTEM
SWITCHGEAR "F6"
G6
NO. 9
UP
N
P
"A6"
ACTUATOR
N
N
DRAIN
DRAIN
P A
R A
P E
T
S P
R
Y
W
L L
S L
O P
E
SPILLWAY
FACE OF
DRAIN
DRAIN
DRAIN
GANTRY CRANE RAILS
CRANE STOP
DRAIN
DRAIN
GLAZED TILE DADO
DRAIN
WATERTIGHT HATCH COVER
PERFORATED GATE SLOT COVER & STEEL FRAME
C O
N T
R A
C T
IO
N
J
O
IN
T
PAVER TILE
DRAIN
GANTRY CRANE DECK
EL. 580.0
GENERATOR ROOM
UNIT NO. 5UNIT NO. 4 UNIT NO. 6
D E
C K
EL. 580.0
SWITCHGEAR ROOM
CABLE TUNNEL
A
B
C
D
E
F
10•10 11 12 12• 13 17161514 14•
1 17
313 315
304 305
311 309
303302
12"0 5' 10' 15'
1'
1'
12'-2" 4'-0"
1'-2" 1'-2"
3'-0"
7'-2" 1'-8"
2‚"
1'-4"
1"
1'-8"
1'-4"
3'-0" 8'-2•" 11'-9•"
1'
1'
1' 1"
1"
1'
7'-7"
1'-5"
6" 3'-0" ƒ
6'-0"
1' 1"1'
3'-0"
9"
14'-0"
7'-8"
7'-7"
9"
2'-0"2'-0"
4'-0"23'-9"
9'-4"18'-10"9'-4"7'-8"
21'-8" 22'-0" 27'-0" 27'-0" 4'-0"
2'-0"2'-0"
439'-5" TO
27'-0" 27'-0" 4'-0"
2'-0"2'-0"
27'-0" 27'-0" 4'-0"
2'-0"2'-0"
1"
58'-0" (TYP.)23'-1…"
1"
6" 5'-2" 6"
9'-6"
9'-6"
8" 7'-9" 8" 8" 8'-5" 6"
1"
8" 7'-9" 8" 21'-8"
6" 8'-1" 6"
1'
7'-3" 3'-4" 1'-10" 3'-0" 2'-8"
6" 18'-1"
THIS CONTRACT
SHELVING NOT IN
SHELVING
STEEL
U N
IT
IR
N D
COMPRESSOR
3" H.D.A.
ORNED-E SK 2/85
D DC
STATION SERVICE SWITCHGEAR "SS"
NO. 2
LTG. TRANSF.
NO. 1
LTG. TRANSF.
LTG. SWGR. "LS"
VENTILATING SWGR. "V1"
P
N
ROOM
DARK
SINK
INSTRUMENT ROOM
NO. 4
ROOM
FAN
S L
O P
E
EL. 594.0
SLOPE
DN.
E L .0
D N
.ORNED-E SK 2/85
& SHELF
HOOK STRIP
TOIL.
KITCHEN
CORRIDOR
RECORDS
JAN.
D .F
NO. 1
ELEV.
N
P
S W
IT
C H
B O
A R
D
"C
S
SWITCHBOARD "MS"
CONTROL ROOM
BENCHBOARD "MB"
NOTE:
LIGHTING MAY BE EXTENDED FOR ADDITIONAL PANELS
CEILING FURRING TO BE ARRANGED SO THAT SWITCHBOARD
S W
IT
C H
B O
A R
D
"A
S
TABLE
REFERENCE
DESK
OPERATOR'S
PLASTER SOFFIT ABOVE
PLATE GLASS PARTITION
PAVER TILE FLOOR
R A
IL
IN
G
R E
M O
V A
B L
E
SECTIONS
REMOVABLE SLAB
SOLE PL
DISMANTLING PLATFORM
EL. 595.0
RUNGS
LADDER
SHAFT
RAILING
CONCRETE
L UNITC
EL. 580.0
GENERATOR ROOM
EL. 595.0
SWITCHGEAR ROOM
L
N T
R A
C T
IO
N
J
O
IN
T
L
N T
R A
C T
IO
N
J
O
IN
T
G E
N E
R A
T
O M
UNIT NO. 1
L
N T
R A
C T
IO
N
J
O
IN
T
D.F.
BRONZE GATE
EL. 595.0
PAVER TILE FLOOR
DRAINS
U P
NO. 2
WATERTIGHT HATCH COVER
GATE SLOT COVER RETAINING WALL
NO. 3
DN. 24 R
UP 26 R
UNIT NO. 2 UNIT NO. 3
D
B
A
B
L E G E N D
INDICATES TERRA COTTA TILE
INDICATES CONCRETE WORK IN THIS CONTRACT
INDICATES BRICK
INDICATES GLAZED TILE
GENERAL NOTES
10•108 8• 97
1 17
6 6•54•4321
A
B
C
D
E
F
E
CA
C
D
E
DISMANTLING FLOOR PLAN - EL. 595.0
12345
B
C
D
A
B
C
D
A
Drawn By:
Date:
Drawing
Number
U.S. ARMY ENGINEER DISTRICT
CORPS OF ENGINEERS
NASHVILLE, TENNESSEE
Checked By:
US Army Corps of Engineers Nashville District
Record Drawing as constructed dated
Approved By:
REV. DESCRIPTION DATE CHECKED
REVISIONS
BY
ATLANTA, GA
CADD CONSULTANT
CARPENTER DUNLAP ASSOCIATES, INC.
Scale:
Sheet
CUMBERLAND RIVER WATERSHED
WOLF CREEK RESERVOIR PROJECT
CUMBERLAND RIVER, KENTUCKY
POWERHOUSE
„" = 1'-0" of
ZGA1:[110,20]Q2D731.DGN
W. M. HALL
T. L. CONE
Scale: „" = 1'-0"
J.R.B.
A.R.K.
CHAS. T. MAIN, INC.
HEAD ENGINEER
H. V. CONAN
COL., C.O.E. DIST. ENG.
Q-2/731.4
1 WALL BETWEEN COLS. 3B & 4B REVISED 12-27-49 H.G.W. T.H.P.
2 7-17-50 C.W.B.
3 7-17-51 J.C.D.
CHANGED LOCATION OF SOLE PLATE
ADDED DARK ROOM; KITCHEN FLOOR REV.
REVISED AS CONSTRUCTED 7-8-91 W.L.
E.B.
FLOOR PLAN - ELEVATION 595.0
UNITS NO. 1-2-3
TOILET & JANITORS CLOSET
DISMANTLING PLATFORM
CONTROL ROOM
RECORD ROOM, CORRIDOR
CONTROL ROOM PARTITION - FIBRE BOARD CEILING.
PAVER TILE FLOOR - CONCRETE WALLS & CEMENT PLASTER ABOVE
WALLS & CEILING
RUBBER TILE FLOOR & ASPHALT COVE BASE - GYPSUM PLASTER
JANITOR'S CLOSET - GLAZED UNIT WALLS & BASE - GYPSUM PLASTER CEILINGS.
CERAMIC TILE FLOOR IN TOILET, CEMENT MORTAR FLOOR FINISH IN
ONLY - CEMENT PLASTER & CONCRETE WALLS - CONCRETE CEILING.
CEMENT MORTAR FLOOR FINISH - CEMENT BASE AT PLASTER WALLS
SWITCHGEAR ROOM
DARK ROOM
INSTRUMENT ROOM
STAIRS NO. 1 & 4
KITCHEN
PLATE GLASS WALLS - ACOUSTICAL TILE CEILING
RUBBER TILE FLOOR & ASPHALT COVE BASE - GYPSUM PLASTER &
STAIRS NO. 2 & 3
BRICK & CONCRETE WALLS - CONCRETE CEILING
CEMENT MORTAR FLOOR FINISH - SMOOTH FACE T.C.
BRICK & CONCRETE WALLS - CONCRETE CEILING
CEMENT MORTAR FLOOR FINISH - SMOOTH FACE T.C.,
CONCRETE STAIRS & SOFFITS - CEMENT PLASTER WALLS
AT PLASTER WALLS ONLY - CONCRETE CEILINGS.
CONCRETE & CEMENT PLASTER WALLS - CEMENT BASE
CONCRETE STAIRS & SOFFITS - PAVER TILE FLOOR -
GYPSUM PLASTER WALLS & CEILING
CERAMIC TILE FLOOR - RD. TOP TILE COVE BASE
ARCHITECTURAL TRIM SCHEDULE
FOR SECTIONS "A-A" & "B-B" SEE DRAWING Q2/736.
FOR SECTION "C-C" SEE DRAWING Q2/735.
FOR SECTION "D-D" SEE DRAWING Q2/737.
FOR SECTION "E-E" SEE DRAWING Q2/738.
FOR STAIRS NO. 1 & NO. 4 SEE DRAWING Q2/729-D.
FOR STAIRS NO. 2 & NO. 3 SEE DRAWING Q2/729-E.
FOR PLATE GLASS PARTITION SEE DRAWING Q2/731-E.
FOR KITCHEN & TOILET ROOM LAYOUT SEE DRAWING Q2/732-E.
FOR REMOVABLE SLAB DETAILS, SEE DRAWING Q2/731-F.
FOR ENTRANCE AT DOORS 301-302-303 SEE DRAWING Q2/731-B.
FOR REMOVABLE RAILING DETAILS, SEE DRAWING Q2/731-D.
FOR TYPICAL WALL SECTIONS SEE DRAWING Q2/733-B.
315313
12"0 5' 10' 15'
6" 8'-1" 6"
8" 7'-9" 8" 21'-8" 6" 26'-9"
1"
6"8'-8"2'-8"3'-0"1'-10"3'-4"7'-3"
3'-6"
6" 53'-1ƒ" 8" 7'-9" 8" 5'-1‚"
3'-0"
1"
1'
1"
" 11
1' 1"
1'
1'-4"
2'-2"
2'-0" 2'-6"
8" CONCRETE WALL
UP TO BOTTOM OF BEAM
1'-8"
1'-4"
8'-6"
"2
1" MIN.
4'-0" 27'-0" 27'-0" 4'-0" 27'-0" 27'-0" 4'-0" 27'-0" 27'-0" 24'-0"
439'-5" TO
ARCHITECTURAL TRIM SCHEDULE
SWITCHGEAR ROOM
CEMENT PLASTER & CONCRETE WALLS - CONCRETE CEILING.
CEMENT MORTAR FLOOR FINISH - CEMENT BASE AT PLASTER WALLS ONLY-
FAN ROOMS
CONCRETE CEILING.
CEMENT MORTAR FLOOR FINISH - SMOOTH FACE T.C. AND CONCRETE WALLS -
STAIR NO. 9
CEMENT PLASTER CEILING
CONCRETE STAIRS AND SOFFIT - CEMENT PLASTER WALLS
GENERAL NOTES
FOR SECTION "D-D" SEE DRAWING Q2/737-A.
FOR SECTION "E-E" SEE DRAWING Q2/738-A.
FOR SECTION F-F SEE DRAWING Q2/735-A.
FOR STAIR NO. 9 SEE DRAWING Q2/729-F.
DISMANTLING FLOOR PLAN - EL. 595.0
EL. 580.0
GENERATOR ROOM
UNIT NO. 5
EL. 580.0
GENERATOR ROOM
RAILING
CONCRETE
VENTILATING SWGR. V2
SWITCHGEAR ROOM
EL. 595.0
SERVICE BUS
SWITCHES "T3"
STA. SERVICE SELECTOR
GRILLE
18"x36"
EL. 595.0
GRILLE
18"x36"
X X
16 R
DN.
SLOPE
E L .0
O V
A
IR
S
C O
N C
P L
A S
C E
IL
IN
G
N
FAN ROOM
GRILLE
18"x18"
IRON LADDER
RAILING
CONCRETE
CRANE CAB ABOVE
OUTLINE OF
EL. 607.0
BALCONY
FLOOR OF
TO CRANE CAB
STUB LADDER
L
N T
R A
C T
IO
N
J
O
IN
T
SWITCHES "T2"
STA. SERVICE SELECTOR
RAILING
CONCRETE
FIN. FL.EL. 595.0
GRILLE
20"x36"
P2
N
NO. 4
ROOM
DARK
SINK
INSTRUMENT ROOM
X X
F
14•
6" T.C. TILE
FIN. FL. EL. 595.0
PLASTER
CEMENT BASE
SLAB EL. 594.33
TOP OF ROUGH
SWITCHGEAR ROOM STORAGE OR FAN ROOM
D D
L UNITSC
GRILLE
20"x36"
F A
N
14 ROOM
FAN
FAN #13
F
EE
DN. 15. R
S L
O P
EF
10•10 11 13 1412 12• 15 16 17
A
B
C
D
E
F
L
N T
R A
C T
IO
N
J
O
IN
T
L
N T
R A
C T
IO
N
J
O
IN
T
E L .0
SLOPE
E L .0
UNIT NO. 6UNIT NO. 4
NO. 9
ƒ" R
12345
C
D
C
D
REV. DESCRIPTION DATE APPROVED
REVISIONS
BY
1 ADDED DARK ROOM AT 9 & F LINE 7-17-51 J.C.P.
A
A
Drawn By:
Date:
Drawing
Number
U.S. ARMY ENGINEER DISTRICT
CORPS OF ENGINEERS
NASHVILLE, TENNESSEE
Checked By:
US Army Corps of Engineers Nashville District
Record Drawing as constructed dated
Approved By:
ATLANTA, GA
CADD CONSULTANT
CARPENTER DUNLAP ASSOCIATES, INC.
Scale:
Sheet
CUMBERLAND RIVER WATERSHED
WOLF CREEK RESERVOIR PROJECT
CUMBERLAND RIVER, KENTUCKY
POWERHOUSE
„" = 1'-0" of 139
W.M. HALL
T.M. CONE
H.V. CONAN
F.M.G. - A.R.K.
J.R.B.
CHAS. T. MAIN, INC.
HEAD ENGINEER
COL., C.O.E. DIST. ENG.
Q-2/731A.1
ZGA1:[110,20]Q2A731A.DGN
Scale: „" = 1'-0"
FLOOR PLAN ELEVATION 595.0
UNITS NO. 4-5-6
L E G E N D
INDICATES TERRA COTTA TILE
INDICATES BRICK
INDICATES CONCRETE IN POWER HOUSE CONTRACT
1 17
E
SCALE: 1•" = 1'-0"
BB
SECTION X-X
CROSS SECTION A-A
CROSS SECTION B-B
43'-4" 24'-0" 22'-0" 24'-0" 23'-7"
22'-0" 24'-0" 23'-7" ƒ
1' ƒ
2'-4" 2'-4"32'-8" 32'-8"
R A
D
IU
S
39'-9" 78'-6" 20'-0"
39'-3" 39'-3"
4'-3" 2'-8 •"
4'-3"
59'-3"
2'-8 •"
EL.506.0
STATION DRAINAGE PIPES.
TOP OF PARAPET EL. 660.87
TOP OF PARAPET EL.638.83
DUCT
TOP OF ROOF
SLAB EL.637.5
DUCT
PLASTER
MARBLE
GRILL
MARBLE
MARBLE
ACOUSTICAL TILE CEILING
GLASS
PLASTER
FIN FLOOR EL.611.0
GRILL
TOP OF PARAPET EL.629.33
TOP OF ROOF SLAB EL.638.0
DRAIN
EARTH
FILL
DRAIN
6"0 POROUS
CON DRAIN
EL.605.0
EL.605.0
POWER
CABLE
TUNNEL
UNITS NO.
4,5,&6
POWER
CABLE
TUNNEL
UNIT NO.
1,2,&3
EL. 583.62
6"I.D. HALF ROUND POROUS
CONC. DRAIN-SEE Q 2/7J8G
EL.537.5
NOT IN
POWER HOUSE
CONTRACT
INSIDE
CONTROL
CABLE
TUNNEL
TERRA
COTTA
CONCRETE BLOCK
DUCT
BRICK
DUCTS
ACOUSTICAL TILE CEILING
PLASTER
LINOLEUM BASE
FIN. FLOOR EL.595.0
PLASTER ABOVE
PARTITION.
METAL AND GLASS
PARTITION
TOP OF CRANE RAIL EL.629.0
CRANE RAIL
CRAIN GRIDER
EL.624.23
OPEN
GLAZED TILE DADO
FIN. FLOOR EL.580.0
STORAGE BIN
NOT IN THIS CONTRACT
EL.550.0
CONCRETE
PIPE RAILING
CONC.
CONC.
BLOCK
CONC.
EL.563.0
TERRA COTTA
CONCRETE
TOP OF CRANE
REMOVABLE PIPE RAILINGS
RAIL EL.587.62
EYE BOLTS
OPEN
EL.550.0
FINISH FLOOR EL.564.0
REMOVABLE RAILING
EL.544.33
VENTILATOR
4" FILL AT RIDGE OF ROD
FOR CATWALKS SEE DWG Q2/743 B & C
TOP OF ROOF SLAB EL.659.5 C L
FILTER BOARD CEILING
ON METAL LATH AND PLASTER
SCUTTLE
PIPE RAILING
LADDER
6" T.C.
12"x12"
GLASS
BLOCK
LIGHTS
DUCT
FIN. FLOOR EL.647.5
FIN FLOOR EL.627.75
GATE
SLOT
EL.594.96
CEILING IN TOILET
ROOMS ON THIS
FLOOR TO BE SAME
HEIGHT
NOT IN
POWER HOUSE
CONTRACT
EL.539.33
EL.537.83
GLAZED
TILE
427 405
209 207
VENTILATOR
C OF UNITSL
REMOVABLE RAILING
EL.595.0
FIN. FLOOR
REMOVABLE SLABS
FIN FLOOR EL.580.0
CONCRETE
TOP OF CRANE RAIL EL.587.62
LEDGE
GOVERNOR
OPENING TO
PIT LINER
FIN. FLOOR
EL.564.0
GENERATOR
FLOOR
STAND
DUCT
EL.567.0
OPEN
PENSTOCKCL
EL.553.33
EL.550.0
EL.544.5
EL.540.0
EL.550.0
BOTTOM OF DISCHARGE PIT EL.533.0
EL.541.0
EL.553.67
CONCRETE
EL.564.0
FIN FLOOR
CONCRETE
WATERTIGHT
DOOR
CONCRETE
EL.595.0
FIN FLOOR
CONCRETE
12"x12"
GLASS
BLOCK
GLASS
BLOCK
12"x12"
CONCRETE
AUTOMATIC SHUTTER
OPENING
TOP OF PARAPET EL.660.87
TOP OF ROOF SLAB EL.659.54
FIN. FLOOR EL.627.75
FIN. FLOOR EL.611.0
TOP OF PARAPET
WATER TIGHT HATCH COVER
GATE SLOT COVER
LADDER RUNGS
NOT IN
POWER HOUSE
CONTRACT
7T@9"1-0"
5'-3"
R
EL.532.5
6 •"
4'-0" RADIUS 4'-0" RADIUS
EL.642.00CL
1'-8"
1'-6 ‚" 1'-0"
Q
U
IS
E R
S
" FIN FL.EL.553.67
OPEN
EL.567.0
OPEN DUCT
RAMP
2"
EL.580.0
1'-8"
1'-7"
3'-0"
3'-8"
9"9"9"9"
C B A
F E D C B A
41 42 43 25
36 37 35
41 42 43 25
36 37 3524
42 43
41 42 43 25
36 37 35
42 43
36 3724
26 37 3433
44 3838 45
36 37 3432 33
100 101
38 45
36 37 2332 33
38 45
36 37 3432 33
38 45
36 3732 33
38 45
36 31 3432 33
38 45
36 37 2332 33
4 3
14 2
4 3
19 19
18 18
20 20 1414
28 22
5" 2'-4" 2'-4" 2'-4" 2'-4" 2'-4" 2'-4" 2'-4" 2'-4" 2'-4" 2'-4" 2'-4" 5"
26'-6"
40 27
40 27
40 27
102 102
4" 2'-4" 2'-4" 2'-4" 2'-4" 2'-4" 2'-4" 2'-4" 2'-4" 2'-4" 2'-4" 2'-4" 4"
26'-4"
1 2
AM
LINE
AM
LINE
AM
LINE
VM
LINE
WM
LINE
VAR
LINE
ANNUNCIATOR L
AM
LINE
AM
LINE
AM
LINE
WM
LINE
WM
LINE
VAR
LINE
ANNUNCIATOR K
AM
LINE
AM
LINE
AM
LINE
WM
LINE
WM
LINE
VAR
LINE
ANNUNCIATOR J ANNUNCIATOR H
AM
TRANSF
VM
TRANSF
WM
TRANSF
AM
GEN
VM
GEN
WM
GEN
ANNUNCIATOR G
Am
GEN
VM
GEN
WM
GEN
RPM GATERPM GATE
AM
SPARE
OCB
AM
SPARE
OCB
AM
SPARE
OCB
WM
SPARE
OCB
VM
TRANSF
VAR
SPARE
OCB
AM
SPARE
OCB
AM
SPARE
OCB
AM
SPARE
OCB
VM
TRANSF
WM
SPARE
OCB
VM
SPARE
VAR
SPARE
OCB
AM
GEN
VM
VAR
GEN
AM VM
VAR
GEN
AM
GEN
VM
GEN
WM
GEN
AM
GEN
VM
GEN
WM
GEN
GATE
AM
VAR
GEN
AM
GEN
VM
GEN
WM
GEN
GATE
VAR
GEN
AM
GEN
VM
GEN
WM
GEN
RPM
GATE
AM
GEN
VAR
GEN
AM
GEN
VM
GEN
WM
GEN
FIELD
AM
GEN
VAR
GEN
FIELD
FIELD
AM
FIELD
LINE
GAR
RPM
1 2
1 2
3'-6
3'-2"
VM
RUN
SYN
FI
RUN
VM
INC
FI
INC
M
IN
. VOLTAGE
REGULATOR
DIRECT
ACTING
TYPE
464646464646
WHM
IN
TRANSF
WHM
GEN
POT
CUR.
POT
CUR.
POT
CUR.
POT
CUR.
POT
CUR.
POT
CUR.
POT
CUR.
POT
CUR.
WHM
IN
WHM
POT
CUR.
POT
CUR.
VOLTAGE
REGULATOR
WHM
IN
WHM
POT
CUR.
POT
CUR.
OUT OUT
VOLTAGE
REGULATOR
WHM
IN
WHM
POT
CUR.
POT
CUR.
OUT
VOLTAGE
REGULATOR
WHM
IN
WHM
POT
CUR.
POT
CUR.
OUT
VOLTAGE
REGULATOR
TYPE
WHM
IN
WHM
POT
CUR.
POT
CUR.
OUT
VOLTAGE
REGULATOR
RHEOSTATIC
ACTING
TYPE
WHM
IN
WHM
POT
CUR.
POT
CUR.
OUT
3148 47
3148 47
3148 47
EXPLANATION
1. OIL CIRCUIT BREAKER CONTROL SWITCH.
2. DISCONNECTING SWITCONTROL SWITCH
3. OIL CIRCUIT BREAKER SYNCHRONIZE SWITCH
4. DISCONNECTING SWITCH PERMISSIVE CONTROL SWITCH
5. GENERATOR NEUTRAL ACB CONTROL SWITCH
6. GENERATOR MAIN ACB CONTROL SWITCH.
7. GENERATOR MAIN ACB SYNCHRONIZING SWITCH
8. MAIN EXCITER FIELD ACB CONTROL SWITCH.
9. MAIN EXCITER FIELD RHEOSTAT CONTROL SWITCH.
10. VOLTAGE REGULATOR TRANSFER SWITCH
11. EMERGENCY SHUTDOWN PUSH BUTTERS
12. GOVERNOR GATE LIMIT CONTROL SWITCH
13. GOVERNOR SPEED LEVEL CONTROL SWITCH
14. VOLTMETER TRANSFER SWITCH.
15. AMMETER TRANSFER SWITCH.
17. TEST TELEPHONE JACK
18. 460 VOLT ACB CONTROL SWITCH.
19. 460 VOLT ACB SYNCHRONIZING SWITCH
20. 15KV MOTOR-OPERATED SELECTOR SWITCH CONTROL SWITCH
22. ILLUMINATED SYMBOL-STATION SERVICE GENERATOR
23. BUS DIFFERENTIAL RELAYS D-C PILOT LIGHT
24. SPARE RELAYS D-C PILOT LIGHT.
25. LINE METERS AND RELAYS BOTANICAL TRANSFER SWITCH.
26. CONTROL BY-PASS SWITCH (TO BY-PASS A AUX SWITCH RELAY ON LINE ACB)
27. NAMEPLATE-MAIN TRANSFORMER BANK (1, 2, 0, 3)
28. NAMEPLATE-STATION SERVICE TRANSFORMER
29. CARRIER CURRENT TRIP CUT-OUT SWITCH.
30. ILLUMINATED SYMBOL-LINE DESIGNATION.
31. CARRIER TEST. SWITCH, 4 POSITION MARKED (1) SEND, (2) RECEIVE.
(3) NORMAL AND (4) RESERVE SIGNAL.
32. FIELD TRIP D-C PILOT LIGHT.
33. GENERATOR RELAYS D-C PILOT LIGHT.
34. TRANSFORMER RELAYS D-C PILOT LIGHT
35. LINE RELAYS D-C PILOT LIGHT.
36. ANNUNCIATOR RESET RESET PUSH-BUTTON.
38. GENERATOR VOLTAGE ADJUSTING RHEOSTAT.
39. STATION SERVICE EXCITER FIELD RHEOSTAT.
40. TRANSFORMER BUS 1 AND 2 OCB INDICATING LIGHTS.
41. HIGH SPEED RECLOSING CUT-OUT SWITCH
42. UNDER VOLTAGE RELAY CUT-OUT SWITCH.
43. SYNCHRONISM CHEEK RELAY CUT-OUT SWITCH.
44. STATION VOLTAGE LEVEL POTENTIAL SELECTOR SWITCH WITH "OFF" POSITION.
45. STATION VOLTAGE LEVEL UNIT CUT-OFF SWITCH.
46. VOLTAGE REGULATOR INDICATING LIGHTS.
47 CARRIER CURRENT MILLIMETER
48. CARRIER CONTROL SWITCH 2 POSITION MARKED (1) CARRIER ON AND
(2) "CARRIER OFF"
49. BUS BACK-UP RELAYS D-C PILOT LIGHT.
100. STATION VOLTAGE LEVEL ADJUSTING RHEOSTAT.
101. CONTROL SWITCH IN VOLTAGE REG. C.T. CIRCUIT. (SEE DWG. Q-2/834B).
102. 15KV MOTOR OPERATED SELECTOR SWITCH. NAMEPLATE (T2, T3).
SINGLE POLE, 30A, 250V, TOGGLE SWITCH.
EL. 595.0
SUMMER SHADE 1
154KV LINE
PANEL 11
NORRIS 1
154 KV LINE & SPARE OCB
PANEL 10
SUMMER SHADE 2
154 KV LINE
PANEL 9
SPARE OCB
154 KV LINE (FUT)
PANEL 8
STATION SERVICE
GENERATOR & TRANSFORMER
PANEL 7
GENERATOR 1
PANEL 6
GENERATOR 2
PANEL 5
GENERATOR 3
PANEL 4
GENERATOR 4
PANEL 3
GENERATOR 5
PANEL 2
GENERATOR 6
PANEL 1
FRONT ELEVATION-INSTRUMENT PANELS
SWITCHBOARD-MM
SUMMER SHADE
PANEL 11
TRANSF BUS NORRIS
PANEL 10
TRANSF BUS SUMMER
SECT. BANK 2 SECT. SHADE 2
PANEL 9
BUS TRANSF FUTURE
SECT BANK 3 LINE
PANEL 8
STATION SERVICE
PANEL 7
GENERATOR 1
PANEL 6
GENERATOR 2
PANEL 5
GENERATOR 3
PANEL 4
GENERATOR 4
PANEL 3
GENERATOR 5
PANEL 2
GENERATOR 6
PANEL 1
BENCH PLAN
BUS. OCB
IND LIGHTS
BUS 2, OCB IND LIGHTS
TRANSF 3
154 KV BUS 2
APRON ELEVATION
BENCHBOARD-MB
GENERAL NOTES
1.
MANUFACTURER.
2.THIS IS A CONTRACT DRAWING USED FOR THE PROCUREMENT OF EQUIPMENT,
AND IS NOT TO BE USED FOR CONSTRUCTION FOR CONSTRUCTION PURPOSES
USE MANUFACTURER'S DRAWING'S.
3.MINOR MODIFICATIONS WILL BE PERMITTED IN APPARATUS ARRANGEMENT,
PANEL WIDTHS, AND OTHER DIMENSIONS IN ORDER TO SUIT THE MANU-
FACTURER'S STANDARDS, SUBJECT TO APPROVAL OF THE CONTRACTING OFFICER
4.
SYMBOLS:
DRILL AND PLUG
GREEN INDICATING SWITCHBOARD LIGHT
RED INDICATING SWITCHBOARD LIGHT
WHITE INDICATING SWITCHBOARD LIGHT
AMBER INDICATING SWITCHBOARD LIGHT
NAMEPLATE
TEST BLOCK
STAINLESS STEEL
WEARING STRIP
BENCH
EACH END OF
BENCHBOARD
APRON
HINGED PANEL
AT REAR OF
EACH SECTION
EL. 595.0'
END ELEVATION
DATE REC. APPR.
C U M B E R L A N D R I V E R W A T E R S H E D
W O L F C R E E K R E S E R V O I R P R O J E C T
C U M B E R L A N D R I V E R, K E N T U C K Y
P O W E R H O U S E
MAIN CONTROL SWITCHBOARD
IN SHEETS SHEET NO
12" 6" 0 1' 2'
SCALE: 1 INCH = 1 FOOT
U.S. ENGINEER OFFICE, NASHVILLE, TENN.,
APPROVAL RECOMMENDED:SUBMITTED APPROVED
PRINCIPAL ENGINEER HEAD ENGINEER COL . CORPS OF ENGINEERS
DISTRICT ENGINEER
SUPV. CHECKED TO ACCOMPANY SPECIFICATIONS
DRAWN TRACED DATED
ERS
C.R.C.
ERS
BENCHBOARD "MB" & INSTRUMENT PANELS "MM"
CHED.BYDESCRIPTION
REVISIONS
VOLTAGE
REGULATOR
154KV. BLS 1
RHEOSTATIC
TYPE
RHEOSTATIC
TYPE
RHEOSTATIC
TYPE
RHEOSTATIC
TYPE
RHEOSTATIC
WAR DEPARTMENT CORPS OF ENGINEERS, U.S. ARMY
SEP 2014 CONVERTED TO CAD MJC JHG
AM
GEN
VM
GATEGATE
AMAM
GEN
RPM
AMAMAM
GEN
RPM
21. ILLUMINATED SYMBOL-MAIN GENERATOR (1,2,3,4,5,6)
103. SHUTDOWN RELAY-HAND RESET
BANK 1 SECT 1
HINGED DOOR AT
Q-2/786.1
37. ANNUNCIATOR TEST PUSH-BUTTON
ANNUNCIATOR WINDOW CABINETS FURNISHED BY ANNUNCIATOR EQUIPMENT
BLUE INDICATING SWITCHBOARD LIGHT**
INSTALLATION OF THIS EQUIPMENT TO BE PAID FOR UNDER CONTRACT
ITEM
FURNISHED BY TURBINE-GOVERNOR CONTRACTOR. MOUNTING AND WIRING
FURNISHED BY GENERATOR CONTRACTOR. MOUNTING AND WIRENING BY
SWITCHGEAR CONTRACTOR.
BY SWITCHGEAR CONTRACTOR.
16. PUSHBUTTON FOR TELEMETERING AUXIARY, RESET
ANNUNCIATOR F ANNUNCIATOR E
FIELD
** POS
ANNUNCIATOR D ANNUNCIATOR C
POS
FIELD
FIELD
PILOT
EXC
** POS
ANNUNCIATOR B ANNUNCIATOR A
PILOT
EXCFIELD
POS**
FRONT ELEVATION
OPERATORS DESK
PLAN
OPERATOR'S DESK
SPACE FOR TELEPHONE
EQUIPMENT RECORDER
END ELEVATION
EI. 595.0
REFERENCE TABLE OR DESK,
FURNISHED BY GOVERNMENT
EXPLANATION:
TRANSFORMER DIFFERENTIAL RELAY-SINGLE PHASE, 2 ELEMENT
TRANSFORMER DIFFERENTIAL AUXILIARY RELAY-HAND RESET
GENERATOR OVERCURRENT RELAY-SINGLE PHASE
GENERATOR DIFFERENTIAL RELAY-SINGLE PHASE
GENERATOR DIFFERENTIAL BACK-UP RELAY
GENERATOR OVERCURRENT AUXILIARY RELAY-SELF RESET
GENERATOR DIFFERENTIAL AUXILIARY RELAY-SELF RESET
GENERATOR OVERVOLTAGE AUXILIARY RELAY-SELF RESET
SHUT DOWN RELAY-HAND RESET
TRANSFORMER DIFFERENTIAL BACK-UP OVERCURRENT RELAY
AUXILIARY RELAY FOR ITEM 81 HAND RESET
BUS DIFFERENTIAL RELAY-SINGLE PHASE (154KV BUSES)
TRANSFORMER OVERCURRENT RELAY-SINGLE PHASE
TRANSFORMER OVERCURRENT AUXILIARY RELAY-SELF RESET
GENERATOR UNDERVOLTAGE RELAY-SINGLE PHASE
GENERATOR UNDERVOLTAGE AUXILIARY RELAY- SELF RESET
BUS BACK UP DIFFERENTIAL GROUND RELAY
HIGH SPEED DIRECTIONAL GROUND RELAY
DIRECTIONAL GROUND RELAY, CURRENT POLARIZED
BUS DIFFERENTIAL AUXILIARY RELAY-HAND RESET
CARRIER CURRENT RECEIVER RELAY
HIGH SPEED ENCLOSING BLOCKING RELAY
TIMING RELAY
DIRECTIONAL GROUND RELAY, POTENTIAL POLARIZED, 1.5-6 AMP
WITH 10-40 AMP INSTANTANEOUS ELEMENT
TELEMETER AUXILIARY RELAY
UNDERCLOTHES RELAY. SEE NOTE 4
ENCLOSING RELAY, SINGLE SHOT, WESTINGHOUSE TYPE SGR-12. SEE NOTE 4
AUXILIARY RELAY FOR HIGH SPEED ENCLOSING SCHEME, 1 AMP
SERIES COIL.
AUXILIARY RELAY, 125V D-C COIL.
BUS BACK-UP, 3-ZONE 1, DISTANCE RELAY
SPARE OCB DISTANCE RELAY WESTINGHOUSE TYPE HZ
SPARE OCB DIRECTIONAL GROUND RELAY; SHORT LINE
SPARE OCB DIRECTIONAL GROUND RELAY, LONG LINE
SPARE OCB RELAYS SHORT-LONG LINE SELECTOR SWITCH
BUS BACK-UP TIMING AUXILIARY RELAY
LINE OCB "A" AUXILIARY SWITCH RELAY (MTD ON INSIDE PANEL)
AUXILIARY RELAY FOR TELEMETERING TEST ANN (MTD ON INSIDE PANEL)
TRANSMITTER-RECEIVER FILAMENT FAILURE ALARM RELAY.
GENERATOR ACB "B" AUXILIARY SWITCH RELAY. (MTD ON INSIDE PANEL)
AUXILIARY TRIPPING RELAY, 125V D-C COIL.
AUXILIARY ALARM RELAY, 125V D-C COIL. SEE NOTE 4
50.
51.
52.
53.
54.
55.
56.
57.
58.
59.
60.
61.
62.
63.
64.
65.
66.
67.
68.
69.
70.
71.
72.
73.
74.
75.
76.
77.
78.
79.
80.
81.
82.
83.
84.
85.
86.
87.
88.
89.
90.
91.
92.
93.
4" 2'-4" 2'-4" 2'-4" 2'-4" 2'-4" 2'-4" 2'-4" 2'-4" 2'-4" 2'-4" 2'-4" 4"
26'-4"
1 2
GENERATOR 6 &
BUS 2 DIFF & BACKUP
PANEL 1
GENERATOR 5 &
PANEL 2
END ELEVATION
6'-6"
TRANSF & SPARE OCB 964 154 KV LINE
GENERATOR 4 &
SPARE OCB 928
PANEL 3
GENERATOR 3 &
TRANSFORMER 2
PANEL 4
GENERATOR 2 &
PANEL 5
GENERATOR 1 &
TRANSFORMER 1
PANEL 6
STA SERV GEN &
PANEL 7 PANEL 8
SUMMER SHADE 2
154 KV LINE
PANEL 9
NORMS 1
154 KV LINE
PANEL 10
SUMMER SHADE 1
154 KV LINE
PANEL 11
EI.595.0
GENERAL NOTES:
THIS IS A CONTRACT DRAWING USED FOR THE PROCUREMENT OF
EQUIPMENT, AND IS NOT TO BE USED FOR CONSTRUCTION. FOR
CONSTRUCTION PURPOSES USE MANUFACTURER'S DRAWINGS
MINOR MODIFICATIONS WILL BE PERMITTED IN APPARATUS
ARRANGEMENT, PANEL WIDTHS, AND OTHER DIMENSIONS IN ORDER
TO SUIT THE MANUFACTURER'S STANDARDS SUBJECT TO APPROVAL
OF THE CONTRACTING OFFICER.
TWO RELAYS, ITEM 88 & 89 (TO BE MOUNTED ON SIDE SHEET,
PANELS 9, 10 & 11.)
FIVE RELAYS ITEM 76, 77, 78, 87 & 93 TO BE MOUNTED ON
SIDE SHEET, PANELS 3 & 7.
ONE RELAY ITEM 91 TO BE MOUNTED ON SIDE SHEET, PANELS
1, 3, & 5. (SEE DWG. Q-2/834B)
1.
2.
3.
4.
5.
GENERAL NOTES: (CONT'D.)
TO BE MOUNTED ON SIDE SHEET PANEL 7, FOR
STATION TRANSF. DIFFERENTIAL RELAYS.
6.
5'-6" 5'-6"±
WAR DEPARTMENT CORPS OF ENGINEERS, U.S. ARMY
DATE REC. APPR.
CUMBERLAND RIVER WATERSHED
WOLF CREEK RESERVOIR PROJECT
CUMBERLAND RIVER, KENTUCKY
POWERHOUSE
IN SHEETS SHEET NO. 4
SCALE: 1 INCH = 1 FOOT
U.S. ENGINEER OFFICE, NASHVILLE, TENN.,
APPROVAL RECOMMENDED:SUBMITTED: APPROVED:
HEAD ENGINEER COL ., CORPS OF ENGINEERS
DISTRICT ENGINEER
DRAWN
TO ACCOMPANY SPECIFICATIONS
DATED
RELAY PANELS MR & OPERATORS DESKS
CHKD.BYDESCRIPTION
REVISIONS
PRINCIPAL ENGINEER
TRACED
CHECKEDE R S
S.P.W.
SUPV.
MAIN CONTROL SWITCHBOARD
E R S
CARRIER RELAYS
3 4 4 1/221
F
E
11 10 9 8 7 6 5 4 3 2 1
11 10 9 8 7 6 5 4 3 2 1
OPER
DESK
REF
TABLE
7 8
1 8
29'-11
26'-4" 15'-1 3/4"
5'-6" 5'-6" 13'-9
5'-0" 4'-0 3/4"26'-8"5'-0"5'-11"
4'-0"
21'-9" 22'-0" 23'-9" 4'-0"
4'-0"
RELAY PANELS MR
BENCH BOARD MB
R E
C O
R D
E R S
W B
D C
S
D -C S
W E
D A
KEY PLAN-CONTROL ROOM
SCALE: 1/8" = 1'-0"
71'-5"
SEP 2014 CONVERTED TO CAD MJC JHG
Q-2/787.1
GENERATOR OVER VOLTAGE RELAY-SINGLE PHASE
TRANSFORMER 3
SYNCHRONISM CHECK RELAY. SEE NOTE 4
SYNCHRONOUS CHECK AUXILIARY RELAY. SEE NOTE 4
THREE AUX. CURRENT TRANSFORMERS, 5-10 AMP.,
NORRIS FUTURE
BUS 1 DIFF AND BACKUP
INSTRUMENT PANELS MM
REAR ELEVATION-RELAY PANELS
SWITCHBOARD-MR
TRANSF
DIFF
TRANSF
DIFF
TRANSF
DIFF
BUS 2
DIFF
BUS 2
DIFF
TRANSF
DIFF
TRANSF
DIFF
TRANSF
DIFF
BUS 1
DIFF
BUS 1
DIFF
TRANSF
DIFF
TRANSF
DIFF
TRANSF
DIFF
TRANSF
DIFF
TRANSF
DIFF
TRANSF
DIFF
68 68 68 68
BUS 2
DIFF
GEN
DIFF
GEN
OC
GEN
DIFF
GEN
OC
GEN
OC
GEN
DIFF
TRANSF
OC
TRANSF
OC
GEN
OV
GEN
DIFF
55 54
57 58 57 58
55 54
TRANSF
OC
59 51 56 56
TIMER
BUS 2
BECK-UP
55 54
57 58
59 59 51 59 70 59 51 56 56 56 93
56 56
GEN
OC
GEN
OC
GEN
OC
GEN
OC
GEN
OC
GEN
OC
6155 54 55 54
TRANSF
OC
TRANSF
OC
TRANSF
OC
TRSNSF
OC
TRANSF
OC
OV
AUX
DIR
GRD
BUS 2
BACK-UP
DIR
DIST
BUS 2
BACH-UP
DIR
GRD
BUS 1
BACK-UP
TRANSF
OC
TRANSF
OC
DIR
DIST
BUS 1
BACK-UP
DIR
GRD
SHORT
LINE
DIR
GRD
SHORT
LINE
TRANS
OC
DIR
DIST
GEN
UV
UV
AUX
DIR
DIST
TRANSF
AUX
DIR
DIST
DIR
GRD
REC
DIR
DIST
DIR
DIST
DIR
GRD
SHORT
LINE
DIR
GRD
LONG
LINE
TRANSF
OC
57 58 57 58
79 80 87 90 92 93 79 80 92 93 79 80 87 92 92 93
68 68
69 72 76 69 72 76
74 71 75 74 71 75
78737873
UV
AUX
DIR
DIST
DIR
DIST
DIR
DIST
DIR
GRD
TIMER
SGR 12
TIMER
BUS 1
DIR
DIST
51 85
BUS 1
DIFF
DWG Q-2/786
RELAY PANELS,
REAR
HINGED DOOR OF EACH
END OR BOARD
NOTE:
FOR INSTRUMENT
PANEL LAYOUT, SEE
INSTRUMENT
BACK UP
TELM
CARR
SYN
CHK
REL
BLOCK
RECL
PANELS FRONT
9'-0" 9'-0" 4'-0" 9'-0" 9'-0" 9'-0" 9'-0" 9'-0"
58'-0"
EL. 610.83
5'-012"
EL. 595.0
8'-0"
B E
A M
EL. 610.83
EL. 595.0
OPENING IN FLOOR
BOX CONTAINING 1 STA. SERVICE
SECTION B-B
K V M
A
IN
L
E A
D S
K
V M
A
IN
L
E A
D S
T2 T3
TO SWGR 64
TO MAIN POWER
TRANSF. BANK NO. 2
TO MAIN POWER
TRANSF. BANK NO. 3
* ELECTRICALLY INTERLOCKED 50 THAT NEITHER
CAN BE OPERATED UNLESS THE OTHER IS OPEN
TRANSFORMER
ONE LINE DIAGRAM
FRONT ELEVATION
GENERAL NOTES:
1.
B E
A M
3 PST 1200A 15 KV
GANG OPERATED
STA. SERVICE SWITCH
2'-3" 2'-3"
8'-0"
F
TRANSFORMER HIGH
7'-1" 11"
4" 1'-0" 1'-0"
OPENING IN FLOOR
EL. 595.0
2" FINISH
6" FILL
5 1/2" SLAB
SECTION A-A
TO G4
FOR CONTINUATION
THIS IS A CONTRACT DRAWING TO BE USED FOR THE
PROCUREMENT OF EQUIPMENT AND IS NOT TO BE USED
FOR CONSTRUCTION. FOR CONSTRUCTION PURPOSES USED
MANUFACTURER'S DRAWINGS.
MINOR MODIFICATIONS WILL BE PERMITTED APPARATUS
ARRANGEMENT, PANEL WIDTHS, AND OTHER DIMENSIONS
IN ORDER TO SUIT THE MANUFACTURER'S STANDARDS,
SUBJECT TO APPROVAL OF THE CONTRACTING OFFICER.
THESE DIMENSIONS WILL DEPEND ON THE DIMENSIONS OF
THE TRANSFORMER FURNISHED AND SHALL BE DETERMINED
FROM THE TRANSFORMER MANUFACTURER'S CERTIFIED
DRAWINGS BEFORE FABRICATION OF THE TIE
BUS.
SWITCHGEAR T2 AND T3 SHALL BOTH HAVE 8 POINT AUX.SWITCHES.
INSTALLATION OF THIS EQUIPMENT WILL BE PAID FOR
UNDER CONTRACT ITEM.
2.
3.
4.
5.
C-
TERMINAL BOARD, 4
POLE WITH SHORT
CIRCUITING STRIPS
CUMBERLAND RIVER WATERSHED
WOLF CREEK RESERVOIR PROJECT
CUMBERLAND RIVER, KENTUCKY
POWERHOUSE
15 KV STATION SERVICE SWITCHGEAR EQPT.
UNITS T2, T3 AND SS TRANSF.
SHEET NO. 8
SHEETSIN 12" 0 1'
SCALE: 1/2 INCH = 1 FOOT
U.S. ENGINEER OFFICE, NASHVILLE, TENN.,
SUBMITTED:
PRINCIPAL ENGINEER
APPROVAL RECOMMENDED:
HEAD ENGINEER
APPROVED:
COL., CORPS OF ENGINEERS
DISTRICT ENGINEER
SUPV.
DRAWN
CHECKED
TRACED
TO ACCOMPANY SPECIFICATIONS
DATED
5-4-50 S.B.F.
BY CHKD. REC. APPR.DATE DESCRIPTION
REALLOCATED SWITCHGEAR T2 & T3
REVISIONS
1'-8" 1'-8"
A
A
4'-1012" 7'-8"
5'-3" OPENING
5'-0"
7'-612"
9'-5"
1'-8" 1'-8"
5'-0"
5'-012" 4'-1012"
5'-3" OPENING
S E
E N
O T
E
STATION SERVICE
SELECTOR SWITCH
GEAR BOX
PROVIDE MEANS FOR
MANUAL OPERATION
MOTOR MECHANISM LIMIT OF BUS
DUCT CONTRACT
OPENING IN FLOOR
1500 KVA 3 STATION SERVICE
TRANSF. 13,200/480 VOLTS
SEE NOTE 3
1 2
DETAILS OF THESE CONNECTIONS TO BE
COORDINATED BETWEEN TRANSFORMER
AND BUS MANUFACTURERS
15 KV STATION SERVICE BUS
SWITCHGEAR T3
DOORS CLOSED
7'-8" TO LINE
480 VOLT BUS TO
SWITCHGEAR SS
SEE DWGS Q-2/793
& Q-2/797
B
B
SWITCHGEAR T2
DOORS OPEN
4 1/2" SLAB
EL. 610.83
12 1/2 13
2' 3' 4' 5'
S.B.F.
CORPS OF ENGINEERS, U. S. ARMYWAR DEPARTMENT
2"± 71
2"±
9'-0" TO 14 LINE
S
L A
B
SEE DWG. Q-6" FILL/799
17 KV 1200 A 1200 SERVICE TIE BAR
TO SWGR G5
FOR SECONDARY LEADS
1 1/4" CONDUIT TO CABLE TUNNEL
/2 S
L A
B
F
IL
L
F
IN
8± 8±
TO STA. SERVICE TRANSFORMER
13,200/480 VOLTS-1500 KVA
3-400/SY MOUNT IN
VOLTAGE COMPARTMENT
* STATION SERVICE SELECTOR SWITCH 15KV 1200A
SEP 2014 CONVERTED TO CAD MJC JHG
Q-2/790.2
V
CONT. CBS
20A,2P
2 4
300A
STATION SERVICE TRANSFORMER
STATION SERVICE GENERATOR
ANNUNCIATION COMPLETE SHUTDOWN
AUX. RELAY NO.1 TRIPS AND
LOCKS OUT:
O.C.B.'S 944 & 948
GENS 3 & 4 MAIN ACB'S 238&243
TRIPS:
STA. SERV. TRANSF. A.C.B. 073
ANNUNCIATOR
AUX. RELAY NO.2 TRIPS AND
LOCKS OUT:
O.C.B.'S 924 & 928
TRIPS:
STA. SERV. TRANSF. A.C.B. 073
ANNUNCIATOR
THRUST BEARING OIL COOLER -LOW WATER FLOW
ALL BEARINGS - HIGH TEMPERATURE
OIL RESERVOIRS -LOW OIL LEVEL
UNDERVOLTAGE RELAY OPERATION
OVERCURRENT RELAY OPERATION (STATION LOAD)
OVERCURRENT RELAY OPERATION (SYSTEM LOAD)
SHUTDOWN RELAY OPERATION
MANUAL EMERGENCY (7G11)
LOW GOVERNOR OIL PRESSURE (63QTS)
UNDER VOLTAGE (27G1X)
87T5X1 87T5X2
GENS 5 & 6 MAIN ACB'S 258 & 268
RELAY RACK
TO ANNUNCIATOR
C O
N T
R O
L T
R A
N S
F O
R M
E R
A N
D P
A N
E L
B O
A R
D
B U
L K
H E
A D H
O
IS
T F
E E
D E
R
N O .1
B R
E A
K E
R 'S A
IR
C
O M
P R
E S
S O
R
T U
N N
E L S
U P
P L
Y F
A N N
O .1
T U
N N
E L S
U P
P L
Y F
A N N
O .1
E X
H A
U S
T F
A N N
O .1
E X
H A
U S
T F
A N N
O .1
E X
H A
U S
T F
A N N
O .1
E X
H A
U S
T F
A N N
.9
X
H A
U S
T F
A N N
.7
H A
U S
T F
A N N
.6
H A
U S
T F
A N N
.5
H A
U S
T F
A N N
.8
H A
U S
T F
A N N
.4
H A
U S
T F
A N N
.3
H A
U S
T F
A N N
.2
H A
U S
T F
A N N
.1
H O
U S
T F
A N N
O .7 D
A M
P E
R
E X
H O
U S
T F
A N N
O .6 D
A M
P E
R
E X
H O
U S
T F
A N N
O .5 D
A M
P E
R
S U
P P
L Y F
A N N
O .8 I
N T
A K
E D
A M
P E
R
S U
P P
L Y F
A N N
O .4 I
N T
A K
E D
A M
P E
R
S U
P P
L Y F
A N N
O .3 I
N T
A K
E D
A M
P E
R
S U
P P
L Y F
A N N
O .2 I
N T
A K
E D
A M
P
P P
L Y F
A N N
O .1 I
N T
A K
E D
A M
P E
R
S U
P P
L Y F
A N N
O .4 R
E C
IR
C U
L A
T
IN
G D
A M
P E
R
S U
P P
L Y F
A N N
O .2 R
E C
IR
C U
L A
T
IN
G D
A M
P E
R
S P
A R
E C
O M
P A
R T
M E
N T
V
H
R
D A
M P
E R F
A N C
O N
T
S
IN
G L E U
N
IT
S P
A R
E C
O M
P A
R T
M E
N T
D
O U
B L E U
N
IT
G R
O U
P "D
"H
E A
T E
R S
G R
O U
P "E
"H
E A
T E
R S
G R
O U
P "B
"H
E A
T E
R S
G R
O U
P "A
"H
E A
T E
R S
G R
O U
P "C
"H
E A
T E
R S
S
IN
G L E U
N
IT
S P
A R
E C
O M
P A
R T
M E
N T
G E
N
A
IR
C
IR
C U
IT
RELAY RACK
TO ANNUNCIATOR
F A
N N
O .2
F A
N N
O .4
F A
N N
O .2
F A
N N
O .2
F A
N N
O .2
F A
N N
O .2
F A
N N
O .4
F A
N N
O .4
F A
N N
O .4
F A
N N
O .4
T O
V
T O
V
H
T O
V
H
"V1" 460V-XENTILATION BUS
FOR CONTINUATION SEE DWG. Q-21784
TO MAIN TRANSFORMER BANK 3
13.8 K.V. STA. SER.BUS
TO MAIN TRANSFORMER BANK 2
51G7-LONG TIME DELAY
5168-SHORT TIME DELAY
51G7X TRIPS ACB 078 (13)
& ANN
51G8X TRIPS ACB 073 (15)
& ANN
27G7X, 63Q75 (LOW GOV.
OIL PRESS), 7511 ACTUATE
86G7
86G7 TRIPS AND LOCKS OUT.
1.GEN. ACB 078 (13)
2.GOV. SHUTDOWN SOL.
3.ANN.
RELAY RACK
TO ANNUNCIATOR
GOVERNOR
FLYBALL MOTOR
ATTACH
INSTANT
AT RIGHT
SEE TABLE
1500 KVA-13,200-480V.
TRANSFORMER BANK
STATION SERVICE
"SS"'-460V MAIN STATION SERVICE
T O F
E E
D E
R B
K R S .S
B D
'SS"-460V MAIN STATION SERVICE BUS NO.1S
P
A R
E C
O M
P A
R T
M E
N T
S P
A R
E C
O M
P A
R T
M E
N T
S P
A R
E C
O M
P A
R T
M E
N T
R O
O M H
T R
S
O N S
W G
R F
T U
R B
IN
E O
IL
P
U M
P
G O
V
O
IL
P
U M
P
B
J A
C K
IN
G P
U M
P
G O
V
O
IL
P
U M
P
A
G E
N
H O
U S
IN
G H
E A
T E
R
T O F
E E
D E
R B
K R S .S B
D
"U1" 460V-UNIT BUS #1
"U2" 460V- UNIT BUS #2
(SAME AS "U1")
"U3" 460V- UNIT BUS #3
(SAME AS "U1")
"U4" 460V- UNIT BUS #4
(SAME AS "U1")
"U6" 460V-UNIT BUS #6
(SAME AS #UI#)
"U5" 460V- UNIT BUS #5
(SAME AS "U1")
"U7" 460V-PUMP AND COMPRESSOR BUS
V
IL
L A
G E P
U M
P N
O .1
B A
T T
C H
A G
R .M
-G S
E T N
O .1
R O
T A
R Y D
IS
P L
A C
E M
E N
T
C
H E
M
IC
A L
P U
M P
F E
E D P
U M
P S F
E E
D E
R /6
C O
N T
S
E T T
A N
K A
G
IT
A T
O R
V
IL
L A
G E P
U M
P N
O .2
N O .1 S
E W
A G
E P
U M
P
N O .2 S
E W
A G
E P
U M
P
N O .1 -1
C
F M A
IR
C
O M
P R
N O .2 -3
C
F M A
IR
C
O M
P R
N O .3 -1
.8
C F
M A
IR
C
O M
P R
N O .2 A
IR
C
O N
D
U N
IT
F
D R
N O .1 A
IR
C
O N
D
U N
IT
F
D R
E L E
V A
T O
R F
E E
D E
R
S P
A R
E B
R E
A K
E R
U N
IT
S P
A R
E C
O M
P A
R T
M E
N T
RELAY RACK
TO ANNUNCIATOR
G O
V
O
IL
P
U M
P
T U
R B
IN
E O
IL
P
U M
P
U
N
IT
S P
A R
E C
O M
P A
R T
M E
N T
R O
O M H
E A
T E
R S
S P
A R
E B
R E
A K
E R
S U
M P P
U M
P N
O .1
A
G A
N T
R Y C
R A
N E F
D R
C A
B L E P
IP
E L
IN
E S
Y S
T E
M
P U
M P
IN
G U
N
IT
O
IL
R
O O
M F
E E
D E
R
M A
C H
IN
E S
H O
P F
E E
D E
R
S P
A R
E B
R E
A K
E R
S U
M P P
U M
P N
.2
M P P
U M
P N
.3
M P P
U M
P N
O .1
B
B A
T T .C
H G .M
-G S
E T N
O .2
S .S
G E
N
H E
A T
E R
S
H U
N T T
R
IP
C O
N T
R O
L T
R A
N S
F O
R M
E R
A N
D P
A N
E L
B O
A R
D
T U
N N
E L S
U P
P L
Y F
A N N
O .2
E X
H A
U S
T F
A N N
O .1
E X
H A
U S
T F
A N N
O .2
E X
H A
U S
T F
A N N
O .2
E X
H A
U S
T F
A N N
O .2
E X
H A
U S
T F
A N N
O .2
E X
H A
U S
T F
A N N
O .2
E X
H O
U S
T F
A N N
O .2
D
A M
P E
R
S U
P P
L Y F
A N N
O .1
I
N T
A K
E D
A M
P E
R
S U
P P
L Y F
A N N
O .1
I
N T
A K
E D
A M
P E
R
S U
P P
L Y F
A N N
O .1
I
N T
A K
E D
A M
P E
R
G R
O U
P "E
"H
E A
T E
R S
G R
O U
P "D
"H
E A
T E
R S
G R
O U
P "C
"H
E A
T E
R S
G R
O U
P "B
"H
E A
T E
R S
G R
O U
P "A
"H
E A
T E
R S
S P
A R
E C
O M
P A
R T
M E
N T
S P
A R
E C
O M
P A
R T
M E
N T
S P
A R
E C
O M
P A
R T
M E
N T
G E
N
A .C .B
A
IR
C
O M
P R
E S
S O
R N
O .2
S U
P P
L Y F
A N
S
I
N T
A K
E D
A M
P E
R
V T -H
T R D
O M
P E
R F
A N C
O N
T
S U
P P
L Y F
A N N
O
S U
P P
L Y F
A N N
O
S U
P P
L Y F
A N N
O
S U
P P
L Y F
A N N
O
S U
P P
L Y F
A N N
O .8 I
N T
A K
E D
A M
P E
R
S U
P P
L Y F
A N N
O .1
R
E C
IR
C U
L A
T
IN
G D
A M
P E
R
C O
N T
R O
L T
U N
N E
L S
U P
P L
Y D
A M
P E
R T O
V
T R
O L L E
Y T
R A
V E
L
B R
ID
G E T
R A
V
X
IL
IA
R Y H
O
IS
T
M A
IN
H
O
IS
T
T R
O L L E
Y T
R A
V E
L
B R
ID
G E T
R A
V
X
IL
IA
R Y H
O
IS
T
M A
IN
H
O
IS
T
CRANE MANUFACTUER
EQUIPMENT FURNISHED BY
SWITCHGEAR SS
D-C DIST. PNLBD.
SWITCHYARD CONTROL
SWITCHBOARD AS
D-C DIST. PNLBD.
SWITCHYARD CONTROL
SWITCHBOARD AS
MAIN STATION SERVICE
POWERHOUSE CRANE
LIGHTING TRANSFORMER
5 KVA-1 -480 TO 120/240V.
F1-F2-F3
FIELD PANEL
F4-F5-F6
FIELD PANEL
SPARE BREAKER
SWITCHYARD (FUTURE)
SWITCHYARD
F7
FIELD PANEL
A S
V
B A
T T
E R
Y B
U S
BREAKER
SPARE
SPARE BREAKER
LC20 & LC19
LTG. CAB.
ANNUNCIATION
SYSTEM DC SUPPLY
METER TEST ROOM
L
IG
H T
IN
G C
A B L
C L
C
S P
A R
E B
R E
A K
E R
L C
L
C
L
IG
H T
IN
G C
A B
L
IG
T H
T
IN
G C
A B L
C L
C
S P
A R
E B
R E
A K
E R
S P
A R
E B
R E
A K
E R
RELAY RACK
TO ANNUNCIATOR
EMERGENCY HTY.L
IG
H T
IN
G C
A B L
C L
C
L
IG
H T
IN
G C
A B L
C
L
IG
H T
IN
G C
A B L
C
,1
L C 'S
EMERGENCY
,1
,1
L C 'S ,4
,8
L C 'S
L C 'S
L C 'S
L C 'S
S P
A R
E B
R E
A K
E R
L
IG
H T
IN
G C
A B L
C
S P
A R
E B
R E
A K
E R
L
IG
H T
IN
G C
A B .L
C
L
IG
H T
IN
G C
A B L
C L
C
L
IG
H T
IN
G C
A B L
C L
C
"V2" 460V-VENTILATION BUS
AT FAN NO.17
CONTROL CENTER "U7"
TO SEC.1 ACB NO.3
CONTROL CENTER "U8"
TO SEC.5 ACB NO.18
LIGHTING SWGR "LS"
120/208V-3 -4- WIRE LIGHTING BUS
3 VOLTMETER FUSES
RELAY RACK
TO ANNUNCIATOR
480-120/208V.
LIGHTING TRANSF. 3 200KVA
BATTERY 60 CELLS
S .S
B D
T O F
E E
D E
R B
K R
S .S
B D
T O F
E E
D E
R B
K R
460V-SUMP PUMP BUS
S P
A R
E C
O M
P A
T M
E N
T
C O
M P F
O R S
U M
P P
U M
P S
E L
S W
S
A N
D R
E L
A Y
S
S P
A R
E C
O M
P A
T M
E N
T
S
IN
G L E U
N
IT
M P P
U M
P N
O .5
S U
M P P
U M
P N
O .6
U N
IT
H
E A
T E
R
S
IN
G L E U
N
IT
A R
E C
O M
P A
T M
E N
T
S U
M P P
U M
P N
O .4
A
S P
A R
E B
R E
A K
E R
C R
A N
E F
E E
D E
R
P O
W E
R H
O U
S E
F D
R
N O .2
S W
IT
C H
B O
A R
D
V
IL
L A
G R F
D R
N O .2
D A
M F
E E
D E
R N
O .1
H E
A D
W A
T E
R F
D R
N O .2
S P
A R
E A
C B
D A
M F
E E
D E
R N
O .1
S W
IT
C H
Y A
R D F
D R
3 VOLTMETER FUSES
VS VS
M G
VM AM AM
M G
VM AM
VM
GR
TS
V
G
AS
VSA VSVSSSPL
ASAS
FB
AS AS
A
T
7 VSSVSVS
BUS NO.2
24 25 26 27
600A 300A
/0
350A
-4
M C
M
-4
M C
M
25 23
450A
450A
15A
25A
CONTROLS
CB'S
CONT.
20A, 2R
25A
25A
20A
20A
20A
20A
20A
20A
20A
20A
15A
35A
35A
25A
25A
10 9 8
90A
27 27
70A
18 18
70A
70A
18 18
70A
27 27
18 18
DISC. T3
SWGR. G5
SAT. C. T.'S
3-400-5Y
5-10Y
51TSX
ANNUNCIATOR
A.C.B. NO. 073 (15)
TRIPS
51TSX
87TSX SW DISC. T3
87T5X2
87TSX190G7
MM
10-5Y
MM
MM MM
MM
DISC.'T2
1-2000-5A
B6G7
2-2000-5A 3-2000-5-5Y
U8
A
MM
A
MM
GEN.
1500KVA
STATION
SERVICE
EX.
AM AM
SS
AR AR
A
REG
VOLT
R
MR
R
MR
AR
AR
MR
MR
T S
T S
AM AM
SS
W W
AR
AR
"A" SW DISC. T2
MR
R
1-480-120V
2-480-120V
43TS
MB
11 12 14 16 17 18 19 20
300A 500A 500A
500A 500A 300A 300A
VM VM
SS MM
21 22 23
800A 400A
SWGR. G4
51G7X
51G8XF7
MR MR MM MM
AM AR AR
51G7 51G8 27G7X
R R WH WH
MR
MB MB
MM
2-480-120V
SS
43TS
R
27G7
VM VM
CS
F7
VM
FC
R
6 7 8 9 10 11
90A 90A
40 2
15A 50A
275A
275A
3 4 5
15A 50A
275A
275A
275A
275A
275A
275A
275A
275A
275A
275A
500A19
16151413121110
150A 20A 125A 125A 50A 150A 500A
9876543
50A
20A 15A 15A20A
15A
70A
15 16 17 18 543
200A 100A 100A200A 50A 150A150A150A
VM29
AM27
800A
2 3 4 5 6 7 8 9 10
500A
500A 500A 800A 400A300A300A 500A 600A 500A
-5
M C
M
-5
M C
M
/0
-4
M C
M
/0
/0
/0
/0
/0
/0
-5
M C
M
-5
M C
M
-5
M C
M
N O .1
/0
/0
/0
H E
A D
G A
T E F
D R
N O .1
/0
D A
M F
E E
D E
R N
O .1
/0
-5
M C
M
/0
50A50A
24A 24B 24C
50A 50A50A
24D 24E 24F
50A
23 8 14
100A 50A 100A 100A
4-500MCM
3-800/5A
#1
21 20 19 18 17 16 14 13 12 10 9 8 7 6 5 4 3
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 18
15A
15A
20A
1 1
50A 125A
50A
50A
100A
60 15 15
125A
50A 15A 70A 100A
T
15A 50A
500A
500A
6KW
275A
275A
15A
CONTROLS 27
15A
25A
25A
35A
20A
20A
20A
20A
20A
25A
35A
25A
50A
50A
35A
35A
15 11
35A
"U8" 460V-STATION UNIT BUS
460 V. BUS
C
C
C
40 50 50
C C
50 50
C C
100A
100A
100A
100A
150A
150A
150A
150A125A
125A
100A
100A
125A
300A
225A
225A
225A
225A
100A
100A
100A
150A
150A
NO.1 CHARGER
NO.2 CHARGER
NONE
NONE
9 10 11 12 19 20 22 2118
100A 100A 100A 100A 150A 150A150A200A100A
VM28
AM
800A
3-800/5A
4-500MCM
#2
59 60 61 62 63 64 65
50A 50A 125A 125A50A 20A
"U9"
2 2 4
1715 15 60
400A
400A
SYMBOLS;
AIR CIRCUIT BREAKER-MANUALLY OPERATED
AIR CIRCUIT BREAKER-ELECTRICALLY OPERATED
AIR CIRCUIT BREAKER-DRAW OUT TYPE
DISCONNECT SWITCH
FUSE
MOTOR STARTER, NON-REVERSING LINESTART TYPE
NUMBER INDICATES NEMA STARTER SIZE
ELECTRIC HEATER,30KW
CRANE MOTOR CONTROLLER
TRANSFORMER
CURRENT TRANSFORMER
POTENTIAL TRANSFERMER
BATTERY
INSTANTANEOUS
TIME
FREQUENCY CONTROLLER
ACB TRIPPING MEANS
GROUND RESISTANCE METER
TEST TRANSFER SWITCH
GREEN IND. LT
120V CONTACTOR-NO. INDICATED NEMA SIZE
RED IND.LT
PUSH BUTTON-START
PUCH BUTTON-STOP
FOR METER SYMBOLS SEE DWG. Q-2/784
TS
GR
FC
C
MOTOR, 15 HORSEPOWER
1 2
2'-6" 2'-6" 2'-6" 2'-6" 1'-4" 3'-6" 3'-6" 3'-6" 1'-4" 2'-6" 2'-6" 2'-6" 2'-6"
33'-5" MAXIMUM
1'-9" 7'-0"
A
AUX. RELAY NO. 2 TRIPS AND LOCKS OUT:
O.C.B.'S 924 & 928
GENS. 5 & 6 MAIN A.C.B.'S
TRIPS:
1 2 3 4 5 6 7 8 9 10 11 12 14
500A
500A
500A
300A
300A
20 52
800A
400A
500A
600A
24 25
350A
300A
SINGLE LINE DIAGRAM
R A
V
STA. SERV. TRANSF. A.C.B.
ANNUNCIATOR
AUX. RELAY NO. 1 TRIPS AND LOCKS OUT:
O.C.B.'S 944 & 948
GENS. 3 & 4 MAIN A.C.B.'S
TRIPS:
STA. SERV. TRANSF. A.C.B.
ANNUNCIATOR
AR
R
Am
FC
AS
GOVERNOR
FLY-BALL MOTOR
FB
MR
ITEM
NO.
USE
VOLTAGE
RATING INT. CAP.
NEMA
FRAME
RATING
NO.
POLES
TRIP
RATING
TERMINAL
& CABLE
SIZE
MAN. OR
ELECT
OPERATED
50,000
50,000
50,000
50,000
50,000
50,000
50,000
50,000
50,000
50,000
50,000
50,000
75,000
75,000
75,000
50,000
50,000
50,000
50,000
50,000
50,000
50,000
50,000
50,000
50,000
50,000
50,000 3
3 800
800 300
500 MAN.
6-#4/0
6-#4/0
3-#4/0
3-#4/0
6-500MCM
3-500MCM
3-500MCM
3-400MCM
3- #4/0
3 #4/0
BUS
BUS
BUS
6- #4/0
6- #4/0
6- #4/0
3- #4/0
3- #4/0
6-500MCM
3-500MCM
3-500MCM
3-400MCM
3- #4/0
3-400MCM
3 #4/0
MAN.
MAN.
MAN.
MAN.
MAN.
MAN.
MAN.
MAN.
MAN.
MAN.
MAN.
ELECT.
ELECT.
ELECT.
MAN.
MAN.
MAN.
MAN.
MAN.
MAN.
MAN.
MAN.
MAN.
MAN.
MAN.
MAN.
STATION SERVICE BUS GRD. RELAY WITH AMBER IND. LIGHT
AMMETER-TRANSFER SWITCH
VOLTMETER-TRANSFER SWITCH
AMMETER-STATION SERVICE TRANSFORMER (0-2000A)
VOLTMETER-STATION SERVICE TRANSFORMER (0-600V)
AMMETER-STATION SERVICE GENERATOR (0-2000A)
VOLTMETER-STATION SERVICE GENERATOR (0-600V)
BUS TRANSITION SPACE
SWITCHYARD FEEDER NO 2 A.C.B.
CRANE FEEDER A.C.B.
VILLAGE FEEDER NO.2 A.C.B.
SWITCHGEAR "U9" & "V2" FEEDER NO.2 A.C.B.
SWITCHGEAR "U8" FEEDER NO.2 A.C.B.
LIGHTING TRANSFORMER NO.2 A.C.B.
SWITCHGEAR "U7" & "V1" FEEDER NO.2 A.C.B.
DAM FEEDER NO.2 A.C.B.
HEADGATE FEEDER NO.2 A.C.B.
SWITCHGEAR "U3" & "U6" FEEDER NO.2 A.C.B.
SWITCHGEAR "U2" & "U5" FEEDER NO.2 A.C.B.
SWITCHGEAR "U1" & "U4" FEEDER NO.2 A.C.B.
STATION SERVICE TRANSFORMER A.C.B.
BUS TIE A.C.B.
STATION SERVICE GENERATOR A.C.B.
SPARE A.C.B.
VILLAGE FEEDER NO.1 A.C.B.
SWITCHGEAR "U9" & V2" FEEDER NO.1 A.C.B.
SWITCHGEAR "U8" FEEDER NO.1 A.C.B.
LIGHTING TRANSFORMER NO.1 A.C.B.
SWITCHGEAR "U7" & "V1" FEEDER NO.1 A.C.B.
DAM FEEDER NO.1 A.C.B.
HEADGATE FEEDER NO.1 A.C.B.
SWITCHGEAR "U3" & "U6" FEEDER NO.1 A.C.B.
SWITCHGEAR "U2" & "U5" FEEDER NO.1 A.C.B.
SWITCHGEAR "U1" & "U4" FEEDER NO.1 A.C.B.
LIST OF EQUIPMENT
CIRCUIT BREAKER
NO DATE R E V I S I O N S BY CHKD
C U M B E R L A N D R I V E R W A T E R S H E D
W O L F C R E E K R E S E R V O I R P R O J E C T
C U M B E R L A N D R I V E R, K E N T U C K Y
P O W E R H O U S E
MAIN STATION SERVICE SWITCHGEAR SS
IN SHEETS SHEET NO. 11
SCALE: 1 INCH = 1 FOOT
U. S. ENGINEER OFFICE, NASHVILLE, TENN.
APPROVAL RECOMMENDED.SUBMITTED. APPROVED.
PRINCIPAL ENGINEER HEAD ENGINEER COL . CORPS OF ENGINEERS
DISTRICT ENGINEER
SUPV. CHECKED TO ACCOMPANY SPECIFICATIONS
DRAWN TRACED DATED
STATION SERVICE
TRANSF BANK
1500 KVA 13,200-180V
F7
VOLT
REG
MM
MR
INSTANT
ATTACH
MR
LINES IS NOT PART OF THIS SWGR.
EQUIPMENT SHOWN IN DASHED
MR INDICATES SWITCHBOARD
ON WHICH INSTRUMENT IS LOCATED.
R A
V
MR
ANNUNCIATOR
A.C. B NO. 5
'A' SW DISC. T3
'A' SW. DISC. T2
5'-0" 5'-5
6'-0"
5" 8" 4"
8"
2"
EL 5950
CABLE PIT
1'-8 1/2"
2000 5-5 CT'S
SECTION A-A
y
SCALE: 1/2" = 1'-0"
EL. 595.0
V
480-120V PT'S
6-#4/0
WAR DEPARTMENT CORPS OF ENGINEERS, U.S. ARMY
12" 6" 0 1' 2'
SEE SPECS
LIMIT OF BUS DUCT DOOR O
-2
-5 -5
Y
MANUFACTURER'S
STANDARDS. VARIATIONS TO SUIT OTHER MANUFACTURER'S
1 SEP 2014 CONVERTED TO CAD MJC JHG
Q-2/793.1
SWITCHYARD.1 FEEDER NO.1 A.C.B.
1 4 7 10
2 5 8 11
3 6 9 12
PANEL NO. 1 PANEL NO. 2 PANEL NO. 3 PANEL NO. 4
33 34
29 30
13 14 15
33 34
31 32
16 19 22 25
17 20 23 26
18 21 24 27
PANEL NO. 9 PANEL NO. 10 PANEL NO. 11 PANEL NO. 12 PANEL NO. 13
5'-6"
SPACE FOR TELEPHONE. TO BE
FURNISHED AND MOUNTED
BY GOVERNMENT
STATION SERVICE GENERATOR
A.C.B. ELECTRICALLY OPERATED
BUS TIE A.C.B.
ELECTRICALLY OPERATED
STATION SERVICE TRANSFORMER
A.C.B. ELECTRICALLY OPERATED
PANEL NO. 5 PANEL NO. 6 PANEL NO. 7
FRONT ELEVATION
C STA. GEN.L
BUS DUCT.
SEE DWG
Q-2/797
Q-2/797
SEE DWG
BUS DUCT.
C STA. TRANSF.L
PANEL NO. 8
SAT. CT'S
3-400-5Y
S W
IT
C H
G E
A R
U
S W
IT
C H
G E
A R
U
S W
IT
C H
G E
A R
U
S W
IT
C H
G E
A R
U
S W
IT
C H
G E
A R
U
S W
IT
C H
G E
A R
U
H E
A D
G A
T E F
E E
D E
R N
O
D A
M F
E E
D E
R N
O
S W
IT
C H
G E
A R
U
S W
IT
C H
G E
A R
V
L
IG
H T
IN
G T
R A
N S
F
N O
S W
IT
C H
G E
A R
U
S W
IT
C H
G E
A R
U
S W
IT
C H
G E
A R
V
V
IL
L A
G E F
E E
D E
R N
O
S W
IT
C H
Y A
R D F
E E
D E
R N
O
S P
A R
E A .C .B
S W
IT
C H
G E
A R
U
S W
IT
C H
G E
A R
U
S W
IT
C H
G E
A R
U
S W
IT
C H
G E
A R
U
S W
IT
C H
G E
A R
U
S W
IT
C H
G E
A R
U
H E
A D
G A
T E F
E E
D E
R N
O
D A
M F
E E
D E
R N
O
S W
IT
C H
G E
A R
U
S W
IT
C H
G E
A R
V
L
IG
H T
IN
G T
R A
N S
F
N O
S W
IT
C H
G E
A R
U
S W
IT
C H
G E
A R
U
S W
IT
C H
G E
A R
V
V
IL
L A
G E F
E E
D E
R N
O
S W
IT
C H
Y A
R D F
E E
D E
R N
O
P O
W E
R H
O U
S E
C R
A N
E F
E E
D E
R
NOTES: (CONT.)
THE CONTRACTING OFFICER HOWEVER, THE GENERAL ORDER AND
ARRANGEMENT OF EQUIPMENT AS SHOWN HERE SHALL BE
FOLLOWED AS NEARLY AS PRACTICABLE.
ALL BREAKERS SHALL BE PROVIDED WITH AUXILIARY SWITCHES
1.
2.
FOR SYMBOLS SEE DWG., Q-2/7923.
THIS IS A CONTRACT DRAWING TO BE USED FOR THE PRO-
CUREMENT OF EQUIPMENT AND IS NOT TO BE USED FOR
CONSTRUCTION. FOR CONSTRUCTION PURPOSES USE
4.
MANUFACTURER'S DRAWINGS.
5. INSTALLATION OF THIS EQUIPMENT WILL BE PAID FOR
UNDER CONTRACT ITEM
C-
AND 2 NORMALLY CLOSED .)
HAVING NOT LESS THAN 4 CONTACTS (2 NORMALLY OPEN
GENERAL NOTES:
1. THE DIMENSIONS AND GENERAL CONSTRUCTION SHOWN ON
THIS DRAWING ARE BASED ON ONE MANUFACTURER'S
STANDARD CONSTRUCTION WILL BE PERMITTED IN ACCORDANCE
WITH THE SPECIFICATIONS AND SUBJECT TO APPROVAL BY
FURNISHED BY GENERATOR MANUFACTURER. MOUNTING
AND WIRING BY SWITCHGEAR MANUFACTURER.
THESE BREAKER'S ELECTRICALLY INTERLOCKED TO
REQUIRE USE OF SYNCHRUSCOPE (SEE SCHEM. DIAGRAMS)
5-200 VA 480-120V POT. TRANSFS.(3 IN GEN. ACB COMPT. AND 2 IN TRANSF. ACB COMPT.
3-2000-5A CT'S (IN GENERATOR ACB COMPT.)
3-10-54 AUXILIARY CTS (IN TRANSTFS. A.C.B. COMPT.)
57&56 D-C PANELBOARDS CONTAINING 15-250V, 2P, 50A FRAME BREAKERS (NOS. 40-54 INCL.) & 3-250V, 2P, 100A
FRAME FEEDER BREAKERS 9NOS. 39,55,&56) FOR TRIP RATING AND USE SEE DWG. Q-2/833
3 2000-5-5ACT'S (IN TRANSF. A.C.B. COMPT.)
TRIP RATING
SEE DWG Q-2/797
ENCLOSED BUS.
600V, 2000A, 3 PHASE
TRIPS:
5-10Y
R
R
SS MM
Am Am
MM MM
AR
AR
AS AS W WH
2-480-120V
VS VS SS
MB
VM VM
SS MM
460 VOLT-3 -60 CYCLE BUS NO. 2
10-5Y
2-480-120V
*1-480-120V
2-2000-5A
*1-2000-5A
1500KVA
STATION
SERVICE
GEN
AMAM
MM SS
T R
IP
S A
C B N
O
L O
N G T
IM
E D
E L
A Y
T R
IP
S A
C B N
O S
H O
R T T
IM
E D
E L
A Y
MR MM MM
WWHR AS AS
RVS VS VSPL SS
CS
MB MB
MR
VMVM
MM SS
VM
F7
460 VOLT-3 -60 CYCLE BUS NO. 1
500A
/0
500A 500A 300A 300A
-5
M
C M
800A
-5
M
C M
400A 500A 600A 300A
/0
/0
-4
M
C M
-5
M
C M
500A
/0
-5
M
C M
-5
M
C M
-5
M
C M
-4
M
C M
/0
-4
M
C M
/0
A 7
8'-4"
1'-8" 1'-8" 1'-8" 1'-8" 1'-8"
5'-0"
1'-8" 1'-8" 1'-8" 5"
1'-8"
GENERAL NOTES:
LIST OF EQUIPMENT - CONTROL CENTERS UI - U6 INCL.
ITEM
NO
VOLTAGE
RATING INT CAP
NEMA
NO.
POLES
FRAME
RATING
HP
LOAD
& CABLE
TERMINAL
TRIP
RATING SIZE
NEMA COIL
VOLTAGE
CIRCUIT BREAKER MOTOR STARTER
USE
SIZE
BUS SUPPLY FDR. NO.1
SPARE COMPARTMENT
GEN. JACKING PUMP MOTOR FDR.
GEN. HSG. HEATER FDR.
GOV. OIL PUMP (#1A-6A) FDR.
TURBINE OIL PUMP MOTOR STARTER
ROOM HEATER (F1-F6) FEEDER
INDICATING LIGHTS FEEDER BREAKER ON SWGR. SS
AUXILIARY RELAY TO OPERATE ALARM ON LOSS OF BUS VOLTAGE
BUS SUPPLY FDR. NO.2
GOV. OIL PUMP (#1B-6B) FDR.
SPARE COMPARTMENT
SPARE COMPARTMENT
INDICATING LIGHTS FEEDER BREAKER ON SWGR. SS
25,000
25,000
15,000
15,000
15,000
15,000
15,000
15,000
3 600 275 - - #4/0
3 600 275 - - #4/0
3 100 15 -- #12
3 100 50 - - #8
3 100 90 - - #4
3 100 90 - - #4
600 100 15 1 440AC #12
600 100 50 - - #8
1 1/2
24 KW
1/2
30 KW
BUS SUPPLY FDR. NO.1
DAM WATER SUPPLY PUMP FDR.
BATT. CHGR. M-G SET NO.1 MOTOR
ROTARY DISPL. & CHEM. FEED PUMPS FDR.
FILTERED WATER PRESSURE PUMP FDR.
NO.1 - 113 CFM AIR COMP. STARTER
NO.1 AIR COND. UNIT FDR.
ELEVATOR FEEDER
BUS SUPPLY FDR. NO.2
NO.1 SEWAGE PUMP MOTOR STARTER
25,000
25,000
15,000
15,000
15,000
15,000
15,000
15,000
3 600 500 - - 500 MCM
3 600 500 - - 500 MCM
3 100 15 1 440AC #12
3 100 15 - - #12
3 100 25 1 440AC #12
3 100 15 1 440AC #12
3 100 70 3 440AC #6
3 225 150 - 440AC #1/0
7 1/2
SPARE BREAKER
SPARE COMPARTMENT
INDICATING LIGHTS - NO.6 FEEDER BREAKER ON SWGR.SS
AUXILIARY RELAY USED TO OPERATE ALARM ON LOSS OF BUS VOLTAGE
NO.2 SEWAGE PUMP MOTOR STARTER
NO.2 - 330 CFM AIR COMP. STARTER
NO.3 - 10.8 CFM AIR COMP. STARTER
NO.2 AIR COND. UNIT FDR.
INDICATING LIGHTS - NO.21 FEEDER BREAKER ON SWGR.SS
600 25,000
15,000
15,000
15,000
15,000
15,000
15,000
120AC
440AC
440AC
#10
#12
#12
#1/0
#1/0
#8
#1/0
LIST OF EQUIPMENT - CONTROL CENTERS UI - U7
CORPS OF ENGINEERS, U. S. ARMY
SEE ONE LINE DIAGRAM FOR BREAKER NUMBERS
* MOUNT CONTROL TRANSFORMER, 480-120VOLT, IN THIS COMPARTMENT
THE DIMENSIONS AND GENERAL CONSTRUCTION SHOWN ON THIS
DRAWING ARE BASED ON ONE MANUFACTURER'S STANDARDS
AND VARIATIONS TO SUIT OTHER MANUFACTURER'S STANDARD
CONSTRUCTION WILL BE PERMITTED IN ACCORDANCE WITH
THE SPECIFICATIONS AND SUBJECT TO APPROVAL OF THE
CONTRACTING OFFICER. HOWEVER THE GENERAL ORDER AND
ARRANGEMENT OF EQUIPMENT SHOWN HERE SHALL BE FOLLOWED
AS NEARLY AS PRACTICABLE.
CONTROL CENTERS UI, THROUGH U6 ARE IDENTICAL AND ONLY
ONE FRONT VIEW, SINGLE LINE DIAGRAM, AND LIST OF
EQUIPMENT ARE SHOWN. HOWEVER, SIX COMPLETE IDENTICAL
CONTROL CENTERS ARE TO BE FURNISHED.
SECTION A-A THRU CONTROL CENTER UI IS ALSO TYPICAL FOR
CONTROL CENTER U7 FOR GENERAL CONSTRUCTION AND
ARRANGEMENT OF INCOMING CABLES.
ALL MOTORS STARTERS SHALL BE NON-REVERSING LINESTART
TYPE AND SHALL HAVE 3 EXTRA AUXILIARY CONTACTS
FOR USE AS INTERLOCKS, ETC.
ITEMS NOS.1 AND 2. CONTROL CENTERS UI THROUGH U6, AND
U7 SHALL BE MECHANICALLY INTERLOCKED SO THAT BOTH
CANNOT BE CLOSED AT THE SAME TIME.
THIS IS A CONTRACT DRAWING TO BE USED FOR THE
PROCUREMENT OF EQUIPMENT AND IS NOT TO BE USED
FOR CONSTRUCTION. FOR CONSTRUCTION PURPOSES USE
MANUFACTURER'S DRAWINGS.
FOR SYMBOLS SEE DWG. Q-2/792
INSTALLATION OF THIS EQUIPMENT TO BE PAID FOR UNDER
CONTRACT ITEM 95
C-
1.
2.
3.
4.
5.
6.
7.
8.
VOID - SEE MFGR'S DWG.
275A 275A 15A 50A 90A 90A 15A 50A
1 2 3 4 5 6 7 8 9 10 11
460 VOLT 3 BUS
TRIP RATING
SIZE
CONTACTOR
SIZE (NEMA)
T O A
N N
U N
C
IA
T O
R
R E
L A
Y R
A C
K
/0
/0
1 1/2 24 40 1/2 30
S U
P P
L Y F
D R
N O .1
S U
P P
L Y F
D R
N O .2
S P
A R
E C
O M
P A
R T
M E
N T
J A
C K
IN
G P
U M
P
G E
N E
R A
T O
R H
O U
S
IN
G H
E A
T E
R
G O
V E
R N
O R O
IL
P
U M
P
A
S P
A R
E C
O M
P A
R T
M E
N T
T U
R B
IN
E O
IL
P
U M
P
R O
O M H
E A
T E
R S O
N S
W G
R .F
S P
A R
E C
O M
P A
R T
M E
N T
G O
V E
R N
O R O
IL
P
U M
P
B
T O A
N N
U N
C
IA
T O
R
R E
L A
Y R
A C
K
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
460 VOLT 3 BUS
500A 500A 50A 15A 15A 25A 15A 15A 70A 150A 20A 125A 125A 50A 150A TRIP RATING
CONTACTOR SIZE
(NEMA)
SIZE
SIZE
SIZE
SIZE
SIZE
SIZE
SIZE
SIZE
-5
M
C M
-5
M
C M
/0
/0
/0
SECTION 1
MASTER TERMINAL BOARDS
A
1 4 9
12 5 10
2 6
3 8
13 7 11
EL.567.0
A
SECTION 1
MASTER TERMINAL BOARD
1 4 9 11 14
17 5 12 15
2 6
18 7
3 8
EL.567.0
FRONT VIEW CONTROL CENTER U1
CONTROL CENTERS U2 - U6 SIMILAR
ONE LINE DIAGRAM -…