W912JB-18-R-9003
ADD WATER MAIN LOOPS
RFI-001
Question: What are the security measures required for when a portion of the fence is removed to install the water main on sheet C-300?
Answer: C/300 and C/302 show details removing and restoring fence. In both areas fence fabric will need to be temporarily secured at the end of each work day. Security Forces will increase evening patrols