Amendment_0005_RFP_W912DW19R0017_.pdf

PDF 848 KB Posted

Attached to
Construct a Hot Refueling System at Gray Army Airfield (GAAF), JBLM, WA
Solicitation number
W912DW19R0017
Issued by

About this file

Amendment 0005 for RFP W912DW19R0017 Construct a Hot Refueling System at Gray Army Airfield (GAAF), Joint Base Lewis McChord (JBLM), WA

View the file

Other files

Show all 17

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

AMENDMENT OF SOLICITATION/MODIFICATION OF CONTRACT

Except as provided herein, all terms and conditions of the document referenced in Item 9A or 10A, as heretofore changed, remains unchanged and in full force and effect.

15A. NAME AND TITLE OF SIGNER (Type or print)

30-105-04EXCEPTION TO SF 30

APPROVED BY OIRM 11-84

STANDARD FORM 30 (Rev. 10-83)

Prescribed by GSA

FAR (48 CFR) 53.243

RFP W912DW19R0017 Construct a Hot Refuel System at Gray Army Airf ield (GAAF) at Joint Base Lew is-McChord (JBLM), WA

Please see Continuation Page for more details.

1. CONTRACT ID CODE PAGE OF PAGES

1 5

16A. NAME AND TITLE OF CONTRACTING OFFICER (Type or print)

16C. DATE SIGNED

BY 02-Jul-2019

16B. UNITED STATES OF AMERICA15C. DATE SIGNED15B. CONTRACTOR/OFFEROR

(Signature of Contracting Officer)(Signature of person authorized to sign)

8. NAME AND ADDRESS OF CONTRACTOR (No., Street, County, State and Zip Code) X W912DW19R0017

X 9B. DATED (SEE ITEM 11)

28-May-2019

10B. DATED (SEE ITEM 13)

9A. AMENDMENT OF SOLICITATION NO.

11. THIS ITEM ONLY APPLIES TO AMENDMENTS OF SOLICITATIONS

X The above numbered solicitation is amended as set forth in Item 14. The hour and date specified for receipt of Offer is extended, X is not extended.

Offer must acknowledge receipt of this amendment prior to the hour and date specified in the solicitation or as amended by one of the following methods:

(a) By completing Items 8 and 15, and returning 1 copies of the amendment; (b) By acknowledging receipt of this amendment on each copy of the offer submitted;

or (c) By separate letter or telegram which includes a reference to the solicitation and amendment numbers. FAILURE OF YOUR ACKNOWLEDGMENT TO BE

RECEIVED AT THE PLACE DESIGNATED FOR THE RECEIPT OF OFFERS PRIOR TO THE HOUR AND DATE SPECIFIED MAY RESULT IN

REJECTION OF YOUR OFFER. If by virtue of this amendment you desire to change an offer already submitted, such change may be made by telegram or letter, provided each telegram or letter makes reference to the solicitation and this amendment, and is received prior to the opening hour and date specified.

12. ACCOUNTING AND APPROPRIATION DATA (If required)

13. THIS ITEM APPLIES ONLY TO MODIFICATIONS OF CONTRACTS/ORDERS.

IT MODIFIES THE CONTRACT/ORDER NO. AS DESCRIBED IN ITEM 14.

A. THIS CHANGE ORDER IS ISSUED PURSUANT TO: (Specify authority) THE CHANGES SET FORTH IN ITEM 14 ARE MADE IN THE

CONTRACT ORDER NO. IN ITEM 10A.

B. THE ABOVE NUMBERED CONTRACT/ORDER IS MODIFIED TO REFLECT THE ADMINISTRATIVE CHANGES (such as changes in paying office, appropriation date, etc.) SET FORTH IN ITEM 14, PURSUANT TO THE AUTHORITY OF FAR 43.103(B).

C. THIS SUPPLEMENTAL AGREEMENT IS ENTERED INTO PURSUANT TO AUTHORITY OF:

D. OTHER (Specify type of modification and authority)

E. IMPORTANT: Contractor is not, is required to sign this document and return copies to the issuing office.

14. DESCRIPTION OF AMENDMENT/MODIFICATION (Organized by UCF section headings, including solicitation/contract subject matter where feasible.)

10A. MOD. OF CONTRACT/ORDER NO.

2. AMENDMENT/MODIFICATION NO. 5. PROJECT NO.(If applicable)

6. ISSUED BY

3. EFFECTIVE DATE

02-Jul-2019

CODE

USA ENGINEER DISTRICT, SEATTLE

ATTN: CENWS-CT

4735 EAST MARGINAL WAY SOUTH, BLDG. 1202

SEATTLE WA 98134-2388

W912DW 7. ADMINISTERED BY (If other than item 6)

4. REQUISITION/PURCHASE REQ. NO.

CODE

See Item 6

FACILITY CODECODE

EMAIL:TEL:

W912DW19R0017

SECTION SF 30 BLOCK 14 CONTINUATION PAGE

SUMMARY OF CHANGES

SECTION SF 30 - BLOCK 14 CONTINUATION PAGE (SF 30)

The following have been added by full text:

AMENDMENT 0005

W912DW19R0017 Construct a Hot Refueling System at Gray Army Airfield (GAAF), Joint Base Lewis-McChord

(JBLM), WA

1. This amendment five (0005) provides for the following changes:

a. Price Schedule

b. Technical Specifications and Drawings:

1. 01 22 00.00 10

2. 26 28 01.00 10

3. 33 52 43.13

4. 33 52 80

5. 33 57 55

6. MS103

2. The proposal submittal time and date remains the same, 08 July 2019 at 2:00:00 p.m. LOCAL TIME. ProjNet will remain open until 03 July 2019 at 10:00:00 a.m. LOCAL Seattle Time.

3. The attached revised sections are to be replaced in their entirety. Specifications changes are generally identified, for convenience, either by strikeout for deletions, and double underlining of text for additions or a single dark line in the margin. All portions of the revised sections shall apply whether or not changes have been indicated.

4. NOTICE TO OFFERORS: Offerors must acknowledge receipt of this amendment by number and date on offer.

SECTION 00 10 00 - SOLICITATION

The following have been modified:

PRICE SCHEDULE

Refueling Facility Construction W912DW19R0017

DESC1905 R0005

Joint Base Lewis–McChord, WA

CONTRACT LINE ITEM PRICING SCHEDULE

BASIC ITEMS

ITEM

NO.

DESCRIPTION QUANTITY UNIT

UNIT

PRICE

AMOUNT

All work complete to provide new rotary wing aircraft direct fuel system including associated appurtenances.

1 Job. N/A $

All work complete to provide three

50,000 gallon F24 above ground fuel storage tanks including concrete slab and associated appurtenances.

1 Job. N/A $

All work complete to provide above and below ground fuel piping including cathodic protection and associated appurtenances.

1 Job. N/A $

All work complete to provide new

POL Operations Building including associated appurtenances.

1 Job. N/A $

All work complete to provide 1 truck fill stand and associated appurtenances.

1 Job. N/A $

All work complete to provide 2 truck offload points and associated appurtenances.

1 Job. N/A $

Demolition Work required for site.

Includes removal and disposal of unsuitable soil, trees, and all existing above and below ground facilities.

1 Job N/A $

All work complete to provide

Airfield Pavement. 1 Job. N/A $

All work complete for construction of all other concrete and asphalt, excluding Option Items below.

1 Job. N/A $

All work complete to provide one electrical generator.

1 Job. N/A $

All work complete for remaining site preparation, earthwork, utilities, service/secondaries, drainage facilities, spill containment, cybersecurity measures, and all other work not included in other Basic Items.

1 Job. N/A $

All work for As-Built drawings as specified in Section 01 78 00

CLOSEOUT SUBMITTALS from preparation to final approval.

Job

N/A

$20,000

All work for O&M manuals as specified in Section 01 78 23

OPERATIONS AND

MAINTENANCE MANUALS

from preparation to final approval.

$50,000

All work for Form DD 1354

Checklist and Equipment in Place

List as specified in Section 01 78

00 CLOSEOUT SUBMITTALS

from preparation to final approval.

$10,000

TOTAL AMOUNT BASIC ITEMS 0001 THROUGH 0014 $

OPTION ITEMS

All work complete to provide one additional 50,000 gallon F24 above ground fuel storage tank and associated appurtenances.

1 Job. N/A $

All work complete to provide one additional truck fillstand and associated appurtenances, including PCC pavement.

1 Job. N/A $

All work complete to provide one

5,000 gallon diesel above ground fuel storage tank including concrete slab, piping, dispenser, offload point, and associated appurtenances.

1 Job. N/A $

All work complete to provide one canopy at filter separator facilities including associated appurtenances.

1 Job. N/A $

All work complete to provide four individual canopies at load and offload facilities including associated appurtenances.

1 Job. N/A $

All work complete to provide one large canopy over load and offload facilities instead of four canopies as shown in CLIN Item

0019.

1 Job. N/A $

Additional amount for Disposal of

Petroleum Contaminated Soil in lieu of basic work for working with uncontaminated soil.

Cubic Yards

(CY)

CY

All work complete to provide

Automatic Tank Gauging System, excluding electrical connections, wiring, backboard and conduit included in CLIN Item 0002.

1 Job. N/A $

All work complete to provide

Automatic Tank Gauging System, excluding electrical connections, wiring, backboard and conduit included in CLIN Item 0015.

1 Job. N/A $

TOTAL AMOUNT OPTION ITEMS 0015 THROUGH 0023 $

TOTAL AMOUNT (ALL BASIC PLUS ALL OPTION ITEMS) $

NOTES:

1. The Government reserves the right to exercise Option 0022 and 0023 within 240 calendar days after notice to proceed. The Government reserves the right to exercise Option Item 0021 anytime while excavation of soil is being performed for this project. The Government reserves the right to exercise Option items 0015 through 0020 within 60 days after Notice to Proceed. Option Item 0023 will only be exercised if

Option Item 0015 is exercised. See FAR 52.217-5 Evaluation of Options.

2. Prices must be entered for all line items on the Pricing Schedule. Total amount prices submitted without prices for individual line items will not be evaluated. Additions will be subject to verification by the

Government. In case of variation between the lump-sum prices and the total amount, the lump-sum prices will be considered the price. In case of variation between the unit price(s) multiplied by the indicated quantity of units and the extension(s), the unit price(s) multiplied by the indicated quantity of units will be considered the price submitted.

3. 100% Design Projects cannot be altered, changed, or re-designed in any way. No alternate proposals will be accepted.

4. To better facilitate the receipt and proposal process, all modifications to proposals are to be submitted on copies of the latest Price Schedule as published in the solicitation or the latest amendment thereto. In lieu of indicating additions/deductions to line items, all Offerors should state their revised prices for each item.

5. Offerors must insert a price on all numbered items of the Price Schedule. Failure to do so may result in the offer being unacceptable.

6. The dollar amount established in Contract Line Item Nos. 0012, 0013, and 0014 shall not be revised by the Offerors.

7. Award of optional items will be made in accordance with FAR 52.217-7, “Option for Increased

Quantity- Separately Priced Line Item (MAR 1989)”, as found in Section 00 72 00.

(End of Summary of Changes)

FY19 GAAF Hot Ref uel i ng Faci l i t y - DESC 1905 19006 Joi nt Base Lewi s McChor d, WA

SECTI ON TABLE OF CONTENTS

DI VI SI ON 01 - GENERAL REQUI REMENTS

SECTI ON 01 22 00. 00 10

PRI CE AND PAYMENT PROCEDURES

08/15

PART 1 GENERAL

1. 1 SI NGLE JOB PAYMENT I TEMS

1. 1. 1 New Rot ar y Wi ng Ai r cr af t Di r ect Fuel Syst em ( BASI C - CLI N

0001)

1. 1. 1. 1 Payment

1. 1. 1. 2 Uni t of Measur e

1. 1. 2 50, 000 Gal l on F24 Above Gr ound Fuel St or age Tanks ( BASI C -

CLI N 0002)

1. 1. 2. 1 Payment

1. 1. 2. 2 Uni t of Measur e

1. 1. 3 Above and Bel ow Gr ound Fuel Pi pi ng ( BASI C - CLI N 0003)

1. 1. 3. 1 Payment

1. 1. 3. 2 Uni t of Measur e

1. 1. 4 New POL Oper at i ons Bui l di ng ( BASI C - CLI N 0004)

1. 1. 4. 1 Payment

1. 1. 4. 2 Uni t of Measur e

1. 1. 5 One Tr uck Fi l l s t and ( BASI C - CLI N 0005)

1. 1. 5. 1 Payment

1. 1. 5. 2 Uni t of Measur e

1. 1. 6 Two Tr uck Of f l oad Poi nt s ( BASI C - CLI N 0006)

1. 1. 6. 1 Payment

1. 1. 6. 2 Uni t of Measur e

1. 1. 7 Demol i t i on Wor k For Si t e ( BASI C - CLI N 0007)

1. 1. 7. 1 Payment

1. 1. 7. 2 Uni t of Measur e

1. 1. 8 Ai r f i el d Pavement ( BASI C - CLI N 0008)

1. 1. 8. 1 Payment

1. 1. 8. 2 Uni t of Measur e

1. 1. 9 Al l Ot her Concr et e and Asphal t Si t e Pavi ng ( BASI C - CLI N 0009)

1. 1. 9. 1 Payment

1. 1. 9. 2 Uni t of Measur e

1. 1. 10 El ect r i cal Gener at or ( BASI C - CLI N 0010)

1. 1. 10. 1 Payment

1. 1. 10. 2 Uni t of Measur e

1. 1. 11 Remai ni ng Si t e Wor k ( BASI C - CLI N 0011)

1. 1. 11. 1 Payment

1. 1. 11. 2 Uni t of Measur e

1. 1. 12 As- Bui l t s ( BASI C - CLI N 0012)

1. 1. 12. 1 Payment

1. 1. 12. 2 Uni t of Measur e

1. 1. 13 Oper at i on and Mai nt enance ( O&M) Manual ( BASI C - CLI N 0013)

1. 1. 13. 1 Payment

1. 1. 13. 2 Uni t of Measur e

1. 1. 14 For m DD 1354 Checkl i st and Equi pment i n Pl ace Li st ( BASI C -

CLI N 0014)

SECTI ON 01 22 00. 00 10 Page 1

W912DW19R0017 R0005

1. 1. 14. 1 Payment

1. 1. 14. 2 Uni t of Measur e

1. 1. 15 50, 000 Gal l on F24 Above Gr ound Fuel St or age Tank ( OPTI ON -

CLI N 0015)

1. 1. 15. 1 Payment

1. 1. 15. 2 Uni t of Measur e

1. 1. 16 One Tr uck Fi l l s t and ( OPTI ON - CLI N 0016)

1. 1. 16. 1 Payment

1. 1. 16. 2 Uni t of Measur e

1. 1. 17 5, 000 Gal l on Di esel Above Gr ound Fuel St or age Tank ( OPTI ON

- CLI N 0017)

1. 1. 17. 1 Payment

1. 1. 17. 2 Uni t of Measur e

1. 1. 18 Canopy At Fi l t er Separ at or Faci l i t i es ( OPTI ON - CLI N 0018)

1. 1. 18. 1 Payment

1. 1. 18. 2 Uni t of Measur e

1. 1. 19 Four Canopi es At Load And Of f l oad Faci l i t i es ( OPTI ON - CLI N

0019)

1. 1. 19. 1 Payment

1. 1. 19. 2 Uni t of Measur e

1. 1. 20 One Lar ge Canopy Over Load and Unl oad Faci l i t i es ( OPTI ON -

CLI N 0020)

1. 1. 20. 1 Payment

1. 1. 20. 2 Uni t of Measur e

1. 1. 21 Di sposal of Pet r ol eum Cont ami nat ed Soi l ( OPTI ON I TEM 0021)

1. 1. 21. 1 Uni t of Measur e

1. 1. 22 Aut omat i c Tank Gaugi ng Syst em ( OPTI ON - CLI N 0022)

1. 1. 22. 1 Payment

1. 1. 22. 2 Uni t of Measur e

1. 1. 23 Aut omat i c Tank Gaugi ng Syst em ( OPTI ON - CLI N 0023)

1. 1. 23. 1 Payment

1. 1. 23. 2 Uni t of Measur e

PART 2 PRODUCTS

PART 3 EXECUTI ON

3. 1 CONTRACT COST BREAKDOWN

3. 2 PROGRESS PAYMENT I NVOI CE

3. 3 COMPLI ANCE WI TH CONSTRUCTI ON WAGE RATE REQUI REMENTS

3. 3. 1 Cont r act or POC

3. 3. 2 Responsi bi l i t i es

3. 3. 3 Cer t i f i cat i on

- - End of Sect i on Tabl e of Cont ent s - -

SECTI ON 01 22 00. 00 10 Page 2

SECTI ON 01 22 00. 00 10

PRI CE AND PAYMENT PROCEDURES

08/15

PART 1 GENERAL

1. 1 SI NGLE JOB PAYMENT I TEMS

Payment i t ems f or t he wor k of t hi s cont r act f or whi ch cont r act j ob payment s wi l l be made ar e l i s t ed i n t he PRICING SCHEDULE and descr i bed bel ow. Al l cost s f or i t ems of wor k, whi ch ar e not speci f i cal l y ment i oned t o be i ncl uded i n a par t i cul ar j ob or uni t pr i ce payment i t em, ar e i ncl uded i n t he l i s t ed j ob i t em most c l osel y associ at ed wi t h t he wor k i nvol ved. The j ob pr i ce and payment made f or each i t em l i st ed const i t ut es f ul l compensat i on f or f ur ni shi ng al l pl ant , l abor , mat er i al s, and equi pment , and per f or mi ng any associ at ed Mobi l i zat i ond and Demobi l i zat i on, Cont r act or qual i t y cont r ol , envi r onment al pr ot ect i on, meet i ng saf et y r equi r ement s, t est s and r epor t s, and f or per f or mi ng al l wor k r equi r ed f or whi ch separ at e payment i s not ot her wi se pr ovi ded.

1. 1. 1 New Rot ar y Wi ng Ai r cr af t Di r ect Fuel Syst em ( BASI C - CLI N 0001)

1. 1. 1. 1 Payment

Payment wi l l be made f or al l wor k compl et e f or const r uct i on of t he new r ot ar y wi ng ai r cr af t di r ect f uel syst em and assoi cat ed appur t enances.

1. 1. 1. 2 Uni t of Measur e

Uni t of measur e: j ob.

1. 1. 2 50, 000 Gal l on F24 Above Gr ound Fuel St or age Tanks ( BASI C - CLI N 0002)

1. 1. 2. 1 Payment

Payment wi l l be made f or al l wor k compl et e f or const r uct i on of t hr ee 50, 000 gal l on F24 above gr ound f uel st or age t anks i ncl udi ng concr et e s l ab, di spenser , of f l oad poi nt and associ at ed appur t enances.

1. 1. 2. 2 Uni t of Measur e

Uni t of measur e: j ob.

1. 1. 3 Above and Bel ow Gr ound Fuel Pi pi ng ( BASI C - CLI N 0003)

1. 1. 3. 1 Payment

Payment wi l l be made f or al l wor k compl et e f or const r uct i on of t he above and bel ow gr ound f uel pi pi ng i ncl udi ng cat hodi c pr ot ect i on and associ at ed appurtenances.

1. 1. 3. 2 Uni t of Measur e

Uni t of measur e: j ob.

SECTI ON 01 22 00. 00 10 Page 3

1. 1. 4 New POL Oper at i ons Bui l di ng ( BASI C - CLI N 0004)

1. 1. 4. 1 Payment

Payment wi l l be made f or al l wor k compl et e f or const r uct i on of t he new POL Oper at i ons Bui l di ng i ncl udi ng associ at ed appur t enances out t o poi nt of 5 f eet out si de of bui l di ng. .

1. 1. 4. 2 Uni t of Measur e

Uni t of measur e: j ob.

1. 1. 5 One Tr uck Fi l l s t and ( BASI C - CLI N 0005)

1. 1. 5. 1 Payment

Payment wi l l be made f or al l wor k compl et e f or const r uct i on of 1 t r uck f i l l s t and and associ at ed appur t enances.

1. 1. 5. 2 Uni t of Measur e

Uni t of measur e: j ob.

1. 1. 6 Two Tr uck Of f l oad Poi nt s ( BASI C - CLI N 0006)

1. 1. 6. 1 Payment

Payment wi l l be made f or cost s associ at ed wi t h oper at i ons necessar y f or const r uct i on of t he 2 t r uck of f l oad poi nt s and associ at ed appur t enances. .

1. 1. 6. 2 Uni t of Measur e

Uni t of measur e: j ob.

1. 1. 7 Demol i t i on Wor k For Si t e ( BASI C - CLI N 0007)

1. 1. 7. 1 Payment

Payment wi l l be made f or al l wor k compl et e f or Demol i t i on Wor k r equi r ed f or s i t e. I ncl udes r emoval and di sposal of unsui t abl e soi l , t r ees, and al l exi st i ng above and bel ow gr ound f aci l i t i es.

1. 1. 7. 2 Uni t of Measur e

Uni t of measur e: j ob.

1. 1. 8 Ai r f i el d Pavement ( BASI C - CLI N 0008)

1. 1. 8. 1 Payment

Payment wi l l be made f or al l wor k compl et e f or const r uct i on of t he ai r f i el d pavement .

1. 1. 8. 2 Uni t of Measur e

Uni t of measur e: j ob.

SECTI ON 01 22 00. 00 10 Page 4

1. 1. 9 Al l Ot her Concr et e and Asphal t Si t e Pavi ng ( BASI C - CLI N 0009)

1. 1. 9. 1 Payment

Payment wi l l be made f or al l wor k compl et e f or const r uct i on of al l ot her concr et e and asphal t , excl udi ng Opt i on I t ems bel ow.

1. 1. 9. 2 Uni t of Measur e

Uni t of measur e: j ob.

1. 1. 10 El ect r i cal Gener at or ( BASI C - CLI N 0010)

1. 1. 10. 1 Payment

Payment wi l l be made f or al l wor k compl et e t o pr ovi de one el ect r i cal generator.

1. 1. 10. 2 Uni t of Measur e

Uni t of measur e: j ob.

1. 1. 11 Remai ni ng Si t e Wor k ( BASI C - CLI N 0011)

1. 1. 11. 1 Payment

Payment wi l l be made f or al l wor k compl et e f or const r uct i on of t he r emai ni ng si t e pr epar at i on, ear t hwor k, ut i l i t i es, gener at or , dr ai nage f aci l i t i es, spi l l cont ai nment , cyber secur i t y measur es, and al l ot her wor k not i ncl uded i n ot her Basi c I t ems.

1. 1. 11. 2 Uni t of Measur e

Uni t of measur e: j ob.

1. 1. 12 El ect r i cal Syst em I nst al l at on ( BASI C - CLI N 0012)

1. 1. 12. 1 Payment

Payment wi l l be made f or al l wor k compl et e f or const r uct i on of t he el ect r i cal syst em i nst al l at i on by ut i l i t y owner .

1. 1. 12. 2 Uni t of Measur e

Uni t of measur e: j ob.

1. 1. 12 As- Bui l t s ( BASI C - CLI N 00132)

1. 1. 12. 1 Payment

Payment wi l l be made at t he cont r act j ob pr i ce f or CLI N 00132, al l wor k f or As- Bui l t dr awi ngs as speci f i ed i n Sect i on 01 78 00 CLOSEOUT SUBMI TTALS f r om pr epar at i on t o f i nal appr oval . Payment shal l const i t ut e f ul l compensat i on f or t hi s i t em, compl et e.

1. 1. 12. 2 Uni t of Measur e

Uni t of measur e: j ob.

SECTI ON 01 22 00. 00 10 Page 5

1. 1. 13 Oper at i on and Mai nt enance ( O&M) Manual ( BASI C - CLI N 00143)

1. 1. 13. 1 Payment

Payment wi l l be made at t he cont r act j ob pr i ce f or CLI N 00143, al l wor k f or O&M manual s as speci f i ed i n Sect i on 01 78 23 OPERATI ONS AND MAI NTENANCE MANUALS f r om pr epar at i on t o f i nal appr oval . Payment shal l const i t ut e f ul l compensat i on f or t hi s i t em, compl et e.

1. 1. 13. 2 Uni t of Measur e

Uni t of measur e: j ob.

1. 1. 14 For m DD 1354 Checkl i st and Equi pment i n Pl ace Li st ( BASI C - CLI N 001 54)

1. 1. 14. 1 Payment

Payment wi l l be made at t he cont r act j ob pr i ce f or CLI N 00154, al l wor k f or For m DD 1354 Checkl i st and Equi pment i n Pl ace Li st as speci f i ed i n Sect i on 01 78 00 CLOSEOUT SUBMI TTALS f r om pr epar at i on t o f i nal appr oval .

Payment shal l const i t ut e f ul l compensat i on f or t hi s i t em, compl et e.

1. 1. 14. 2 Uni t of Measur e

Uni t of measur e: j ob.

1. 1. 15 50, 000 Gal l on F24 Above Gr ound Fuel St or age Tank ( OPTI ON - CLI N 0016 5)

1. 1. 15. 1 Payment

Payment wi l l be made f or al l wor k compl et e f or const r uct i on of one addi t i onal 50, 000 gal l on F24 above gr ound f uel st or age t ank and associ at ed appurtenances.

1. 1. 15. 2 Uni t of Measur e

Uni t of measur e: j ob.

1. 1. 16 One Tr uck Fi l l s t and ( OPTI ON - CLI N 00176)

1. 1. 16. 1 Payment

Payment wi l l be made f or al l wor k compl et e f or const r uct i on of one t r uck f i l l s t and and associ at ed appur t enances, i ncl udi ng PCC pavement .

1. 1. 16. 2 Uni t of Measur e

Uni t of measur e: j ob.

1. 1. 17 5, 000 Gal l on Di esel Above Gr ound Fuel St or age Tank ( OPTI ON - CLI N 00187)

1. 1. 17. 1 Payment

Payment wi l l be made f or al l wor k compl et e f or const r uct i on of t he 5, 000 gal l on di esel above gr ound f uel st or age t ank i ncl udi ng concr et e s l ab, di spenser , of f l oad poi nt , and associ at ed appur t enances.

SECTI ON 01 22 00. 00 10 Page 6

1. 1. 17. 2 Uni t of Measur e

Uni t of measur e: j ob.

1. 1. 18 Canopy At Fi l t er Separ at or Faci l i t i es ( OPTI ON - CLI N 00198)

1. 1. 18. 1 Payment

Payment wi l l be made f or al l wor k compl et e t o pr ovi de one canopy at f i l t er separ at or f aci l i t i es i ncl udi ng associ at ed appur t enances.

1. 1. 18. 2 Uni t of Measur e

Uni t of measur e: j ob.

1. 1. 19 Four Canopi es At Load And Of f l oad Faci l i t i es ( OPTI ON - CLI N 002019

1. 1. 19. 1 Payment

Payment wi l l be made f or al l wor k compl et e t o pr ovi de f our i ndi v i dual canopi es at l oad and of f l oad f aci l i t i es i ncl udi ng associ at ed appur t enances.

1. 1. 19. 2 Uni t of Measur e

Uni t of measur e: j ob.

1. 1. 20 One Lar ge Canopy Over Load and Unl oad Faci l i t i es ( OPTI ON - CLI N 0021 0)

1. 1. 20. 1 Payment

Payment wi l l be made f or al l wor k compl et e t o pr ovi de one l ar ge canopy over l oad and unl oad Faci l i t i es i nst ead of 4 separ at e canopi es i ncl uded i n OPTI ON I t em 002019.

1. 1. 20. 2 Uni t of Measur e

Uni t of measur e: j ob.

1. 1. 21 Di sposal of Pet r ol eum Cont ami nat ed Soi l ( OPTI ON I TEM 00221)

Addi t i onal cost f or Di sposal of Pet r ol eum Cont ami nat ed Soi l s i n l i eu of basi c wor k i t ems deal i ng wi t h uncont ami nat ed soi l . Payment i t ems f or t he wor k of t hi s cont r act on whi ch t he cont r act uni t pr i ce payment s wi l l be made ar e l i s t ed i n t he PRICING SCHEDULE and descr i bed bel ow. The uni t pr i ce and payment made f or each i t em l i st ed must const i t ut e f ul l compensat i on f or f ur ni shi ng al l pl ant , l abor , mat er i al s, and equi pment , and per f or mi ng any associ at ed Cont r act or qual i t y cont r ol , envi r onment al pr ot ect i on, meet i ng saf et y r equi r ement s, t est s and r epor t s, and f or per f or mi ng al l wor k r equi r ed f or t he uni t pr i ce i t em.

1. 1. 21. 1 Uni t of Measur e

Uni t of measur e: cubi c yar d.

SECTI ON 01 22 00. 00 10 Page 7

1. 1. 22 Aut omat i c Tank Gaugi ng Syst em ( OPTI ON - CLI N 00232)

1. 1. 22. 1 Payment

Payment wi l l be made f or al l wor k compl et e f or const r uct i on of t he Aut omat i c Tank Gaugi ng Syst em, excl udi ng el ect r i cal connect i ons, wi r i ng, backboar d and condui t i ncl uded i n BASI C CLI N I t em 0002.

1. 1. 22. 2 Uni t of Measur e

Uni t of measur e: j ob.

1. 1. 23 Aut omat i c Tank Gaugi ng Syst em ( OPTI ON - CLI N 00243)

1. 1. 23. 1 Payment

Payment wi l l be made f or al l wor k compl et e f or const r uct i on of t he Aut omat i c Tank Gaugi ng Syst em, excl udi ng el ect r i cal connect i ons, wi r i ng, backboar d and condui t i ncl uded i n OPTI ON CLI N I t em 0015.

1. 1. 23. 2 Uni t of Measur e

Uni t of measur e: j ob.

PART 2 PRODUCTS

Not Used

PART 3 EXECUTI ON

Not Used

3. 1 CONTRACT COST BREAKDOWN

The Cont r act or must f ur ni sh wi t hi n 30 days af t er t he dat e of Not i ce t o Pr oceed, and pr i or t o t he submi ssi on of i t s f i r st par t i al payment est i mat e, a br eakdown of i t s s i ngl e j ob pay i t em or i t ems whi ch wi l l be r evi ewed by t he Cont r act i ng Of f i cer as t o pr opr i et y of di st r i but i on of t he t ot al cost t o t he var i ous account s. Any unbal anced i t ems as bet ween ear l y and l at e payment i t ems or ot her di scr epanci es wi l l be r evi sed by t he Cont r act i ng Of f i cer t o agr ee wi t h a r easonabl e cost of t he wor k i ncl uded i n t he var i ous i t ems. Thi s cont r act cost br eakdown wi l l t hen be ut i l i zed as t he basi s f or pr ogr ess payment s t o t he Cont r act or .

3. 2 PROGRESS PAYMENT I NVOI CE

Request s f or payment shal l be submi t t ed i n accor dance wi t h Feder al Acqui s i t i on Regul at i ons ( FAR) Subpar t 32. 9, ent i t l ed " PROMPT PAYMENT" , and Cl auses 52. 232- 5 and 52. 232- 27, ent i t l ed " Payment s Under Fi xed- Pr i ce Const r uct i on Cont r act s" , and " Pr ompt Payment f or Const r uct i on Cont r act s" , r espect i vel y. I n addi t i on each r equest shal l be submi t t ed i n t he number of copi es and t o t he desi gnat ed bi l l i ng of f i ce as shown i n t he Cont r act .

When submi t t i ng payment r equest s, compl et e Bl ocks 1 t hr ough 12 of t he " PROGRESS PAYMENT I NVOI CE" For m as di r ect ed by t he Cont r act i ng Of f i cer ( pr ovi ded i n RMS) . The compl et ed f or m shal l t hen become t he cover document t o whi ch al l ot her suppor t dat a shal l be at t ached.

One addi t i onal copy of t he ent i r e r equest f or payment , t o i ncl ude t he

SECTI ON 01 22 00. 00 10 Page 8

" PROGRESS PAYMENT I NVOI CE" cover document , shal l be f or war ded t o a separ at e addr ess as desi gnat ed by t he Cont r act i ng Of f i cer .

Submi t wi t h each pay r equest , a l i s t of subcont r act or s t hat have wor ked dur i ng t hat pay per i od. The l i s t i ng shal l be br oken down i nt o weeks, i dent i f y i ng each subcont r act or t hat has wor ked dur i ng a par t i cul ar week, and i ndi cat e t he t ot al number of empl oyees t hat have wor ked on si t e f or each subcont r act or f or each week. Al so i ndi cat e t he t ot al number of empl oyees f or on- si t e st af f f or each week.

3. 3 COMPLI ANCE WI TH CONSTRUCTI ON WAGE RATE REQUI REMENTS

3. 3. 1 Cont r act or POC

Wi t hi n 14 days af t er awar d of t he cont r act , desi gnat e a poi nt of cont act ( POC) who wi l l be r esponsi bl e f or t he Const r uct i on Wage Rat es Requi r ement s Pr ogr am f or t he Cont r act or and al l subcont r act or s under t hi s cont r act as r equi r ed by t he Cont r act Cl auses and FAR 52. 222.

3. 3. 2 Responsibilities

The desi gnat ed Cont r act or POC shal l be r esponsi bl e f or Const r uct i on Wage Rat es Requi r ement s Pr ogr am act i v i t i es i ncl udi ng, but not l i mi t ed t o:

a. Document at i on and r ecor d keepi ng;

b. Submi t t al and accur acy of cer t i f i ed payr ol l s;

c. Submi t t al of r equi r ed l abor f or ms i ncl udi ng r equest s f or addi t i onal c l assi f i cat i ons and r at es, St at ement s and Acknowl edgement , et c. ;

d. Post i ng of t he wage det er mi nat i on, appr oved addi t i onal c l assi f i cat i ons and r at es, l abor and EEO post er s;

e. Coor di nat i on wi t h t he Cont r act i ng Of f i cer ' s Labor Pr ogr am POC.

Pr i or t o submi t t al t o t he Gover nment , payr ol l s shal l be r evi ewed f or compl i ance t o al l appl i cabl e l abor st andar ds, t o i ncl ude, but not be l i mi t ed t o t he f ol l owi ng i t ems: cor r ect wage r at es, cor r ect over t i me cl assi f i cat i on and pay, mi scl assi f i cat i on of wor ker s f or wor k act ual l y per f or med, appr ent i ce t o j our neyman r at i os, and r egi st r at i on of appr ent i ce. Cor r ect i ve act i ons shal l be t aken as necessar y t o ensur e Cont r act or compl i ance wi t h appl i cabl e cont r act and FAR cl auses.

3. 3. 3 Certification

The Cont r act or POC shal l pr ovi de a s i gned cer t i f i cat i on st at i ng t he f ol l owi ng: " I cer t i f y t hat t he submi t t ed i t ems bei ng f or war ded have been r evi ewed i n det ai l and ar e cor r ect and i n st r i ct conf or mance wi t h t he Labor St andar ds of t he cont r act except as ot her wi se st at ed. "

- - End of Sect i on - -

SECTI ON 01 22 00. 00 10 Page 9

FY19 GAAF REFUELING FACILITY CONSTRUCTION PROJECT NO. DESC 1905 19006

Joint Base Lewis McChord, WA

SECTION TABLE OF CONTENTS

DIVISION 26 - ELECTRICAL

SECTION 26 28 01.00 10

COORDINATED POWER SYSTEM PROTECTION

10/07

PART 1 GENERAL

1.1 REFERENCES

1.2 SYSTEM DESCRIPTION

1.3 SUBMITTALS

1.4 QUALITY ASSURANCE

1.4.1 System Coordinator

1.4.2 System Installer

1.5 DELIVERY, STORAGE, AND HANDLING

1.6 PROJECT/SITE CONDITIONS

PART 2 PRODUCTS

2.1 STANDARD PRODUCT

2.2 NAMEPLATES

2.3 CORROSION PROTECTION

2.4 MOTOR CONTROLS AND MOTOR CONTROL CENTERS

2.4.1 Motor Starters

2.4.2 Thermal-Overload Protection

2.4.3 Low-Voltage Motor Overload Relays

2.4.3.1 General

2.4.3.2 Construction

2.4.3.3 Ratings

2.4.4 Automatic Control Devices

2.4.4.1 Direct Control

2.4.4.2 Pilot-Relay Control

2.4.4.3 Manual/Automatic Selection

2.4.5 Motor Control Centers

2.5 LOW-VOLTAGE FUSES

2.5.1 General

2.5.2 Cartridge Fuses; Noncurrent-Limiting Type

2.5.3 Cartridge Fuses; Current-Limiting Type

2.5.3.1 Continuous Current Ratings (600 amperes and smaller)

2.5.3.2 Continuous Current Ratings (greater than 600 amperes)

2.5.3.3 Motor and Transformer Circuit Fuses

2.6 NOT USED

2.7 MOTOR SHORT-CIRCUIT PROTECTOR (MSCP)

2.7.1 General

2.7.2 Construction

2.7.3 Ratings

2.8 MOLDED-CASE CIRCUIT BREAKERS

2.8.1 General

2.8.2 Construction

2.8.3 Ratings

2.8.4 Cascade System Ratings

2.8.5 Thermal-Magnetic Trip Elements

SECTION 26 28 01.00 10 Page 1

2.8.6 Solid-State Trip Elements

2.8.7 Current-Limiting Circuit Breakers

2.8.8 SWD Circuit Breakers

2.8.9 HACR Circuit Breakers

2.8.10 Motor Circuit Protectors (MCP)

2.9 INSTRUMENT TRANSFORMERS

2.9.1 General

2.9.2 Current Transformers

2.9.2.1 Voltage Transformers

2.10 COORDINATED POWER SYSTEM PROTECTION

2.10.1 Scope of Analyses

2.10.2 Determination of Facts

2.10.3 Single Line Diagram

2.10.4 Fault Current Analysis

2.10.4.1 Method

2.10.4.2 Data

2.10.4.3 Fault Current Availability

2.10.5 Coordination Study

2.10.6 Study report

PART 3 EXECUTION

3.1 EXAMINATION

3.2 INSTALLATION

3.3 FIELD TESTING

3.3.1 General

3.3.2 Safety

3.3.3 Molded-Case Circuit Breakers

3.3.4 Power Circuit Breakers

3.3.4.1 General

-- End of Section Table of Contents --

SECTION 26 28 01.00 10 Page 2

SECTION 26 28 01.00 10

COORDINATED POWER SYSTEM PROTECTION

10/07

PART 1 GENERAL

1.1 REFERENCES

The publications listed below form a part of this specification to the extent referenced. The publications are referred to within the text by the basic designation only.

INSTITUTE OF ELECTRICAL AND ELECTRONICS ENGINEERS (IEEE)

IEEE 242 (2001; Errata 2003) Recommended Practice for Protection and Coordination of Industrial and Commercial Power Systems - Buff Book

IEEE 399 (1997) Brown Book IEEE Recommended Practice for Power Systems Analysis

IEEE C2 (2017; Errata 1-2 2017; INT 1 2017) National Electrical Safety Code

IEEE C57.13 (2016) Requirements for Instrument Transformers

NATIONAL ELECTRICAL MANUFACTURERS ASSOCIATION (NEMA)

NEMA FU 1 (2012) Low Voltage Cartridge Fuses

NEMA ICS 1 (2000; R 2015) Standard for Industrial Control and Systems: General Requirements

NEMA ICS 2 (2000; R 2005; Errata 2008) Industrial Control and Systems Controllers, Contactors, and Overload Relays Rated 600 V

NEMA ICS 3 (2005; R 2010) Medium-Voltage Controllers Rated 2001 to 7200 V AC

NEMA ICS 6 (1993; R 2016) Industrial Control and Systems: Enclosures

NEMA/ANSI C12.11 (2007) Instrument Transformers for Revenue Metering, 10 kV BIL through 350 kV BIL (0.6 kV NSV through 69 kV NSV)

NATIONAL FIRE PROTECTION ASSOCIATION (NFPA)

NFPA 70 (2017; ERTA 1-2 2017; TIA 17-1; TIA 17-2;

TIA 17-3; TIA 17-4; TIA 17-5; TIA 17-6;

TIA 17-7; TIA 17-8; TIA 17-9; TIA 17-10;

TIA 17-11; TIA 17-12; TIA 17-13; TIA

SECTION 26 28 01.00 10 Page 3

17-14) National Electrical Code

U.S. DEPARTMENT OF DEFENSE (DOD)

UFC 3-310-04 (2013; with Change 1) Seismic Design of Buildings

UNDERWRITERS LABORATORIES (UL)

UL 1203 (2013; Reprint Apr 2015) UL Standard for Safety Explosion-Proof and Dust-Ignition-Proof Electrical Equipment for Use in Hazardous (Classified) Locations

UL 198M (2003; Reprint Feb 2013) Standard for Mine-Duty Fuses

UL 486E (2009; Reprint May 2013) Equipment Wiring Terminals for Use with Aluminum and/or Copper Conductors

UL 489 (2016) UL Standard for Safety Molded-Case Circuit Breakers, Molded-Case Switches and Circuit-Breaker Enclosures

UL 508 (2018) UL Standard for Safety Industrial Control Equipment

UL 845 (2005; Reprint Jul 2011) Motor Control Centers

1.2 SYSTEM DESCRIPTION

The power system covered by this specification consists of: New primary radial, with a transformer feeding motor control center, and panelboards..

1.3 SUBMITTALS

Government approval is required for submittals with a "G" designation;

submittals not having a "G" designation are for Contractor Quality Control approval. Submit the following in accordance with Section 01 33 00

SUBMITTAL PROCEDURES:

SD-03 Product Data

Fault Current Analysis Protective Device Coordination Study Equipment System Coordinator

Installation

SD-06 Test Reports

Field Testing

SD-07 Certificates

Devices and Equipment

SECTION 26 28 01.00 10 Page 4

1.4 QUALITY ASSURANCE

1.4.1 System Coordinator

System coordination, recommended ratings and settings of protective devices, and design analysis shall be accomplished by a registered professional electrical power engineer with a minimum of 3 years of current experience in the coordination of electrical power systems. Submit verification of experience and license number, of a registered Professional Engineer as specified above. Experience data shall include at least five references for work of a magnitude comparable to this contract, including points of contact, addresses and telephone numbers.

1.4.2 System Installer

Calibration, testing, adjustment, and placing into service of the protective devices shall be accomplished by a manufacturer's product field service engineer or independent testing company with a minimum of two years of current product experience in protective devices.

1.5 DELIVERY, STORAGE, AND HANDLING

Devices and equipment shall be visually inspected when received and prior to acceptance from conveyance. Protect stored items from the environment in accordance with the manufacturer's published instructions. Damaged items shall be replaced.

1.6 PROJECT/SITE CONDITIONS

Submit certificates attesting that all devices or equipment meet the requirements of the contract documents. Devices and equipment furnished under this section shall be suitable for the following site conditions.

Seismic details shall conform to UFC 3-310-04 and Sections 13 48 00 SEISMIC

PROTECTION FOR MISCELLANEOUS EQUIPMENT, 13 48 00.00 10 SEISMIC PROTECTION

FOR MECHANICAL EQUIPMENT AND 26 05 48.00 10 SEISMIC PROTECTION FOR

ELECTRICAL EQUIPMENT .

Altitude 240'

Average Temperature 54 degrees F

Frequency 60 hz

Hazardous Classification As indicated on drawings

PART 2 PRODUCTS

2.1 STANDARD PRODUCT

Provide protective devices and equipment which are the standard product of a manufacturer regularly engaged in the manufacture of the product and that essentially duplicate items that have been in satisfactory utility type use for at least two years prior to bid opening. Submit data consisting of manufacturer's time-current characteristic curves for individual protective devices, recommended settings of adjustable protective devices, and recommended ratings of non-adjustable protective devices.

SECTION 26 28 01.00 10 Page 5

2.2 NAMEPLATES

Provide nameplates to identify all protective devices and equipment.

Nameplate information shall be in accordance with UL 489.

2.3 CORROSION PROTECTION

Metallic materials shall be protected against corrosion. Ferrous metal hardware shall be zinc or chrome-plated.

2.4 MOTOR CONTROLS AND MOTOR CONTROL CENTERS

Motor controls and motor control centers shall be in accordance with NEMA ICS 1, NEMA ICS 2, NEMA ICS 3 and NEMA ICS 6, and UL 508and UL 845.

2.4.1 Motor Starters

Provide combination starters with circuit breakers and as indicated.

2.4.2 Thermal-Overload Protection

Each motor of 1/8 hp or larger shall be provided with thermal-overload protection. Polyphase motors shall have overload protection in each ungrounded conductor. The overload-protection device shall be provided either integral with the motor or controller, or shall be mounted in a separate enclosure. Unless otherwise specified, the protective device shall be of the manually reset type. Single or double pole tumbler switches specifically designed for alternating-current operation only may be used as manual controllers for single-phase motors having a current rating not in excess of 80 percent of the switch rating.

2.4.3 Low-Voltage Motor Overload Relays

2.4.3.1 General

Thermal overload relays shall conform to NEMA ICS 2 and UL 508. Overload protection shall be provided either integral with the motor or controller, and shall be rated in accordance with the requirements of NFPA 70.

2.4.3.2 Construction

Manual reset type thermal relays shall be melting alloy construction.

Automatic reset type relays shall be bimetallic construction. Magnetic current relays shall consist of a contact mechanism and a dash pot mounted on a common frame.

2.4.3.3 Ratings

Voltage ratings shall be not less than the applicable circuit voltage.

Trip current ratings shall be established by selection of the replaceable overload device and shall not be adjustable. Where the controller is remotely-located or difficult to reach, an automatic reset, non-compensated overload relay shall be provided. Manual reset overload relays shall be provided otherwise, and at all locations where automatic starting is provided. Where the motor is located in a constant ambient temperature, and the thermal device is located in an ambient temperature that regularly varies by more than 14 degrees F, an ambient temperature-compensated overload relay shall be provided.

SECTION 26 28 01.00 10 Page 6

2.4.4 Automatic Control Devices

2.4.4.1 Direct Control

Automatic control devices (such as thermostats, float or pressure switches) which control the starting and stopping of motors directly shall be designed for that purpose and have an adequate horsepower rating.

2.4.4.2 Pilot-Relay Control

Where the automatic-control device does not have such a rating, a magnetic starter shall be used, with the automatic-control device actuating the pilot-control circuit.

2.4.4.3 Manual/Automatic Selection

a. Where combination manual and automatic control is specified and the automatic-control device actuates the pilot control circuit of a magnetic starter, the magnetic starter shall be provided with a three-position selector switch marked MANUAL-OFF-AUTOMATIC.

b. Connections to the selector switch shall only allow the normal automatic regulatory control devices to be bypassed when the switch is in the Manual position; all safety control devices, such as low-or high-pressure cutouts, high-temperature cutouts, and motor-overload protective devices, shall be connected in the motor-control circuit in both the Manual and the Automatic positions of the selector switch.

Control circuit connections to any MANUAL-OFF-AUTOMATIC switch or to more than one automatic regulatory control device shall be made in accordance with wiring diagram approved by the contracting Officer unless such diagram is included on the drawings. All controls shall be 120 volts or less unless otherwise indicated.

2.4.5 Motor Control Centers

Control centers shall be indoor type and shall contain combination starters and other equipment as indicated. Control centers shall be NEMA ICS 2, Class I, Type B. Each control center shall be mounted on floor sills or mounting channels. Each circuit shall have a suitable metal or laminated plastic nameplate with white cut letters. Motor control centers shall be provided with a full-length ground bus bar.

2.5 LOW-VOLTAGE FUSES

2.5.1 General

Low-voltage fuses shall conform to NEMA FU 1. Time delay and nontime delay options shall be as shown. Equipment provided under this contract shall be provided with a complete set of properly rated fuses when the equipment manufacturer utilizes fuses in the manufacture of the equipment, or if current-limiting fuses are required to be installed to limit the ampere-interrupting capacity of circuit breakers or equipment to less than the maximum available fault current at the location of the equipment to be installed. Fuses shall have a voltage rating of not less than the phase-to-phase circuit voltage, and shall have the time-current characteristics requires for effective power system coordination.

SECTION 26 28 01.00 10 Page 7

2.5.2 Cartridge Fuses; Noncurrent-Limiting Type

Cartridge fuses of the noncurrent-limiting type shall be Class H, nonrenewable, dual element, time lag type and shall have interrupting capacity of 10,000 amperes. Class H Fuses shall conform to UL 198M. At 500 percent current, cartridge fuses shall not blow in less than 10 seconds. Cartridge fuses shall be used for circuits rated in excess of 30 amperes, 125 volts, except where current-limiting fuses are indicated.

2.5.3 Cartridge Fuses; Current-Limiting Type

Cartridge fuses, current-limiting type, Class G J K L RK1 T CC shall have tested interrupting capacity not less than 100,000 amperes. Fuse holders shall be the type that will reject Class H fuses.

a. Class G J L CC fuses shall conform to UL 198M.

b. Class K fuses shall conform to UL 198M.

c. Class R fuses shall conform to UL 198M.

d. Class T fuses shall conform to UL 198M.

2.5.3.1 Continuous Current Ratings (600 amperes and smaller)

Service entrance and feeder circuit fuses (600 amperes and smaller) shall be Class RK1 or J, current-limiting, time-delay with 200,000 amperes interrupting capacity.

2.5.3.2 Continuous Current Ratings (greater than 600 amperes)

Service entrance and feeder circuit fuses (greater than 600 amperes) shall be Class L, current-limiting, time-delay with 200,000 amperes interrupting capacity.

2.5.3.3 Motor and Transformer Circuit Fuses

Motor, motor controller, transformer, and inductive circuit fuses shall be Class RK1 or RK5, current-limiting, time-delay with 200,000 amperes interrupting capacity.

2.6 NOT USEDMEDIUM-VOLTAGE AND HIGH-VOLTAGE FUSES

2.6.1 General

Medium-voltage and high-voltage fuses shall be distribution fuse cutouts or power fuses, E-rated, C-rated, or R-rated current-limiting fuses as shown.

2.6.2 Construction

Units shall be suitable for outdoor use. Fuses shall have integral blown-fuse indicators. All ratings shall be clearly visible.

2.6.3 Ratings

Voltage ratings shall be not less than the applicable circuit voltage.

Continuous-current ratings shall be as shown.

SECTION 26 28 01.00 10 Page 8

2.6.3.1 Fuse Cutouts

Medium-voltage fuses and cutouts shall be of the as required type construction rated 15 kV and of the extra-heavy -duty type. Open-link cutouts are not acceptable. Fuses shall be either indicating or dropout type. Fuse ratings shall be as indicated. Fuses cutouts shall be equipped with mounting brackets suitable for the indicated installations.

2.6.3.2 Power Fuses

Current-limiting power fuses shall have ratings in accordance with IEEE C37.46 and as follows:

Nominal voltage 4.8 kV

Rated maximum voltage 15 kV

Maximum symmetrical interrupting capacity

25-50 kA

Rated continuous current as indicated

BIL 95 kV, crest

2.6.3.3 E-Rated, Current-Limiting Power Fuses

E-rated, current-limiting, power fuses shall conform to IEEE C37.46.

2.6.3.4 C-Rated, Current-Limiting Fuses

C-rated, current-limiting, power fuses shall open in 1000 seconds at currents between 170 and 240 percent of the C rating.

2.6.3.5 R-Rated, Current-Limiting Fuses

R-rated, current-limiting, fuses shall be used with medium-voltage motor controllers only. R-rated fuses shall conform to IEEE C37.46.

2.7 MOTOR SHORT-CIRCUIT PROTECTOR (MSCP)

2.7.1 General

Motor short-circuit protectors shall conform to UL 508 and shall be provided as shown. Protectors shall be used only as part of a combination motor controller which provides coordinated motor branch-circuit overload and short-circuit protection, and shall be rated in accordance with the requirements of NFPA 70.

2.7.2 Construction

Motor short-circuit protector bodies shall be constructed of high temperature, dimensionally stable, long life, nonhygroscopic materials.

Protectors shall fit special MSCP mounting clips and shall not be interchangeable with any commercially available fuses. Protectors shall have 100 percent one-way interchangeability within the A-Y letter designations. All ratings shall be clearly visible.

SECTION 26 28 01.00 10 Page 9

2.7.3 Ratings

Voltage ratings shall be not less than the applicable circuit voltage.

Letter designations shall be A through Y for motor controller Sizes 0, 1, 2, 3, 4, and 5, with 100,000 amperes interrupting capacity rating. Letter designations shall correspond to controller sizes as follows:

CONTROLLER SIZE MSCP DESIGNATION

NEMA 0 A-N

NEMA 1 A-P

NEMA 2 A-S

NEMA 3 A-U

NEMA 4 A-W

NEMA 5 A-Y

2.8 MOLDED-CASE CIRCUIT BREAKERS

2.8.1 General

Molded-case circuit breakers shall conform to UL 489 and UL 489. Circuit breakers may be installed in panelboards, switchboards, enclosures, motor control centers, or combination motor controllers. Circuit breakers and circuit breaker enclosures located in hazardous (classified) areas shall conform to UL 1203.

2.8.2 Construction

Molded-case circuit breakers shall be assembled as an integral unit in a supporting and enclosing housing of glass reinforced insulating material providing high dielectric strength. Circuit breakers shall be suitable for mounting and operating in any position. Lugs shall be listed for copper conductors only in accordance with UL 486E. Single-pole circuit breakers shall be full module size with not more than one pole per module.

Multi-pole circuit breakers shall be of the common-trip type having a single operating handle such that an overload or short circuit on any one pole will result in all poles opening simultaneously. Sizes of 100 amperes or less may consist of single-pole breakers permanently factory assembled into a multi-pole unit having an internal, mechanical, nontamperable common-trip mechanism and external handle ties. All circuit breakers shall have a quick-make, quick-break overcenter toggle-type mechanism, and the handle mechanism shall be trip-free to prevent holding the contacts closed against a short-circuit or sustained overload. All circuit breaker handles shall assume a position between "ON" and "OFF" when tripped automatically.

All ratings shall be clearly visible.

2.8.3 Ratings

Voltage ratings shall be not less than the applicable circuit voltage. The interrupting rating of the circuit breakers shall be at least equal to the available short-circuit current at the line terminals of the circuit

SECTION 26 28 01.00 10 Page 10 breaker and correspond to the UL listed integrated short-circuit current rating specified for the panelboards and switchboards. Molded-case circuit breakers shall have nominal voltage ratings, maximum continuous-current ratings, and maximum short-circuit interrupting ratings in accordance with UL 489. Ratings shall be coordinated with system X/R ratio.

2.8.4 Cascade System Ratings

Circuit breakers used in series combinations shall be in accordance with UL 489. Equipment, such as switchboards and panelboards, which house series-connected circuit breakers shall be clearly marked accordingly.

Series combinations shall be listed in the UL Recognized Component Directory under "Circuit Breakers-Series Connected."

2.8.5 Thermal-Magnetic Trip Elements

Thermal magnetic circuit breakers shall be provided as shown. Automatic operation shall be obtained by means of thermal-magnetic tripping devices located in each pole providing inverse time delay and instantaneous circuit protection. The instantaneous magnetic trip shall be adjustable and accessible from the front of all circuit breakers on frame sizes above 150 amperes.

2.8.6 Solid-State Trip Elements

Solid-state circuit breakers shall be provided as shown. All electronics shall be self-contained and require no external relaying, power supply, or accessories. Printed circuit cards shall be treated to resist moisture absorption, fungus growth, and signal leakage. All electronics shall be housed in an enclosure which provides protection against arcs, magnetic interference, dust, and other contaminants. Solid-state sensing shall measure true RMS current with error less than one percent on systems with distortions through the 13th harmonic. Peak or average actuating devices are not acceptable. Current sensors shall be toroidal construction, encased in a plastic housing filled with epoxy to protect against damage and moisture and shall be integrally mounted on the breaker. Where indicated on the drawings, circuit breaker frames shall be rated for 100 percent continuous duty. Circuit breakers shall have tripping features as shown on the drawings and as described below:

a. Long-time current pick-up, adjustable from 50 percent to 100 percent of continuous current rating.

b. Adjustable long-time delay.

c. Short-time current pick-up, adjustable from 1.5 to 9 times long-time current setting.

d. Adjustable short-time delay.

e. Short-time I square times t switch.

f. Instantaneous current pick-up, adjustable from 1.5 to 9 times long-time current setting.

g. Ground-fault pick-up, adjustable from 20 percent to 60 percent of sensor rating, but in no case greater than 1200 amperes. Sensing of ground-fault current at the main bonding jumper or ground strap shall not be permitted.

SECTION 26 28 01.00 10 Page 11

h. Adjustable ground-fault delay.

i. Ground-fault I square times t switch.

j. trip indicators shall be provided.

2.8.7 Current-Limiting Circuit Breakers

Current-limiting circuit breakers shall be provided as shown.

Current-limiting circuit breakers shall limit the let-through I square times t to a value less than the I square times t of one-half cycle of the symmetrical short-circuit current waveform. On fault currents below the threshold of limitation, breakers shall provide conventional overload and short-circuit protection. Integrally-fused circuit breakers shall not be used.

2.8.8 SWD Circuit Breakers

Circuit breakers rated 15 amperes or 20 amperes and intended to switch 277 volts or less fluorescent lighting loads shall be marked "SWD."

2.8.9 HACR Circuit Breakers

Circuit breakers 60 amperes or below, 240 volts, 1-pole or 2-pole, intended to protect multi-motor and combination-load installations involved in heating, air conditioning, and refrigerating equipment shall be…

This is the start of the file's text. The full file is on GovTribe.