23_00_00_Final.pdf

PDF 187 KB Posted

Attached to
Eisenhower Barracks, West Point N. Y. Federal contract opportunity
Solicitation number
W912DS-17-B-0005
Issued by
Department of the Army Corps of Engineers Engineering District New York

About this file

23 00 00

View the file

Other files for this federal contract opportunity

Other files attached to Eisenhower Barracks, West Point N. Y., newest first.
File Type Posted
Bid_Abstract.pdf PDF
Amendment_0006.pdf PDF
08_71_00_Final.pdf PDF
Amendment_05_All_Revised_Drawings.pdf PDF
W912DS-17-B-0005-Amendment_0005.pdf PDF
Amendment_0004.pdf PDF
Site_Vist_Sign-In_Sheet.pdf PDF
Amendment_0003.pdf PDF
Amendment__0002.pdf PDF
Amendment_0001.pdf PDF
W912DS-17-B-0005_Specifications.pdf PDF
Set_3_Eisenhower_Bid_Set_-_Stamped-3.pdf PDF
Set_4_Eisenhower_Bid_Set_-_Stamped-4.pdf PDF
Set_2_Eisenhower_Bid_Set_-_Stamped-2.pdf PDF
Set_5_Eisenhower_Bid_Set_-_Stamped-5.pdf PDF
Set_1_Eisenhower_Bid_Set_-_Stamped-1.pdf PDF
W912DS-17-B-0005.pdf PDF
Show all 17

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Repai r t o Ei senhower Bar r acks 012111

SECTI ON 23 00 00

AI R SUPPLY, DI STRI BUTI ON, VENTI LATI ON, AND EXHAUST SYSTEMS

08/10

AMENDMENT 05

PART 1 GENERAL

1. 1 REFERENCES

The publ i cat i ons l i s t ed bel ow f or m a par t of t hi s speci f i cat i on t o t he ext ent r ef er enced. The publ i cat i ons ar e r ef er r ed t o wi t hi n t he t ext by t he basi c desi gnat i on onl y.

AI R MOVEMENT AND CONTROL ASSOCI ATI ON I NTERNATI ONAL ( AMCA)

AMCA 201 ( 2002; R 2011) Fans and Syst ems

AMCA 210 ( 2007) Labor at or y Met hods of Test i ng Fans f or Aer odynami c Per f or mance Rat i ng

AMCA 300 ( 2014) Rever ber ant Room Met hod f or Sound Test i ng of Fans

AMCA 301 ( 2014) Met hods f or Cal cul at i ng Fan Sound Rat i ngs f r om Labor at or y Test Dat a

AMCA 500- D ( 2012) Labor at or y Met hods of Test i ng Damper s f or Rat i ng

AI R- CONDI TI ONI NG, HEATI NG AND REFRI GERATI ON I NSTI TUTE ( AHRI )

AHRI 350 ( 2008) Sound Rat i ng of Non- Duct ed I ndoor Ai r - Condi t i oni ng Equi pment

AHRI 410 ( 2001; Addendum 1 2002; Addendum 2 2005;

Addendum 3 2011) For ced- Ci r cul at i on Ai r - Cool i ng and Ai r - Heat i ng Coi l s

AHRI 430 ( 2009) Cent r al - St at i on Ai r - Handl i ng Uni t s

AHRI 440 ( 2008) Room Fan- Coi l s and Uni t Vent i l at or s

AHRI Gui del i ne D ( 1996) Appl i cat i on and I nst al l at i on of Cent r al St at i on Ai r - Handl i ng Uni t s

AMERI CAN BEARI NG MANUFACTURERS ASSOCI ATI ON ( ABMA)

ABMA 11 ( 2014) Load Rat i ngs and Fat i gue Li f e f or Rol l er Bear i ngs

ABMA 9 ( 2015) Load Rat i ngs and Fat i gue Li f e f or Bal l Bear i ngs

SECTI ON 23 00 00 Page 1

AMERI CAN SOCI ETY OF HEATI NG, REFRI GERATI NG AND AI R- CONDI TI ONI NG

ENGI NEERS ( ASHRAE)

ASHRAE 52. 2 ( 2012; Er r at a 2013; I NT 1 2014; ADD A, B, AND D SUPP 2015; I NT 3 2015; Er r at a 2 2015; ADD C 2015) Met hod of Test i ng Gener al Vent i l at i on Ai r - Cl eani ng Devi ces f or Removal Ef f i c i ency by Par t i c l e Si ze

ASHRAE 62. 1 ( 2010) Vent i l at i on f or Accept abl e I ndoor Ai r Qual i t y

ASHRAE 70 ( 2006; R 2011) Met hod of Test i ng f or Rat i ng t he Per f or mance of Ai r Out l et s and Inlets

ASHRAE 84 ( 2013; Addenda A 2013) Met hod of Test i ng Ai r - t o- Ai r Heat Exchanger s

ASHRAE 90. 1 - I P ( 2013) Ener gy St andar d f or Bui l di ngs Except Low- Ri se Resi dent i al Bui l di ngs

ASME I NTERNATI ONAL ( ASME)

ASME A13. 1 ( 2015) Scheme f or t he I dent i f i cat i on of Pi pi ng Syst ems

ASTM I NTERNATI ONAL ( ASTM)

ASTM A123/ A123M ( 2013) St andar d Speci f i cat i on f or Zi nc ( Hot - Di p Gal vani zed) Coat i ngs on I r on and St eel Pr oduct s

ASTM A167 ( 2011) St andar d Speci f i cat i on f or St ai nl ess and Heat - Resi st i ng Chr omi um- Ni ckel St eel Pl at e, Sheet , and Strip

ASTM A53/ A53M ( 2012) St andar d Speci f i cat i on f or Pi pe, St eel , Bl ack and Hot - Di pped, Zi nc- Coat ed, Wel ded and Seaml ess

ASTM A924/ A924M ( 2014) St andar d Speci f i cat i on f or Gener al Requi r ement s f or St eel Sheet , Met al l i c- Coat ed by t he Hot - Di p Pr ocess

ASTM B117 ( 2016) St andar d Pr act i ce f or Oper at i ng Sal t Spr ay ( Fog) Appar at us

ASTM B152/ B152M ( 2013) St andar d Speci f i cat i on f or Copper Sheet , St r i p, Pl at e, and Rol l ed Bar

ASTM B209 ( 2014) St andar d Speci f i cat i on f or Al umi num and Al umi num- Al l oy Sheet and Pl at e

ASTM B280 ( 2013) St andar d Speci f i cat i on f or Seaml ess Copper Tube f or Ai r Condi t i oni ng and Ref r i ger at i on Fi el d Ser vi ce

SECTI ON 23 00 00 Page 2

ASTM B766 ( 1986; R 2015) St andar d Speci f i cat i on f or El ect r odeposi t ed Coat i ngs of Cadmi um

ASTM C1071 ( 2012) St andar d Speci f i cat i on f or Fi br ous Gl ass Duct Li ni ng I nsul at i on ( Ther mal and Sound Absor bi ng Mat er i al )

ASTM C553 ( 2013) St andar d Speci f i cat i on f or Mi ner al Fi ber Bl anket Ther mal I nsul at i on f or Commer ci al and I ndust r i al Appl i cat i ons

ASTM D1654 ( 2008) Eval uat i on of Pai nt ed or Coat ed Speci mens Subj ect ed t o Cor r osi ve Environments

ASTM D3359 ( 2009; E 2010; R 2010) Measur i ng Adhesi on by Tape Test

ASTM D520 ( 2000; R 2011) Zi nc Dust Pi gment

ASTM E2016 ( 2015) St andar d Speci f i cat i on f or I ndust r i al Woven Wi r e Cl ot h

NATI ONAL ELECTRI CAL MANUFACTURERS ASSOCI ATI ON ( NEMA)

NEMA MG 1 ( 2014) Mot or s and Gener at or s

NEMA MG 10 ( 2013) Ener gy Management Gui de f or Sel ect i on and Use of Fi xed Fr equency Medi um AC Squi r r el - Cage Pol yphase I nduct i on Mot or s

NEMA MG 11 ( 1977; R 2012) Ener gy Management Gui de f or Sel ect i on and Use of Si ngl e Phase Mot or s

NATI ONAL FI RE PROTECTI ON ASSOCI ATI ON ( NFPA)

NFPA 701 ( 2015) St andar d Met hods of Fi r e Test s f or Fl ame Pr opagat i on of Text i l es and Fi l ms

NFPA 90A ( 2015) St andar d f or t he I nst al l at i on of Ai r Condi t i oni ng and Vent i l at i ng Syst ems

SCI ENTI FI C CERTI FI CATI ON SYSTEMS ( SCS)

SCS Sci ent i f i c Cer t i f i cat i on Syst ems ( SCS) I ndoor Advant age

SHEET METAL AND AI R CONDI TI ONI NG CONTRACTORS' NATI ONAL ASSOCI ATI ON

(SMACNA)

SMACNA 1819 ( 2002) Fi r e, Smoke and Radi at i on Damper I nst al l at i on Gui de f or HVAC Syst ems, 5t h Edition

SMACNA 1966 ( 2005) HVAC Duct Const r uct i on St andar ds Met al and Fl exi bl e, 3r d Edi t i on

SMACNA 1972 CD ( 2012) HVAC Ai r Duct Leakage Test Manual -

SECTI ON 23 00 00 Page 3

2nd Edi t i on

SMACNA 1981 ( 2008) Sei smi c Rest r ai nt Manual Gui del i nes f or Mechani cal Syst ems, 3r d Edi t i on

U. S. DEPARTMENT OF ENERGY ( DOE)

Ener gy St ar ( 1992; R 2006) Ener gy St ar Ener gy Ef f i c i ency Label i ng Syst em ( FEMP)

U. S. NATI ONAL ARCHI VES AND RECORDS ADMI NI STRATI ON ( NARA)

40 CFR 82 Pr ot ect i on of St r at ospher i c Ozone

PL 109- 58 Ener gy Pol i cy Act of 2005 ( EPAct 05)

UL ENVI RONMENT ( ULE)

ULE Gr eenguar d UL Gr eenguar d Cer t i f i cat i on Pr ogr am

UNDERWRI TERS LABORATORI ES ( UL)

UL 181 ( 2013) Fact or y- Made Ai r Duct s and Ai r Connectors

UL 1995 ( 2015) Heat i ng and Cool i ng Equi pment

UL 555 ( 2006; Repr i nt Aug 2016) UL St andar d f or Saf et y Fi r e Damper s

UL 555S ( 2014; Repr i nt Aug 2016) UL St andar d f or Saf et y Smoke Damper s

UL 586 ( 2009; Repr i nt Sep 2014) St andar d f or Hi gh- Ef f i c i ency Par t i cul at e, Ai r Fi l t er Units

UL 6 ( 2007; Repr i nt Nov 2014) El ect r i cal Ri gi d Met al Condui t - St eel

UL 705 ( 2004; Repr i nt Dec 2013) St andar d f or Power Vent i l at or s

UL 900 ( 2015) St andar d f or Ai r Fi l t er Uni t s

UL Bl d Mat Di r ( 2012) Bui l di ng Mat er i al s Di r ect or y

UL El ect r i cal Const r uct n ( 2012) El ect r i cal Const r uct i on Equi pment Directory

UL Fi r e Resi st ance ( 2014) Fi r e Resi st ance Di r ect or y

1. 2 SYSTEM DESCRI PTI ON

Fur ni sh duct wor k, pi pi ng of f set s, f i t t i ngs, and accessor i es as r equi r ed t o pr ovi de a compl et e i nst al l at i on. Coor di nat e t he wor k of t he di f f er ent t r ades t o avoi d i nt er f er ence bet ween pi pi ng, equi pment , st r uct ur al , and el ect r i cal wor k. Pr ovi de compl et e, i n pl ace, al l necessar y of f set s i n pi pi ng and duct wor k, and al l f i t t i ngs, and ot her component s, r equi r ed t o

SECTI ON 23 00 00 Page 4 i nst al l t he wor k as i ndi cat ed and speci f i ed.

1. 2. 1 Mechani cal Equi pment I dent i f i cat i on

The number of char t s and di agr ams shal l be equal t o or gr eat er t han t he number of mechani cal equi pment r ooms. Wher e mor e t han one char t or di agr am per space i s r equi r ed, mount t hese i n edge pi vot ed, swi ngi ng l eaf , ext r uded al umi num f r ame hol der s whi ch open t o 170 degr ees.

1. 2. 1. 1 Charts

Pr ovi de char t l i s t i ng of equi pment by desi gnat i on number s and capaci t i es such as f l ow r at es, pr essur e and t emper at ur e di f f er ences, heat i ng and cool i ng capaci t i es, hor sepower , pi pe s i zes, and vol t age and cur r ent characteristics.

1. 2. 1. 2 Diagrams

Submi t pr oposed di agr ams, at l east 2 weeks pr i or t o st ar t of r el at ed t est i ng. pr ovi de neat mechani cal dr awi ngs pr ovi ded wi t h ext r uded al umi num f r ame under 1/ 8- i nch gl ass or l ami nat ed pl ast i c, syst em di agr ams t hat show t he l ayout of equi pment , pi pi ng, and duct wor k, and t yped condensed oper at i on manual s expl ai ni ng pr event at i ve mai nt enance pr ocedur es, met hods of checki ng t he syst em f or nor mal , saf e oper at i on, and pr ocedur es f or saf el y st ar t i ng and st oppi ng t he syst em. Af t er appr oval , post t hese i t ems wher e di r ect ed.

1. 2. 2 Ser vi ce Label i ng

Label equi pment , i ncl udi ng f ans, ai r handl er s, t er mi nal uni t s, et c. wi t h l abel s made of sel f - st i cki ng, pl ast i c f i l m desi gned f or per manent i nst al l at i on. Label s shal l be i n accor dance wi t h t he t ypi cal exampl es below:

SERVICE LABEL AND TAG DESI GNATI ON

Ai r handl i ng uni t Number AHU - #

Cont r ol and i nst r ument ai r CONTROL AND I NSTR.

Exhaust Fan Number EF - #

VAV Box Number VAV - #

Fan Coi l Uni t Number FC - #

Ter mi nal Box Number TB - #

Uni t Vent i l at or Number UV - #

I dent i f y s i mi l ar ser vi ces wi t h di f f er ent t emper at ur es or pr essur es. Wher e pr essur es coul d exceed 125 pounds per squar e i nch, gage, i ncl ude t he maxi mum syst em pr essur e i n t he l abel . Label and ar r ow pi pi ng i n accor dance wi t h t he f ol l owi ng:

a. Each poi nt of ent r y and exi t of pi pe passi ng t hr ough wal l s.

SECTI ON 23 00 00 Page 5

b. Each change i n di r ect i on, i . e. , el bows, t ees.

c. I n congest ed or hi dden ar eas and at al l access panel s at each poi nt r equi r ed t o c l ar i f y ser vi ce or i ndi cat ed hazar d.

d. I n l ong st r ai ght r uns, l ocat e l abel s at di st ances wi t hi n eyesi ght of each ot her not t o exceed 75 f eet . Al l l abel s shal l be v i s i bl e and l egi bl e f r om t he pr i mar y ser vi ce and oper at i ng ar ea.

For Bar e or I nsul at ed Pi pes f or Out si de Di amet er s of Lettering

1/ 2 t hr u 1- 3/ 8 i nch 1/ 2 i nch

1- 1/ 2 t hr u 2- 3/ 8 i nch 3/ 4 i nch

2- 1/ 2 i nch and l ar ger 1- 1/ 4 i nch

1. 2. 3 Col or Codi ng

Col or codi ng of al l pi pi ng syst ems shal l be i n accor dance wi t h ASME A13. 1 .

1. 3 SUBMITTALS

Gover nment appr oval i s r equi r ed f or submi t t al s wi t h a " G" desi gnat i on;

submi t t al s not havi ng a " G" desi gnat i on ar e f or i nf or mat i on onl y. When used, a desi gnat i on f ol l owi ng t he " G" desi gnat i on i dent i f i es t he of f i ce t hat wi l l r evi ew t he submi t t al f or t he Gover nment . Submi t t al s wi t h an " S" ar e f or i ncl usi on i n t he Sust ai nabi l i t y Not ebook, i n conf or mance t o Sect i on 01 33 29 SUSTAI NABI LI TY REPORTI NG. Submi t t he f ol l owi ng i n accor dance wi t h Sect i on 01 33 00 SUBMI TTAL PROCEDURES:

SD- 02 Shop Dr awi ngs

Det ai l Dr awi ngs; G, AE

SD- 03 Pr oduct Dat a

Met al l i c Fl exi bl e Duct ; G, AE I nsul at ed Nonmet al l i c Fl exi bl e Duct Runout s; G, AE Duct Connect or s; G, AE Duct Access Door s; G, AE Fi r e Damper s; G, AE Manual Bal anci ng Damper s; G, AE Sound At t enuat i on Equi pment ; G, AE Acoust i cal Duct Li ner ; G, AE Di f f user s; G, AE Regi st er s and Gr i l l es; G, AE Louver s; G, AE Ai r Vent s, Pent houses, and Goosenecks; G, AE Cent r i f ugal Fans; G, AE I n- Li ne Cent r i f ugal Fans Axi al Fl ow Fans Cent r i f ugal Type Power Roof Vent i l at or s; G, AE Pr opel l er Type Power Roof Vent i l at or s Cei l i ng Exhaust Fans Ai r Handl i ng Uni t s; G, AE

SECTI ON 23 00 00 Page 6

Room Fan- Coi l Uni t s; G, AE Coi l I nduct i on Uni t s; G, AEReheat Uni t s; G, AE Ener gy Recover y Devi ces; G, AE Test Pr ocedur es Di agr ams; G, AE

SD- 06 Test Repor t s

Per f or mance Test s; G Damper Accept ance Test ; G

SD- 07 Cer t i f i cat es

Certification Ozone Depl et i ng Subst ances

SD- 08 Manuf act ur er ' s I nst r uct i ons

Manuf act ur er ' s I nst al l at i on I nst r uct i ons Oper at i on and Mai nt enance Tr ai ni ng

SD- 10 Oper at i on and Mai nt enance Dat a

Oper at i on and Mai nt enance Manual s; G Fi r e Damper s; G Manual Bal anci ng Damper s; G Cent r i f ugal Fans; G Cent r i f ugal Type Power Roof Vent i l at or s; G Ai r Handl i ng Uni t s; G Room Fan- Coi l Uni t s; G Reheat Uni t s; G Ener gy Recover y Devi ces; G

SD- 11 Cl oseout Submi t t al s

Ener gy Ef f i c i ent Equi pment ; S Reduce Vol at i l e Or gani c Compounds ( VOC) ; S I ndoor Ai r Qual i t y Dur i ng Const r uct i on; S Ozone Depl et i ng Subst ances f or Ref r i ger ant s; S

1. 4 QUALI TY ASSURANCE

Except as ot her wi se speci f i ed, appr oval of mat er i al s and equi pment i s based on manuf act ur er ' s publ i shed dat a.

a. Wher e mat er i al s and equi pment ar e speci f i ed t o conf or m t o t he st andar ds of t he Under wr i t er s Labor at or i es, t he l abel of or l i s t i ng wi t h r eexami nat i on i n UL Bl d Mat Di r , and UL 6 i s accept abl e as suf f i c i ent evi dence t hat t he i t ems conf or m t o Under wr i t er s Labor at or i es r equi r ement s. I n l i eu of such l abel or l i s t i ng, submi t a wr i t t en cer t i f i cat e f r om any nat i onal l y r ecogni zed t est i ng agency, adequat el y equi pped and compet ent t o per f or m such ser vi ces, st at i ng t hat t he i t ems have been t est ed and t hat t he uni t s conf or m t o t he speci f i ed r equi r ement s. Out l i ne met hods of t est i ng used by t he speci f i ed agenci es.

b. Wher e mat er i al s or equi pment ar e speci f i ed t o be const r uct ed or t est ed, or bot h, i n accor dance wi t h t he st andar ds of t he ASTM I nt er nat i onal ( ASTM) , t he ASME I nt er nat i onal ( ASME) , or ot her

SECTI ON 23 00 00 Page 7 st andar ds, a manuf act ur er ' s cer t i f i cat e of compl i ance of each i t em i s accept abl e as pr oof of compl i ance.

c. Conf or mance t o such agency r equi r ement s does not r el i eve t he i t em f r om compl i ance wi t h ot her r equi r ement s of t hese speci f i cat i ons.

d. Wher e pr oduct s ar e speci f i ed t o meet or exceed t he speci f i ed ener gy ef f i c i ency r equi r ement of FEMP- desi gnat ed or Ener gy St ar cer t i f i ed pr oduct cat egor i es, equi pment sel ect ed shal l have as a mi ni mum t he ef f i c i ency r at i ng i dent i f i ed under " Ener gy- Ef f i c i ent Pr oduct s" at http://www1.eere.energy.gov/femp/procurement .

These speci f i cat i ons conf or m t o t he ef f i c i ency r equi r ement s as def i ned i n Publ i c Law PL 109- 58, " Ener gy Pol i cy Act of 2005" f or f eder al pr ocur ement of ener gy- ef f i c i ent pr oduct s. Equi pment havi ng a l ower ef f i c i ency t han Ener gy St ar or FEMP r equi r ement s may be speci f i ed i f t he desi gner det er mi nes t he equi pment t o be mor e l i f e- cycl e cost ef f ect i ve usi ng t he l i f e- cycl e cost anal ysi s met hodol ogy and pr ocedur e i n 10 CFR 436.

1. 4. 1 Pr event i on of Cor r osi on

Pr ot ect met al l i c mat er i al s agai nst cor r osi on. Manuf act ur er shal l pr ovi de r ust - i nhi bi t i ng t r eat ment and st andar d f i ni sh f or t he equi pment encl osur es. Do not use al umi num i n cont act wi t h ear t h, and wher e connect ed t o di ssi mi l ar met al . Pr ot ect al umi num by appr oved f i t t i ngs, bar r i er mat er i al , or t r eat ment . Fer r ous par t s such as anchor s, bol t s, br aces, boxes, bodi es, c l amps, f i t t i ngs, guar ds, nut s, pi ns, r ods, shi ms, t hi mbl es, washer s, and mi scel l aneous par t s not of cor r osi on- r esi st ant st eel or nonf er r ous mat er i al s shal l be hot - di p gal vani zed i n accor dance with ASTM A123/ A123M f or ext er i or l ocat i ons and cadmi um- pl at ed i n conf or mance wi t h ASTM B766 f or i nt er i or l ocat i ons.

1. 4. 2 Asbest os Pr ohi bi t i on

Do not use asbest os and asbest os- cont ai ni ng pr oduct s.

1. 4. 3 Ozone Depl et i ng Subst ances Used as Ref r i ger ant s

Mi ni mi ze r el eases of Ozone Depl et i ng Subst ances ( ODS) dur i ng r epai r , mai nt enance, ser vi c i ng or di sposal of appl i ances cont ai ni ng ODS' s by compl yi ng wi t h al l appl i cabl e sect i ons of 40 CFR 82 Par t 82 Subpar t F.

Any per son conduct i ng r epai r , mai nt enance, ser vi c i ng or di sposal of equi pment cont ai ni ng r ef r i ger ant s must compl y wi t h t he f ol l owi ng:

a. Do not knowi ngl y vent or ot her wi se r el ease i nt o t he envi r onment , Cl ass I or Cl ass I I subst ances used as a r ef r i ger ant .

b. Do not open appl i ances wi t hout meet i ng t he r equi r ement s of 40 CFR 82 Par t 82. 156 Subpar t F, r egar di ng r equi r ed pr act i ces f or evacuat i on and col l ect i on of r ef r i ger ant , and 40 CFR 82 Par t 82. 158 Subpar t F, r egar di ng st andar ds of r ecycl i ng and r ecover y equi pment .

c. Onl y per sons who compl y wi t h 40 CFR 82 Par t 82. 161 Subpar t F, r egar di ng t echni c i an cer t i f i cat i on, can conduct wor k on appl i ances cont ai ni ng r ef r i ger ant .

I n addi t i on, pr ovi de copi es of al l appl i cabl e cer t i f i cat i ons t o t he Cont r act i ng Of f i cer at l east 14 cal endar days pr i or t o i ni t i at i ng

SECTI ON 23 00 00 Page 8 mai nt enance, r epai r , ser vi c i ng, di smant l i ng or di sposal of appl i ances, including:

a. Pr oof of Techni c i an Cer t i f i cat i on

b. Pr oof of Equi pment Cer t i f i cat i on f or r ecover y or r ecycl i ng equi pment .

c. Pr oof of avai l abi l i t y of cer t i f i ed r ecover y or r ecycl i ng equi pment .

1. 4. 4 Use of Ozone Depl et i ng Subst ances, Ot her t han Ref r i ger ant s

The use of Cl ass I or Cl ass I I ODS' s l i s t ed as nonessent i al i n 40 CFR 82 Par t 82. 66 Subpar t C i s pr ohi bi t ed. These pr ohi bi t ed mat er i al s and uses include:

a. Any pl ast i c par t y spr ay st r eamer or noi se hor n whi ch i s pr opel l ed by a chlorofluorocarbon

b. Any cl eani ng f l ui d f or el ect r oni c and phot ogr aphi c equi pment whi ch cont ai ns a chl or of l uor ocar bon; i ncl udi ng l i qui d packagi ng, sol vent wi pes, sol vent spr ays, and gas spr ays.

c. Any pl ast i c f l exi bl e or packagi ng f oam pr oduct whi ch i s manuf act ur ed wi t h or cont ai ns a chl or of l uor ocar bon, i ncl udi ng, open cel l f oam, open cel l r i gi d pol yur et hane pour ed f oam, c l osed cel l ext r uded pol yst yr ene sheet f oam, c l osed cel l pol yet hyl ene f oam and cl osed cel l pol ypr opyl ene f oam except f or f l exi bl e or packagi ng f oam used i n coaxi al cabl i ng.

d. Any aer osol pr oduct or ot her pr essur i zed di spenser whi ch cont ai ns a chl or of l uor ocar bon, except f or t hose l i s t ed i n 40 CFR 82 Par t 82. 66 Subpar t C.

Request a wai ver i f a f aci l i t y r equi r ement di ct at es t hat a pr ohi bi t ed mat er i al i s necessar y t o achi eve pr oj ect goal s. Submi t t he wai ver r equest i n wr i t i ng t o t he Cont r act i ng Of f i cer . The wai ver wi l l be eval uat ed and dispositioned.

1. 4. 5 Det ai l Dr awi ngs

Submi t det ai l dr awi ngs showi ng equi pment l ayout , i ncl udi ng assembl y and i nst al l at i on det ai l s and el ect r i cal connect i on di agr ams; duct wor k l ayout showi ng t he l ocat i on of al l suppor t s and hanger s, t ypi cal hanger det ai l s, gauge r ei nf or cement , r ei nf or cement spaci ng r i gi di t y c l assi f i cat i on, and st at i c pr essur e and seal c l assi f i cat i ons. I ncl ude any i nf or mat i on r equi r ed t o demonst r at e t hat t he syst em has been coor di nat ed and f unct i ons pr oper l y as a uni t on t he dr awi ngs and show equi pment r el at i onshi p t o ot her par t s of t he wor k, i ncl udi ng cl ear ances r equi r ed f or oper at i on and mai nt enance. Submi t dr awi ngs showi ng bol t - set t i ng i nf or mat i on, and f oundat i on bol t s pr i or t o concr et e f oundat i on const r uct i on f or al l equi pment i ndi cat ed or r equi r ed t o have concr et e f oundat i ons. Submi t f unct i on desi gnat i on of t he equi pment and any ot her r equi r ement s speci f i ed t hr oughout t hi s Sect i on wi t h t he shop dr awi ngs.

1. 4. 6 Test Pr ocedur es

Submi t pr oposed t est pr ocedur es and t est schedul es f or t he duct wor k l eak t est , and per f or mance t est s of syst ems, at l east 2 weeks pr i or t o t he st ar t of r el at ed t est i ng.

SECTI ON 23 00 00 Page 9

1. 4. 7 Sust ai nabl e Desi gn Cer t i f i cat i on

Pr oduct shal l be t hi r d par t y cer t i f i ed i n accor dance wi t h ULE Gr eenguar d Gold, SCS Sci ent i f i c Cer t i f i cat i on Syst ems I ndoor Advant age Gol d or equal . Cer t i f i cat i on shal l be per f or med annual l y and shal l be cur r ent .

1. 5 DELI VERY, STORAGE, AND HANDLI NG

Pr ot ect st or ed equi pment at t he j obsi t e f r om t he weat her , humi di t y and t emper at ur e var i at i ons, di r t and dust , or ot her cont ami nant s.

Addi t i onal l y, cap or pl ug al l pi pes unt i l i nst al l ed.

PART 2 PRODUCTS

2. 1 PRODUCT SUSTAI NABI LI TY CRI TERI A

For pr oduct s i n t hi s sect i on, wher e appl i cabl e and t o ext ent al l owed by per f or mance cr i t er i a, pr ovi de and document t he f ol l owi ng:

2. 1. 1 Ener gy Ef f i c i ent Equi pment

Pr ovi de document at i on i n conf or mance wi t h Sect i on 01 33 29 SUSTAI NABI LI TY REPORTI NG par agr aph ENERGY EFFI CI ENT EQUI PMENT t hat t he f ol l owi ng pr oduct s meet ener gy ef f i c i ency r equi r ement s as out l i ned i n t hi s sect i on:

a. Cent r i f ugal Fans

b. Cent r i f ugal Type Power Roof Vent i l at or s

c. Ai r Handl i ng Uni t s

d. Ener gy Recover y Devi ces

2. 1. 2 Reduce Vol at i l e Or gani c Compounds ( VOC) f or seal ant s, coat i ngs or adhesives

Low or no VOC' s and no added ur ea f or mal dehyde f or duct seal ant s, coat i ngs or adhesi ves, i n conf or mance wi t h Sect i on 01 33 29 SUSTAI NABI LI TY REPORTI NG par agr aph REDUCE VOLATI LE ORGANI C COMPOUNDS ( VOC) .

2. 1. 3 Ozone Depl et i ng Subst ances f or Ref r i ger ant s

Do not use any Ozone Depl et i ng Subst ances ( ODS) as Ref r i ger ant s per r equi r ement s i n 01 33 29 SUSTAI NABI LI TY REPORTI NG par agr aph OZONE

DEPLETI NG SUBSTANCES.

2. 2 STANDARD PRODUCTS

Pr ovi de component s and equi pment t hat ar e " st andar d pr oduct s" of a manuf act ur er r egul ar l y engaged i n t he manuf act ur i ng of pr oduct s t hat ar e of a s i mi l ar mat er i al , desi gn and wor kmanshi p. " St andar d pr oduct s" i s def i ned as bei ng i n sat i sf act or y commer ci al or i ndust r i al use f or 2 year s bef or e bi d openi ng, i ncl udi ng appl i cat i ons of component s and equi pment under s i mi l ar c i r cumst ances and of s i mi l ar s i ze, sat i sf act or i l y compl et ed by a pr oduct t hat i s sol d on t he commer ci al mar ket t hr ough adver t i sement s, manuf act ur er s ' cat al ogs, or br ochur es. Pr oduct s havi ng l ess t han a 2- year f i el d ser vi ce r ecor d ar e accept abl e i f a cer t i f i ed r ecor d of sat i sf act or y f i el d oper at i on, f or not l ess t han 6000 hour s excl usi ve of t he manuf act ur er ' s f act or y t est s, can be shown. Pr ovi de equi pment i t ems t hat ar e suppor t ed by a ser vi ce or gani zat i on.

SECTI ON 23 00 00 Page 10

2. 3 I DENTI FI CATI ON PLATES

I n addi t i on t o st andar d manuf act ur er ' s i dent i f i cat i on pl at es, pr ovi de engr aved l ami nat ed phenol i c i dent i f i cat i on pl at es f or each pi ece of mechani cal equi pment . I dent i f i cat i on pl at es ar e t o desi gnat e t he f unct i on of t he equi pment . Submi t desi gnat i on wi t h t he shop dr awi ngs.

I dent i f i cat i on pl at es shal l be t hr ee l ayer s, bl ack- whi t e- bl ack, engr aved t o show whi t e l et t er s on bl ack backgr ound. Let t er s shal l be upper case.

I dent i f i cat i on pl at es 1- 1/ 2- i nches hi gh and smal l er shal l be 1/ 16- i nch t hi ck, wi t h engr aved l et t er i ng 1/ 8- i nch hi gh; i dent i f i cat i on pl at es l ar ger t han 1- 1/ 2- i nches hi gh shal l be 1/ 8- i nch t hi ck, wi t h engr aved l et t er i ng of sui t abl e hei ght . I dent i f i cat i on pl at es 1- 1/ 2- i nches hi gh and l ar ger shal l have bevel ed edges. I nst al l i dent i f i cat i on pl at es usi ng a compat i bl e adhesive.

2. 4 EQUI PMENT GUARDS AND ACCESS

Ful l y encl ose or guar d bel t s, pul l eys, chai ns, gear s, coupl i ngs, pr oj ect i ng set scr ews, keys, and ot her r ot at i ng par t s exposed t o per sonnel cont act accor di ng t o OSHA r equi r ement s. Pr oper l y guar d or cover wi t h i nsul at i on of a t ype speci f i ed, hi gh t emper at ur e equi pment and pi pi ng exposed t o cont act by per sonnel or wher e i t cr eat es a pot ent i al f i r e hazar d. The r equi r ement s f or cat wal ks, oper at i ng pl at f or ms, l adder s, and guar dr ai l s ar e speci f i ed i n Sect i on 05 50 13 MI SCELLANEOUS METAL

FABRICATIONS.

2. 5 ELECTRI CAL WORK

a. Pr ovi de mot or s, cont r ol l er s, i nt egr al di sconnect s, cont act or s, and cont r ol s wi t h t hei r r espect i ve pi eces of equi pment , except cont r ol l er s i ndi cat ed as par t of mot or cont r ol cent er s. Pr ovi de el ect r i cal equi pment , i ncl udi ng mot or s and wi r i ng, as speci f i ed i n Sect i on 26 20 00I NTERI OR DI STRI BUTI ON SYSTEM. Pr ovi de manual or aut omat i c cont r ol and pr ot ect i ve or s i gnal devi ces r equi r ed f or t he oper at i on speci f i ed and cont r ol wi r i ng r equi r ed f or cont r ol s and devi ces speci f i ed, but not shown. For packaged equi pment , i ncl ude manuf act ur er pr ovi ded cont r ol l er s wi t h t he r equi r ed moni t or s and t i med restart.

b. For s i ngl e- phase mot or s, pr ovi de hi gh- ef f i c i ency t ype, f r act i onal - hor sepower al t er nat i ng- cur r ent mot or s, i ncl udi ng mot or s t hat ar e par t of a syst em, i n accor dance wi t h NEMA MG 11. I nt egr al s i ze mot or s shal l be t he pr emi um ef f i c i ency t ype i n accor dance wi t h

NEMA MG 1.

c. For pol yphase mot or s, pr ovi de squi r r el - cage medi um i nduct i on mot or s, i ncl udi ng mot or s t hat ar e par t of a syst em , and t hat meet t he ef f i c i ency r at i ngs f or pr emi um ef f i c i ency mot or s i n accor dance wi t h NEMA MG 1. Sel ect pr emi um ef f i c i ency pol yphase mot or s i n accor dance with NEMA MG 10.

d. Pr ovi de mot or s i n accor dance wi t h NEMA MG 1 and of suf f i c i ent s i ze t o dr i ve t he l oad at t he speci f i ed capaci t y wi t hout exceedi ng t he namepl at e r at i ng of t he mot or . Pr ovi de mot or s r at ed f or cont i nuous dut y wi t h t he encl osur e speci f i ed. Pr ovi de mot or dut y t hat al l ows f or maxi mum f r equency st ar t - st op oper at i on and mi ni mum encount er ed i nt er val bet ween st ar t and st op. Pr ovi de mot or t or que capabl e of accel er at i ng t he connect ed l oad wi t hi n 20 seconds wi t h 80 per cent of t he r at ed vol t age mai nt ai ned at mot or t er mi nal s dur i ng one st ar t i ng

SECTI ON 23 00 00 Page 11 per i od. Pr ovi de mot or st ar t er s compl et e wi t h t her mal over l oad pr ot ect i on and ot her necessar y appur t enances. Fi t mot or bear i ngs wi t h gr ease suppl y f i t t i ngs and gr ease r el i ef t o out si de of t he encl osur e.

e. Pr ovi de var i abl e f r equency dr i ves f or mot or s as speci f i ed i n Sect i on

26 29 23 VARI ABLE FREQUENCY DRI VE SYSTEMS UNDER 600 VOLTS.

2. 6 ANCHOR BOLTS

Pr ovi de anchor bol t s f or equi pment pl aced on concr et e equi pment pads or on concr et e s l abs. Bol t s t o be of t he s i ze and number r ecommended by t he equi pment manuf act ur er and l ocat ed by means of sui t abl e t empl at es.

I nst al l at i on of anchor bol t s shal l not degr ade t he sur r oundi ng concr et e.

2. 7 SEI SMI C ANCHORAGE

Anchor equi pment i n accor dance wi t h appl i cabl e sei smi c cr i t er i a f or t he ar ea and as def i ned i n SMACNA 1981

2. 8 PAINTING

Pai nt equi pment uni t s i n accor dance wi t h appr oved equi pment manuf act ur er ' s st andar ds unl ess speci f i ed ot her wi se. Fi el d r et ouch onl y i f appr oved.

Ot her wi se, r et ur n equi pment t o t he f act or y f or r ef i ni shi ng.

2. 9 I NDOOR AI R QUALI TY

Pr ovi de equi pment and component s t hat compl y wi t h t he r equi r ement s of ASHRAE 62. 1 unl ess mor e st r i ngent r equi r ement s ar e speci f i ed her ei n.

2. 10 DUCT SYSTEMS

2. 10. 1 Met al Duct wor k

Pr ovi de met al duct wor k const r uct i on, i ncl udi ng al l f i t t i ngs and component s, t hat compl i es wi t h SMACNA 1966, as suppl ement ed and modi f i ed by t hi s speci f i cat i on.

a. Duct wor k shal l be const r uct ed meet i ng t he r equi r ement s f or t he duct syst em st at i c pr essur e speci f i ed i n APPENDI X D of Sect i on 23 05 93

TESTI NG, ADJUSTI NG AND AI R BALANCI NG FOR HVAC.

b. Pr ovi de r adi us t ype el bows wi t h a cent er l i ne r adi us of 1. 5 t i mes t he wi dt h or di amet er of t he duct wher e space per mi t s. Ot her wi se, el bows havi ng a mi ni mum r adi us equal t o t he wi dt h or di amet er of t he duct or squar e el bows wi t h f act or y f abr i cat ed t ur ni ng vanes ar e al l owed.

c. Pr ovi de duct wor k t hat meet s t he seal and l eak c l ass schedul ed on t he Drawings.

d. Pr ovi de seal ant s t hat conf or m t o f i r e hazar d c l assi f i cat i on speci f i ed i n Sect i on 23 07 00 THERMAL I NSULATI ON FOR MECHANI CAL SYSTEMS and ar e sui t abl e f or t he r ange of ai r di st r i but i on and ambi ent t emper at ur es t o whi ch i t i s exposed. Do not use pr essur e sensi t i ve t ape as a seal ant .

e. Make spi r al l ock seam duct , and f l at oval wi t h duct seal ant and l ock wi t h not l ess t han 3 equal l y spaced dr i ve scr ews or ot her appr oved met hods i ndi cat ed i n SMACNA 1966. Appl y t he seal ant t o t he exposed

SECTI ON 23 00 00 Page 12 mal e par t of t he f i t t i ng col l ar so t hat t he seal er i s on t he i nsi de of t he j oi nt and f ul l y pr ot ect ed by t he met al of t he duct f i t t i ng. Appl y one br ush coat of t he seal ant over t he out si de of t he j oi nt t o at l east 2 i nch band wi dt h cover i ng al l scr ew heads and j oi nt gap. Dent s i n t he mal e por t i on of t he s l i p f i t t i ng col l ar ar e not accept abl e.

Fabr i cat e out door ai r i nt ake duct s and pl enums wi t h wat er t i ght sol der ed or br azed j oi nt s and seams.

2. 10. 1. 1 Met al l i c Fl exi bl e Duct

a. Pr ovi de duct t hat conf or ms t o UL 181 and NFPA 90A wi t h f act or y- appl i ed i nsul at i on, vapor bar r i er , and end connect i ons. Pr ovi de duct assembl y t hat does not exceed 25 f or f l ame spr ead and 50 f or smoke devel oped.

Pr ovi de duct s desi gned f or wor ki ng pr essur es of 2 i nches wat er gauge posi t i ve and 1. 5 i nches wat er gauge negat i ve. Pr ovi de f l exi bl e r ound duct l engt h t hat does not exceed 5 f eet . Secur e connect i ons by appl y i ng adhesi ve f or 2 i nches over r i gi d duct , appl y f l exi bl e duct 2 i nches over r i gi d duct , appl y met al c l amp, and pr ovi de mi ni mum of t hr ee No. 8 sheet met al scr ews t hr ough cl amp and r i gi d duct .

b. I nner duct cor e: Pr ovi de i nt er l ocki ng spi r al or hel i cal l y cor r ugat ed f l exi bl e cor e const r uct ed of z i nc- coat ed st eel , al umi num, or st ai nl ess st eel ; or const r uct ed of i nner l i ner of cont i nuous gal vani zed spr i ng st eel wi r e hel i x f used t o cont i nuous, f i r e- r et ar dant , f l exi bl e vapor bar r i er f i l m, i nner duct cor e.

c. I nsul at i on: Pr ovi de i nner duct cor e t hat i s i nsul at ed wi t h mi ner al f i ber bl anket t ype f l exi bl e i nsul at i on, mi ni mum of 1 i nch t hi ck.

Pr ovi de i nsul at i on cover ed on ext er i or wi t h manuf act ur er ' s st andar d f i r e r et ar dant vapor bar r i er j acket f or f l exi bl e r ound duct .

2. 10. 1. 2 I nsul at ed Nonmet al l i c Fl exi bl e Duct Runout s

Use f l exi bl e duct r unout s onl y wher e i ndi cat ed. Runout l engt h i s i ndi cat ed on t he dr awi ngs, and i s not t o exceed 5 f eet . Pr ovi de r unout s t hat ar e pr ei nsul at ed, f act or y f abr i cat ed, and t hat compl y wi t h NFPA 90A and UL 181. Pr ovi de ei t her f i el d or f act or y appl i ed vapor bar r i er .

Pr ovi de not l ess t han 20 ounce gl ass f abr i c duct connect or s coat ed on bot h s i des wi t h neopr ene. Wher e coi l i nduct i on or hi gh vel oci t y uni t s ar e suppl i ed wi t h ver t i cal ai r i nl et s, use a st r eaml i ned, vaned and mi t er ed el bow t r ansi t i on pi ece f or connect i on t o t he f l exi bl e duct or hose.

Pr ovi de a di e- st amped el bow and not a f l exi bl e connect or as t he l ast el bow t o t hese uni t s ot her t han t he ver t i cal ai r i nl et t ype. I nsul at ed f l exi bl e connect or s ar e al l owed as r unout s. Pr ovi de i nsul at ed mat er i al and vapor bar r i er t hat conf or m t o t he r equi r ement s of Sect i on 23 07 00 THERMAL I NSULATI ON FOR MECHANI CAL SYSTEMS. Do not expose t he i nsul at i on mat er i al sur f ace t o t he ai r st r eam.

2. 10. 1. 3 Gener al Ser vi ce Duct Connect or s

Pr ovi de a f l exi bl e duct connect or appr oxi mat el y 6 i nches i n wi dt h wher e sheet met al connect i ons ar e made t o f ans or wher e duct s of di ssi mi l ar met al s ar e connect ed. For r ound/ oval duct s, secur e t he f l exi bl e mat er i al by st ai nl ess st eel or z i nc- coat ed, i r on c l i nch- t ype dr aw bands. For r ect angul ar duct s, i nst al l t he f l exi bl e mat er i al l ocked t o met al col l ar s usi ng nor mal duct const r uct i on met hods. Pr ovi de a composi t e connect or syst em t hat compl i es wi t h NFPA 701 and i s c l assi f i ed as " f l ame- r et ar dant f abr i cs" i n UL Bl d Mat Di r .

SECTI ON 23 00 00 Page 13

2. 10. 1. 4 Hi gh Temper at ur e Ser vi ce Duct Connect i ons

Pr ovi de mat er i al t hat i s appr oxi mat el y 3/ 32 i nch t hi ck, 35 t o 40- ounce per squar e yar d wei ght , pl ai n weave f i br ous gl ass c l ot h wi t h, ni ckel / chr ome wi r e r ei nf or cement f or ser vi ce i n excess of 1200 degr ees F.

2. 10. 1. 5 Al umi num Duct s

ASTM B209, al l oy 3003- H14 f or al umi num sheet and al l oy 6061- T6 or equi val ent st r engt h f or al umi num connect or s and bar st ock.

2. 10. 1. 6 Copper Sheet s

ASTM B152/ B152M, l i ght col d r ol l ed t emper .

2. 10. 1. 7 Cor r osi on Resi st i ng ( St ai nl ess) St eel Sheet s

ASTM A167

2. 10. 2 Duct Access Door s

Pr ovi de hi nged access door s conf or mi ng t o SMACNA 1966 i n duct wor k and pl enums wher e i ndi cat ed and at al l ai r f l ow measur i ng pr i mar i es, aut omat i c damper s, f i r e damper s, coi l s, t her most at s, and ot her appar at us r equi r i ng ser vi ce and i nspect i on i n t he duct syst em. Pr ovi de access door s upst r eam and downst r eam of ai r f l ow measur i ng pr i mar i es and heat i ng and cool i ng coi l s. Pr ovi de door s t hat ar e a mi ni mum 15 by 18 i nches, unl ess ot her wi se shown. Wher e duct s i ze does not accommodat e t hi s s i ze door , make t he door s as l ar ge as pr act i cabl e. Equi p door s 24 by 24 i nches or l ar ger wi t h f ast ener s oper abl e f r om i nsi de and out si de t he duct . Use i nsul at ed t ype door s i n i nsul at ed duct s.

2. 10. 3 Fi r e Damper s

Use 1. 5 hour r at ed f i r e damper s unl ess ot her wi se i ndi cat ed. Pr ovi de f i r e damper s t hat conf or m t o t he r equi r ement s of NFPA 90A and UL 555. Per f or m t he f i r e damper t est as out l i ned i n NFPA 90A. Pr ovi de a pr essur e r el i ef door upst r eam of t he f i r e damper . I f t he duct wor k connect ed t o t he f i r e damper i s t o be i nsul at ed t hen pr ovi de a f act or y i nst al l ed pr essur e r el i ef damper . Pr ovi de aut omat i c oper at i ng f i r e damper s wi t h a dynami c r at i ng sui t abl e f or t he maxi mum ai r vel oci t y and pr essur e di f f er ent i al t o whi ch i t i s subj ect ed. Pr ovi de f i r e damper s appr oved f or t he speci f i c appl i cat i on, and i nst al l accor di ng t o t hei r l i s t i ng. Equi p f i r e damper s wi t h a st eel s l eeve or adequat el y s i zed f r ame i nst al l ed i n such a manner t hat di sr upt i on of t he at t ached duct wor k, i f any, does not i mpai r t he oper at i on of t he damper . Equi p s l eeves or f r ames wi t h per i met er mount i ng angl es at t ached on bot h s i des of t he wal l or f l oor openi ng. Const r uct duct wor k i n f i r e- r at ed f l oor - cei l i ng or r oof - cei l i ng assembl y syst ems wi t h ai r duct s t hat pi er ce t he cei l i ng of t he assembl i es i n conf or mance wi t h UL Fi r e Resi st ance. Pr ovi de cur t ai n t ype wi t h damper bl ades out of t he ai r st r eam f i r e damper s. I nst al l damper s t hat do not r educe t he duct or t he ai r t r ansf er openi ng cr oss- sect i onal ar ea. I nst al l damper s so t hat t he cent er l i ne of t he damper dept h or t hi ckness i s l ocat ed i n t he cent er l i ne of t he wal l , par t i t i on or f l oor s l ab dept h or t hi ckness.

Unl ess ot her wi se i ndi cat ed, compl y wi t h t he i nst al l at i on det ai l s gi ven i n SMACNA 1819 and i n manuf act ur er ' s i nst r uct i ons f or f i r e damper s. Per f or m accept ance t est i ng of f i r e damper s accor di ng t o par agr aph Fi r e Damper Accept ance Test and NFPA 90A.

SECTI ON 23 00 00 Page 14

2. 10. 4 Manual Bal anci ng Damper s

Fur ni sh manual bal anci ng damper s wi t h accessi bl e oper at i ng mechani sms.

Use chr omi um pl at ed oper at or s ( wi t h al l exposed edges r ounded) i n f i ni shed por t i ons of t he bui l di ng. Pr ovi de manual vol ume cont r ol damper s t hat ar e oper at ed by l ocki ng- t ype quadr ant oper at or s. I nst al l damper s t hat ar e 2 gauges heavi er t han t he duct i n whi ch i nst al l ed. Unl ess ot her wi se i ndi cat ed, pr ovi de opposed bl ade t ype mul t i l eaf damper s wi t h maxi mum bl ade wi dt h of 12 i nches. Pr ovi de access door s or panel s f or al l conceal ed damper oper at or s and l ocki ng set scr ews. Pr ovi de st and- of f mount i ng br acket s, bases, or adapt er s not l ess t han t he t hi ckness of t he i nsul at i on when t he l ocki ng- t ype quadr ant oper at or s f or damper s ar e i nst al l ed on duct s t o be t her mal l y i nsul at ed, t o pr ovi de cl ear ance bet ween t he duct sur f ace and t he oper at or . St and- of f mount i ng i t ems shal l be i nt egr al wi t h t he oper at or or st andar d accessor y of t he damper manuf act ur er .

2. 10. 4. 1 Aut omat i c Bal anci ng Damper s

Pr ovi de damper s as speci f i ed i n par agr aph SUPPLEMENTAL COMPONENTS/ SERVI CES, subpar agr aph CONTROLS.

2. 10. 5 Ai r Suppl y And Exhaust Ai r Damper s

Wher e out door ai r suppl y and exhaust ai r damper s ar e r equi r ed t hey shal l have a maxi mum l eakage r at e when t est ed i n accor dance wi t h AMCA 500- D as r equi r ed by ASHRAE 90. 1 - I P, i ncl udi ng maxi mum Damper Leakage f or :

a. Cl i mat e Zones 1, 2, 6, 7, 8 t he maxi mum damper l eakage at 1. 0 i nch w. g.

f or mot or i zed damper s i s 4 cf m per squar e f oot of damper ar ea and non- mot or i zed damper s ar e not al l owed.

b. Al l ot her Cl i mat e Zones t he maxi mum damper l eakage at 1. 0 i nch w. g. i s 10 cf m per squar e f oot and f or non- mot or i zed damper s i s 20 cf m per squar e f oot of damper ar ea.

Damper s smal l er t han 24 i nches i n ei t her di r ect i on may have l eakage of 40 cf m per squar e f oot .

2. 10. 6 Ai r Def l ect or s and Br anch Connect i ons

Pr ovi de ai r def l ect or s at al l duct mount ed suppl y out l et s, at t akeof f or ext ensi on col l ar s t o suppl y out l et s, at duct br anch t akeof f connect i ons, and at 90 degr ee el bows, as wel l as at l ocat i ons as i ndi cat ed on t he dr awi ngs or ot her wi se speci f i ed. Coni cal br anch connect i ons or 45 degr ee ent r y connect i ons ar e al l owed i n l i eu of def l ect or s f or br anch connect i ons. Fur ni sh al l ai r def l ect or s, except t hose i nst al l ed i n 90 degr ee el bows, wi t h an appr oved means of adj ust ment . Pr ovi de easi l y accessi bl e means f or adj ust ment i nsi de t he duct or f r om an adj ust ment wi t h st ur dy l ock on t he f ace of t he duct . When i nst al l ed on duct s t o be t her mal l y i nsul at ed, pr ovi de ext er nal adj ust ment s wi t h st and- of f mount i ng br acket s, i nt egr al wi t h t he adj ust ment devi ce, t o pr ovi de cl ear ance bet ween t he duct sur f ace and t he adj ust ment devi ce not l ess t han t he t hi ckness of t he t her mal i nsul at i on. Pr ovi de f act or y- f abr i cat ed ai r def l ect or s consi st i ng of cur ved t ur ni ng vanes or l ouver bl ades desi gned t o pr ovi de uni f or m ai r di st r i but i on and change of di r ect i on wi t h mi ni mum t ur bul ence or pr essur e l oss. Pr ovi de f act or y or f i el d assembl ed ai r def l ect or s. Make adj ust ment f r om t he f ace of t he di f f user or by posi t i on adj ust ment and l ock ext er nal t o t he duct . Pr ovi de st and- of f br acket s on i nsul at ed duct s as descr i bed her ei n. Pr ovi de f i xed ai r def l ect or s, al so

SECTI ON 23 00 00 Page 15 cal l ed t ur ni ng vanes, i n 90 degr ee el bows.

2. 10. 7 Sound At t enuat i on Equi pment

2. 10. 7. 1 Syst ems wi t h t ot al pr essur e above 4 I nches Wat er Gauge

Pr ovi de sound at t enuat or s on t he di schar ge duct of each f an oper at i ng at a t ot al pr essur e above 4 i nch wat er gauge, and, when i ndi cat ed, at t he i nt ake of each f an syst em. Pr ovi de sound at t enuat or s el sewher e as i ndi cat ed. Pr ovi de f act or y f abr i cat ed sound at t enuat or s, t est ed by an i ndependent l abor at or y f or sound and per f or mance char act er i st i cs. Pr ovi de a net sound r educt i on as i ndi cat ed. Maxi mum per mi ssi bl e pr essur e dr op i s not t o exceed 0. 63 i nch wat er gauge. Const r uct t r aps t o be ai r t i ght when oper at i ng under an i nt er nal st at i c pr essur e of 10 i nch wat er gauge.

Pr ovi de ai r - s i de sur f ace capabl e of wi t hst andi ng ai r vel oci t y of 10, 000 f pm.

Cer t i f y t hat t he equi pment can obt ai n t he sound r educt i on val ues speci f i ed af t er t he equi pment i s i nst al l ed i n t he syst em and coor di nat ed wi t h t he sound i nf or mat i on of t he syst em f an t o be pr ovi ded. Pr ovi de sound absor bi ng mat er i al conf or mi ng t o ASTM C1071, Type I or I I . Pr ovi de sound absor bi ng mat er i al t hat meet s t he f i r e hazar d r at i ng r equi r ement s f or i nsul at i on speci f i ed i n Sect i on 23 07 00 THERMAL I NSULATI ON FOR MECHANI CAL SYSTEMS. For connect i on t o duct wor k, pr ovi de a duct t r ansi t i on sect i on.

Fact or y f abr i cat ed doubl e- wal l ed i nt er nal l y i nsul at ed spi r al l ock seam and r ound duct and f i t t i ngs desi gned f or hi gh pr essur e ai r syst em can be pr ovi ded i f compl yi ng wi t h r equi r ement s speci f i ed f or f act or y f abr i cat ed sound at t enuat or s, i n l i eu of f act or y f abr i cat ed sound at t enuat or s.

Const r uct t he doubl e- wal l ed duct and f i t t i ngs f r om an out er met al pr essur e shel l of z i nc- coat ed st eel sheet , 1 i nch t hi ck acoust i cal bl anket i nsul at i on, and an i nt er nal per f or at ed zi nc- coat ed met al l i ner . Pr ovi de a suf f i c i ent l engt h of r un t o obt ai n t he noi se r educt i on coef f i c i ent speci f i ed. Cer t i f y t hat t he sound r educt i on val ue speci f i ed can be obt ai ned wi t hi n t he l engt h of duct r un pr ovi ded. Pr ovi de wel ded or spi r al l ock seams on t he out er sheet met al of t he doubl e- wal l ed duct t o pr event wat er vapor penet r at i on. Pr ovi de duct and f i t t i ngs wi t h an out er sheet t hat conf or ms t o t he met al t hi ckness of hi gh- pr essur e spi r al and r ound duct s and f i t t i ngs shown i n SMACNA 1966. Pr ovi de acoust i cal i nsul at i on wi t h a t her mal conduct i v i t y " k" of not mor e t han 0. 27 Bt u/ i nch/ squar e f oot / hour / degr ee F at 75 degr ees F mean t emper at ur e. Pr ovi de an i nt er nal per f or at ed zi nc- coat ed met al l i ner t hat i s not l ess t han 24 gauge wi t h per f or at i ons not l ar ger t han 1/ 4 i nch i n di amet er pr ovi di ng a net open ar ea not l ess t han 10 per cent of t he sur f ace.

2. 10. 7. 2 Syst em wi t h t ot al pr essur e of 4 I nch Wat er Gauge and Lower

Use sound at t enuat or s onl y wher e i ndi cat ed. Pr ovi de f act or y f abr i cat ed sound at t enuat or s t hat ar e const r uct ed of gal vani zed st eel sheet s.

Pr ovi de at t enuat or wi t h out er casi ng t hat i s not l ess t han 22 gauge.

Pr ovi de f i br ous gl ass acoust i cal f i l l . Pr ovi de net sound r educt i on i ndi cat ed. Obt ai n val ues on a t est uni t not l ess t han 24 by 24 i nches out si de di mensi ons made by a cer t i f i ed nat i onal l y r ecogni zed i ndependent acoust i cal l abor at or y. Pr ovi de ai r f l ow capaci t y as i ndi cat ed or r equi r ed. Pr ovi de pr essur e dr op t hr ough t he at t enuat or t hat does not exceed t he val ue i ndi cat ed, or t hat i s not i n excess of 15 per cent of t he t ot al ext er nal st at i c pr essur e of t he ai r handl i ng syst em, whi chever i s l ess. Acoust i cal l y t est at t enuat or s wi t h met al duct i nl et and out l et sect i ons whi l e under t he r at ed ai r f l ow condi t i ons. I ncl ude wi t h t he noi se r educt i on dat a t he ef f ect s of f l anki ng pat hs and vi br at i on t r ansmi ssi on. Const r uct sound at t enuat or s t o be ai r t i ght when oper at i ng at t he i nt er nal st at i c pr essur e i ndi cat ed or speci f i ed f or t he duct

SECTI ON 23 00 00 Page 16 syst em, but i n no case l ess t han 2 i nch wat er gauge.

2. 10. 7. 3 Acoust i cal Duct Li ner

Use f i br ous gl ass desi gned or f l exi bl e el ast omer i c duct l i ner f or l i ni ng duct wor k and conf or mi ng t o t he r equi r ement s of ASTM C1071, Type I and I I .

Pr ovi de uni f or m densi t y, gr aduat ed densi t y, or dual densi t y l i ner composi t i on, as st andar d wi t h t he manuf act ur er . Pr ovi de not l ess t han 1 i nch t hi ck coat ed l i ni ng. Wher e acoust i cal duct l i ner i s used, pr ovi de t he t her mal equi val ent of t he i nsul at i on speci f i ed i n Sect i on 23 07 00 THERMAL I NSULATI ON FOR MECHANI CAL SYSTEMS f or l i ner or combi nat i on of l i ner and i nsul at i on appl i ed t o t he ext er i or of t he duct wor k. I ncr ease duct s i zes shown t o compensat e f or t he t hi ckness of t he l i ni ng used.

2. 10. 8 Di f f user s, Regi st er s, and Gr i l l es

Pr ovi de f act or y- f abr i cat ed uni t s of st eel or al umi num t hat di st r i but e t he speci f i ed quant i t y of ai r evenl y over space i nt ended wi t hout causi ng not i ceabl e dr af t s, ai r movement f ast er t han 50 f pm i n occupi ed zone, or dead spot s anywher e i n t he condi t i oned ar ea. Pr ovi de out l et s f or di f f usi on, spr ead, t hr ow, and noi se l evel as r equi r ed f or speci f i ed per f or mance. Cer t i f y per f or mance accor di ng t o ASHRAE 70. Pr ovi de sound r at ed and cer t i f i ed i nl et s and out l et s accor di ng t o ASHRAE 70. Pr ovi de sound power l evel as i ndi cat ed. Pr ovi de di f f user s and r egi st er s wi t h vol ume damper wi t h accessi bl e oper at or , unl ess ot her wi se i ndi cat ed; or i f st andar d wi t h t he manuf act ur er , an aut omat i cal l y cont r ol l ed devi ce i s accept abl e. Pr ovi de opposed bl ade t ype vol ume damper s f or al l di f f user s and r egi st er s, except l i near s l ot di f f user s. Pr ovi de l i near s l ot di f f user s wi t h r ound or el l i pt i cal bal anci ng damper s. Wher e t he i nl et and out l et openi ngs ar e l ocat ed l ess t han 7 f eet above t he f l oor , pr ot ect t hem by a gr i l l e or scr een accor di ng t o NFPA 90A. Pr ovi de al umi num uni t s wher e connect ed t o al umi num duct wor k. Pr ovi de st ai nl ess st eel uni t s wher e connect ed t o st ai nl ess st eel duct wor k.

2. 10. 8. 1 Diffusers

Pr ovi de di f f user t ypes i ndi cat ed. Fur ni sh cei l i ng mount ed uni t s wi t h ant i - smudge devi ces, unl ess t he di f f user uni t mi ni mi zes cei l i ng smudgi ng t hr ough desi gn f eat ur es. Pr ovi de di f f user s wi t h ai r def l ect or s of t he t ype i ndi cat ed. Pr ovi de ai r handl i ng t r of f er s or combi nat i on l i ght and cei l i ng di f f user s conf or mi ng t o t he r equi r ement s of UL El ect r i cal Const r uct n f or t he i nt er changeabl e use as cool ed or heat ed ai r suppl y di f f user s or r et ur n ai r uni t s. I nst al l cei l i ng mount ed uni t s wi t h r i ms t i ght agai nst cei l i ng. Pr ovi de sponge r ubber gasket s bet ween cei l i ng and sur f ace mount ed di f f user s f or ai r l eakage cont r ol . Pr ovi de sui t abl e t r i m f or f l ush mount ed di f f user s. For connect i ng t he duct t o di f f user , pr ovi de duct col l ar t hat i s ai r t i ght and does not i nt er f er e wi t h vol ume cont r ol l er . Pr ovi de r et ur n or exhaust uni t s t hat ar e s i mi l ar t o suppl y di f f user s.

2. 10. 8. 2 Regi st er s and Gr i l l es

Pr ovi de uni t s t hat ar e f our - way di r ect i onal - cont r ol t ype, except pr ovi de r et ur n and exhaust r egi st er s t hat ar e f i xed hor i zont al or ver t i cal l ouver t ype si mi l ar i n appear ance t o t he suppl y r egi st er f ace. Fur ni sh r egi st er s wi t h sponge- r ubber gasket bet ween f l anges and wal l or cei l i ng. I nst al l wal l suppl y r egi st er s at l east 6 i nches bel ow t he cei l i ng unl ess ot her wi se i ndi cat ed. Locat e r et ur n and exhaust r egi st er s 6 i nches above t he f l oor unl ess ot her wi se i ndi cat ed. Achi eve f our - way di r ect i onal cont r ol by a

SECTI ON 23 00 00 Page 17 gr i l l e f ace whi ch can be r ot at ed i n 4 posi t i ons or by adj ust ment of hor i zont al and ver t i cal…