49_24__TPF4.0_Overall_Supply_Plumbing_Schematic.pdf

PDF 439 KB Posted

Attached to
Tyndall AFB Temporary Modular Medical Facility Federal contract opportunity
Solicitation number
W9127S19Q6039
Issued by
Department of the Army Corps of Engineers Engineering District Little Rock

About this file

Part of Attachment I - As-Builts, 49-TPF Combined

View the file

Other files for this federal contract opportunity

Other files attached to Tyndall AFB Temporary Modular Medical Facility, newest first.
File Type Posted
55_TQ4.11D_-_FFE_PLAN_-_TPF_PHASE_2,_AREA_D.pdf PDF
49_23__TCP1.5_Combined_Clinic_TPF_RCP.pdf PDF
49_25__TPFV2.0_STANDARD_RAMP_AND_STAIR_DETAILS_STAMPED.pdf PDF
49_24__TPF2.0-PI_Full_Building_Plan-Phase_1.pdf PDF
1-V1.01_SURVEY_PLAN.pdf PDF
49_23__TCP1.3_Combined_Clinic_TPF_RCP.pdf PDF
55_TQ4.01_-_FFE_JSN_LEGEND.pdf PDF
1-V1.05_SURVEY_PLAN.pdf PDF
49_21__TFP3.3_Combined_Clinic_TPF_Fire_Suppression_Notes_and_Details.pdf PDF
49_21__TFP4.3_Combined_Clinic_TPF_Fire_Alarm_Details_and_Notes.pdf PDF
55_TQ3.11A_-_FFE_PLAN_-_TPF_PHASE_1,_AREA_A.pdf PDF
1-V1.04_SURVEY_PLAN.pdf PDF
49_25__TPFV4.0_STANDARD_RAMP_AND_STAIR_DETAILS_STAMPED.pdf PDF
55_TQ3.11C_-_FFE_PLAN_-_TPF_PHASE_1,_AREA_C.pdf PDF
36_10_TSP2.0_Plumbing_Schematics.pdf PDF
29_02_TNA3.0_Reflective_Ceiling_Plan.pdf PDF
36_14_TSFD1.0_Foundation_Plan_and_Details.pdf PDF
36_11_TSE4.0_MDP_-_One_Line_Diagram.pdf PDF
36_09_TSA3.0-PII_Reflective_Ceiling_Plan.pdf PDF
29_04_TNE1.0_Elec_Plan.pdf PDF
36_12_TSM1.0-PII_Mechanical_HVAC_Plan.pdf PDF
43_16_TCCA2.0_Floor_Plan.pdf PDF
36_10_TSP4.0_Plumbing_Plan_-_DWV_Phase_1.pdf PDF
36_11_TSE1.0-PII_Electrical_Plan.pdf PDF
36_09_TSA2.1_Interior_Elevations.pdf PDF
29_02_TNA1.0_Exterior_Elevations.pdf PDF
43_16_TCCA3.0_Reflective_Ceiling_Plan.pdf PDF
36_09_TSA2.0-PII_Floor_Plan_-_Phase_2.pdf PDF
29_02_TNA2.0_Floor_Plan.pdf PDF
29_06_TNX1.0_Building_Cross_Section.pdf PDF
43_16_TCCA1.0_Exterior_Elevations.pdf PDF
36_10_TSP3.0-PII_Plumbing_Plan_-_Supply_Phase_2.pdf PDF
07_E0-02_-_SYMBOL_LEGEND_AND_GENERAL_NOTES.pdf PDF
36_09_TSA2.0_Floor_Plan.pdf PDF
36_11_TSE3.0_Task_Lighting_Illumination_Plan.pdf PDF
29_02_TNA4.0_Egress_Plan.pdf PDF
36_09_TSA3.0_Reflective_Ceiling_Plan.pdf PDF
29_03_TNP2.0_Plumbing_Schematics.pdf PDF
43_16_TCCA4.0_Egress_Plan.pdf PDF
43_17_TCCE1.0_Elec_Plan.pdf PDF
29_04_TNE3.0_Task_Lighting_Illumination_Plan.pdf PDF
29_05_TNM1.0_Mechanical_HVAC_Plan.pdf PDF
W9127S19Q6039_Tyndall_TMMF_Combined_Synopsis_Solicitation_13Aug19.pdf PDF
Tyndall_TMMF_Statement_of_Work_13Aug19.pdf PDF
Attachment_F_-_Codes_&_Criteria.pdf PDF
Attachment_D_-_DHA_LAN_WLAN_Guides.pdf PDF
Attachment_A_-_Siting_&_Parking.pdf PDF
Attachment_C_-_AFMSA_Design_Guidance.pdf PDF
Attachment_B_-_Utility_Plans.pdf PDF
W9127S19Q6039_Tyndall_TMMF_Combined_Synopsis_Solicitation.pdf PDF
Show all 50

Tyndall AFB Temporary Modular Medical Facility has more files on GovTribe.

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

O V

E R

A

LL

S U

P P

LY

P

LU

M

B

IN

G S

C H

E M

A

TI

C

TPF-

4.0

A

54321

B

C

D

E

B A

S E

C

IV

IL

E

N G

IN

EE

R /D

EP

U

TY

C H

IE

F

E N

G

IN

E E

R

IN

G F

LI

G

H T

(C

EP

C H

IE

F

C O

N

TR

AC

TS

S

EC

TI

O

N (C

EP

M

R

EC

O M

M E

N D

ED

R

EC

O M

M E

N D

ED

A P

P R

O

VE

D

E N

G

IN

E E

R \D

ES

IG

N

ER

D R

A W

N B

Y

S C

A

LE

D

AT

E

R

EV

3/

/2

S O

LI

C

IT

AT

IO

N

N U

M B

ER

C O

N

TR

AC

T

N U

M

BE

R D

ES

IG

N T

E

AM

C

EP

M

U S

IN

G

A G

EN

C

Y

C H

E C

K

ED

B Y

H O

EF

ER

W

YS

O C

K I

A R

C H

IT

EC

TS

JE DUNN + HWA

CLEARWATER, FL 33756

CONSULTING ENGINEER

1765 CARNEGIE AVENUE

Ph: (727) 505-9941

JAMES E. BRADLEY, P.E.

J E B

0' 4' 8' 16' 32' 1/8" = 1'-0"

0' 2' 4' 8' 16' 1/4" = 1'-0"

0' 1' 2' 3/4" = 1'-0"

4'0' 1' 1 1/2" = 1'-0"

2' 2'1'6"6"3"0' 6" 3" = 1'-0"

1'3"

2500 INDUSTRIAL STREET LEESBURG, FL 34748 (352) 728-2930

TPF TYNDALL -

CONNECTING CORRIDOR

TY

N

D A

LL

A

FB

C

O N

N E

C

TI

N G

C O

R R

ID

O

R

M

A G

N O

LI

A

C

IR

C

LE

T

YN

D

AL

L A

FB

, F

L

A S

IN

D

IC

AT

ED

J.

L.

B.

W

5-

-R -6

W

5-

-D

-6

JA

M

E S

E . B

R A

D

LE

Y, P

.E

JE

D

U N

N

S U

B M

IT

TA

L #4

C

O R

R E

C

TE

D F

IN

A

L A

M E

N D

M E

N T

J.

E

.B

Sy m bo l

D es cr ip tio n

Tr ac ki ng

N o.

A ct io n

D at e

TPF TYNDALL - NORTH

PUBLIC HEALTH BLDG

TPF TYNDALL - SOUTH

AMBULANCE SERVICES BLDG

MODULE A

MODULE B

MODULE C

MODULE D

MODULE E

MODULE F

MODULE G

MODULE H

MODULE I

MODULE J

MODULE K

MODULE L

MODULE M

MODULE N

MODULE O

MODULE P

MODULE

PERIMETER

MODULE A

MODULE B

MODULE C

MODULE D

MODULE E

MODULE F

MODULE G

MODULE

MATELINE

MODULE H

MODULE I

MODULE J

MODULE K

MODULE L

MODULE M

MODULE N

MODULE O

MODULE P

MODULE A

MODULE B

MODULE C

MODULE D

MODULE E

MODULE F

MODULE G

MODULE H

MODULE I

MODULE J

MODULE K

MODULE L

MODULE M

MODULE N

MODULE O

MODULE P

REFERENCE UTILITY

PLAN 1-CU1.01 FOR

ADDITIONAL WASTE

PIPING INFORMATION

SUPPLY LINE NOTES:

1. SUPPLY LINE SIZING IS BASED ON AN ASSUMED AVAILABLE PRESSURE OF

60 PSI AT THE LOCATION OF THE INLET(S) SHOWN AFTER ANY DEDUCTIONS

FOR PRESSURE LOSS DUE TO METER, TAP INTO MAIN, WATER PRESSURE

REDUCING VALVES, SPECIAL EQUIPMENT SUCH AS BACKFLOW PREVENTOR,

FILTER, SOFTENER, ETC. THIS AVAILABLE PRESSURE MUST BE VERIFIED

PRIOR TO CONSTRUCTION. IF A BOOSTER PUMP IS NEEDED TO ACHIEVE

REQUIRED PRESSURE THEN THE BUILDING OWNER IS RESPONSIBLE FOR

DESIGN AND INSTALLATION OF PUMP SYSTEM.

2. SUPPLY LINE INLET(S) SHOWN ON THESE PLANS ARE ASSUMED TO

EXTEND ONLY TO EXTERIOR WALL. ALL SERVICE SUPPLY LINES UP TO THE

INLET(S) ARE DESIGNED BY OTHERS AND SITE INSTALLED UNLESS

OTHERWISE SPECIFIED.

3. SUPPLY LINE SIZING MUST BE REDESIGNED IF THE BUILDING DOES NOT

COMPLY WITH ANY OF THE ABOVE ASSUMPTIONS.

4. UNLESS OTHERWISE SPECIFIED ALL SUPPLY LINES ARE 1"Ø MINIMUM TO

FLUSHOMETER VALVE WATER CLOSETS AND 3/4"Ø MINIMUM TO ALL

OTHER FIXTURES. UNLESS OTHERWISE SPECIFIED ALL STUB-UPS ARE 1"Ø TO

FLUSHOMETER WATER CLOSETS, 3/4"Ø TO FLUSH VALVE URINALS AND

1/2"Ø TO ALL OTHER FIXTURES.

5. EACH URINAL SHALL NOT REQUIRE MORE THAN 15 PSI OF PRESSURE (12

GPM) TO ACTIVATE THE FLUSHOMETER VALVE.

6. EACH WATER CLOSET SHALL NOT REQUIRE MORE THAN 25 PSI OF

PRESSURE (25 GPM) TO ACTIVATE THE FLUSHOMETER VALVE.60 PSI AT MAIN INLET AND SHOULD BE VERIFIED

AN ASSUMED AVAILABLE PRESSURE OF 46 TO

SPECIFIED. SUPPLY LINE SIZING IS BASED ON

PRIOR TO CONSTURCTION.

STUB-UPS SHALL BE 1/2" UNLESS OTHERWISE

ALL SUPPLY LINES SHALL BE 3/4" AND ALL

SUPPLY RISER

COLD

HOT

SCALE: N.T.S.

SINK

SHOWER

SINK

WC

LAV

LAV SHOWER

LAV

SINK

WC

LAV

MOP

SINK

LAV

LAV

WC

URINAL

URINAL

LAV

LAV MOP

SINK

LAV

WC

WC

WC

WCLAV

LAV

MOP

SINK

SINK

SINK

SINK

SINK

LAV

1/2"

1/ 2"

1/ 2"

1/ 2"

WC

F.D.

w/T.P. 1/2"

3/4"

1/ 2"

1/ 2"

1/ 2"

1/ 2"

1/ 2"

1/ 2"

1/ 2"

1/ 2"

LAV

F.D.

w/T.P.

F.D.

w/T.P.

1/ 2"

1/ 2"

1/ 2"

1/ 2"

1/ 2"1/

2"

1/ 2"

1/ 2"

1/ 2"

1/ 2" 1/

2"1/ 2"

1/ 2"

1/ 2"

1/ 2"

3/ 4"

3/ 4"

1/ 2" 3/4"

1/2"

3/4"

1" 1/2"

3/4"

3/4"

3/4"

3/4"

1/2"

1"

1"

1"

1/ 2"

1/ 2"

1/ 2"

1/ 2" 1/2"1/2"

1/2"1/2"

F.D.

w/T.P.

F.D.

w/T.P.

3/4" 3/4"

3/4"

3/4" 3/4"

3/4" 3/4"

3/4"

3/4"

1/2"

F.D.

w/T.P.

1" 1"

3/4" 3/4"

1" 1"

1/ 2"1/

2"1/ 2"

1/ 2"

1/ 2"

1/ 2"

1/ 2"

1/ 2"

1/ 2"

1/ 2"

1/ 2"

1/ 2" 1/

2"

1/ 2"

1/ 2"

1/2"1/2"

WC

3/4"

3/4" 3/4"

1/2"

1/ 2"1/ 2"

1/ 2"

1/ 2"

1/ 2"

1/ 2"

1/ 2"

3/4"3/4"

3/4"3/4"

3/4"1"

1"

VALVE

T&P

30 GAL.

W/H

1"

VALVE

T&P

30 GAL.

W/H

3/4"

3/4"

3/4"

3/4"

3/4"

1/2"3/4" 1"

1/2"

1 1/4"

1 1/4"

1 1/4"

1 1/4"

1 1/4"

1 1/4"

1 1/4"

1 1/4"

1/2" 1/2"

1"

3/ 4"

3/ 4"

VALVE

T&P

30 GAL.

W/H

1/2"

1/2"

3/4"

3/4"

3/4"3/4"

3/4"

1/2"

3/4"

1/2"

REFERENCE TPF-5.0

FOR OVERALL WASTE

PIPING ISOMETRIC

STAINLESS

STEEL WALL

MOUNTED

HAND SINK

1/ 2"

1/ 2"

SINK

1/ 2"

1/ 2"

3/4"

1/2" 1/2"

EYE

WASH

STATION

1/2"

1/2"1/2"

MODULE

PERIMETER

MODULE A

MODULE B

MODULE C

MODULE D

MODULE E

MODULE F

MODULE G

MODULE

MATELINE

MODULE H

MODULE I

MODULE J

MODULE K

MODULE L

MODULE M

MODULE N

MODULE O

MODULE P

MODULE H

SINK

SINK

LAV

LAV

LAV

WC

LAV

WC

LAV

LAV

LAV

LAV

LAV

LAV

LAV

MOP

SINK

LAV

LAV

1/2"

1/ 2"1/

2"

3/4"

1/ 2"1/

2"

VALVE

T&P

30 GAL.

W/H

1" A-112

1"

1"

1"

1"

1" 1/2"

SINK

1/2"

1/ 2"1/

2" 1/2"

1/2"

1/2"

3/4"

3/4"

1/2" 1/2"

LAV

LAV 3/4"

3/4"

1/2" 1/2"

LAV

1/2"

1/2"

1/2"

3/4"

3/4"

3/4"

3/4"

WF

1/2"

1"

1"

1"

1" 3/4"

3/4"

3/4"

1"

1"

1/2"

1/ 2"1/

2"

1/2"

1/ 2"1/

2"

1/ 2"1/

2"

1/2"

1/2"

1/2"

1/2"

1/2"

1/2"

1"

1 1/4"

1 1/4"

1" 3/4"

1/2"

1/2"

1/ 2"1/ 2"

1/ 2"

WC

1/ 2"1/

2"

1 1/4"

1 1/4"

1 1/4"

1 1/4"

1/ 2"

1/ 2"

1/ 2"

1/ 2"

1/ 2"

1/ 2"1/ 2"

1/ 2"

1/ 2"

1/ 2"1/ 2"

1/ 2"

1/ 2"

1/ 2"

1/ 2"

1/ 2"

1/ 2"

1/ 2"

1/ 2"

1/ 2"

1/ 2"

1/ 2"

1/ 2"

1/ 2"

1/ 2"

1/ 2"

F.D.

w/T.P.

F.D.

w/T.P.

F.D.

w/T.P.

F.D.

w/T.P.

1"

1"

1"

1"

1"

3/4"

1"

1"

1"

1"

1"

1"

1"

1"

1"

1"

1"

1"

1"

1/2"

3/4"

FLOW

FLOW

FLOW

FLOW

FLOW

FLOW

FLOW

FLOW

FLOW

FLOW

FLOW

FLOW

FLOW

FLOW

FLOW

FLOW

FLOW

FLOW

FLOW

FLOW

FLOW

HOT RETURN

P D

F cr ea te d w ith p df Fa ct or y tri al v er si on w w w

.p df fa ct or y.

co m http://www.pdffactory.com tim.kitchens Snapshot

File details come from the government source that posted it.