49_24__TPF2.1-P2_Full_Building_Plan_Phase_2.pdf

PDF 649 KB Posted

Attached to
Tyndall AFB Temporary Modular Medical Facility Federal contract opportunity
Solicitation number
W9127S19Q6039
Issued by
Department of the Army Corps of Engineers Engineering District Little Rock

About this file

Part of Attachment I - As-Builts, 49-TPF Combined

View the file

Other files for this federal contract opportunity

Other files attached to Tyndall AFB Temporary Modular Medical Facility, newest first.
File Type Posted
1-V1.04_SURVEY_PLAN.pdf PDF
49_25__TPFV4.0_STANDARD_RAMP_AND_STAIR_DETAILS_STAMPED.pdf PDF
55_TQ3.11C_-_FFE_PLAN_-_TPF_PHASE_1,_AREA_C.pdf PDF
55_TQ3.11_-_FFE_PLAN_-_TPF_PHASE_1.pdf PDF
55_TQ4.11C_-_FFE_PLAN_-_TPF_PHASE_2,_AREA_C.pdf PDF
49_24__TPF3.0_Full_Luminary_Plan.pdf PDF
49_23__TCP1.2_Combined_Clinic_TPF_RCP.pdf PDF
49_23__TCP1.0_Combined_Clinic_TPF_RCP.pdf PDF
55_TQ3.11B_-_FFE_PLAN_-_TPF_PHASE_1,_AREA_B.pdf PDF
49_24__TPF7.0_Overall_Plumbing_Plan_-_D.W.V.pdf PDF
49_25__TPFV3.0_STANDARD_RAMP_AND_STAIR_DETAILS_STAMPED.pdf PDF
49_25__TPFV5.0_STANDARD_CANOPY_DETAILS_STAMPED.pdf PDF
55_TQ4.11D_-_FFE_PLAN_-_TPF_PHASE_2,_AREA_D.pdf PDF
49_23__TCP1.5_Combined_Clinic_TPF_RCP.pdf PDF
49_25__TPFV2.0_STANDARD_RAMP_AND_STAIR_DETAILS_STAMPED.pdf PDF
49_24__TPF2.0-PI_Full_Building_Plan-Phase_1.pdf PDF
29_06_TNX1.0_Building_Cross_Section.pdf PDF
43_16_TCCA1.0_Exterior_Elevations.pdf PDF
36_10_TSP3.0-PII_Plumbing_Plan_-_Supply_Phase_2.pdf PDF
07_E0-02_-_SYMBOL_LEGEND_AND_GENERAL_NOTES.pdf PDF
36_09_TSA2.0_Floor_Plan.pdf PDF
36_11_TSE3.0_Task_Lighting_Illumination_Plan.pdf PDF
29_02_TNA4.0_Egress_Plan.pdf PDF
36_09_TSA3.0_Reflective_Ceiling_Plan.pdf PDF
29_03_TNP2.0_Plumbing_Schematics.pdf PDF
43_16_TCCA4.0_Egress_Plan.pdf PDF
43_17_TCCE1.0_Elec_Plan.pdf PDF
29_04_TNE3.0_Task_Lighting_Illumination_Plan.pdf PDF
29_05_TNM1.0_Mechanical_HVAC_Plan.pdf PDF
36_10_TSP4.0-PII_Plumbing_Plan_-_DWV_Phase_2.pdf PDF
36_10_TSP1.0_Plumbing_Schematics.pdf PDF
36_09_TSA1.0_Exterior_Elevations.pdf PDF
W9127S19Q6039_Tyndall_TMMF_Response_to_Questions_19Aug19.pdf PDF
29_04_TNE4.0_MDP_-_One_Line_Diagram.pdf PDF
05_1-CU1.02_UTILITY_PLAN_-_PHASE_2_AND_3.pdf PDF
29_03_TNP3.0_Plumbing_Plan.pdf PDF
36_10_TSP2.0_Plumbing_Schematics.pdf PDF
29_02_TNA3.0_Reflective_Ceiling_Plan.pdf PDF
36_14_TSFD1.0_Foundation_Plan_and_Details.pdf PDF
36_11_TSE4.0_MDP_-_One_Line_Diagram.pdf PDF
36_09_TSA3.0-PII_Reflective_Ceiling_Plan.pdf PDF
29_04_TNE1.0_Elec_Plan.pdf PDF
36_12_TSM1.0-PII_Mechanical_HVAC_Plan.pdf PDF
W9127S19Q6039_Tyndall_TMMF_Combined_Synopsis_Solicitation_13Aug19.pdf PDF
Attachment_C_-_AFMSA_Design_Guidance.pdf PDF
Attachment_B_-_Utility_Plans.pdf PDF
W9127S19Q6039_Tyndall_TMMF_Combined_Synopsis_Solicitation.pdf PDF
Attachment_G_-_PFD_TYNDALL_TPF_v2_20190702.pdf PDF
Attachment_F_-_Codes_&_Criteria.pdf PDF
Attachment_D_-_DHA_LAN_WLAN_Guides.pdf PDF
Show all 50

Tyndall AFB Temporary Modular Medical Facility has more files on GovTribe.

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

F U

L L

B U

IL

D

IN

G

P L A

N

P H

A S

E

TPF-

2.1 - P2

A

54321

B

C

D

E

B A

S E

C

IV

IL

E

N G

IN

E

E R

/D E

P U

T Y

C H

IE

F

E N

G

IN

E E

R

IN

G F

L

IG

H T

C

E P

C H

IE

F

C O

N T

R A

C T

S S

E C

T

IO

N

C E

P M

R E

C O

M M

E N

D E

D

R E

C O

M M

E N

D E

D

A P

P R

O V

E D

E N

G

IN

E E

R \D

E S

IG

N

E R

D R

A W

N B

Y

S C

A L

E

D A

T E

R

E V

3/

/2

S O

L

IC

IT

A

T

IO

N N

U M

B E

R

C O

N T

R A

C T

N U

M B

E R

D E

S

IG

N T

E A

M C

E P

M

U S

IN

G

A G

E N

C Y

C H

E C

K E

D B

Y

H O

E F

E R

W Y

S O

C K

I A

R C

H

IT

E C

T S

JE DUNN + HWA

CLEARWATER, FL 33756

CONSULTING ENGINEER

1765 CARNEGIE AVENUE

Ph: (727) 505-9941

JAMES E. BRADLEY, P.E.

J E B

0' 4' 8' 16' 32'

1/8" = 1'-0"

0' 2' 4' 8' 16'

1/4" = 1'-0"

0' 1' 2'

3/4" = 1'-0"

4'0' 1'

1 1/2" = 1'-0"

2' 2'1'6"6"3"0' 6"

3" = 1'-0"

1'3"

2500 INDUSTRIAL STREET LEESBURG, FL 34748 (352) 728-2930

TPF TYNDALL -

CONNECTING CORRIDOR

T Y

N D

A L

L A

F B

C O

N N

E C

T

IN

G C

O R

R

ID

O R

M

A G

N O

L

IA

C

IR

C L

E T

Y N

D A

L L

A F

B

F L

A S

I N

D

IC

A T

E D

J .L

.B

W

-1

-R -6

W

-1

-D -6

J A

M E

S E

B

R A

D L

E Y

P

.E

J E

D U

N N

S U

B M

IT

T

A L

C O

R R

E C

T E

D F

IN

A

L A

M E

N D

M E

N T

J .E

.B

& ASSOCIATES

HILBORN, WERNER, CARTER

1627 SOUTH MYRTLE AVE.

CLEARWATER, FLORIDA 33756

THIRD PARTY:

S y m b o l

D es cr ip ti o n T ra ck in g N o

A ct io n

D at e

TPF TYNDALL - NORTH

PUBLIC HEALTH BLDG

TPF TYNDALL - SOUTH

AMBULANCE SERVICES BLDG

OVERALL FLOOR PLAN - PHASE 2

SCALE: N.T.S.

CORRIDOR CORRIDOR

PANEL "B"

100 AMP

120/208v, 1Ø

PANEL "A"

100 AMP

120/208v, 1Ø

NOTE: DO NOT INSTALL

REMOTE HEADS IN CORRIDOR

INSTALL PLATES, TYP.

DN

DN

DN

DN

ED A

186'-8"

11'-8"

11'-8" 11'-8" 11'-8" 11'-8" 11'-8" 11'-8" 11'-8" 11'-8" 11'-8" 11'-8" 11'-8" 11'-8" 11'-8" 11'-8" 11'-8"

25'-0"

60'-0" 62'-0"

186'-8"

11'-8" 11'-8" 11'-8" 11'-8" 11'-8" 11'-8" 11'-8" 11'-8" 11'-8" 11'-8" 11'-8" 11'-8" 11'-8" 11'-8" 11'-8" 11'-8"

39'-8"

DN

A B C i K MJ L N o P

3/0x6/8 3/0x6/8 3/0x6/8

/0 x6

/8

3/0x6/8

3/0x6/8 3/0x6/8

3/0x6/8

3/0x6/8 3/0x6/8 3/0x6/8 3/0x6/8 3/0x6/8 3/0x6/8

3/0x6/8

3/0x6/8 3/0x6/83/0x6/8

/0 x6 /8

/0 x6 /8

/0 x6 /8

3/0x6/8

3/0x6/8 3/0x6/8 3/0x6/83/0x6/8

3/0x6/83/0x6/83/0x6/83/0x6/8

3/0x6/8 3/0x6/8

/0 x6 /8

/0 x6 /8

/0 x6 /8

/0 x6 /8

3/0x6/8

3/0x6/8

/0 x6 /8

/0 x6 /8

3/0x6/8 3/0x6/8

3/0x6/83/0x6/8

3/0x6/8 3/0x6/8

/0 x6 /8

3/0x6/83/0x6/8

3/0x6/83/0x6/83/0x6/84/0x6/8 3/0x6/83/0x6/8

MEDICAL

STANDARDS

OFFICE

(MSME)

PROVIDER

OFFICE

PHA

TECHNICIAN

WORKSTATION

PHA

TECHNICIAN

WORKSTATION

NURSE

WORKROOM

SOILED

UTILITY

NCOIC

OFFICE

OIC

OFFICE

PHA

INTERVIEW

ROOM

STAFF

TOILET

JANITOR'S

CLOSET

30 GAL

W/H

ELECTRICAL

ROOM

COMM

ROOM

PHA/DEPLOYMENT

MED/EXAM

ROOM

LPN

OFFICE

NCOIC

OFFICE

OIC

OFFICE

OPTOMETRIST

OFFICE

VISUAL

FIELD

OPTOMETRIST

OFFICE

SUB-WAITING

TOILET

COPY/FILE

DISTRORECEPTIONWAITING

VISUAL

SCREENING

MULTI-DIAGNOSTIC

ROOM

PUBLIC

HEATH

CENTER

AUDIO

TESTINGTECH

OFFICE /

INT OCC

HEALTH

EXAM

ROOM

EXAM

ROOM

IDMT

EXAM

ROOM

EXAM

ROOM

CLEAN

UTILITY

PROVIDER

OFFICE/OICY

PROVIDER

OFFICE

PROVIDER

OFFICE

TECHNOLOGY

OFFICE

STAFF

LOUNGE/TEAM

CONFERENCE

ROOM

TECH

TECH

IDMT

TECH

IDMT

TECH

EXAM

ROOM

EXAM

ROOM

EXAM

ROOM

TREATMENT

ROOM

MULTI-DIAGNOSTIC

ROOM

TECH

RECORD

FIXED

SHELVING

TECHNICIAN

OFFICE/INTERVIEW

COMMUNITY

HEALTH

COPY/FILE

DISTRO

DEPLOYMENT

MED OFFICE

COUNSELING

ROOM

TECHNICIAN

OFFICE/INTERVIEW

COMMUNITY

HEALTH

AUDIO

TESTING

FULL

EYE-LANE

FULL

EYE-LANE

FRAMES

CONTACTS

STORAGE

FOLDED

EYE-LANE

FOLDED

EYE-LANE

FITTING

DISPENSING

AREA

/0 x5 /0

V S

2/0x5/0VS

2/0x5/0VS

2/0x5/0VS

2/0x5/0VS

2/0x5/0VS

2/0x5/0VS

/0 x5 /0

V S

/0 x5 /0

V S

/0 x5 /0

V S

/0 x5 /0

V S

/0 x5 /0

V S

B

B

B

B

B

B

B

B

B

B

B B

B

B

B

B B

B

B

B

B B

B

B

B

B

B

B B

B

B H H H A H H H H H H H H H

D

D

B

B

B

D

B

D

B

B B

B

A B B B B

B B B B B B B B B B B B

B

B B B

B B B

B B B B

D

B

B B B B

BB B B

B B B B

B B

B B

B

B B

B B B B B B B

B

C

B

B

B

B B B F B B B B

B

BBBB

B B

B B

3 3

D

D

B

B

B

B B

B B B

B B8

8 EE

E E

B

B

SITE INSTALLED STRUCT

HEADER; TYP. of (2)

D

(4

LA

Y

E R

/4 x

P

LY

W

O O

D

(4

LA

Y

E R

/4 x

P

LY

W

O O

D

(4

LA

Y

E R

/4 x

P

LY

W

O O

D

(4

LA

Y

E R

/4 x

P

LY

W

O O

D

(4

LA

Y

E R

/4 x

P

LY

W

O O

D

(4

LA

Y

E R

/4 x

P

LY

W

O O

D

(4

LA

Y

E R

/4 x

P

LY

W

O O

D

(4

LA

Y

E R

/4 x

P

LY

W

O O

D

(4

LA

Y

E R

/4 x

P

LY

W

O O

D

(4

LA

Y

E R

/4 x

P

LY

W

O O

D

(4

LA

Y

E R

/4 x

P

LY

W

O O

D

(4

LA

Y

E R

/4 x

P

LY

W

O O

D

(4

LA

Y

E R

/4 x

P

LY

W

O O

D

(4

LA

Y

E R

/4 x

P

LY

W

O O

D

(4

LA

Y

E R

/4 x

P

LY

W

O O

D

(4

LA

Y

E R

/4 x

P

LY

W

O O

D

(4

LA

Y

E R

/4 x

P

LY

W

O O

D

(4

LA

Y

E R

/4 x

P

LY

W

O O

D

(4

LA

Y

E R

/4 x

P

LY

W

O O

D

(4

LA

Y

E R

/4 x

P

LY

W

O O

D

(4

LA

Y

E R

/4 x

P

LY

W

O O

D

(4

LA

Y

E R

/4 x

P

LY

W

O O

D

(4

LA

Y

E R

/4 x

P

LY

W

O O

D

(4

LA

Y

E R

/4 x

P

LY

W

O O

D

(4

LA

Y

E R

/4 x

P

LY

W

O O

D

(4

LA

Y

E R

/4 x

P

LY

W

O O

D

(4

LA

Y

E R

/4 x

P

LY

W

O O

D

(4

LA

Y

E R

/4 x

P

LY

W

O O

D

60"x12"(D) LAMINATED

COUNTER AT 34" A.F.F.

60"x12"(D) LAMINATED

COUNTER AT 34" A.F.F.

60"x12"(D) LAMINATED

COUNTER AT 34" A.F.F.

C-116

175.44 SF

V.C.T.

C-117

108.00 SF

V.C.T.

C-118b

123.33 SF

V.C.T.

C-122

123.33 SF

V.C.T.

C-120

84.00 SF

V.R.G.

C-124

123.33 SF

V.C.T.

C-125

116.00 SF

V.C.T. D-108

92.00

SF

V.C.T.

A-110

57.85 SF

V.R.G.

A-112

76.00 SF

V.C.T.

D-114

108.00 SF

V.C.T.

D-112

108.00 SF

V.C.T.

D-116

108.00 SF

V.C.T.

D-117

104.00 SF

V.C.T.

D-118

108.00 SF

V.C.T.

D-119

108.00 SF

V.C.T.

E-110

108.00 SF

V.C.T.

E-111

108.00 SF

V.C.T.

E-112

187.78 SF

V.C.T.

E-113

60.00 SF

V.C.T.

E-115

57.17 SF

V.C.T.

E-102a

52.36 SF

V.C.T.

E-102

94.79 SF

V.C.T.

E-101

176.94 SF

V.C.T.

E-103

118.85 SF

V.C.T.

E-104

144.44 SF

V.C.T.

D-107

93.33 SF

V.C.T.

D-106

93.33 SF

V.C.T.

D-103

93.33 SF

V.C.T.

C-104

110.84 SF

V.C.T.

C-106

110.84 SF

V.C.T.

110.84 SF

V.C.T.

C-110

93.33 SF

V.C.T.

C-111

105.63 SF

V.C.T.

C-112

105.63 SF

V.C.T.

C-114

105.63 SF

V.C.T.

C-115

105.63 SF

V.C.T.

C-109

279.56 SF

V.C.T.

C-107

105.15 SF

V.C.T.

C-105

106.08 SF

V.C.T.

C-103

105.15 SF

V.C.T.

C-121

160.06 SF

V.C.T.

C-123

146.81 SF

V.C.T.

A-516

147.00 SF

V.C.T.

D-110

81.00 SF

V.C.T.

C-102a

195.56 SF

V.C.T.

D-115

137.72 SF

V.C.T.

D-113

115.38 SF

V.C.T. D-105

89.33 SF

V.C.T.D-104

89.33 SF

V.C.T.

E-108

200.43 SF

V.C.T.

E-109

200.43 SF

V.C.T.

E-114

108.33 SF

V.C.T.

E-107

156.33 SF

V.C.T.

E-105

156.33 SF

V.C.T.

E-116

108.33 SF

V.C.T.

C-113c

140.00 SF

V.C.T.

PANEL "A"

150 AMP

120/208v, 1Ø

PANEL "B"

150 AMP

120/208v, 1Ø

PANEL "C"

150 AMP

120/208v, 1Ø

PANEL "D"

150 AMP

120/208v, 1Ø

PANEL "E"

150 AMP

120/208v, 1Ø

PANEL "F"

150 AMP

120/208v, 1Ø

PANEL "G"

150 AMP

120/208v, 1Ø

PANEL "H"

150 AMP

120/208v, 1Ø

PANEL "i"

150 AMP

120/208v, 1Ø

PANEL "J"

150 AMP

120/208v, 1Ø PANEL "K"

150 AMP

120/208v, 1Ø

PANEL "L"

150 AMP

120/08v, 1Ø

PANEL "M"

150 AMP

120/208v, 1Ø

PANEL "N"

150 AMP

120/208v, 1Ø

PANEL "o"

150 AMP

120/208v, 1Ø

PANEL "P"

150 AMP

120/208v, 1Ø

(2) 2" CONDUITS

UP THRU FLOOR

I/ D

U N

IT

O/D UNIT

3/4" x 48"x96" PLYWOOD

PAINTED WITH FIRE

RESISTANT PAINT, TYP.

6/0x6/8

/0 x6 /8

B

MULTI-DIAGNOSTIC

ROOM

E-106

148.89 SF

V.C.T.

B 3/0x6/8

E

C-117a c-118a

WAITING

C-101

431.68 SF

V.C.T.

C-108

C-108a

C-113a

C-113b

C-113d

A-511

RECEPTION RECEPTION

C-102 D-102

COPY/FILE

DISTRO

C-102a

3/0x6/8

B

/0 x6 /8

B

3/0x6/8

E

3/0x6/8

E

A

3/0x6/8

B

/0 x6 /8

B

STORAGE

C-117b

63.00 SF

V.C.T.

B

STAFF

TOILET

A-111

57.85 SF

V.R.G.

PHA

INTERVIEW

ROOM

D-109

94.00

SF

V.C.T.

PHA

INTERVIEW

ROOM

D-111

94.00

SF

V.C.T.

3/0x6/8

B 3/0x6/8

B

A 4

24"(D) LAMINATE

COUNTER-TOP @

30" A.F.F.

24"(D) LAMINATE

COUNTER-TOP @

30" A.F.F.

B

STC 50

STC 50 STC 50 STC 50

STC 50STC 50STC 50

A

TNA2.1

B

TNA2.1

H

TNA2.1

C

TNA2.1

D

TNA2.1

G

TNA2.1

E

TNA2.1

F

TNA2.1

E

TNA2.1

F

TNP1.0

STC 50

CORRIDOR

D-101

WAITING

TECH

WORKSTATION

E-116a

LINE PLENUM WALL WITH

MIN. 1/2" GYPSUM, TYP.

3/0x5/0VS

A B C D E F G H i J K L M N o P

4/0x6/8

3/0x6/8

/0 x6 /8

3/0x6/8

/0 x6 /8

3/0x6/8

3/0x6/8

/0 x6 /8

3/0x6/83/0x6/8

/0 x6 /8

/0 x6 /8

/0 x6 /8

/0 x6 /8

3/0x6/8

3/0x6/8

/0 x6 /8

3/0x6/8

3/0x6/8

3/0x6/8

/0 x6 /8

/0 x6 /8

3/0x6/8

/0 x6 /8

/0 x6 /8

/0 x6 /8

/0 x6 /8

/0 x6 /8

3/0x6/8 3/0x6/8

3/0x6/8

/0 x6 /8

/0 x6 /8

STORAGE

3/0x6/8

STAFF

LOUNGE/TEAM

CONFERENCE

ROOM

NCO

OFFICE

(SHARED)

PERSONAL

PROPERTY

LOCKERS

PATIENT

TOILET

STAFF

TOILET JANITOR'S

CLOSET

30 GAL

W/H

STAFF

LOUNGE /

CONFERENCE

ROOM

WAITING

COMM

ROOM

SHIPPING/

RECEIVING

TECHNICAL

SUPERVISOR

SHARED

NCOIC

OFFICE

OIC

OFFICE

CENTRAL

STORAGE

M/TLT

MICRO

BIOLOGY

JANITOR

30 GAL

W/H

F/TLT

SPECIMEN

TOILET

WAITING

RECEPTION

COPY/FILE

DISTRO

TECH

TECH

BLOOD

DRAW AREA

CORE

LAB

STAFF

LOUNGE/TEAM

CONFERENCE

ROOM

/0 x5 /0

V S

/0 x5 /0

V S

/0 x5 /0

V S

2/0x5/0VS

2/0x5/0VS

2/0x5/0VS

2/0x5/0VS

LINE PLENUM WALL WITH

MIN. 1/2" GYPSUM, TYP.

LINE PLENUM WALL WITH

MIN. 1/2" GYPSUM, TYP.

PANEL "A"

150 AMP

120/208v, 1Ø

F

PANEL "B"

150 AMP

120/208v, 1Ø

PANEL "C"

150 AMP

120/208v, 1Ø

PANEL "D"

150 AMP

120/208v, 1Ø

PANEL "E"

150 AMP

120/208v, 1Ø

PANEL "F"

150 AMP

120/208v, 1Ø

PANEL "G"

150 AMP

120/208v, 1Ø

PANEL "H"

150 AMP

120/208v, 1Ø

PANEL "i"

150 AMP

120/208v, 1Ø

PANEL "J"

150 AMP

120/208v, 1Ø

PANEL "K"

150 AMP

120/208v, 1Ø PANEL "L"

150 AMP

120/208v, 1Ø

PANEL "M"

150 AMP

120/208v, 1Ø

PANEL "N"

150 AMP

120/208v, 1Ø

PANEL "o"

150 AMP

120/208v, 1Ø

PANEL "P"

150 AMP

120/208v, 1Ø

B B

B

F

D

HK

A

E

EB

C

C

C

DD

C

C

CC

C

C

C

C

D

C

C

C

C

C

D

C G

C

C

C

H

B

B

B

D

D

B

C

F

B

C

B

B B

F

H J

F F

F

B

F

EXERCISE

AREA

F

B B

B

B

B

B

H

B

B B

B

B

H H H HB B B

D

D

D

D D

D

D

D

D D

D

B

B

B

B

B

B

B

B

B

B

B

B B

D

D

F

B-102

82.50 SF

V.C.T.

B-104

343.75 SF

V.C.T.

B-101

94.50 SF

CARPET

S-102

126.67 SF

CARPET

V.C.T.

V.C.T.

G-109a

63.89 SF

V.R.G.

G-109b

46.67 SF

V.R.G.

A-107

61.83 SF

V.R.G.

G-108

35.00 SF

V.R.G.

A-106

114.67 SF

V.C.T.

G-107

80.00 SF

CARPET

G-106

80.00 SF

CARPET

G-101

153.75 SF

V.C.T.

G-103

565.76 SF

V.C.T.

G-103

556.28 SF

V.C.T.

A-101

145.00 SF

CARPET

A-102

145.00 SF

V.C.T.

G-105

166.75 SF

V.C.T.

G-104

166.75 SF

V.C.T.

A-105

170.00 SF

V.C.T.

A-104

60.00 SF

V.R.G.

A-103

170.00 SF

V.C.T.

K-107

164.33 SF

V.C.T.

K-103

314.33 SF

V.C.T.

K-104

108.00 SF

V.C.T.

K-104a

108.00 SF

V.C.T.

K-101

279.00 SF

V.C.T.

K-102

52.50 SF

V.R.G.

K-108

225.50 SF

V.C.T.

K-109

102.00 SF

CARPET

K-111

106.72 SF

CARPETK-112

151.67 SF

V.C.T.

P-106

520.67 SF

CARPET

113.34 SF

CARPET

K-105a

106.67 SF

V.C.T.

K-105

735.00 SF

V.C.T.

P-101

195.00 SF

V.C.T.

A-108

281.64 SF

V.C.T.

V.C.T.

V.C.T.

V.C.T.

V.C.T.

P-102

98.82 SF

CARPET

P-103

140.83 SF

CARPET

V.C.T.

V.C.T.

V.C.T.

A

(4

LA

Y

E R

/4 x

P

LY

W

O O

D

(4

LA

Y

E R

/4 x

P

LY

W

O O

D

(4

LA

Y

E R

/4 x

P

LY

W

O O

D

(4

LA

Y

E R

/4 x

P

LY

W

O O

D

(4

LA

Y

E R

/4 x

P

LY

W

O O

D

(4

LA

Y

E R

/4 x

P

LY

W

O O

D

(4

LA

Y

E R

/4 x

P

LY

W

O O

D

(4

LA

Y

E R

/4 x

P

LY

W

O O

D

(4

LA

Y

E R

/4 x

P

LY

W

O O

D

(4

LA

Y

E R

/4 x

P

LY

W

O O

D

(4

LA

Y

E R

/4 x

P

LY

W

O O

D

(4

LA

Y

E R

/4 x

P

LY

W

O O

D

(4

LA

Y

E R

/4 x

P

LY

W

O O

D

(4

LA

Y

E R

/4 x

P

LY

W

O O

D

(4

LA

Y

E R

/4 x

P

LY

W

O O

D

(4

LA

Y

E R

/4 x

P

LY

W

O O

D

(4

LA

Y

E R

/4 x

P

LY

W

O O

D

(4

LA

Y

E R

/4 x

P

LY

W

O O

D

(4

LA

Y

E R

/4 x

P

LY

W

O O

D

(4

LA

Y

E R

/4 x

P

LY

W

O O

D

(4

LA

Y

E R

/4 x

P

LY

W

O O

D

(4

LA

Y

E R

/4 x

P

LY

W

O O

D

(4

LA

Y

E R

/4 x

P

LY

W

O O

D

(4

LA

Y

E R

/4 x

P

LY

W

O O

D

(4

LA

Y

E R

/4 x

P

LY

W

O O

D

(4

LA

Y

E R

/4 x

P

LY

W

O O

D

60"x12"(D) LAMINATED

COUNTER AT 34" A.F.F.

FLOORS:

NOTE: FLOOR JOISTS IN

UNITS "G & H" FROM 32'-0"

TO 40'-0" TO BE 12" O.C.

/0 x6 /8

STAFF

TOILET

D

B-103

61.83 SF

V.R.G.

/0 x6 /8

F

3/0x6/8

C

ON-CALL

ROOM

B-105

66.00 SF

V.C.T.

/0 x6 /8

C

KITCHEN

B-104a

K-105b

STAFF

TOILET

JANITOR

A-106

38.50 SF

V.R.G.

K-106

30.00 SF

V.R.G.

H

3/0x6/8

C

/0 x6 /8

C

/0 x6

/8

C

A1.0

3/0x6/8

/0 x6 /8

D

/0 x6 /8 C

P-105

75.83 SF

V.C.T.

3/0x6/8

C

A-646

110.00 SF

CARPET

C

D

3/0x6/8

CC

G-107

118.08 SF

V.C.T.

PATIENT

TOILET

B

(4

LA

Y

E R

/4 x

P

LY

W

O O

D

(4

LA

Y

E R

/4 x

P

LY

W

O O

D

HSMR

STORAGE

STORAGE

/0 x6 /8

C

3/0x6/8

C

747.40 SF

V.C.T.

168.42 SF

V.C.T.

FIT

170.00 SF

V.C.T.

LIBRARY

79.33 SF

V.C.T.

3/0x6/8

C

OFFICEOFFICE

STORAGE

BEE

WORK ROOM

OFFICE

LAB

VACANTVACANT

BMET

VACANT

VACANT

VACANT

VACANT

VACANT

/0 x6 /8

C

B

B

B

30 GAL

W/H

3/0x6/8

C

NON-STRUCT

HEADER; SITE

INSTALL DOOR

3/0x6/8

B

/0 x6 /8

G

B

D

CANOPY

C

3/0x6/8

C

ON-CALL

ROOM

B-106

66.00 SF

V.C.T.

C

TSA2.1

B

TSA2.1

A

TSA2.1

D

TSA2.1

E

TSA2.1

E

TSA2.1

E

TSA2.1

F

TSA2.1

H

TSA2.1

G

TSA2.1

J

TSA2.1

K

TSA2.1

M

TSA2.1

L

TSA2.1

N

TSA2.1

P

TSA2.1

E

TSA2.1

Q

TSA2.1

R

TSA2.1

S

IN

K

SINK S

IN

K

NOTE: CORE LAB FLOOR DEFLECTION

"L/240" TO BE LESS THAN 1/8 INCH

B U

LK

H

E A

D

B U

LK

H

E A

D

BULKHEAD

B U

LK

H

E A

D

B U

LK

H

E A

D

B U

LK

H

E A

D

STAINLESS STEEL

WALL MOUNTED

HAND SINK

/0 x6 /8

C

EMERGENCY DRENCH

SHOWER/EYEWASH STATION

O/D UNIT