HAAW179035_Fire Alarm_ADDENDUM-001.pdf

PDF 695 KB Posted

Attached to
Squadron Operations Center Build / Upgrade Federal contract opportunity
Solicitation number
W50S8N20B0001
Issued by
Department of the Army National Guard

About this file

This document contains details for a federal construction contract opportunity and related solicitation documents. The solicitation seeks bids for Project No. HAAW179035, which includes the construction of a new 3,365 square foot, one-story addition to an existing building and renovations and upgrades to an existing Squadron Operations Facility building at Hancock Field Air National Guard Base in Syracuse, NY. Work will be performed in accordance with the contract, plans, and technical specifications. The North American Industry Classification code is 236220 and the size standard for small businesses is $39.5M average annual revenue. The project magnitude is between $1M and $5M. Bids are due by the date specified in the solicitation and funds are expected to become available by September 30, 2020. This action has been identified on the National Guard priority list contingent upon available funding and prices within an awardable range.

View the file

Other files for this federal contract opportunity

Other files attached to Squadron Operations Center Build / Upgrade, newest first.
File Type Posted
Bid Opening Sign In.pdf PDF
Bid Abstract.pdf PDF
Questions and Answers 29 May 2020.docx DOCX document
W50S8N20B00010004 Amendment.pdf PDF
Questions and Answers 27 May 2020.docx DOCX document
W50S8N20B00010004 Amendment.pdf PDF
W50S8N20B00010003 Amendment.pdf PDF
Questions and Answers 20 May 2020.docx DOCX document
HAAW179035-Addendum 02 - Dwg_R-A-601.pdf PDF
HAAW162100-Addendum 02 - Dwg_S-A-601.pdf PDF
HAAW162100-Addendum 02 - Spec_09 29 00.pdf PDF
W50S8N20B00010001 Amendment.pdf PDF
HAAW179035-Addendum 02 - Spec_09 29 00.pdf PDF
W50S8N20B00010002 Amendment.pdf PDF
Questions and Answers 18 May 2020.docx DOCX document
Tax Form NY ST120_1_fill_in.pdf PDF
HAAW179035-Addendum 02 - Spec_08 14 00.pdf PDF
HAAW179035-Addendum 02 - Spec_23 11 25.pdf PDF
HAAW162100-Addendum 02 - Spec_08 14 00.pdf PDF
W50S8N20B00010001 Amendment.pdf PDF
HAAW179035_Arch_ADDENDUM-001.pdf PDF
HAAW179035_Elec_Comm_ADDENDUM-001.pdf PDF
Pre-bid Slides HAAW179035-HAAW162100.pptx PPTX presentation
B643 Pre-Bid Sign In Sheet.pdf PDF
Attachment 7 - HAAW162100 Drawings.pdf PDF
W50S8N20B0001 IFB Add_Alter B643.pdf PDF
Attachment 5 - HAAW162100 Vol 2.pdf PDF
Attachment 4 - HAAW162100 Vol 1.pdf PDF
Attachment 2 - HAAW179035 Vol 1.pdf PDF
Attachment 6 - HAAW179035 Drawings.pdf PDF
Attachment 3 - HAAW179035 Vol 2.pdf PDF
Attachment 1 - SOW HAAW179035_162100 25 Mar 2020.docx DOCX document
Show all 32

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

DN

A B C E F H J K L M N P

AABBCCDDEE

FA02

F

FA01

ACTIVE ICD 705

PERIMETER

PHASE 0

L O

C

A C

U

B A

T T

N A

C

F A

C

F A

C U

B A

T T

N A

C

F A

A

L O

C

AIR CREW

SCHEDULING

MECH RM #1

LOCKER ROOM

MISSION

PLANNING

SIMULATOR

174A

OFFICE

174B

OFFICE

174C

COMM CLOSET

CORR

SSO

COMM RM #

MISSION

PLANNING

COMM MX

MEN'S

MAN TRAP

SHIFT BREAK

DINING

137 MEAL KITCHEN

FITNESS

COMM RM #3

STAN EVAL OGV

OG CHIE

OG / CD

CORRIDO

FLT / CCs

MAIL/COPY ROOM

ELEC RM #2

117B GENERAL

STORAGE

CONFERENCE

COMM ROOM

AS / CHIEF

CLOSET

SOC

TRAINING CBT

CENTER

AIR CREW

TRAINING /

RECORDS OFFICE

121 CORRIDOR

JAN. CLOSET

SHARM OFFICE

COMM ROOM

117A

TRAINING ADO

CHEIF OF STAN

EVAL

AIR CREW

TESTING

CLOSET

148A-3

GENERAL

STORAGE

177D

JAN. CLOSET

WOMEN'S VEST.

WOMEN'S

ELEC RM #1-3

146-3

FIXED GCS

BRIEFING #1

ISSO-2

148-2

INTEL WEAPONS

TACTICS

CLOSET

168A

SERVER ROOM

COMM. WORK

AREA

CLOSET

155A

GCS MX

E.O.C

JAN. CLOSET

CLOSET-3

149A-3

CONTRACTOR

SUPPORT

OSS ADMIN

WORK AREA

RECEPTION

CORRIDOR

CORRIDOR

MEN'S VEST.

LOCKER ROOM

MEN'S ROOM

WOMEN'S ROOM

ENTRANCE #2

100B

CORRIDOR

177C

CORRIDOR

177B

CORR

COMMAND POST

AS / DO

AS / CC

OG / CC-2

CORRIDOR

177A

LIBRARY

DEBREIFING

BRIEFING

MAN TRAP-3

147-3

BRIEFING

SCIF CORRIDOR

MAIN CORRIDOR

AS / ADMIN

PUB. STORAGE

ELEC ROOM

CONFERENCE

ACTIVE

ICD 705 PERIMETER

PHASES 1 & 2

ACTIVE ICD 705

PERIMETER

PHASE 0

Space

149WWWW

Space

149BBBBB

date detailed checkeddesigned ofsheet sheets project contract rev.drawing file

no. date descriptionby ckd

1 1312111098765432

I

H

G

F

E

D

C

B

A

CONSTRUCT REAPER OPERATIONS

CENTER BUILDING 643

HAAW179035

174 ATTACK WING

HANCOCK FIELD AIR NATIONAL GUARD BASE

SYRACUSE, NEW YORK

10 N PARK PLACE, SUITE 330

MORRISTOWN, NEW JERSEY 07960

973-884-8701

BMCD LICENSE NO 000165

103179

D

/2

/2

:0

:0

P

M

103182_F_CENTRAL

R-FD011

FIRE ALARM & MASS NOTIFICATION

DEMOLITION PLAN

04/09/19

A. CARABILLO C. QUINN

K. DISPOTO

SCALE IN FEET

0 8' 16' 24'

NOTES:

1. REFER TO R-FA001 FOR GENERAL NOTES, DESIGN CRITERIA,

ABBREVIATIONS AND SYMBOLS.

2. REFER TO R-AG004 FOR PHASING PLANS.

3. REFER TO BASE INWS PROJECT (MNS UPGRADE) FOR ALL MNS

NOTIFICATION APPLIANCES AND EQUIPMENT IN THE BUILDING.

CONTRACTOR SHALL COORDINATE ALL WORK WITH THE INWS

PROJECT.

4. ALL EXISTING DEVICES SHALL REMAIN, UON.

KEYED NOTES:

DISCONNECT AND REMOVE EXISTING PULL STATION AND

HORN/STROBE, WIRING, CONDUIT, SUPPORTS, ETC BACK TO NAC AND

SLC CIRCUITS.

DISCONNECT AND REMOVE EXISTING HORN/STROBE AND WIRING

BACK TO NAC AND SLC CIRCUITS. BACKBOX AND CONDUIT SHALL

REMAIN. FILL BACKBOX WITH ACOUSTICAL PUTTY AND SOUND

ATTENUATION BATT TO MEET REQUIRED STC RATING.

NORTH

FA01

FA02

FA0#

FIRE ALARM & MASS

NOTIFICATION DEMOLITION PLAN

A 05/20/19 AAC AAC TYPE B-2 SUBMITTAL

B 07/26/19 AAC AAC TYPE B-2 SUBMITTAL TO NGB

C 12/09/19 AAC AAC TYPE B-3 SUBMITTAL

D 02/20/20 ACC AAC ADDENDUM 001

D

A B C E F H J K L M N P

AABBCCDDEE

11.4

9.4

6.2

3.7

BB.5DD.7

FF

FA

C

FA

C

U

BA

TT

N

AC

FA

A

N

AC

F

F

FA03

FA02

WP

WP

WP

WP

LO

C

LO

C

FA04

FA01

FA05

FA07

AOM S

RTSS

DX-1R

AOM S

RTSS

DX-1

AOM

RTS

AOM

RTS

CRAC-1 CRAC-1R

AOM S

RTSS

RTU-1R

AOM S

RTSS

RTU-1

AC

U

BA

TT

N

AC

ACTIVE

ICD 705 PERIMETER

PHASES 1 & 2

AIR CREW

SCHEDULING

MECH RM #1

LOCKER ROOM

MISSION

PLANNING

SIMULATOR

174A

OFFICE

174B

OFFICE

174C

COMM CLOSET

CORR

SSO

COMM RM #

MISSION

PLANNING

COMM MX

MEN'S

MAN TRAP

SHIFT BREAK

DINING

137 MEAL KITCHEN

FITNESS

COMM RM #3

STAN EVAL OGV

OG CHIE

OG / CD

CORRIDO

FLT / CCs

MAIL/COPY ROOM

ELEC RM #2

117B GENERAL

STORAGE

CONFERENCE

COMM ROOM

AS / CHIEF

CLOSET

SOC

AIR CREW

TRAINING /

RECORDS OFFICE

CORRIDOR

JAN. CLOSET

SHARM OFFICE

COMM ROOM

117A

TRAINING ADO

CHEIF OF STAN

EVAL

AIR CREW

TESTING

CLOSET

148A-3

GENERAL

STORAGE

177D

JAN. CLOSET

WOMEN'S VEST.

143WOMEN'S

ELEC RM #1-3

146-3

FIXED GCS

BRIEFING #1

ISSO-2

148-2

INTEL WEAPONS

TACTICS

CLOSET

168A

SERVER ROOM

COMM. WORK

AREA

CLOSET

155A

GCS MX

E.O.C

JAN. CLOSET

CLOSET-3

149A-3

CONTRACTOR

SUPPORT

OSS ADMIN

WORK AREA

RECEPTION

CORRIDOR

CORRIDOR

MEN'S VEST.

LOCKER ROOM

MEN'S ROOM

WOMEN'S ROOM

ENTRANCE #2

100B

CORRIDOR

177C

CORRIDOR

177B

CORR

COMMAND POST

AS / DO

AS / CC

OG / CC-2

FIXED GCS

CORRIDOR

177A

LIBRARY

DEBREIFING

BRIEFING

MAN TRAP-3

147-3

BRIEFING

SCIF CORRIDOR

PASSAGE

MAINTENANCE

182 RESTROOM

MAIN CORRIDOR

AS / ADMIN

PUB. STORAGE

ELEC ROOM

REAPER

OPERATIONS

CENTER

CONFERENCE

SERVER ROOM

FA05 FA04

ACU

AC

U

FA08 FA09

FA09

S P

AS

D

AOM

AOM

FA10

FA06

PROVIDE CEILING MOUNTED COMBINATION SPEAKERS/

AMBER STROBES AND WALL MOUNTED CLEAR FIRE HORN/

STROBES AS REQUIRED TO ACHIEVE DESIGN CRITERIA.

EXISTING BUILDING - INITIATION AND NOTIFICATION

APPLIANCES ARE EXISTING TO REMAIN, UON.

FIRE ALARM / MASS NOTIFICATION HATCH LEGEND

NO HATCH

PROVIDE CEILING MOUNTED COMBINATION SPEAKER/AMBER

STROBES AND WALL MOUNTED CLEAR FIRE STROBES AS

REQUIRED TO ACHIEVE DESIGN CRITERIA. PROVIDE SMOKE

ASPIRATION SYSTEM WITHIN RAISED FLOOR AND ROOM

CAVITY SPACES IN ACCORDANCE WITH NFPA 72.

PROVIDE CEILING MOUNTED COMBINATION

SPEAKERS/AMBER STROBES AND WALL MOUNTED CLEAR

FIRE STROBES AS REQUIRED TO ACHIEVE DESIGN CRITERIA.

PROVIDE SMOKE DETECTION WITHIN RAISED FLOOR

ACCORDANCE WITH NFPA 72.

date detailed checkeddesigned ofsheet sheets project contract rev.drawing file

no. date descriptionby ckd

1 1312111098765432

I

H

G

F

E

D

C

B

A

CONSTRUCT REAPER OPERATIONS

CENTER BUILDING 643

HAAW179035

174 ATTACK WING

HANCOCK FIELD AIR NATIONAL GUARD BASE

SYRACUSE, NEW YORK

10 N PARK PLACE, SUITE 330

MORRISTOWN, NEW JERSEY 07960

973-884-8701

BMCD LICENSE NO 000165

103179

F

2/

/2

1:

:5

103182_F_CENTRAL

R-FA101

FIRE ALARM & MASS NOTIFICATION PLAN

11/26/18

A. CARABILLO C. QUINN

D. GIGLIO

FIRE ALARM & MASS

NOTIFICATION PLAN

SCALE IN FEET

0 8' 16' 24'

NOTES:

1. REFER TO FA001 FOR GENERAL NOTES, DESIGN CRITERIA,

ABBREVIATIONS AND SYMBOLS.

2. REFER TO R-AG004 FOR PHASING PLANS.

3. COORDINATE EXACT LOCATION OF ALL MECHANICAL EQUIPMENT,

FURNITURE AND MISCELLANEOUS EQUIPMENT PRIOR TO ROUGH-IN.

4. PROVIDE EXPANSION JOINT FITTINGS WHERE REQUIRED. REFER TO

ARCHITECTURAL DRAWINGS FOR LOCATIONS.

5. HUNG CEILINGS SHALL BE REMOVED AS REQUIRED TO PERMIT

INSTALLATION OF NEW EQUIPMENT FOR ALL TRADES. DISCONNECT,

REMOVE, REINSTALL AND RECONNECT ALL EXISTING LIGHTING, LOW

VOLTAGE DEVICES, WIRING, AND CONDUIT AFFECTED BY THIS REMOVAL

TO RESTORE CEILING TO EXISTING CONDITIONS. PROVIDE TEMPORARY

LIGHTING, CIRCUITING, ETC. TO MAINTAIN EXISTING LIGHTING LEVELS AND

ALL EQUIPMENT FUNCTIONALITY THROUGHOUT CONSTRUCTION.

6. THE INWS PROJECT (MNS UPGRADE) HAS BEEN COMPLETED IN THIS

BUILDING. CONTRACTOR SHALL COORDINATE ALL NEW WORK UNDER

THIS CONTRACT WITH THE EXISTING INWS PROJECT.

7. ALL NEW INWS/MNS DEVICES SHALL MATCH EXISTING IN TYPE AND KIND.

8. ALL NEW DEVICES AND ASSOCIATED CONDUIT MOUNTED ON EXTERIOR

ICD 705 WALLS SHALL BE SURFACE MOUNTED.

KEYED NOTES:

PROVIDE AIR SAMPLING DETECTION PORTS THROUGHOUT THE AREA

SPACED IN ACCORDANCE WITH NFPS 72. PROVIDE SEPARATE ZONES

FOR THE ROOM, BELOW THE FLOOR , ABOVE THE CEILING, AND FOR

THE INTAKE AND DISCHARGE OF EACH COMPUTER ROOM AIR HANDLER.

EACH IF THE SAMPLING BRANCH LINES SHALL TERMINATE AT A

COMMON LOCATION AT APPROXIMATELY 5 FT AFF WITH A TEST PORT.

PROVIDE (3) ASD PANELS AND POWER BOOSTERS, ONE FOR EACH

ZONE. SYSTEM SHALL BE PROVIDED FOR THE RAISED FLOOR, ROOM

CAVITY, ABOVE CEILING SPACES. ALL PIPING SHALL BE COORDINATED

WITH OTHER SYSTEMS IN THE ROOM. PANELS SHALL BE LOCATED IN

THE ROOM CAVITY.

PROVIDE RED STROBE LIGHT TO NOTIFY OCCUPANTS OF AN

ASPIRATING SMOKE DETECTOR ALARM. PLACARD AND LOCATION

SHALL BE INSTALLED BELOW STROBE AND COORDINATED WITH THE

BASE. TYPICAL OF 4.

PROVIDE SPEAKERS WITHIN THE ICD 705 PERIMETER SECURE SPACE

(NEW CONSTRUCTION AND RENOVATION). FOR ANY NEW CONDUITS,

UTILIZE EXISTING COMMON PERIMETER WALL PENETRATIONS. REFER

TO WALL PENETRATION DETAIL ON DRAWING R-FA501 FOR ANY NEW

CONDUIT PENETRATION.

PROVIDE SLC WIRING IN 1-2"C. (GFGI) TO UPS SHELTER FOR

MONITORING OF UPS SHELTER FIRE ALARM SIGNALS. REFER TO DETAIL

ON DRAWING R-E-501. COORDINATE WORK WITH GFGI EQUIPMENT. SEE

DRAWING R-ES101 FOR CONTINUATION.

ALL NEW DEVICES INSTALLED ALONG THE LENGTH OF THE ICD 705

WALL (BOTH SIDES) MUST BE SURFACE MOUNTED.

EXISTING MNS/INWS CONTROL SUB-ACU PANEL (FOC TO COPPER

MEDIA CONVERTER).

NORTH

FA01

FA02

FA03

FA04

FA05

FA06

FA07

FA08

FA09

FA10

FA0#

PROVIDE NEW MNS/INWS SUB-ACU WITH

LOC PANEL TO SERVE THE PHASE 2

REAPER ADDITION CONSTRUCTION AREA.

PROVIDE 1-3" FIRE RATED CONDUIT

SLEEVES AT LOCATIONS OF WALL

PENETRATIONS, AND SEAL THE SLEEVES

DURING PHASE I OF CONSTRUCTION.

INSTALLATION OF WIRING SHALL OCCUR

DURING PHASE II OF CONSTRUCTION.

FOR SEF-1 AND ASSOCIATED DAMPERS.

A 01/03/19 AAC AAC MOCA

B 01/18/19 AAC AAC TYPE B-1 SUBMITTAL

C 05/20/19 AAC AAC TYPE B-2 SUBMITTAL

D 07/26/19 AAC AAC TYPE B-2 SUBMITTAL TO NGB

E 12/09/19 AAC AAC TYPE B-3 SUBMITTAL

F 02/20/20 ACC AAC ADDENDUM 001

F

F

Sheets
R-FD011 - FIRE ALARM & MASS NOTIFICATION DEMOLITION PLAN
R-FA101 - FIRE ALARM & MASS NOTIFICATION PLAN

File details come from the government source that posted it. Updated .