RFIs- Backflow Preventors - 10Sep26.xlsx

XLSX spreadsheet 18 KB Posted

Attached to
Backflow Preventer Upgrades
Solicitation number
W50S7X-26-Q-0010
Issued by

About this file

This is a Request for Information (RFI) document providing government responses to contractor questions regarding backflow preventer replacement work at McConnell Air Force Base, Kansas, under Solicitation W50S7X-26-Q-0010.

The RFI addresses five key inquiries from potential contractors. Question 1 provides manufacturer, model, and serial number details for five backflow preventer devices scheduled for replacement across Buildings 33, 44, 48, and 65, including a 6" Maxim 200 DC in Building 33, a 1" Watts 909 RPZ in Building 44 Room 118, a 4" Colt 200 DC in Building 44 Room 122, a 4" Colt 200 DC in Building 48, and a 2-1/2" Wilkins 350 DC in Building 65. Question 2 clarifies that contractors must unwire and rewire alarm tamper switches on existing backflow valves when needed, requiring 24-hour advance notice. Question 3 identifies the devices at Buildings 5 and 56 as Watts 1-1/2" and 1" 009M2 QT RP models respectively, with serial numbers 140892 and 277591. Question 4 confirms that the August 12 site visit materials satisfy the requirement to inspect site conditions, though contractors are welcome to conduct additional inspections of Buildings 5 and 56, and site pictures have been provided. Question 5 clarifies that the government accepts properly sized, code-compliant like-for-like or equivalent replacement backflow preventers meeting all SOW requirements, without specifying particular manufacturers or models.

View the file

Other files

Show all 15

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Sheet1

QuestionResponse
1The scope identifies the following:
•Buildings 33 and 44, Room 122: Double Check Valve (DCV)
•Building 44, Room 118, boiler makeup: Presumed Reduced Pressure Zone (RP) assemblyPlease provide the manufacturer, model, and serial number for each device scheduled for replacement, including the devices located in Buildings 48 and 65.BLDG 33 South Bay, Fire Suppression

6” Maxim 200 DC JC-0416

BLDG 44 Room 118 (East Mech Room), Boiler Makeup 1” Watts 909 RPZ 548898

BLDG 44 Room 122 (South Mech Room), Fire Suppression 4” Colt 200 DC EC-0652

BLDG 48 Fire Riser Room, Fire Suppression 4” Colt 200 DC EL-0865

BLDG 65 South Mech Room, Domestic Main 2-1/2” Wilkins 350 DC J22384

2At the walk through some backflows valves have alarm tamper switches. Is it the intenet of the governement to unwire them and wire the new ones once completed.We will unwire and rewire these switches when needed. We do ask for a 24 hour notice for each occasion.
3Please confirm whether the 1.5-inch backflow preventer at Building 5 is an RPZ or double-check valve. Could you also provide photos of the existing backflows at Buildings 5 and 56?Building 5: Watts 1-1/2” 009M2 QT RP 140892

Building 56: Watts 1” 009M2 QT RP 277591

4SW 9 of the revised SOW requires the contractor to acknowledge that it has inspected and is fully cognizant of the site conditions. Since the August 12 site-visit materials do not appear to reflect Buildings 5 and 56, please confirm whether the prior organized site visit satisfies this requirement for the revised scope or whether a supplemental inspection/access opportunity is required or available.The contractor is welcome to make a return visit to examine Buildings 5 and 56 but we are not requiring it as pics of these two devices are included in the posting
5confirm whether a properly sized, code-compliant like-for-like/equivalent replacement meeting the revised SOW requirements is acceptable for each location.We are not calling out a specific model or manufacturer. Please meet all requirements specified in the SOW